This file attachment relates to a federal contract solicitation for construction services. The Department of Veterans Affairs Technology Acquisition Center Austin is seeking bids for Project 202-318-REHAB Building Construction at the TOGUS-ME location under Solicitation Number 36C77624B0006. Drawings for the project are provided in the 17MB PDF file. Construction services required include rehabilitation of an existing building. The bid response deadline is not specified in the attachment but the solicitation is for firm-fixed-price bids. No other details on offer terms, pricing, schedules, or incumbent are included in this file attachment.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DN

4 4

A

A

B

B

C

C

D

D E

E 0.50.5

A.5

A.5

STAIR 2

S2-1

124 SF

STAFF BREAK

A-109

190 SF

STAFF TLT

A-110

64 SF

OFFICE 3

A-111

81 SF

OFFICE 1

A-112

83 SF

OFFICE 2

A-113

104 SF

MULTIPURPOSE

A-108

210 SF

MULTIPURPOSE

A-107

212 SF

EXAM RM

A-106

117 SF UDS TLT

A-105

72 SF

REC ROOM & KITCHEN

A-103

857 SF

PUBLIC TLT

A-104

65 SF

ELEVATOR

A-001

89 SF

CORRIDOR

A-131

416 SF

SHARED LAUNDRY

A-114

185 SF

MEN'S LOUNGE

A-115

331 SF

WOMEN'S LOUNGE

A-116

224 SF

FAMILY VISITATION

A-117

236 SF

TELECOM ROOM

A-119

93 SF

HAC

A-118

70 SF

FIRE RISER ROOM

A-120

74 SF

VESTIBULE

A-100

148 SF

WAITING

A-101

663 SF

RECEPTION

A-102

103 SF

STAIR 1

S1-1

187 SF

CLOSET

A-101A

31 SF

CORRIDOR

A-132

114 SF

CORRIDOR

A-130

180 SF

CORRIDOR

A-133

502 SF

CORRIDOR

A-134

76 SF

DEDUCT ALT 1: ELIMINATE CONNECTING CORRIDOR.

EXTERIOR PATHWAY ONLY.

REMOVE FIRE SPRINKLERS FROM THIS AREA IF THIS

DEDUCT IS SELECTED.

CLOSET

A-130B

15 SF

ELEC CLOSET

A-130A

20 SF

UTILITY CHASE

A-425

41 SF

DEDUCT ALT 2: ELIMINATE

THREE SEPARATE MEN'S

LOUNGE, WOMEN'S LOUNGE &

FAMILY VISITATION ROOMS AND

COMBINE INTO SINGLE SPACE.

THIS AREA BECOMES

STORAGE - ORDINARY HAZARD

GROUP 2.

A

B C D E 0.50.5

A.5

A.5

STAIR 2

S2-2

149 SF

LOGISTICS SUPPLY

A-210

126 SF

UNIT 7

A-209

120 SF

UNIT 8

A-207

135 SF

UNIT 9

A-206

116 SF

UNIT 10

A-204

124 SF

UNIT 11

A-203

124 SF

BARIATRIC UNIT 12

A-202

180 SF

SHARED BATH

A-205

89 SF

SHARED BATH

A-208

89 SF

PRIVATE BATH

A-211

88 SF

MED ROOM

A-227

115 SF

NURSE STATION

A-226

163 SF

STAFF TLT

A-225

54 SF

HAC

A-224

87 SF

ELEVATOR

A-002

89 SF

LINEN & SUPPLY STOR.

A-201

121 SF

BARIATRIC BATH

A-202A

91 SF

SECURE CORRIDOR

A-220

95 SF

UNIT 1

A-222

173 SF

SOILED UTILITY

A-419

98 SF

UNIT 2

A-221

144 SF

SHARED BATH

A-223

101 SF

TELECOM ROOM

A-219

93 SF

STAIR 1

S2-1

189 SF

SHARED BATH

A-214

102 SF

SHARED BATH

A-217

101 SF

UNIT 3

A-216

159 SF

UNIT 4

A-215

139 SF

UNIT 5

A-213

140 SF

UNIT 6

A-212

167 SF

CORRIDOR

A-252

322 SF

CORRIDOR

A-250

620 SF

CORRIDOR

A-251

603 SF

UTILITY ACCESS

A-421

77 SF

UTILITY CHASE

A-422

33 SF

A

B C D E 0.50.5

A.5

A.5

STAIR

2S-3

170 SF

MECHANICAL PENTHOUSE

A-300

1914 SF

ELEC ROOM

A-301

128 SF

EMERGENCY POWER

A-302

128 SF

FIRE PROTECTION SPRINKLER SYSTEM DESIGN CRITERIA

SPACE TYPE

HAZARD

CLASSIFICATION

DISCHARGE

DENSITY

MAXIMUM

COVERAGE

AREA PER

SPRINKLER

MAXIMUM

SPACING

SPRINKLER TYPE NOTES

GPM/FT² FT² FT.

GENERAL,

EXCEPT AS

LISTED BELOW

LIGHT HAZARD 0.10 225 15

SEMI-RECESSED

PENDENT, QUICK

RESPONSE, UL LISTED,

FM APPROVED

KITCHEN /

STORAGE, LINEN

ORDINARY

HAZARD

GROUP 2

0.20 130 15

SEMI-RECESSED

PENDENT OR UPRIGHT,

QUICK RESPONSE,

UL LISTED, FM APPROVED

EQUIPMENT

ROOM

ORDINARY

HAZARD

GROUP 1

0.15 130 15

QUICK RESPONSE

UPRIGHT, UL LISTED, FM

APPROVED

NOTES:

1. WATER DEMAND REQUIREMENTS ARE FOR HYDRAULIC CALCULATION METHOD. IF OTHER METHOD IS USED ADJUST

VALUES ACCORDING TO NFPA 13 REQUIREMENTS.

2. PROVIDE INTERMEDIATE TEMPERATURE SPRINKLER HEAD ONLY WITHIN ELEVATOR PIT IN ACCORDANCE WITH VA FIRE

PROTECTION DESIGN MANUAL.

HAZARD

SYMBOL

ELEVATOR

SHAFT

ORDINARY

HAZARD

GROUP 1

0.15 130 15

QUICK RESPONSE

UPRIGHT, UL LISTED, FM

APPROVED

1, 2

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

N

AREA B

KEY PLAN

AREA A

WORK AREA

EXISTING BUILDING

EXISTING BUILDING

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

TRIPLE C - The A/E Group 100 Pearl Street, 14th floor Hartfort, CT 06103

(315) 484-5958 Mat Perkins

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

MES GROUP

550 North Reo St, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephensen, P.E.

STRUCTURAL

C&S Companies 2575 E Camelback Rd, Suite 740 Phoenix, AZ 85016

(602) 997-7536 Bryan K. Salt, P.E. S.E.

B

IM

/4

-3

C o n s tr u c t S u b s ta n c e U s e

R e s id e n ti a l R e h a b

B u ild in g /4

-3

.A u g u s ta

.M E

P F

.R

.r v t

/2

/2

:4

:3

P

M

FX201

FIRE PROTECTION HAZARD CLASSIFICATION

PLANS

402-318

BLDG 258

07/26/2022 DCM/CB TH/DCM

100% CONSTRUCTION

DOCUMENTS ISSUED FOR

BIDDING

Construct Substance Use Residential Rehab Building

1 VA Center, Augusta, Maine

1/8" = 1'-0"

FIRE SPRINKLER ZONE PLAN - FIRST FLOOR

1/8" = 1'-0"

FIRE SPRINKLER ZONE PLAN - SECOND FLOOR

1/8" = 1'-0"

FIRE SPRINKLER ZONE PLAN - PENTHOUSE

DEDUCTIVE ALTERNATE LIST:

DEDUCT ALTERNATE 1: ELIMINATE CONNECTING

CORRIDOR. EXTERIOR PATHWAY ONLY.

DEDUCTIVE ALTERNATE 2: ELIMINATE THREE

SEPARATE MEN'S LOUNGE, WOMEN'S LOUNGE &

FAMILY VISITATION ROOMS AND COMBINE INTO

SINGLE SPACE.

Revisions: Date:

07/26/2022

GENERAL NOTES

1. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND INDICATIVE OF WORK TO BE PROVIDED (FURNISHED AND INSTALLED)

UNDER THIS CONTRACT. DRAWINGS SHOULD NOT BE SCALED.

2. THE CONTRACTOR IS RESPONSIBLE TO EXAMINE THE EXISTING CONDITIONS UNDER WHICH THEY SHALL OPERATE AND VERIFY

THE EXTENT OF WORK REQUIRED TO COMPLETE THE WORK UNDER THIS CONTRACT.

3. PRIOR TO ORDERING AND FABRICATING ANY EQUIPMENT, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO EXAMINE THE PHYSICAL CONDITIONS AT THE PROJECT SITE AND VERIFY SPACE AND SUFFICIENT CLEARANCES ARE AVAILABLE FOR INSTALLING EQUIPMENT, DUCTWORK, PIPING, AND APPURTENANCES, AND TO DETERMINE ANY NECESSARY MODIFICATIONS.

4. PERFORM ALL WORK IN COMPLIANCE WITH ALL APPLICABLE FEDERAL, STATE, AND LOCAL CODES, REGULATIONS, AND STANDARDS ADOPTED BY THE AUTHORITY HAVING JURISDICTION. IF CONFLICTS EXIST BETWEEN THESE ENGINEERING

DOCUMENTS AND CODES, THE MOST STRINGENT REQUIREMENTS SHALL GOVERN.

5. ALL CONSTRUCTION WORK SHALL ALSO MEET THE FOLLOWING CODE REQUIREMENTS:

• VA DESIGN MANUALS

• INTERNATIONAL BUILDING CODE (IBC) 2021

• INTERNATIONAL EXISTING BUILDING CODE 2021

• IBC MECHANICAL 2021

• IBC PLUMBING 2021

• IBC ENERGY CONSERVATION 2021

• ASHRAE 90.1-2013, ENERGY STANDARD FOR BUILDING EXCEPT LOW-RISE RESIDENTIAL BUILDINGS

• NFPA 1-2021, THE UNIFORM FIRE CODE

• NFPA 101-2021, THE LIFE SAFETY CODE

• NFPA 51B-2019, STANDARD FOR FIRE PREVENTION DURING WELDING, CUTTING AND OTHER HOT WORK

• NFPA 13-2019, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS

• NFPA 70-2020, NATIONAL ELECTRICAL CODE

• NFPA 90A-2021, STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTING SYSTEMS.

• NFPA 99-2021, STANDARD FOR HEALTH CARE FACILITIES

• NFPA 241-2019, STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION AND DEMOLITION OPERATIONS.

