This document includes a federal solicitation notice and related project details for concrete repair work. The Department of Veterans Affairs intends to solicit proposals for a firm-fixed-price contract to expand an existing patient parking garage at the Cleveland VA Medical Center. The project scope involves completing the fourth deck of the garage to add 132 parking spaces, along with extending vertical transportation and stairs. Additional work includes improving lighting and matching the facade on the existing structure. The solicitation will be set aside for Service-Disabled Veteran-Owned Small Businesses and issued as an Invitation for Bid in accordance with FAR procedures. The estimated value is between $2-5 million. Bids are due in October 2019, and the period of performance is approximately 280 days.

36E77619B0020 0003 S-301_-_CONCRETE_REPAIR_DETAILS.pdf

View the file

Other files

File Type Posted
36E77619B0020-0007003.pdf PDF
36E77619B0020-0007004.pdf PDF
36E77619B0020-0007002.pdf PDF
36E77619B0020-0007000.docx DOCX document
36E77619B0020-0007001.pdf PDF
36E77619B0020-0007005.pdf PDF
36E77619B0020-0006004.pdf PDF
36E77619B0020-0006001.pdf PDF
36E77619B0020-0006003.pdf PDF
36E77619B0020-0006000.docx DOCX document
36E77619B0020-0006002.pdf PDF
36E77619B0020-0005000.docx DOCX document
36E77619B0020-0005002.pdf PDF
36E77619B0020-0005001.pdf PDF
36E77619B0020-0004000.docx DOCX document
36E77619B0020-0004001.pdf PDF
36E77619B0020-0004002.pdf PDF
36E77619B0020-0003002.pdf PDF
36E77619B0020-0003016.pdf PDF
36E77619B0020-0003022.pdf PDF
36E77619B0020-0003011.pdf PDF
36E77619B0020-0003004.pdf PDF
36E77619B0020-0003018.pdf PDF
36E77619B0020-0003003.pdf PDF
36E77619B0020-0003006.pdf PDF
36E77619B0020-0003017.pdf PDF
36E77619B0020-0003023.pdf PDF
36E77619B0020-0003014.pdf PDF
36E77619B0020-0003020.pdf PDF
36E77619B0020-0003009.pdf PDF
36E77619B0020-0003021.pdf PDF
36E77619B0020-0003013.pdf PDF
36E77619B0020-0003019.pdf PDF
36E77619B0020-0003025.pdf PDF
36E77619B0020-0003007.pdf PDF
36E77619B0020-0003012.pdf PDF
36E77619B0020-0003026.pdf PDF
36E77619B0020-0003010.pdf PDF
36E77619B0020-0003000.docx DOCX document
36E77619B0020-0003001.pdf PDF
36E77619B0020-0003005.pdf PDF
36E77619B0020-0003008.pdf PDF
36E77619B0020-0003015.pdf PDF
36E77619B0020-0002002.pdf PDF
36E77619B0020-0002001.pdf PDF
36E77619B0020-0002000.docx DOCX document
36E77619B0020-0001001.pdf PDF
36E77619B0020-0001000.docx DOCX document
36E77619B0020-0001000.docx DOCX document
36E77619B0020-0001001.pdf PDF
Show 40 more

Latest 50 of 66 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SURFACE CRACK

(OTHER THAN HAIRLINE CRACK)

TOOLED CONCRETE CUT

ROUT OUT AND FILL GROOVE WITH SIKADUR 52 (OR

APPROVED EQUAL) IN ACCORDANCE WITH

MANUFACTURER'S INSTALLATION SPECIFICATIONS

ALL CEILING AND WALL CRACKS 1/16" OR WIDER SHALL

BE ROUTED OUT AND FILLED WITH SIKADUR 52 (OR

APPROVED EQUAL) IN ACCORDANCE WITH

MANUFACTURER'S INSTALLATION SPECIFICATIONS

3/8"

/2

FOR BIDDING PURPOSES: ASSUME

(5) LOCATIONS ~ 2 LF EACH

APPLY SCRUB COAT

CORR-BOND

REPAIR DAMAGED AREAS

WITH SIKATOP 111 PLUS (OR

APPROVED EQUAL)

SPALLING CONCRETE REPAIR PROCEDURES:

1. CREATE AN ENLARGED CAVITY BY PROVIDING A SAW CUT EDGE 1/4" TO 1/2" IN DEPTH, LOCATED A MINIMUM OF 2" IN SOUND CONCRETE

BEYOND THE PERIMETER OF THE CAVITY. DO NOT DAMAGE REINFORCING STEEL. ALL SAWCUTS SHALL BE RECTANGULAR IN SHAPE.

