This document is a solicitation for a commercial contract to provide medical gas maintenance services to the VA Nebraska-Western Iowa Health Care System. The solicitation is a total set-aside for Veteran-Owned Small Businesses, with a period of performance from July 1, 2024 to June 30, 2029. The Department of Veterans Affairs is seeking quotes for an Indefinite Delivery Indefinite Quantity contract to perform medical gas system maintenance, inspections, and repairs at facilities within the VA Nebraska-Western Iowa Health Care System. Quotes are due by June 6, 2024. The contract will be a firm fixed-price award, with the NAICS code 541350 (Building Inspection Services) and a size standard of $11.5 million. Technical questions on the solicitation are due by May 30, 2024.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MEDICAL GAS SYMBOLS
SYMBOL DESCRIPTION ADDITIONAL REMARKS
ALARM / CONTROL PANEL (MASTER OR
AREA)
ZONE VALVE BOX
# OF CIRCLES/PIPES INDICATES NUMBER OF
VALVES; ARROW INDICATES VALVE ACCESS SIDE
REFER TO MOUNTING HEIGHTS DETAIL FOR MOUNTING ELEVATION
REFER TO ABBREVIATIONS FOR TYPE
REFER TO MOUNTING HEIGHTS DETAIL FOR MOUNTING ELEVATION
EMERGENCY OXYGEN CONNECTION REFER TO MOUNTING HEIGHTS DETAIL FOR MOUNTING ELEVATION
ISOLATION VALVE
REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM.
LOCATE ABOVE CEILING AND PROVIDE WITH LOCKABLE HANDLE.
SENSING LOCATION XXXX
MEDICAL GAS OUTLET
REFER TO ABBREVIATIONS FOR GAS TYPE. PROVIDE BRACKET WITH EACH
VACUUM OUTLET. REFER TO MOUNTING HEIGHTS DETAILS FOR MOUNTING
ELEVATION. COORDINATE WITH ARCHITECTURAL DIVISION.
ABBREVIATION
LABORATORY AND MEDICAL GAS ABBREVIATIONS
DESCRIPTION
MEDICAL COMPRESSED AIRA
MEDICAL COMPRESSED AIR INTAKEAI
AREA ALARM PANELAAP
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS
COMPRESSED AIR (NON-MEDICAL)CA
MEDICAL CARBON DIOXIDEC
DENTAL AIRDA
DENTAL AIR INTAKEDAI
DENTAL VACUUMDV
DENTAL VACUUM EXHAUSTDVE
EMERGENCY OXYGEN CONNECTIONEOC
MEDICAL HELIUMHE
HORSEPOWERHP
INSTRUMENT AIRIA
INSTRUMENT AIR INTAKEIAI
LABORATORY AIR LA
LABORATORY AIR INTAKELAI
ABBREVIATION DESCRIPTION
LABORATORY VACUUMLV
LABORATORY VACUUM EXHAUSTLVE
MEDICAL AIR COMPRESSORMAC
MASTER ALARM PANELMAP
MEDICAL VACUUM PUMPMVP
MEDICAL NITROGENN
MEDICAL NITROUS OXIDENO
MEDICAL OXYGENO
PRESSURE REDUCING VALVEPRV
MEDICAL VACUUMV
MEDICAL VACUUM EXHAUSTVE
VALVE BOXVB
MEDICAL WASTE ANESTHESIA GAS DISPOSALWAG
WATER COLUMNWC
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
ACC
B
IM
/2
V A
O m a h a a n d
G ra n d I s la n d /B
V A
O m a h a
M
E P
.r v t
/2
/2
:4
:5
P
M
ACC-P000
SYMBOLS AND ABBREVIATIONS MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT
4101 WOOLWORTH AVE, OMAHA, NE 68105
36C26323Q1052
01/28/2024 RJH HLPRevisions: Date:
SHEET INDEX - ACC
SHEET NUMBER SHEET NAME
ACC-P000 SYMBOLS AND ABBREVIATIONS
ACC-PG10B BASEMENT LEVEL - OVERALL - MEDICAL GAS
ACC-PG10BA BASEMENT LEVEL - AREA A - MEDICAL GAS
ACC-PG10BB BASEMENT LEVEL - AREA B - MEDICAL GAS
ACC-PG10BC BASEMENT LEVEL - AREA C - MEDICAL GAS
ACC-PG101 FIRST LEVEL - OVERALL - MEDICAL GAS
ACC-PG101A FIRST LEVEL - AREA A - MEDICAL GAS
ACC-PG101B FIRST LEVEL - AREA B - MEDICAL GAS
ACC-PG101C FIRST LEVEL - AREA C - MEDICAL GAS
ACC-PG102 SECOND LEVEL - OVERALL - MEDICAL GAS
ACC-PG102A SECOND LEVEL - AREA A - MEDICAL GAS
ACC-PG102B SECOND LEVEL - AREA B - MEDICAL GAS
ACC-PG102C SECOND LEVEL - AREA C - MEDICAL GAS
ACC-PG103 THIRD LEVEL - OVERALL - MEDICAL GAS
ACC-PG103B PENTHOUSE LEVEL - AREA B - MEDICAL GAS
ACC-PG400 ACC MEDICAL GAS RISER DIAGRAM - OXYGEN
ACC-PG401 MEDICAL GAS RISER DIAGRAM - MEDICAL VACUUM
ACC-PG402 MEDICAL GAS RISER DIAGRAM - MEDICAL AIR
ACC-PG403 MEDICAL GAS RISER DIAGRAM - CARBON DIOXIDE
ACC-PG404 MEDICAL GAS RISER DIAGRAM - NITROUS OXIDE
ACC-PG405 MEDICAL GAS RISER DIAGRAM - NITROGEN
UP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A
B
C
KEY PLAN
N
ACC
B
IM
/2
V A
O m a h a a n d
G ra n d I s la n d /B
V A
O m a h a
M
E P
.r v t
/2
/2
:4
:5
P
M
ACC-PG10B
BASEMENT LEVEL - OVERALL -
MEDICAL GAS
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT
4101 WOOLWORTH AVE, OMAHA, NE 68105
36C26323Q1052
01/28/2024 RJH HLP
1/16" = 1'-0"
BASEMENT LEVEL - OVERALL - MEDICAL GAS
Revisions: Date:
200 SF
TELECOMMUNICATIONS
RM.