6. CONTRACTOR SHALL COORDINATE AND SEQUENCE DEMOLITION, CLEANING, AND CONSTRUCTION WORK.

7. CONTRACTOR SHALL NOTE ANY SPECIAL REQUIREMENTS FOR INSTALLATION OF WORK UNDER THIS CONTRACT. DISMANTLE AND REASSEMBLE EQUIPMENT AS NECESSARY FOR ENTRY INTO THE BUILDING AND THE LOCATION OF INSTALLATION.

8. THE CONTRACTOR SHALL MAINTAIN A COMPLETE PROJECT SCHEDULE AND SHALL UPDATE THIS SCHEDULE WEEKLY. ANY

CHANGES SHALL BE NOTED AND AN UPDATED SCHEDULE SHALL BE PROVIDED TO THE OWNER.

9. ALL PERMITS, FEES, TAXES, ETC SHALL BE PAID BY CONTRACTOR AS PART OF THE TOTAL PROJECT COST.

10. MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE RATED WALLS, PARTITIONS, CEILINGS, AND FLOORS. SEAL ALL PENETRATIONS THROUGH RATED ASSEMBLIES WITH FIRESTOP MATERIAL IN ACCORDANCE WITH U.L. REQUIREMENTS TO

MAINTAIN THE ASSEMBLY RATING.

11. CONTRACTOR SHALL FURNISH U.L. APPROVED DRAWINGS FOR EACH TYPE OF FIRE AND SMOKE RATED ASSEMBLY PENETRATION BY DUCTS, PIPES, OR CONDUITS, AND SHALL DISPLAY THESE DRAWINGS ON THE JOB SITE AT ALL TIMES

DURING CONSTRUCTION.

12. CONTRACTOR SHALL REFER TO ALL DETAILS FOR PROPER GUIDANCE.

13. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND EQUIPMENT SUBMITTALS FOR ALL PRODUCTS USED ON PROJECT.

14. THE ENGINEER'S APPROVAL OF SUBMITTAL DATA SHALL NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR DEVIATIONS FROM THE REQUIREMENTS OF CONTRACT DOCUMENTS UNLESS THE CONTRACTOR HAS RECEIVED WRITTEN APPROVAL FROM THE ENGINEER TO THE SPECIFIC DEVIATION. THE ENGINEER'S APPROVAL OF SUBMITTAL DATA SHALL NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR ERRORS OR OMISSIONS IN HIS OR HER SUBMITTAL DATA.

15. THE CONTRACTOR IS REQUIRED TO SUBMIT THREE COMPLETE O&M MANUALS IN THREE RING BINDERS AT SUBSTANTIAL COMPLETION. MANUALS SHALL INCLUDE INSTALLATION AND MAINTENANCE DATA ON ALL NEW EQUIPMENT AND MATERIALS, CERTIFIED TECHNICAL PRODUCT DATA, EQUIPMENT SHOP DRAWINGS, SPARE PARTS DATA, ETC. PROVIDE AN INDEX AND

ASSOCIATED DIVIDERS.

16. CLOSE OUT DOCUMENTS: THE CONTRACTOR IS TO MAINTAIN ONE SET OF CONSTRUCTION DRAWINGS ON SITE AND KEEP CURRENT WITH MARK UP AS-BUILT CONDITIONS DURING CONSTRUCTION OF THE PROJECT. THIS SET IS TO INCLUDE ALL CONTRACT CHANGES, MODIFICATIONS AND CLARIFICATIONS. THIS SET ALONG WITH ALL SHOP DRAWINGS SHALL BE TURNED OVER TO THE ARCHITECT/ENGINEER AFTER CONSTRUCTION COMPLETION. REFER TO SPECIFICATION SECTIONS 01 00 00 FOR

WARRANTY REQUIREMENTS AND 01 33 23 FOR SUBMITTAL REQUIREMENTS.

17. IT IS THE RESPONSIBILITY OF ALL BIDDERS TO THOROUGHLY REVIEW AND UNDERSTAND ALL CONSTRUCTION DOCUMENTS.

THIS INCLUDES BUT IS NOT LIMITED TO ALL DRAWINGS, SPECIFICATION SECTIONS, ETC. THE DRAWINGS ARE SCHEMATIC IN NATURE. THEREFORE BEFORE STARTING ANY WORK, THE CONTRACTOR SHALL REVIEW ALL OTHER CONSTRUCTION DOCUMENTS, VERIFY FIELD CONDITIONS AND SHALL MAKE ANY REQUIRED MINOR ADJUSTMENTS WITHOUT EXTRA COST TO THE OWNER. ANY MAJOR DISCREPANCIES FOUND SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER.

THE BASE BID SHALL REFLECT THE TOTAL COST OF NEW EQUIPMENT INSTALLATION. THIS INCLUDES LABOR, EQUIPMENT AND MATERIALS. NO CHANGE ORDERS SHALL BE ISSUED WITHOUT WRITTEN CONSENT AND APPROVAL FROM ENGINEER AND

ARCHITECT.

DRAWING KEYNOTE#

EQUIPMENT MARK

POINT OF NEW CONNECTION

LIMIT OF DEMOLITION

POINT OF CONNECTION TO CIVIL

PIPE RISER TAG

CW COLD WATER PIPING

HW HOT WATER PIPING

HWR HOT WATER RETURN PIPING

SAN SANITARY PIPING

V SANITARY VENT PIPING

PIPE UP

PIPE DOWN

GCO GRADE CLEAN OUT (1-WAY OR 2-WAY)OR

HOSE BIB WITH VACUUM BREAKER

OR VTR VENT THRU ROOF

WCO WALL CLEAN OUT

FCO FLOOR CLEAN OUT (1-WAY OR 2-WAY)OR

INVERT ELEVATIONIE

PIPE CAP

WCO

FLOOR DRAIN

BALL VALVE

BUTTERFLY VALVE

CHECK VALVE

GATE VALVE

PLUG VALVE

STRAINER

UNION

PRESSURE RELIEF VALVEPRV

BACKFLOW PREVENTER

FLOOR SINK

PLUMBING LEGEND

FD-C

FD-S

X-XX

CR COLD WATER RETURN PIPING

PLUMBING NOTES

1. REVIEW PLANS OF ALL TRADES PRIOR TO BIDDING AND BEGINNING WORK. INSTALLATIONS ARE TO INCLUDE ALL PLUMBING

FOR COMPLETE SYSTEMS SHOWN ON THE PLANS AND AS REQUIRED.

2. COORDINATE WITH OTHER TRADES TO PREVENT INTERFERENCE WITH HVAC DUCTS, STRUCTURE, ELECTRICAL, LIGHTING, AND OTHER PIPING IN THE CEILING SPACE. VENT PIPING AND WATER PIPING SHALL BE HELD EITHER ABOVE OR BELOW HVAC

DUCTWORK, AS COORDINATED WITH THE HVAC CONTRACTOR.

3. ALL CHANGES SHALL BE REVIEWED BY THE ARCHITECT.

4. COORDINATE WITH ARCHITECTURAL DRAWINGS BEFORE ROUGHING-IN PLUMBING FIXTURES AND EQUIPMENT SUPPLIES.

5. THE PLUMBING SUBCONTRACTOR SHALL FURNISH AND INSTALL ALL PLUMBING FIXTURES, UNLESS NOTED OTHERWISE.

6. VERIFY MOUNTING HEIGHT AND WATER CONNECTION SIZES OF ALL PLUMBING FIXTURES PRIOR TO ROUGH-IN. FURNISH CUT- OUT TEMPLATES, FOR PLUMBING FIXTURES TO BE INSTALLED IN MILLWORK, TO THE GENERAL CONTRACTOR.

7. MAKE PROPER HOT AND COLD WATER, WASTE AND VENT PIPING CONNECTIONS TO ALL FIXTURES AND EQUIPMENT EVEN

THOUGH ALL FITTINGS AND CONNECTIONS ARE NOT SHOWN ON DRAWINGS.

8. VERIFY LOCATION OF WATER SERVICE AND THE LOCATION/INVERTS OF SANITARY PIPING PRIOR TO INSTALLATION.

9. CUT AND PATCH CONCRETE AS REQUIRED.

10. IT IS NOT THE INTENT OF THESE DRAWINGS TO COVER ALL WORK AND MATERIAL. ANY EQUIPMENT, PLUMBING FIXTURE, TRIM HARDWARE AND/OR DEVICES USUALLY UTILIZED IN THE CLASS OF WORK, THOUGH NOT SPECIFICALLY MENTIONED OR SHOWN ON THESE DRAWINGS, BUT WHICH MAY BE NECESSARY FOR THE SATISFACTORY COMPLETION OF THE WORK (AS DETERMINED BY THE ARCHITECT) SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR AS PART OF HIS TOTAL WORK.

11. THE EQUIPMENT ROUGH-IN ITEMS AND THEIR DIMENSIONED LOCATIONS FOR ALL CONNECTIONS ARE ACCURATE TO THE BEST OF OUR KNOWLEDGE. IN SOME INSTANCES THE OWNER OR SUPPLIER MAY MAKE SUBSTITUTIONS OR EQUIPMENT ITEMS MAY VARY FROM WHAT IS SHOWN. THEREFORE, THESE ITEMS AND DIMENSIONS SHALL BE VERIFIED WITH THE EQUIPMENT SUPPLIER, OWNER AND/OR EQUIPMENT ROUGH-IN DRAWING. FAILURE OF THE APPROPRIATE CONTRACTOR TO VERIFY ROUGH-INS OR THEIR LOCATIONS SHALL PLACE THE RESPONSIBILITY FOR ANY SUBSEQUENT RELOCATION AND/OR

ADDITIONAL ROUGH-INS DIRECTLY UPON THAT CONTRACTOR.

12. CONTRACTOR SHALL SUPPLY TO THE ARCHITECT/ENGINEER THE REQUIRED COPIES OF SHOP DRAWINGS FOR APPROVAL SO THE QUALITY OF INTENDED MATERIALS OR EQUIPMENT CAN BE REVIEWED BEFORE INSTALLATION. THERE WILL BE NO INSTALLATION UNTIL SHOP DRAWINGS HAVE BEEN SUBMITTED AND REVIEWED BY THE ARCHITECT/ENGINEER.

13. DO NOT SCALE THIS DRAWING. REFER TO ARCHITECTURAL FLOOR PLAN FOR BUILDING DIMENSIONS.

14. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT NECESSARILY SHOW ALL ELBOWS, OFFSETS, UNIONS, VALVES, FITTINGS, ETC. REQUIRED TO COMPLETE THE INSTALLATION OF THE WORK. THE SUBMISSION OF A PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT THE CONTRACTOR HAS FAMILIARIZED HIMSELF WITH THE PLANS AND BUILDING SITE. CLAIMS MADE SUBSEQUENT TO THE PROPOSAL FOR MATERIALS AND LABOR BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE

RECOGNIZED IF THEY COULD HAVE BEEN FORESEEN HAD PROPER EXAMINATION BEEN MADE.

