S02_Drawings_Upgrd NFS Bldg 2_HS.pdf
PDF 30 MB Posted
- Solicitation number
- 36C26325B0010
About this file
This document is a drawing file (S02_Drawings_Upgrd NFS Bldg 2_HS.pdf) for a U.S. Department of Veterans Affairs (VA) project at the Black Hills Health Care System in Hot Springs, South Dakota. The architectural drawing includes technical symbols, legends, and design specifications for upgrading the Nutrition and Food Service (NFS) building, specifically Building 2.
The related federal contract opportunity (Solicitation Number: 36C26325B0010) is a pre-solicitation for a 100% Service-Disabled Veteran Owned Small Business (SDVOSB) set-aside construction project. The project involves renovating the existing kitchen and serving area, with upgrades to finishes, HVAC, plumbing, and electrical systems. The kitchen will be designed to serve three meals daily for 100 residents, with a planned construction period of 180 calendar days. The Invitation for Bid (IFB) is scheduled to be issued on or about April 2, 2025, with an award expected within 60 calendar days of the bid opening. The project's estimated value falls between $2-5 million, under NAICS code 236220, with a small business size standard of $45,000,000.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26325B0010 0002_IFB CANCELLATION.pdf | ||
| MS30_MFR_36C26325B0010 0001.pdf | ||
| S02_Specifications_Upgrade NFS Bldg 2_HS.pdf | ||
| S02_Wage Det_1.3.25_568A4-22-205.pdf | ||
| 36C26325B0010_1.pdf | ||
| 36C26325B0010.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SYMBOLS LEGEND
RIGID INSULATION
WOOD ROUGH (CONTINUOUS)
WOOD ROUGH (SPACED)
EARTH
CONCRETE
BLOCK WALL/VENEER
GYPSUM BOARD
PLYWOOD
BATT INSULATION
NEW CONSTRUCTION
EXISTING CONSTRUCTION TO
BE REMOVED
DIMENSION LINE
BREAK LINE
DETAIL INDICATOR
X
X-XX
DETAIL INDICATOR
X
X-XX
X
WALL SECTION
INDICATOR
X
X-XX
X
X-XX
ELEVATION
INDICATOR, EXTERIOR
ELEVATION INDICATOR
CENTER LINE
ELEVATION INDICATOR,
INTERIOR,X-XX
X
X-XX
X
X
X
X
NORTH ARROW
CG
CORNER GUARD
FEC FIRE EXTINGUISHER CABINET
XX KEYNOTE
A GRID LINES
XXX
ROOM
ROOM NAME AND NUMBER
XX
FURNITURE, FIXTURE OR EQUIPMENT,
AND FINISHES INDICATOR
XXX
DOOR OPENING/BORROWED
LIGHT IDENTIFIER
XX DRAWING BLOCK
TITLE, TYPICAL
DRAWING TITLE
XX=XX
XX INTERIOR PARTITION TYPES
NORTH
X
X-XX
BUILDING SECTION
INDICATOR
X
X-XX
DETAIL INDICATOR
X-XX
MAPS
VA BLACK HILLS HEALTH CARE SYSTEM
OFFICE OF CONSTRUCTION AND FACILITIES MANAGEMENT
HOT SPRINGS
500 N 5TH ST
HOT SPRINGS, SD 57747NORTH
ENGINEERING
PROJECT
LOCATION
VICINITY MAP
LOCATION MAP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD
A/E:
STAMPCONSULTANTS
321 4 5 6 7 8 9 10 o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t
VA #
MECHANICAL / ELECTRICAL:
WEST PLAINS ENGINEERING, INC.
1750 RAND RD
RAPID CITY, SD 57702
Phone: 605-348-7455
STUCTURAL:
ALBERTSON ENGINEERING INC.
3202 W MAIN ST SUITE C
RAPID CITY, SD 57702
Phone: 605-343-9606
FOOD SERVICE:
HC DESIGN
614 FERGUSON AVE STE 11
BOZEMAN, MT 59718
Phone: 406-522-59719
C
S G
A R e v it L o c a l\
V A
H o t S p ri n g s U p g ra d e
N F
S B ld g d a rr in tJ
Y L .r v t
/1
/2
:4
:4
P
M
GI000
COVER SHEET
Stone Group Architects
600 E 7th Street
Sioux Falls, SD 57103
605-271-1144
UPGRADE NUTRITION AND FOOD
SERVICE DESIGN
Hot Springs, SD
6-13-2023 TRS DT / GV
PERMIT / BID SET
SGA #211916
VA #568A4-22-205
UPGRADE NUTRITION AND FOOD
SERVICE DESIGN
U.S. DEPARTMENT OF
VETERANS AFFAIRS
500 N 5TH ST, HOT SPRINGS, SD 57747
6-13-2023 PERMIT / BID SET
568A4-22-205
ABBREVIATIONS
SYMBOLS
# POUND OR NUMBER
& AND
< ANGLE
<< DOUBLE ANGLE
@ AT
d PENNEY
Ø ROUND OR DIAMETER
A
A/E ARCHITECT/ENGINEER
AB ANCHOR BOLT
ABV ABOVE
AC ASPHALTIC CONCRETE/AIR CONDITIONER
ACC ACCESSIBLE
ACM ALUMINUM COMPOSITE MATERIAL
ACOUS ACOUSTICAL
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN
ADA AMERICANS WITH DISABILITIES ACT
ADD ADDENDUM
ADH ADHESIVE
ADJ ADJUSTABLE, ADJACENT, ADJOINING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
ALT ALTERNATIVE
ALUM ALUMINUM
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APC ACOUSTICAL PANEL CEILING
APPROX APPROXIMATE
ARCH ARCHITECT (URAL)
ASI ARCHITECT'S SUPPLEMENTAL INSTRUCTIONS
B
BD BOARD
BEV BEVELED
BFF BELOW FINISH FLOOR
BL BRICK LEDGE
BLDG BUILDING
BLKG BLOCK (ING)
BM BEAM
BO BOTTOM OF
BOC BOTTOM OF CONCRETE
BOF BOTTOM OF FOOTING
BOT BOTTOM
BRG BEARING
BRK BRICK
BRKT BRACKET
BSMT BASEMENT
BTWN BETWEEN
BUR BUILT UP ROOFING
C
C CHANNEL/CELSIUS
CAB CABINET
CB CERAMIC BASE
CCW COUNTER CLOCKWISE
CD CONSTRUCTION DOCUMENTS
ABBREVIATIONS
CEM CEMENT
CF CUBIC FEET OR FOOT
CG CORNER GUARD
CH CHANNEL
CIPC CAST-IN-PLACE CONCRETE
CJ CONTROL/CONSTRUCTION JOINT
CL CENTER LINE
CLKG CAULKING
CLO CLEAR, CLEARANCE
CMU CONCRETE MASONRY UNIT
CO CHANGE ORDER/CLEANOUT
COL COLUMN
COMB COMBINATION
COMP COMPOSITE/COMPOSITION
CONC CONCRETE
CONN CONNECT (ION)
CONST CONSTRUCTION
CONT CONTINUOUS, CONTINUE
CONTR CONTRACT (OR)
COORD COORDINATE
CORR CORRUGATED/CORRIDOR
CPPT CARPET TILE
CPT CARPET
CSMT CASEMENT
CT CERAMIC TILE
CTB CARPET TILE BASE
CTR CENTER
D
D DEPTH
DBL DOUBLE
DEMO DEMOLITION, DEMOLISH
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DISP DISPENSER
DN DOWN
DR DOOR
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING (S)
DWR DRAWER
DWTR DUMBWAITER
E
(E) EXISTING
E EAST
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELVE ELEVATOR
EMER EMERGENCY
ENGR ENGINEER
ENL ENLARGED
ABBREVIATIONS
EOP EDGE OF PAVEMENT
EPDM ETHYLENE PROPYLENE DIENE TERPOLYMER
MEMBRANE
EPS EXPANDED POLYSTYRENE BOARD
EPT EPOXY PAINT
EQ EQUAL
EQUIP EQUIPMENT
ES EACH SIDE
EST ESTIMATE
ETC ETCETERA
ETR EXISTING TO REMAIN
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXC EXCAVATE/EXCAVATION
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION/EXPOSED
EXT EXTERIOR
F
FA FIRE ALARM
FAB FABRICATE/FABRICATION
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISHED FLOOR
FFE FINISHED FLOOR ELEVATION
FIN FINISH (ED)
FLR FLOOR (ING)
FLUOR FLUORESCENT
FO FACE OF
FOC FACE OF CONCRETE
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUD
FR FIRE RESISTANT/FRAME
FRP FIBERGLASS REINFORCED PANEL
FS FLOOR SINK
FT FOOR, FEET/FIRE TREATED
FTG FOOTING
FURN FURNISH
FUT FUTURE
G
GA GAGE, GAUGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GI GALVANIZED IRON
GL GLASS
GLU LAM GLUE LAMINATED (BEAM)
GWB GYPSUM WALL BOARD
GYP BD GYPSUM
H
HB HOSE BIB
HC HANDICAP / HOLLOW CORE
ABBREVIATIONS
HD HEAVY DUTY
HDBD HARDBOARD
HDR HEADER
HM HOLLOW METAL
HORZ HORIZONTAL
HR HOUR
HT HEIGHT
HVAC HEATING, VENTILATION, AIRCONDITIONING
I
IBC INTERNATIONAL BUILDING CODE
ICC INTERNATIONAL CODE COUNCIL
ID INSIDE DIAMETER/DIMENSION
IFC INTERNATIONAL FIRE CODE
IN INCH (ES)
INCL INCLUDE (D), INCLUDING
INFO INFORMATION
INSP INSPECTION
INSTR INSTRUCTION (S)
INSUL INSULATE (D), INSULATION
INT INTERIOR
J
JAN JANITOR
JST JOIST
JT JOINT
K
KCJ KEYED CONSTRUCTION JOINT
KO KNOCK OUT
L
L LENGHT / ANGLE
LAB LABORATORY
LAM LAMINATE (D)
LAV LAVATORY
LB POUND
LF LINEAR FEET
LH LEFT HAND
