Attachment 5 HEFP SEP Design Alert 7.pdf

PDF 767 KB Posted

Attached to
C1BG--EHRM Infrastructure Upgrades – Salisbury, NC 659-22-700 (VA-22-00010153) Design
Solicitation number
36C77622R0027
Issued by

About this file

This document is a pre-solicitation notice from the Department of Veterans Affairs seeking standard form SF 330 qualification packages from architecture and engineering firms for the design of EHRM infrastructure upgrades at the VA Medical Center in Salisbury, North Carolina. The project involves upgrades to network infrastructure including fiber optics, structured cabling, electrical distribution, UPS systems, building management/automation systems, HVAC, telecom room renovations, data center reconfiguration, electronic and physical security, and associated systems with a construction budget between $20-50 million. Responses are due February 21, 2022. Firms will be evaluated on their experience with IT and network projects, construction scheduling, infection control, and familiarity with VA design standards. The selected firm must complete construction documents within 365 days of award. This is a 100% SDVOSB set-aside requiring a minimum of 50% SDVOSB participation.

View the file

Other files

File Type Posted
Attachment 2 -Entire site map Salisbury VA.pdf PDF
Attachment 1 - 659-22-700 Questions and Answers.pdf PDF
Attachment 4 - STS 3.1.pdf PDF
Attachment 3 - Salisbury VAMC Design and Construction Manual.pdf PDF
36C77622R0027_2.docx DOCX document
36C77622R0027_1.docx DOCX document
Attachment 09 - Station Floor Plans_10-13-2021.zip ZIP file
Attachment 01 - VHA Required Div 01 Spec Sections - Copy.docx DOCX document
Attachment 13 - 659-22-700_SOW EHRM Infrastructure Upgrades-Salisbury_V5_ 11-16-2021.docx DOCX document
Attachment 07 - Seasonal Influenza with Vaccines.pdf PDF
Attachment 14 - Wage Determinations SCA 2015 4423 10.20.2021.gov.pdf PDF
36C77622R0027.docx DOCX document
Attachment 06 - PG 18-15 AE Submission Reqts Vol C - Copy.doc DOC document
Attachment 02 - VA OEHRM Site Infrastructure Reqs 1.9 - Copy.pdf PDF
Attachment 12 - Training and Admin Support Planning Guide.pdf PDF
Attachment 04 - Sensitive Infrastructure Data Classification Memo - Copy.pdf PDF
Attachment 15 - Past Performance Questionnaire.docx DOCX document
Attachment 11 - VHA Sup Contract Reqs for Combatting COVID-19 Updated 12-14-2021.docx DOCX document
Attachment 10 - SBYVAMC-Site Plan.pdf PDF
Attachment 05 - 01 32 16.01 EHRM Arch and Eng CPM Schedule Spec - Copy.docx DOCX document
Attachment 03 - HEFP SEP Design Alert 1-6.zip ZIP file
Attachment 08 - VHA Directive 1061 .pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HEFP/10NA5G/10DEC2021

HEFP SEP (SOCAMES 6) Design Alert 7

There are specific circumstances when construction of a conditioned Telecommunication Room (TR) is infeasible or impractical in non-clinical buildings such as engineering/maintenance buildings, warehouses, temporary modular trailers and quarters that were converted to administrative space. In cases where existing space, structural or other constraints do not practically allow for construction of a TR, the use of a Telecommunication Enclosure (TE) is appropriate.

HEFP SEP has seen a considerable increase in variance requests to deviate from the 80 square foot TR space standard as defined in the Infrastructure Standards for Telecommunications Spaces (ISTS). The variance requests specifically address low use, non-clinical TRs where expansion or new construction are not viable solutions due to space and/or environmental constraints.

The site should make every reasonable effort to comply with the current ISTS standard for all TRs in non-clinical buildings. However, where space and/or environmental constraints cannot support a new TR, both a Standard TE and Non-Standard TE are available for consideration under the conditions described below.