15. VERIFY SERVICE POINTS AND METERING LOCATIONS FOR PROJECTS WITH VA (DOMESTIC WATER, SANITARY SEWER, GAS, ETC.).

16. THE CONTRACTOR SHALL COOPERATE FULLY AMONG ALL TRADES.

17. ALL ROOF PENETRATIONS FOR ROOF DRAINS AND PLUMBING, GAS, AND REFRIGERANT PIPING SHALL BE MADE IN ACCORDANCE WITH ROOF SYSTEM MANUFACTURER'S GUIDELINES. COORDINATE WITH ARCHITECTURAL DETAILS AND/OR

MANUFACTURER FOR ROOF SYSTEM USED.

18. ALL PLUMBING VENTS IN EXTERIOR WALLS SHALL BE OFFSET A MINIMUM OF 3'-0" BEFORE ROOF PENETRATION.

19. INSTALL 1" INSULATION WITH ALL-SERVICE JACKET ON ALL ROOF LEADERS ABOVE CEILING.

20. THE WATER PIPING SYSTEM SHALL BE FLUSHED AND STERILIZED IN ACCORDANCE WITH LOCAL REGULATIONS.

21. HOT AND COLD WATER SUPPLY BRANCHES FOR ALL SYSTEMS HAVING QUICK CLOSING VALVES OF ANY TYPE SHALL HAVE WATER HAMMER ARRESTORS INSTALLED AT THE HIGH POINT ON THE END OF EACH BRANCH AND AS REQUIRED. SUPPLY

ACCESS DOORS IF SPACE IS NOT ACCESSIBLE.

22. ALL PIPES HANGING FROM SINGLE VERTICAL RODS / HANGERS SHALL NOT MOVE OR SWAY DURING OPERATION. SUITABLE

LATERAL SUPPORTS OR BRACING SHALL BE USED TO PREVENT SWAY OR MOVEMENT.

23. PROVIDE SHUTOFF BALL VALVES AND DIELECTRIC UNIONS FOR ALL EQUIPMENT HOT AND COLD WATER LINES. PLUMBING CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS TO EQUIPMENT. COORDINATE WITH EQUIPMENT SUPPLIER FOR EXACT

REQUIREMENTS.

24. VERIFY MOUNTING HEIGHTS OF ALL BARRIER FREE FIXTURES WITH ARCHITECTURAL PLANS.

25. PROVIDE COPPER INDIRECT WASTE PIPING REQUIRED FROM EQUIPMENT TO FLOOR DRAINS, OPEN RECEPTACLES, OR FLOOR SINKS. PIPING SHALL COMPLY WITH STATE AND LOCAL CODES. COORDINATE WITH ALL EQUIPMENT SUPPLIERS AND SIZES AS REQUIRED BY PIECE OF EQUIPMENT SERVED. HOLD PIPING TIGHT TO WALL WHERE APPLICABLE. PROPERLY SECURE AS REQUIRED. COORDINATE WITH CASEWORK SUPPLIER FOR MAXIMUM CLEARANCE UNDER CABINETS.

26. PROVIDE CHROME PLATED ESCUTCHEONS AT ALL WALL PENETRATIONS.

27. INSTALL STORM AND CONDENSATE PIPING WITH A MINIMUM SLOPE OF 1/8" PER FOOT. INSTALL SANITARY PIPING AS FOLLOWS:

LESS THAN 3" PIPING SHALL BE SLOPED AT 1/4" PER FOOT, 3 TO 6" PIPING SHALL BE SLOPED AT 1/8" PER FOOT, 8" AND LARGER SHALL BE SLOPED AT 1/16" PER FOOT. CONTRACTOR IS RESPONSIBLE FOR PROPER DRAINAGE OF ALL SYSTEMS.

28. ALL FLOOR DRAINS ARE TO BE PROVIDED WITH MINIMUM 3" DRAIN LINES, DEEP SEAL TRAPS, AND AUTOMATIC TRAP PRIMERS.

TRAP PRIMERS SHALL BE LOCATED IN A SERVICEABLE LOCATION AND INSTALLED PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. HOLD TOP OF FLOOR DRAINS FLUSH WITH FINISHED FLOOR; SEE ARCHITECTURAL SHEETS FOR FLOOR

SLOPES AND PROPER FINISHED FLOOR ELEVATION.

29. ALL VENT PIPE TO BE COMPATIBLE WITH STRUCTURE, MECHANICAL EQUIPMENT, DUCTWORK, ELECTRICAL EQUIPMENT, AND LIGHTING. ALL VTR'S SHALL BE EXTENDED TO A MINIMUM OF 2" ABOVE PARAPET HEIGHT AND MAINTAINED 10'-0" MINIMUM

FROM ALL OUTSIDE AIR INTAKES.

30. MATERIALS, EQUIPMENT, ASSEMBLIES AND SYSTEMS SHALL MEET ALL PERTINENT REQUIREMENTS OF NATIONALLY RECOGNIZED TESTING ORGANIZATIONS SUCH AS UL, ASTM, ASSE, AWWE, AGA AND NFPA AS WELL AS THE MOST CURRENT

ADOPTED VERSION OF THE STATE AND LOCAL CODES.

31. ALL INSTALLED SYSTEMS, DEVICES AND RELATED ITEMS SHALL BE TESTED IN PLACE. REPLACE ANY AND ALL CONTRACTOR SUPPLIED DEFECTIVE DEVICES, ITEMS, OR SYSTEMS AT CONTRACTOR'S EXPENSE, BEFORE COMPLETION OF PROJECT.

32. WHERE JOB CONDITIONS REQUIRE CHANGES FROM THE CONTRACT DOCUMENTS THAT DO NOT CHANGE THE SCOPE OR NATURE OF WORK REQUIRED, THE CONTRACTOR SHALL MAKE SUCH CHANGES WITHOUT ADDITIONAL COST TO THE OWNER.

NO OTHER CHANGES MAY BE MADE WITHOUT WRITTEN PERMISSION FROM THE ENGINEER.

33. ALL EQUIPMENT, FIXTURES AND MATERIALS SHALL BE NEW AND UNUSED, AND INSTALLED IN STRICT CONFORMANCE TO MANUFACTURER'S RECOMMENDATIONS (UNLESS OTHERWISE NOTED). PROVIDE COMPLETE WITH ALL TRIM, STOPS, HANGERS, CARRIERS, SUPPORTS, ETC., INCLUDING PROVISIONS FOR BARRIER FREE USE, IF REQUIRED. WHERE FIXTURES ARE

ACCESSIBLE THEY MUST COMPLY WITH ALL FEDERAL ADA REGULATIONS.

34. CONTRACTOR SHALL GUARANTEE ALL WORK FOR WHICH MATERIALS ARE FURNISHED, FABRICATED, FIELD ERECTED, ALL FACTORY ASSEMBLED EQUIPMENT FOR WHICH NO SPECIFIC MANUFACTURER'S GUARANTEE IS FURNISHED, AND ALL WORK IN CONNECTION WITH INSTALLATION OF MANUFACTURER'S GUARANTEED EQUIPMENT. THE CONTRACTOR'S GUARANTEE SHALL LAST ONE YEAR FROM THE FINAL OWNER ACCEPTANCE OF THE WORK AND SHALL APPLY TO ALL DEFECTS IN MATERIALS AND

WORKMANSHIP OF ANY KIND.

35. ALL FAUCET CONTROLS SHALL BE OPERABLE WITH ONE HAND AND NOT REQUIRE TIGHTGRASPING.

36. ALL BARRIER FREE WATER CLOSET CONTROLS SHALL BE LOCATED ON UNIT AWAY FROM CLOSEST WALL. VERIFY IF RIGHT OR

LEFT SIDE LOCATION.

(E) EXISTING

AFF ABOVE FINISHED FLOOR

BFF BELOW FINISHED FLOOR

CO PIPE CLEAN OUT

CP CIRCULATOR PUMP

CTE CONNECT TO EXISTING

CR COLD WATER RETURN

CW COLD WATER

DEMO DEMOLISH OR DEMOLITION

DFU DRAINAGE FIXTURE UNITS

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST EXISTING

FCO FLOOR CLEAN OUT

FD FLOOR DRAIN

FS FLOOR SINK

G GAS

GCO GRADE CLEAN OUT

GPM GALLONS PER MINUTE

HB HOSE BIB

HD HUB DRAIN

HW HOT WATER

HWR HOT WATER RETURN

IB ICE MAKER OUTLET BOX

IBC INTERNATIONAL BUILDING CODE

IE INVERT ELEVATION

LAV LAVATORY

LP LIQUEFIED PETROLEUM GAS

MS MOP SINK

NC NORMALLY CLOSED

NG NATURAL GAS

NO NORMALLY OPEN

OD OVERFLOW ROOF DRAIN

OSD OVERFLOW (SECONDARY) STORM WATER DRAIN

PSD PRIMARY STORM WATER DRAIN

RD ROOF DRAIN

S SINK

SAN SANITARY

SH SHOWER

TWH TANKLESS WATER HEATER

VTR VENT THROUGH ROOF

W WASTE

WC WATER CLOSET

WCO WALL CLEAN OUT

WH WALL HYDRANT

WHA WATER HAMMER ARRESTOR

WSFU WATER SUPPLY FIXTURE UNITS

ABBREVIATIONS

PLUMBING ACCESSORIES

FD-S:

FLOOR SINK - REFER TO SPECIFICATION SECTION 22 13 00 FOR MORE INFORMATION. CONNECT TRAP TO FLOOR DRAIN.

TRAP PRIMER - REFER TO SPECIFICATION SECTION 22 13 00 FOR MORE INFORMATION.

FD-C

FLOOR DRAIN - REFER TO SPECIFICATION SECTION 22 13 00 FOR MORE INFORMATION. CONNECT TRAP PRIMER TO FLOOR

DRAIN.

TRAP PRIMER - REFER TO SPECIFICATION SECTION 22 13 00 FOR MORE INFORMATION.

WCO:

WALL CLEANOUT - REFER TO SPECIFICATION SECTION 22 14 00 FOR MORE INFORMATION.

GCO:

GRADE CLEANOUT - REFER TO SPECIFICATION SECTION 22 14 00 FOR MORE INFORMATION.

RD:

ROOF DRAIN - REFER TO SPECIFICATION SECTION 22 14 00 FOR MORE INFORMATION.

OD:

OVERFLOW (SECONDARY) ROOF DRAIN - REFER TO SPECIFICATION SECTION 22 14 00 FOR MORE INFORMATION.

