This document is a solicitation for a commercial contract to provide medical gas maintenance services to the VA Nebraska-Western Iowa Health Care System. The solicitation is a total set-aside for Veteran-Owned Small Businesses, with a period of performance from July 1, 2024 to June 30, 2029. The Department of Veterans Affairs is seeking quotes for an Indefinite Delivery Indefinite Quantity contract to perform medical gas system maintenance, inspections, and repairs at facilities within the VA Nebraska-Western Iowa Health Care System. Quotes are due by June 6, 2024. The contract will be a firm fixed-price award, with the NAICS code 541350 (Building Inspection Services) and a size standard of $11.5 million. Technical questions on the solicitation are due by May 30, 2024.

View the file

Other files

Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MEDICAL GAS SYMBOLS

SYMBOL DESCRIPTION ADDITIONAL REMARKS

ALARM / CONTROL PANEL (MASTER OR

AREA)

ZONE VALVE BOX

# OF CIRCLES/PIPES INDICATES NUMBER OF

VALVES; ARROW INDICATES VALVE ACCESS SIDE

REFER TO MOUNTING HEIGHTS DETAIL FOR MOUNTING ELEVATION

REFER TO ABBREVIATIONS FOR TYPE

REFER TO MOUNTING HEIGHTS DETAIL FOR MOUNTING ELEVATION

EMERGENCY OXYGEN CONNECTION REFER TO MOUNTING HEIGHTS DETAIL FOR MOUNTING ELEVATION

ISOLATION VALVE

REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM.

LOCATE ABOVE CEILING AND PROVIDE WITH LOCKABLE HANDLE.

SENSING LOCATION XXXX

MEDICAL GAS OUTLET

REFER TO ABBREVIATIONS FOR GAS TYPE. PROVIDE BRACKET WITH EACH

VACUUM OUTLET. REFER TO MOUNTING HEIGHTS DETAILS FOR MOUNTING

ELEVATION. COORDINATE WITH ARCHITECTURAL DIVISION.

ABBREVIATION

LABORATORY AND MEDICAL GAS ABBREVIATIONS

DESCRIPTION

MEDICAL COMPRESSED AIRA

MEDICAL COMPRESSED AIR INTAKEAI

AREA ALARM PANELAAP

NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS

COMPRESSED AIR (NON-MEDICAL)CA

MEDICAL CARBON DIOXIDEC

DENTAL AIRDA

DENTAL AIR INTAKEDAI

DENTAL VACUUMDV

DENTAL VACUUM EXHAUSTDVE

EMERGENCY OXYGEN CONNECTIONEOC

MEDICAL HELIUMHE

HORSEPOWERHP

INSTRUMENT AIRIA

INSTRUMENT AIR INTAKEIAI

LABORATORY AIR LA

LABORATORY AIR INTAKELAI

ABBREVIATION DESCRIPTION

LABORATORY VACUUMLV

LABORATORY VACUUM EXHAUSTLVE

MEDICAL AIR COMPRESSORMAC

MASTER ALARM PANELMAP

MEDICAL VACUUM PUMPMVP

MEDICAL NITROGENN

MEDICAL NITROUS OXIDENO

MEDICAL OXYGENO

PRESSURE REDUCING VALVEPRV

MEDICAL VACUUMV

MEDICAL VACUUM EXHAUSTVE

VALVE BOXVB

MEDICAL WASTE ANESTHESIA GAS DISPOSALWAG

WATER COLUMNWC

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

ACC

B

IM

/2

V A

O m a h a a n d

G ra n d I s la n d /B

V A

O m a h a

M

E P

.r v t

/2

/2

:4

:5

P

M

ACC-P000

SYMBOLS AND ABBREVIATIONS MEDICAL GAS SYSTEM

INSPECTION AND ASSESSMENT

4101 WOOLWORTH AVE, OMAHA, NE 68105

36C26323Q1052

01/28/2024 RJH HLPRevisions: Date:

SHEET INDEX - ACC

SHEET NUMBER SHEET NAME

ACC-P000 SYMBOLS AND ABBREVIATIONS

ACC-PG10B BASEMENT LEVEL - OVERALL - MEDICAL GAS

ACC-PG10BA BASEMENT LEVEL - AREA A - MEDICAL GAS

ACC-PG10BB BASEMENT LEVEL - AREA B - MEDICAL GAS

ACC-PG10BC BASEMENT LEVEL - AREA C - MEDICAL GAS

ACC-PG101 FIRST LEVEL - OVERALL - MEDICAL GAS

ACC-PG101A FIRST LEVEL - AREA A - MEDICAL GAS

ACC-PG101B FIRST LEVEL - AREA B - MEDICAL GAS

ACC-PG101C FIRST LEVEL - AREA C - MEDICAL GAS

ACC-PG102 SECOND LEVEL - OVERALL - MEDICAL GAS

ACC-PG102A SECOND LEVEL - AREA A - MEDICAL GAS

ACC-PG102B SECOND LEVEL - AREA B - MEDICAL GAS

ACC-PG102C SECOND LEVEL - AREA C - MEDICAL GAS

ACC-PG103 THIRD LEVEL - OVERALL - MEDICAL GAS

ACC-PG103B PENTHOUSE LEVEL - AREA B - MEDICAL GAS

ACC-PG400 ACC MEDICAL GAS RISER DIAGRAM - OXYGEN

ACC-PG401 MEDICAL GAS RISER DIAGRAM - MEDICAL VACUUM

ACC-PG402 MEDICAL GAS RISER DIAGRAM - MEDICAL AIR

ACC-PG403 MEDICAL GAS RISER DIAGRAM - CARBON DIOXIDE

ACC-PG404 MEDICAL GAS RISER DIAGRAM - NITROUS OXIDE

ACC-PG405 MEDICAL GAS RISER DIAGRAM - NITROGEN

UP

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

A

B

C

KEY PLAN

N

ACC

B

IM

/2

V A

O m a h a a n d

G ra n d I s la n d /B

V A

O m a h a

M

E P

.r v t

/2

/2

:4

:5

P

M

ACC-PG10B

BASEMENT LEVEL - OVERALL -

MEDICAL GAS

MEDICAL GAS SYSTEM

INSPECTION AND ASSESSMENT

4101 WOOLWORTH AVE, OMAHA, NE 68105

36C26323Q1052

01/28/2024 RJH HLP

1/16" = 1'-0"

BASEMENT LEVEL - OVERALL - MEDICAL GAS

Revisions: Date:

200 SF

TELECOMMUNICATIONS

RM.