LKR LOCKER
LOC LOCATION
LONG LONGITUDINAL
LT LIGHT
LVR LOUVER
LVT LUXURY VINYL TILE
M
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MC MEDICINE CABINET
MECH MECHANICAL
MEMB MEMBRANE
MEZZ MEZZANINE
MFR MANUFACTURE (R)
MIN MINIMUM
MISC MISCELLANEOUS
MNTG MOUNTING
MO MASONRY OPENING
ABBREVIATIONS
MR MIRROR
MTL METAL
N
(N) NEW
N NORTH
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
O
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED / CONTRACTOR
INSTALLED
OFOI OWNER FURNISHED / OWNER INSTALLED
OH OVERHEAD
OPG OPENING
OPP OPPOSITE
ORD OVERFLOW ROOF DRAIN
ORIG ORIGINAL
OZ OUNCE
P
PAR PARALLEL
PCF POUNDS PER CUBIC FOOT
PED PEDISTAL
PERF PERFORATED
PERP PERPENDICULAR
PL PLATE
PLAM PLASTIC LAMINATE
PLMG PLUMBING
PLYWD PLYWOOD
PNL PANEL
PR PAIR / PROPOSAL REQUEST
PRCST PRECAST
PREFAB PREFABRICATE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT / PRESSURE TREATED
PTD PAPER TOWEL DISPENSER
PTN PARTITION
PTR PAPER TOWEL RECEPTICAL
PVC POLYVINYL CHOLORIDE
Q
QT QUARRY TILE
R
R RADIUS / RISER
RB RUBBER BASE
RBR RUBBER
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REBAR REINFORCING BAR
REC RECESSED
REF REFERENCE / REFRIGERATOR
ABBREVIATIONS
REINF REINFORC (D), (ING), (MENT)
REQ REQUIRE
REQD REQUIRED
RES RESILIENT FLOORING
RET RETURN
REV REVISION (S), REVISED
RFG ROOFING
RFI REQUEST FOR INFORMATION
RFP REQUEST FOR PROPOSAL
RH RIGHT HAND
RL RIDGE LINE
RM ROOM
RO ROUGH OPENING
ROW RIGHT OF WAY
RVS REVERSE (SIDE)
RWL RAIN WATER LEADER
S
S SOUTH
SB SPLASH BACK
SC SOLID CORE
SCHED SCHEDULE
SCR SHOWER CURTAIN ROD
SCT SECTION
SD SOAP DISPENSER
SF SQUARE FOOT
SHT SHEET
SHTHG SHEATHING
SIM SIMILAR
SLDG SLIDING
SLNT SEALANT
SND SANITARY NAPKIN DISPENSER
SNX SANIARY NAPKIN DISPOSAL
SOG SLAB ON GRADE
SPEC SPECIFICATION (S)
SQ SQUARE
SSM SOLID SURFACE MATERIAL
SST STAINLESS STEEL
ST STREET
STC SOUND TRANSMISSION CLASS
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
SV SHEET VINYL
SW SHEARWALL
SYM SYMMETRICAL
T
T TREAD
T&B TOP & BOTTOM
T&G TOUNGE AND GROOVE
TB TOWEL BAR
TBD TO BE DETERMINED
TEMP TEMPORARY / TEMPERED
TER TERRAZZO
TFE TOP FOOTING ELEVATION
THD THREAD (ED) (S)
ABBREVIATIONS
THK THICKNESS
THRU THROUGH
TKBD TACKBOARD
TL TILE
TO TOP OF
TOB TOP OF BEAM
TOC TOP O F CONCRETE/CURB
TOD TOP OF DECK
TOF TOP OF FOOTING (FOUNDATION)
TOJ TOP OF JOIST
TOM TOP OF MASONRY
TOP TOP OF PIER
TOS TOP OF SLAB/STEEL
TOW TOP OF WALL
TPD TOILET PAPER DISPENSER
TPO THERMOPLASTIC POLYOLEFIN
TPTN TOILET PARTITION
TRANS TRANSVERSE
TS TUBE STEEL
TYP TYPICAL
U
UG UNDERGROUND
UH UNIT HEATER
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
UON UNLESS OTHERWISE NOTED
UTIL UTILITY
V
V SHEAR
VAR VARIES
VB VAPOR BARRIER
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VR VAPOR RETARDER
VWC VINYL WALL COVERING
W
W WEST/WIDTH
W/ WITH
W//O WITHOUT
WA WEDGE ACHOR
WB WOOD BASE
WC WATER CLOSET
WD WOOD/WOODWORK
WDW WINDOW
WF (W) WIDE FLANGE
WG WALL GUARD
WH WATER HEATER
WI WROUGHT IRON
WL WIND LOAD
WP WATERPROOF (ING)
WR WATER RESISTANT
WRB WEATHER RESISTANT BARRIER
WSCT WAINSCOT
WT WEIGHT / WINDOW TREATMENT
WWF WELDED WIRE FABRIC
SHEET INDEX
01 - GENERAL
GI000 COVER SHEET
GI101 ACCESSIBILITY DETAILS
GI102 LIFE SAFETY CODE REVIEW
GI103 LIFE SAFETY PLAN - THIRD FLOOR
04 - STRUCTURAL
S001 STRUCTURAL GENERAL NOTES
S101 FLOOR FRAMING PLAN
S102 ROOF FRAMING PLAN
S501 STANDARD AND TYPICAL DETAILS
05 - ARCHITECTURAL DEMOLITION
AD101 DEMO - THIRD FLOOR
AD110 DEMO - REFLECTED CEILING PLAN - THIRD FLOOR
06 - ARCHITECTURAL
AE101 FLOOR PLAN - THIRD FLOOR
AE111 REFLECTED CEILING PLAN - THIRD FLOOR
AE450 INTERIOR ELEVATIONS
AE601 SCHEDULES & BUILDING DETAILS
AE801 FINISH PLAN - THIRD FLOOR
AE802 FINISH SCHEDULES AND FLOOR TRANSITION DETAILS
10 - MECHANICAL
M101 THIRD LEVEL MECHANICAL DEMOLITION PLAN
M201 SECOND LEVEL WASTE & VENT REMODEL PLAN
M202 THIRD LEVEL WASTE & VENT REMODEL PLAN
M301 SECOND LEVEL PIPING REMODEL PLAN
M302 THIRD LEVEL PIPING REMODEL PLAN
M401 THIRD LEVEL HVAC REMODEL PLAN
M402 CLEARSTORY HVAC PLAN & HVAC SECTIONS
M501 MECHANICAL DETAILS, SCHEDULES & SYMBOLS
M502 MECHANICAL DETAILS, SCHEDULES & SYMBOLS
SHEET INDEX
11 - ELECTRICAL
E101 THIRD LEVEL ELECTRICAL DEMOLITION PLAN
E201 THIRD LEVEL LIGHTING REMODEL PLAN
E301 THIRD LEVEL POWER REMODEL PLAN
E401 THIRD LEVEL SIGNAL REMODEL PLAN
E501 ELECTRICAL SCHEDULES & DETAILS
E601 ELECTRICAL SPECIFICATIONS
E701 ELECTRICAL DETAILS, SYMBOLS & ABBREVIATIONS
12 - FOOD SERVICE
FS0.0 FOOD SERVICE COVER PAGE
FS0.1 EQUIPMENT PLAN - DEMO
FS1.0 EQUIPMENT PLAN
FS1.1 EQUIPMENT PLAN
FS2.0 EQUIPMENT ELEVATIONS
FS2.1 EQUIPMENT ELEVATIONS
FS2.2 3D VIEWS
FS3.0 ELECTRICAL PLAN
FS4.0 PLUMBING PLAN
FS5.0 DETAILS
FS6.0 BUILDING WORKS PLAN
FS6.1 BUILDING WORKS PLAN
FS7.0 WALK IN DETAILS
FS7.1 RDT DETAILS
FS7.2 WALK IN DETAILS
TOTAL SHEET COUNT: 47
Revision# Description Date:
Figure 303.2 Vertical Change in Level
Figure 303.3 Beveled Change in Level
Figure 305.3 Clear Floor or Ground Space
Figure 305.5 Position of Clear Floor or Ground Space
Figure 305.7.1 Maneuvering Clearance in an
Alcove, Forward Approach
Figure 305.7.2 Maneuvering Clearance in an
Alcove, Parallel Approach
Figure 306.2 Toe Clearance
Figure 306.3 Knee Clearance
Figure 308.3.1 Unobstructed Side
Reach
Figure 308.3.2 Unobstructed High Side
Reach
Figure 308.2.2 Obstructed High Forward Reach
Figure 308.2.1 Unobstructed Forward Reach
Figure 307.2 Limits of Protruding Objects
Figure 307.3 Post-Mounted Protruding Objects
Figure 403.5.1 Clear Width of an Accessible Route
Figure 404.2.4.3 Maneuvering Clearance at Recessed Doors and Gates
Figure 404.2.4.1 Maneuvering Clearance at Manual Swinging Doors and Gates
Figure 404.2.3 Clear Width of Doorways
A C
C E
S S
IB
L
E R
O U
T E
S B
U
IL
D
IN
G B
L O
C K
S
1/4 max
1/4
1/4 1/2
1/2 2
52 min m in
36 min 60 min
X
X
6 max
17-25 m in
11 min
9 min
8 min m in m in
25 max
(b) plan
(a) elevation
(b) plan
(a) elevation m ax m in
10 max
>10 - 24 max m ax m ax m ax
10 max m ax m ax
> 20 - 25 max20 max m ax
(a) (b) (b)(a) m ax m inX
4 max
X m in m ax
4 max (typ.)
X > 12
X > 12
4 max4 max
(a) (b)
36 min
32 min
32 min
36 min m ax m ax m in m in
18 min
X > 8
X > 8 X > 8
12 min m in m in m in m in m in m in
18 min 12 min*
36 min
42 min m in
(e) hinge approach, pull side
(j) latch approach, push side
(k) latch approach, push side
*48 min if door provided with closer
(i) latch approach, pull side
*54 min if door provided with closer
(h) latch approach, pull side
(f) hinge approach, push side
(g) hinge approach, push side
*if door provided with both closer and latch ** 48 min if both closer and latch provided
(b) front approach, push side
(c) front approach, push side
*if door provided with both closer and latch
(a) front approach, pull side
(a) hinged door
(b) sliding door
(c) folding door
(d) doorways without doors
(a) pull side
(b) push side
(c) push side, door provided with both closer and latch
(d) hinge approach, pull side
24 min
22 min
12 min* m in m in
24 min
36 min
32 min
32 min32 min
90.