DS:

DOWNSPOUT - REFER TO SPECIFICATION SECTION 22 14 00 FOR MORE INFORMATION.

1-1-GT:

GREASE TRAP - PDI-G101 SIZED FOR 10 GPM. REFER TO SPECIFICATION SECTION 22 13 23 FOR MORE INFORMATION.

1-1-ENC-GT:

ENCLOSURE - IN-FLOOR PIT ENCLOSURE, 30"L x 24"W x 30"D. PROVIDE WITH COMPOSITE LINER, STEEL SECURING RODS FOR INSTALLATION IN CONCRETE SLAB, ADJUSTABLE FRAME AND COVER. PROVIDE WITH BORDERLESS COVER, COORDINATE TILE COVERING THICKNESS WITH ARCHITECT. COVER SHALL BE MECHANICALLY FASTENED WITH VANDAL PROOF HARDWARE.

ENCLOSURE BASIS OF DESIGN IS CRAIGG MANUFACTURING MODEL ADL.

PLUMBING SHEET INDEX

PL001 PLUMBING LEGEND, NOTES, & ABBREVIATIONS

PL101 PLUMBING PLANS - FIRST FLOOR

PL102 PLUMBING PLANS - SECOND FLOOR

PL102.1 PLUMBING PLAN - SECOND FLOOR STORM DRAINAGE

PL103 PLUMBING PLAN - PENTHOUSE

PL104 PLUMBING PLAN - PENTHOUSE ROOF

PL501 PLUMBING DETAILS

PW301 WASTE & VENT RISER DIAGRAMS

PW302 DOMESTIC RISER DIAGRAM

PW303 STORM RISER DIAGRAM

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

TRIPLE C - The A/E Group 100 Pearl Street, 14th floor Hartfort, CT 06103

(315) 484-5958 Mat Perkins

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

MES GROUP

550 North Reo St, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephensen, P.E.

STRUCTURAL

C&S Companies 2575 E Camelback Rd, Suite 740 Phoenix, AZ 85016

(602) 997-7536 Bryan K. Salt, P.E. S.E.

B

IM

/4

-3

C o n s tr u c t S u b s ta n c e U s e

R e s id e n ti a l R e h a b

B u ild in g /4

-3

.A u g u s ta

.M E

P F

.R

.r v t

/2

/2

:4

:0

P

M

PL001

PLUMBING LEGEND, NOTES, & ABBREVIATIONS 402-318

BLDG 258

07/26/2022 DCM/CB TH/DCM

100% CONSTRUCTION

DOCUMENTS ISSUED FOR

BIDDING

Construct Substance Use Residential Rehab Building

1 VA Center, Augusta, Maine

PLUMBING FIXTURE SCHEDULE

FIXTURE

MARK

FIXTURE DESCRIPTION

ROUGH-IN PIPE SIZES FIXTURE UNITS BASIS OF DESIGN

COLD

WATER

SUPPLY

HOT

WATER

SUPPLY

FIXTURE

TRAP

FIXTURE

DRAIN

COLD

WATER

HOT

WATER

DRAINAGE MANUFACTURER MODEL NUMBER

P-103

WATER CLOSET - WALL HUNG -

ADA. AUTO FLUSH VALVE, HARD

WIRED, PROVIDE WITH

TRANSFORMER. REFER TO

SPECIFICATION SECTION 22 40

00 FOR MORE INFORMATION.

1" N/A 4" 4" 10 0 4 ZURN, ZURN, ZURN, SLOAN, SLOAN

Z1201-N_4, Z5615-BWL, Z5950,

ROYAL 111-ESS

HARDWIRED-1.28-YO-TMO-HW,

034515PK EL-154

P-114

WATER CLOSET - WALL HUNG -

ADA REFER TO SPECIFICATION

SECTION 22 40 00 FOR MORE

INFORMATION.

1" N/A 4" 4" 10 0 4 METCRAFT, SLOAN ROYAL 4675, 111-1.6-YO

P-418

LAVATORY - WALL HUNG - ADA,

AUTO FAUCET, HARD WIRED,

PROVIDE WITH TRANSFORMER.

PROVIDE WITH ASSE-1070

THERMOSTATIC MIXING VALVE.

REFER TO SPECIFICATION

SECTION 22 40 00 FOR MORE

INFORMATION.

1/2" 1/2" 1 1/4" 2" 1.5 1.5 2

ZURN, KOHLER, TRUEBRO,

AMERICAN STANDARD, AMERICAN

STANDARD, CHICAGO FAUCETS

Z1231, K-2054, 103 E-Z, NEXTGEN

SELECTRONIC 775B.315, NEXTGEN

SLECTRONIC PK00.HAC,

131-CFMAB

P-502

JANITOR SINK. REFER TO

SPECIFICATION SECTION 22 40

00 FOR MORE INFORMATION.

1/2" 1/2" 3" 3" 2.25 2.25 2 FIAT, CHICAGO FAUCET TSBCR, 540-LD897SWXF204CP

P-505

CLINICAL SINK, FLOOR

MOUNTED, WITH SERVICE

FAUCET REFER TO

SPECIFICATION SECTION 22 40

00 FOR MORE INFORMATION.

1/2" 1/2" 3" 3" 3 3 2

ZURN, KOHLER, CHICAGO FAUCETS,

SLOAN ROYAL, CHICAGO FAUCET

Z1217, CAMERTON K-12867,

814-VBCP, ROYAL 310-6.5,

910-G777-19KCP

P-528

SINGLE COMPARTMENT SINK -

COUNTER. REFER TO

SPECIFICATION SECTION 22 40

00 FOR MORE INFORMATION.

1/2" 1/2" 1 1/2" 2" 1.5 1.5 2

JUST MANUFACTURING COMPANY,

CHICAGO FAUCET, JUST

MANUFACTURING COMPANY,

CHICAGO FAUCETS

SL-ADA-2122-A-GR,

1102-GN8AE3-317AB, J-35,

131-CFMAB

P-604

WATER COOLER. REFER TO

SPECIFICATION SECTION 22 40

00 FOR MORE INFORMATION.

1/2" N/A 1 1/4" 2" 0.25 0 0.5 ELKAY LZWS-LRPBM8K

P-701

SHOWER STALL - ADA. REFER TO

SPECIFICATION SECTION 22 40

00 FOR MORE INFORMATION.

1/2" 1/2" 1 1/4" 2" 3 3 2 CHICAGO FAUCETS, JOSAM SH-PB1-11-044, 46200

P-708

EMERGENCY EYE/FACE WASH -

WALL MOUNTED, PROVIDE WITH

ASSE-1071 THERMOSTATIC

MIXING VALVE. REFER TO

SPECIFICATION SECTION 22 40

00 FOR MORE INFORMATION.

1/2" 1/2" 1 1/2" 2" 1 1 2 GUARDIAN, GUARDIAN G1750, G6024

P-808

WASHING MACHINE OUTLET BOX.

REFER TO SPECIFICATION

SECTION 22 40 00 FOR MORE

INFORMATION.

1/2" 1/2" 1 1/4" 2" 2.25 2.25 3 GUY GRAY 82327

P-812

ICE MAKER OUTLET BOX. REFER

TO SPECIFICATION SECTION 22

40 00 FOR MORE INFORMATION.

1/2" N/A N/A N/A 0.25 0 3 GUY GRAY 88164

CIRCULATOR PUMP SCHEDULE

MARK CAPACITY TOTAL HEAD SHUTOFF HEAD MOTOR POWER

ELECTRICAL DATA BASIS OF DESIGN

NOTES

VOLTAGE PHASE MANUFACTURER

MODEL

NUMBER

1-3-CPC01 4.0 GPM 24 ftH2O 35 ftH2O 0.125 hp 115 V 1 TACO 009-SF5 1

1-3-CPH01 4.0 GPM 24 ftH2O 35 ftH2O 0.125 hp 115 V 1 TACO 009-SF5 1

THERMOSTATIC MIXING STATION SCHEDULE

MARK CAPACITY

ELECTRICAL DATA BASIS OF DESIGN

NOTES

VOLTAGE PHASE MANUFACTURER MODEL NUMBER

1-3-TMV01 60.0 GPM 115 V 1 POWERS / WATTS LFIS150CFSLP+ 1-6

NOTES:

1. PROVIDE ELECTRICAL CONNECTION TO THERMOSTATIC MIXING STATION, CIRCULATOR PUMP SHALL BE CONTROLLED BY

THERMOSTATIC MIXING STATION.

NOTES:

1. PROVIDE AS PRE-PIPED SYSTEM MOUNTED ON UNISTRUT. PROVIDE ALL ADDITIONAL MOUNTING STRUCTURE

REQUIRED.

2. PROVIDE CONTROLS WITH BACNET GATEWAY FOR INTEGRATION WITH FACILITY BUILDING AUTOMATION

SYSTEM.

3. DISCHARGE OF MIXING STATION SHALL BE SET TO 140°F (ADJ.) UNDER NORMAL OPERATION.

4. PROVIDE WITH ABILITY TO OVERRIDE OUTLET TEMPERATURE SETTINGS TO DISCHARGE 180°F FOR THERMAL

ERADICATION.

5. PROVIDE WITH INLET AND OUTLET TEMPERATURE SENSORS THAT CAN REPORT READINGS TO BUILDING

AUTOMATION SYSTEM.

6. WIRE MIXING STATION CONTROLS TO POWER AND CONTROL CIRCULATOR PUMP TO MAINTAIN HOT WATER

DISCHARGE AND HOT WATER RETURN TEMPERATURE DIFFERENTIAL OF ~2°F (ADJ.).

REVERSE OSMOSIS FILTER SCHEDULE

MARK SYSTEM

BASIS OF DESIGN MAXIMUM FLOW

RATE

SYSTEM

CAPACITY (GPD)

PUMP MOTOR

HP

MCA MOCP PHASE VOLTAGE NOTES

MANUFACTURER MODEL NO.

1-3-ROF01 HYDRONIC US WATER AR-4-1000 4.0 GPM 1000.0 1/2 8.2 A 15.0 A 1 120 V 1-2

ELEVATOR SUMP PUMP SCHEDULE

MARK SYSTEM

BASIS OF DESIGN PUMP FLOW

RATE

PUMP HEAD (FT)

PUMP MOTOR

HP

FLA PHASE VOLTAGE NOTES

MANUFACTURER MODEL NO.