G011

UP

G320

G015

G018

G402G312

G401G311 G300.B

G302

G300.A

G301.A

G401.A

G402.AG312.A

G311.AG301

G322

G013 G014

G300

G012

G302

G120

G220

G003

G005

G007

G202

G201G111

G112

G212

G100.B

G200.B

G100.A

G211.A

G112.AG111.A

G201.A

G202.A

G211

G222

G002

G006.A

G000.A

G050

G200

G006

G001

SG002

G122

G200.A

G101

G103

G051

G052

EL-2

EL-3

G010

G002.A

G102

G100

G121

EL-1

G009G008

O2-G104-1

VAC-G104-1

MA-G104-1

O2-G211-1

VAC-G211-1

MA-G211-1

O2-G301-1

VAC-G301-1

MA-G301-1

3/4" A 2" V

1/2" O

3/4" A 2" V 1/2" O

1/2" O 2" V 3/4" A 3/4" A

1/2" O 2" V

1/2" O 2" V 3/4" A

ITEM # DEFICIENCY CODE / GUIDELINE

REFERENCE

SECTION

1 LABELING WITHIN PANEL INACCURATE VA SPECIFICATIONS 26 0511

2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511

3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL

4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2

5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7

6 MEDICAL GAS PIPING SHALL NOT BE PAINTED 5.1.11.1.5

7 NON-COMPLIANT MEDICAL GAS VALVE 5.1.4.6

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

MEDICAL GAS DEFICIENCY LIST

8 ZONE VALVE DOES NOT PROPERLY LABEL AREAS SERVED 5.1.11.2.8

9 MEDICAL GAS PIPING NOT PROPERLY LABELED NFPA 99 2024 5.1.11.1

10 ZONE VALVE BOX SHALL NOT BE INSTALLED WHERE HIDDEN FROM PLAIN VIEW 5.1.4.6.1

11 ZONE VALVE BOX SHALL BE IN LOCATION SUCH THAT WALL INTERVENES BOX AND OUTLETS SERVED

12 ALL ANESTHETIZING LOCATIONS SHALL HAVE DEDICATED ZONE VALVE BOX

13 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE 517.32(C), 517.35

NFPA 99 2024

NFPA 99 2024

NFPA 70 2023

14 MEDICAL AIR SHALL BE USED ONLY FOR HUMAN RESPIRATION OR CALIBRATION OF MEDICAL DEVICES 5.1.3.6.2

15 ZONE VALVE SHALL NOT BE LOCATED DOWNSTREAM OF ANOTHER ZONE VALVE NFPA 99 2024 5.1.4.6.2

16 WAGD PIPING TO BE CONNECTED TO MEDICAL VACUUM DOWNSTREAM OF ZONE VALVE VA PLUMBING DESIGN MANUAL 8.2.3.e

17 EACH ZONE VALVE SHALL HAVE AN AREA ALARM PANEL FOR ALARMING 8.2.4

18 EACH MAIN LINE OFF A RISER SHALL HAVE A SHUTOFF VALVE 5.1.4.4

19 ALL OUTLETS SHALL BE SUPPLIED THROUGH A ZONE VALVE 5.1.4.6.1

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

VA PLUMBING DESIGN MANUAL

5.1.4.6.1

5.1.4.6.2

1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL

MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.

2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE

MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.

GENERAL NOTES:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

A

B

C

KEY PLAN

N

ACC

B

IM

/2

V A

O m a h a a n d

G ra n d I s la n d /B

V A

O m a h a

M

E P

.r v t

/2

/2

:4

:5

P

M

ACC-PG10BA

BASEMENT LEVEL - AREA A -

MEDICAL GAS

MEDICAL GAS SYSTEM

INSPECTION AND ASSESSMENT

4101 WOOLWORTH AVE, OMAHA, NE 68105

36C26323Q1052

01/28/2024 RJH HLP

1/8" = 1'-0"

BASEMENT LEVEL - AREA A - MEDICAL GAS

G320

G405 G305

G317

G314

G316G306

G407

G408

G406

G404

G318G308

G307

G402G312

G313G303 G403

G302

G320.A

G328G327

G320.D

G426

G321

G309

G330

G330.A

SG004

G304

G306

G308

G307

G303

G302

G309

G310

G304

G306

G308

G307

G303

G309

G304

G306

G308

G307

G309

G315 G320.B

G320.C G319

G409

G126

G120

G220

G228

G118.A

G205

G214

G217

G204

G207

G218

G216

G208

G206

G117 G107

G118G108

G202

G112

G213G203

G212

G104.A

G114.A

G202.A

G105

G219

G220.A

G226

G123

G227G127

G220.D G120.C

G128

G124.A

G221

G059

G061

G060

G109

G110 G210

G130

G220.B

G230.AG130.A

G063

G065

G062

G113

G104

G106

G114

G103

G054

G053

G052

G055

G120.A

SG004

G119

G056

G125

G124

G215

G064

G310

G220.C

EL-4

G105.A

G121

G057

G110.A

G140

G113.A

EL-5

G209

G230

GLSL

O2-G104-1

VAC-G104-1

MA-G104-1

O2-G301-1

VAC-G301-1

MA-G301-1

O2-G105-1

VAC-G105-1

MA-G105-1

1/2" O 2" V 3/4" A

3/4" A 2" V

1/2" O

1/2" O 2" V 3/4" A

1 1/4" O DN

& OVER TO

BULK SYSTEM

RELIEF VENT

ITEM # DEFICIENCY CODE / GUIDELINE

REFERENCE

SECTION

1 LABELING WITHIN PANEL INACCURATE VA SPECIFICATIONS 26 0511

2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511

3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL

4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2

5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7

6 MEDICAL GAS PIPING SHALL NOT BE PAINTED 5.1.11.1.5

7 NON-COMPLIANT MEDICAL GAS VALVE 5.1.4.6

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

MEDICAL GAS DEFICIENCY LIST

8 ZONE VALVE DOES NOT PROPERLY LABEL AREAS SERVED 5.1.11.2.8

9 MEDICAL GAS PIPING NOT PROPERLY LABELED NFPA 99 2024 5.1.11.1

10 ZONE VALVE BOX SHALL NOT BE INSTALLED WHERE HIDDEN FROM PLAIN VIEW 5.1.4.6.1

11 ZONE VALVE BOX SHALL BE IN LOCATION SUCH THAT WALL INTERVENES BOX AND OUTLETS SERVED

12 ALL ANESTHETIZING LOCATIONS SHALL HAVE DEDICATED ZONE VALVE BOX

13 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE 517.32(C), 517.35

NFPA 99 2024

NFPA 99 2024

NFPA 70 2023

14 MEDICAL AIR SHALL BE USED ONLY FOR HUMAN RESPIRATION OR CALIBRATION OF MEDICAL DEVICES 5.1.3.6.2

15 ZONE VALVE SHALL NOT BE LOCATED DOWNSTREAM OF ANOTHER ZONE VALVE NFPA 99 2024 5.1.4.6.2

16 WAGD PIPING TO BE CONNECTED TO MEDICAL VACUUM DOWNSTREAM OF ZONE VALVE VA PLUMBING DESIGN MANUAL 8.2.3.e

17 EACH ZONE VALVE SHALL HAVE AN AREA ALARM PANEL FOR ALARMING 8.2.4

18 EACH MAIN LINE OFF A RISER SHALL HAVE A SHUTOFF VALVE 5.1.4.4

19 ALL OUTLETS SHALL BE SUPPLIED THROUGH A ZONE VALVE 5.1.4.6.1

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

VA PLUMBING DESIGN MANUAL

5.1.4.6.1

5.1.4.6.2

1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL

MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.

2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE

MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.

GENERAL NOTES:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

A

B

C

KEY PLAN

N

ACC

B

IM

/2

V A

O m a h a a n d

G ra n d I s la n d /B

V A

O m a h a

M

E P

.r v t

/2

/2

:4

:5

P

M

ACC-PG10BB

BASEMENT LEVEL - AREA B -

MEDICAL GAS

MEDICAL GAS SYSTEM

INSPECTION AND ASSESSMENT

4101 WOOLWORTH AVE, OMAHA, NE 68105

36C26323Q1052

01/28/2024 RJH HLP

1/8" = 1'-0"

BASEMENT LEVEL - AREA B - MEDICAL GAS

265 SF

RM.