(a) forward
(b) parallel
Figure 703.2.5 Height of Raised
Characters
Figure 703.4.1 Height of Tactile Characters
Above Floor or Ground
Figure 703.4.2 Location of Tactile Signs at Doors
Figure 703.6.1 Pictogram Field
Figure 703.7.2.1 International Symbol of Accessibility m ax m in
AREA OF
REFUGE
18 min
18 min centered on tactile characters
AREA OF
REFUGE
m in
MEN not in pictogram field
5/
LIBRARY
.00
C O
M M
U N
IC
A
T
IO
N E
L E
M E
N T
S A
N D
F E
A T
U R
E S
Figure 403.5.2 Clear Width at Turn m in m in
42 min42 min
X < 52 X < 52
36 min 36 min
(B) 180 degree turn
Option 2
(A) 180 degree turn
Option 1 m in
43 min43 min
X < 52
(C) 180 degree turn
Option 3
Sanitary Napkin Disposal
Sanitary Napkin Dispenser m ax
Soap Dispenser
Paper Towel Dispenser
T .O
. d is p en se r
O P
G m ax
Baby Changing Station to B
.O m in to h ig h es t p ar t m ax
LINE OF WALL
Coat/Robe Hook
4' -0
A
C C
5' -4
T
Y P
Mirror Height to g la ss
Fire Extinguisher Cabinet to b as e o f ca b in et m ax
Fire Extinguisher m ax
Hand Dryer
Trash Receptical m ax w o rk s u rf ac e o f w o rk s u rf ac e
T .O
. o p er ab le p o rt io n m ax
Toilet Seat Cover Dispenser
Sharps Disposal
Figure 302.3 Elongated Openings in Floor or
Ground Surfaces d ir ec ti o n o f tr av el lo n g d im d o m in an t p er p in d ic u la r to
1/2" max dominant direction of travel
S T
A N
D A
R D
M O
U N
T
IN
G H
E
IG
H T
S
Figure 304.3.1.2 Circular Turning Space - Existing
Buildings Size and Overlap
Overlap of knee and toe clearnce
6.
2.
m ax
P er ø 5'-0" min
Figure 304.3.2.2 T-Shaped Turning Space - Existing
Buildings Size and Overlap ar m ar m base
60" min min
12" min
36" min
12" m in36 m in m in
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD
A/E:
STAMPCONSULTANTS
321 4 5 6 7 8 9 10 o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t
MECHANICAL / ELECTRICAL:
WEST PLAINS ENGINEERING, INC.
1750 RAND RD
RAPID CITY, SD 57702
Phone: 605-348-7455
STUCTURAL:
ALBERTSON ENGINEERING INC.
3202 W MAIN ST SUITE C
RAPID CITY, SD 57702
Phone: 605-343-9606
FOOD SERVICE:
HC DESIGN
614 FERGUSON AVE STE 11
BOZEMAN, MT 59718
Phone: 406-522-59719
C
S G
A R e v it L o c a l\
V A
H o t S p ri n g s U p g ra d e
N F
S B ld g d a rr in tJ
Y L .r v t
/1
/2
:1
:3
A
M
GI101
ACCESSIBILITY DETAILS
Stone Group Architects
600 E 7th Street
Sioux Falls, SD 57103
605-271-1144
UPGRADE NUTRITION AND FOOD
SERVICE DESIGN
Hot Springs, SD
6-13-2023 TRS DT / GV
PERMIT / BID SET
SGA #211916
VA #568A4-22-205
PROJECT INFORMATION:
1. CONSTRUCTION PURPOSE: RENOVATION
2. REASON FOR SUBMITTAL: RENOVATION
3. I CERTIFY THAT TO THE BEST OF OUR KNOWLEDGE THE SUBMITTED PLANS FOR THE
ABOVE-REFERENCED PROJECT COMPLY WITH THE REQUIREMENTS OF THE FOLLOWING:
NFPA 101-18 (AND ALL REFERENCED DOCUMENTS)
2018 INTERNATIONAL MECHANICAL CODE (IMC)
2015 UNIFORM PLUMBING CODE (UPC)
2017 NATIONAL ELECTRICAL CODE (NFPA-70)
2018 LIFE SAFETY CODE (NFPA-101)
2015 ABA ACCESSIBILITY STANDARDS
BARRIER FREE DESIGN
2018 IBC WITH LOCAL AMENDMENTS
ASHRAE STANDARD 90.1 (2007)
ASHRAE 62.1 (2007)
4. LOCATION OF ANY ANTICIPATED FUTURE ADDITIONS: UNKNOWN
5. OWNER:
DEPARTMENT OF VETERANS AFFAIRS
OFFICE OF CONSTRUCTION AND FACILITIES MANAGEMENT
500 NORTH 5TH STREET
HOT SPRINGS, SD 57747
6. DESIGN TEAM:
STONE GROUP ARCHITECTS - 605-271-1144
600 E 7TH STREET - SIOUX FALLS, SD 57103
CONTACT: GARRY BLACK - GARRYB@STONEGROUPARCH.COM
ALBERTSON ENGINEERDING - 651-343-9606
3202 W MAIN ST, SUITE C - RAPID CITY, SD 57702
CONTACT: JUSTIN KEPLER (STRUCTURAL) - JUSTIN@ALBERTSONENGINEERING.COM
WEST PLAINS ENGINEERING - 605-348-7455
1750 RAND ROAD - RAPID CITY, SD 57702
CONTACT:
MATT VONHADEN (ELECTRICAL) - MATT.VONHADEN@WESTPLAINSENGINEERING.COM
DAVE RIEMENSCHNEIDER (MECHANICAL) -
DAVE.RIEMENSCHNEIDER@WESTPLAINSENGINEERING.COM
HC DESIGN (FOODSERVICE) - 406-522-7700
614 FERGUSON AVE SUITE 1 - BOZEMAN, MT 59718
CONTACT: MICHAEL MILES - MICHAEL@HC.DESIGN
7. ARCHITECTS SEAL: SEE STAMP AT BOTTOM
8. FIRE SERVICE: HOT SPRINGS FIRE DEPARTMENT
9. INSPECTION: VISN SAFETY OFFICER
10. OCCUPANCY GROUP TYPE: A-2 ASSEMBLY
- RESTAURANTS, CAFETERIAS AND SIMILAR DINING FACILITIES
(INCLUDING ASSOCIATED COMMERCIAL KITCHENS)
11. CONSTRUCTION TYPE: TYPE V (111) FULLY SPRINKLERED
HISTORIC BUILDING: YES
A. ALLOWABLE AREA PER FLOOR: NO CHANGE
B. BUILDING HEIGHT: NO CHANGE
STORIES: 3
12. ACTIVE FIRE SAFETY SYSTEMS
(a) SMOKE DETECTORS THROUGHOUT
(b) EMERGENCY LIGHTING
(c) BATTERY POWERED EXIT LIGHTING
(d) HOOD SUPPRESSION SYSTEM
(e) PORTABLE EXTINGUISHERS
(f) AUTOMATIC AIR-HANDLING SHUT-DOWN
(g) FIRE ALARM SYSTEM
13. WATER SUPPLY: NATURAL SPRING
14. SEWAGE TREATMENT: CITY OF HOT SPRINGS
15. HANDICAP PROVISIONS: ACCESSIBLE ROUTE
LAVATORIES AND SIGNAGE
16. OCCUPATIONAL LOAD:
KITCHENS, COMMERCIAL: 200 GSF/OCC
STORAGE & MECHANICAL EQUIP. RMS: 300 GSF/OCC
ASSEMBLY WITHOUT FIXED SEATS: 15 NSF/OCC
EGRESS CAPACITY:
STAIRWAY: .3 IN./PERSON
DOOR: .2 IN./PERSON
CODE INFORMATION
• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD
STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE INFORMATION ON THE
TECHNICAL INFORMATION LIBRARY (TIL)
• INTERNATIONAL BUILDING CODE (IBC) (ONLY WHEN SPECIFICALLY REFERENCED IN VA
DESIGN DOCUMENTS)
• 2018 NFPA 101 LIFE SAFETY CODE
• 2018 IBC
• NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900
• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS
• VA SEISMIC DESIGN REQUIREMENTS, H-18-8
• NATIONAL ELECTRICAL CODE (NEC)
• INTERNATIONAL PLUMBING CODE (IPC)
• ASME BOILER AND PRESSURE VESSEL CODE
• ASME CODE FOR PRESSURE PIPING
• ARCHITECTURAL BARRIER ACT ACCESSIBILITY STANDARDS (ABAAS) INCLUDING VA
SUPPLEMENT, BARRIER FREE DESIGN GUIDE (PG-18-13)
• VA FIRE PROTECTION DESIGN MANUAL
NOTE: ALL WORK IS TO BE PERFORMED TO THE LATEST EDITION OF THE FOLLOWING CODES, ORDINANCES, AND LAWS WHICH INCLUDE, BUT ARE NOT LIMITED TO:
1. CONTRACTOR IS NOT AUTHORIZED TO SCALE
CONSTRUCTION DOCUMENTS. ARCHITECT IS TO BE
NOTIFIED IN THE EVENT A DISCREPANCY IS FOUND IN
EITHER SPECIFICATIONS OR CONTRACT DOCUMENTS AT THE
EARLIEST PRACTICAL OPPORTUNITY.
2. GENERAL CONTRACTOR SHALL OBSERVE ALL REGULATIONS
IMPOSED BY GOVERNING BODIES.
3. CONSTRUCTION SHALL PROCEED IN AN ORDERLY AND
CONTINUOUS FASHION IN ACCORDANCE WITH THE
INTERNATIONAL BUILDING CODES AND ALL OTHER
APPLICABLE CODES.
4. THE CONTRACTOR SHALL CONTAIN ALL CONSTRUCTION
ACTIVITY, INCLUDING STORAGE OF MATERIAL AND
EQUIPMENT, WITHIN THE CONSTRUCTION LIMITS, AT ALL
TIMES BEING RESPONSIBLE FOR AND ABIDING BY RULES
AND REGULATIONS OF THE OWNER.
