Updated Contractor QA.docx
DOCX document 2 MB Posted
- Attached to
- Y1DA--437-23-103 Update Wing 4B Federal contract opportunity
- Solicitation number
- 36C26325B00090002
About this file
The document is a Contractor Q&A file for the VA Fargo Medical Center's Wing 4B Renovation Project (Solicitation Number: 36C26325B0009), detailing critical project specifications and contractor requirements. The project involves renovating a locked mental health ward, with specific guidelines for construction, phasing, patient safety, and operational constraints. Key requirements include maintaining patient safety during construction, using proper egress routes, implementing strict sally port access protocols, and ensuring minimal patient disruption during the renovation.
The Q&A document addresses multiple technical and operational aspects, including installation of VA-provided equipment (beds, tables, night stands), asbestos analysis (completed in 2022), construction hours (Monday-Friday, 8:00 AM to 4:00 PM, with limited after-hours work from 5-7 PM), and specific staffing requirements. Contractors must adhere to strict badging processes, with a 90-day initial period allocated for background checks and ID badge preparation. Critical project constraints include maintaining 1-hour-rated hard partitions, preventing patient elopement, using ligature-resistant construction methods, and coordinating patient relocations with VA nursing staff during different construction phases.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C26325B0009 0002.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Name: Update Wing 4B Project Number: 437-23-103 Solicitation Number: 36C26325B0009 RE: Contractor Questions with Government Responses
Question: 1 Please confirm if we are able to utilize the stairways without going thru the sally Port.
VHA Response: Outside of egress purposes, it is not allowed as it is an elopement risk for patients. During phases where the existing sally port is under construction, a temporary sally port must be maintained and used to maintain safety standards for our patients.
Will the stairways be locked and inaccessible?
VHA Response: The stairways during normal operations (when the existing sally port is not under construction) are for emergency egress routes only. When the existing sally port is under construction, a temporary sally port must be maintained and used to maintain safety standards for our patients.
Will we be able to provide in and out checkouts at the stairways?
VHA Response: The stairways during normal operations (when the existing sally port is not under construction) are for emergency egress routes only. When the existing sally port is under construction, a temporary sally port must be maintained and used to maintain safety standards for our patients.
Question: 2 Is there any supplied materials by owner that require factory trained technicians?
VHA Response: The VA supplied materials are outlined in drawing A1.00 Floor Plan. These VA provided, Contractor installed (V/C) items include 11-27: Existing Television, 12-01: Bolted Down Patient Bed, 12-02: Bolted Down Dining Table, and 12-03: Bolted Down Night Stand. These listed items do not require factory trained technicians for installation.
Question: 3 Are we allowed to utilize our Procore system for submittals?
VHA Response: Yes, there is precedent for this. See the Contracting Officer and/or Contracting Specialist for details; the COR and alternate COR for the project will need to be given access as approvers, as well as the A/E stakeholders/approval authorities. Fair and reasonable requests shall be considered.
Are we allowed to utilize our Procore system for management of project RFI’s etc.?
VHA Response: Yes, there is precedent for this. See the Contracting Officer and/or Contracting Specialist for details; the COR and alternate COR for the project will need to be given access as approvers, as well as the A/E stakeholders/approval authorities. Fair and reasonable requests shall be considered.
Question: 4 Can the superintendent perform duel hat responsibility’s functions as superintendent and quality control manager?
VHA Response: No, the superintendent shall not be the quality control manager. Superintendents must be full-time superintendents: superintending solely for this project and no others.
Question: 5 Can the Site Safety Officer also perform the superintendent and quality control functions ie Triple hat Functions?
VHA Response: The Site Safety Officer may be either the superintendent or the quality control manager or may be a separate individual.
The superintendent shall not be the quality control manager. Superintendents must be full-time superintendents: superintending solely for this project and no others.
Question: 6 If the substrates after flooring removal is completed and does not meet the substrate requirements this would indicate an unforeseen site condition?
VHA Response: If the general contractor had no way of inspecting nor anticipating substrate condition prior to floor removal, and removing the flooring revealed deficient substrates, this may be an unforeseen site condition; determination is up to the Contracting Officer and/or Contracting Specialist to authorize a decision. In no other case shall this be assumed nor authorized. Fair and reasonable requests shall be considered.
Are we required to provide All of the floors to include a moisture remediation coating?
VHA Response: Yes, this is required.
Question: 7 Has there been an asbestos flooring analysis performed on the flooring being removed?
VHA Response: Yes, in 2022. Analysis report attached in related response below.