G433

G420

G405

G019G018 G021

G502

G407

G418

G417

G408

G416G406

G414 G404

G402

G401

G400.B

G403

G413

G412

G411.A

G415

G401.A

G402.A

G411

G419

G420.A

G422

G427

G420.D

G431

G426

G421

G432

G506

G505

G504

G510

G330

G300

G023

G420.B

G430.A

SG003

G507

G020

G501

G503

G430

G428

G016

G017

G420.CG409

G501.1 G502.1

AREA ALARM PANEL

120V/1Ø

FED FROM GLSL CIRCUIT #8

OXYGEN RESERVE MANIFOLD

120V/1Ø

FED FROM GCRLCEP CIRCUIT #2

NITROGEN MANIFOLD

120V/1Ø

FED FROM GCRLCEP CIRCUIT #8

NITROUS OXIDE MANIFOLD

120V/1Ø

FED FROM GCRLCEP CIRCUIT #4

CARBON DIOXIDE MANIFOLD

120V/1Ø

FED FROM GCRLCEP CIRCUIT #6

GEQDPH

GCRLCEP

O2-G411-1

VAC-G411-1

MA-G411-1

1 1/4" N UP

1/2" NO UP

3/4" C UP

3" V UP

1" A UP

1" O UP

MEDICAL VACUUM

PUMP EXHAUST

MEDICAL AIR

INTAKE

1/2" O 2" V

3/4" A

1/2" O

3/4" A 2" V

1 1/4" O DN

& OVER TO

BULK SYSTEM

RELIEF VENT

EMERGENCY OXYGEN

CONNECTION

ITEM # DEFICIENCY CODE / GUIDELINE

REFERENCE

SECTION

1 LABELING WITHIN PANEL INACCURATE VA SPECIFICATIONS 26 0511

2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511

3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL

4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2

5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7

6 MEDICAL GAS PIPING SHALL NOT BE PAINTED 5.1.11.1.5

7 NON-COMPLIANT MEDICAL GAS VALVE 5.1.4.6

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

MEDICAL GAS DEFICIENCY LIST

8 ZONE VALVE DOES NOT PROPERLY LABEL AREAS SERVED 5.1.11.2.8

9 MEDICAL GAS PIPING NOT PROPERLY LABELED NFPA 99 2024 5.1.11.1

10 ZONE VALVE BOX SHALL NOT BE INSTALLED WHERE HIDDEN FROM PLAIN VIEW 5.1.4.6.1

11 ZONE VALVE BOX SHALL BE IN LOCATION SUCH THAT WALL INTERVENES BOX AND OUTLETS SERVED

12 ALL ANESTHETIZING LOCATIONS SHALL HAVE DEDICATED ZONE VALVE BOX

13 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE 517.32(C), 517.35

NFPA 99 2024

NFPA 99 2024

NFPA 70 2023

14 MEDICAL AIR SHALL BE USED ONLY FOR HUMAN RESPIRATION OR CALIBRATION OF MEDICAL DEVICES 5.1.3.6.2

15 ZONE VALVE SHALL NOT BE LOCATED DOWNSTREAM OF ANOTHER ZONE VALVE NFPA 99 2024 5.1.4.6.2

16 WAGD PIPING TO BE CONNECTED TO MEDICAL VACUUM DOWNSTREAM OF ZONE VALVE VA PLUMBING DESIGN MANUAL 8.2.3.e

17 EACH ZONE VALVE SHALL HAVE AN AREA ALARM PANEL FOR ALARMING 8.2.4

18 EACH MAIN LINE OFF A RISER SHALL HAVE A SHUTOFF VALVE 5.1.4.4

19 ALL OUTLETS SHALL BE SUPPLIED THROUGH A ZONE VALVE 5.1.4.6.1

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

VA PLUMBING DESIGN MANUAL

5.1.4.6.1

5.1.4.6.2

1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL

MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.

2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE

MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.

GENERAL NOTES:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

A

B

C

KEY PLAN

N

ACC

B

IM

/2

V A

O m a h a a n d

G ra n d I s la n d /B

V A

O m a h a

M

E P

.r v t

/2

/2

:4

:5

P

M

ACC-PG10BC

BASEMENT LEVEL - AREA C -

MEDICAL GAS

MEDICAL GAS SYSTEM

INSPECTION AND ASSESSMENT

4101 WOOLWORTH AVE, OMAHA, NE 68105

36C26323Q1052

01/28/2024 RJH HLP

1/8" = 1'-0"

BASEMENT LEVEL - AREA C - MEDICAL GAS

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

A

B

C

KEY PLAN

N

ACC

B

IM

/2

V A

O m a h a a n d

G ra n d I s la n d /B

V A

O m a h a

M

E P

.r v t

/2

/2

:4

:5

P

M

ACC-PG101

FIRST LEVEL - OVERALL -

MEDICAL GAS

MEDICAL GAS SYSTEM

INSPECTION AND ASSESSMENT

4101 WOOLWORTH AVE, OMAHA, NE 68105

36C26323Q1052

01/28/2024 RJH HLP

1/16" = 1'-0"

FIRST LEVEL - OVERALL - MEDICAL GAS

199 SF

RM.

1301.A

1300.B

1300.A

1311.A

1312.A

1401.A

1402.A

1016.A

1000.A

1200.B

1100.B

1100.A

1101.A 1211.A

1201.A

1202.A

1111.A 1112.A

S1002

1/2" O

1 1/4" V 3/4" A

O2-1101-1

VAC-1101-1

MA-1101-1

O2-1211-1

VAC-1211-1

MA-1211-1

O2-1301-1

VAC-1301-1

MA-1301-1

3/4" A 1 1/4" V

1/2" O

3/4" A

1" V

1/2" O

ITEM # DEFICIENCY CODE / GUIDELINE

REFERENCE

SECTION

1 LABELING WITHIN PANEL INACCURATE VA SPECIFICATIONS 26 0511

2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511

3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL

4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2

5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7

6 MEDICAL GAS PIPING SHALL NOT BE PAINTED 5.1.11.1.5

7 NON-COMPLIANT MEDICAL GAS VALVE 5.1.4.6

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

MEDICAL GAS DEFICIENCY LIST

8 ZONE VALVE DOES NOT PROPERLY LABEL AREAS SERVED 5.1.11.2.8

9 MEDICAL GAS PIPING NOT PROPERLY LABELED NFPA 99 2024 5.1.11.1

10 ZONE VALVE BOX SHALL NOT BE INSTALLED WHERE HIDDEN FROM PLAIN VIEW 5.1.4.6.1

11 ZONE VALVE BOX SHALL BE IN LOCATION SUCH THAT WALL INTERVENES BOX AND OUTLETS SERVED

12 ALL ANESTHETIZING LOCATIONS SHALL HAVE DEDICATED ZONE VALVE BOX

13 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE 517.32(C), 517.35

NFPA 99 2024

NFPA 99 2024

NFPA 70 2023

14 MEDICAL AIR SHALL BE USED ONLY FOR HUMAN RESPIRATION OR CALIBRATION OF MEDICAL DEVICES 5.1.3.6.2

15 ZONE VALVE SHALL NOT BE LOCATED DOWNSTREAM OF ANOTHER ZONE VALVE NFPA 99 2024 5.1.4.6.2

16 WAGD PIPING TO BE CONNECTED TO MEDICAL VACUUM DOWNSTREAM OF ZONE VALVE VA PLUMBING DESIGN MANUAL 8.2.3.e

17 EACH ZONE VALVE SHALL HAVE AN AREA ALARM PANEL FOR ALARMING 8.2.4

18 EACH MAIN LINE OFF A RISER SHALL HAVE A SHUTOFF VALVE 5.1.4.4

19 ALL OUTLETS SHALL BE SUPPLIED THROUGH A ZONE VALVE 5.1.4.6.1

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

VA PLUMBING DESIGN MANUAL

5.1.4.6.1

5.1.4.6.2

1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL

MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.

2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE

MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.