1-1-ESP01

ELEVATOR SUMP

PUMP

LIBERTY PUMPS ELV280 50.0 GPM 14.0 1/2 8.5 A 1 120 V 1-5

NOTES:

1. PROVIDE SUMP PUMP SYSTEM WITH OIL DETECTION THAT DE-ENERGIZES PUMP WHEN OIL OR HYDRAULIC FLUID IS DETECTED.

2. PROVIDE WITH FLOAT SWITCH.

3. PROVIDE WITH PUMP CONTROLLER.

4. PROVIDE WITH REMOTE ALARM.

5. PROVIDE SIGNAL FROM PUMP CONTROLLER TO ALERT BUILDING AUTOMATION SYSTEM ON HIGH LEVEL, OIL DETECTION, OR PUMP FAILURE.

NOTES:

1. PROVIDE FULLY PACKAGED, INLINE REVERSE OSMOSIS FILTER SYSTEM.

2. PROVIDE WITH STAINLESS STEEL PUMP.

P-528 P-103

P-418

P-808

P-808

P-418 P-808

P-808

P-528

P-103

P-418

P-103

P-528

STAIR 2

S2-1

STAFF BREAK

A-109

MULTIPURPOSE

A-108

OFFICE 2

A-113

OFFICE 3

A-111

OFFICE 1

A-112

CORRIDOR

A-131

SHARED LAUNDRY

A-114

EXAM RM

A-106

UDS TLT

A-105

MULTIPURPOSE

A-107

STAFF TLT

A-110

REC ROOM & KITCHEN

A-103

RECEPTION

A-102

ELEVATOR

A-001

MEN'S LOUNGE

A-115

WOMEN'S LOUNGE

A-116

FAMILY VISITATION

A-117

STAIR 1

S1-1

TELECOM ROOM

A-119

HAC

A-118

FIRE RISER ROOM

A-120

CLOSET

A-101A

VESTIBULE

A-100

WAITING

A-101

4 4

A

A

B

B

C

C

D

D E

E 0.50.5

A.5

P-418

P-418

P-418

P-812

P-812

1 1/4" CW

1 1/4" HW

1/2" HW-R

1/2" CR

1/2" CR

3/4" CW

1/2" HW

1/2" HW-R

3/4" HW

1/2" CR1/2" HW-R

1 1/2" CW

3/4" HW

1/2" CR 1/2" HW

1 1/2" CW

1" HW

1/2" HW-R 1/2" CR

1 1/2" CW

1/2" HW

3" CW

P-502

1" CW

1" HW

2" CW

1" HW

1 1/2" CW

1 1/2" HW

2" CW

DEDUCT ALT 1: ELIMINATE CONNECTING CORRIDOR.

EXTERIOR PATHWAY ONLY.

NO CHANGE TO DOMESTIC WATER SCOPE OR WORK.

P-604

P-812

P-812

DEDUCT ALT 2: ELIMINATE

THREE SEPARATE MEN'S

LOUNGE, WOMEN'S LOUNGE &

FAMILY VISITATION ROOMS AND

COMBINE INTO SINGLE SPACE.

DOMESTIC WATER PIPING

SHALL BE ROUGHED IN 6"

BEYOND ISOLATION VALVES AT

CORRIDOR WALL.

P-812 P-812

CORRIDOR

A-133

PUBLIC TLT

A-104

4" SS

P-528

P-103

P-418

P-808

P-808 P-418

P-808

P-808

P-528

P-103

P-418

P-103

P-528

STAIR 2

S2-1

STAFF BREAK

A-109

MULTIPURPOSE

A-108

OFFICE 2

A-113

OFFICE 3

A-111

OFFICE 1

A-112

CORRIDOR

A-131

SHARED LAUNDRY

A-114

EXAM RM

A-106

UDS TLT

A-105

MULTIPURPOSE

A-107

STAFF TLT

A-110

REC ROOM & KITCHEN

A-103

RECEPTION

A-102

ELEVATOR

A-001

MEN'S LOUNGE

A-115

WOMEN'S LOUNGE

A-116

FAMILY VISITATION

A-117

STAIR 1

S1-1

TELECOM ROOM

A-119

HAC

A-118

FIRE RISER ROOM

A-120

CLOSET

A-101A

VESTIBULE

A-100

WAITING

A-101

4" SS

4" SS

4" SS

3" SS

4 4

A

A

B

B

C

C

D

D E

E 0.5

A.5

P-418

P-418

P-418

P-502

1-1-ESP01

1 1/2" PD

1 1/2" PD

4" FCO

3" SD

3" OSD

4" SD

2" SD

3" SD 3" OSD5

2" OSD

DEDUCT ALT 1: ELIMINATE CONNECTING CORRIDOR.

EXTERIOR PATHWAY ONLY.

REPLACE FLOOR CLEANOUT WITH GRADE CLEANOUT

IN SIDEWALK.

2" FD-C

P-604

3" OSD

3" SD

4" SS

DEDUCT ALT 2: ELIMINATE THREE

SEPARATE MEN'S LOUNGE, WOMEN'S

LOUNGE & FAMILY VISITATION ROOMS

AND COMBINE INTO SINGLE SPACE.

STORMWATER PIPING AND SANITARY

PIPING FROM ABOVE SHALL BE

INSTALLED AS SHOWN ON PLAN AND

SANITARY PIPING SHALL BE ROUGHED

IN TO ACCOMMODATE FUTURE

CONNECTION TO SINK P-528.

FD-S

P-812

P-812

3" FCO

1-1-GT 20

FD-S 21

1-1-ENC-GT 22

2" SS 1 1/2" V

1 1/2" V

PLUMBING SHEET NOTES

A THIS PLAN IS DIAGRAMMATIC IN NATURE AND SHALL NOT BE SCALED TO

DETERMINE THE LOCATION OR DIMENSION OF THE WORK. CONTRACTOR SHALL

VERIFY EXACT LOCATION OF PIPING AND PENETRATIONS.

B CONTRACTOR SHALL BE RESPONSIBLE TO VERIFY THE LOCATION OF EXISTING

BELOW GRADE WASTE PIPING AND REFLECT ANY DEVIATION GREATER THAN 1'-0"

FROM THIS PLAN ON THE AS-BUILT DRAWINGS.

C CUTTING, BORING, SAWCUTTING OR DRILLING THROUGH THE NEW AND EXISTING

STRUCTURAL ELEMENTS TO BE DONE ONLY WHEN DETAILED IN THE DRAWINGS

OR ACCEPTED BY THE APPROVAL THE STRUCTURAL ENGINEER AND VA.

D REPAIR WALL SURFACE AFTER INSTALLATION AND INSPECTION OF EACH

PLUMBING FIXTURE AND PIPING INSTALLED.

E ALL WALL-MOUNTED ACCESS PANELS SHALL BE LOCKABLE TYPE.

F MAINTAIN MINIMUM 10-0" SEPARATION BETWEEN FLUE AND PLUMBING VENT

OUTLETS AND ANY FRESH AIR INTAKE. COORDINATE WITH HVAC CONTRACTOR.

G FLOORS SHALL SLOPE TO DRAINS AT 1% MINIMUM SLOPE. SEE ARCHITECTURAL

PLANS FOR MORE INFORMATION.

H PROVIDE ALL FLOOR DRAINS, FLOOR SINKS, TRENCH DRAINS, ETC. WITH TRAP

GUARD DEVICES (ASSE 1072 COMPLIANT).

I PROVIDE WALL CLEAN OUTS IN ALL VENT RISERS ON BRANCHES LONGER THAN

5'-0" AND ON BRANCHES SERVING SINKS OR URINALS.

J SEE RISER DIAGRAMS FOR PIPE SIZING.

N

AREA B

KEY PLAN

WORK AREA

EXISTING BUILDING

EXISTING BUILDING

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

TRIPLE C - The A/E Group 100 Pearl Street, 14th floor Hartfort, CT 06103

(315) 484-5958 Mat Perkins

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

MES GROUP

550 North Reo St, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephensen, P.E.

STRUCTURAL

C&S Companies 2575 E Camelback Rd, Suite 740 Phoenix, AZ 85016

(602) 997-7536 Bryan K. Salt, P.E. S.E.

B

IM

/4

-3

C o n s tr u c t S u b s ta n c e U s e

R e s id e n ti a l R e h a b

B u ild in g /4

-3

.A u g u s ta

.M E

P F

.R

.r v t

/2

/2

:4

:1

P

M

PL101

PLUMBING PLANS - FIRST FLOOR 402-318

BLDG 258

07/26/2022 DCM/CB TH/DCM

100% CONSTRUCTION

DOCUMENTS ISSUED FOR

BIDDING

Construct Substance Use Residential Rehab Building

1 VA Center, Augusta, Maine

1/8" = 1'-0"

LEVEL 1 PLUMBING PLAN - DOMESTIC WATER PIPING

1/8" = 1'-0"

LEVEL 1 PLUMBING PLAN - SANITARY & VENT PIPING

KEYNOTES

1 3" DOMESTIC COLD WATER PIPING. REFER TO CIVIL FOR CONTINUATION.

2 CW, HW, CWR, AND HWR, DOWN FROM SECOND FLOOR.

3 3" DOMESTIC COLD WATER PIPING UP TO PENTHOUSE ON THIRD LEVEL. REFER TO

PL103 FOR CONTINUATION.

4 PRIMARY STORM DRAINAGE. REFER TO CIVIL FOR CONTINUATION.

5 OVERFLOW STORM DRAINAGE. TERMINATE 18" ABOVE GRADE WITH DOWNSPOUT.

6 SANITARY PIPING DOWN FROM SECOND FLOOR.

7 4" SANITARY PIPING TO GRADE CLEANOUT AT AN INVERT ELEVATION OF 165.17'.

REFER TO CIVIL UTILITY PLANS FOR CONTINUATION.

8 PUMPED DRAIN FROM ELEVATOR SUMP PUMP 1-1-ESP01. TERMINATE PIPE 18"

ABOVE GRADE.

9 PUMPED DRAIN FROM ELEVATOR SUMP PUMP UP TO ABOVE FIRST FLOOR

CEILING.

10 MECHANICAL CONDENSATE PIPING. ROUTE PIPING TO FLOOR DRAIN LOCATED IN

FIRE RISER ROOM.

11 PROVIDE CAP ON END OF SANITARY PIPING. CONTRACTOR SHALL LEAVE A

MINIMAL LENGTH DEAD-HEAD TO ALLOW FOR CONNECTION OF FUTURE BUILDING

EXPANSION.

12 IF DEDUCTIVE ALTERNATE #1 IS SELECTED, NOTED FLOOR CLEANOUT SHALL BE

REPLACED WITH A GRADE CLEANOUT.

13 PROVIDE FIXTURES IN UDS TOILET ROOM WITH CONTROLS AS SHOWN IN UDS

TOILET FIXTURE CONTROL DETAIL ON SHEET PL501, FIXTURES SHALL HAVE THE

ABILITY TO BE TURNED ON/OFF WITH A REMOTE LOCATED SWITCH. LOCATE

SWITCH IN EXAM ROOM A-106.