Question: 8 Drawing G1.00 Phasing notes 1. THE CONTRACTOR SHALL ACCOMPLISH THE WORK FOR EACH PHASE WITH MINIMAL INTERRUPTIONS AND AGITATION OF PATIENTS. IF PATIENTS BECOME AGITATED, WORK WILL BE SUSPENDED AND MAY START AGAIN WITH APPROVAL OF THE CO,CS, COR OR THE NURSE MANAGER.
Will we be allowed additional contact time for extended shutdowns if we document the shutdown periods?
VHA Response: Consult the Contracting Officer and/or Contracting Specialist for details, as they are the authorities for this. Fair and reasonable requests shall be considered.
Question: 9 Drawing G1.00 Phasing notes 6. CONTRACTOR'S SCHEDULE HAS TO INCLUDE VA MOVE TIME.
Can you provide the amount of time to allocate for the VA to move into the spaces?
VHA Response: Amount of time necessary for VA patients and staff to move from impacted areas to areas not impacted by a given phase will depend upon the patient census and should be coordinated daily between the COR, general contractor, and 4B nursing staff. At no point shall contractor(s) presume nor be authorized to begin work on-site without clearing status of patients and nurses with the COR. A minimum of 2 days per phase shall be provided for relocation of patients, staff, and equipment.
Question: 10 Drawing G1.00 Phasing notes 7. THE PROJECT DURATION HAS 90 DAYS INCLUDED IN THE BEGINNING OF THE JOB FOR THE GENERAL CONTRACTOR AND SUBCONTRACTORS TO COORDINATE WITH THE VA FOR ID BADGES. BACKGROUND CHECKS, ETC. WILL NEED TO BE COMPLETED FOR ID BADGING. NO CONTRACTOR SHALL BE ABLE TO BE ON A JOB SITE WITHOUT THE OFFICIAL ID BADGE. TRAINING IS REQUIRED FOR ALL CONTRACTORS WHO WISH TO ACCESS THE SITE.
If the badging process takes more than 90 days are we able to extend the contract time?
VHA Response: If the root cause of the badging process delay lies with the VA, the Contracting Officer and/or Contracting Specialist may authorize an extension. In no other case shall this be assumed nor authorized. Fair and reasonable requests shall be considered.
Question: 11 Drawing G1.00 Phasing notes 8. REMODEL WING 4B – PHASING SCHEDULE STANDARD WORK HOURS FOR THE FARGO VA MEDICAL CENTER ARE MONDAY–FRIDAY, 8:00 A.M. TO 4:00 P.M. AFTER HOURS WORK MAY BE REQUIRED BY THE CONTRACTOR PENDING NOISE, VIBRATION OR OTHER CONSTRUCTION IMPACTS THAT WOULD LIMIT CARE TO PATIENTS.
Can you provide the after-work hours start time and end time?
VHA Response: As the mental health ward houses patient sleeping quarters, the expected after-work hours shall be from 1700 (5 PM) until 1900 (7 PM) local time, to not disturb sleeping patients after 7 PM, nor to disrupt group therapy sessions that occur during normal business hours, nor to disrupt the patients’ morning routines.
Question: 12 Drawing G1.00 Pre-Construction Phasing Activities The department is to remain operational, for work in phase 2 will patients and staff be occupying or using this area?
VHA Response: The patients and staff shall not be inside of active construction areas. Areas not under construction during phase 2 will be considered occupied by patients and staff.
Will patients and staff be occupying or using Phase 1 area?
VHA Response: The patients and staff shall not be inside of active construction areas. Areas not under construction during phase 1 will be considered occupied by patients and staff.
Will patients and staff be occupying or using Phase 3 area?
VHA Response: The patients and staff shall not be inside of active construction areas. Areas not under construction during phase 3 will be considered occupied by patients and staff.
Question: 13 Drawing G2.00 Detail 4 - Are we allowed to provide temporary barriers to underside of ceiling system in lieu of deck?
VHA Response: All changes to allow construction activities must meet NFPA 101, outlined ICRA and PCRA requirements (Class IV), be represented with ILSMs as applicable and prevent patient elopement to maintain safety requirements for patients and staff.
Question: 14 Drawing G2.00 Detail 4 - Would light containment systems similar to STARC be utilized in lieu of 1-hour partitions?
VHA Response: No, STARC and similar light containment systems are not robust enough to prevent patient elopement and are therefore not acceptable solutions in lieu of 1-hour-rated hard partitions and barriers.
Question: 15 Owner provided equipment Can you provide product data, delivery times for equipment to incorporated into work which is owner supplied and contractor installed?
VHA Response: Please find attached the product information for the new beds, night stands, tables, and chairs supplied by VA and to be installed by contractor:
Question: 16 Spec Section 01 33 23 Section 1.10.D states the VA review period is 21 days.