G011
UP
G320
G015
G018
G402G312
G401G311 G300.B
G302
G300.A
G301.A
G401.A
G402.AG312.A
G311.AG301
G322
G013 G014
G300
G012
G302
G120
G220
G003
G005
G007
G202
G201G111
G112
G212
G100.B
G200.B
G100.A
G211.A
G112.AG111.A
G201.A
G202.A
G211
G222
G002
G006.A
G000.A
G050
G200
G006
G001
SG002
G122
G200.A
G101
G103
G051
G052
EL-2
EL-3
G010
G002.A
G102
G100
G121
EL-1
G009G008
O2-G104-1
VAC-G104-1
MA-G104-1
O2-G211-1
VAC-G211-1
MA-G211-1
O2-G301-1
VAC-G301-1
MA-G301-1
3/4" A 2" V
1/2" O
3/4" A 2" V 1/2" O
1/2" O 2" V 3/4" A 3/4" A
1/2" O 2" V
1/2" O 2" V 3/4" A
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 LABELING WITHIN PANEL INACCURATE VA SPECIFICATIONS 26 0511
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7
6 MEDICAL GAS PIPING SHALL NOT BE PAINTED 5.1.11.1.5
7 NON-COMPLIANT MEDICAL GAS VALVE 5.1.4.6
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
MEDICAL GAS DEFICIENCY LIST
8 ZONE VALVE DOES NOT PROPERLY LABEL AREAS SERVED 5.1.11.2.8
9 MEDICAL GAS PIPING NOT PROPERLY LABELED NFPA 99 2024 5.1.11.1
10 ZONE VALVE BOX SHALL NOT BE INSTALLED WHERE HIDDEN FROM PLAIN VIEW 5.1.4.6.1
11 ZONE VALVE BOX SHALL BE IN LOCATION SUCH THAT WALL INTERVENES BOX AND OUTLETS SERVED
12 ALL ANESTHETIZING LOCATIONS SHALL HAVE DEDICATED ZONE VALVE BOX
13 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE 517.32(C), 517.35
NFPA 99 2024
NFPA 99 2024
NFPA 70 2023
14 MEDICAL AIR SHALL BE USED ONLY FOR HUMAN RESPIRATION OR CALIBRATION OF MEDICAL DEVICES 5.1.3.6.2
15 ZONE VALVE SHALL NOT BE LOCATED DOWNSTREAM OF ANOTHER ZONE VALVE NFPA 99 2024 5.1.4.6.2
16 WAGD PIPING TO BE CONNECTED TO MEDICAL VACUUM DOWNSTREAM OF ZONE VALVE VA PLUMBING DESIGN MANUAL 8.2.3.e
17 EACH ZONE VALVE SHALL HAVE AN AREA ALARM PANEL FOR ALARMING 8.2.4
18 EACH MAIN LINE OFF A RISER SHALL HAVE A SHUTOFF VALVE 5.1.4.4
19 ALL OUTLETS SHALL BE SUPPLIED THROUGH A ZONE VALVE 5.1.4.6.1
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
VA PLUMBING DESIGN MANUAL
5.1.4.6.1
5.1.4.6.2
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
GENERAL NOTES:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A
B
C
KEY PLAN
N
ACC
B
IM
/2
V A
O m a h a a n d
G ra n d I s la n d /B
V A
O m a h a
M
E P
.r v t
/2
/2
:4
:5
P
M
ACC-PG10BA
BASEMENT LEVEL - AREA A -
MEDICAL GAS
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT
4101 WOOLWORTH AVE, OMAHA, NE 68105
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
BASEMENT LEVEL - AREA A - MEDICAL GAS
G320
G405 G305
G317
G314
G316G306
G407
G408
G406
G404
G318G308
G307
G402G312
G313G303 G403
G302
G320.A
G328G327
G320.D
G426
G321
G309
G330
G330.A
SG004
G304
G306
G308
G307
G303
G302
G309
G310
G304
G306
G308
G307
G303
G309
G304
G306
G308
G307
G309
G315 G320.B
G320.C G319
G409
G126
G120
G220
G228
G118.A
G205
G214
G217
G204
G207
G218
G216
G208
G206
G117 G107
G118G108
G202
G112
G213G203
G212
G104.A
G114.A
G202.A
G105
G219
G220.A
G226
G123
G227G127
G220.D G120.C
G128
G124.A
G221
G059
G061
G060
G109
G110 G210
G130
G220.B
G230.AG130.A
G063
G065
G062
G113
G104
G106
G114
G103
G054
G053
G052
G055
G120.A
SG004
G119
G056
G125
G124
G215
G064
G310
G220.C
EL-4
G105.A
G121
G057
G110.A
G140
G113.A
EL-5
G209
G230
GLSL
O2-G104-1
VAC-G104-1
MA-G104-1
O2-G301-1
VAC-G301-1
MA-G301-1
O2-G105-1
VAC-G105-1
MA-G105-1
1/2" O 2" V 3/4" A
3/4" A 2" V
1/2" O
1/2" O 2" V 3/4" A
1 1/4" O DN
& OVER TO
BULK SYSTEM
RELIEF VENT
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 LABELING WITHIN PANEL INACCURATE VA SPECIFICATIONS 26 0511
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7
6 MEDICAL GAS PIPING SHALL NOT BE PAINTED 5.1.11.1.5
7 NON-COMPLIANT MEDICAL GAS VALVE 5.1.4.6
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
MEDICAL GAS DEFICIENCY LIST
8 ZONE VALVE DOES NOT PROPERLY LABEL AREAS SERVED 5.1.11.2.8
9 MEDICAL GAS PIPING NOT PROPERLY LABELED NFPA 99 2024 5.1.11.1
10 ZONE VALVE BOX SHALL NOT BE INSTALLED WHERE HIDDEN FROM PLAIN VIEW 5.1.4.6.1
11 ZONE VALVE BOX SHALL BE IN LOCATION SUCH THAT WALL INTERVENES BOX AND OUTLETS SERVED
12 ALL ANESTHETIZING LOCATIONS SHALL HAVE DEDICATED ZONE VALVE BOX
13 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE 517.32(C), 517.35
NFPA 99 2024
NFPA 99 2024
NFPA 70 2023
14 MEDICAL AIR SHALL BE USED ONLY FOR HUMAN RESPIRATION OR CALIBRATION OF MEDICAL DEVICES 5.1.3.6.2
15 ZONE VALVE SHALL NOT BE LOCATED DOWNSTREAM OF ANOTHER ZONE VALVE NFPA 99 2024 5.1.4.6.2
16 WAGD PIPING TO BE CONNECTED TO MEDICAL VACUUM DOWNSTREAM OF ZONE VALVE VA PLUMBING DESIGN MANUAL 8.2.3.e
17 EACH ZONE VALVE SHALL HAVE AN AREA ALARM PANEL FOR ALARMING 8.2.4
18 EACH MAIN LINE OFF A RISER SHALL HAVE A SHUTOFF VALVE 5.1.4.4
19 ALL OUTLETS SHALL BE SUPPLIED THROUGH A ZONE VALVE 5.1.4.6.1
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
VA PLUMBING DESIGN MANUAL
5.1.4.6.1
5.1.4.6.2
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
GENERAL NOTES:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A
B
C
KEY PLAN
N
ACC
B
IM
/2
V A
O m a h a a n d
G ra n d I s la n d /B
V A
O m a h a
M
E P
.r v t
/2
/2
:4
:5
P
M
ACC-PG10BB
BASEMENT LEVEL - AREA B -
MEDICAL GAS
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT
4101 WOOLWORTH AVE, OMAHA, NE 68105
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
BASEMENT LEVEL - AREA B - MEDICAL GAS
265 SF
RM.
