This document is a combined synopsis/solicitation for a Request for Quote (RFQ) issued by the Department of Veterans Affairs (VA) Veterans Health Administration for Medical Gas Maintenance services in support of the VA Nebraska-Western Iowa Health Care System. The VA is seeking a Veteran-Owned Small Business (VOSB) contractor to provide these services under a firm fixed price Indefinite Delivery Indefinite Quantity (IDIQ) contract with a period of performance from 07-01-2024 to 06-30-2029. Quotes are due by 10:00am Central Standard Time on 06-06-2024 and should be emailed to the Contracting Officer. The NAICS code is 541350 with a $11.5 Million size standard. Additional details regarding the required services, site visits, and quote submission instructions are provided in the solicitation document.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MEDICAL GAS SYMBOLS
SYMBOL DESCRIPTION ADDITIONAL REMARKS
ALARM / CONTROL PANEL (MASTER OR
AREA)
ZONE VALVE BOX
# OF CIRCLES/PIPES INDICATES NUMBER OF
VALVES; ARROW INDICATES VALVE ACCESS SIDE
REFER TO MOUNTING HEIGHTS DETAIL FOR MOUNTING ELEVATION
REFER TO ABBREVIATIONS FOR TYPE
REFER TO MOUNTING HEIGHTS DETAIL FOR MOUNTING ELEVATION
EMERGENCY OXYGEN CONNECTION REFER TO MOUNTING HEIGHTS DETAIL FOR MOUNTING ELEVATION
ISOLATION VALVE
REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM.
LOCATE ABOVE CEILING AND PROVIDE WITH LOCKABLE HANDLE.
SENSING LOCATION XXXX
MEDICAL GAS OUTLET
REFER TO ABBREVIATIONS FOR GAS TYPE. PROVIDE BRACKET WITH EACH
VACUUM OUTLET. REFER TO MOUNTING HEIGHTS DETAILS FOR MOUNTING
ELEVATION. COORDINATE WITH ARCHITECTURAL DIVISION.
ABBREVIATION
LABORATORY AND MEDICAL GAS ABBREVIATIONS
DESCRIPTION
MEDICAL COMPRESSED AIRA
MEDICAL COMPRESSED AIR INTAKEAI
AREA ALARM PANELAAP
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS
COMPRESSED AIR (NON-MEDICAL)CA
MEDICAL CARBON DIOXIDEC
DENTAL AIRDA
DENTAL AIR INTAKEDAI
DENTAL VACUUMDV
DENTAL VACUUM EXHAUSTDVE
EMERGENCY OXYGEN CONNECTIONEOC
MEDICAL HELIUMHE
HORSEPOWERHP
INSTRUMENT AIRIA
INSTRUMENT AIR INTAKEIAI
LABORATORY AIR LA
LABORATORY AIR INTAKELAI
ABBREVIATION DESCRIPTION
LABORATORY VACUUMLV
LABORATORY VACUUM EXHAUSTLVE
MEDICAL AIR COMPRESSORMAC
MASTER ALARM PANELMAP
MEDICAL VACUUM PUMPMVP
MEDICAL NITROGENN
MEDICAL NITROUS OXIDENO
MEDICAL OXYGENO
PRESSURE REDUCING VALVEPRV
MEDICAL VACUUMV
MEDICAL VACUUM EXHAUSTVE
VALVE BOXVB
MEDICAL WASTE ANESTHESIA GAS DISPOSALWAG
WATER COLUMNWC
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:4
P
M
P000
PLUMBING SYMBOLS AND
ABBREVIATIONS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
SHEET INDEX
Sheet Number Sheet Name
P000 PLUMBING SYMBOLS AND ABBREVIATIONS
PG200 BUILDING 7 - BOILER PLANT MEDICAL GAS
PG20B BASEMENT LEVEL - OVERALL - MEDICAL GAS
PG20B.1 BASEMENT LEVEL - AREA 1 - MEDICAL GAS
PG20B.2 BASEMENT LEVEL - AREA 2 - MEDICAL GAS
PG20B.3 BASEMENT LEVEL - AREA 3 - MEDICAL GAS
PG20B.4 BASEMENT LEVEL - AREA 4 - MEDICAL GAS
PG20G GROUND LEVEL - OVERALL - MEDICAL GAS
PG20G.1 GROUND LEVEL - AREA 1 - MEDICAL GAS
PG20G.2 GROUND LEVEL - AREA 2 - MEDICAL GAS
PG20G.3 GROUND LEVEL - AREA 3 - MEDICAL GAS
PG20G.4 GROUND LEVEL - AREA 4 - MEDICAL GAS
PG201 FIRST LEVEL - OVERALL - MEDICAL GAS
PG201.1 FIRST LEVEL - AREA 1 - MEDICAL GAS