Does that include the VA provided AE review time as well?
VHA Response: The A/E review period is included in the VA’s review period if the RFI/submittal is disbursed simultaneously and in parallel.
However, the total review period of both the VA review and the A/E review shall not exceed 21 days if not disbursed simultaneously and in parallel, with a guarantee of 21 days of review provided to the VA for submittals and a guarantee of 14 days of review provided to the VA for RFIs.
Question: 17 Will any of the commissioning for this project require commissioning services for existing systems in the building?
VHA Response: Electrical and HVAC commissioning may be required; onus on general contractor to provide and retain commissioning services as needed.
Question: 18 General Note – Was there an asbestos study performed in the remodeled areas.?
VHA Response: Yes, there was in 2022.
Would you Please provide the asbestos report in the bidding documents.
VHA Response: Yes. Attached here:
Relevant items: rows 101-177: rooms in wing 4B. ACM consists of nonfriable transite panels and pucks remaining from removal of steam heaters.
Question: 19 Will time be added to the project is the badging period goes beyond the 120-day allotment due to Government review time & process?
VHA Response: If the root cause of the badging process delay lies with the VA, the Contracting Officer and/or Contracting Specialist may authorize an extension. In no other case shall this be assumed nor authorized. Fair and reasonable requests shall be considered.
Assuming the GC is moving forward with badging submissions at a reasonable pace?
VHA Response: If the root cause of the badging process delay lies with the VA, the Contracting Officer and/or Contracting Specialist may authorize an extension. In no other case shall this be assumed nor authorized. Fair and reasonable requests shall be considered.
Question: 20 If badging requirements change after the award, to a laborious method or requirements, would this be justifiable for additional costs?
VHA Response: Consult the Contracting Officer and/or Contracting Specialist for details, as they are the authorities for this. Fair and reasonable requests shall be considered.
Question: 21 Is there any elevation drawings for the window specifically?
VHA Response: Yes, See attached AutoCAD drawing and/or .pdf for more details:
Looking to confirm window sizes for the film SOW and painting take offs if these can be provided, please?
FourFront Design as the CPS engineers Response: From existing drawings the existing window size at the nurse station is roughly 24”x32”; this was verified by VHA staff. See above attached AutoCAD drawing and/or .pdf for more details.
Question: 22 If days are lost to the necessary and unforeseen patient care, will these be added into the Period of Performance later to compensate?
VHA Response: Consult the Contracting Officer and/or Contracting Specialist for details, as they are the authorities for this. Fair and reasonable requests shall be considered.
Question: 23 Ligature resistant construction partitions and hardware, including handles. Is there a make and model to reference for pricing and procurement?
VHA Response: For temporary construction partitions, no specific ligature resistant hardware manufacturer required. Follow drawings and specifications for temp construction barriers and per Fargo VA requirements.
Question: 24 Hand Painted signs. Are these to match existing style or be updated/revised?
VHA Response: The project should maintain station standards for signage.
Is there a stencil available or can the General Contractor submit a stencil for approval?
VHA Response: The VHA does not have a stencil for signage. A submitted stencil may be approved in conformance with station standards.
Question: 25 Can the SSHO & Superintendent roles be a dual-hatted individual or must they be two separate people?
VHA Response: The Site Safety Officer may be either the superintendent or the quality control manager or may be a separate individual. The superintendent shall not be the quality control manager. Superintendents must be full-time superintendents: superintending solely for this project and no others.
Question: 26 Will badging requirements be implemented for testing agency staff who will only be onsite 1 or 2 times throughout the project period of performance?
VHA Response: Testing agency staff and subcontractor staff on-site less than 15 days per calendar year may be provisioned a temporary badge with escort in lieu of full background check and badging process.
Would an escort be acceptable for them?
VHA Response: Testing agency staff and subcontractor staff onsite less than 15 days per calendar year may be provisioned a temporary badge with escort in lieu of full background check and badging process.
Photo of yellow.pdf image3.emf
4B ACM Analysis.xlsx InspectionDataF
BuildingSearch FloorSearch RoomSearch ACMOnly SampleSearch Building Floor Room Number Suspect Material Present Material Identification Size Exterior Description Quantity Units Condition Asbestos Content Asbestos Friability Sample Reference Notes ACM?