14 2.5" VENT PIPING UP TO SECOND FLOOR.

15 OVERFLOW STORM DRAINAGE DOWN FROM SECOND FLOOR. PIPING LOCATED IN

FIRST FLOOR CEILING.

16 PRIMARY STORM DRAINAGE DOWN FROM SECOND FLOOR. PIPING LOCATED IN

FIRST FLOOR CEILING.

17 ICE BOX HOOKUP LOCATED BEHIND LOWER CABINET.

18 STORM DRAINAGE PIPING DOWN FROM SECOND FLOOR. PIPE TO RUN IN FIRST

FLOOR CEILING BELOW BEAM AND INTO CHASE.

19 PROVIDE FUR OUT FOR STORM PIPING. TYP.

20 ROUTE SANITARY WASTE PIPING FROM KITCHEN SINK TO IN-FLOOR GREASE TRAP

AND ROUTE DISCHARGE FROM GREASE TRAP TO SANITARY PIPING. GREASE TRAP

SHALL BE PROVIDED WITH PDI-G101 REQUIRED FLOW CONTROL VALVE AND SIDE

DISCHARGE KIT.

21 PROVIDE FLOOR SINK WITHIN CASEWORK TO RECEIVE DRAIN FROM COUNTERTOP

MOUNTE ICE MAKER.

22 PROVIDE GREASE TRAP WITHIN IN-FLOOR PIT ENCLOSURE. ALL PENETRATIONS

THROUGH ENCLOSURE WALLS SHALL BE SEALED. PROVIDE FILL WITHIN

ENCLOSURE TO SUPPORT GREASE TRAP ACCORDING TO MANUFACTURERS

RECCOMMENDATIONS.

23 PROVIDE 3" BACKFLOW PREVENTER IN INCOMING WATER SERVICE PIPING.

24 PROVIDE DOMESTIC WATER SUBMETER AS DESCRIBED IN SPECIFICATION

SECTION 25 10 10 ADVANCED UTILITY METERING. SUBMETER SHALL BE

INTEGRADTED WITH BUILDING AUTOMATION SYSTEM.

DEDUCTIVE ALTERNATE LIST:

DEDUCT ALTERNATE 1: ELIMINATE CONNECTING

CORRIDOR. EXTERIOR PATHWAY ONLY.

DEDUCTIVE ALTERNATE 2: ELIMINATE THREE

SEPARATE MEN'S LOUNGE, WOMEN'S LOUNGE &

FAMILY VISITATION ROOMS AND COMBINE INTO

SINGLE SPACE.

Revisions: Date:

DRAWING KEYNOTE#

EQUIPMENT MARK

CW COLD WATER PIPING

HW HOT WATER PIPING

HWR HOT WATER RETURN PIPING

SAN SANITARY PIPING

V SANITARY VENT PIPING

PIPE UP

PIPE DOWN

GCO GRADE CLEAN OUT (1-WAY OR 2-WAY)OR

HOSE BIB WITH VACUUM BREAKER

OR VTR VENT THRU ROOF

WCO WALL CLEAN OUT

FCO FLOOR CLEAN OUT (1-WAY OR 2-WAY)OR

PIPE CAP

WCO

FLOOR DRAIN

BALL VALVE

BACKFLOW PREVENTER

FLOOR SINK

PLUMBING LEGEND

FD-C

FD-S

X-XX

CR COLD WATER RETURN PIPING

FIXTURE SCHEDULE

FIXTURE MARK FIXTURE DESCRIPTION

P-103

WATER CLOSET - WALL HUNG - ADA. AUTO FLUSH VALVE,

HARD WIRED, PROVIDE WITH TRANSFORMER. REFER TO

SPECIFICATION SECTION 22 40 00 FOR MORE

INFORMATION.

P-114

WATER CLOSET - WALL HUNG - ADA REFER TO

SPECIFICATION SECTION 22 40 00 FOR MORE

INFORMATION.

P-418

LAVATORY - WALL HUNG - ADA, AUTO FAUCET, HARD

WIRED, PROVIDE WITH TRANSFORMER. PROVIDE WITH

ASSE-1070 THERMOSTATIC MIXING VALVE. REFER TO

SPECIFICATION SECTION 22 40 00 FOR MORE

INFORMATION.

P-502

JANITOR SINK. REFER TO SPECIFICATION SECTION 22 40 00

FOR MORE INFORMATION.

P-505

CLINICAL SINK, FLOOR MOUNTED, WITH SERVICE FAUCET

REFER TO SPECIFICATION SECTION 22 40 00 FOR MORE

INFORMATION.

P-528

SINGLE COMPARTMENT SINK - COUNTER. REFER TO

SPECIFICATION SECTION 22 40 00 FOR MORE

INFORMATION.

P-604

WATER COOLER. REFER TO SPECIFICATION SECTION 22 40

00 FOR MORE INFORMATION.

P-701

SHOWER STALL - ADA. REFER TO SPECIFICATION SECTION

22 40 00 FOR MORE INFORMATION.

P-708

EMERGENCY EYE/FACE WASH - WALL MOUNTED, PROVIDE

WITH ASSE-1071 THERMOSTATIC MIXING VALVE. REFER TO

SPECIFICATION SECTION 22 40 00 FOR MORE

INFORMATION.

P-808

WASHING MACHINE OUTLET BOX. REFER TO

SPECIFICATION SECTION 22 40 00 FOR MORE

INFORMATION.

P-812

ICE MAKER OUTLET BOX. REFER TO SPECIFICATION

SECTION 22 40 00 FOR MORE INFORMATION.

P-418

P-103

P-418 P-418

P-114

P-418

P-103

P-418

P-103

P-103 P-418

P-103

P-418

P-103

P-418

STAIR 2

S2-2

LOGISTICS SUPPLY

A-210

UNIT 7

A-209

UNIT 8

A-207

UNIT 9

A-206

UNIT 10

A-204

UNIT 11

A-203

BARIATRIC UNIT 12

A-202

BARIATRIC BATH

A-202A

SHARED BATH

A-205

SHARED BATH

A-208

PRIVATE BATH

A-211

MED ROOM

A-227

NURSE STATION

A-226

STAFF TLT

A-225

HAC

A-224

ELEVATOR

A-002

LINEN & SUPPLY STOR.

A-201

UNIT 1

A-222

SECURE CORRIDOR

A-220

UNIT 2

A-221

SOILED UTILITY

A-419

SHARED BATH

A-223

TELECOM ROOM

A-219

STAIR 1

S2-1

CORRIDOR

A-250

UNIT 6

A-212

UNIT 5

A-213

UNIT 4

A-215

UNIT 3

A-216

SHARED BATH

A-217

SHARED BATH

A-214

P-701

P-701

P-701

P-701

P-701P-701

4 4

A

A

B

B

C

C

D

D E

E 0.50.5

A.5

A.5

P-418

P-502

P-418

P-505

P-418

P-701

P-103

1 1/4" HW

2" CW

1/2" HW-R

1/2" CR

1 1/2" HW2 1/2" CW

1/2" HW

1" CW

1/2" CR

1/2" HW-R

1 1/4" HW 2" CW1" HW2" CW

1/2" HW

1/2" CW

1/2" CR

1/2" HW-R

1/2" HW

1/2" CW

3/4" HW

1 1/2" CW

1/2" HW 1 1/2" CW

3/4" HW

1 1/2" CW

1/2" CW

1" CW

1/2" HW

UTILITY ACCESS

A-4212

P-708

1/2" HW-R

1 1/2" HW

2" CW

P-418

P-103

P-418 P-418

P-114

P-418

P-103

P-418

P-103

P-103

P-418

P-103

P-418

P-103

P-418

P-701

P-701

P-701

P-701

P-701P-701

STAIR 2

S2-2

LOGISTICS SUPPLY

A-210

UNIT 7

A-209

UNIT 8

A-207

UNIT 9

A-206

UNIT 10

A-204

UNIT 11

A-203

BARIATRIC UNIT 12

A-202

BARIATRIC BATH

A-202A

SHARED BATH

A-205

SHARED BATH

A-208

PRIVATE BATH

A-211

MED ROOM

A-227 NURSE STATION

A-226

STAFF TLT

A-225

HAC

A-224

ELEVATOR

A-002

CORRIDOR

A-250

LINEN & SUPPLY STOR.

A-201

UNIT 1

A-222

SECURE CORRIDOR

A-220

UNIT 2

A-221

SOILED UTILITY

A-419

SHARED BATH

A-223

TELECOM ROOM

A-219

STAIR 1

S2-1

UNIT 6

A-212

UNIT 5

A-213

UNIT 4

A-215

UNIT 3

A-216

SHARED BATH

A-217

SHARED BATH

A-214

4 4

A

A

B

B

C

C

D

D E

E 0.50.5

A.5

A.5

P-418

P-418

P-502

P-418

P-505

4" SS

P-701

P-103

2" V

4" SS

2" V

2" V

3" SS

4" SS

2" SS

2" SS

1 1/2" V

2" SS

2" SS

2" SS

4" SS

2" SS

3" SS

2" SS

4" SS

2" SS

UTILITY ACCESS

A-421

3" VTR

3" VTR

3" VTR

1 1/2" V1 1/2" V

2" V

2" SS 2" V

P-708

4" SS

4" SS

PLUMBING SHEET NOTES

A THIS PLAN IS DIAGRAMMATIC IN NATURE AND SHALL NOT BE SCALED TO

DETERMINE THE LOCATION OR DIMENSION OF THE WORK. CONTRACTOR SHALL

VERIFY EXACT LOCATION OF PIPING AND PENETRATIONS.

B CONTRACTOR SHALL BE RESPONSIBLE TO VERIFY THE LOCATION OF EXISTING

BELOW GRADE WASTE PIPING AND REFLECT ANY DEVIATION GREATER THAN 1'-0"

FROM THIS PLAN ON THE AS-BUILT DRAWINGS.

C CUTTING, BORING, SAWCUTTING OR DRILLING THROUGH THE NEW AND EXISTING

STRUCTURAL ELEMENTS TO BE DONE ONLY WHEN DETAILED IN THE DRAWINGS

OR ACCEPTED BY THE APPROVAL THE STRUCTURAL ENGINEER AND VA.

D REPAIR WALL SURFACE AFTER INSTALLATION AND INSPECTION OF EACH

PLUMBING FIXTURE AND PIPING INSTALLED.

E ALL WALL-MOUNTED ACCESS PANELS SHALL BE LOCKABLE TYPE.

F MAINTAIN MINIMUM 10-0" SEPARATION BETWEEN FLUE AND PLUMBING VENT

OUTLETS AND ANY FRESH AIR INTAKE. COORDINATE WITH HVAC CONTRACTOR.

