Attachment 17 Section 23 31 00 - HVAC DUCTS AND CASINGS.pdf

PDF 630 KB Posted

Attached to
Y1DA--636-804 Minor Construction Iowa City Relocate Woman's Health and Specialty Clinics for Building 50 (VA-23-00000881)
Solicitation number
36C77623R0138
Issued by

About this file

This document is a specification section outlining requirements for HVAC ducts and casings for the Iowa City VA Medical Center project to relocate women's health and specialty clinics. Key requirements include galvanized sheet metal or aluminum ducts meeting SMACNA standards for gauge, joint types, reinforcement and pressure classifications up to 6 inches WG supply and 3 inches WG return. Ducts must meet Class A seal standards and pass leakage tests below 4% of design airflow. Additional specifications cover round and flat oval ducts, casings, access doors, fire dampers, smoke dampers, flexible ducts, sound attenuators and duct mounted steam humidifiers. Installation must follow SMACNA guidelines and ductwork must be leak tested and repaired as required before insulation and balancing.

View the file

Other files

File Type Posted
Attachment 12 Technical Questions and Answers.docx DOCX document
Attachment 6 Updated 02122024 Davis Bacon Wage Rates Johnson County.pdf PDF
36C77623R0138 0005 02132024.docx DOCX document
Attachment 15 SECTION 05 40 00 COLD-FORMED METAL FRAMING.pdf PDF
36C77623R0138 0004.pdf PDF
Attachmnet 16 636-804 (VEG 20.12) Addendum 3 Drawings.pdf PDF
Attachment 12 Technical Questions and Answers.docx DOCX document
Attachment 14 SECTION 01 00 00 GENERAL REQUIREMENTS.pdf PDF
Attachment 13 SECTION 00 01 10 - TABLE OF CONTENTS.pdf PDF
Attachment 01 36C7763R0138 Womans Health Site Visit Sign In.pdf PDF
36C77623R0138 0003.docx DOCX document
Attachment 1 SPECIFICATIONS 636-804 (20.12) Spec Vol l_Addendum 2 122123.pdf PDF
36C77623R0138 0002.docx DOCX document
36C77623R0138 0001.docx DOCX document
Attachment 8 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 1 SPECIFICATIONS 636-804 (20.12) Spec Vol l_Addendum 2.pdf PDF
Attachment 3 Drawings 636-804 - Bid Set - Vol 1 of 3.pdf PDF
Attachment 11 - Division Breakdown Pricing Sheet.xls XLS spreadsheet
Attachment 4 Drawings 636-804 - Bid Set - Vol 2 of 3.pdf PDF
Attachment 10 - Scope of Work- 636-804.pdf PDF
36C77623R0138_1.docx DOCX document
Attachment 5 Drawings 636-804 - Bid Set - Vol 3 of 3.pdf PDF
Attachment 6 Davis Bacon Wage Rates Johnson County 1023.pdf PDF
Attachment 9 - SITE-MASTER Site Map.pdf PDF
Attachment 2 SPECIFICATIONS 636-804 (20.12) Spec Vol II 100_stamped REV Final.pdf PDF
Attachment 7 Brand Name Justification - ICVAMC _Redacted.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

02-01-20

23 31 00 - 1

SECTION 23 31 00

HVAC DUCTS AND CASINGS

PART 1 - GENERAL

1.1 DESCRIPTION

A. Ductwork and accessories for HVAC including the following:

1. Supply air, return air, outside air, exhaust, make-up air, and relief systems.

B. Definitions:

1. SMACNA Standards as used in this specification means the HVAC Duct

Construction Standards, Metal and Flexible.

2. Seal or Sealing: Use of liquid or mastic sealant, with or without compatible tape overlay, or gasketing of flanged joints, to keep air leakage at duct joints, seams, and connections to an acceptable minimum.

3. Duct Pressure Classification: SMACNA HVAC Duct Construction

Standards, Metal and Flexible.

4. Exposed Duct: Exposed to view in a finished room, exposed to weather.

1.2 RELATED WORK

A. Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES.

B. Section 07 84 00, FIRESTOPPING: Fire Stopping Material.

C. Section 08 90 00, LOUVERS and VENTS: Outdoor and Exhaust Louvers.

D. Section 22 11 00, FACILITY WATER DISTRIBUTION: Plumbing Connections.

E. Section 23 05 11, COMMON WORK RESULTS FOR HVAC: General Mechanical

Requirements.

F. Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIPING and

EQUIPMENT: Noise Level Requirements.