4 9 4 4A-01 2' x 4' Ceiling Tile CT-9-1 Widthwise Fissures 115 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-03 2' x 4' Ceiling Tile CT-9-1 Widthwise Fissures 115 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-05 2" Ceramic Floor Tile Gray 180 sf Non ACM Non-Suspect New FALSE
4 9 4 4A-05 4" Ceramic Wall Tile Cream 225 sf Non ACM Non-Suspect New FALSE
4 9 4 4A-05 2' x 4' Ceiling Tile CT-9-1 Widthwise Fissures 180 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-07 2' x 4' Ceiling Tile CT-9-1 Widthwise Fissures 180 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-07 4" Ceramic Wall Tile Cream 225 sf Non ACM Non-Suspect New FALSE
4 9 4 4A-07 2" Ceramic Floor Tile Gray 180 sf Non ACM Non-Suspect New FALSE
4 9 4 4A-15 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 420 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-16 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 100 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-17 4" Ceramic Wall Tile Cream 180 sf Non ACM Non-Suspect New FALSE
4 9 4 4A-17 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 100 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-19 No Suspect Material Non ACM FALSE
4 9 4 4A-20 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-20 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 200 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-22 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-22 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 145 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-22 Corridor 12" x 12" Floor Tile and Mastic FT-9-5 White w/Gray Streaks 875 sf None Detected Non ACM 09-014 FALSE
4 9 4 4A-22 Corridor 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 875 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-23 Transite Panel/Pucks (3) s Black 30 lf Good Assumed ACM Non-Friable Assumed (3) Register Cabinets TRUE
4 9 4 4A-23 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 315 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-23A 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 20 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-24 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-24 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 145 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-26 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-26 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 145 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-27 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-27 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 145 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-28 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-28 12" x 12" Floor Tile and Mastic FT-9-2 Tan w/Brown and White Specks 145 sf None Detected Non ACM 09-002 FALSE
4 9 4 4A-28 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 145 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-29 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-29 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 145 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-30 Transite Panel/Pucks (2) s Black 20 lf Good Assumed ACM Non-Friable Assumed (2) Register Cabinets TRUE
4 9 4 4A-30 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 200 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-31 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-31 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 145 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-32 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-32 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 145 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-33 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 145 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-34 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-34 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 145 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-35 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-35 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 115 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-36 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 115 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-38 2" Ceramic Floor Tile Gray 80 sf Non ACM Non-Suspect New FALSE
4 9 4 4A-38 4" Ceramic Wall Tile Gray 120 sf Non ACM Non-Suspect New FALSE
4 9 4 4A-38 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 80 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-40 No Suspect Material Non ACM FALSE
4 9 4 4A-42 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-42 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 120 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-42 Corridor 12" x 12" Floor Tile and Mastic FT-9-5 White w/Gray Streaks 875 sf None Detected Non ACM 09-014 FALSE
4 9 4 4A-42 Corridor 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 875 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-43 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-43 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 150 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-44 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-44 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 150 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-45 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-45 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 120 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-46 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-46 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 120 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-47 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-47 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 150 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-48 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-48 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 120 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-50 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-50 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 200 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-51 No Suspect Material Non ACM FALSE
