This document outlines requirements for a construction project to rehabilitate a building at the Togus VA Medical Center in Maine. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas, as number 36C77624B0006 for project number 202-318-REHAB. Scope of work includes construction services to renovate a private patient bed ward and includes specifications for items like doors, door hardware, glazing, and construction documents. The response due date is not provided.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Togus Residential Rehab, Addendum 1
TRIPLE C – THE A&E GROUP
OUR REASONABLE SERVICE - TO PROVIDE YOU WITH EXEMPLARY SERVICE
410 Grand Avenue, Suite 201C Laramie, Wyoming 82070 Telephone: (307) 460-2054 Fax: (307) 460-2053
Addendum #1
Project: 402-318 – Construct Substance Use Residential Rehab at Togus VAMC
Date: 12/08/2023
Summary of Clarifications In response to bidders questions.
Added specification section 083616 for High Performance Barn (Sliding) Doors. Replaced specifications 08 71 00 Door hardware, and 08 80 00 Glazing
Added sheet A-720 for details regarding typical partition types. Replaced Sheets GI101, A-101A, A-
101B, and A600 for update of door 130C, clarification of door hardware and glazing coordination.
Specifications:
SECTION DESCRIPTION OF/REASON FOR CHANGE
08 36 16 High Performance Barn (Sliding) Door spec section added to specifications
08 71 00 Door hardware specification – hardware sets updated
08 80 00 Glazing specification – Glazing types updated
Drawing Changes:
SHEET NUMBER REVISION
NUMBER
DESCRIPTION OF/REASON FOR CHANGE
GI101 1 Door 130C has been changed to be a dual egress door
A-101A 1 Door 130C has been changed to be a dual egress door. Door hardware numbers have been updated.
A-101b 1 Door hardware numbers have been updated.
A-600 1 Door hardware and glazing types have been updated
A-702 1 Sheet has been added to show typical partition types.
End of Addendum
Notes
CVE Verified Service-Disabled Veteran-Owned Small Business
Minneapolis Renovate Private Patient Bed Ward 3D Building70 Project #: 618-22-102
High Performance Barn (Sliding) Door
08 36 16.13 - 1
SECTION 08 36 16.13
HIGH PERFORMANCE BARN (SLIDING) DOOR
PART 1 - GENERAL
1.1 SUMMARY
A. Sliding Barn Doors - flush wood and flush wood with glass, aluminum frames and related hardware.
1.2 RELATED SECTION
A. Section 08 14 00 – INTERIOR WOOD DOORS
B. Section 08 71 00 – DOOR HARDWARE
C. Section 08 80 00 – GLAZING
D. Section 09 22 16 – NON-STRUCTURAL METAL FRAMING
E. Section 10 14 00 - SIGNAGE
F. Division 26 – Electrical
G. Section 28 13 00 – Physical Access Control System
1.3 SUBMITTALS
A. Comply with Section 01 33 23 – SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES
B. Product Data: Submit manufacturer’s product data, including installation instructions.
C. Shop Drawings: Submit manufacturer’s shop drawings, including plans, elevations, sections, and details, indicating dimensions, tolerances, materials, components, hardware, finish, options, and accessories. Shop Drawings to show required blocking by others.
D. Samples: Submit manufacturer’s samples of the following sliding door components:
1. Door veneer or laminate sample
2. Aluminum Frame finish sample
E. Manufacturer’s Certification: Submit manufacturer’s certification that materials comply with specified requirements and are suitable for intended application.
F. Warranty Documentation: Submit manufacturer’s standard warranty.
G. Test Reports: Submit acoustical reports or UL1784 as applicable.
1.4 QUALITY ASSURANCE
A. Product Options: Drawings indicate size, profiles, and dimensional requirements of interior aluminum frames and doors.
B. Source: Integrated assembly Obtain sliding aluminum framed doors, Door leaves and door hardware and seal systems from single source integrated assembly manufacturer.
C. Manufacturer's Qualifications: Manufacturer regularly engaged for past 5 years in manufacture of sliding doors similar to that specified.
D. Installers Qualifications: Certified by Manufacturer as an approved installer. Minimum of 5 years experience in installing system.
1.5 MOCK UP:
A. Provide full installation of one door, including all hardware and leveling. Door function must be inspected by Manufacturer’s representative and COR. Do not proceed with installation of other
Construct Substance Use Residential Rehab Building Project #: 402-318
08 36 16.13 - 2 locations, until mockup has been approved by COR. This location will be used as the standard for installation on all other doors.
1.6 PREINSTALLATION MEETING
A. Conduct preinstallation meeting at project site a minimum 30 days before beginning Work of this Section.
1. Required Participants:
a. Contracting Officer's Representative.
b. Inspection and Testing Agency.
c. Contractor.
d. Installer.
e. Manufacturer's field representative.
f. Other installers responsible for adjacent and intersecting work. exterior wall system.
2. Meeting Agenda: Distribute agenda to participants minimum 3 days before meeting.
a. Installation schedule.
b. Installation sequence.
c. Preparatory work.
d. Protection before, during, and after installation.
e. Installation.
f. Transitions and connections to other work.
g. Inspecting and testing.
h. Other items affecting successful completion.
3. Document and distribute meeting minutes to participants to record decisions affecting installation.
1.7 REFERENCES
A. Architectural Barriers Act
B. Department of Veterans Affairs Barrier Free Design Standard PG-18-13
C. ANSI – American National Standards Institute
1. ANSI 156.18 Materials and Finishes
2. ANSI A117.1 Specifications for making buildings and facilities usable by physically handicapped people.
D. BHMA – Builders Hardware Manufacturers Association
E. DHI – Door and Hardware Institute
F. NFPA – National Fire Protection Association
1. NFPA 80 – Fire Doors and Windows
2. NFPA 101 – Life Safety code
3. NFPA 105 – Smoke and Draft Control Door Assemblies
4. NFPA 252 – Fire Tests of Doors Assemblies
G. AWS – Architectural Woodwork Standards
1.8 PERFORMANCE
A. Aluminum perimeter frames with integral acoustic seals
B. Maximum Ambient Air Infiltration of 1.569CFM/ft2 @ 25Pa.
C. Maximum Elevated Temperature Air Infiltration 1.475 CFM/ft2 @ 25Pa and 400f.
D. Soft self-closing mechanism integrated with top track.
E. Soft-closing mechanism at both sides of door integrated with top track. Soft Closers tested to a minimum of 150,000 cycles.