5. GENERAL CONTRACTOR TO BE RESPONSIBLE FOR
REPAIRING ANY AND ALL SURFACES DAMAGED BY HIMSELF
OR SUBCONTRACTORS UNDER HIS CONTROL. REPAIRS ARE
TO MATCH EXISTING MATERIALS AND MUST BE ACCEPTABLE
TO OWNER.
6. ADEQUATELY PATCH/REPAIR TO MATCH ADJACENT
CONSTRUCTION, ALL BUILDING STRUCTURES,
COMPONENTS, AND UTILITIES WHICH ARE DISTURBED AND
REQUIRE REPAIR AS A RESULT OF WORK PERFORMED
UNDER THIS CONTRACT.
7. ALL FLOOR TRANSITIONS BETWEEN DIFFERENT MATERIALS
SHALL BE SMOOTH AND FLUSH (MAXIMUM SLOPE = 1/8" PER
FOOT).
8. GENERAL CONTRACTOR SHALL REMOVE ALL
CONSTRUCTION DEBRIS FROM JOBSITE. ALL
CONSTRUCTION DEBRIS SHALL BE CONTAINED INSIDE
CONSTRUCTION LIMITS.
9. ALL WALLS WITH ITEMS SUCH AS GRAB BARS, TOILET
ACCESSORIES, WOOD TRIM, SHELVING, CASEWORK, ETC.
SHALL BE REINFORCED WITH CONCEALED, FIRE TREATED
WOOD BLOCKING OR METAL STUD BLOCKING. (GENERAL
CONTRACTOR TO INSTALL BLOCKING TYP.)
10. BUILDING 2 WILL REMAIN OCCUPIED THROUGHOUT THE
CONSTRUCTION PERIOD. THE CONTRACTOR SHALL TAKE
EVERY NECESSARY PRECAUTION TO ENSURE THE
UNINTERRUPTED OPERATION OF THE FACILITY, STAFF,
PATIENTS AND VISITORS. DISRUPTION TO ADJACENT
DEPARTMENTS AS WELL AS DEPARTMENTS ON FLOORS
ABOVE OR BELOW SHALL BE COORDINATED WITH THE
FACILITY CONTRACT OFFICER. THE CONTRACTOR SHALL
COORDINATE ALL WORK, CONSTRUCTION, PATHWAYS,
ELEVATOR USAGE, AND UTILITY INTERRUPTION WITH THE
OWNER.
11. CONTRACTOR TO EXERCISE ALL PRECAUTIONS TO PROVIDE
FOR STAFF, PATIENTS, VISITORS, AND WORKMEN'S SAFETY
DURING THE PERFORMANCE OF THIS CONTRACT PER EPA,
OSHA, AND OTHER APPLICABLE CODES, STANDARDS, AND
REGULATIONS.
12. THE CONTRACTOR SHALL MAINTAIN & KEEP BARRIER FREE
THE EXISTING MEANS OF EGRESS.
13. ALL GYPSUM BOARD TO BE MOISTURE/MOLD RESISTANT
TYPE X.
14. THE CONTRACTOR IS RESPONSIBLE FOR CONSTRUCTION OF
TEMPORARY PARTITIONS AND TEMPORARY VENTILATION
SYSTEMS AS REQUIRED TO PREVENT THE SPREAD OF DUST
FROM THE CONSTRUCTION AREA TO OCCUPIED AREAS OF
THE BUILDING. OCCUPIED AREAS SHALL REMAIN DUST FREE
THROUGHOUT THE CONSTRUCTION. THE CONTRACTOR
SHALL MAINTAIN THE AFFECTED AREAS OF THE BUILDING
(INCLUDING MATERIAL TRANSPORT ROUTES) CLEAN AND
DUST FREE.
15. ALL WOOD USED IN WALL CONSTRUCTION SHALL BE FIRE-
RETARDANT-TREATED LUMBER.
16. ALL WRITTEN CORRESPONDENCE WILL BE TRANSMITTED
FROM SUBCONTRACTOR THROUGH GENERAL CONTRACTOR
THROUGH ARCHITECT TO OWNER. ALL PARTIES
CORRESPONDENCE ARE TO RECEIVE WRITTEN AND SIGNED
COPIES OF SUCH. NO VERBAL AGREEMENTS AFFECTING
COST OR ALTERNATIVE CONSTRUCTION METHODS AND
ARRANGEMENTS WILL BE CONSIDERED VALID OR BINDING,
AND ARE THEREFORE, DISALLOWED.
17. GENERAL CONTRACTOR SHALL COMPLY WITH ALL
DIRECTIVES OF THE OWNER. IF CONFLICTS BETWEEN
DRAWINGS, SPECIFICATIONS AND REQUIREMENTS OF
BUILDING OWNER AND/OR OPERATORS ARISE, THEY SHALL
BE BROUGHT TO THE ATTENTION OF THE ARCHITECT
IMMEDIATELY.
18. THE HVAC, PLUMBING AND ELECTRICAL CONTRACTORS
SHALL COORDINATE THEIR WORK WITH THE WORK OF
OTHER TRADES TO ASSURE THAT THE WORK CAN BE
INSTALLED IN A WORKMAN-LIKE MANNER. EACH
CONTRACTOR SHALL BE EXPECTED TO COOPERATE WITH
OTHER CONTRACTORS IN THE PLACEMENT OF WORK TO
AVOID CONFLICTS AND MAINTAIN JOB PROGRESS.
19. IT IS THE INTENT OF THESE DRAWINGS THAT A COMPLETE
JOB IS TO BE ACCOMPLISHED IN PREPARING THE BID. THE
BIDDER SHALL MAKE ALLOWANCES FOR DETAILS WHICH
MIGHT HAVE BEEN INADVERTENTLY OMITTED FROM THE
DRAWINGS.
20. ALL EXISTING DUCTWORK, ELECTRICAL OR PIPING IS NOT
NECESSARILY SHOWN ON THE DRAWINGS.
21. BEFORE CONTRACTOR(S) BID THE JOB, IT IS IMPERATIVE
THEY VISIT THE JOBSITE AND FIELD VERIFY THE EXACT
LOCATION OF ALL EXISTING EQUIPMENT, DUCTWORK, ETC. IT
WILL BE PART OF THE CONTRACTOR'S RESPONSIBILITY TO
DESIGN AND RELOCATE ANY EXISTING OBSTACLES WHICH
WILL INTERFERE WITH THE CONTRACTOR'S ABILITY TO
INSTALL ALL NEW OR RELOCATED WORK ON HIS CONTRACT.
1. ALL EXISTING DUCTWORK, ELECTRICAL OR PIPING IS NOT NECESSARILY SHOWN ON THE
DRAWINGS.
2. BEFORE CONTRACTOR(S) BID THE JOB, IT IS IMPERATIVE THEY VISIT THE JOBSITE AND FIELD
VERIFY THE EXACT LOCATION OF ALL EXISTING EQUIPMENT, DUCTWORK, ETC. IT WILL BE
PART OF THE CONTRACTOR'S RESPONSIBILITY AND COST TO ENGINEER AND RELOCATE ANY
EXISTING OBSTACLES WHICH WILL INTERFERE WITH THE CONTRACTOR'S ABILITY TO INSTALL
ALL NEW OR RELOCATED WORK ON HIS CONTRACT.
3. CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN FIELD AND NOTIFY PROJECT ARCHITECT OF
ALL DISCREPANCIES IF ANY, FOUND PRIOR TO PLACEMENT OF ANY COMPONENTS
4. THE CONTRACTOR WILL TAKE ALL NECESSARY PRECAUTIONS INCLUDING THE BUILDING AND
MAINTENANCE OF DUST TIGHT PARTITIONS, DAILY VACUUMING, SWEEPING, AND PROVISION
OF CLEAN FLOOR MATS AT THE PROJECT ENTRANCES, TO PREVENT THE INFILTRATION OF
DIRT AND DUST FROM THE CONSTRUCTION AREAS INTO THE OWNER OCCUPIED AREAS.
5. PATCH ALL FINISHES WHERE DISTURBED BY THE WORK AND WHERE UNFINISHED SURFACES
HAVE BEEN EXPOSED BY DEMOLITION. PATCHING MUST MATCH ADJACENT MATERIALS,
COLORS, AND FINISHES. WALL SURFACES THAT ARE PATCHED SHALL HAVE THE FINISHES
(PAINT, VINYL WALL COVERING, ETC.) REPLACED FROM CORNER TO CORNER AND FLOOR TO
CEILING.
6. UNLESS OTHERWISE INDICATED FINISH ALL NEW FRAMES AND PARTITIONS TO MATCH
SURROUNDING. NEW HOLLOW METAL DOORS SHALL BE PAINTED SAME COLOR AS FRAMES.
7. PAINT ALL EXPOSED NEW AND EXISTING PIPING, CONDUIT, WIRE MOLD, ELECTRICAL PANELS, ACCESS PANELS, ETC.,TO MATCH WALL FINISH UNLESS OTHERWISE NOTED.
8. CORRIDOR WALLS AND PLUMBING PARTITIONS SHALL BE CONSIDERED 1 HOUR FIRE RATED
WALLS AND NEW OR EXISTING PENETRATIONS MUST BE SEALED ACCORDINGLY WITH
APPROVED FIRESTOPPING MATERIAL THE SAME DAY THE PENETRATION IS MADE OR
DISCOVERED. ALL FLOOR SLABS, VERTICAL SHAFTS AND STAIRWELLS SHALL BE CONSIDERED
2 HOUR RATED PARTITIONS AND BE SEALED ACCORDINGLY IN THE MANNER LISTED HEREIN.
PENETRATIONS THROUGH THE EXTERIOR WALLS SHALL BE SEALED WATERTIGHT.
9. ALL NEW VERTICAL AND HORIZONTAL DUCTS, PIPES, CONDUITS, ETC.,IN FINISHED ROOMS OR
AREAS THROUGHOUT BUILDING, NOT ENCASED IN MASONRY OR CONCRETE CONSTRUCTION,
SHALL BE FURRED IN, THE FURRING FINISHED TO MATCH THE ROOM FINISH.