G. Section 23 05 93, TESTING, ADJUSTING, and BALANCING FOR HVAC: Testing and Balancing of Air Flows.

H. Section 23 07 11, HVAC, and BOILER PLANT INSULATION: Duct Insulation.

I. Section 23 09 23, DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC: Duct Mounted

Instrumentation.

J. Section 23 34 00, HVAC FANS: Return Air and Exhaust Air Fans.

K. Section 23 36 00, AIR TERMINAL UNITS: Air Flow Control Valves and

Terminal Units.

Iowa City VA Medical Center Relocate Women's Health Clinic & Specialty Clinics

February 09, 2024 Addendum A3

Project No. 636-804

23 31 00 - 2

L. Section 23 40 00, HVAC AIR CLEANING DEVICES: Air Filters and Filters'

Efficiencies.

M. Section 23 73 00, INDOOR CENTRAL-STATION AIR-HANDLING UNITS: Supply Air

Fans.

N. Section 23 82 00, CONVECTION HEATING and COOLING UNITS.

O. Section 23 82 16, AIR COILS: Duct Mounted Coils.

P. Section 28 31 00, FIRE DETECTION and ALARM: Smoke Detectors.

1.3 QUALITY ASSURANCE

A. Refer to article, QUALITY ASSURANCE, in Section 23 05 11, COMMON WORK

RESULTS FOR HVAC.

B. Fire Safety Code: Comply with NFPA 90A.

C. Duct System Construction and Installation: Referenced SMACNA Standards are the minimum acceptable quality.

D. Duct Sealing, Air Leakage Criteria, and Air Leakage Tests: Ducts shall be sealed as per duct sealing requirements of SMACNA HVAC Air Duct

Leakage Test Manual for duct pressure classes shown on the drawings.

E. Duct accessories exposed to the air stream, such as dampers of all types (except smoke dampers) and access openings, shall be of the same material as the duct or provide at least the same level of corrosion resistance.

1.4 SUBMITTALS

A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT

DATA, and SAMPLES.

B. Manufacturer's Literature and Data:

1. Rectangular ducts:

a. Schedules of duct systems, materials and selected SMACNA construction alternatives for joints, sealing, gage, and reinforcement.

b. Duct liner.

c. Sealants and gaskets.

d. Access doors.

2. Round and flat oval duct construction details:

a. Manufacturer's details for duct fittings.

b. Duct liner.

c. Sealants and gaskets.

d. Access sections.

Iowa City VA Medical Center Relocate Women's Health Clinic & Specialty Clinics

February 09, 2024

23 31 00 - 3

e. Installation instructions.

3. Volume dampers, back draft dampers.

4. Upper hanger attachments.

5. Fire dampers, fire doors, and smoke dampers with installation instructions.

6. Sound attenuators, including pressure drop and acoustic performance.

7. Flexible ducts and clamps, with manufacturer's installation instructions.

8. Flexible connections.

9. Instrument test fittings.

10. Details and design analysis of alternate or optional duct systems.

11. COMMON WORK RESULTS FOR HVAC and STEAM GENERATION.

C. Coordination Drawings: Refer to article, SUBMITTALS, in Section 23 05

11-COMMON WORK RESULTS FOR HVAC AND STEAM GENERATION.

1.5 APPLICABLE PUBLICATIONS

A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.

B. American Society of Civil Engineers (ASCE):

ASCE7-2017..............Minimum Design Loads for Buildings and Other

Structures

C. American Society for Testing and Materials (ASTM):

A167-2009...............Standard Specification for Stainless and

Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip

A653-2019...............Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy coated (Galvannealed) by the Hot-Dip process

A1011-2018..............Standard Specification for Steel, Sheet and

Strip, Hot rolled, Carbon, structural, High-

Strength Low-Alloy, High Strength Low-Alloy with Improved Formability, and Ultra-High

Strength

B209-2014...............Standard Specification for Aluminum and

Aluminum-Alloy Sheet and Plate

Iowa City VA Medical Center Relocate Women's Health Clinic & Specialty Clinics

February 09, 2024

23 31 00 - 4

C1071-2019..............Standard Specification for Fibrous Glass Duct

Lining Insulation (Thermal and Sound Absorbing

Material)

E84-2014................Standard Test Method for Surface Burning

Characteristics of Building Materials

D. National Fire Protection Association (NFPA):

90A-2018................Standard for the Installation of Air

Conditioning and Ventilating Systems

96-2018.................Standard for Ventilation Control and Fire

Protection of Commercial Cooking Operations

E. Sheet Metal and Air Conditioning Contractors National Association

(SMACNA):

3rd Edition–/2006.......HVAC Duct Construction Standards, Metal and

Flexible

2nd Edition-2012........HVAC Air Duct Leakage Test Manual

6th Edition–2016........Fibrous Glass Duct Construction Standards

F. Underwriters Laboratories, Inc. (UL):

181-2013................Factory-Made Air Ducts and Air Connectors

555-2006 ...............Standard for Fire Dampers

555S-2014...............Standard for Smoke Dampers

PART 2 - PRODUCTS

2.1 DUCT MATERIALS AND SEALANTS

A. General: Except for systems specified otherwise, construct ducts, casings, and accessories of galvanized sheet steel, ASTM A653, coating

G90; or, aluminum sheet, ASTM B209, alloy 1100, 3003 or 5052.