2. DEPTH OF SOUND SUBSTRATE 3/4" BEYOND CORRODED REINFORCING STEEL OR GREATER THAN THE LARGEST AGGREGATE COVERED.

CONCRETE REMOVAL SHALL EXTEND ALONG LENGTH OF REINFORCING STEEL TO LOCATIONS FREE OF CORROSION.

3. SCARIFY AND CLEAN THE CAVITY WITH POTABLE WATER. REMOVE ANY BOND INHIBITIVE MATERIALS.

4. REINFORCING STEEL TO BE MECHANICALLY CLEANED (FREE OF ALL RUST) AND COATED WITH SIKA ARMATEC 110 EPOCEM (OR APPROVED

EQUAL) IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.

5. DRILL AND SET 1/4" S.S. THREADED RODS @ MAX 6" INTERVALS WITH 2" MINIMUM EMBEDMENT WHERE DEPTH OF SPALL EXCEEDS 1 1/2" IN

VERTICAL AND UNDERSIDE REPAIRS. APPLY MODIFIED REPAIR LOW SHRINK MORTAR AS RECOMMENDED BY THE MANUFACTURER.

1/4" MIN SAW CUT EDGE, NO

FEATHER EDGES PERMITTED

RETAIN OR RECONSTRUCT

DRIP EDGE AFTER WORK IS

COMPLETE

FOR BIDDING PURPOSES: ASSUME

(15) LOCATIONS ~ 1 SF EACH

EXPOSED REINFORCING STEEL TO BE MECHANICALLY CLEANED AND COATED

WITH SIKA ARMATEC 110 EPOCEM (OR APPROVED EQUAL) IN ACCORDANCE

WITH MANUFACTURER'S INSTRUCTIONS. INSPECT REBARS AND REPAIR AS

PER TYPICAL REBAR REPAIRS DETAIL

REPAIR ALL SPALLED AREAS WITH SIKATOP 111 PLUS (OR

APPROVED EQUAL)

1/4" MIN SAW CUT EDGE. NO

FEATHERED EDGES PERMITTED

SPALL REPAIR PROCEDURES:

1. CREATE AN ENLARGED CAVITY BY PROVIDING A SAW CUT EDGE 1/4" TO 1/2" IN DEPTH, LOCATED A MINIMUM OF 2" IN SOUND CONCRETE

BEYOND THE PERIMETER OF THE CAVITY. DO NOT DAMAGE REINFORCING STEEL. ALL SAWCUTS SHALL BE RECTILINEAR IN SHAPE.

2. DEPTH OF SOUND SUBSTRATE 3/4" BEYOND CORRODED REINFORCING STEEL OR GREATER THAN THE LARGEST AGGREGATE COVERED.

CONCRETE REMOVAL SHALL EXTEND ALONG LENGTH OF REINFORCING STEEL TO LOCATIONS FREE OF CORROSION.

3. SCARIFY AND CLEAN THE CAVITY WITH POTABLE WATER. REMOVE ANY BOND INHIBITIVE MATERIALS.

4. REINFORCING STEEL TO BE MECHANICALLY CLEANED (FREE OF ALL RUST) AND COATED WITH SIKA ARMATEC 110 EPOCEM (OR APPROVED

EQUAL) IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.

5. DRILL AND SET 1/4" S.S. THREADED RODS @ MAX 6" INTERVALS WHERE DEPTH OF SPALL EXCEEDS 1 1/2" IN VERTICAL AND UNDERSIDE

REPAIRS. APPLY MODIFIED REPAIR LOW SHRINK MORTAR AS RECOMMENDED BY THE MANUFACTURER.