10. WHENEVER EXISTING EQUIPMENT, PIPING, DUCTS, ETC., ARE REQUIRED TO BE REMOVED, SUCH REMOVAL SHALL INCLUDE ALL ANCHORS, HANGERS, FOUNDATIONS, ETC., UNLESS
NOTED OTHERWISE. AFTER REMOVAL; FLOORS, WALLS, AND CEILINGS SHALL BE FINISHED TO
MATCH ADJOINING SURFACES.
11. UTILITY WORK THAT WILL REQUIRE A SHUTDOWN OF EXISTING SERVICE(S) WILL BE DONE
AFTER NORMAL WORKING HOURS (NIGHTS, WEEKENDS, HOLIDAYS, ETC.) AT NO ADDITIONAL
COST TO THE GOVERNMENT. WORK MUST BE SCHEDULED WITH THE COR.
12. WORK THAT MUST OCCUR IN OCCUPIED AREAS, SUCH AS PUBLIC CORRIDORS, OF THE
MEDICAL CENTER OR DISRUPT A MEDICAL CENTER FUNCTION WILL BE DONE AT TIMES OTHER
THAN NORMAL WORKING HOURS (NIGHTS, WEEKENDS, HOLIDAYS, ETC.) AT NO ADDITIONAL
COST TO THE GOVERNMENT. WORK MUST BE SCHEDULED WITH THE V.A. PROJECT ENGINEER.
13. ALL ELECTRICAL CIRCUITRY TO BE CONCEALED UNLESS OTHERWISE SPECIFIED. CIRCUITING
FOR ELECTRIC DOOR HOLD OPENS IN MASONRY WALLS SHALL BE SURFACE RACEWAY.
14. COORDINATE ALL WORK WITH OTHER TRADES AND EXISTING CONDITIONS TO ELIMINATE
CONFLICTS AND/OR INTERFERENCES. THE CONTRACTOR SHALL PROVIDE ALL OFFSETS,
FITTINGS, TRANSITIONS, EXTENSIONS, ETC., REQUIRED FOR A COMPLETE AND FUNCTIONAL
SYSTEM.
15. DRAWINGS ARE DIAGRAMMATIC AND SHOW ONLY THE GENERAL ARRANGEMENT OF EACH
SYSTEM. BECAUSE OF SMALL SCALE OF DRAWINGS IT IS NOT POSSIBLE TO SHOW OR
INDICATE ALL BRANCHES, OFFSETS, FITTINGS, BOXES, AND ACCESSORIES WHICH MAY BE
REQUIRED. CONTRACTOR MUST CAREFULLY INVESTIGATE STRUCTURAL AND FINISH
CONDITIONS AFFECTING ALL WORK, FURNISHING SUCH FITTINGS, TRAPS, VALVES, BOXES,
ACCESSORIES, ETC., AS MAY BE REQUIRED.
16. LOCATIONS OF NEW EQUIPMENT, PIPING, AND ASSOCIATED ITEMS SHOWN ON THE DRAWINGS
ARE SCHEMATIC ONLY. THE CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION AND
ELEVATION FOR ALL WORK, INCLUDING CONNECTIONS TO EXISTING WORK. ALL OFFSETS,
FITTINGS, TRANSITIONS, EXTENSIONS, ETC., REQUIRED FOR A COMPLETE AND FUNCTIONAL
SYSTEM SHALL BE PROVIDED AT NO ADDITIONAL COST.
17. ALL EXISTING DUCTWORK, ELECTRICAL OR MECHANICAL PIPING, CABLE TRAYS, ETC., IS NOT
NECESSARILY SHOWN ON THE DRAWINGS. BEFORE CONTRACTOR PLACES A BID IT IS
IMPERATIVE THEY VISIT THE JOBSITE AND FIELD VERIFY THE EXACT LOCATION OF ALL
EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC. IT WILL BE PART OF THE CONTRACTOR'S
RESPONSIBILITY AND THE CONTRACTOR WILL BEAR THE COST TO ENGINEER AND RELOCATE
ANY EXISTING OBSTACLES WHICH WILL INTERFERE WITH THE CONTRACTOR'S ABILITY TO
INSTALL ALL NEW OR RELOCATED WORK IN THIS PROJECT.
18. CONTRACTOR SHALL NOT INSTALL CONDUIT, PIPING, LIGHTING, OR OTHER OBSTRUCTIONS
UNDER OR ADJACENT TO HVAC EQUIPMENT THAT WILL ELIMINATE OR OBSTRUCT ACCESS TO
COILS, MOTORS, VALVES, SWITCHES, PANELS, ETC.
19. BEFORE THE CONTRACTOR BEGINS WORK HE SHALL RECORD ANY EXISTING SYSTEM
INFORMATION SUCH AS TEMPERATURE, FLOW RATE, PRESSURE, CURRENT, VOLATAGE, OR
ANY OTHER INFORMATION NECESSARY FOR HIM TO RETURN THE AFFECTED SYSTEM TO
ORIGINAL OPERATING CONDITION. UNLESS NOTED OTHERWISE IT IS ASSUMED THAT ALL
SYSTEMS ( HVAC, ELECTRICAL, PLUMBING, ETC.) ARE WORKING PROPERLY IN EVERY MANNER
AT THE BEGINNING OF THE PROJECT. THE CONTRACTOR'S RECORDED MEASUREMENTS MUST
BE SUBMITTED TO THE PROJECT ENGINEER FOR REVIEW AND ACCEPTANCE BEFORE ANY
DEMOLITION OR OTHER RELATED WORK CAN PROCEED.
20. FOR DOORS BEING REPLACED: IF THE EXISTING DOOR HAS SIGNAGE APPLIED TO IT, THIS
SIGNAGE SHOULD BE CAREFULLY REMOVED AND REAPPLIED TO THE NEW DOOR. IF THE
SIGNAGE IS DAMAGED DURING REMOVAL OR CANNOT OTHERWISE BE REAPPLIED IT SHOULD
BE REPLACED WITH NEW SIGNAGE OF IDENTICAL TYPE.
21. THE CONTRACTOR WILL BE RESPONSIBLE FOR MAINTAINING ALL EXISTING ACCESS DOORS TO
CONSTRUCTION AREAS, EXISTING MECHANICAL AND ELECTRICAL AREAS, ASSIGNED STORAGE
AREAS, EQUIPMENT ACCESS AREAS, ETC. DOORS MUST BE RESTORED TO THE CONDITION
ENCOUNTERED AT BEGINNING OF PROJECT. THIS INCLUDES DOOR REPLACEMENT,
HARDWARE REPLACEMENT, HARDWARE REPAIR, DOOR REPAIR, ETC.
22. IT IS IMPORTANT THAT ALL REPLACEMENT DOORS HAVE A GAP OF LESS THAN 3/4" BETWEEN
THE BOTTOM OF THE DOOR AND THE FLOOR AT ALL POINTS. CONTRACTOR MUST
COORDINATE INSTALLED DOOR FRAME HEIGHT OR MAKE OTHER NECESSARY MODIFICATIONS0
TO MEET THIS REQUIREMENT AND KEEP FIRE RATING OF DOOR AND FRAME. BOTTOM
SWEEPS ARE NOT ACCEPTABLE UNLESS SPECIFICALLY STATED ON DRAWING.
23. IF THERE IS ANY WORK TO BE DONE ON EXISTING ROOFS, SUCH AS ROOF PENETRATIONS OR
STANDS, OR ANYTHING THAT DAMAGES THE INTEGRITY OF THE ROOF, THIS WORK MUST BE
DONE BY A CONTRACTOR LICENSED BY THE ROOFING MEMBRANE MANUFACTURER. HE MUST
BE APPROVED BY THE MEMBRANE MANUFACTURER SO AS TO NOT VOID OR INTERRUPT
EXISTING SINGLE PLY MEMBRANE ROOF WARRANTIES.
24. EXISTING CIRCUITRY (CONDUIT, BOXES, WIRE, ETC.) MAY BE REUSED AT THE CONTRACTOR'S
OPTION AS LONG AS IT MEETS THE SAME SPECIFICATIONS REQUIRED FOR NEW CIRCUITRY.
ALL WORK, NEW AND EXISTING, SHALL COMPLY WITH THE LATEST NEC CODE.
25. WHERE DOOR AND HARDWARE ARE SHOWN TO BE REMOVED, THE DOOR STOPS ARE TO
REMAIN AND BE REUSED UNLESS NOTED OTHERWISE.
CONTRACTOR GENERAL NOTESPROJECT GENERAL NOTES
BUILDING CODES, GUIDE AND MANUALS
• BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, AMERICAN CONCRETE
INSTITUTE AND COMMENTARY (ACI 318)
• MANUAL OF STEEL CONSTRUCTION, LOAD AND RESISTANCE FACTOR DESIGN
SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS, AMERICAN INSTITUTE OF STEEL
CONSTRUCTION (AISC)
• DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL,
COMMERCIAL AND MULTI-FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND NEW LOW-
RISE RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434, AND 435.
• FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS:
MEMORANDUM OF UNDERSTANDING (MOU)
• EXECUTIVE ORDER 13834
• THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL
REQUIRMENTS SECTION 01010 IF THE VA MASTER CONSTRUCTION SPECIFICATION.
• VENTILATION FOR THE ACCEPTABLE INDOOR AIR QUALITY – ASHRAE STANDARD 62.1 –
2004.
• SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE STANDARD 15 – 2007.