F. Concealed door guide.
08 36 16.13 - 3
1.9 DELIVERY: STORAGE AND PROTECTION
A. Delivery and Acceptance Requirements: Deliver materials to site in manufacturer’s original, unopened containers and packaging, with labels clearly identifying product name and manufacturer.
B. Notify manufacturer immediately of any shipping damage.
C. Storage and Handling Requirements:
1. Store and handle materials in accordance with manufacturer’s instructions.
2. Keep materials in manufacturer’s original, unopened containers and packaging until installation.
3. Store materials in clean, dry area indoors.
4. Protect materials and finish during storage, handling, and installation to prevent damage.
PART 2 - PRODUCTS
A. Basis of Design: AD SYSTEMS
1. 2201 100th St. SW, Everett, WA 98204 | Website: specADsystems.com | Phone: 425-
374-1360 | Attn: Estimating: estimating@specADsystems.com
B. Approved Alternate: Serenity Sliding Door Systems
1. Website: Serenityslidingdoor.com | Phone: 719-212-6007 | Email:
info@SerenitySlidingDoor.com
2.2 INTERIOR SLIDING ALUMINUM-FRAMED DOORS AND PARTITIONS
A. Interior Aluminum-Framed Integrated Assembly High Performance Top-Hung Sliding Doors with no visible bottom track.
B. Specified Wall Thickness: See Plans
C. Frame Profiles: Extruded aluminum frame “wrap” frame with integral vertical jamb (stile pocket).
1. Finish:
a. Standard: Painted Hardcoat (Kynar) Finish. Meets AAMA 2604 Standard Colors:
Light Sequin 789G048.
D. Door Leaves. All Doors to be factory machined for hardware including pilot and function holes.
1. 1-3/4" Flush Wood Door: Reference Spec Section 08 14 00 Interior Wood Doors or other section as applicable.
E. Integrated Assembly Door Components:
1. Single Top Track: High Performance barn door track
2. Valances: Extruded aluminum with integral end caps
a. Sloped valance
3. Top Rollers: Tandem nylon roller sized to match door weight with integral soft close mechanism at both sides of door.
4. Concealed Floor Guide: Automatic Drop down acoustic and smoke seal with Integral concealed floor guide. (No bottom track in floor)
5. Soft-Closer: Soft and self-closing damper mechanism at one sides of door leaf
6. Handles:
a. Standard Ladder Pull: 16” long x 1” diameter. Finish: US32D Satin Stainless Steel
F. Accessories:
1. Door Locks:
a. Mortise Latch and Lock Options:
1) SLI-1 Thumbturn with Privacy Indicator & 16-inch Ladder Pull
2) SLI-3 - Key Cylinder & Lever
2. Install, adjust, instruct all hardware per Part 3 of Division 8, 26, 28 to the satisfaction of
COR
08 36 16.13 - 4
3. Install, adjust, instruct all hardware per Part 3 of Division 8, 26, 28 to the satisfaction of
COR
a.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine wall openings to receive sliding doors for plumb, level, and square. Rough Opening cannot vary by more than ¼” from what is show on shop drawings. Note: Finish door operation will be affected by out of tolerance framing.
B. Verify dimensions of wall openings.
C. Examine surfaces to receive top and bottom guide.
D. Notify COR and Architect of conditions that would adversely affect installation or subsequent use of sliding doors.
E. Do not begin installation until unacceptable conditions are corrected. COR must be present for inspection of final rough opening prior to start of installation.
F. Base of door side to be flush or minimal. Rubber Base acceptable.
3.2 INSTALLATION
A. Install one door as Mockup. Schedule inspection with Manufacturer’s Representative and COR.
Installation must be accepted before proceeding with the rest of installation.
B. Install sliding doors in accordance with manufacturer’s instructions at locations indicated on the Drawings.
C. Install sliding doors plumb, level, square, and in proper alignment.
D. Install sliding doors to close against walls without gaps
E. Install sliding doors to open and close smoothly.
F. Anchor sliding doors securely in place to supports. Required: Fire treated 2 x 6 blocking required full length of track.
3.3 ADJUSTING
A. Adjust sliding doors for proper operation in accordance with manufacturer’s instructions.
B. Adjust sliding doors to operate smoothly without binding.
C. Schedule final inspection with COR. Adjust doors until deemed acceptable by COR.
D. Repair minor damages to finish in accordance with manufacturer’s instructions and as approved by COR.
3.4 CLEANING
A. Clean sliding doors promptly after installation in accordance with manufacturer’s instructions.
B. Do not use harsh cleaning materials or methods that could damage materials or finish.
3.5 PROTECTION
A. Protect installed sliding doors from damage during construction.
END OF SECTION
Door Hardware
08 71 00 - 1
SECTION 08 71 00
DOOR HARDWARE
PART 1 - GENERAL
1.1 DESCRIPTION
A. Door hardware and related items necessary for complete installation and operation of doors.
1.2 RELATED WORK
A. Caulking: Section 07 92 00 JOINT SEALANTS.
B. Application of Hardware:
1. Section 08 14 00, WOOD DOORS
2. Section 08 11 13, HOLLOW METAL DOORS AND FRAMES
3. Section 08 17 10, INTEGRATED DOOR ASSEMBLIES
4. Section 08 41 13, ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
5. Section 08 71 13, AUTOMATIC DOOR OPERATORS
C. Painting: Section 09 91 00, PAINTING.
D. Card Readers: Section 28 13 00, PHYSICAL ACCESS CONTROL SYSTEMS.
E. Electrical: Division 26, ELECTRICAL.
F. Fire Detection: Section 28 31 00, FIRE DETECTION AND ALARM.
1.3 GENERAL
A. All hardware shall comply with ABAAS, (Architectural Barriers Act Accessibility Standard) unless specified otherwise.
B. Provide rated door hardware assemblies where required by most current version of the International Building Code (IBC).