TO BE USED IF CONCRETE IS DAMAGED DURING REMOVAL

OF WALL IN FUTURE DRIVE AISLES. FOR BIDDING PURPOSES:

ASSUME (3) LOCATIONS

FOR CRACKS 3/16" WIDE OR LESS: WHILE

CRACK IS WET, INJECT CRACK WITH JAHN

M30 #31 GROUT PER MANUFACTURER'S

SPECIFICATIONS.

3/16"

3/16" - 9/16" FOR CRACKS BETWEEN 3/16" AND

9/16" WIDE: WHILE CRACK IS WET,

INJECT CRACK WITH JAHN M40

GROUT (OR APPROVED EQUAL) PER

MANUFACTURER'S SPECIFICATIONS.

MAX DEPTH = 1 1/2", NOT TO EXCEED 25% OF

OVERALL DEPTH OF CASE ELEMENT

FOR BIDDING PURPOSES: ASSUME

(15) LOCATIONS ~ 2 LF EACH1

WHEN REPAIRING HORIZONTAL SURFACES USING REPAIR MORTAR, APPLY MATERIAL FLUSH TO THE SURFACE AND FINISH TO A TIGHT STEEL TROWELED

FINISH, FLOAT, OR BROOM TO ACHIEVE A TEXTURED EFFECT. WHEN REPAIRING VERTICAL SURFACES, BUILD UP MATERIAL BEYOND THE SURFACE OF THE

SUBSTRATE.

INCORRECT: FEATHERED EDGE

CORRECT SQUARE CUT

NOTE:

1. REMOVE ALL LOOSE MORTAR AND MASONRY PRIOR TO INSTALLATION OF THE REPAIR MORTAR. SOUND MASONRY WITH A HAMMER TO VERIFY ITS INTEGRITY.

IF NECESSARY, CUT AWAY AN ADDITIONAL 1/2" OF THE SUBSTRATE TO ENSURE THE SURFACE TO BE REPAIRED IS SOLID AND STABLE. REMOVE ANY SEALANT

RESIDUE.

2. CUT THE EDGES OF THE REPAIR AREA TO PROVIDE A MINIMUM DEPTH OF 1/2". THE EDGES OF THE REPAIR SHOULD BE SQUARE CUT. DO NOT ALLOW ANY

FEATHERED EDGES IN THE REPAIR AREA. REMOVE ALL DETERIORATED STONE PLUS AN ADDITIONAL 1/4" TO SOUND SUBSTRATE.

3. WASH PREPARED SURFACE WITH CLEAN WATER AND A BRISTLE BRUSH TO REMOVE DUST FROM THE PORES.

4. CUT OUT AND REPLACE ALL REINFORCEMENT WHOSE STRUCTURAL INTEGRITY IS IN QUESTION. STRUCTURALLY SOUND CORRODED REINFORCING STEEL MUST

BE MECHANICALLY ABRADED TO A WHITE METAL FINISH. MECHANICAL MEANS, SUCH AS SANDBLASTING, GRINDING OR WIRE BRUSHING ARE ACCEPTABLE.

COAT EXPOSED STEEL WITH CORONADO SURFACE TOLERANT MASTIC, 113 LINE (CORONADO INDUSTRIAL COATINGS) (OR APPROVED EQUAL). APPLY REPAIR

MORTAR ONLY AFTER COATING IS COMPLETELY DRY.

SURFACE SPALL REPAIR FOR CONCRETE ELEMENTS MAY BE CONSIDERED AS AN ALTERNATIVE TO REPLACEMENT ONLY AS APPROVED BY THE ENGINEER ON A SPECIFIC

CASE BASIS.

EXISTING CAST-IN-PLACE ELEMENT

APPLY A "PEANUT BUTTER" COAT (REPAIR MORTAR MIXED WITH WATER TO THE CONSISTENCY OF WET PUTTY), APPROXIMATELY 1/8" THICK. TO ACHIEVE PROPER

BOND, THE "PEANUT BUTTER" COAT MUST NOT DRY OUT PRIOR TO APPLICATION OF MORTAR.