B. Specified Corrosion Resistant Systems: Stainless steel sheet, ASTM

A167, Class 302 or 304, Condition A (annealed) Finish No. 4 for exposed ducts and Finish No. 2B for concealed duct or ducts located in mechanical rooms.

C. Joint Sealing: Refer to SMACNA HVAC Duct Construction Standards.

1. Sealant: Elastomeric compound, gun or brush grade, maximum 25 flame spread, and 50 smoke developed (dry state) compounded specifically for sealing ductwork as recommended by the manufacturer. Generally, provide liquid sealant, with or without compatible tape, for low clearance slip joints and heavy, permanently elastic, mastic type

Iowa City VA Medical Center Relocate Women's Health Clinic & Specialty Clinics

February 09, 2024

23 31 00 - 5 where clearances are larger. Oil base caulking and glazing compounds are not acceptable because they do not retain elasticity and bond.

2. Tape: Use only tape specifically designated by the sealant manufacturer and apply only over wet sealant. Pressure sensitive tape shall not be used on bare metal or on dry sealant.

3. Gaskets in Flanged Joints: Soft neoprene.

D. Approved factory-made joints may be used.

2.2 DUCT CONSTRUCTION AND INSTALLATION

A. Regardless of the pressure classifications outlined in the SMACNA

Standards, fabricate and seal the ductwork in accordance with the following pressure classifications:

B. Duct Pressure Classification: (unless otherwise noted on plans):

1. Supply ductwork upstream of terminal units 6” wg.

2. Downstream of terminal units 3” wg.

3. Return, exhaust, and outside air ductwork 3” wg.

C. Seal Class: All ductwork shall receive Class A Seal

D. Duct for Negative Pressure Up to 750 Pa (3-inch W.G.): Provide for exhaust duct between HEPA filters and exhaust fan inlet including systems for Autopsy Suite exhaust.

1. Round Duct: Galvanized steel, spiral lock seam construction with standard slip joints.

2. Rectangular Duct: Galvanized steel, minimum 1.0 mm (20 gage), Pittsburgh lock seam, companion angle joints 32 mm by 3.2 mm (1-1/4 by 1/8 inch) minimum at not more than 2.4 m (8 feet) spacing.

Approved pre-manufactured joints are acceptable in lieu of companion angles.

E. Round and Flat Oval Ducts: Furnish duct and fittings made by the same manufacturer to ensure good fit of slip joints. When submitted and approved in advance, round and flat oval duct, with size converted on the basis of equal pressure drop, may be furnished in lieu of rectangular duct design shown on the drawings.

1. Elbows: Diameters 80 through 200 mm (3 through 8 inches) shall be two sections die stamped, all others shall be gored construction, maximum 18 degree angle, with all seams continuously welded or standing seam. Coat galvanized areas of fittings damaged by welding

Iowa City VA Medical Center Relocate Women's Health Clinic & Specialty Clinics

February 09, 2024

23 31 00 - 6 with corrosion resistant aluminum paint or galvanized repair compound.

2. Provide bell mouth, conical tees or taps, laterals, reducers, and other low loss fittings as shown in SMACNA HVAC Duct Construction

Standards.

3. Ribbed Duct Option: Lighter gage round/oval duct and fittings may be furnished provided certified tests indicating that the rigidity and performance is equivalent to SMACNA standard gage ducts are submitted.

a. Ducts: Manufacturer's published standard gage, G90 coating, spiral lock seam construction with an intermediate standing rib.

b. Fittings: May be manufacturer's standard as shown in published catalogs, fabricated by spot welding and bonding with neoprene base cement or machine formed seam in lieu of continuous welded seams.

4. Provide flat side reinforcement of oval ducts as recommended by the manufacturer and SMACNA HVAC Duct Construction Standard S3.13.

Because of high pressure loss, do not use internal tie-rod reinforcement unless approved by the COR.

F. VA Type A and B Canopy Hoods, Reagent Grade Water Treatment Room and

Battery Charging Room Exhausts: Constructed of 1.3 mm (18 gage) stainless steel.