C. Hardware for Labeled Fire Doors and Exit Doors: Conform to requirements of NFPA 80 for labeled fire doors and to NFPA 101 for exit doors, as well as to other requirements specified.
Provide hardware listed by UL, except where heavier materials, large size, or better grades are specified herein under paragraph HARDWARE SETS. In lieu of UL labeling and listing, test reports from a nationally recognized testing agency may be submitted showing that hardware has been tested in accordance with UL test methods and that it conforms to NFPA requirements.
D. Hardware for application on metal and wood doors and frames shall be made to standard templates. Furnish templates to the fabricator of these items in sufficient time so as not to delay the construction.
E. The following items shall be of the same manufacturer, except as otherwise specified:
1. Mortise locksets.
2. Hinges for hollow metal and wood doors.
3. Surface applied overhead door closers.
4. Exit devices.
5. Floor closers.
1.4 WARRANTY
A. Automatic door operators shall be subject to the terms of FAR Clause 52.246-21, except that the Warranty period shall be two years in lieu of one year for all items except as noted below:
1. Locks, latchsets, and panic hardware: 5 years.
2. Door closers and continuous hinges: 10 years.
08 71 00 - 2
1.5 MAINTENANCE MANUALS
A. In accordance with Section 01 00 00, GENERAL REQUIREMENTS Article titled "INSTRUCTIONS", furnish maintenance manuals and instructions on all door hardware. Provide installation instructions with the submittal documentation.
1.6 SUBMITTALS
A. Submittals shall be in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. Submit 6 copies of the schedule per Section 01 33 23. Submit 2 final copies of the final approved schedules to VAMC Locksmith as record copies (VISN Locksmith if the VAMC does not have a locksmith).
B. Hardware Schedule: AHC certified hardware consultant to prepare and submit hardware schedule in the following form:
Hardware Item
Quantity Size Reference Publication Type No.
Finish Mfr.
Name and Catalog No.
Key Control Symbols
UL Mark (if fire rated and listed)
ANSI/BHMA
Finish Designation
C. Samples and Manufacturers' Literature:
1. Samples: All hardware items (proposed for the project) that have not been previously approved by Builders Hardware Manufacturers Association shall be submitted for approval. Tag and mark all items with manufacturer's name, catalog number and project number.
2. Samples are not required for hardware listed in the specifications by manufacturer's catalog number, if the contractor proposes to use the manufacturer's product specified.
D. Certificate of Compliance and Test Reports: Submit certificates that hardware conforms to the requirements specified herein. Certificates shall be accompanied by copies of reports as referenced. The testing shall have been conducted either in the manufacturer's plant and certified by an independent testing laboratory or conducted in an independent laboratory, within four years of submittal of reports for approval.
1.7 DELIVERY AND MARKING
A. Deliver items of hardware to job site in their original containers, complete with necessary appurtenances including screws, keys, and instructions. Tag one of each different item of hardware and deliver to COR for reference purposes. Tag shall identify items by Project Specification number and manufacturer's catalog number. These items shall remain on file in COR's office until all other similar items have been installed in project, at which time the COR will deliver items on file to Contractor for installation in predetermined locations on the project.
1.8 PREINSTALLATION MEETING
A. Convene a preinstallation meeting not less than 30 days before start of installation of door hardware. Require attendance of parties directly affecting work of this section, including Contractor and Installer, Architect, Project Engineer and VA Locksmith, Hardware Consultant, and Hardware Manufacturer’s Representative. Review the following:
1. Inspection of door hardware.
2. Job and surface readiness.
3. Coordination with other work.
4. Protection of hardware surfaces.
08 71 00 - 3
5. Substrate surface protection.
6. Installation.
7. Adjusting.
8. Repair.
9. Field quality control.
10. Cleaning.
1.9 INSTRUCTIONS
A. Hardware Set Symbols on Drawings: Except for protective plates, door stops, mutes, thresholds and the like specified herein, hardware requirements for each door are indicated on drawings by symbols. Symbols for hardware sets consist of letters (e.g., "HW") followed by a number. Each number designates a set of hardware items applicable to a door type.
B. Keying: All cylinders shall be keyed into existing Grand Master Key System. Provide removable core cylinders that are removable only with a special key or tool without disassembly of knob or lockset. Cylinders shall be 7 pin type. Keying information shall be furnished at a later date by the COR.
1.10 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. In text, hardware items are referred to by series, types, etc., listed in such specifications and standards, except as otherwise specified.
B. ASTM International(ASTM):
F883-13 ................................. Padlocks
E2180-18................Standard Test Method for Determining the Activity of Incorporated Antimicrobial Agent(s) In Polymeric or Hydrophobic Materials
C. American National Standards Institute/Builders Hardware Manufacturers Association
(ANSI/BHMA):
A156.1-06 .............................. Butts and Hinges
A156.2-03 .............................. Bored and Pre-assembled Locks and Latches
A156.3-08 .............................. Exit Devices, Coordinators, and Auto Flush Bolts
A156.4-08 .............................. Door Controls (Closers)
A156.5-14 .............................. Cylinders and Input Devices for Locks.