G433
G420
G405
G019G018 G021
G502
G407
G418
G417
G408
G416G406
G414 G404
G402
G401
G400.B
G403
G413
G412
G411.A
G415
G401.A
G402.A
G411
G419
G420.A
G422
G427
G420.D
G431
G426
G421
G432
G506
G505
G504
G510
G330
G300
G023
G420.B
G430.A
SG003
G507
G020
G501
G503
G430
G428
G016
G017
G420.CG409
G501.1 G502.1
AREA ALARM PANEL
120V/1Ø
FED FROM GLSL CIRCUIT #8
OXYGEN RESERVE MANIFOLD
120V/1Ø
FED FROM GCRLCEP CIRCUIT #2
NITROGEN MANIFOLD
120V/1Ø
FED FROM GCRLCEP CIRCUIT #8
NITROUS OXIDE MANIFOLD
120V/1Ø
FED FROM GCRLCEP CIRCUIT #4
CARBON DIOXIDE MANIFOLD
120V/1Ø
FED FROM GCRLCEP CIRCUIT #6
GEQDPH
GCRLCEP
O2-G411-1
VAC-G411-1
MA-G411-1
1 1/4" N UP
1/2" NO UP
3/4" C UP
3" V UP
1" A UP
1" O UP
MEDICAL VACUUM
PUMP EXHAUST
MEDICAL AIR
INTAKE
1/2" O 2" V
3/4" A
1/2" O
3/4" A 2" V
1 1/4" O DN
& OVER TO
BULK SYSTEM
RELIEF VENT
EMERGENCY OXYGEN
CONNECTION
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 LABELING WITHIN PANEL INACCURATE VA SPECIFICATIONS 26 0511
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7
6 MEDICAL GAS PIPING SHALL NOT BE PAINTED 5.1.11.1.5
7 NON-COMPLIANT MEDICAL GAS VALVE 5.1.4.6
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
MEDICAL GAS DEFICIENCY LIST
8 ZONE VALVE DOES NOT PROPERLY LABEL AREAS SERVED 5.1.11.2.8
9 MEDICAL GAS PIPING NOT PROPERLY LABELED NFPA 99 2024 5.1.11.1
10 ZONE VALVE BOX SHALL NOT BE INSTALLED WHERE HIDDEN FROM PLAIN VIEW 5.1.4.6.1
11 ZONE VALVE BOX SHALL BE IN LOCATION SUCH THAT WALL INTERVENES BOX AND OUTLETS SERVED
12 ALL ANESTHETIZING LOCATIONS SHALL HAVE DEDICATED ZONE VALVE BOX
13 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE 517.32(C), 517.35
NFPA 99 2024
NFPA 99 2024
NFPA 70 2023
14 MEDICAL AIR SHALL BE USED ONLY FOR HUMAN RESPIRATION OR CALIBRATION OF MEDICAL DEVICES 5.1.3.6.2
15 ZONE VALVE SHALL NOT BE LOCATED DOWNSTREAM OF ANOTHER ZONE VALVE NFPA 99 2024 5.1.4.6.2
16 WAGD PIPING TO BE CONNECTED TO MEDICAL VACUUM DOWNSTREAM OF ZONE VALVE VA PLUMBING DESIGN MANUAL 8.2.3.e
17 EACH ZONE VALVE SHALL HAVE AN AREA ALARM PANEL FOR ALARMING 8.2.4
18 EACH MAIN LINE OFF A RISER SHALL HAVE A SHUTOFF VALVE 5.1.4.4
19 ALL OUTLETS SHALL BE SUPPLIED THROUGH A ZONE VALVE 5.1.4.6.1
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
VA PLUMBING DESIGN MANUAL
5.1.4.6.1
5.1.4.6.2
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
GENERAL NOTES:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A
B
C
KEY PLAN
N
ACC
B
IM
/2
V A
O m a h a a n d
G ra n d I s la n d /B
V A
O m a h a
M
E P
.r v t
/2
/2
:4
:5
P
M
ACC-PG10BC
BASEMENT LEVEL - AREA C -
MEDICAL GAS
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT
4101 WOOLWORTH AVE, OMAHA, NE 68105
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
BASEMENT LEVEL - AREA C - MEDICAL GAS
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A
B
C
KEY PLAN
N
ACC
B
IM
/2
V A
O m a h a a n d
G ra n d I s la n d /B
V A
O m a h a
M
E P
.r v t
/2
/2
:4
:5
P
M
ACC-PG101
FIRST LEVEL - OVERALL -
MEDICAL GAS
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT
4101 WOOLWORTH AVE, OMAHA, NE 68105
36C26323Q1052
01/28/2024 RJH HLP
1/16" = 1'-0"
FIRST LEVEL - OVERALL - MEDICAL GAS
199 SF
RM.
1301.A
1300.B
1300.A
1311.A
1312.A
1401.A
1402.A
1016.A
1000.A
1200.B
1100.B
1100.A
1101.A 1211.A
1201.A
1202.A
1111.A 1112.A
S1002
1/2" O
1 1/4" V 3/4" A
O2-1101-1
VAC-1101-1
MA-1101-1
O2-1211-1
VAC-1211-1
MA-1211-1
O2-1301-1
VAC-1301-1
MA-1301-1
3/4" A 1 1/4" V
1/2" O
3/4" A
1" V
1/2" O
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 LABELING WITHIN PANEL INACCURATE VA SPECIFICATIONS 26 0511
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7
6 MEDICAL GAS PIPING SHALL NOT BE PAINTED 5.1.11.1.5
7 NON-COMPLIANT MEDICAL GAS VALVE 5.1.4.6
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
MEDICAL GAS DEFICIENCY LIST
8 ZONE VALVE DOES NOT PROPERLY LABEL AREAS SERVED 5.1.11.2.8
9 MEDICAL GAS PIPING NOT PROPERLY LABELED NFPA 99 2024 5.1.11.1
10 ZONE VALVE BOX SHALL NOT BE INSTALLED WHERE HIDDEN FROM PLAIN VIEW 5.1.4.6.1
11 ZONE VALVE BOX SHALL BE IN LOCATION SUCH THAT WALL INTERVENES BOX AND OUTLETS SERVED
12 ALL ANESTHETIZING LOCATIONS SHALL HAVE DEDICATED ZONE VALVE BOX
13 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE 517.32(C), 517.35
NFPA 99 2024
NFPA 99 2024
NFPA 70 2023
14 MEDICAL AIR SHALL BE USED ONLY FOR HUMAN RESPIRATION OR CALIBRATION OF MEDICAL DEVICES 5.1.3.6.2
15 ZONE VALVE SHALL NOT BE LOCATED DOWNSTREAM OF ANOTHER ZONE VALVE NFPA 99 2024 5.1.4.6.2
16 WAGD PIPING TO BE CONNECTED TO MEDICAL VACUUM DOWNSTREAM OF ZONE VALVE VA PLUMBING DESIGN MANUAL 8.2.3.e
17 EACH ZONE VALVE SHALL HAVE AN AREA ALARM PANEL FOR ALARMING 8.2.4
18 EACH MAIN LINE OFF A RISER SHALL HAVE A SHUTOFF VALVE 5.1.4.4
19 ALL OUTLETS SHALL BE SUPPLIED THROUGH A ZONE VALVE 5.1.4.6.1
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
VA PLUMBING DESIGN MANUAL
5.1.4.6.1
5.1.4.6.2
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
GENERAL NOTES:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A
B
C
KEY PLAN
N
ACC
B
IM
/2
V A
O m a h a a n d
G ra n d I s la n d /B