G. Casings and Plenums: Construct in accordance with SMACNA HVAC Duct

Construction Standards Section 6, including curbs, access doors, pipe penetrations, eliminators and drain pans. Access doors shall be hollow metal, insulated, with latches and door pulls, 500 mm (20 inches) wide by 1200 - 1350 mm (48 - 54 inches) high. Provide view port in the doors where shown. Provide drain for outside air louver plenum. Outside air plenum shall have exterior insulation. Drain piping shall be routed to the nearest floor drain.

H. Volume Dampers: Single blade or opposed blade, multi-louver type as detailed in SMACNA Standards. Refer to SMACNA for Single Blade and

Figure 2.13 for Multi-blade Volume Dampers.

I. Duct Hangers and Supports: Refer to SMACNA Standards Section IV. Avoid use of trapeze hangers for round duct.

Iowa City VA Medical Center Relocate Women's Health Clinic & Specialty Clinics

February 09, 2024

23 31 00 - 7

J. Ductwork in excess of 620 cm2 (96 square inches) shall be protected unless the duct has one dimension less than 150 mm (6 inches) if it passes through the areas listed below. Refer to the Mission Critical

Physical Design Manual for VA Facilities. This applies to the following:

1. Agent cashier spaces

2. Perimeter partitions of caches

3. Perimeter partitions of computer rooms

4. Perimeter of a COOP sites

5. Perimeter partitions of Entrances

6. Security control centers (SCC)

2.3 DUCT LINER (WHERE INDICATED ON DRAWINGS)

A. Duct sizes shown on drawings for lined duct are clear opening inside lining.

B. Fibrous Glass Duct liner is only permitted to be used for return, relief, and general exhaust ducts. Duct liner is not permitted for outside air ducts, supply air ducts or any other positive pressure ductwork (provide exterior insulation only). However, flexible, closed-cell elastomeric acoustic duct liner is allowed for supply air ducts, where shown on drawings.

C. Rectangular Duct or Casing Liner (return, exhaust, and general exhaust ducts only): ASTM C1071, Type I (flexible), or Type II (board), 25 mm

(one inch) minimum thickness, applied with mechanical fasteners and 100 percent coverage of adhesive in conformance with SMACNA, Duct Liner

Application Standard.

D. Rectangular Duct or Casing Liner (supply air ducts): Closed-Cell

Elastomeric Acoustic Duct Liner, ASTM C177, C518, k = 0.040 (0.28) at

24 degrees C (75 degrees F), flame spread not over 25, smoke developed not over 50, for temperatures from minus 4 degrees C (40 degrees F) to

93 degrees C (200 degrees F). No jacket required.

E. Round and Oval Duct Liner: Factory fabricated double-walled with 25 mm

(one inch) thick sound insulation and inner perforated galvanized metal liner. Construction shall comply with flame and smoke rating required by NFPA 90A. Metal liner shall be 1.0 to 0.60 mm (20 to 24 gage) having perforations not exceeding 2.4 mm (3/32 inch) diameter and approximately 22 percent free area. Metal liner for fittings need not

Iowa City VA Medical Center Relocate Women's Health Clinic & Specialty Clinics

February 09, 2024

23 31 00 - 8 be perforated. Assemblies shall be complete with continuous sheet Mylar liner, 2 mil thickness, between the perforated liner and the insulation to prevent erosion of the insulation. Provide liner couplings/spacer for metal liner. At the end of insulated sections, provide insulation end fittings to reduce outer shell to liner size. Provide liner spacing/concentricity leaving airway unobstructed.

2.4 DUCT ACCESS DOORS, PANELS AND SECTIONS

A. Provide access doors, sized and located for maintenance work, upstream, in the following locations:

1. Each duct mounted coil and humidifier.

2. Each fire damper (for link service), smoke damper and automatic control damper.

3. Each duct mounted smoke detector.

4. For cleaning operating room supply air duct and kitchen hood exhaust duct, locate access doors at 6 m (20 feet) intervals and at each change in duct direction.

B. Openings shall be as large as feasible in small ducts, 300 mm by 300 mm

(12 inch by 12 inch) minimum where possible. Access sections in insulated ducts shall be double-wall, insulated. Transparent shatterproof covers are preferred for uninsulated ducts.

1. For rectangular ducts: Refer to SMACNA HVAC Duct Construction

Standards (Figure 2-12).

2. For round and flat oval duct: Refer to SMACNA HVAC duct Construction

Standards (Figure 2-11).

2.5 FIRE DAMPERS

A. Galvanized steel, interlocking blade type, UL listing and label, 1-1/2-hour rating, 70 degrees C (160 degrees F) fusible line, 100 percent free opening with no part of the blade stack or damper frame in the air stream.