GENERAL NOTES:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

A

B

C

KEY PLAN

N

ACC

B

IM

/2

V A

O m a h a a n d

G ra n d I s la n d /B

V A

O m a h a

M

E P

.r v t

/2

/2

:4

:0

P

M

ACC-PG101A

FIRST LEVEL - AREA A - MEDICAL

GAS

MEDICAL GAS SYSTEM

INSPECTION AND ASSESSMENT

4101 WOOLWORTH AVE, OMAHA, NE 68105

36C26323Q1052

01/28/2024 RJH HLP

1/8" = 1'-0"

FIRST LEVEL - AREA A - MEDICAL GAS

14021312

1320.A

13281327

1320.D

1320.B

1330.A

1320.C

12021112

1120.A

1220.A

12261127 1227

1220.D 1120.D

1220.B

1130.A 1230.A

S1004

1120.B

1120.C 1220.C

O2-1101-1

VAC-1101-1

MA-1101-1

O2-1211-1

VAC-1211-1

MA-1211-1

O2-1301-1

VAC-1301-1

MA-1301-1

1LSL

ITEM # DEFICIENCY CODE / GUIDELINE

REFERENCE

SECTION

1 LABELING WITHIN PANEL INACCURATE VA SPECIFICATIONS 26 0511

2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511

3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL

4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2

5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7

6 MEDICAL GAS PIPING SHALL NOT BE PAINTED 5.1.11.1.5

7 NON-COMPLIANT MEDICAL GAS VALVE 5.1.4.6

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

MEDICAL GAS DEFICIENCY LIST

8 ZONE VALVE DOES NOT PROPERLY LABEL AREAS SERVED 5.1.11.2.8

9 MEDICAL GAS PIPING NOT PROPERLY LABELED NFPA 99 2024 5.1.11.1

10 ZONE VALVE BOX SHALL NOT BE INSTALLED WHERE HIDDEN FROM PLAIN VIEW 5.1.4.6.1

11 ZONE VALVE BOX SHALL BE IN LOCATION SUCH THAT WALL INTERVENES BOX AND OUTLETS SERVED

12 ALL ANESTHETIZING LOCATIONS SHALL HAVE DEDICATED ZONE VALVE BOX

13 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE 517.32(C), 517.35

NFPA 99 2024

NFPA 99 2024

NFPA 70 2023

14 MEDICAL AIR SHALL BE USED ONLY FOR HUMAN RESPIRATION OR CALIBRATION OF MEDICAL DEVICES 5.1.3.6.2

15 ZONE VALVE SHALL NOT BE LOCATED DOWNSTREAM OF ANOTHER ZONE VALVE NFPA 99 2024 5.1.4.6.2

16 WAGD PIPING TO BE CONNECTED TO MEDICAL VACUUM DOWNSTREAM OF ZONE VALVE VA PLUMBING DESIGN MANUAL 8.2.3.e

17 EACH ZONE VALVE SHALL HAVE AN AREA ALARM PANEL FOR ALARMING 8.2.4

18 EACH MAIN LINE OFF A RISER SHALL HAVE A SHUTOFF VALVE 5.1.4.4

19 ALL OUTLETS SHALL BE SUPPLIED THROUGH A ZONE VALVE 5.1.4.6.1

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

VA PLUMBING DESIGN MANUAL

5.1.4.6.1

5.1.4.6.2

1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL

MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.

2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE

MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.

GENERAL NOTES:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

A

B

C

KEY PLAN

N

ACC

B

IM

/2

V A

O m a h a a n d

G ra n d I s la n d /B

V A

O m a h a

M

E P

.r v t

/2

/2

:4

:0

P

M

ACC-PG101B

FIRST LEVEL - AREA B - MEDICAL

GAS

MEDICAL GAS SYSTEM

INSPECTION AND ASSESSMENT

4101 WOOLWORTH AVE, OMAHA, NE 68105

36C26323Q1052

01/28/2024 RJH HLP

1/8" = 1'-0"

FIRST LEVEL - AREA B - MEDICAL GAS

146 SF

RM.

10211018

1400.B

1504.A

1411.A

1312.A

1401.A

1402.A

1420.A

1420.D

1430.A

1420.B

1420.C

S1003

14281426

1016.A

1" O UP

1" A UP

3" V UP

3/4" C UP

1/2" NO UP

1 1/4" N UP

1 1/4" N DN

1/2" NO DN

3/4" C DN

3" V DN

1" A DN

1" O DN

O2-1411-1

VAC-1411-1

MA-1411-1

3/4" A 1" V

1/2" O

3/4" A 1 1/4" V

1/2" O

AREA ALARM PANEL

120V/1Ø

FED FROM 1LSL CIRCUIT #4

ITEM # DEFICIENCY CODE / GUIDELINE

REFERENCE

SECTION

1 LABELING WITHIN PANEL INACCURATE VA SPECIFICATIONS 26 0511

2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511

3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL

4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2

5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7

6 MEDICAL GAS PIPING SHALL NOT BE PAINTED 5.1.11.1.5

7 NON-COMPLIANT MEDICAL GAS VALVE 5.1.4.6

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

MEDICAL GAS DEFICIENCY LIST

8 ZONE VALVE DOES NOT PROPERLY LABEL AREAS SERVED 5.1.11.2.8

9 MEDICAL GAS PIPING NOT PROPERLY LABELED NFPA 99 2024 5.1.11.1

10 ZONE VALVE BOX SHALL NOT BE INSTALLED WHERE HIDDEN FROM PLAIN VIEW 5.1.4.6.1

11 ZONE VALVE BOX SHALL BE IN LOCATION SUCH THAT WALL INTERVENES BOX AND OUTLETS SERVED

12 ALL ANESTHETIZING LOCATIONS SHALL HAVE DEDICATED ZONE VALVE BOX

13 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE 517.32(C), 517.35

NFPA 99 2024

NFPA 99 2024

NFPA 70 2023

14 MEDICAL AIR SHALL BE USED ONLY FOR HUMAN RESPIRATION OR CALIBRATION OF MEDICAL DEVICES 5.1.3.6.2

15 ZONE VALVE SHALL NOT BE LOCATED DOWNSTREAM OF ANOTHER ZONE VALVE NFPA 99 2024 5.1.4.6.2

16 WAGD PIPING TO BE CONNECTED TO MEDICAL VACUUM DOWNSTREAM OF ZONE VALVE VA PLUMBING DESIGN MANUAL 8.2.3.e

17 EACH ZONE VALVE SHALL HAVE AN AREA ALARM PANEL FOR ALARMING 8.2.4

18 EACH MAIN LINE OFF A RISER SHALL HAVE A SHUTOFF VALVE 5.1.4.4

19 ALL OUTLETS SHALL BE SUPPLIED THROUGH A ZONE VALVE 5.1.4.6.1

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

VA PLUMBING DESIGN MANUAL

5.1.4.6.1

5.1.4.6.2

1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL

MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.

2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE

MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.

GENERAL NOTES:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

A

B

C

KEY PLAN

N

ACC

B

IM

/2

V A

O m a h a a n d

G ra n d I s la n d /B

V A

O m a h a

M

E P

.r v t

/2

/2

:4

:0

P

M

ACC-PG101C

FIRST LEVEL - AREA C - MEDICAL

GAS

MEDICAL GAS SYSTEM

INSPECTION AND ASSESSMENT

4101 WOOLWORTH AVE, OMAHA, NE 68105

36C26323Q1052

01/28/2024 RJH HLP

1/8" = 1'-0"

FIRST LEVEL - AREA C - MEDICAL GAS

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

A

B

C

KEY PLAN

N

ACC

B

IM

/2

V A

O m a h a a n d

G ra n d I s la n d /B

V A

O m a h a

M

E P

.r v t

/2

/2

:4

:0

P

M

ACC-PG102

SECOND LEVEL - OVERALL -

MEDICAL GAS

MEDICAL GAS SYSTEM

INSPECTION AND ASSESSMENT

4101 WOOLWORTH AVE, OMAHA, NE 68105

36C26323Q1052

01/28/2024 RJH HLP

1/16" = 1'-0"

SECOND LEVEL - OVERALL - MEDICAL GAS

155 SF

RM.