A Variance is NOT REQUIRED for a STANDARD TE (fan-cooled) if all the following criteria are met:

1. Space Classification: The space is one of the following:

a) Parking structures

b) Technical spaces such as warehouses, kitchens, laundries, mechanical/electrical plant buildings, chiller or boiler plants, garages, and paint shops

c) Historical quarters converted to administrative use

d) Buildings with no VA staffing presence and no requirements for connectivity to the VA

LAN or guest Wi-Fi

e) Temporary modular trailers. Temporary buildings and trailers must be validated as temporary, with a planned removal date and no history of previous deferred or cancelled removal plans.

Problem

Background

Solution

HEFP SEP (SOCAMES 6) Design Alert 7

2. Usage: Usage is limited to a maximum of 96 Work Area Outlets (WAOs). Each data jack in a workspace telecommunications outlet, wired back to the patch panels in the TE, is considered a WAO for these purposes. Where 1-48 WAOs are planned, a 12RU (half-height) standardized TE is used. Where 49-96 WAOs are planned, a 26RU (full height) standardized TE is used.

3. Environment: Spaces meet the environmental envelope conditions for a TR, as described in Figure 19 and Table 24 of the Infrastructure Standard for Telecommunications Spaces.

Ambient air conditions in the space are between 41°F-95°F dry bulb, 8-80% RH, and dew point less than 82.4°F, measured at the intake point of the TE.

Standard TE’s (or equal) are provided below:

12RU - https://www.chatsworth.com/en-us/products/cabinets-enclosures-containment/wall-mount-cabinets/swing-frame/cube-it-wall-mount-cabinet/11900-e24

26RU - https://www.chatsworth.com/en-us/products/cabinets-enclosures-containment/wall-mount-cabinets/swing-frame/cube-it-wall-mount-cabinet/12419-e48

If all the above criteria are met, except for paragraph 3. Environment, a NON-STANDARD (Environmentally Conditioned) TE may be considered, and a Variance is REQUIRED. To request a NON-STANDARD TE Variance:

1. Determine if another space in the building meets the environmental and physical security criteria for the installation of a standardized TE. If so, a standardized TE shall be relocated to the environmentally appropriate space in the building.

2. If no other spaces in the building meet the environmental and physical security criteria, submit a Variance request to DCIE for installation of a non-standard (environmentally conditioned) TE. Select which non-standard TE is proposed for use and submit the installation plan, showing the location on an as-built drawing.

3. A sampling of vendors that may meet the intent of a non-standard (environmentally conditioned) TE solution include:

a. Liebert (Vertiv) MCR Mini Computer Room Enclosure https://www.vertiv.com/en-us/products-catalog/facilities-enclosures-and-racks/integrated-solutions/mcr---mini-computer-room-enclosure/

b. Hoffman Spectracool – A side-mount A/C unit capable of attaching to many common manufacturer’s cabinets (comes in a variety of sizes) https://hoffman.nvent.com/sites/g/files/hdkjer316/files/acquiadam/2021- 05/Spec-00728.pdf?asset_type=Spec

HEFP SEP (SOCAMES 6) Design Alert 7

c. EIC Solutions Protector Series, Wall-Mount Enclosure S723616 Wall-mount AC Enclosure - 72"H x 36"W x 16"D with EIC Solutions CB Series, Compressor-Based, Side-Mount, Hazardous Location Enclosure CBIQ6000V16XP2 - 6,000 BTU Hazardous Location Air Conditioner https://www.eicsolutions.com/protector-series-air-conditioned-electronic-enclosures/ and https://www.eicsolutions.com/product/cbiq6000v16xp2/

Variance request information is in the Infrastructure Standard for Telecommunication Spaces (ISTS) standard, Section 1.3.1 and Appendix A.

Once approved, the designer of record MUST incorporate the approved TE into the design documents.