B. Fire dampers in wet air exhaust shall be of stainless-steel construction, all others may be galvanized steel.

C. Minimum requirements for fire dampers:

1. The damper frame may be of design and length as to function as the mounting sleeve, thus eliminating the need for a separate sleeve, as allowed by UL 555. Otherwise provide sleeves and mounting angles, Iowa City VA Medical Center Relocate Women's Health Clinic & Specialty Clinics

February 09, 2024

23 31 00 - 9 minimum 1.9 mm (14 gage), required to provide installation equivalent to the damper manufacturer's UL test installation.

2. Submit manufacturer's installation instructions conforming to UL rating test.

2.6 SMOKE DAMPERS

A. Maximum air velocity, through free area of open damper, and pressure loss: Low pressure and medium pressure duct (supply, return, exhaust, outside air): 450 m/min (1500 fpm). Maximum static pressure loss: 32 Pa

(0.13 inch W.G.).

B. Maximum air leakage, closed damper: 0.32 cubic meters /min/square meter

(4.0 CFM per square foot) at 750 Pa (3-inch W.G.) differential pressure.

C. Minimum requirements for dampers:

1. Shall comply with requirements of Table 6-1 of UL 555S, except for the Fire Endurance and Hose Stream Test.

2. Frame: Galvanized steel channel with side, top and bottom stops or seals.

3. Blades: Galvanized steel, parallel type preferably, 300 mm (12 inch) maximum width, edges sealed with neoprene, rubber or felt, if required to meet minimum leakage. Airfoil (streamlined) type for minimum noise generation and pressure drop are preferred for duct mounted dampers.

4. Shafts: Galvanized steel.

5. Bearings: Nylon, bronze sleeve, or ball type.

6. Hardware: Zinc plated.

7. Operation: Automatic open/close. No smoke damper that requires manual reset or link replacement after actuation is acceptable. See drawings for required control operation.

D. Motor operator (actuator): Provide pneumatic or electric as required by the automatic control system, externally mounted on stand-offs to allow complete insulation coverage.

2.7 COMBINATION FIRE AND SMOKE DAMPERS

A. Combination fire and smoke dampers: Multi-blade type units meeting all requirements of both fire dampers and smoke dampers shall be used where shown and may be used at the Contractor's option where applicable.

Iowa City VA Medical Center Relocate Women's Health Clinic & Specialty Clinics

February 09, 2024

23 31 00 - 10

2.8 FIRE DOORS

A. Galvanized steel, interlocking blade type, UL listing and label, 71 degrees C (160 degrees F) fusible link, 3-hour rating and approved for openings in Class A fire walls with rating up to 4 hours, 100 percent free opening with no part of the blade stack or damper frame in the air stream.

2.9 FLEXIBLE AIR DUCT

A. General: Factory fabricated, complying with NFPA 90A for connectors not passing through floors of buildings. Flexible ducts shall not penetrate any fire or smoke barrier which is required to have a fire resistance rating of one hour or more. Flexible duct length shall not exceed 1.5 m

(5 feet). Provide insulated acoustical air duct connectors in supply air duct systems and elsewhere as shown.

B. Flexible ducts shall be listed by Underwriters Laboratories, Inc., complying with UL 181. Ducts larger than 200 mm (8 inches) in diameter shall be Class 1. Ducts 200 mm (8 inches) in diameter and smaller may be Class 1 or Class 2.

C. Insulated Flexible Air Duct: Factory made including mineral fiber insulation with maximum C factor of 0.25 at 24 degrees C (75 degrees F) mean temperature, encased with a low permeability moisture barrier outer jacket, having a puncture resistance of not less than 50 Beach

Units. Acoustic insertion loss shall not be less than 3 dB per 300 mm

(foot) of straight duct, at 500 Hz, based on 150 mm (6 inch) duct, of

750 m/min (2500 fpm).

D. Application Criteria:

1. Temperature range: -18 to 93 degrees C (0 to 200 degrees F) internal.

2. Maximum working velocity: 1200 m/min (4000 feet per minute).

3. Minimum working pressure, inches of water gage: 2500 Pa (10 inches) positive, 500 Pa (2 inches) negative.

E. Duct Clamps: 100 percent nylon strap, 80 kg (175 pounds) minimum loop tensile strength manufactured for this purpose or stainless-steel strap with cadmium plated worm gear tightening device. Apply clamps with sealant and as approved for UL 181, Class 1 installation.