A156.6-05 .............................. Architectural Door Trim
A156.8-05 .............................. Door Controls-Overhead Stops and Holders
A156.11-14 ............................ Cabinet Locks
A156.12-05 ............. .............. Interconnected Locks and Latches
A156.13-05 ............................ Mortise Locks and Latches Series 1000
A156.14-07 ............. .............. Sliding and Folding Door Hardware
A156.15-06 ............................ Release Devices-Closer Holder, Electromagnetic and Electromechanical
A156.16-08 ............................ Auxiliary Hardware
A156.17-04 ............. .............. Self-Closing Hinges and Pivots
A156.18-06 ............................ Materials and Finishes
A156.20-06 ............. .............. Strap and Tee Hinges, and Hasps
08 71 00 - 4
A156.21-09 ............................ Thresholds
A156.22-05 ............................ Door Gasketing and Edge Seal Systems
A156.23-04 ............................ Electromagnetic Locks
A156.24-03 ............................ Delayed Egress Locking Systems
A156.25-07 ............. .............. Electrified Locking Devices
A156.26-06 ............................ Continuous Hinges
A156.28-07 ............. .............. Master Keying Systems
A156.29-07 ............. .............. Exit Locks and Alarms
A156.30-03 ............. .............. High Security Cylinders
A156.31-07 ........................... Electric Strikes and Frame Mounted Actuators
A156.36-10 ............................ Auxiliary Locks
A250.8-03 .............................. Standard Steel Doors and Frames
D. National Fire Protection Association (NFPA):
80-19 ..................................... Fire Doors and Other Opening Protectives
101-21 ................................... Life Safety Code
E. Underwriters Laboratories, Inc. (UL):
1. Building Materials Directory
PART 2 - PRODUCTS
2.1 BUTT HINGES
A. ANSI A156.1. Provide only three-knuckle hinges, except five-knuckle where the required hinge type is not available in a three-knuckle version (e.g., some types of swing-clear hinges). The following types of butt hinges shall be used for the types of doors listed, except where otherwise specified:
1. Exterior Doors: Type A2112/A5112 for doors 900 mm (3 feet) wide or less and Type
A2111/A5111 for doors over 900 mm (3 feet) wide. Hinges for exterior outswing doors shall have non-removable pins. Hinges for exterior fire-rated doors shall be of stainless steel material.
2. Interior Doors: Type A8112/A5112 for doors 900 mm (3 feet) wide or less and Type A8111/A5111 for doors over 900 mm (3 feet) wide. Hinges for doors exposed to high humidity areas (shower rooms, toilet rooms, kitchens, janitor rooms, etc. shall be of stainless steel material.
B. Provide quantity and size of hinges per door leaf as follows:
1. Doors up to 1210 mm (4 feet) high: 2 hinges.
2. Doors 1210 mm (4 feet) to 2260 mm (7 feet 5 inches) high: 3 hinges minimum.
3. Doors greater than 2260 mm (7 feet 5 inches) high: 4 hinges.
4. Doors up to 900 mm (3 feet) wide, standard weight: 114 mm x 114 mm (4-1/2 inches x 4-
1/2 inches) hinges.
5. Doors over 900 mm (3 feet) to 1065 mm (3 feet 6 inches) wide, standard weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).
6. Doors over 1065 mm (3 feet 6 inches) to 1210 mm (4 feet), heavy weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).
7. Provide heavy-weight hinges where specified.
8. At doors weighing 330 kg (150 pounds) or more, furnish 127 mm (5 inch) high hinges.
C. See Articles "MISCELLANEOUS HARDWARE" and "HARDWARE SETS" for pivots and hinges other than butts specified above and continuous hinges specified below.
08 71 00 - 5
2.2 CONTINUOUS HINGES
A. ANSI/BHMA A156.26, Grade 1-600.
1. Listed under Category N in BHMA's "Certified Product Directory."
B. General: Minimum 0.120-inch- (3.0-mm-) thick, hinge leaves with minimum overall width of 4 inches (102 mm); fabricated to full height of door and frame and to template screw locations;
with components finished after milling and drilling are complete
C. Continuous, Barrel-Type Hinges: Hinge with knuckles formed around a Teflon-coated 6.35mm (0.25-inch) minimum diameter pin that extends entire length of hinge.
1. Base Metal for Exterior Hinges: Stainless steel.
2. Base Metal for Interior Hinges: Stainless steel
3. Base Metal for Hinges for Fire-Rated Assemblies: Stainless steel.
4. Provide with non-removable pin (hospital tip option) at lockable outswing doors.
5. Where required to clear adjacent casing, trim, and wall conditions and allow full door swing, provide wide throw hinges of minimum width required.
6. Provide with manufacturer’s cut-outs for separate mortised power transfers and/or mortised automatic door bottoms where they occur.
7. Where thru-wire power transfers are integral to the hinge, provide hinge with easily removable portion to allow easy access to wiring connections.
8. Where models are specified that provide an integral wrap-around edge guard for the hinge edge of the door, provide manufacturer’s adjustable threaded stud and machine screw mechanism to allow the door to be adjusted within the wrap-around edge guard.
9. Provide additional fire labels for both frame and door panel(s) on the top of door panel and head of frame.
2.3 DOOR CLOSING DEVICES
A. Closing devices shall be products of one manufacturer.
2.4 OVERHEAD CLOSERS
A. Conform to ANSI A156.4, Grade 1.
B. Closers shall conform to the following:
1. The closer shall have minimum 50 percent adjustable closing force over minimum value for that closer and have adjustable hydraulic back check effective between 60 degrees and 85 degrees of door opening.
2. Where specified, closer shall have hold-open feature.
3. Size Requirements: Provide multi-size closers, sizes 1 through 6, except where multi-size closer is not available for the required application.
4. Material of closer body shall be forged or cast.
5. Arm and brackets for closers shall be steel, malleable iron or high strength ductile cast iron.
6. Where closers are exposed to the exterior or are mounted in rooms that experience high humidity, provide closer body and arm assembly of stainless steel material.
7. Closers shall have full size metal cover; plastic covers will not be accepted.
8. Closers shall have adjustable hydraulic back-check, separate valves for closing and latching speed, adjustable back-check positioning valve, and adjustable delayed action valve.
9. Provide closers with any accessories required for the mounting application, including (but not limited to) drop plates, special soffit plates, spacers for heavy-duty parallel arm fifth screws, bull-nose or other regular arm brackets, longer or shorter arm assemblies, and special factory templating. Provide special arms, drop plates, and templating as needed to allow mounting at doors with overhead stops and/or holders.
10. Closer arms or backcheck valve shall not be used to stop the door from overswing, except in applications where a separate wall, floor, or overhead stop cannot be used.
11. Provide parallel arm closers with heavy duty rigid arm.
08 71 00 - 6
12. Where closers are to be installed on the push side of the door, provide parallel arm type except where conditions require use of top jamb arm.