2100.A

2111.A

2101.A

20092008

S2002

2112.A

2501.B

2311.B

2311.A

2400.A

2400.C

2319 2320

2411.A

2316 2323

2400.B

2332.A

2332.B

1" V 3/4" A 1/2" O

1/2" O

3/4" A 1" V

1/2" O

3/4" A

1" V

1/2" O 3/4" A 1" V

1/2" O 3/4" A 1 1/4" V 1/2" C

1/2" NO

3/4" N

1/2" O 1 1/4" V

1/2" NO

3/4" A

1/2" C 3/4" N

1/2" O 1 1/4" V 3/4" A

1/2" C 3/4" N

1/2" NO

1" V 3/4" A

1/2" O

O2-2101-1

VAC-2101-1

MA-2101-1

O2-2201-1

VAC-2201-1

MA-2201-1

O2-2203-1

VAC-2203-1

MA-2203-1

O2-2301-1 O2-2301-2

VAC-2301-1

VAC-2301-2

VAC-2301-3

MA-2301-1

O2-2302-1 O2-2302-2

VAC-2302-1

VAC-2302-2

VAC-2302-3

MA-2302-1

O2-2304-1 O2-2304-2

VAC-2304-1

VAC-2304-2

VAC-2304-3

MA-2304-1

O2-2305-1 O2-2305-2

VAC-2305-1

VAC-2305-2

VAC-2305-3

MA-2305-1

O2-2318-1 O2-2318-2

VAC-2318-1

VAC-2318-2

VAC-2318-3

MA-2318-1

O2-2321-1 O2-2321-2

VAC-2321-1

VAC-2321-2

VAC-2321-3

MA-2321-1

O2-2315-1 O2-2315-2

VAC-2315-1

VAC-2315-2

VAC-2315-3

MA-2315-1

O2-2324-1 O2-2324-2

VAC-2324-1

VAC-2324-2

VAC-2324-3

MA-2324-1

O2-2333-1 O2-2333-2

VAC-2333-1

VAC-2333-2

VAC-2333-3

MA-2333-1

O2-2334-1 O2-2334-2

VAC-2334-1

VAC-2334-2

VAC-2334-3

MA-2334-1

O2-2336-1 O2-2336-2

VAC-2336-1

VAC-2336-2

VAC-2336-3

MA-2336-1

O2-2337-1 O2-2337-2

VAC-2337-1

VAC-2337-2

VAC-2337-3

MA-2337-1

O2-2401-1 O2-2401-2

VAC-2401-1

VAC-2401-2

MA-2401-1

MA-2401-2

NO2-2401-1

WAGD-2401-1

2" V UP

1" A UP

2" V 1" A

2" V

1" A 1" O

ITEM # DEFICIENCY CODE / GUIDELINE

REFERENCE

SECTION

1 LABELING WITHIN PANEL INACCURATE VA SPECIFICATIONS 26 0511

2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511

3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL

4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2

5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7

6 MEDICAL GAS PIPING SHALL NOT BE PAINTED 5.1.11.1.5

7 NON-COMPLIANT MEDICAL GAS VALVE 5.1.4.6

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

MEDICAL GAS DEFICIENCY LIST

8 ZONE VALVE DOES NOT PROPERLY LABEL AREAS SERVED 5.1.11.2.8

9 MEDICAL GAS PIPING NOT PROPERLY LABELED NFPA 99 2024 5.1.11.1

10 ZONE VALVE BOX SHALL NOT BE INSTALLED WHERE HIDDEN FROM PLAIN VIEW 5.1.4.6.1

11 ZONE VALVE BOX SHALL BE IN LOCATION SUCH THAT WALL INTERVENES BOX AND OUTLETS SERVED

12 ALL ANESTHETIZING LOCATIONS SHALL HAVE DEDICATED ZONE VALVE BOX

13 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE 517.32(C), 517.35

NFPA 99 2024

NFPA 99 2024

NFPA 70 2023

14 MEDICAL AIR SHALL BE USED ONLY FOR HUMAN RESPIRATION OR CALIBRATION OF MEDICAL DEVICES 5.1.3.6.2

15 ZONE VALVE SHALL NOT BE LOCATED DOWNSTREAM OF ANOTHER ZONE VALVE NFPA 99 2024 5.1.4.6.2

16 WAGD PIPING TO BE CONNECTED TO MEDICAL VACUUM DOWNSTREAM OF ZONE VALVE VA PLUMBING DESIGN MANUAL 8.2.3.e

17 EACH ZONE VALVE SHALL HAVE AN AREA ALARM PANEL FOR ALARMING 8.2.4

18 EACH MAIN LINE OFF A RISER SHALL HAVE A SHUTOFF VALVE 5.1.4.4

19 ALL OUTLETS SHALL BE SUPPLIED THROUGH A ZONE VALVE 5.1.4.6.1

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

VA PLUMBING DESIGN MANUAL

5.1.4.6.1

5.1.4.6.2

1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL

MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.

2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE

MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.

GENERAL NOTES:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

A

B

C

KEY PLAN

N

ACC

B

IM

/2

V A

O m a h a a n d

G ra n d I s la n d /B

V A

O m a h a

M

E P

.r v t

/2

/2

:4

:0

P

M

ACC-PG102A

SECOND LEVEL - AREA A -

MEDICAL GAS

MEDICAL GAS SYSTEM

INSPECTION AND ASSESSMENT

4101 WOOLWORTH AVE, OMAHA, NE 68105

36C26323Q1052

01/28/2024 RJH HLP

1/8" = 1'-0"