Iowa City VA Medical Center Relocate Women's Health Clinic & Specialty Clinics

February 09, 2024

23 31 00 - 11

2.10 FLEXIBLE DUCT CONNECTIONS

A. Where duct connections are made to fans, air terminal units, and air handling units, install a non-combustible flexible connection of 822 g

(29 ounce) neoprene coated fiberglass fabric approximately 150 mm (6 inches) wide. For connections exposed to sun and weather provide hypalon coating in lieu of neoprene. Burning characteristics shall conform to NFPA 90A. Securely fasten flexible connections to round ducts with stainless steel or zinc-coated iron draw bands with worm gear fastener. For rectangular connections, crimp fabric to sheet metal and fasten sheet metal to ducts by screws 50 mm (2 inches) on center.

Fabric shall not be stressed other than by air pressure. Allow at least

25 mm (one inch) slack to ensure that no vibration is transmitted.

2.11 SOUND ATTENUATING UNITS

A. Casing, not less than 1.0 mm (20 gage) galvanized sheet steel, or 1.3 mm (18 gage) aluminum fitted with suitable flanges to make clean airtight connections to ductwork. Sound-absorbent material faced with glass fiber cloth and covered with not less than 0,6 mm (24 gage) or heavier galvanized perforated sheet steel, or 0.85 mm (22 gage) or heavier perforated aluminum. Perforations shall not exceed 4 mm (5/32 inch) diameter, approximately 25 percent free area. Sound absorbent material shall be long glass fiber acoustic blanket meeting requirements of NFPA 90A.

B. Entire unit shall be completely air tight and free of vibration and buckling at internal static pressures up to 2000 Pa (8 inches W.G.) at operating velocities.

C. Pressure drop through each unit: Not to exceed indicated value at design air quantities indicated.

D. Submit complete independent laboratory test data showing pressure drop and acoustical performance.

E. Cap open ends of attenuators at factory with plastic, heavy duty paper, cardboard, or other appropriate material to prevent entrance of dirt, water, or any other foreign matter to inside of attenuator. Caps shall not be removed until attenuator is installed in duct system.

2.12 PREFABRICATED ROOF CURBS

A. Galvanized steel or extruded aluminum 300 mm (12 inches) above finish roof service, continuous welded corner seams, treated wood nailer, 40

Iowa City VA Medical Center Relocate Women's Health Clinic & Specialty Clinics

February 09, 2024

23 31 00 - 12 mm (1-1/2 inch) thick, 48 kg/cubic meter (3 pound/cubic feet) density rigid mineral fiberboard insulation with metal liner, built-in can’t strip (except for gypsum or tectum decks). For surface insulated roof deck, provide raised cant strip (recessed mounting flange) to start at the upper surface of the insulation. Curbs shall be constructed for pitched roof or ridge mounting as required to keep top of curb level.

2.13 FIRESTOPPING MATERIAL

A. Refer to Section 07 84 00, FIRESTOPPING.

2.14 SEISMIC RESTRAINT FOR DUCTWORK (NOT USED)

2.15 DUCT MOUNTED THERMOMETER (AIR)

A. Stem Type Thermometers: ASTM E1, 7-inch scale, red appearing mercury, lens front tube, cast aluminum case with enamel finish and clear glass or polycarbonate window, brass stem, 2 percent of scale accuracy to

ASTM E77 scale calibrated in degrees Fahrenheit.

B. Thermometer Supports:

1. Socket: Brass separable sockets for thermometer stems with or without extensions as required, and with cap and chain.

2. Flange: 3 inch outside diameter reversible flange, designed to fasten to sheet metal air ducts, with brass perforated stem.

2.16 DUCT MOUNTED TEMPERATURE SENSOR (AIR)

A. Refer to Section 23 09 23, DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC.

2.17 INSTRUMENT TEST FITTINGS

A. Manufactured type with a minimum 50 mm (two inch) length for insulated duct, and a minimum 25 mm (one inch) length for duct not insulated.

Test hole shall have a flat gasket for rectangular ducts and a concave gasket for round ducts at the base, and a screw cap to prevent air leakage.

B. Provide instrument test holes at each duct or casing mounted temperature sensor or transmitter, and at entering and leaving side of each heating coil, cooling coil, and heat recovery unit.

2.18 AIR FLOW CONTROL VALVES (AFCV) (NOT USED)

2.19 LEAD COVERED DUCT

A. Sheet Lead: 3.1 mm (1/8 inch) thick, securely installed, free of waves, lumps, or wrinkles and with as few joints as possible.

B. Joints shall be made to obtain X-ray absorption equivalent to adjacent sheet lead and finished smooth and neat.

Iowa City VA Medical Center Relocate Women's Health Clinic & Specialty Clinics

February 09, 2024

23 31 00 - 13

2.20 ELECTROSTATIC SHIELDING

A. At the point of penetration of shielded rooms ducts shall be made electrically discontinuous by means of a flexible, nonconductive connection outside shielded room.