4 9 4 4A-52 No Access Non ACM FALSE
4 9 4 4A-53 2" Ceramic Floor Tile Gray 100 sf Non ACM Non-Suspect New FALSE
4 9 4 4A-53 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 100 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-53 4" Ceramic Wall Tile Gray 150 sf Non ACM Non-Suspect New FALSE
4 9 4 4A-54 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-54 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 220 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-55 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-55 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 150 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-56 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-56 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 150 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-57 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-57 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 150 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-58 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-58 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 150 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-59 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-59 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 150 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-60 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-60 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 150 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-61 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-61 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 150 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-62 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-62 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 150 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-63 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-63 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 150 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-64 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-64 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 150 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-67 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-67 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 150 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-68 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4A-68 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 150 sf None Detected Non ACM 09-006 FALSE
4 9 4 4A-70 No Access Non ACM FALSE
4 9 4 4B-02 2' x 4' Ceiling Tile CT-9-1 Widthwise Fissures 115 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-04 2' x 4' Ceiling Tile CT-9-1 Widthwise Fissures 115 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-06 2' x 4' Ceiling Tile CT-9-1 Widthwise Fissures 115 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-10 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 115 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-12 2' x 4' Ceiling Tile CT-9-1 Widthwise Fissures 130 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-14 2' x 4' Ceiling Tile CT-9-1 Widthwise Fissures 115 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-16 2' x 4' Ceiling Tile CT-9-1 Widthwise Fissures 200 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-19 Occupied Non ACM FALSE
4 9 4 4B-20 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 300 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-23 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 125 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-23 12" x 12" Floor Tile and Mastic FT-9-2 (Under Carpet) Tan w/Brown and White Specks 125 sf None Detected Non ACM 09-002 (Under Carpet) FALSE
4 9 4 4B-23 Corridor 12" x 12" Floor Tile and Mastic FT-9-2 Tan w/Brown and White Specks 430 sf None Detected Non ACM 09-002 FALSE
4 9 4 4B-23 Corridor 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 430 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-24 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 125 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-24 12" x 12" Floor Tile and Mastic FT-9-2 (Under Carpet) Tan w/Brown and White Specks 125 sf None Detected Non ACM 09-002 (Under Carpet) FALSE
4 9 4 4B-26 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 125 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-26 12" x 12" Floor Tile and Mastic FT-9-2 (Under Carpet) Tan w/Brown and White Specks 125 sf None Detected Non ACM 09-002 (Under Carpet) FALSE
4 9 4 4B-36 12" x 12" Floor Tile and Mastic FT-9-2 (Under Carpet) Tan w/Brown and White Specks 200 sf None Detected Non ACM 09-002 (Under Carpet) FALSE
4 9 4 4B-36 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 200 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-40 12" x 12" Floor Tile and Mastic FT-9-2 Tan w/Brown and White Specks 130 sf None Detected Non ACM 09-002 FALSE
4 9 4 4B-42 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4B-42 Sheet Vinyl Floor Cream 100 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-43 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4B-43 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 130 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-44 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4B-44 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 130 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-45 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4B-45 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 130 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-46 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4B-46 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 130 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-47 Sheet Vinyl Floor Cream 100 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-47 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 100 