SECOND LEVEL - AREA A - MEDICAL GAS

2130.A

21142104

2106 2116

2120.D

2103 2113

2120.A

22162214

2220.A

22242223

2300.A

2300.B

22302130

2120.C

2120.B

2112.A

2311.F

2311.D

2311.B

2400.E

2311.E

2332.E

23272312

23522351

2350.A

S2004

2316 2323

2404.A

2332.D

2332.C

2332.B

2311.C

1/2" O

3/4" A

1" V

1" V 3/4" A 1/2" O 3/4" O3/4" A

1" V

1/2" O

3/4" A 1" V

1/2" O

3/4" A

1" V

1/2" O

3/4" A

1" V

1 1/4" V 3/4" A 3/4" O

1" V 3/4" A 3/4" O

1/2" O 3/4" A 1" V

1/2" O 3/4" A 1 1/4" V 1/2" C

1/2" NO

3/4" N

1/2" O 1 1/4" V

1/2" NO

3/4" A

1/2" C 3/4" N

O2-2101-1

VAC-2101-1

MA-2101-1

O2-2203-1

VAC-2203-1

MA-2203-1

O2-2304-1 O2-2304-2

VAC-2304-1

VAC-2304-2

VAC-2304-3

MA-2304-1

O2-2305-1 O2-2305-2

VAC-2305-1

VAC-2305-2

VAC-2305-3

MA-2305-1

O2-2306-1 O2-2306-2

VAC-2306-1

VAC-2306-2

VAC-2306-3

MA-2306-1

O2-2307-1 O2-2307-2

VAC-2307-1

VAC-2307-2

VAC-2307-3

MA-2307-1

O2-2309-1 O2-2309-2

VAC-2309-1

VAC-2309-2

VAC-2309-3

MA-2309-1

O2-2310-1 O2-2310-2

VAC-2310-1

VAC-2310-2

VAC-2310-3

MA-2310-1

O2-2315-1 O2-2315-2

VAC-2315-1

VAC-2315-2

VAC-2315-3

MA-2315-1

O2-2324-1 O2-2324-2

VAC-2324-1

VAC-2324-2

VAC-2324-3

MA-2324-1

O2-2312-1 O2-2312-2

VAC-2312-1

VAC-2312-2

VAC-2312-3

MA-2312-1

O2-2327-1 O2-2327-2

VAC-2327-1

VAC-2327-2

VAC-2327-3

MA-2327-1

O2-2341-1 O2-2341-2

VAC-2341-1

VAC-2341-2

VAC-2341-3

MA-2341-1

O2-2340-1 O2-2340-2

VAC-2340-1

VAC-2340-2

VAC-2340-3

MA-2340-1

O2-2336-1 O2-2336-2

VAC-2336-1

VAC-2336-2

VAC-2336-3

MA-2336-1

1" V 3/4" A 1/2" O

O2-2337-1 O2-2337-2

VAC-2337-1

VAC-2337-2

VAC-2337-3

MA-2337-1

O2-2402-1 O2-2402-2

VAC-2402-1

VAC-2402-2

MA-2402-1

MA-2402-2

NO2-2402-1

WAGD-2402-1

MASTER ALARM PANEL

120V/1Ø

FED FROM 2LSL CIRCUIT #6

AREA ALARM PANEL

120V/1Ø

FED FROM 2LSL CIRCUIT #5

AREA ALARM PANEL

120V/1Ø

FED FROM 2LSL CIRCUIT #7

2LSL

2" V UP

1" A UP

2" V 1" A

ITEM # DEFICIENCY CODE / GUIDELINE

REFERENCE

SECTION

1 LABELING WITHIN PANEL INACCURATE VA SPECIFICATIONS 26 0511

2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511

3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL

4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2

5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7

6 MEDICAL GAS PIPING SHALL NOT BE PAINTED 5.1.11.1.5

7 NON-COMPLIANT MEDICAL GAS VALVE 5.1.4.6

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

MEDICAL GAS DEFICIENCY LIST

8 ZONE VALVE DOES NOT PROPERLY LABEL AREAS SERVED 5.1.11.2.8

9 MEDICAL GAS PIPING NOT PROPERLY LABELED NFPA 99 2024 5.1.11.1

10 ZONE VALVE BOX SHALL NOT BE INSTALLED WHERE HIDDEN FROM PLAIN VIEW 5.1.4.6.1

11 ZONE VALVE BOX SHALL BE IN LOCATION SUCH THAT WALL INTERVENES BOX AND OUTLETS SERVED

12 ALL ANESTHETIZING LOCATIONS SHALL HAVE DEDICATED ZONE VALVE BOX

13 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE 517.32(C), 517.35

NFPA 99 2024

NFPA 99 2024

NFPA 70 2023

14 MEDICAL AIR SHALL BE USED ONLY FOR HUMAN RESPIRATION OR CALIBRATION OF MEDICAL DEVICES 5.1.3.6.2

15 ZONE VALVE SHALL NOT BE LOCATED DOWNSTREAM OF ANOTHER ZONE VALVE NFPA 99 2024 5.1.4.6.2

16 WAGD PIPING TO BE CONNECTED TO MEDICAL VACUUM DOWNSTREAM OF ZONE VALVE VA PLUMBING DESIGN MANUAL 8.2.3.e

17 EACH ZONE VALVE SHALL HAVE AN AREA ALARM PANEL FOR ALARMING 8.2.4

18 EACH MAIN LINE OFF A RISER SHALL HAVE A SHUTOFF VALVE 5.1.4.4

19 ALL OUTLETS SHALL BE SUPPLIED THROUGH A ZONE VALVE 5.1.4.6.1

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

VA PLUMBING DESIGN MANUAL

5.1.4.6.1

5.1.4.6.2

1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL

MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.

2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE

MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.

GENERAL NOTES:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

A

B

C

KEY PLAN

N

ACC

B

IM

/2

V A

O m a h a a n d

G ra n d I s la n d /B

V A

O m a h a

M

E P

.r v t

/2

/2

:4

:1

P

M

ACC-PG102B

SECOND LEVEL - AREA B -

MEDICAL GAS

MEDICAL GAS SYSTEM

INSPECTION AND ASSESSMENT

4101 WOOLWORTH AVE, OMAHA, NE 68105

36C26323Q1052

01/28/2024 RJH HLP

1/8" = 1'-0"

SECOND LEVEL - AREA B - MEDICAL GAS

162 SF

RM.