B. Metallic duct portion inside shielded room shall be electrically bonded to shielding.

2.21 DUCT MOUNTED ELECTRODE STEAM HUMIDIFIERS

A. Fabrication requirements:

1. Enclosure shall be constructed with:

a. 22-gauge galvannealed cold rolled steel back/bottom panel.

b. 20-gauge painted galvannealed cold rolled steel side/top panel.

c. 22-gauge galvannealed cold rolled steel doors; coordinated, painted, and suitable for finished spaces.

d. Separate compartments for the steam cylinder and for electrical components. Enclosure shall be designed and secured to prevent accidental contact with electrical components.

2. Enclosure shall have LED indicator lights that shall be visible from the outside of the cabinet.

3. Enclosure shall have two removable doors, one for the cylinder side and one for the electrical side. Removable doors shall allow full front access for installation and service.

4. Enclosure shall have pre-punched mounting holes for ease of wall mounting and leveling.

5. Steam outlet on top of cylinder shall be configured to connect to a dispersion tube assembly in a duct via hose or tubing.

6. Plastic disposable steam cylinder shall:

a. Have welded seams to ensure water tightness.

b. Provide full output for entire cylinder life.

c. Have integral high water sensor probe to prevent overfilling.

7. Steam cylinder enclosure compartment shall have reusable cylinder plugs to ensure safe, secure connection of primary voltage leads to the steam cylinder for life of unit.

8. Drain: An electric drain valve shall be cabinet-mounted to allow cylinder to automatically drain periodically and at the end of a humidification season. The cylinder shall automatically and completely drain if it does not receive a humidity demand signal for

Iowa City VA Medical Center Relocate Women's Health Clinic & Specialty Clinics

February 09, 2024

23 31 00 - 14

72 hours, eliminating potential contaminant buildup in the cylinder, and to extend cylinder life during long periods of inactivity. After draining at the end of a humidification season, the unit shall automatically reset and start normal operation when it receives a humidity demand signal. Integral drain cup shall prevent water leakage.

B. Water requirements: The humidifier shall be capable of generating steam from potable unsoftened or softened water. Water conductivity operating range shall be 350 to 1250 µS/cm.

C. Dispersion Tube:

1. Dispersion tube shall be fabricated of stainless steel tubing with uniformly spaced tubelets for steam dispersion. Each tubelet shall be made of a thermal-resin material designed for high steam temperatures. Each tubelet shall extend through the wall and to the center of dispersion tube and incorporate a properly sized calibrated orifice.

2. Dispersion tube shall be pitched 2"/ft (15%) toward humidifier to allow condensate to return to humidifier.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Comply with provisions of Section 23 05 11, COMMON WORK RESULTS FOR

HVAC, particularly regarding coordination with other trades and work in existing buildings.

B. Fabricate and install ductwork and accessories in accordance with referenced SMACNA Standards:

1. Drawings show the general layout of ductwork and accessories but do not show all required fittings and offsets that may be necessary to connect ducts to equipment, boxes, diffusers, grilles, etc., and to coordinate with other trades. Fabricate ductwork based on field measurements. Provide all necessary fittings and offsets at no additional cost to the government. Coordinate with other trades for space available and relative location of HVAC equipment and accessories on ceiling grid. Duct sizes on the drawings are inside dimensions which shall be altered by Contractor to other dimensions with the same air handling characteristics where necessary to avoid interferences and clearance difficulties.

Iowa City VA Medical Center Relocate Women's Health Clinic & Specialty Clinics

February 09, 2024

23 31 00 - 15

2. Provide duct transitions, offsets and connections to dampers, coils, and other equipment in accordance with SMACNA Standards. Provide streamliner when an obstruction cannot be avoided and must be taken in by a duct. Repair galvanized areas with galvanizing repair compound.

3. Provide bolted construction and tie-rod reinforcement in accordance with SMACNA Standards.

4. Construct casings, eliminators, and pipe penetrations in accordance with SMACNA Standards, Chapter 6. Design casing access doors to swing against air pressure so that pressure helps to maintain a tight seal.

C. Install duct hangers and supports in accordance with SMACNA Standards.

D. Install fire dampers, smoke dampers and combination fire/smoke dampers in accordance with the manufacturer's instructions to conform to the installation used for the rating test. Install fire dampers, smoke dampers and combination fire/smoke dampers at locations indicated and where ducts penetrate fire rated and/or smoke rated walls, shafts and where required by the COR. Install with required perimeter mounting angles, sleeves, breakaway duct connections, corrosion resistant springs, bearings, bushings, and hinges per UL and NFPA. Demonstrate re-setting of fire dampers and operation of smoke dampers to the COR.