• ENERGY POLICY ACT OF 2005 (EPACT)
PLUMBING WATER LAVATORIES SHOWER DRINKING SERVICE
FIXTURES FOUNTAINS SINKS
RESIDENTIAL 1 PER 25 1 PER 40 1 PER 100 1 SINK
(FIRST 50) (FIRST 80)
TOTAL REQUIRED N/A N/A N/A N/A 1 SINKS
TOTAL PROVIDED N/A N/A N/A N/A 1 SINKS
ARRANGEMENT OF MEANS OF EGRESS
LARGE RESIDENTIAL BOARD AND CARE - FULLY SPRINKLERED
TRAVEL DISTANCE
WITHIN ROOM TO CORRIDOR (NFPA 101 33.3.2.6.2) 125 FT
CORRIDOR DOOR TO EXIT (NFPA 101 33.3.2.6.3.1) 100 FT
COMMON PATH OF TRAVEL (NFPA 101 33.3.2.5.3) 160 FT
DEAD END (NFPA 101 33.3.2.5.4) 50 FT
MISCELLANEOUS
YES NO
FIRE RESISTIVE CORRIDORS
SMOKE TIGHT CORRIDORS (SMOKE PARTITIONS)
INCIDENTAL USE AREA RATINGS SEE PLANS
INTERIOR FINISHES CLASSIFICATION EXITS A
EXIT ACCESS CORRDORS A
OTHER SPACES B
FIRE-RESISTANCE REQUIREMENTS: CONSTRUCTION TYPE V (111)
STRUCTURAL FRAME:
COLUMNS: EXISTING / 1HR NFPA - A.8.2.1.2
GIRDERS: EXISTING / 1HR NFPA - A.8.2.1.2
TRUSSES: EXISTING / 1HR NFPA - A.8.2.1.2
BEARING WALLS:
EXTERIOR BEARING WALLS: EXISTING / 1 HR NFPA - A.8.2.1.2
BEARING WALLS INTERIOR: EXISTING / 1 HR NFPA - A.8.2.1.2
NON-BEARING WALLS:
EXTERIOR NON-BEARING WALLS: 0 HR NFPA - A.8.2.1.2
INTERIOR NON-BEARING WALLS: SEE LIFE PLANS
FLOOR CONSTRUCTION:
FLOOR AND FLOOR/CEILING: EXISTING / 1HR NFPA - A.8.2.1.2
PRIME & SEC. BEAMS & JOISTS: EXISTING / 0HR NFPA - A.8.2.1.2
ROOF CONSTRUCTION:
ROOF AND ROOF/CEILING: EXISTING / 1HR NFPA - A.8.2.1.2
PRIME & SEC. BEAMS & JOISTS: EXISTING / 0HR NFPA - A.8.2.1.2
OTHER:
SHAFTS & EXIT PASSAGEWAYS: 1HR NFPA - 33.2.3.1.3, 8.6.5
ELEVATOR (ACCESSIBLE EGRESS) 2HR NFPA - 7.2.12.2.4, 7.2.3.3
EXTERIOR DOORS & WINDOWS: 0 HR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD
A/E:
STAMPCONSULTANTS
321 4 5 6 7 8 9 10 o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t
MECHANICAL / ELECTRICAL:
WEST PLAINS ENGINEERING, INC.
1750 RAND RD
RAPID CITY, SD 57702
Phone: 605-348-7455
STUCTURAL:
ALBERTSON ENGINEERING INC.
3202 W MAIN ST SUITE C
RAPID CITY, SD 57702
Phone: 605-343-9606
FOOD SERVICE:
HC DESIGN
614 FERGUSON AVE STE 11
BOZEMAN, MT 59718
Phone: 406-522-59719
C
S G
A R e v it L o c a l\
V A
H o t S p ri n g s U p g ra d e
N F
S B ld g d a rr in tJ
Y L .r v t
/1
/2
:1
:3
A
M
GI102
LIFE SAFETY CODE REVIEW
Stone Group Architects
600 E 7th Street
Sioux Falls, SD 57103
605-271-1144
UPGRADE NUTRITION AND FOOD
SERVICE DESIGN
Hot Springs, SD
6-13-2023 TRS DT / GV
PERMIT / BID SET
SGA #211916
VA #568A4-22-205
UP
UP
UP
UP
UP
CODE PLAN LEGEND
0.0"
0.0"
OCCUPANTS
REQUIRED WIDTH
PROVIDED WIDTH
OCCUPANT LOAD
RATED WALL KEY
1-HOUR WALL
2-HOUR WALL
A. ANY DISCREPANCIES OR CONFLICTS FOUND IN THE VARIOUS PARTS OF THE CONSTRUCTION
DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND THE OWNER BEFORE
PROCEEDING WITH THE WORK.
B. PROVIDE AND INSTALL SMOKE SEALS ON ALL RATED DOORS.
C. SEE MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.
GENERAL CODE PLAN NOTES:
PREP AREA
WALK-IN
FREEZER
KITCHEN
OFFICE
WAREWASHING
PASSAGE
EXISTING
WALK IN
COOLER
DRY GOODS
CART WASH
AREA
MECHANICAL
SERVING AREA
50'- 0"
50'-0"
50'-0"
50'-0"
'-0
1.10A
1.10A
LE
N
G T
H O
F T
R A
V E
L: 7 3' -8"
LE
N
G T
H O
F T
R A
V E
L:
8' -8
1.10A
1.10
1.10
1.6"
34.0"
1.4"
34.0"
8.4"
82.0"
8.4"
82.0"
8.4"
82.0"
TRAY RETURN
CARTS
BEVERAGES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD
A/E:
STAMPCONSULTANTS
321 4 5 6 7 8 9 10 o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t
MECHANICAL / ELECTRICAL:
WEST PLAINS ENGINEERING, INC.
1750 RAND RD
RAPID CITY, SD 57702
Phone: 605-348-7455
STUCTURAL:
ALBERTSON ENGINEERING INC.
3202 W MAIN ST SUITE C
RAPID CITY, SD 57702
Phone: 605-343-9606
FOOD SERVICE:
HC DESIGN
614 FERGUSON AVE STE 11
BOZEMAN, MT 59718
Phone: 406-522-59719
C
S G
A R e v it L o c a l\
V A
H o t S p ri n g s U p g ra d e
N F
S B ld g d a rr in tJ
Y L .r v t
/1
/2
:1
:4
A
M
GI103
LIFE SAFETY PLAN - THIRD FLOOR
Stone Group Architects
600 E 7th Street
Sioux Falls, SD 57103
605-271-1144
UPGRADE NUTRITION AND FOOD
SERVICE DESIGN
Hot Springs, SD
6-13-2023 TRS DT / GV
PERMIT / BID SET
SGA #211916
VA #568A4-22-205
KEYNOTES_SGA
Key Value Keynote Text
1.10 EXISTING FIRE EXTINGUISHER
1.10A EXISTING FIRE EXTINGUISHER RELOCATED. PROVIDE BLOCKING IN WALL FOR MOUNTING.
1/4" = 1'-0" F3
CODE PLAN - THIRD LEVEL
NORTH
1/2" 1"0" 2"SCALE: FULL
XC1 R1
XX" Ø X
XX'-X" XX'-X"
X
XN
XXNNN
XN
XXNNN
XN
XXNNN
F1
A
HSS _x_x_
B1
20GA TYPE 'W3' MTL DECK
PC S
PAN
Hx R15:12
B
B
GENERAL STRUCTURAL NOTES
INDEX TO STRUCTURAL SHEETS
SYMBOLS LEGEND
S J
W--x--
(XXX'-XX")
ELEVATION
INDICATOR
CUT SECTION
INDICATOR
WALL
REINFORCING
INDICATOR
PC SPAN
IDENTIFIER
STEP TOP OF
WALL INDICATOR
PIER TAG CALLOUT INDICATOR
ROOF SLOPE
INDICATOR
STEP TOP OF
FOOTING
IDENTIFIER
MASONRY PIER
INDICATOR
CORNER REINF
INDICATOR
CONTINUOUS
BEAM
INDICATOR
MATCH LINE INDICATOR
PLAN NORTH ORIENTED 90°
TO THE SHEET W/ MAGNETIC
NORTH (OPTIONAL)
DETAIL BUBBLE
INDICATOR
DETAIL/SECTION/PLAN
BLOCK TITLE INDICATOR
EXT ELEVATION
INDICATOR
COLUMN
INDICATOR(S)
KEYNOTE
IDENTIFIER
REVISION
SYMBOL
FOOTING/PIER
IDENTIFIER
STEP
INDICATOR
HOLDOWN
INDICATOR
BEAM
INDICATOR(S)
MOMENT
INDICATOR
DECK INDICATOR
SHEAR WALL
INDICATOR
LINTEL
INDICATOR
RAFTER
INDICATOR
ASTERISK
INDICATOR
SLOPE
INDICATOR
WORK POINT
INDICATOR
XN
ELEVATION INDICATOR
SECTION
INDICATOR
COLUMN/FND
GRID INDICATOR
SLAB JOINT
INDICATOR
STRUCTURAL HATCH PATTERNS
BRICK
CONCRETE
NATIVE
UNDISTURBED
SOIL
BACKFILL/FILL
ENGINEERED FILL
DRAINAGE
COURSE
GYPSUM
BOARD
WD- BLKG
OR SHIM
PLYWOOD/OSB
/PARTICLE BD
WD- GLUED
/LAMINATED
WOOD-
CONTINUOUS
FRAMING
INSUL/FIRE
SAFING
METAL FLOOR
GRATING
GROUT
RIGID
INSUL/ICF/SIP
/EIFS SYSTEMS
METALS
MORTAR
CMU
ROUGH LOG
WALL
WOOD STUD
BRG WALL
CONC WALL
HOLDOWN
(BLOCKOUT)
STONE/
ROCK WALL
C1
Hx
XXX' - XX"
TOx
NTRUE
NORTH
CONT
MC-x
-xx"
/REF - ---
/REF - ---
INSULATED
PRECAST WALL
SW
-x
SOLID PRECAST
WALL
CONCRETE PROPERTIES
LOCATION
28 DAY
COMPRESSIVE
STRENGTH
ENTRAINED
AIR
SLUMP
MAX W/C
RATIO
FOOTINGS
INTERIOR SLABS
FND WALLS & ALL
OTHER CONC
EXTERIOR SLABS
3,500 PSI
4,500 PSI
4,000 PSI
5,000 PSI
4.0% - 6.0%
5.0% - 7.0%
≤ 3.0%
5.0% - 7.0%
5" +/- 1"
4"+/- 1"
3" +/- 1"
3" +/ - 1"
0.55
0.45
0.5
0.40
MOST COMMONLY USED STRUCTURAL ABBREVIATIONS
SYMBOLS USED AS ABBREVIATIONS:
& AND
L ANGLE
LL DOUBLE ANGLE
@ AT
CL ℄ CENTER LINE
// PARALLEL
d PENNY (NAIL)
┴ PERPENDICULAR
PL PLATE
# POUND OR NUMBER
Ø ROUND OR DIAMETER
ABBREVIATIONS:
(A)--------------------
A/E ARCHITECT/ENGINEER
AB ANCHOR BOLT/ROD
ABV ABOVE
ADDL ADDITIONAL
ADDM ADDENDUM
ADH ADHESIVE