13. Provide all surface closers with the same body attachment screw pattern for ease of replacement and maintenance.
14. All closers shall have a 1 ½” (38mm) minimum piston diameter.
2.5 FLOOR CLOSERS AND FLOOR PIVOT SETS
A. Comply with ANSI A156.4. Provide stainless steel floor plates for floor closers and floor pivots, except where metal thresholds occur. Provide cement case for all floor closers. Floor closers specified for fire doors shall comply with Underwriters Laboratories, Inc., requirements for concealed type floor closers for classes of fire doors indicated on drawings. Hold-open mechanism, where required, shall engage when door is opened 105 degrees, except when door swing is limited by building construction or equipment, the hold-open feature shall engage when door is opened approximately 90 degrees. The hold-open mechanism shall be selectable on/off by turning a screw through the floor plate. Floor closers shall have adjustable hydraulic back-check, adjustable close speed, and adjustable latch speed. Provide closers with delayed action where a hold-open mechanism is not required. Floor closers shall be multi-sized. Single acting floor closers shall also have built in dead stop. Where required, provide closers with special cement cases appropriate for shallow deck installation or where concrete joint lines run through the floor blockout. At offset-hung doors installed in deep reveals, provide special closer arm and spindle to allow for installation. Where stone or terrazzo is applied over the floor closer case, provide closer without floor plate and with extended spindle (length as required) and special cover pan (depth as required) to allow closer to be accessed without damaging the material applied over the closer. Pivots for non-labeled doors shall be cast, forged or extruded brass or bronze.
B. Where floor closer appears in hardware set provide the following as applicable.
1. Double Acting Floor Closers: Type C06012.
2. Single Acting Floor Closer: Type C06021 (center pivoted). (Intermediate pivot is not required).
3. Single Acting Floor Closers: Type C06041 (offset pivoted).
4. Single Acting Floor Closer for Labeled Fire Doors: Type C06051 (offset pivoted).
5. Single Acting Floor Closers For Lead Lined Doors: Type C06071 (offset pivoted).
2.6 DOOR STOPS
A. Conform to ANSI A156.16.
B. Provide door stops wherever an opened door or any item of hardware thereon would strike a wall, column, equipment or other parts of building construction. For concrete, masonry or quarry tile construction, use expansion shields for mounting door stops.
C. Where locks with turn pieces or pushbuttons occur, equip wall bumpers Type L02251 (rubber pads having concave face) to receive turn piece or button.
D. Provide floor stops (Type L02141 or L02161) in office areas; Type L02121 x 3 screws into floor elsewhere. Wall bumpers, where used, must be installed to impact the trim or the door within the leading half of its width. Floor stops, where used, must be installed within 4-inches of the wall face and impact the door within the leading half of its width.
E. Where drywall partitions occur, use floor stops, Type L02141 or L02161 in office areas, Type L02121 elsewhere.
F. Omit stops where floor mounted door holders are required and where automatic operated doors occur.
G. Provide appropriate roller bumper for each set of doors (except where closet doors occur) where two doors would interfere with each other in swinging.
H. Provide appropriate door mounted stop on doors in individual toilets where floor or wall mounted stops cannot be used.
08 71 00 - 7
I. Provide overhead surface applied stop Type C02541, ANSI A156.8 on patient toilet doors in bedrooms where toilet door could come in contact with the bedroom door.
J. Provide door stops on doors where combination closer magnetic holders are specified, except where wall stops cannot be used or where floor stops cannot be installed within 4-inches of the wall.
K. Where the specified wall or floor stop cannot be used, provide concealed overhead stops (surface-mounted where concealed cannot be used).
2.7 OVERHEAD DOOR STOPS AND HOLDERS
A. Conform to ANSI Standard A156.8. Overhead holders shall be of sizes recommended by holder manufacturer for each width of door. Set overhead holders for 110 degree opening, unless limited by building construction or equipment. Provide Grade 1 overhead concealed slide type:
stop-only at rated doors and security doors, hold-open type with exposed hold-open on/off control at all other doors requiring overhead door stops.
2.8 LOCKS AND LATCHES
A. Conform to ANSI A156.2. Locks and latches for doors 45 mm (1-3/4 inch) thick or over shall have beveled fronts. Lock cylinders shall have not less than seven pins. Cylinders for all locksets shall be removable core type. Cylinders shall be furnished with construction removable cores and construction master keys. Cylinder shall be removable by special key or tool.
Construct all cores so that they will be interchangeable into the core housings of all mortise locks, rim locks, cylindrical locks, and any other type lock included in the Master Key System.
Disassembly of lever or lockset shall not be required to remove core from lockset. All locksets or latches on double doors with fire label shall have latch bolt with 19 mm (3/4 inch) throw, unless shorter throw allowed by the door manufacturer’s fire label. Provide temporary keying device or construction core to allow opening and closing during construction and prior to the installation of final cores.
B. In addition to above requirements, locks and latches shall comply with following requirements:
1. Mortise Lock and Latch Sets: Conform to ANSI/BHMA A156.13. Mortise locksets shall be series 1000, minimum Grade 2. All locksets and latchsets, except on designated doors in Psychiatric (Mental Health) areas, shall have lever handles fabricated from cast stainless steel. Provide sectional (lever x rose) lever design. No substitute lever material shall be accepted. All locks and latchsets shall be furnished with 122.55 mm (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8-inch) lip-to-center dimension. Lock function F02 shall be furnished with emergency tools/keys for emergency entrance. All lock cases installed on lead lined doors shall be lead lined before applying final hardware finish. Furnish armored fronts for all mortise locks. Where mortise locks are installed in high-humidity locations or where exposed to the exterior on both sides of the opening, provide non-ferrous mortise lock case.
2. Cylindrical Lock and Latch Sets: levers shall meet ADA (Americans with Disabilities Act) requirements. Cylindrical locksets shall be series 4000 Grade I. All locks and latchsets shall be furnished with 122.55 mm (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8-inch) lip-to-center dimension. Provide lever design to match design selected by Architect or to match existing lever design. Where two turn pieces are specified for lock F76, turn piece on inside knob shall lock and unlock inside knob, and turn piece on outside knob shall unlock outside knob when inside knob is in the locked position. (This function is intended to allow emergency entry into these rooms without an emergency key or any special tool.)
3. Auxiliary locks shall be as specified under hardware sets and conform to ANSI A156.36.
4. Locks on designated doors in Psychiatric (Mental Health) areas shall be paddle type with arrow projection covers and be UL Listed. Provide these locks with paddle in the down position on both sides of the door. Locks shall be fabricated of wrought stainless steel.