E. Seal openings around duct penetrations of floors and fire rated partitions with fire stop material as required by NFPA 90A.

F. Flexible duct installation: Refer to SMACNA Standards, Chapter 3. Ducts shall be continuous, single pieces not over 1.5 m (5 feet) long (NFPA

90A), as straight and short as feasible, adequately supported.

Centerline radius of bends shall be not less than two duct diameters.

Make connections with clamps as recommended by SMACNA. Clamp per SMACNA with one clamp on the core duct and one on the insulation jacket.

Flexible ducts shall not penetrate floors, or any chase or partition designated as a fire or smoke barrier, including corridor partitions fire rated one hour or two hours. Support ducts SMACNA Standards.

G. Where diffusers, registers and grilles cannot be installed to avoid seeing inside the duct, paint the inside of the duct with flat black paint to reduce visibility.

H. Control Damper Installation:

Iowa City VA Medical Center Relocate Women's Health Clinic & Specialty Clinics

February 09, 2024

23 31 00 - 16

1. Provide necessary blank-off plates required to install dampers that are smaller than duct size. Provide necessary transitions required to install dampers larger than duct size.

2. Assemble multiple sections dampers with required interconnecting linkage and extend required number of shafts through duct for external mounting of damper motors.

3. Provide necessary sheet metal baffle plates to eliminate stratification and provide air volumes specified. Locate baffles by experimentation, and affix and seal permanently in place, only after stratification problem has been eliminated.

4. Install all damper control/adjustment devices on stand-offs to allow complete coverage of insulation.

I. Air Flow Measuring Devices (AFMD): Install units with minimum straight run distances, upstream and downstream as recommended by the manufacturer.

J. Low Pressure Duct Liner: Install in accordance with SMACNA, Duct Liner

Application Standard.

K. Electrode Steam Humidifiers: Install per manufacturer’s written instructions.

L. Protection and Cleaning: Adequately protect equipment and materials against physical damage. Place equipment in first class operating condition or return to source of supply for repair or replacement, as determined by COR. Protect equipment and ducts during construction against entry of foreign matter to the inside and clean both inside and outside before operation and painting. When new ducts are connected to existing ductwork, clean both new and existing ductwork by mopping and vacuum cleaning inside and outside before operation.

3.2 DUCT LEAKAGE TESTS AND REPAIR

A. Ductwork leakage testing shall be performed by the Testing and

Balancing Contractor directly contracted by the General Contractor and independent of the Sheet Metal Contractor.

B. Ductwork leakage testing shall be performed for the entire air distribution system (including all supply, return, exhaust, and relief ductwork), section by section, including fans, coils, and filter sections. Based upon satisfactory initial duct leakage test results, the scope of the testing may be reduced by the COR on ductwork

Iowa City VA Medical Center Relocate Women's Health Clinic & Specialty Clinics

February 09, 2024

23 31 00 - 17 constructed to the 500 Pa (2" WG) duct pressure classification. In no case shall the leakage testing of ductwork constructed above the 500 Pa

(2" WG) duct pressure classification or ductwork located in shafts or other inaccessible areas be eliminated.

C. Test procedure, apparatus and report shall conform to SMACNA Leakage

Test manual. The maximum leakage rate allowed is 4 percent of the design air flow rate.

D. All ductwork shall be leak tested first before enclosed in a shaft or covered in other inaccessible areas.

E. All tests shall be performed in the presence of the COR and the Test and Balance agency. The Test and Balance agency shall measure and record duct leakage and report to the COR and identify leakage source with excessive leakage.

F. If any portion of the duct system tested fails to meet the permissible leakage level, the Contractor shall rectify sealing of ductwork to bring it into compliance and shall retest it until acceptable leakage is demonstrated to the COR.

G. All tests and necessary repairs shall be completed prior to insulation or concealment of ductwork.

H. Make sure all openings used for testing flow and temperatures by TAB

Contractor are sealed properly.

3.3 DUCTWORK EXPOSED TO WIND VELOCITY

A. Provide additional support and bracing to all exposed ductwork installed on the roof or outside the building to withstand wind velocity of 145 km/h (90 mph).

3.4 TESTING, ADJUSTING AND BALANCING (TAB)

A. Refer to Section 23 05 93, TESTING, ADJUSTING, and BALANCING FOR HVAC.

3.5 OPERATING AND PERFORMANCE TESTS

A. Refer to Section 23 05 11, COMMON WORK RESULTS FOR HVAC.

- - - E N D - - -