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-48 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4B-48 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 130 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-49 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 9 4 4B-49 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 130 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-50 2" Ceramic Floor Tile Gray 100 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-50 4" Ceramic Wall Tile Cream 150 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-55 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 75 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-55A 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 115 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-57 Sheet Vinyl Floor Gray Mosaic 130 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-57A Epoxy Floor Gray 45 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-58 Sheet Vinyl Floor Gray Mosaic 130 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-58 Corridor Sheet Vinyl Floor Gray Mosaic 400 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-58A Epoxy Floor Gray 45 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-59 Sheet Vinyl Floor Gray Mosaic 130 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-59A Epoxy Floor Gray 45 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-60 Sheet Vinyl Floor Gray Mosaic 130 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-60A Epoxy Floor Gray 45 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-62 Sheet Vinyl Floor Gray Mosaic 100 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-63 Sheet Vinyl Floor Gray Mosaic 130 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-63A Epoxy Floor Gray 45 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-64 No Suspect Materials Non ACM FALSE
4 9 4 4B-64A No Suspect Materials Non ACM FALSE
4 9 4 4B-65 Sheet Vinyl Floor Gray Mosaic 220 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-66 Sheet Vinyl Floor Gray Mosaic 50 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-67 Sheet Vinyl Floor Gray Mosaic 50 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-70 Transite Panel/Pucks Black 20 lf Good Assumed ACM Non-Friable Assumed (2) Register Cabinets TRUE
4 9 4 4B-70 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 400 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-70A 2" Ceramic Floor Tile Gray 25 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-70A 4" Ceramic Wall Tile Cream 50 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-70A 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 25 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-70B 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 130 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-70B Sheet Vinyl Floor Gray Mosaic 130 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-71 No Suspect Materials Non ACM FALSE
4 9 4 4B-72 12" x 12" Floor Tile and Mastic FT-9-2 Tan w/Brown and White Specks 130 sf None Detected Non ACM 09-002 FALSE
4 9 4 4B-72A Epoxy Floor Gray 25 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-73 12" x 12" Floor Tile and Mastic FT-9-2 Tan w/Brown and White Specks 130 sf None Detected Non ACM 09-002 FALSE
4 9 4 4B-73A Epoxy Floor Gray 25 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-74 12" x 12" Floor Tile and Mastic FT-9-2 Tan w/Brown and White Specks 130 sf None Detected Non ACM 09-002 FALSE
4 9 4 4B-74A Epoxy Floor Gray 25 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-75 12" x 12" Floor Tile and Mastic FT-9-2 Tan w/Brown and White Specks 130 sf None Detected Non ACM 09-002 FALSE
4 9 4 4B-75 Corridor 12" x 12" Floor Tile and Mastic FT-9-2 Tan w/Brown and White Specks 400 sf None Detected Non ACM 09-002 FALSE
4 9 4 4B-75 Corridor 2' x 2' Ceiling Tile CT-9-3 Long Fissures w/Pinholes 400 sf None Detected Non ACM 09-006 FALSE
4 9 4 4B-75A Epoxy Floor Gray 25 sf Non ACM Non-Suspect New FALSE
4 9 4 4B-76 12" x 12" Floor Tile and Mastic FT-9-2 Tan w/Brown and White Specks 130 sf None Detected Non ACM 09-002 FALSE
4 9 4 4B-76A Epoxy Floor Gray 25 sf Non ACM Non-Suspect New FALSE
4 46 4 4C-01 2' x 2' Ceiling Tile CT-1 2' x 2' Long Fissures 10 sf Good None Detected Non ACM 46-002 FALSE
4 46 4 4C-01 Sheet Vinyl Floor Gray 10 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-02 2' x 2' Ceiling Tile CT-1 2' x 2' Long Fissures 40 sf Good None Detected Non ACM 46-002 FALSE
4 46 4 4C-02 Sheet Vinyl Floor Gray 40 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-03 2" Ceramic Flooring 2" Gray 50 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-03 4" Ceramic Wall Tile 4" Cream 100 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-03 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 50 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-05 12" x 12" Vinyl Floortile FT-7 12" Brn/Green/Red/Blk Specks (stick down) 75 sf Good None Detected Non ACM 46-016 FALSE
4 46 4 4C-05 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 75 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-06 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 50 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-06 Sheet Vinyl Floor Brown 50 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-07 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 220 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-07 Corridor 2' x 2' Ceiling Tile CT-1 2' x 2' Long Fissures 350 sf Good None Detected Non ACM 46-002 FALSE