08 71 00 - 8
2.9 PUSH-BUTTON COMBINATION LOCKS
A. ANSI/BHMA A156.5, Grade 1. Battery operated pushbutton entry.
B. Construction: Heavy duty mortise lock housing conforming to ANSI/BHMA A156.13, Grade 1.
Lever handles and operating components in compliance with the ABAAS and the VA Barrier Free Guidelines. Match lever handles of locks and latchsets on adjacent doors.
C. Special Features: Key override to permit a master keyed security system and a pushbutton security code activated passage feature to allow access without using the entry code.
2.10 ELECTROMAGNETIC LOCKS
A. ANSI/BHMA A156.23; electrically powered, of strength and configuration indicated; with electromagnet attached to frame and armature plate attached to door. Listed under Category E in BHMA's "Certified Product Directory."
1. Type: Full exterior or full interior, as required by application indicated.
2. Strength Ranking: 500 pound force minimum per leaf.
3. Inductive Kickback Peak Voltage: Not more than 0 V.
4. Residual Magnetism: Not more than 4 pound force to separate door from magnet.
B. Delayed-Egress Locks: BHMA A156.24. Listed under Category G in BHMA's "Certified Product Directory".
1. Means of Egress Doors: Lock releases within 15 seconds after applying a force not more than 15 pound force for not more than 3 seconds, as required by NFPA 101.
2. Security Grade: Activated from secure side of door by initiating device.
3. Movement Grade: Activated by door movement as initiating device.
4. The lock housing shall not project more than 4-inches (101mm) from the underside of the frame head stop.
2.11 ELECTRIC STRIKES
A. ANSI/ BHMA A156.31 Grade 1.
B. General: Use fail-secure electric strikes at fire-rated doors.
2.12 KEYS
A. Stamp all keys with change number and key set symbol. Furnish keys in quantities as follows:
Locks/Keys Quantity
Cylinder locks 2 keys each
Cylinder lock change key blanks 100 each different key way
Master-keyed sets 6 keys each
Grand Master sets 6 keys each
Great Grand Master set 5 keys
Control key 2 keys
2.13 ARMOR PLATES, KICK PLATES, MOP PLATES AND DOOR EDGING
A. Conform to ANSI Standard A156.6.
B. Provide protective plates and door edging as specified below:
1. Kick plates, mop plates and armor plates of metal, Type J100 series.
2. Provide kick plates and mop plates where specified. Kick plates shall be 254 mm (10 inches) or 305 mm (12 inches) high. Mop plates shall be 152 mm (6 inches) high. Both kick and mop plates shall be minimum 1.27 mm (0.050 inches) thick. Provide kick and mop plates beveled on all 4 edges (B4E). On push side of doors where jamb stop
08 71 00 - 9 extends to floor, make kick plates 38 mm (1-1/2 inches) less than width of door, except pairs of metal doors which shall have plates 25 mm (1 inch) less than width of each door.
Extend all other kick and mop plates to within 6 mm (1/4 inch) of each edge of doors.
Kick and mop plates shall butt astragals. For jamb stop requirements, see specification sections pertaining to door frames.
3. Kick plates and/or mop plates are not required on following door sides:
a. Armor plate side of doors;
b. Exterior side of exterior doors;
c. Closet side of closet doors;
d. Both sides of aluminum entrance doors.
4. Where louver or grille occurs in lower portion of doors, substitute stretcher plate and kick plate in place of armor plate. Size of stretcher plate and kick plate shall be 254 mm (10 inches) high.
5. Provide stainless steel edge guards where so specified at wood doors. Provide mortised type instead of surface type except where door construction and/or ratings will not allow.
Provide edge guards of bevel and thickness to match wood door. Provide edge guards with factory cut-outs for door hardware that must be installed through or extend through the edge guard. Provide full-height edge guards except where door rating does not allow; in such cases, provide edge guards to height of bottom of typical lockset armor front. Forward edge guards to wood door manufacturer for factory installation on doors.
6. Armor plates for doors shall be listed per NFPA 80; installed per door testing, and bear label from testing agency. Forward armor plates to wood door manufacturer for factory installation on doors.
2.14 EXIT DEVICES
A. Conform to ANSI Standard A156.3. Exit devices shall be Grade 1; type and function are specified in hardware sets. Provide flush with finished floor strikes for vertical rod exit devices in interior of building. Trim shall have cast satin stainless steel lever handles of design similar to locksets, unless otherwise specified. Provide key cylinders for keyed operating trim and, where specified, cylinder dogging.
B. Surface vertical rod panics shall only be provided less bottom rod; provide fire pins as required by exit device and door fire labels. Do not provide surface vertical rod panics at exterior doors.
C. Concealed vertical rod panics shall be provided less bottom rod at interior doors, unless lockable or otherwise specified; provide fire pins as required by exit device and door fire labels.
Where concealed vertical rod panics are specified at exterior doors, provide with both top and bottom rods.
D. Where removable mullions are specified at pairs with rim panic devices, provide mullion with key-removable feature.
E. At non-rated openings with panic hardware, provide panic hardware with key cylinder dogging feature.
F. Exit devices for fire doors shall comply with Underwriters Laboratories, Inc., requirements for Fire Exit Hardware. Submit proof of compliance.
G. Electrified devices:
1. Include concealed Power Transfer devices where electrified Exit devices are scheduled.
a. Select Power Transfer models having required number of conductors and conductors of the wire gauge recommended for the device served.
2. Include Power Supply as required.
2.15 FLUSH BOLTS (LEVER EXTENSION)
A. Conform to ANSI A156.16. Flush bolts shall be Type L24081 unless otherwise specified.
Furnish proper dustproof strikes conforming to ANSI A156.16, for flush bolts required on lower part of doors.
08 71 00 - 10
B. Lever extension manual flush bolts shall only be used at non-fire-rated pairs for rooms only accessed by maintenance personnel.