ADJ ADJUSTABLE, ADJACENT,
ADJOINING
AFF ABOVE FINISH FLOOR
AGGR AGGREGATE
AHR ANCHOR, ANCHORAGE
ALT ALTERNATE
APPROX APPROXIMATE
**AR ANCHOR ROD
ARCH ARCHITECT (URAL)
(B)---------------------
BEV BEVELED
BFF BELOW FINISH FLOOR
**BL BRICK LEDGE
BLDG BUILDING
BLW BELOW
**BLK BLOCK (ING)
BM BEAM
BOT BOTTOM
**BO BOTTOM OF
**BOC BOTTOM OF CONCRETE
**BOF BOTTOM OF FOOTING
BRG BEARING
**BRK BRICK
BSMT BASEMENT
BTWN BETWEEN
BU BUILT-UP
(C)---------------------
C CHANNEL
CAM*(C=) CAMBER
CB CARRIAGE BOLT
CU FT CUBIC FEET OR FOOT
CHFR CHAMFER
CIP CAST-IN-PLACE
**CIPC CAST-IN-PLACE CONCRETE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLR CLEAR, CLEARANCE
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECT (ION)
CONSTR CONSTRUCTION
CONT CONTINUOUS, CONTINUE
CONTR CONTRACT (OR)
COORD COORDINATE
CTR CENTER
CU CUBIC
CU YD CUBIC YARD
(D)---------------------
D DEEP, DEPTH, PENNY (NAIL)
DBL DOUBLE
DEMO DEMOLITION, DEMOLISH
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL, DIAGRAM
DIM DIMENSION
DIR DIRECTION
DIV DIVIDE, DIVISION
**DKG DECKING
DL DEAD LOAD
DOUG FIR DOUGLAS FIR
DR DRAIN
DT DRAIN TILE
DWG DRAWING (S)
(E)---------------------
**(E) EXISTING (SEE EXIST)
EA EACH
**EAB EPOXY ANCHOR BOLT
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
**EMB EMBED (ED)
EPS EXPANDED POLYSTYRENE
EQ EQUAL
EQUIP EQUIPMENT
EST ESTIMATE
EW EACH WAY
EXIST EXISTING
EXP EXPANSION, EXPOSED
EXP BT EXPANSION BOLT
EXT EXTERIOR, EXTERNAL
(F)---------------------
FD FLOOR DRAIN
**FND FOUNDATION
FF EL FINISH FLOOR ELEVATION
FIN FINISH (ED)
FLG FLANGE
FLR FILLER, FLOOR (ING)
**FO FACE OF
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FOS FACE OF STUD
**FOW FACE OF WALL
FS FAR SIDE
FT FOOT, FEET
FTG FOOTING
FRMG FRAMING
FUT FUTURE
**FV FIELD VERIFY
(G)---------------------
GA GAGE, GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
**GL GLUE LAMINATED (BEAM)
GLU LAM GLUE LAMINATED (BEAM)
GR BM GRADE BEAM
GRTG GRATING
GYP GYPSUM
GYP BD GYPSUM BOARD
(H)---------------------
H HIGH
**HAB HEADED ANCHOR BOLT
**HAS HEADED ANCHOR STUD
HC HOLLOW CORE
HDR HEADER
HGR HANGER
HORIZ HORIZONTAL
HS HIGH STRENGTH
**HSB HIGH STRENGTH BOLT
**HSS HOLLOW STRUCTURAL SHAPE
HT HEIGHT
(I)---------------------
ID INSIDE DIAMETER
INCL INCLUDE (D), INCLUDING
INFO INFORMATION
INSUL INSULATE (D), INSULATION
INT INTERIOR
INV EL INVERT ELEVATION
(J)---------------------
**JST JOIST
**JT JOINT
(K)---------------------
K THOUSAND (KIP)
**KCJ KEYED CONSTRUCTION JOINT
KIP THOUSAND POUND
KLF KIPS PER LINEAR FOOT
KSF KIPS PER SQUARE FOOT
KSI KIPS PER SQUARE INCH
(L)---------------------
L ANGLE
LAM LAMINATE (ED)
**LB POUND
LF LINEAR FEET
**LGR LEDGER
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LOC LOCATION
LONG LONGITUDINAL
**LSL LAMINATED STRAND LUMBER
LT WT LIGHTWEIGHT
**LVL LAMINATED VENEER LUMBER
LVR LOUVER
(M)---------------------
MACH MACHINE
MB MACHINE BOLT
MATL MATERIAL
MAX MAXIMUM
MBR MEMBER
**MC MISCELLANEOUS CHANNEL
MECH MECHANICAL
MEZZ MEZZANINE
MFD MANUFACTURED
MFR MANUFACTURER
MFR REC MANUFACTURER'S
RECOMMENDATION
MIN MINIMUM
MISC MISCELLANEOUS
MTL METAL
(N)---------------------
**(N) NEW
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
(O)---------------------
OC ON CENTER
OD OUTSIDE DIAMETER
OH DR OVERHEAD DOOR
OPNG OPENING
OPP OPPOSITE
**OSB ORIENTED STRAND BOARD
**OVS OVERSIZED
(P)---------------------
**PAF POWDER ACTUATED
FASTENER
PAR PARALLEL
PCF POUNDS PER CUBIC FOOT
PED PEDESTAL
PERF PERFORATED
PERP PERPENDICULAR
PL PLATE
PLF POUNDS PER LINEAR FOOT
PLYWD PLYWOOD
PNL PANEL
PR PAIR, PIPE RAIL
PRCST PRECAST CONCRETE
PREFAB PREFABRICATE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
**PSL PARALLEL STRAND LUMBER
PT POST TENSION (ED),
PRESSURE TREATED
PVC POLYVINYL CHLORIDE
(R)---------------------
R RADIUS/RISE (R)
RCP REINFORCED CONCRETE PIPE
REF REFERENCE
REINF REINFORCE (D), (ING)
REQ REQUIRE
REQD REQUIRED
REV REVISION (S), REVISED
RO ROUGH OPENING
RS ROUGH SAWN
RVS REVERSE (SIDE)
(S)---------------------
SCHED SCHEDULE
SECT SECTION
SHT SHEET
SHTHG SHEATHING
SIM SIMILAR
**SL SNOW LOAD
SLNT SEALANT
SLV SLEEVE
**SOG SLAB-ON-GRADE
SPEC SPECIFICATION (S)
SQ SQUARE
**SSL SHORT SLOTTED (HOLE)
**SSLT SHORT SLOTTED (HOLE)
TRANSVERSE
SST STAINLESS STEEL
STD STANDARD
STIF STIFFENER
STL STEEL
STRUCT STRUCTURAL
SUB FL SUBFLOOR
SUSP SUSPENDED
**SW SHEAR WALL
SYMM SYMMETRY, SYMMETRICAL
(T)---------------------
T TREAD
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
**TBD TO BE DETERMINED
THD THREAD (ED) (S)
THK THICKNESS
THRU THROUGH
**TL TOTAL LOAD
TO TOP OF
TOB TOP OF BEAM
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOM TOP OF MASONRY
TOP TOP OF PIER
TO PAR TOP OF PARAPET
TOS TOP OF STEEL, SLAB
TO SHTHG TOP OF SHEATHING
TO SUB FL TOP OF SUBFLOOR
TOW TOP OF WALL
**TRANS TRANSVERSE
TRTD TREATED
TS TUBE STEEL
TYP TYPICAL
(U)--------------------
UNO UNLESS NOTED OTHERWISE
(V)---------------------
**V SHEAR
VERT VERTICAL
VIF VERIFY IN FIELD
VR VAPOR RETARDER
VRFY VERIFY
(W)---------------------
W WIDTH
W/ WITH
W/O WITHOUT
**WA WEDGE ANCHOR
WD WOOD
WF (W) WIDE FLANGE
WL WIND LOAD
WLD WELD (ED)
WP WATERPROOFING, WORKING
POINT
**WS WALL STEP
WT WEIGHT
WWF WELDED WIRE FABRIC
(X)---------------------
XPS EXTRUDED POLYSTYRENE
(Y)---------------------
YD YARD
** NOT LISTED IN THE NCS MANUAL
CL
a. WHERE APPLICABLE, SEE SECTION 1705.12, SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE.
b. SPECIFIC REQUIREMENTS FOR SPECIAL INSPECTION SHALL BE INCLUDED IN THE RESEARCH REPORT FOR THE ANCHOR ISSUED BY AN APPROVED SOURCE IN ACCORDANCE WITH 17.8.2 IN ACI 318, OR OTHER QUALIFICATION PROCEDURES. WHERE SPECIFIC REQUIREMENTS ARE NOT PROVIDED, SPECIAL INSPECTION REQUIREMENTS SHALL BE SPECIFIED BY THE REGISTERED DESIGN PROFESSIONAL AND SHALL BE APPROVED BY THE BUILDING OFFICIAL PRIOR TO THE COMMENCEMENT OF THE WORK.
MATERIAL TESTS.
IN THE ABSENCE OF SUFFICIENT DATA OR DOCUMENTATION PROVIDING EVIDENCE OF CONFORMANCE TO QUALITY STANDARDS FOR MATERIALS IN CHAPTERS 19 AND 20 OF ACI 318, THE BUILDING OFFICIAL SHALL REQUIRE TESTING OF MATERIALS IN ACCORDANCE WITH THE APPROPRIATE STANDARDS AND CRITERIA FOR THE MATERIAL IN CHAPTERS 19 AND 20 OF ACI 318.
IBC 2021 TABLE 1705.3 REQUIRED SPECIAL INSPECTION
AND TESTS OF CONCRETE CONSTRUCTION
4. INSPECT ANCHORS POST-INSTALLED IN HARDENED CONCRETE
MEMBERS.b
10. INSPECT ERECTION OF PRECAST CONCRETE MEMBERS.
A. APPLICATION OF PRESTRESSING FORCES.
8. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND
TECHNIQUES.
6. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR
STRENGTH TESTS, PERFORM SLUMP AND AIR CONTENT TESTS, AND
DETERMINE THE TEMPERATURE OF THE CONCRETE.
7. INSPECT CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER
APPLICATION TECHNIQUES
ACI 318: CH. 26.9
ACI 318: 26.10
ACI 318: 26.5.3-26.5.5
ACI 318: 26.5
ASTM C172, ASTM C31,
ACI 318: 26.5, 26.12
ACI 318: 17.8.2.4,
ACI 318: 17.8.2
X
X
X
X
X
X
ACI 318: 26.13.1.3
1908.9
1908.6, 1908.7, 1908.8
3. INSPECT ANCHORS CAST IN CONCRETE.
2. REINFORCING BAR WELDING:
1. INSPECTION REINFORCEMENT, INCLUDING PRESTRESSING
TENDONS, AND VERIFY PLACEMENT
TYPE
ACI 318 CH 20, 25.2,
25.3, 26.6.1-26.6.3
REFERENCED
STANDARDa
CONTINUOUS
SPECIAL
INSPECTION
X
AWS D1.4,
ACI 318: 26.6.4
IBC REFERENCE
1908.4
X
ACI 318: 17.8.2
5. VERIFY USE OF REQUIRED DESIGN MIX.
ACI 318: CH. 19,
26.4.3, 26.4.4
X
1904.1, 1904.2
12. INSPECT INSTALLATION TOLERANCES OF PRECAST CONCRETE DIAPHRAGM
CONNECTIONS FOR COMPLIANCE WITH ACI 550.5.
ACI 318: 26.13.1.3X
9. INSPECT OF PRESTRESSED CONCRETE FOR:
B. GROUTING OF BONDED PRESTRESSING TENDONS.
11. FOR PRECAST CONCRETE DIAPHRAGM CONNECTIONS OR REINFORCEMENT
AT JOINTS CLASSIFIED AS MODERATE OR HIGH DEFORMABILITY ELEMENTS
(MDE OR HDE) IN STRUCTURES ASSIGNED TO SEISMIC DESIGN CATEGORY C,
D, E, OR F, INSPECT SUCH CONNECTIONS AND REINFORCEMENT IN THE
FIELD FOR:
X
A. VERIFY WELDABILITY OF REINFORCING BARS OTHER THAN ASTM A706.
X
B. INSPECT SINGLE-PASS FILLET WELDS, MAXIMUM 5/16".
C. INSPECT ALL OTHER WELDS
A. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR
UPWARDLY INCLINED ORIENTATIONS TO RESIST SUSTAINED
TENSION LOADS.
B. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT
DEFINED IN 4A.
X
X
X
PERIODIC
SPECIAL
INSPECTION
REQUIRED ON
PROJECT
YES
NO
YES
YES
YES
YES
YES
NO
YES
YES
NO
X ACI 318: 26.11.2
14. INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS OF THE
CONCRETE MEMBER BEING FORMED.
ACI 318: 26.11.1.2(b)X
13. VERIFY IN-SITU CONCRETE STRENGTH, PRIOR TO STRESSING OF TENDONS
IN POST-TENSIONED CONCRETE AND PRIOR TO REMOVAL OF SHORES AND
FORMS FROM BEAMS AND STRUCTURAL SLABS.
NO
YES
A. INSTALLATION OF EMBEDDED PARTS.
B. COMPLETION OF THE CONTINUITY OF REINFORCEMENT ACROSS JOINTS.
C. COMPLETION OF CONNECTIONS IN THE FIELD.
X
X
X
ACI 550.5 -
NO
NO
1. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB
SPECIFICATIONS AND ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND
SITE DRAWINGS. CONSULT THESE DRAWINGS FOR SLEEVES, DEPRESSIONS AND
OTHER DETAILS NOT SHOWN ON STRUCTURAL DRAWINGS.
2. ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. ANY
DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE
PROCEEDING WITH THE AFFECTED PART OF THE WORK.
3. THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE
BUILDING IS COMPLETE. IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO
DETERMINE ERECTION PROCEDURES AND SEQUENCE TO ENSURE SAFETY OF THE
BUILDING AND ITS COMPONENTS DURING ERECTION. THIS INCLUDES THE ADDITION
OF NECESSARY SHORING, SHEETING, TEMPORARY BRACING (AND ACCOMPANYING
FOOTINGS), GUYS OR TIE-DOWNS.
4. ADDITIONAL OBSERVATIONS AS A RESULT OF REJECTION OF WORK COMPLETED
AND/OR ADDITIONAL OBSERVATIONS DUE TO THE DEFICIENCIES IN WORK OBSERVED
WILL BE AT THE EXPENSE OF THE CONTRACTOR.
5. ALL STRUCTURAL SHOP DRAWINGS TO BE REVIEWED BY JOB SUPERINTENDENT IN
ADDITION TO ALL PERSONNEL DEEMED NECESSARY BY CONTRACTOR PRIOR TO
SUBMITTAL TO ENGINEER FOR APPROVAL.
6. ALL SHOP DRAWINGS TO BE REVIEWED BY ALBERTSON ENGINEERING INC. SHALL
HAVE ELECTRONIC COPIES PROVIDED TO ALBERTSON ENGINEERING INC. FOR
REVIEW. AN ELECTRONIC MARKED SET OF THOSE DRAWINGS WILL BE RETURNED TO
THE CONTRACTOR. NO ADDITIONAL HARD COPIES OF THE SHOP DRAWINGS NEED TO
BE PROVIDED TO ALBERTSON ENGINEERING INC., ALTHOUGH OTHER PARTIES MAY
REQUIRE HARD COPIES OF THE MARKED UP DRAWINGS. THESE REQUIREMENTS ARE
IN ADDITION TO THE TYPICAL PROJECT SHOP DRAWING SUBMITTAL REQUIREMENTS
STATED IN THE PROJECT SPECIFICATIONS.
7. THE DESIGN OF THE STRUCTURE SHOWN IN THESE CONSTRUCTION DOCUMENTS IS
FOR THE ONE-TIME USE AT THE SPECIFIC SITE REFERENCED IN THE TITLEBLOCK.
FOUNDATIONS ARE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 1,500
PSF ON EXISTING SOILS. BEFORE CONSTRUCTION COMMENCES, SOIL BEARING
CAPACITY SHALL BE VERIFIED BY A SUBSURFACE INVESTIGATION, A CERTIFIED TESTING
LABORATORY, WHOSE REPORT SHALL INCLUDE ANALYSIS AND RECOMMENDATIONS
FOR SITE PREPARATION IN ORDER TO BEAR THE FOUNDATION LOADS. ABOVE REPORT
SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER FOR REVIEW BEFORE
FOUNDATION CONSTRUCTION BEGINS.
MINIMUM SLEEVE SPACING SHALL BE TWO DIAMETERS CENTER TO CENTER TO THE
LARGER SLEEVE OR 6" CLEAR BETWEEN SLEEVES, WHICHEVER IS GREATER. PRIOR TO
CONSTRUCTION SLEEVE LOCATIONS AND SIZES SHALL BE APPROVED BY THE
STRUCTURAL ENGINEER OF RECORD.
SHALL BE A POLYMER INJECTION SYSTEM SUCH AS HILTI-HY 200 EPOXY, OR APPROVED
EQUAL, INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS INSTRUCTIONS.
INSTALLERS SHALL BE TRAINED BY THE MANUFACTURER'S REPRESENTATIVE.
1. SHALL BE A36 THREADED ROD. PROVIDE HOT DIP GALVANIZE FINISH ON ALL
ANCHOR BOLTS PERMANENTLY EXPOSED TO EXTERIOR OR IN CONTACT WITH
PRESSURE TREATED LUMBER.
2. THREADED ROD EMBEDMENT DEPTH SPECIFIED IN THE DRAWINGS SHALL BE FROM
TOP OF CONCRETE TO TOP OF DOUBLE NUT.
1. CONCRETE TESTING SHALL BE PAID FOR BY THE OWNER. TESTING LABORATORY
SHALL PERFORM THE FOLLOWING TEST ON CAST-IN-PLACE CONCRETE:
A. ASTM C143 - "STANDARD TEST METHOD FOR SLUMP OF PORTLAND CEMENT
CONCRETE."
B. ASTM C39 - "STANDARD TEST METHOD FOR COMPRESSIVE STRENGTH OF
CYLINDRICAL CONCRETE SPECIMENS. A SEPARATE TEST SHALL BE CONDUCTED
FOR EACH CLASS, FOR EVERY 50 CUBIC YARDS (OR FRACTION THEREOF), PLACED
PER DAY. REQUIRED CYLINDER(S) QUANTITIES AND TEST AGE AS FOLLOWS:
a. AT 7 DAYS
b. AT 28 DAYS
C. PROVIDE ONE ADDITIONAL RESERVE CYLINDER TO BE TESTED UNDER THE
DIRECTION OF THE ENGINEER, IF REQUIRED. IF 28 DAY STRENGTH IS ACHIEVED,
THE ADDITIONAL CYLINDER(S) MAY BE DISCARDED.
D. TESTING SHALL BE BASED UPON CONCRETE TAKEN AT POINT OF PLACEMENT.
E. IN ADDITION TO TYPICAL TESTING REQUIREMENTS, SLUMP AND AIR CONTENT
SAMPLES SHALL BE TAKEN AT BEGINNING OF FIRST TRUCK PRIOR TO ANY
PLACEMENT AND REPEATED AT THE MIDDLE OF FIRST TRUCK. CONCRETE
PLACEMENT SHALL NOT START IF INITIAL TEST(S) FAIL AND SHALL NOT CONTINUE
OF TEST TAKEN AT MIDDLE OF FIRST LOAD FAILS.
F. IF ANY SLUMP OR AIR CONTENT FAILS DURING PLACEMENT, TESTS SHALL BE
IMMEDIATELY REPORTED AND RETAKEN. IF RETAKEN TESTS FAIL THEN ALL
SUBSEQUENT LOADS MUST BE TESTED AT ARRIVAL AND TEST MUST SHOW
COMPLIANCE…