4 46 4 4C-07 Corridor Sheet Vinyl Floor Multi-color Mosaic 350 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-08 Sheet Vinyl Floor Brown 50 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-08 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 50 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-10 Sheet Vinyl Floor Gray 115 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-10 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 115 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-11 Sheet Vinyl Floor Gray 140 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-11 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 140 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-12 Sheet Vinyl Floor Brown 140 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-12 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 140 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-13 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 140 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-13 Sheet Vinyl Floor Brown 140 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-14 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 140 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-14 Sheet Vinyl Floor Brown 140 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-15 2' x 2' Ceiling Tile CT-1 2' x 2' Long Fissures 300 sf Good None Detected Non ACM 46-002 FALSE
4 46 4 4C-15 Corridor Sheet Vinyl Floor Multi-color Mosaic 300 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-15 Corridor 2' x 2' Ceiling Tile CT-1 2' x 2' Long Fissures 300 sf Good None Detected Non ACM 46-002 FALSE
4 46 4 4C-16 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 140 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-16 Sheet Vinyl Floor Brown 140 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-17 Sheet Vinyl Floor Brown 140 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-17 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 140 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-18 Sheet Vinyl Floor Brown 115 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-18 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 115 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-20 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 115 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-20 Sheet Vinyl Floor Brown 115 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-21 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 115 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-21 Sheet Vinyl Floor Brown 115 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-22 Sheet Vinyl Floor Brown 115 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-22 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 115 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-23 12" x 12" Vinyl Floortile FT-7 12" Brn/Green/Red/Blk Specks (stick down) 125 sf Good None Detected Non ACM 46-016 FALSE
4 46 4 4C-23 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 125 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-23A 2" Ceramic Flooring 2" Gray 50 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-23A 4" Ceramic Wall Tile 4" Cream 100 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-23A 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 50 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-24 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 100 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-24 12" x 12" Vinyl Floortile FT-7 12" Brn/Green/Red/Blk Specks (stick down) 100 sf Good None Detected Non ACM 46-016 FALSE
4 46 4 4C-24 Corridor Sheet Vinyl Floor Multi-color Mosaic 900 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-24 Corridor 2' x 2' Ceiling Tile CT-1 2' x 2' Long Fissures 900 sf Good None Detected Non ACM 46-002 FALSE
4 46 4 4C-25 No Suspect Material 2' x 2' Metal Ceiling sf Non ACM 2' x 2' Metal Ceiling FALSE
4 46 4 4C-26 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 120 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-27 12" x 12" Vinyl Floortile FT-7 12" Brn/Green/Red/Blk Specks (stick down) 120 sf Good None Detected Non ACM 46-016 FALSE
4 46 4 4C-28 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 120 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-29 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 120 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-30 2' x 2' Ceiling Tile CT-1 2' x 2' Long Fissures 350 sf Good None Detected Non ACM 46-002 FALSE
4 46 4 4C-31 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 60 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-32 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 60 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-33 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 60 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-34 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 130 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-35 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 130 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-39 2' x 2' Ceiling Tile CT-1 2' x 2' Long Fissures 250 sf Good None Detected Non ACM 46-002 FALSE
4 46 4 4C-40 2' x 2' Ceiling Tile CT-1 2' x 2' Long Fissures 480 sf Good None Detected Non ACM 46-002 FALSE
4 46 4 4C-40 Corridor 2' x 2' Ceiling Tile CT-1 2' x 2' Long Fissures 1,030 sf Good None Detected Non ACM 46-002 FALSE
4 46 4 4C-40 Corridor Sheet Vinyl Floor Multi-color Mosaic 1,030 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-44 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 150 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-45 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 250 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-46 Sheet Vinyl Floor Brown 50 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-46 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 50 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-47 Sheet Vinyl Floor Brown 50 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-47 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 50 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-48 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 240 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-49 12" x 12" Vinyl Floortile FT-7 12" Brn/Green/Red/Blk Specks (stick down) 155 sf Good None Detected Non ACM 46-016 FALSE
4 46 4 4C-49 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 155 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-50 12" x 12" Vinyl Floortile FT-7 12" Brn/Green/Red/Blk Specks (stick down) 155 sf Good None Detected Non ACM 46-016 FALSE