NOTES:

1. MOISTEN THE SUBSTRATE USING CLEAN WATER. REPAIR MORTAR SHOULD BE APPLIED TO A GLISTENING WET SURFACE ON VERTICAL APPLICATIONS AND TO A

DAMPENED SURFACE ON HORIZONTAL APPLICATIONS (WITH NO POOLING WATER).

2. REPAIR MORTAR MAY BE PLACED IN DEEP APPLICATIONS USING SUCCESSIVE LIFTS. IF A CEMENT SKIN FORMS BETWEEN APPLICATIONS (THE SURFACE WILL APPEAR

GLOSSY), SCRAPE AWAY ENOUGH OF THE SURFACE TO REMOVE THE SKIN (ABOUT 1/16" OF MATERIAL) THIS WILL OPEN THE PORES BEFORE AN ADDITIONAL LAYER

OF MATERIAL IS APPLIED. THE SURFACE SHOULD BE MOISTENED AGAIN BEFORE CONTINUING THE APPLICATION.

3. ALLOW MORTAR 30 TO 60 MINUTES TO SET SLIGHTLY (WAIT TIME WILL VARY WITH TEMPERATURE AND HUMIDITY-LONGER IN COOL WEATHER), AND THEN SCRAPE

OFF EXCESS MATERIAL USING A STRAIGHT EDGE (A PLASTERER'S MITER ROD IS GOOD FOR THIS). DO NOT PRESS DOWN OR "FLOAT" THE REPAIR. WHERE REPAIRS

OCCUR AT PANEL EDGES OR CORNERS, FORM MORTAR TO MATCH THE PROFILE OF THE SURROUNDING MASONRY. IN ALL CASES, FINISH AND TEXTURE REPAIR SO

THAT IT IS AS INDISTINGUISHABLE AS POSSIBLE FROM THE ADJACENT MASONRY.

/2

M

IN

/2

M

IN

*CONTRACTOR SHALL USE THE FOLLOWING MORTARS DEPENDING ON THE MATERIAL OR APPROVED EQUAL

MATERIAL - PRODUCT

PRECAST - JAHN M150 - COLOR MATCHED

LIMESTONE - JAHN M70 - COLOR MATCHED

SANDSTONE - JAHN M70 - COLOR MATCHED

FOR BIDDING PURPOSES:

ASSUME (2) LOCATIONS - 2 SF EA1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

PVE ENGINEERING, LLC.

Waterfront Corporate Park III, Suite 101

2000 Georgetowne Drive, Sewickley, PA 15143

Phone: 724-444-1100

Email: info@pve-llc.com

AE Works, LTD.

209 Sandusky Street

Pittsburgh, PA 15212

Phone: 412-287-7333 www.ae-works.com

S-301

CONCRETE REPAIR DETAILS EXPAND PATIENT PARKING

GARAGE

10701 EAST BOULEVARD, CLEVELAND, OH 44106

161651

05/24/2019 Checker Author

100% BID SET

N.T.S.

CONCRETE CRACK REPAIR (WIDER SURFACE CRACKS)

N.T.S.

SPALLING CONCRETE REPAIR @ SLAB EDGE OR PARAPET WALL

N.T.S.

SPALLING CONCRETE REPAIR (TOPSIDE AND UNDERSIDE) -

N.T.S.

CONCRETE CRACK REPAIR DETAIL (SHALLOW)

# Revisions Date

1 Addendum for Solilcitation 11/22/2019

3" = 1'-0"

SPALLING CAST ELEMENT REPAIR (SHALLOW)

Sheets
S-001 - GENERAL NOTES
S-100 - LEVEL4 FRAMING PLAN
S-101 - LEVEL 4 POST-TENSIONING PLAN
S-300 - CONCRETE DETAILS
S-301 - CONCRETE REPAIR DETAILS
S-302 - POST-TENSIONED DETAILS
S-305 - CONCRETE BEAM SCHEDULE & DETAILS