C. Face plates for cylindrical strikes shall be rectangular and not less than 25 mm by 63 mm (1 inch by 2-1/2 inches).
D. Friction-fit cylindrical dustproof strikes with circular face plate may be used only where metal thresholds occur.
E. Provide extension rods for top bolt where door height exceeds 2184 mm (7 feet 2 inches).
2.16 FLUSH BOLTS (AUTOMATIC)
A. Conform to ANSI A156.3. Dimension of flush bolts shall conform to ANSI A115. Bolts shall conform to Underwriters Laboratories, Inc., requirements for fire door hardware. Flush bolts shall automatically latch and unlatch. Furnish dustproof strikes conforming to ANSI A156.16 for bottom flushbolt. Face plates for dustproof strike shall be rectangular and not less than 38 mm by 90 mm (1-1/2 by 3-1/2 inches).
B. At interior doors, provide auto flush bolts less bottom bolt, unless otherwise specified, except at wood pairs with fire-rating greater than 20 minutes; provide fire pins as required by auto flush bolt and door fire labels.
2.17 DOOR PULLS WITH PLATES
A. Conform to ANSI A156.6. Pull Type J401, 152 mm CTC (6 inches CTC) length by 19 mm (3/4 inches) diameter minimum with plate Type J302, 90 mm by 381 mm (3-1/2 inches by 15 inches), unless otherwise specified. Provide pull with projection of 57.2 mm (2 1/4 inches) minimum and a clearance of 38.1 mm (1 1/2 inches) minimum. Cut plates of door pull plate for cylinders, or turn pieces where required.
2.18 PUSH PLATES
A. Conform to ANSI A156.6. Metal, Type J302, 203 mm (8 inches) wide by 406.4 mm (16 inches) high. Provide metal Type J302 plates 102 mm (4 inches) wide by 406.4 mm (16 inches) high where push plates are specified for doors with stiles less than 203 mm (8 inches) wide. Cut plates for cylinders, and turn pieces where required.
2.19 COMBINATION PUSH AND PULL PLATES
A. Conform to ANSI 156.6. Type J303, stainless steel 3 mm (1/8 inch) thick, 80 mm (3-1/3 inches) wide by 800 mm (16 inches) high), top and bottom edges shall be rounded. Secure plates to wood doors with 38 mm (1-1/2 inch) long No. 12 wood screws. Cut plates for turn pieces, and cylinders where required. Pull shall be mounted down.
2.20 COORDINATORS
A. Conform to ANSI A156.16. Coordinators, when specified for fire doors, shall comply with Underwriters Laboratories, Inc., requirements for fire door hardware. Coordinator may be omitted on exterior pairs of doors where either door will close independently regardless of the position of the other door. Coordinator may be omitted on interior pairs of non-labeled open where open back strike is used. Open back strike shall not be used on labeled doors. Paint coordinators to match door frames, unless coordinators are plated. Provide bar type coordinators, except where gravity coordinators are required at acoustic pairs. For bar type coordinators, provide filler bars for full width and, as required, brackets for push-side surface mounted closers, overhead stops, and vertical rod panic strikes.
2.21 THRESHOLDS
A. Conform to ANSI A156.21, mill finish extruded aluminum, except as otherwise specified. In existing construction, thresholds shall be installed in a bed of sealant with ¼-20 stainless steel machine screws and expansion shields. In new construction, embed aluminum anchors coated with epoxy in concrete to secure thresholds. Furnish thresholds for the full width of the openings.
08 71 00 - 11
B. For thresholds at elevators entrances see other sections of specifications.
C. At exterior doors and any interior doors exposed to moisture, provide threshold with non-slip abrasive finish.
D. Provide with miter returns where threshold extends more than 12 mm (0.5 inch) beyond face of frame.
2.22 AUTOMATIC DOOR BOTTOM SEAL AND RUBBER GASKET FOR LIGHT PROOF OR
SOUND CONTROL DOORS AND SMOKE SEALS.
A. Conform to ANSI A156.22. Provide mortise or under-door type, except where not practical. For mortise automatic door bottoms, provide type specific for door construction (wood or metal).
B. Perimeter Gasketing
1. Perimeter Gasketing – Self-Adhesive Seals:
a. Seal: Silicone.
b. Fasteners: Self-adhesive strip.
c. Color: Black
d. Use R0Y154.
2.23 WEATHERSTRIPS (FOR EXTERIOR DOORS)
A. Conform to ANSI A156.22. Air leakage shall not to exceed 0.50 CFM per foot of crack length (0.000774m3/s/m).
B. Perimeter Gasketing
1. Perimeter Gasketing - Heavy Duty Type:
a. Material: Extruded tempered aluminum 6063-T6.
b. Finish (ANSI/BHMA 156.18): Clear anodized aluminum.
c. Seal: Silicone.
d. Fasteners: Stainless steel.
e. Use R3E165
2. 90 Degree Aluminum Retainer Brush Weatherstrip:
a. Material: Extruded tempered aluminum 6063-T6.
b. Finish (ANSI/BHMA A156.18): Clear anodized aluminum.
c. Brush Construction: Densely compressed nylon filaments encased in galvanized retainer.
d. Color: Aluminum color, black and gray nylon.
e. Use R3A414
2.24 MISCELLANEOUS HARDWARE
A. Access Doors (including Sheet Metal, Screen and Woven Wire Mesh Types): Except for fire-rated doors and doors to Temperature Control Cabinets, equip each single or double metal access door with Lock Type E07213, conforming to ANSI A156.11. Key locks as directed. Ship lock prepaid to the door manufacturer. Hinges shall be provided by door manufacturer.
B. Cylinders for Various Partitions and Doors: Key cylinders same as entrance doors of area in which partitions and door occur. Provide cylinders to operate locking devices where specified for following partitions and doors:
1. Folding doors and partitions.
2. Fire-rated access doors-Engineer's key set.
C. Mutes: Conform to ANSI A156.16. Provide door mutes or door silencers Type L03011 or L03021, depending on frame material, of white or light gray color, on each steel or wood door frame, except at fire-rated frames, lead-lined frames and frames for sound-resistant, lightproof and electromagnetically shielded doors. Furnish 3 mutes for single doors and 2 mutes for each pair of doors, except double-acting doors. Provide 4 mutes or silencers for frames for each Dutch type door. Provide 2 mutes for each edge of sliding door which would contact door frame.