4 46 4 4C-50 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 155 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-51 12" x 12" Vinyl Floortile FT-7 12" Brn/Green/Red/Blk Specks (stick down) 130 sf Good None Detected Non ACM 46-016 FALSE
4 46 4 4C-51 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 130 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-52 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 100 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-52 12" x 12" Vinyl Floortile FT-7 12" Brn/Green/Red/Blk Specks (stick down) 100 sf Good None Detected Non ACM 46-016 FALSE
4 46 4 4C-55 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 115 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-55 2" Ceramic Flooring 2" Gray 115 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-55 4" Ceramic Wall Tile 4" Cream 200 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-56 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 115 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4C-56 2" Ceramic Flooring 2" Gray 115 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4C-56 4" Ceramic Wall Tile 4" Cream 200 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4D-04 2' x 4' Ceiling Tile CT-5 2' x 4' Widthwise Fissures 75 sf Good None Detected Non ACM 46-011 FALSE
4 46 4 4D-04 4" Ceramic Wall Tile 4" Cream 150 sf Good Non ACM Non-Suspect New FALSE
4 46 4 4D-04 2" Ceramic Flooring 2" Gray 75 sf Good Non ACM Non-Suspect New FALSE
4 1 4 4D-05 No Suspect Material Non ACM FALSE
4 1 4 4D-06 No Suspect Material Non ACM FALSE
4 1 4 4D-06 Corridor 2' x 2' Ceiling Tile CT-1-4 2'x2' Long Fissures w/Pinholes 500 sf Good None Detected Non ACM 01-010 FALSE
4 1 4 4D-06 Corridor 12" X 12" Floortile and Mastic FT-1-7 12"x12" Tan w/Brown/Gray/White Specks 500 sf Good None Detected Non ACM 01-030 FALSE
4 1 4 4D-07 No Suspect Material Non ACM FALSE
4 1 4 4D-07A No Suspect Material Non ACM FALSE
4 1 4 4D-08 No Suspect Material Non ACM FALSE
4 1 4 4E-09 2' x 2' Ceiling Tile CT-1-4 2'x2' Long Fissures w/Pinholes 5 sf Good None Detected Non ACM 01-010 FALSE
4 1 4 4E-10 Thermal System Insulation Gray 16 lf Assumed ACM Friable Assumed In Chase TRUE
4 1 4 4E-10 2' x 4' Ceiling Tile CT-1-3 2'x4' Widthwisw Fissures w/Pinholes 2,200 sf Good None Detected Non ACM 01-009 Carpet FALSE
4 1 4 4E-14 2' x 2' Ceiling Tile CT-1-4 2'x2' Long Fissures w/Pinholes 120 sf Good None Detected Non ACM 01-010 Carpet FALSE
4 1 4 4E-15 2' x 2' Ceiling Tile CT-1-4 2'x2' Long Fissures w/Pinholes 360 sf Good None Detected Non ACM 01-010 Carpet FALSE
4 1 4 4E-15A 2' x 4' Ceiling Tile CT-1-3 2'x4' Widthwisw Fissures w/Pinholes 110 sf Good None Detected Non ACM 01-009 Carpet FALSE
4 1 4 4E-16 2' x 4' Ceiling Tile CT-1-3 2'x4' Widthwisw Fissures w/Pinholes 120 sf Good None Detected Non ACM 01-009 Carpet FALSE
4 1 4 4E-17 2' x 4' Ceiling Tile CT-1-3 2'x4' Widthwisw Fissures w/Pinholes 350 sf Good None Detected Non ACM 01-009 Carpet FALSE
4 1 4 4E-18 2' x 4' Ceiling Tile CT-1-3 2'x4' Widthwisw Fissures w/Pinholes 100 sf Good None Detected Non ACM 01-009 Carpet FALSE
4 1 4 4E-19 Transite Panel/Pucks Black 50 lf Good Assumed ACM Non-Friable Assumed (5) Register Cabinets TRUE
4 1 4 4E-19E No Suspect Material Non ACM FALSE
4 1 4 4E-20 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 1 4 4E-20 2' x 2' Ceiling Tile CT-1-4 2'x2' Long Fissures w/Pinholes 100 sf Good None Detected Non ACM 01-010 Carpet FALSE
4 1 4 4E-21 12" X 12" Floortile and Mastic FT-1-7 12"x12" Tan w/Brown/Gray/White Specks 50 sf Good None Detected Non ACM 01-030 FALSE
4 1 4 4E-21 2' x 2' Ceiling Tile CT-1-4 2'x2' Long Fissures w/Pinholes 50 sf Good None Detected Non ACM 01-010 FALSE
4 1 4 4E-22 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE
4 1 4 4E-22 2' x 2' Ceiling Tile CT-1-4 2'x2' Long Fissures w/Pinholes 100 sf Good None Detected Non ACM 01-010 Carpet FALSE
4 1 4 4E-23 2' x 2' Ceiling Tile CT-1-4 2'x2' Long Fissures w/Pinholes 100 sf Good None Detected Non ACM 01-010 Carpet FALSE
4 1 4 4E-24 2' x 2' Ceiling Tile CT-1-4 2'x2' Long Fissures w/Pinholes 100 sf Good None Detected Non ACM 01-010 Carpet FALSE
4 1 4 Corridor Outside Elevator #4 Spray On Texture White 120 sf Good None Detected Non ACM 01-051A-C FALSE
4 1 4 Independence Elevator Corridor 12" X 12" Floortile and Mastic FT-1-7 12"x12" Tan w/Brown/Gray/White Specks 500 sf Good None Detected Non ACM 01-030 FALSE
4 1 4 Independence Elevator Corridor 2' x 2' Ceiling Tile CT-1-4 2'x2' Long Fissures w/Pinholes 500 sf Good None Detected Non ACM 01-010 FALSE
4 1 4 Stair #3 12" X 12" Floortile and Mastic FT-1-14 12"x12" Tan/Brown/White 50 sf Good 8% Chrysotile (Mastic) ACM Non-Friable 01-050 removed Jan. 2024 Horsely and Trio for air sampling TRUE
4 9 4 Stairwell #10 Transite Panel/Pucks Black 10 lf Good Assumed ACM Assumed Register Cabinet TRUE
4 9 4 Stairwell #14 Sheet Vinyl Floor Cream 120 sf Non ACM Non-Suspect New FALSE
4 9 4 Stairwell #9 Transite Panel/Pucks Black 10 lf Good Assumed ACM Non-Friable Assumed Register Cabinet TRUE image4.emf
5_Int Elev Sched.dwg image5.emf
Elevation Schedule image1.emf
Product Data
LINE QTY
1 10
2 10
3 10
4 10
5 10
6 1
7 2
8 1
9 4
10 2
11 8
12 1
13 1
EAST WING DINING ROOM
Pineapple Ryno Activity Table, Floor fixed, 1RYAT-00-MG-B Top: Gray Base: Black
Pineapple Ryno Dining Chair, 1RYD-02-VY Weighted to 119lbs Color: Moonwalk Gray
OTHER
Pineapple Ryno Rocker, weighted to 143 lbs, 1RYR-123-TL Color: Cool Green
Pineapple Zenplus Rocker 1ZENRP1-900-C Upholstered in Grade C vinyl
Pineapple Ryno Nightstand 1RYOB-FF-EB Includes floor fixing kit Color: Teal
WEST WING ACTIVITY ROOM
Pineapple 2-seater, weighted to 271 lbs, 1RY2-123-EB
Pineapple Ryno Rocker, weighted to 143 lbs, 1RYR-123-TL
Pineapple Ryno Activity Table, Floor fixed, 1RYAT-00-MG-B Top: Gray Base: Black
Pineapple Ryno Dining Chair, 1RYD-02-VY Weighted to 119 lbs
PATIENT ROOMS
DESCRIPTION
Pineapple Rotomold Twin Bed 1RYB-TL
Pineapple Bed Infill Panel, Left 1RYB-IL-TL
Pineapple Bed Infill Panel, Right 1RYB-IR-TL
Pineapple Taurus Twin Mattress, 1TRM6-78-36 image2.emf