V A
O m a h a
M
E P
.r v t
/2
/2
:4
:0
P
M
ACC-PG101A
FIRST LEVEL - AREA A - MEDICAL
GAS
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT
4101 WOOLWORTH AVE, OMAHA, NE 68105
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
FIRST LEVEL - AREA A - MEDICAL GAS
14021312
1320.A
13281327
1320.D
1320.B
1330.A
1320.C
12021112
1120.A
1220.A
12261127 1227
1220.D 1120.D
1220.B
1130.A 1230.A
S1004
1120.B
1120.C 1220.C
O2-1101-1
VAC-1101-1
MA-1101-1
O2-1211-1
VAC-1211-1
MA-1211-1
O2-1301-1
VAC-1301-1
MA-1301-1
1LSL
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 LABELING WITHIN PANEL INACCURATE VA SPECIFICATIONS 26 0511
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7
6 MEDICAL GAS PIPING SHALL NOT BE PAINTED 5.1.11.1.5
7 NON-COMPLIANT MEDICAL GAS VALVE 5.1.4.6
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
MEDICAL GAS DEFICIENCY LIST
8 ZONE VALVE DOES NOT PROPERLY LABEL AREAS SERVED 5.1.11.2.8
9 MEDICAL GAS PIPING NOT PROPERLY LABELED NFPA 99 2024 5.1.11.1
10 ZONE VALVE BOX SHALL NOT BE INSTALLED WHERE HIDDEN FROM PLAIN VIEW 5.1.4.6.1
11 ZONE VALVE BOX SHALL BE IN LOCATION SUCH THAT WALL INTERVENES BOX AND OUTLETS SERVED
12 ALL ANESTHETIZING LOCATIONS SHALL HAVE DEDICATED ZONE VALVE BOX
13 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE 517.32(C), 517.35
NFPA 99 2024
NFPA 99 2024
NFPA 70 2023
14 MEDICAL AIR SHALL BE USED ONLY FOR HUMAN RESPIRATION OR CALIBRATION OF MEDICAL DEVICES 5.1.3.6.2
15 ZONE VALVE SHALL NOT BE LOCATED DOWNSTREAM OF ANOTHER ZONE VALVE NFPA 99 2024 5.1.4.6.2
16 WAGD PIPING TO BE CONNECTED TO MEDICAL VACUUM DOWNSTREAM OF ZONE VALVE VA PLUMBING DESIGN MANUAL 8.2.3.e
17 EACH ZONE VALVE SHALL HAVE AN AREA ALARM PANEL FOR ALARMING 8.2.4
18 EACH MAIN LINE OFF A RISER SHALL HAVE A SHUTOFF VALVE 5.1.4.4
19 ALL OUTLETS SHALL BE SUPPLIED THROUGH A ZONE VALVE 5.1.4.6.1
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
VA PLUMBING DESIGN MANUAL
5.1.4.6.1
5.1.4.6.2
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
GENERAL NOTES:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A
B
C
KEY PLAN
N
ACC
B
IM
/2
V A
O m a h a a n d
G ra n d I s la n d /B
V A
O m a h a
M
E P
.r v t
/2
/2
:4
:0
P
M
ACC-PG101B
FIRST LEVEL - AREA B - MEDICAL
GAS
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT
4101 WOOLWORTH AVE, OMAHA, NE 68105
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
FIRST LEVEL - AREA B - MEDICAL GAS
146 SF
RM.
10211018
1400.B
1504.A
1411.A
1312.A
1401.A
1402.A
1420.A
1420.D
1430.A
1420.B
1420.C
S1003
14281426
1016.A
1" O UP
1" A UP
3" V UP
3/4" C UP
1/2" NO UP
1 1/4" N UP
1 1/4" N DN
1/2" NO DN
3/4" C DN
3" V DN
1" A DN
1" O DN
O2-1411-1
VAC-1411-1
MA-1411-1
3/4" A 1" V
1/2" O
3/4" A 1 1/4" V
1/2" O
AREA ALARM PANEL
120V/1Ø
FED FROM 1LSL CIRCUIT #4
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 LABELING WITHIN PANEL INACCURATE VA SPECIFICATIONS 26 0511
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7
6 MEDICAL GAS PIPING SHALL NOT BE PAINTED 5.1.11.1.5
7 NON-COMPLIANT MEDICAL GAS VALVE 5.1.4.6
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
MEDICAL GAS DEFICIENCY LIST
8 ZONE VALVE DOES NOT PROPERLY LABEL AREAS SERVED 5.1.11.2.8
9 MEDICAL GAS PIPING NOT PROPERLY LABELED NFPA 99 2024 5.1.11.1
10 ZONE VALVE BOX SHALL NOT BE INSTALLED WHERE HIDDEN FROM PLAIN VIEW 5.1.4.6.1
11 ZONE VALVE BOX SHALL BE IN LOCATION SUCH THAT WALL INTERVENES BOX AND OUTLETS SERVED
12 ALL ANESTHETIZING LOCATIONS SHALL HAVE DEDICATED ZONE VALVE BOX
13 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE 517.32(C), 517.35
NFPA 99 2024
NFPA 99 2024
NFPA 70 2023
14 MEDICAL AIR SHALL BE USED ONLY FOR HUMAN RESPIRATION OR CALIBRATION OF MEDICAL DEVICES 5.1.3.6.2
15 ZONE VALVE SHALL NOT BE LOCATED DOWNSTREAM OF ANOTHER ZONE VALVE NFPA 99 2024 5.1.4.6.2
16 WAGD PIPING TO BE CONNECTED TO MEDICAL VACUUM DOWNSTREAM OF ZONE VALVE VA PLUMBING DESIGN MANUAL 8.2.3.e
17 EACH ZONE VALVE SHALL HAVE AN AREA ALARM PANEL FOR ALARMING 8.2.4
18 EACH MAIN LINE OFF A RISER SHALL HAVE A SHUTOFF VALVE 5.1.4.4
19 ALL OUTLETS SHALL BE SUPPLIED THROUGH A ZONE VALVE 5.1.4.6.1
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
VA PLUMBING DESIGN MANUAL
5.1.4.6.1
5.1.4.6.2
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
GENERAL NOTES:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A
B
C
KEY PLAN
N
ACC
B
IM
/2
V A
O m a h a a n d
G ra n d I s la n d /B
V A
O m a h a
M
E P
.r v t
/2
/2
:4
:0
P
M
ACC-PG101C
FIRST LEVEL - AREA C - MEDICAL
GAS
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT
4101 WOOLWORTH AVE, OMAHA, NE 68105
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
FIRST LEVEL - AREA C - MEDICAL GAS
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A
B
C
KEY PLAN
N
ACC
B
IM
/2
V A
O m a h a a n d
G ra n d I s la n d /B
V A
O m a h a
M
E P
.r v t
/2
/2
:4
:0
P
M
ACC-PG102
SECOND LEVEL - OVERALL -
MEDICAL GAS
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT
4101 WOOLWORTH AVE, OMAHA, NE 68105
36C26323Q1052
01/28/2024 RJH HLP
1/16" = 1'-0"
SECOND LEVEL - OVERALL - MEDICAL GAS
155 SF
RM.