08 71 00 - 12
2.25 CONTROLLED ACCESS ACCESSORY ITEMS
A. Keyswitch (KS):
1. Wall mounted, single gang box activation device.
2. Maintained contacts unless otherwise noted; field-selectable to momentary action.
3. Red/green LED.
4. Include Cylinder.
5. Base Product: 653-L2 by Schlage.
B. Exit Button (EB):
1. Wall mounted, single gang box lock release button for emergency egress.
2. Momentary contacts.
3. Locate EB where indicated in Drawings.
4. Base Product: 623-RD-EX by Schlage.
C. Remote Lock Release (RLR) Button:
1. Wall mounted, single gang box activation device.
2. Convenience releasing device, located remotely from opening, to release an electrified locking mechanism.
a. Where used with Automatic Doors: RLR shall also activate operator to open.
3. Momentary contacts.
4. Base Product: 623-GR by Schlage.
D. Remote Lock Activation (RLA) Button:
1. Wall mounted, single gang box activation device.
2. Crisis lock Actuation Device located remotely from opening, to activate and hold an electrified locking mechanism in the event of threat to facility or occupants.
a. Where used with Automatic Doors: RLA shall also disable other Actuation Devices on the unsecured side.
3. Alternate action/Maintained contacts.
4. Base Product: 623-GR-AA-DP by Schlage.
E. Remote Lock Release (RLR) Button:
1. Surface mounted under countertop or under cabinets.
2. Convenience lock release device for staff use.
3. Where used with Automatic Doors: RLR shall also activate operator to open.
4. Momentary contacts.
5. Base Product: 660-PB by Schlage.
F. Remote Lock Activation (RLA) Button:
1. Surface mounted under countertop or under cabinets.
2. Crisis lock Actuation Device to activate and hold an electrified locking mechanism in the event of threat to facility or occupants.
3. Where used with Automatic Doors: RLA shall disable other Actuation Devices on the unsecured side.
4. Maintained contacts.
5. Base Product: 660-T4 by Schlage.
G. Card Readers:
1. Per Section 28 13 00, PHYSICAL ACCESS CONTROL SYSTEM.
H. Door Position Switches (DPS):
1. Per Section 28 13 00, PHYSICAL ACCESS CONTROL SYSTEM.
a. Exception: Where Hardware Sets specifically call for DPS to be provided by Section 08 71 00 (this section), refer to the following paragraph.
I. Div 08 Door Position Switches (DPS) specified herein:
1. Description: Magnetic, concealed mounting, normally closed contacts.
2. Provided and installed by Hardware supplier/installer.
3. Base Product: 679-05WD/HM by Schlage
08 71 00 - 13
J. Request-to-Exit (REX) motion sensors:
1. Provide where necessary to shunt alarm.
K. Request-to-Exit (REX) motion sensors by Division 08:
1. REX devices provided by Division 08 where used to momentarily drop a lock for free egress. (See Security System for REX Motion Sensors used to shunt alarm).
2. Passive Infrared (PIR) technology, unaffected by Fire Alarm Strobes, camera flashes, ambulance lights etc.
3. Adjustable latch time, up to 60 seconds.
4. Tilt adjustable.
5. Selectable Voltage: 12-24 VDC.
6. Base Product: Scan II by Schlage.
7. Optional Product: XMS by Securitron.
L. Touch Bars:
1. Non-latching exit bar with no moving parts used to momentarily release Magnetic Lock when touched by user.
2. Base Product: 692 SmartBar by Locknetics.
3. Base Product: TSB-CL Touch Sense Exit Device by Securitron.
M. Fire Alarm Relays:
1. Specified with Fire Alarm System in Section 28 31 00.
N. Low Voltage Power (centrally supplied by Security System):
1. Unless otherwise noted, Section 28 13 [00, PHYSICAL ACCESS CONTROL
SYSTEM][16, PHYSICAL ACCESS CONTROL SYSTEM AND DATABASE
MANAGEMENT].will provide low voltage power required to power items with current draw less than 2 AMP (24 VDC) including the following:
a. Magnetic Locks.
b. Electric Strikes.
c. Electro-Mechanical Mortise Locksets.
d. Electro-Mechanical Cylindrical Locksets.
O. Power Supplies (PS) – Division 08 devices installed local to opening:
1. Provide filtered, regulated power.
2. Include relay modules that interface with Fire Alarm System.
3. Select power supply units that are:
a. Same brand as primary devices being powered.
b. Capable of receiving Fire Alarm Inputs.
c. Capable of interfacing scheduled hardware with automatic operators.
d. Include time delay modules where required for described function.
4. Provide UL listed power supply units where ever Magnetic Locks, Electrified Locksets, Electric Strikes and similar items are scheduled.
a. Base Product (Electrified Locks): PS900 Series by Schlage.
b. Base Product (Electric Strikes): PS900 Series by Von Duprin/Schlage.
c. Base Product (Magnetic Locks): PS900 Series by Locknetics/Schlage.
2.26 THERMOSTATIC TEMPERATURE CONTROL VALVE CABINETS
A. Where lock is shown, equip each cabinet door (metal) with lock Type E06213, conforming to ANSI A156.36. Key locks in Key Sets approved by Contracting Officer. See mechanical drawings and specifications for location of cabinets.
B. Cabinet manufacturer shall supply the hinges, bolts and pulls. Ship locks to cabinet manufacturer for installation.
2.27 HINGED WIRE GUARDS (FOR WINDOWS, DOORS AND TRANSOMS) AND WIRE
PARTITION DOORS
A. Butt hinges, type A8133 (special swaging) 100 mm by 90 mm (4 inches by 3-1/2 inches), Finish
US2C.
08 71 00 - 14
1. 3 hinges for guards over 1060 mm (3-1/2 feet) high.
2. 2 hinges for guards less than 1060 mm (3-1/2 feet) high.
B. Conform to ANSI A156.36. Lock Type E06081 for guards and Type E06061 for partitions.
1. Keying: Except as noted otherwise, key locks like entrance door or space wherein guards and partitions are located except as otherwise specified.
2. Key locks for partitions enclosing mechanical and electrical equipment in Engineer's Set.
(See detailed drawings for number of locks and butt hinges required for each guard).
2.28 FINISHES
A.