G FLOORS SHALL SLOPE TO DRAINS AT 1% MINIMUM SLOPE. SEE ARCHITECTURAL

PLANS FOR MORE INFORMATION.

H PROVIDE ALL FLOOR DRAINS, FLOOR SINKS, TRENCH DRAINS, ETC. WITH TRAP

GUARD DEVICES (ASSE 1072 COMPLIANT).

I PROVIDE WALL CLEAN OUTS IN ALL VENT RISERS ON BRANCHES LONGER THAN

5'-0" AND ON BRANCHES SERVING SINKS OR URINALS.

J SEE RISER DIAGRAMS FOR PIPE SIZING.

N

AREA B

KEY PLAN

WORK AREA

EXISTING BUILDING

EXISTING BUILDING

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

TRIPLE C - The A/E Group 100 Pearl Street, 14th floor Hartfort, CT 06103

(315) 484-5958 Mat Perkins

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

MES GROUP

550 North Reo St, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephensen, P.E.

STRUCTURAL

C&S Companies 2575 E Camelback Rd, Suite 740 Phoenix, AZ 85016

(602) 997-7536 Bryan K. Salt, P.E. S.E.

B

IM

/4

-3

C o n s tr u c t S u b s ta n c e U s e

R e s id e n ti a l R e h a b

B u ild in g /4

-3

.A u g u s ta

.M E

P F

.R

.r v t

/2

/2

:4

:2

P

M

PL102

PLUMBING PLANS - SECOND FLOOR 402-318

BLDG 258

07/26/2022 DCM/CB TH/DCM

100% CONSTRUCTION

DOCUMENTS ISSUED FOR

BIDDING

Construct Substance Use Residential Rehab Building

1 VA Center, Augusta, Maine

1/8" = 1'-0"

LEVEL 2 PLUMBING PLAN - DOMESTIC WATER PIPING

1/8" = 1'-0"

LEVEL 2 PLUMBING PLAN - SANITARY & VENT PIPING

KEYNOTES

1 SANITARY PIPING DOWN TO FIRST FLOOR.

2 3" CW UP TO PENTHOUSE ON THIRD LEVEL FROM FLOOR BELOW.

3 2 1/2" VENT UP FROM FIRST FLOOR.

4 3" SANITARY DOWN FROM FLOOR DRAIN LOCATED IN PENTHOUSE.

5 SANITARY PIPING LOCATED IN CEILING OF SECOND FLOOR. COORDINATE WITH

OTHER TRADES.

6 MECHANICAL CONDENSATE PIPING. ROUTE PIPING DOWN TO FIRST FLOOR AND

CONNECT INTO FIRST FLOOR CONDENSATE PIPING.

7 PROVIDE VENT PIPING UP TO VENT THROUGH ROOF ABOVE.

8 CW, HW, CWR, AND HWR PIPING DOWN TO FIRST FLOOR.

9 CW, HW, CWR, AND HWR PIPING UP TO PENTHOUSE ABOVE.

Revisions: Date:

DRAWING KEYNOTE#

EQUIPMENT MARK

CW COLD WATER PIPING

HW HOT WATER PIPING

HWR HOT WATER RETURN PIPING

SAN SANITARY PIPING

V SANITARY VENT PIPING

PIPE UP

PIPE DOWN

GCO GRADE CLEAN OUT (1-WAY OR 2-WAY)OR

HOSE BIB WITH VACUUM BREAKER

OR VTR VENT THRU ROOF

WCO WALL CLEAN OUT

FCO FLOOR CLEAN OUT (1-WAY OR 2-WAY)OR

PIPE CAP

WCO

FLOOR DRAIN

BALL VALVE

FLOOR SINK

PLUMBING LEGEND

FD-C

FD-S

X-XX

CR COLD WATER RETURN PIPING

BACKFLOW PREVENTER

FIXTURE SCHEDULE

FIXTURE MARK FIXTURE DESCRIPTION

P-103

WATER CLOSET - WALL HUNG - ADA. AUTO FLUSH VALVE,

HARD WIRED, PROVIDE WITH TRANSFORMER. REFER TO

SPECIFICATION SECTION 22 40 00 FOR MORE

INFORMATION.

P-114

WATER CLOSET - WALL HUNG - ADA REFER TO

SPECIFICATION SECTION 22 40 00 FOR MORE

INFORMATION.

P-418

LAVATORY - WALL HUNG - ADA, AUTO FAUCET, HARD

WIRED, PROVIDE WITH TRANSFORMER. PROVIDE WITH

ASSE-1070 THERMOSTATIC MIXING VALVE. REFER TO

SPECIFICATION SECTION 22 40 00 FOR MORE

INFORMATION.

P-502

JANITOR SINK. REFER TO SPECIFICATION SECTION 22 40 00

FOR MORE INFORMATION.

P-505

CLINICAL SINK, FLOOR MOUNTED, WITH SERVICE FAUCET

REFER TO SPECIFICATION SECTION 22 40 00 FOR MORE

INFORMATION.

P-528

SINGLE COMPARTMENT SINK - COUNTER. REFER TO

SPECIFICATION SECTION 22 40 00 FOR MORE

INFORMATION.

P-604

WATER COOLER. REFER TO SPECIFICATION SECTION 22 40

00 FOR MORE INFORMATION.

P-701

SHOWER STALL - ADA. REFER TO SPECIFICATION SECTION

22 40 00 FOR MORE INFORMATION.

P-708

EMERGENCY EYE/FACE WASH - WALL MOUNTED, PROVIDE

WITH ASSE-1071 THERMOSTATIC MIXING VALVE. REFER TO

SPECIFICATION SECTION 22 40 00 FOR MORE

INFORMATION.

P-808

WASHING MACHINE OUTLET BOX. REFER TO

SPECIFICATION SECTION 22 40 00 FOR MORE

INFORMATION.

P-812

ICE MAKER OUTLET BOX. REFER TO SPECIFICATION

4 4

A

A

B

B

C

C

D

D E

E

0.50.5

A.5

STAIR 2

S2-2

LOGISTICS SUPPLY

A-210

UNIT 7

A-209

UNIT 8

A-207

UNIT 9

A-206

UNIT 10

A-204

UNIT 11

A-203 BARIATRIC UNIT 12

A-202

BARIATRIC BATH

A-202A

SHARED BATH

A-205

SHARED BATH

A-208

PRIVATE BATH

A-211

MED ROOM

A-227

NURSE STATION

A-226

STAFF TLT

A-225 HAC

A-224

ELEVATOR

A-002

CORRIDOR

A-250

LINEN & SUPPLY STOR.

A-201

UNIT 1

A-222

SECURE CORRIDOR

A-220

UNIT 2

A-221

SOILED UTILITY

A-419

SHARED BATH

A-223

TELECOM ROOM

A-219

STAIR 1

S2-1

UNIT 6

A-212

UNIT 5

A-213

UNIT 4

A-215

UNIT 3

A-216

SHARED BATH

A-217

SHARED BATH

A-214

2" OSD

2" OSD

2" OSD

2" SD

UTILITY ACCESS

A-421

2 1

2" SD

2" OSD

3" SD

2" SD

3" OSD

2" OSD

2" SD

2" SD

CO

CO

CO

2" SD

N

AREA B

KEY PLAN

WORK AREA

EXISTING BUILDING

EXISTING BUILDING

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

TRIPLE C - The A/E Group 100 Pearl Street, 14th floor Hartfort, CT 06103

(315) 484-5958 Mat Perkins

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

MES GROUP

550 North Reo St, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephensen, P.E.

STRUCTURAL

C&S Companies 2575 E Camelback Rd, Suite 740 Phoenix, AZ 85016

(602) 997-7536 Bryan K. Salt, P.E. S.E.

B

IM

/4

-3

C o n s tr u c t S u b s ta n c e U s e

R e s id e n ti a l R e h a b

B u ild in g /4

-3

.A u g u s ta

.M E

P F

.R

.r v t

/2

/2

:4

:2

P

M

PL102.1

PLUMBING PLAN - SECOND FLOOR STORM

DRAINAGE

402-318

BLDG 258

07/26/2022 DCM/CB TH/DCM

100% CONSTRUCTION

DOCUMENTS ISSUED FOR

BIDDING

Construct Substance Use Residential Rehab Building

1 VA Center, Augusta, Maine

1/4" = 1'-0"

LEVEL 2 PLUMBING PLAN - STORM DRAINAGE

PLUMBING SHEET NOTES

A THIS PLAN IS DIAGRAMMATIC IN NATURE AND SHALL NOT BE SCALED TO

DETERMINE THE LOCATION OR DIMENSION OF THE WORK. CONTRACTOR SHALL

VERIFY EXACT LOCATION OF PIPING AND PENETRATIONS.

B CONTRACTOR SHALL BE RESPONSIBLE TO VERIFY THE LOCATION OF EXISTING

BELOW GRADE WASTE PIPING AND REFLECT ANY DEVIATION GREATER THAN 1'-0"

FROM THIS PLAN ON THE AS-BUILT DRAWINGS.

C CUTTING, BORING, SAWCUTTING OR DRILLING THROUGH THE NEW AND EXISTING

STRUCTURAL ELEMENTS TO BE DONE ONLY WHEN DETAILED IN THE DRAWINGS

OR ACCEPTED BY THE APPROVAL THE STRUCTURAL ENGINEER AND VA.

D REPAIR WALL SURFACE AFTER INSTALLATION AND INSPECTION OF EACH

PLUMBING FIXTURE AND PIPING INSTALLED.

E ALL WALL-MOUNTED ACCESS PANELS SHALL BE LOCKABLE TYPE.

F MAINTAIN MINIMUM 10-0" SEPARATION BETWEEN FLUE AND PLUMBING VENT

OUTLETS AND ANY FRESH AIR INTAKE. COORDINATE WITH HVAC CONTRACTOR.

G FLOORS SHALL SLOPE TO DRAINS AT 1% MINIMUM SLOPE. SEE ARCHITECTURAL

PLANS FOR MORE INFORMATION.

H PROVIDE ALL FLOOR DRAINS, FLOOR SINKS, TRENCH DRAINS, ETC. WITH TRAP

GUARD DEVICES (ASSE 1072 COMPLIANT).

I PROVIDE WALL CLEAN OUTS IN ALL VENT RISERS ON BRANCHES LONGER THAN

5'-0" AND ON BRANCHES SERVING SINKS OR URINALS.

J SEE RISER DIAGRAMS FOR PIPE SIZING.

KEYNOTES

1 PRIMARY AND OVERFLOW STORM DRAINAGE TO OD AND RD ABOVE.

2 ROUTE RAIN LEADERS IN CEILING SPACE. COORDINATE INSTALLATION WITH

OTHER TRADES.