2100.A
2111.A
2101.A
20092008
S2002
2112.A
2501.B
2311.B
2311.A
2400.A
2400.C
2319 2320
2411.A
2316 2323
2400.B
2332.A
2332.B
1" V 3/4" A 1/2" O
1/2" O
3/4" A 1" V
1/2" O
3/4" A
1" V
1/2" O 3/4" A 1" V
1/2" O 3/4" A 1 1/4" V 1/2" C
1/2" NO
3/4" N
1/2" O 1 1/4" V
1/2" NO
3/4" A
1/2" C 3/4" N
1/2" O 1 1/4" V 3/4" A
1/2" C 3/4" N
1/2" NO
1" V 3/4" A
1/2" O
O2-2101-1
VAC-2101-1
MA-2101-1
O2-2201-1
VAC-2201-1
MA-2201-1
O2-2203-1
VAC-2203-1
MA-2203-1
O2-2301-1 O2-2301-2
VAC-2301-1
VAC-2301-2
VAC-2301-3
MA-2301-1
O2-2302-1 O2-2302-2
VAC-2302-1
VAC-2302-2
VAC-2302-3
MA-2302-1
O2-2304-1 O2-2304-2
VAC-2304-1
VAC-2304-2
VAC-2304-3
MA-2304-1
O2-2305-1 O2-2305-2
VAC-2305-1
VAC-2305-2
VAC-2305-3
MA-2305-1
O2-2318-1 O2-2318-2
VAC-2318-1
VAC-2318-2
VAC-2318-3
MA-2318-1
O2-2321-1 O2-2321-2
VAC-2321-1
VAC-2321-2
VAC-2321-3
MA-2321-1
O2-2315-1 O2-2315-2
VAC-2315-1
VAC-2315-2
VAC-2315-3
MA-2315-1
O2-2324-1 O2-2324-2
VAC-2324-1
VAC-2324-2
VAC-2324-3
MA-2324-1
O2-2333-1 O2-2333-2
VAC-2333-1
VAC-2333-2
VAC-2333-3
MA-2333-1
O2-2334-1 O2-2334-2
VAC-2334-1
VAC-2334-2
VAC-2334-3
MA-2334-1
O2-2336-1 O2-2336-2
VAC-2336-1
VAC-2336-2
VAC-2336-3
MA-2336-1
O2-2337-1 O2-2337-2
VAC-2337-1
VAC-2337-2
VAC-2337-3
MA-2337-1
O2-2401-1 O2-2401-2
VAC-2401-1
VAC-2401-2
MA-2401-1
MA-2401-2
NO2-2401-1
WAGD-2401-1
2" V UP
1" A UP
2" V 1" A
2" V
1" A 1" O
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 LABELING WITHIN PANEL INACCURATE VA SPECIFICATIONS 26 0511
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7
6 MEDICAL GAS PIPING SHALL NOT BE PAINTED 5.1.11.1.5
7 NON-COMPLIANT MEDICAL GAS VALVE 5.1.4.6
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
MEDICAL GAS DEFICIENCY LIST
8 ZONE VALVE DOES NOT PROPERLY LABEL AREAS SERVED 5.1.11.2.8
9 MEDICAL GAS PIPING NOT PROPERLY LABELED NFPA 99 2024 5.1.11.1
10 ZONE VALVE BOX SHALL NOT BE INSTALLED WHERE HIDDEN FROM PLAIN VIEW 5.1.4.6.1
11 ZONE VALVE BOX SHALL BE IN LOCATION SUCH THAT WALL INTERVENES BOX AND OUTLETS SERVED
12 ALL ANESTHETIZING LOCATIONS SHALL HAVE DEDICATED ZONE VALVE BOX
13 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE 517.32(C), 517.35
NFPA 99 2024
NFPA 99 2024
NFPA 70 2023
14 MEDICAL AIR SHALL BE USED ONLY FOR HUMAN RESPIRATION OR CALIBRATION OF MEDICAL DEVICES 5.1.3.6.2
15 ZONE VALVE SHALL NOT BE LOCATED DOWNSTREAM OF ANOTHER ZONE VALVE NFPA 99 2024 5.1.4.6.2
16 WAGD PIPING TO BE CONNECTED TO MEDICAL VACUUM DOWNSTREAM OF ZONE VALVE VA PLUMBING DESIGN MANUAL 8.2.3.e
17 EACH ZONE VALVE SHALL HAVE AN AREA ALARM PANEL FOR ALARMING 8.2.4
18 EACH MAIN LINE OFF A RISER SHALL HAVE A SHUTOFF VALVE 5.1.4.4
19 ALL OUTLETS SHALL BE SUPPLIED THROUGH A ZONE VALVE 5.1.4.6.1
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
VA PLUMBING DESIGN MANUAL
5.1.4.6.1
5.1.4.6.2
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
GENERAL NOTES:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A
B
C
KEY PLAN
N
ACC
B
IM
/2
V A
O m a h a a n d
G ra n d I s la n d /B
V A
O m a h a
M
E P
.r v t
/2
/2
:4
:0
P
M
ACC-PG102A
SECOND LEVEL - AREA A -
MEDICAL GAS
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT
4101 WOOLWORTH AVE, OMAHA, NE 68105
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
SECOND LEVEL - AREA A - MEDICAL GAS
2130.A
21142104
2106 2116
2120.D
2103 2113
2120.A
22162214
2220.A
22242223
2300.A
2300.B
22302130
2120.C
2120.B
2112.A
2311.F
2311.D
2311.B
2400.E
2311.E
2332.E
23272312
23522351
2350.A
S2004
2316 2323
2404.A
2332.D
2332.C
2332.B
2311.C
1/2" O
3/4" A
1" V
1" V 3/4" A 1/2" O 3/4" O3/4" A
1" V
1/2" O
3/4" A 1" V
1/2" O
3/4" A
1" V
1/2" O
3/4" A
1" V
1 1/4" V 3/4" A 3/4" O
1" V 3/4" A 3/4" O
1/2" O 3/4" A 1" V
1/2" O 3/4" A 1 1/4" V 1/2" C
1/2" NO
3/4" N
1/2" O 1 1/4" V
1/2" NO
3/4" A
1/2" C 3/4" N
O2-2101-1
VAC-2101-1
MA-2101-1
O2-2203-1
VAC-2203-1
MA-2203-1
O2-2304-1 O2-2304-2
VAC-2304-1
VAC-2304-2
VAC-2304-3
MA-2304-1
O2-2305-1 O2-2305-2
VAC-2305-1
VAC-2305-2
VAC-2305-3
MA-2305-1
O2-2306-1 O2-2306-2
VAC-2306-1
VAC-2306-2
VAC-2306-3
MA-2306-1
O2-2307-1 O2-2307-2
VAC-2307-1
VAC-2307-2
VAC-2307-3
MA-2307-1
O2-2309-1 O2-2309-2
VAC-2309-1
VAC-2309-2
VAC-2309-3
MA-2309-1
O2-2310-1 O2-2310-2
VAC-2310-1
VAC-2310-2
VAC-2310-3
MA-2310-1
O2-2315-1 O2-2315-2
VAC-2315-1
VAC-2315-2
VAC-2315-3
MA-2315-1
O2-2324-1 O2-2324-2
VAC-2324-1
VAC-2324-2
VAC-2324-3
MA-2324-1