2400.E

2412.B

2400.A

2400.C

2412.F

2412.D

2412.A

2412.E

2412.C

2416 2419

2428 2429

2417 2418

2411.A

S2003

2" V 1" A

1" O 3/4" N

1/2" NO

3/4" C

3" V 3/4" A

1/2" O

1/2" O

1/2" O 1 1/4" V

1/2" NO

3/4" A

1/2" C 3/4" N

1/2" O 1 1/4" V 3/4" A

1/2" C 3/4" N

1/2" NO

1" O DN

1" A DN

3" V DN

3/4" C DN

1/2" NO DN

1 1/4" N DN1/2" O

1 1/4" V 3/4" A

1/2" NO

3/4" N 1/2" C

1/2" O 1 1/4" V 3/4" A

1/2" NO1/2" C

3/4" N

1/2" O 1 1/4" V 3/4" A

1/2" NO

3/4" N 1/2" C

O2-2401-1 O2-2401-2

VAC-2401-1

VAC-2401-2

MA-2401-1

MA-2401-2

NO2-2401-1

WAGD-2401-1

O2-2401-3

VAC-2401-3

VAC-2401-4

MA-2401-3

N2-2401-1

CO2-2401-1

O2-2402-1 O2-2402-2

VAC-2402-1

VAC-2402-2

MA-2402-1

MA-2402-2

NO2-2402-1

WAGD-2402-1

O2-2402-3

VAC-2402-3

VAC-2402-4

MA-2402-3

N2-2402-1

CO2-2402-1

O2-2407-2 O2-2407-3

VAC-2407-3

VAC-2407-4

MA-2407-2

MA-2407-3

NO2-2407-1

WAGD-2407-1

O2-2407-1

VAC-2407-1

VAC-2407-2

MA-2407-1

N2-2407-1

CO2-2407-1

O2-2408-2 O2-2408-3

VAC-2408-3

VAC-2408-4

MA-2408-2

MA-2408-3

NO2-2408-1

WAGD-2408-1

O2-2408-1

VAC-2408-1

VAC-2408-2

MA-2408-1

N2-2408-1

CO2-2408-1

O2-2409-2 O2-2409-3

VAC-2409-3

VAC-2409-4

MA-2409-2

MA-2409-3

NO2-2409-1

WAGD-2409-1

O2-2409-1

VAC-2409-1

VAC-2409-2

MA-2409-1

N2-2409-1

CO2-2409-1

ITEM # DEFICIENCY CODE / GUIDELINE

REFERENCE

SECTION

1 LABELING WITHIN PANEL INACCURATE VA SPECIFICATIONS 26 0511

2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511

3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL

4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2

5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7

6 MEDICAL GAS PIPING SHALL NOT BE PAINTED 5.1.11.1.5

7 NON-COMPLIANT MEDICAL GAS VALVE 5.1.4.6

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

MEDICAL GAS DEFICIENCY LIST

8 ZONE VALVE DOES NOT PROPERLY LABEL AREAS SERVED 5.1.11.2.8

9 MEDICAL GAS PIPING NOT PROPERLY LABELED NFPA 99 2024 5.1.11.1

10 ZONE VALVE BOX SHALL NOT BE INSTALLED WHERE HIDDEN FROM PLAIN VIEW 5.1.4.6.1

11 ZONE VALVE BOX SHALL BE IN LOCATION SUCH THAT WALL INTERVENES BOX AND OUTLETS SERVED

12 ALL ANESTHETIZING LOCATIONS SHALL HAVE DEDICATED ZONE VALVE BOX

13 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE 517.32(C), 517.35

NFPA 99 2024

NFPA 99 2024

NFPA 70 2023

14 MEDICAL AIR SHALL BE USED ONLY FOR HUMAN RESPIRATION OR CALIBRATION OF MEDICAL DEVICES 5.1.3.6.2

15 ZONE VALVE SHALL NOT BE LOCATED DOWNSTREAM OF ANOTHER ZONE VALVE NFPA 99 2024 5.1.4.6.2

16 WAGD PIPING TO BE CONNECTED TO MEDICAL VACUUM DOWNSTREAM OF ZONE VALVE VA PLUMBING DESIGN MANUAL 8.2.3.e

17 EACH ZONE VALVE SHALL HAVE AN AREA ALARM PANEL FOR ALARMING 8.2.4

18 EACH MAIN LINE OFF A RISER SHALL HAVE A SHUTOFF VALVE 5.1.4.4

19 ALL OUTLETS SHALL BE SUPPLIED THROUGH A ZONE VALVE 5.1.4.6.1

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

VA PLUMBING DESIGN MANUAL

5.1.4.6.1

5.1.4.6.2

1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL

MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.

2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE

MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.

GENERAL NOTES:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

A

B

C

KEY PLAN

N

ACC

B

IM

/2

V A

O m a h a a n d

G ra n d I s la n d /B

V A

O m a h a

M

E P

.r v t

/2

/2

:4

:1

P

M

ACC-PG102C

SECOND LEVEL - AREA C -

MEDICAL GAS

MEDICAL GAS SYSTEM

INSPECTION AND ASSESSMENT

4101 WOOLWORTH AVE, OMAHA, NE 68105

36C26323Q1052

01/28/2024 RJH HLP

1/8" = 1'-0"

SECOND LEVEL - AREA C - MEDICAL GAS

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

A

B

C

KEY PLAN

N

ACC

B

IM

/2

V A

O m a h a a n d

G ra n d I s la n d /B

V A

O m a h a

M

E P

.r v t

/2

/2

:4

:1

P

M

ACC-PG103

THIRD LEVEL - OVERALL -

MEDICAL GAS

MEDICAL GAS SYSTEM

INSPECTION AND ASSESSMENT

4101 WOOLWORTH AVE, OMAHA, NE 68105

36C26323Q1052

01/28/2024 RJH HLP

1/16" = 1'-0"

THIRD LEVEL - OVERALL - MEDICAL GAS

MEDICAL AIR COMPRESSOR

480V/3Ø

FED FROM PEQDPH CIRCUIT #31, 33, 35

MEDICAL VACUUM PUMP

480V/3Ø

FED FROM PEQDPH CIRCUIT #25, 27, 29

P E

Q D

P H

VAC EXHAUST

TERMINATION

MEDICAL AIR INTAKE

FROM AHU SUPPLY DUCT

3/4" AI DN

4" VE DN

2" V 1" A

2" V DN

1" A DN

ITEM # DEFICIENCY CODE / GUIDELINE

REFERENCE

SECTION

1 LABELING WITHIN PANEL INACCURATE VA SPECIFICATIONS 26 0511

2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511

3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL

4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2

5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7

6 MEDICAL GAS PIPING SHALL NOT BE PAINTED 5.1.11.1.5

7 NON-COMPLIANT MEDICAL GAS VALVE 5.1.4.6

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

MEDICAL GAS DEFICIENCY LIST

8 ZONE VALVE DOES NOT PROPERLY LABEL AREAS SERVED 5.1.11.2.8

9 MEDICAL GAS PIPING NOT PROPERLY LABELED NFPA 99 2024 5.1.11.1

10 ZONE VALVE BOX SHALL NOT BE INSTALLED WHERE HIDDEN FROM PLAIN VIEW 5.1.4.6.1

11 ZONE VALVE BOX SHALL BE IN LOCATION SUCH THAT WALL INTERVENES BOX AND OUTLETS SERVED

12 ALL ANESTHETIZING LOCATIONS SHALL HAVE DEDICATED ZONE VALVE BOX

13 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE 517.32(C), 517.35

NFPA 99 2024

NFPA 99 2024

NFPA 70 2023

14 MEDICAL AIR SHALL BE USED ONLY FOR HUMAN RESPIRATION OR CALIBRATION OF MEDICAL DEVICES 5.1.3.6.2

15 ZONE VALVE SHALL NOT BE LOCATED DOWNSTREAM OF ANOTHER ZONE VALVE NFPA 99 2024 5.1.4.6.2

16 WAGD PIPING TO BE CONNECTED TO MEDICAL VACUUM DOWNSTREAM OF ZONE VALVE VA PLUMBING DESIGN MANUAL 8.2.3.e

17 EACH ZONE VALVE SHALL HAVE AN AREA ALARM PANEL FOR ALARMING 8.2.4

18 EACH MAIN LINE OFF A RISER SHALL HAVE A SHUTOFF VALVE 5.1.4.4

19 ALL OUTLETS SHALL BE SUPPLIED THROUGH A ZONE VALVE 5.1.4.6.1

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

NFPA 99 2024

VA PLUMBING DESIGN MANUAL

5.1.4.6.1

5.1.4.6.2

1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL

MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.

2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE

MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.

GENERAL NOTES:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

A

B

C

KEY PLAN

N

ACC

B

IM

/2

V A

O m a h a a n d

G ra n d I s la n d /B

V A

O m a h a

M

E P

.r v t

/2

/2

:4

:1

P

M

ACC-PG103B

PENTHOUSE LEVEL - AREA B -

MEDICAL GAS

MEDICAL GAS SYSTEM

INSPECTION AND ASSESSMENT

4101 WOOLWORTH AVE, OMAHA, NE 68105

36C26323Q1052

01/28/2024 RJH HLP

1/8" = 1'-0"

THIRD LEVEL - AREA B - MEDICAL GAS

OXYGEN

RESERVE

MANIFOLD

1 1/4" TO BULK

SYSTEM

RELIEF VENTZONE VALVE

G411

ZONE VALVE

G301

ZONE VALVE

G211

ZONE VALVE

G110 S

ZONE VALVE

G110 N

G411

G301

G211

G105

G104

ZONE VALVE

ZONE VALVE

ZONE VALVE

ZONE VALVE

11011101

ZV-16

ZV-17

ZV-18

ZV-15

ZV-14

24072408240924012402

ZV-13

ZV-12

ZV-11

ZV-10

2337233623342333

2341234023272312

2318232123242315

2301230223042305

2310230923072306

220322012101

1 1/4"

1"

1/2" TYP.