3 PRIMARY STORM DRAINAGE DOWN TO FLOOR BELOW. SEE PL101 FOR

CONTINUATION.

4 OVERFLOW STORM DRAINAGE DOWN TO FLOOR BELOW. SEE PL101 FOR

CONTINUATION.

Revisions: Date:

DRAWING KEYNOTE#

EQUIPMENT MARK

CW COLD WATER PIPING

HW HOT WATER PIPING

HWR HOT WATER RETURN PIPING

SAN SANITARY PIPING

V SANITARY VENT PIPING

PIPE UP

PIPE DOWN

GCO GRADE CLEAN OUT (1-WAY OR 2-WAY)OR

HOSE BIB WITH VACUUM BREAKER

OR VTR VENT THRU ROOF

WCO WALL CLEAN OUT

FCO FLOOR CLEAN OUT (1-WAY OR 2-WAY)OR

PIPE CAP

WCO

FLOOR DRAIN

BALL VALVE

FLOOR SINK

PLUMBING LEGEND

FD-C

FD-S

X-XX

CR COLD WATER RETURN PIPING

BACKFLOW PREVENTER

3" CW DOWN TO FLOOR BELOW

3" CW

4 4

A

A

B

B

C

C

D

D E

E

0.50.5

A.5

STAIR

2S-3

ELEC ROOM

A-301

EMERGENCY POWER

A-302

RD-1

362 SF

OD-1

362 SF OD-1

365 SF

RD-1

365 SF

RD-1

575 SF

OD-1

575 SF

RD-1

570 SF

OD-1

570 SF

OD-1

466 SF

RD-1

466 SF

OD-1

422 SF

RD-1

422 SF

OD-1

510 SF

RD-1

510 SF

3/4" HW-R

3" CW

3" HW

3/4" CR

4" SD

2" SD

2" SD

3" SD

2" SD

2" SD

3 2

2" OSD

3" OSD 3" OSD

2" OSD

2" OSD

1-3-HX01

1-3-HX02

3" VTR

3" VTR

3" VTR

1-3-TMV01

1-3-CPH01

1-3-CPC01

3" FD-1

3" FD-1

1-3-ROF01

1" RO

1" RO

2" FD-C

10 10 10 10

MECHANICAL PENTHOUSE

A-300

2" VTR

1/4" = 1'-0"

ROOF PLUMBING PLAN

PLUMBING SHEET NOTES

A THIS PLAN IS DIAGRAMMATIC IN NATURE AND SHALL NOT BE SCALED TO

DETERMINE THE LOCATION OR DIMENSION OF THE WORK. CONTRACTOR SHALL

VERIFY EXACT LOCATION OF PIPING AND PENETRATIONS.

B CONTRACTOR SHALL BE RESPONSIBLE TO VERIFY THE LOCATION OF EXISTING

BELOW GRADE WASTE PIPING AND REFLECT ANY DEVIATION GREATER THAN 1'-0"

FROM THIS PLAN ON THE AS-BUILT DRAWINGS.

C CUTTING, BORING, SAWCUTTING OR DRILLING THROUGH THE NEW AND EXISTING

STRUCTURAL ELEMENTS TO BE DONE ONLY WHEN DETAILED IN THE DRAWINGS

OR ACCEPTED BY THE APPROVAL THE STRUCTURAL ENGINEER AND VA.

D REPAIR WALL SURFACE AFTER INSTALLATION AND INSPECTION OF EACH

PLUMBING FIXTURE AND PIPING INSTALLED.

E ALL WALL-MOUNTED ACCESS PANELS SHALL BE LOCKABLE TYPE.

F MAINTAIN MINIMUM 10-0" SEPARATION BETWEEN FLUE AND PLUMBING VENT

OUTLETS AND ANY FRESH AIR INTAKE. COORDINATE WITH HVAC CONTRACTOR.

G FLOORS SHALL SLOPE TO DRAINS AT 1% MINIMUM SLOPE. SEE ARCHITECTURAL

PLANS FOR MORE INFORMATION.

H PROVIDE ALL FLOOR DRAINS, FLOOR SINKS, TRENCH DRAINS, ETC. WITH TRAP

GUARD DEVICES (ASSE 1072 COMPLIANT).

I PROVIDE WALL CLEAN OUTS IN ALL VENT RISERS ON BRANCHES LONGER THAN

5'-0" AND ON BRANCHES SERVING SINKS OR URINALS.

J SEE RISER DIAGRAMS FOR PIPE SIZING.

N

AREA B

KEY PLAN

WORK AREA

EXISTING BUILDING

EXISTING BUILDING

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

TRIPLE C - The A/E Group 100 Pearl Street, 14th floor Hartfort, CT 06103

(315) 484-5958 Mat Perkins

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

MES GROUP

550 North Reo St, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephensen, P.E.

STRUCTURAL

C&S Companies 2575 E Camelback Rd, Suite 740 Phoenix, AZ 85016

(602) 997-7536 Bryan K. Salt, P.E. S.E.

B

IM

/4

-3

C o n s tr u c t S u b s ta n c e U s e

R e s id e n ti a l R e h a b

B u ild in g /4

-3

.A u g u s ta

.M E

P F

.R

.r v t

/2

/2

:4

:3

P

M

PL103

PLUMBING PLAN - PENTHOUSE 402-318

BLDG 258

07/26/2022 DCM/CB TH/DCM

100% CONSTRUCTION

DOCUMENTS ISSUED FOR

BIDDING

Construct Substance Use Residential Rehab Building

1 VA Center, Augusta, Maine

KEYNOTES

1 PROVIDE PRIMARY AND SECONDARY ROOF DRAINS SIZED PER CODE,

COORDINATE EXACT LOCATIONS WITH ARCHITECTURAL.

2 PRIMARY AND OVERFLOW STORM DRAINAGE TO OD AND RD ABOVE.

3 ROUTE RAIN LEADERS IN CEILING SPACE. COORDINATE INSTALLATION WITH

OTHER TRADES.

4 OVERFLOW STORM DRAINAGE DOWN TO FIRST FLOOR. SEE PL101 FOR

CONTINUATION.

5 PRIMARY STORM DRAINAGE DOWN TO FIRST FLOOR. SEE PL101 FOR

CONTINUATION.

6 PROVIDE 1" RO TREATED WATER DOWN TO CLEAN STEAM GENERATOR, 1-3-CSG01.

REFER TO MECHANICAL PLANS FOR CLEAN STEAM GENERATOR INFORMATION.

7 PROVIDE RO TREATED WATER FOR HYDRONIC MAKE-UP FEED WATER SUPPLY.

8 MECHANICAL CONDENSATE PIPING. RUN PIPING ALONG ADJACENT WALL AND

TERMINATE AT FLOOR DRAIN.

9 ROUTE MECHANICAL CONDENSATE PIPING FROM AIR HANDLER TO FLOOR DRAIN.

10 MECHANICAL EQUIPMENT SHOWN FOR REFERENCE. SEE MECHANICAL SHEETS

FOR MORE INFORMATION.

11 REFER TO SHEET PL102 FOR SANITARY PIPING SERVING FLOOR DRAIN.

Revisions: Date:

DRAWING KEYNOTE#

EQUIPMENT MARK

CW COLD WATER PIPING

HW HOT WATER PIPING

HWR HOT WATER RETURN PIPING

SAN SANITARY PIPING

V SANITARY VENT PIPING

PIPE UP

PIPE DOWN

GCO GRADE CLEAN OUT (1-WAY OR 2-WAY)OR

HOSE BIB WITH VACUUM BREAKER

OR VTR VENT THRU ROOF

WCO WALL CLEAN OUT

FCO FLOOR CLEAN OUT (1-WAY OR 2-WAY)OR

PIPE CAP

WCO

FLOOR DRAIN

BALL VALVE

FLOOR SINK

PLUMBING LEGEND

FD-C

FD-S

X-XX

CR COLD WATER RETURN PIPING

SECOND FLOOR SECTION 1

SECOND FLOOR SECTION 2

SECOND FLOOR SECTION 3

SECOND FLOOR SECTION 4

SECOND FLOOR SECTION 5

SECOND FLOOR SECTION 6 SECOND FLOOR SECTION 7

STORMWATER CALCULATIONS

DRAIN FLOW (GPM) =

RAINFALL RATE (in/hr) * ROOF AREA(ft2) * 144 (in2/ft2)

231 (in3/gal) * 60 (min/hr)

FLOOR ROOF CALCULATION - SECTION 1

ROOF AREA: 510 + 60 = 570 ft2

1/2 WALL AREA: 1/2 * 32 * 13 = 208 ft2

TOTAL AREA: 778 ft2

RAINFALL RATE: 2.3 in/hr (PER IPC-2021)

DRAIN FLOW: 18.6 GPM

PIPE SIZE: 2 in PIPE SLOPE: 1/8 in/ft (PER IPC-2021, TABLE 1106.2)

SECOND FLOOR ROOF CALCULATION - SECTION 2

ROOF AREA: 422 ft2

RAINFALL RATE: 2.3 in/hr (PER IPC-2021)

DRAIN FLOW: 10.1 GPM

PIPE SIZE: 2 in PIPE SLOPE: 1/8 in/ft (PER IPC-2021, TABLE 1106.2)

SECOND FLOOR ROOF CALCULATION - SECTION 3

ROOF AREA: 466+60 = 526 ft2

RAINFALL RATE: 2.3 in/hr (PER IPC-2021)

DRAIN FLOW: 12.6 GPM

PIPE SIZE: 2 in PIPE SLOPE: 1/8 in/ft (PER IPC-2021, TABLE 1106.2)

SECOND FLOOR ROOF CALCULATION - SECTION 4

ROOF AREA: 362 ft2

1/2 WALL AREA: 1/2 * 24 * 13 = 156 ft2

TOTAL AREA: 518 ft2

RAINFALL RATE: 2.3 in/hr (PER IPC-2021)

DRAIN FLOW: 12.4 GPM

PIPE SIZE: 2 in PIPE SLOPE: 1/8 in/ft (PER IPC-2021, TABLE 1106.2)

SECOND FLOOR ROOF CALCULATION - SECTION 5

ROOF AREA: 365 ft2

1/2 WALL AREA: 1/2 * 24.25 * 13 = 158 ft2

TOTAL AREA: 523 ft2

RAINFALL RATE: 2.3 in/hr (PER IPC-2021)

DRAIN FLOW: 12.5 GPM

PIPE SIZE: 2 in PIPE SLOPE: 1/8 in/ft (PER IPC-2021, TABLE 1106.2)

SECOND FLOOR ROOF CALCULATION - SECTION 6

ROOF AREA: 575 + 60 = 635 ft2

1/2 WALL…