O2-2312-1 O2-2312-2
VAC-2312-1
VAC-2312-2
VAC-2312-3
MA-2312-1
O2-2327-1 O2-2327-2
VAC-2327-1
VAC-2327-2
VAC-2327-3
MA-2327-1
O2-2341-1 O2-2341-2
VAC-2341-1
VAC-2341-2
VAC-2341-3
MA-2341-1
O2-2340-1 O2-2340-2
VAC-2340-1
VAC-2340-2
VAC-2340-3
MA-2340-1
O2-2336-1 O2-2336-2
VAC-2336-1
VAC-2336-2
VAC-2336-3
MA-2336-1
1" V 3/4" A 1/2" O
O2-2337-1 O2-2337-2
VAC-2337-1
VAC-2337-2
VAC-2337-3
MA-2337-1
O2-2402-1 O2-2402-2
VAC-2402-1
VAC-2402-2
MA-2402-1
MA-2402-2
NO2-2402-1
WAGD-2402-1
MASTER ALARM PANEL
120V/1Ø
FED FROM 2LSL CIRCUIT #6
AREA ALARM PANEL
120V/1Ø
FED FROM 2LSL CIRCUIT #5
AREA ALARM PANEL
120V/1Ø
FED FROM 2LSL CIRCUIT #7
2LSL
2" V UP
1" A UP
2" V 1" A
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 LABELING WITHIN PANEL INACCURATE VA SPECIFICATIONS 26 0511
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7
6 MEDICAL GAS PIPING SHALL NOT BE PAINTED 5.1.11.1.5
7 NON-COMPLIANT MEDICAL GAS VALVE 5.1.4.6
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
MEDICAL GAS DEFICIENCY LIST
8 ZONE VALVE DOES NOT PROPERLY LABEL AREAS SERVED 5.1.11.2.8
9 MEDICAL GAS PIPING NOT PROPERLY LABELED NFPA 99 2024 5.1.11.1
10 ZONE VALVE BOX SHALL NOT BE INSTALLED WHERE HIDDEN FROM PLAIN VIEW 5.1.4.6.1
11 ZONE VALVE BOX SHALL BE IN LOCATION SUCH THAT WALL INTERVENES BOX AND OUTLETS SERVED
12 ALL ANESTHETIZING LOCATIONS SHALL HAVE DEDICATED ZONE VALVE BOX
13 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE 517.32(C), 517.35
NFPA 99 2024
NFPA 99 2024
NFPA 70 2023
14 MEDICAL AIR SHALL BE USED ONLY FOR HUMAN RESPIRATION OR CALIBRATION OF MEDICAL DEVICES 5.1.3.6.2
15 ZONE VALVE SHALL NOT BE LOCATED DOWNSTREAM OF ANOTHER ZONE VALVE NFPA 99 2024 5.1.4.6.2
16 WAGD PIPING TO BE CONNECTED TO MEDICAL VACUUM DOWNSTREAM OF ZONE VALVE VA PLUMBING DESIGN MANUAL 8.2.3.e
17 EACH ZONE VALVE SHALL HAVE AN AREA ALARM PANEL FOR ALARMING 8.2.4
18 EACH MAIN LINE OFF A RISER SHALL HAVE A SHUTOFF VALVE 5.1.4.4
19 ALL OUTLETS SHALL BE SUPPLIED THROUGH A ZONE VALVE 5.1.4.6.1
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
VA PLUMBING DESIGN MANUAL
5.1.4.6.1
5.1.4.6.2
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
GENERAL NOTES:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A
B
C
KEY PLAN
N
ACC
B
IM
/2
V A
O m a h a a n d
G ra n d I s la n d /B
V A
O m a h a
M
E P
.r v t
/2
/2
:4
:1
P
M
ACC-PG102B
SECOND LEVEL - AREA B -
MEDICAL GAS
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT
4101 WOOLWORTH AVE, OMAHA, NE 68105
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
SECOND LEVEL - AREA B - MEDICAL GAS
162 SF
RM.
2400.E
2412.B
2400.A
2400.C
2412.F
2412.D
2412.A
2412.E
2412.C
2416 2419
2428 2429
2417 2418
2411.A
S2003
2" V 1" A
1" O 3/4" N
1/2" NO
3/4" C
3" V 3/4" A
1/2" O
1/2" O
1/2" O 1 1/4" V
1/2" NO
3/4" A
1/2" C 3/4" N
1/2" O 1 1/4" V 3/4" A
1/2" C 3/4" N
1/2" NO
1" O DN
1" A DN
3" V DN
3/4" C DN
1/2" NO DN
1 1/4" N DN1/2" O
1 1/4" V 3/4" A
1/2" NO
3/4" N 1/2" C
1/2" O 1 1/4" V 3/4" A
1/2" NO1/2" C
3/4" N
1/2" O 1 1/4" V 3/4" A
1/2" NO
3/4" N 1/2" C
O2-2401-1 O2-2401-2
VAC-2401-1
VAC-2401-2
MA-2401-1
MA-2401-2
NO2-2401-1
WAGD-2401-1
O2-2401-3
VAC-2401-3
VAC-2401-4
MA-2401-3
N2-2401-1
CO2-2401-1
O2-2402-1 O2-2402-2
VAC-2402-1
VAC-2402-2
MA-2402-1
MA-2402-2
NO2-2402-1
WAGD-2402-1
O2-2402-3
VAC-2402-3
VAC-2402-4
MA-2402-3
N2-2402-1
CO2-2402-1
O2-2407-2 O2-2407-3
VAC-2407-3
VAC-2407-4
MA-2407-2
MA-2407-3
NO2-2407-1
WAGD-2407-1
O2-2407-1
VAC-2407-1
VAC-2407-2
MA-2407-1
N2-2407-1
CO2-2407-1
O2-2408-2 O2-2408-3
VAC-2408-3
VAC-2408-4
MA-2408-2
MA-2408-3
NO2-2408-1
WAGD-2408-1
O2-2408-1
VAC-2408-1
VAC-2408-2
MA-2408-1
N2-2408-1
CO2-2408-1
O2-2409-2 O2-2409-3
VAC-2409-3
VAC-2409-4
MA-2409-2
MA-2409-3
NO2-2409-1
WAGD-2409-1
O2-2409-1
VAC-2409-1
VAC-2409-2
MA-2409-1
N2-2409-1
CO2-2409-1
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 LABELING WITHIN PANEL INACCURATE VA SPECIFICATIONS 26 0511
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7
6 MEDICAL GAS PIPING SHALL NOT BE PAINTED 5.1.11.1.5
7 NON-COMPLIANT MEDICAL GAS VALVE 5.1.4.6
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
MEDICAL GAS DEFICIENCY LIST
8 ZONE VALVE DOES NOT PROPERLY LABEL AREAS SERVED 5.1.11.2.8
9 MEDICAL GAS PIPING NOT PROPERLY LABELED NFPA 99 2024 5.1.11.1
10 ZONE VALVE BOX SHALL NOT BE INSTALLED WHERE HIDDEN FROM PLAIN VIEW 5.1.4.6.1