1/2" TYP

1/2" TYP

1"

3/4"

BASEMENT

FIRST FLOOR

SECOND FLOOR

PENTHOUSE

EMERGENCY

OXYGEN

CONNECTION

1 1/4"

1/2"

1"

1/2" TYP

1"1/2"

1"

3/4"

1/2"

1/2"3/4"

1/2"

1/2"

1/2"1/2"1/2"1/2"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

ACC

B

IM

/2

V A

O m a h a a n d

G ra n d I s la n d /B

V A

O m a h a

M

E P

.r v t

/2

/2

:4

:1

P

M

ACC-PG400

ACC MEDICAL GAS RISER

DIAGRAM - OXYGEN

MEDICAL GAS SYSTEM

INSPECTION AND ASSESSMENT

4101 WOOLWORTH AVE, OMAHA, NE 68105

36C26323Q1052

01/28/2024

NO SCALE

ACC MEDICAL GAS RISER DIAGRAM - OXYGEN

MEDICAL

VACUUM PUMP

ZONE VALVE

ZONE VALVE

ZONE VALVE

ZONE VALVE

11011101

ZONE VALVE

G411

ZONE VALVE

G301

ZONE VALVE

G211

ZONE VALVE

G110 S

ZONE VALVE

G110 N

G411

G301

G211

G105

G104

ZV-16

ZV-17

ZV-18

ZV-15

ZV-14

24072408240924012402

ZV-13

ZV-12

ZV-11

ZV-10

2337233623342333

2341234023272312

2318232123242315

2301230223042305

2310230923072306

220322012101

BASEMENT

FIRST FLOOR

SECOND FLOOR

PENTHOUSE

3"

3"

1 1/4"

3"

2"

2" 2"2"2"

1"1 1/4"

1"

1 1/4"

1 1/2"

1 1/4" TYP

1 1/2" 1 1/4"

1 1/4"

1 1/2"

1"

1"

1"1" 1"

MEDICAL

VACUUM PUMP

2"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

ACC

B

IM

/2

V A

O m a h a a n d

G ra n d I s la n d /B

V A

O m a h a

M

E P

.r v t

/2

/2

:4

:1

P

M

ACC-PG401

MEDICAL GAS RISER DIAGRAM -

MEDICAL VACUUM

MEDICAL GAS SYSTEM

INSPECTION AND ASSESSMENT

4101 WOOLWORTH AVE, OMAHA, NE 68105

36C26323Q1052

01/28/2024

NO SCALE

ACC MEDICAL GAS RISER DIAGRAM - VACUUM

MEDICAL AIR

COMPRESSOR

ZONE VALVE

G510

ZONE VALVE

ZONE VALVE

ZONE VALVE

G110 S

ZONE VALVE

G110 N

ZONE VALVE

G411

G301

G211

G105

G104

ZONE VALVE

ZONE VALVE

ZONE VALVE

11011101

ZV-16

ZV-17

ZV-18

ZV-15

ZV-14

24072408240924012402

ZV-13

ZV-12

ZV-11

ZV-10

2337233623342333

2341234023172312

2318232123242315

2301230223042305

2310230923072306

220322012101

1"

MEDICAL AIR

INTAKE

3/4"

3/4"

3/4"

BASEMENT

FIRST FLOOR

SECOND FLOOR

PENTHOUSE

3/4"

1"

3/4"

1"

3/4"

1"

3/4"

3/4"

MEDICAL AIR

COMPRESSOR

1"

MEDICAL AIR

INTAKE FROM AHU

SUPPLY DUCT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

ACC

B

IM

/2

V A

O m a h a a n d

G ra n d I s la n d /B

V A

O m a h a

M

E P

.r v t

/2

/2

:4

:1

P

M

ACC-PG402

MEDICAL GAS RISER DIAGRAM -

MEDICAL AIR

MEDICAL GAS SYSTEM

INSPECTION AND ASSESSMENT

4101 WOOLWORTH AVE, OMAHA, NE 68105

36C26323Q1052

01/28/2024

NO SCALE

ACC MEDICAL GAS RISER DIAGRAM - MEDICAL AIR

BASEMENT

FIRST FLOOR

SECOND FLOOR

PENTHOUSE

ZV-16

ZV-17

ZV-18

ZV-15

ZV-14

24072408240924012402

CARBON

DIOXIDE

MANIFOLD

3/4"

3/4"1/2"

TYP.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

ACC

B

IM

/2

V A

O m a h a a n d

G ra n d I s la n d /B

V A

O m a h a

M

E P

.r v t

/2

/2

:4

:1

P

M

ACC-PG403

MEDICAL GAS RISER DIAGRAM -

CARBON DIOXIDE

MEDICAL GAS SYSTEM

INSPECTION AND ASSESSMENT

4101 WOOLWORTH AVE, OMAHA, NE 68105

36C26323Q1052

01/28/2024

NO SCALE

ACC MEDICAL GAS RISER DIAGRAM - CARBON DIOXIDE

ZV-16

ZV-17

ZV-18

ZV-15

ZV-14

24072408240924012402

NITROUS

OXIDE

MANIFOLD

1/2"

1/2"

BASEMENT

FIRST FLOOR

SECOND FLOOR

PENTHOUSE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

ACC

B

IM

/2

V A

O m a h a a n d

G ra n d I s la n d /B

V A

O m a h a

M

E P

.r v t

/2

/2

:4

:1

P

M

ACC-PG404

MEDICAL GAS RISER DIAGRAM -

NITROUS OXIDE

MEDICAL GAS SYSTEM

INSPECTION AND ASSESSMENT

4101 WOOLWORTH AVE, OMAHA, NE 68105

36C26323Q1052

01/28/2024

NO SCALE

ACC MEDICAL GAS RISER DIAGRAM - NITROUS OXIDE

NITROGEN

MANIFOLD

ZV-16

ZV-17

ZV-18

ZV-15

ZV-14

24072408240924012402

1 1/4"

3/4"

BASEMENT

FIRST FLOOR

SECOND FLOOR

PENTHOUSE

3/4"

TYP

1 1/4"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project :

ACC

B

IM

/2

V A

O m a h a a n d

G ra n d I s la n d /B

V A

O m a h a

M

E P

.r v t

/2

/2

:4

:1

P

M

ACC-PG405

MEDICAL GAS RISER DIAGRAM -

NITROGEN

MEDICAL GAS SYSTEM

INSPECTION AND ASSESSMENT

4101 WOOLWORTH AVE, OMAHA, NE 68105

36C26323Q1052

01/28/2024

NO SCALE

ACC MEDICAL GAS RISER DIAGRAM - NITROGEN

B01_23377_VA Omaha_MEP_21 - Sheet - ACC-P000 - SYMBOLS AND ABBREVIATIONS
B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG10B - BASEMENT LEVEL - OVERALL - MEDICAL GAS
B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG10BA - BASEMENT LEVEL - AREA A - MEDICAL GAS
B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG10BB - BASEMENT LEVEL - AREA B - MEDICAL GAS
B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG10BC - BASEMENT LEVEL - AREA C - MEDICAL GAS
B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG101 - FIRST LEVEL - OVERALL - MEDICAL GAS
B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG101A - FIRST LEVEL - AREA A - MEDICAL GAS
B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG101B - FIRST LEVEL - AREA B - MEDICAL GAS
B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG101C - FIRST LEVEL - AREA C - MEDICAL GAS
B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG102 - SECOND LEVEL - OVERALL - MEDICAL GAS
B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG102A - SECOND LEVEL - AREA A - MEDICAL GAS
B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG102B - SECOND LEVEL - AREA B - MEDICAL GAS
B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG102C - SECOND LEVEL - AREA C - MEDICAL GAS
B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG103 - THIRD LEVEL - OVERALL - MEDICAL GAS
B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG103B - PENTHOUSE LEVEL - AREA B - MEDICAL GAS
B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG400 - ACC MEDICAL GAS RISER DIAGRAM - OXYGEN
B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG401 - MEDICAL GAS RISER DIAGRAM - MEDICAL VACUUM
B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG402 - MEDICAL GAS RISER DIAGRAM - MEDICAL AIR
B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG403 - MEDICAL GAS RISER DIAGRAM - CARBON DIOXIDE
B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG404 - MEDICAL GAS RISER DIAGRAM - NITROUS OXIDE
B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG405 - MEDICAL GAS RISER DIAGRAM - NITROGEN