11 ZONE VALVE BOX SHALL BE IN LOCATION SUCH THAT WALL INTERVENES BOX AND OUTLETS SERVED
12 ALL ANESTHETIZING LOCATIONS SHALL HAVE DEDICATED ZONE VALVE BOX
13 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE 517.32(C), 517.35
NFPA 99 2024
NFPA 99 2024
NFPA 70 2023
14 MEDICAL AIR SHALL BE USED ONLY FOR HUMAN RESPIRATION OR CALIBRATION OF MEDICAL DEVICES 5.1.3.6.2
15 ZONE VALVE SHALL NOT BE LOCATED DOWNSTREAM OF ANOTHER ZONE VALVE NFPA 99 2024 5.1.4.6.2
16 WAGD PIPING TO BE CONNECTED TO MEDICAL VACUUM DOWNSTREAM OF ZONE VALVE VA PLUMBING DESIGN MANUAL 8.2.3.e
17 EACH ZONE VALVE SHALL HAVE AN AREA ALARM PANEL FOR ALARMING 8.2.4
18 EACH MAIN LINE OFF A RISER SHALL HAVE A SHUTOFF VALVE 5.1.4.4
19 ALL OUTLETS SHALL BE SUPPLIED THROUGH A ZONE VALVE 5.1.4.6.1
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
VA PLUMBING DESIGN MANUAL
5.1.4.6.1
5.1.4.6.2
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
GENERAL NOTES:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A
B
C
KEY PLAN
N
ACC
B
IM
/2
V A
O m a h a a n d
G ra n d I s la n d /B
V A
O m a h a
M
E P
.r v t
/2
/2
:4
:1
P
M
ACC-PG102C
SECOND LEVEL - AREA C -
MEDICAL GAS
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT
4101 WOOLWORTH AVE, OMAHA, NE 68105
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
SECOND LEVEL - AREA C - MEDICAL GAS
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A
B
C
KEY PLAN
N
ACC
B
IM
/2
V A
O m a h a a n d
G ra n d I s la n d /B
V A
O m a h a
M
E P
.r v t
/2
/2
:4
:1
P
M
ACC-PG103
THIRD LEVEL - OVERALL -
MEDICAL GAS
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT
4101 WOOLWORTH AVE, OMAHA, NE 68105
36C26323Q1052
01/28/2024 RJH HLP
1/16" = 1'-0"
THIRD LEVEL - OVERALL - MEDICAL GAS
MEDICAL AIR COMPRESSOR
480V/3Ø
FED FROM PEQDPH CIRCUIT #31, 33, 35
MEDICAL VACUUM PUMP
480V/3Ø
FED FROM PEQDPH CIRCUIT #25, 27, 29
P E
Q D
P H
VAC EXHAUST
TERMINATION
MEDICAL AIR INTAKE
FROM AHU SUPPLY DUCT
3/4" AI DN
4" VE DN
2" V 1" A
2" V DN
1" A DN
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 LABELING WITHIN PANEL INACCURATE VA SPECIFICATIONS 26 0511
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7
6 MEDICAL GAS PIPING SHALL NOT BE PAINTED 5.1.11.1.5
7 NON-COMPLIANT MEDICAL GAS VALVE 5.1.4.6
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
MEDICAL GAS DEFICIENCY LIST
8 ZONE VALVE DOES NOT PROPERLY LABEL AREAS SERVED 5.1.11.2.8
9 MEDICAL GAS PIPING NOT PROPERLY LABELED NFPA 99 2024 5.1.11.1
10 ZONE VALVE BOX SHALL NOT BE INSTALLED WHERE HIDDEN FROM PLAIN VIEW 5.1.4.6.1
11 ZONE VALVE BOX SHALL BE IN LOCATION SUCH THAT WALL INTERVENES BOX AND OUTLETS SERVED
12 ALL ANESTHETIZING LOCATIONS SHALL HAVE DEDICATED ZONE VALVE BOX
13 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE 517.32(C), 517.35
NFPA 99 2024
NFPA 99 2024
NFPA 70 2023
14 MEDICAL AIR SHALL BE USED ONLY FOR HUMAN RESPIRATION OR CALIBRATION OF MEDICAL DEVICES 5.1.3.6.2
15 ZONE VALVE SHALL NOT BE LOCATED DOWNSTREAM OF ANOTHER ZONE VALVE NFPA 99 2024 5.1.4.6.2
16 WAGD PIPING TO BE CONNECTED TO MEDICAL VACUUM DOWNSTREAM OF ZONE VALVE VA PLUMBING DESIGN MANUAL 8.2.3.e
17 EACH ZONE VALVE SHALL HAVE AN AREA ALARM PANEL FOR ALARMING 8.2.4
18 EACH MAIN LINE OFF A RISER SHALL HAVE A SHUTOFF VALVE 5.1.4.4
19 ALL OUTLETS SHALL BE SUPPLIED THROUGH A ZONE VALVE 5.1.4.6.1
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
NFPA 99 2024
VA PLUMBING DESIGN MANUAL
5.1.4.6.1
5.1.4.6.2
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
GENERAL NOTES:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
A
B
C
KEY PLAN
N
ACC
B
IM
/2
V A
O m a h a a n d
G ra n d I s la n d /B
V A
O m a h a
M
E P
.r v t
/2
/2
:4
:1
P
M
ACC-PG103B
PENTHOUSE LEVEL - AREA B -
MEDICAL GAS
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT
4101 WOOLWORTH AVE, OMAHA, NE 68105
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
THIRD LEVEL - AREA B - MEDICAL GAS
OXYGEN
RESERVE
MANIFOLD
1 1/4" TO BULK
SYSTEM
RELIEF VENTZONE VALVE
G411
ZONE VALVE
G301
ZONE VALVE
G211
ZONE VALVE
G110 S
ZONE VALVE
G110 N
G411
G301
G211
G105
G104
ZONE VALVE
ZONE VALVE
ZONE VALVE
ZONE VALVE
11011101
ZV-16
ZV-17
ZV-18
ZV-15
ZV-14
24072408240924012402
ZV-13
ZV-12
ZV-11
ZV-10
2337233623342333
2341234023272312
2318232123242315
2301230223042305
2310230923072306
220322012101
1 1/4"
1"
1/2" TYP.
1/2" TYP
1/2" TYP
1"
3/4"
BASEMENT
FIRST FLOOR
SECOND FLOOR
PENTHOUSE
EMERGENCY
OXYGEN
CONNECTION
1 1/4"
1/2"
1"
1/2" TYP
1"1/2"
1"
3/4"
1/2"
1/2"3/4"
1/2"
1/2"
1/2"1/2"1/2"1/2"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
ACC
B
IM
/2
V A
O m a h a a n d
G ra n d I s la n d /B
V A
O m a h a
M
E P
.r v t
/2
/2
:4
:1
P
M
ACC-PG400
ACC MEDICAL GAS RISER
DIAGRAM - OXYGEN
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT
4101 WOOLWORTH AVE, OMAHA, NE 68105
36C26323Q1052
01/28/2024
NO SCALE
ACC MEDICAL GAS RISER DIAGRAM - OXYGEN
MEDICAL
VACUUM PUMP
ZONE VALVE
ZONE VALVE
ZONE VALVE
ZONE VALVE
11011101
ZONE VALVE
G411
ZONE VALVE
G301
ZONE VALVE
G211
ZONE VALVE
G110 S
ZONE VALVE
G110 N
G411
G301
G211
G105
G104
ZV-16
ZV-17
ZV-18
ZV-15
ZV-14
24072408240924012402
ZV-13
ZV-12
ZV-11
ZV-10
2337233623342333
2341234023272312
2318232123242315
2301230223042305
2310230923072306
220322012101
BASEMENT
FIRST FLOOR
SECOND FLOOR
PENTHOUSE
3"
3"
1 1/4"
3"
2"
2" 2"2"2"
1"1 1/4"
1"
1 1/4"
1 1/2"
1 1/4" TYP
1 1/2" 1 1/4"
1 1/4"
1 1/2"
1"
1"
1"1" 1"
MEDICAL
VACUUM PUMP
2"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
ACC
B
IM
/2
V A
O m a h a a n d
G ra n d I s la n d /B
V A
O m a h a
M
E P
.r v t
/2
/2
:4
:1
P
M
ACC-PG401
MEDICAL GAS RISER DIAGRAM -
MEDICAL VACUUM
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT
4101 WOOLWORTH AVE, OMAHA, NE 68105
36C26323Q1052
01/28/2024
NO SCALE
ACC MEDICAL GAS RISER DIAGRAM - VACUUM
MEDICAL AIR
COMPRESSOR
ZONE VALVE
G510
ZONE VALVE
ZONE VALVE
ZONE VALVE
G110 S
ZONE VALVE
G110 N
ZONE VALVE
G411
G301
G211
G105
G104
ZONE VALVE
ZONE VALVE
ZONE VALVE
11011101
ZV-16
ZV-17
ZV-18
ZV-15
ZV-14
24072408240924012402
ZV-13
ZV-12
ZV-11
ZV-10
2337233623342333
2341234023172312
2318232123242315
2301230223042305
2310230923072306
220322012101
1"
MEDICAL AIR
INTAKE
3/4"
3/4"
3/4"
BASEMENT
FIRST FLOOR
SECOND FLOOR
PENTHOUSE
3/4"
1"
3/4"
1"
3/4"
1"
3/4"
3/4"
MEDICAL AIR
COMPRESSOR
1"
MEDICAL AIR
INTAKE FROM AHU
SUPPLY DUCT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
ACC
B
IM
/2
V A
O m a h a a n d
G ra n d I s la n d /B
V A
O m a h a
M
E P
.r v t
/2
/2
:4
:1
P
M
ACC-PG402
MEDICAL GAS RISER DIAGRAM -
MEDICAL AIR
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT
4101 WOOLWORTH AVE, OMAHA, NE 68105
36C26323Q1052
01/28/2024
NO SCALE
ACC MEDICAL GAS RISER DIAGRAM - MEDICAL AIR
BASEMENT
FIRST FLOOR
SECOND FLOOR
PENTHOUSE
ZV-16
ZV-17
ZV-18
ZV-15
ZV-14
24072408240924012402
CARBON
DIOXIDE
MANIFOLD
3/4"
3/4"1/2"
TYP.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
ACC
B
IM
/2
V A
O m a h a a n d
G ra n d I s la n d /B
V A
O m a h a
M
E P
.r v t
/2
/2
:4
:1
P
M
ACC-PG403
MEDICAL GAS RISER DIAGRAM -
CARBON DIOXIDE
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT
4101 WOOLWORTH AVE, OMAHA, NE 68105
36C26323Q1052
01/28/2024
NO SCALE
ACC MEDICAL GAS RISER DIAGRAM - CARBON DIOXIDE
ZV-16
ZV-17
ZV-18
ZV-15
ZV-14
24072408240924012402
NITROUS
OXIDE
MANIFOLD
1/2"
1/2"
BASEMENT
FIRST FLOOR
SECOND FLOOR
PENTHOUSE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
ACC
B
IM
/2
V A
O m a h a a n d
G ra n d I s la n d /B
V A
O m a h a
M
E P
.r v t
/2
/2
:4
:1
P
M
ACC-PG404
MEDICAL GAS RISER DIAGRAM -
NITROUS OXIDE
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT
4101 WOOLWORTH AVE, OMAHA, NE 68105
36C26323Q1052
01/28/2024
NO SCALE
ACC MEDICAL GAS RISER DIAGRAM - NITROUS OXIDE
NITROGEN
MANIFOLD
ZV-16
ZV-17
ZV-18
ZV-15
ZV-14
24072408240924012402
1 1/4"
3/4"
BASEMENT
FIRST FLOOR
SECOND FLOOR
PENTHOUSE
3/4"
TYP
1 1/4"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project :
ACC
B
IM
/2
V A
O m a h a a n d
G ra n d I s la n d /B
V A
O m a h a
M
E P
.r v t
/2
/2
:4
:1
P
M
ACC-PG405
MEDICAL GAS RISER DIAGRAM -
NITROGEN
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT
4101 WOOLWORTH AVE, OMAHA, NE 68105
36C26323Q1052
01/28/2024
NO SCALE
ACC MEDICAL GAS RISER DIAGRAM - NITROGEN
| B01_23377_VA Omaha_MEP_21 - Sheet - ACC-P000 - SYMBOLS AND ABBREVIATIONS |
| B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG10B - BASEMENT LEVEL - OVERALL - MEDICAL GAS |
| B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG10BA - BASEMENT LEVEL - AREA A - MEDICAL GAS |
| B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG10BB - BASEMENT LEVEL - AREA B - MEDICAL GAS |
| B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG10BC - BASEMENT LEVEL - AREA C - MEDICAL GAS |
| B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG101 - FIRST LEVEL - OVERALL - MEDICAL GAS |
| B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG101A - FIRST LEVEL - AREA A - MEDICAL GAS |
| B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG101B - FIRST LEVEL - AREA B - MEDICAL GAS |
| B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG101C - FIRST LEVEL - AREA C - MEDICAL GAS |
| B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG102 - SECOND LEVEL - OVERALL - MEDICAL GAS |
| B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG102A - SECOND LEVEL - AREA A - MEDICAL GAS |
| B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG102B - SECOND LEVEL - AREA B - MEDICAL GAS |
| B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG102C - SECOND LEVEL - AREA C - MEDICAL GAS |
| B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG103 - THIRD LEVEL - OVERALL - MEDICAL GAS |
| B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG103B - PENTHOUSE LEVEL - AREA B - MEDICAL GAS |
| B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG400 - ACC MEDICAL GAS RISER DIAGRAM - OXYGEN |
| B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG401 - MEDICAL GAS RISER DIAGRAM - MEDICAL VACUUM |
| B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG402 - MEDICAL GAS RISER DIAGRAM - MEDICAL AIR |
| B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG403 - MEDICAL GAS RISER DIAGRAM - CARBON DIOXIDE |
| B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG404 - MEDICAL GAS RISER DIAGRAM - NITROUS OXIDE |
| B01_23377_VA Omaha_MEP_21 - Sheet - ACC-PG405 - MEDICAL GAS RISER DIAGRAM - NITROGEN |