PG201.2 FIRST LEVEL - AREA 2 - MEDICAL GAS
PG201.3 FIRST LEVEL - AREA 3 - MEDICAL GAS
PG201.4 FIRST LEVEL - AREA 4 - MEDICAL GAS
PG202 SECOND LEVEL - OVERALL - MEDICAL GAS
PG202.1 SECOND LEVEL - AREA 1 - MEDICAL GAS
PG202.2 SECOND LEVEL - AREA 2 - MEDICAL GAS
PG202.3 SECOND LEVEL - AREA 3 - MEDICAL GAS
PG202.4 SECOND LEVEL - AREA 4 - MEDICAL GAS
PG203 THIRD LEVEL - OVERALL - MEDICAL GAS
PG203.1 THIRD LEVEL - AREA 1 - MEDICAL GAS
PG203.2 THIRD LEVEL - AREA 2 - MEDICAL GAS
PG203.3 THIRD LEVEL - AREA 3 - MEDICAL GAS
PG203.4 THIRD LEVEL - AREA 4 - MEDICAL GAS
PG204 FOURTH LEVEL - OVERALL - MEDICAL GAS
PG204.1 FOURTH LEVEL - AREA 1 - MEDICAL GAS
PG204.2 FOURTH LEVEL - AREA 2 - MEDICAL GAS
PG204.3 FOURTH LEVEL - AREA 3- MEDICAL GAS
PG204.4 FOURTH LEVEL - AREA 4 - MEDICAL GAS
PG205 FIFTH LEVEL - OVERALL - MEDICAL GAS
PG205.1 FIFTH LEVEL - AREA 1 - MEDICAL GAS
PG205.2 FIFTH LEVEL - AREA 2 - MEDICAL GAS
PG205.3 FIFTH LEVEL - AREA 3 - MEDICAL GAS
PG205.4 FIFTH LEVEL - AREA 4 - MEDICAL GAS
PG206 SIXTH LEVEL - OVERALL - MEDICAL GAS
PG206.1 SIXTH LEVEL - AREA 1 - MEDICAL GAS
PG206.2 SIXTH LEVEL - AREA 2 - MEDICAL GAS
PG206.3 SIXTH LEVEL - AREA 3 - MEDICAL GAS
PG206.4 SIXTH LEVEL - AREA 4 - MEDICAL GAS
PG400 MEDICAL GAS RISER DIAGRAM - OXYGEN
PG401 MEDICAL GAS RISER DIAGRAM - MEDICAL VACUUM
PG402 MEDICAL GAS RISER DIAGRAM - MEDICAL AIR
PG403 MEDICAL GAS RISER DIAGRAMS - DENTAL AIR & VACUUM
PG404 MEDICAL GAS RISER DIAGRAM - COMPRESSED AIR
Grand total: 47
Revisions: Date:
2'
A01
A02
A04 03
D 010
ELEVATOR SHAFT
MECH RM
STOR
STAIR
UP
E
LE
V . 1
2.
S
LO
P
E D
O W
N
'-1 0"
FOUNDATION DF
PAD & GUTTER ON
GROUND FLOOR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:4
P
M
PG20B
BASEMENT LEVEL - OVERALL -
MEDICAL GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
1/16" = 1'-0"
BASEMENT LEVEL - OVERALL - MEDICAL GAS
3/4" V UP
1/2" V UP
1/2" O UP
1/2" A 3/4" V 1/2" O
3/4" V UP
3/4" V UP
3/4" V UP
3/4" V UP
3/4" CA UP
1/2" CA UP1/2" CA UP
1 1/2" V
PIPING IN TUNNEL
TO BOILER PLANT
MEDICAL GAS DEFICIENCY LIST
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE NFPA 70 2023 517.32(C), 517.35
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7NFPA 99 2024
GENERAL NOTES:
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD
VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:4
P
M
PG20B.1
BASEMENT LEVEL - AREA 1 -
MEDICAL GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
BASEMENT LEVEL - AREA 1 - MEDICAL GAS
3/4" V UP
1/2" A
1/2" O 3/4" V
1/2" O
1/2" A 3/4" V
1/2" O 1/2" A 1" V
1" V UP
1/2" A UP
1/2" O UP
1/2" V UP
1/2" A 1/2" A
1" V
1/2" V
3/4" V
3/4" V UP
1/2" A UP
3/4" A UP
3/4" O UP
1/2" CA UP
3/4" CA
1/2" A1" V
1/2" CA
1/2" CA UP
1/2" CA UP
3/4" CA 3/4" CA
1/2" CA UP
1 1/2" V UP
1 1/2" V UP
1 1/2" A UP
MEDICAL GAS DEFICIENCY LIST
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE NFPA 70 2023 517.32(C), 517.35
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7NFPA 99 2024
GENERAL NOTES:
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD
VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:4
P
M
PG20B.2
BASEMENT LEVEL - AREA 2 -
MEDICAL GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
BASEMENT LEVEL - AREA 2 - MEDICAL GAS
2'
S
LO
P E
D O
W N
'-1
0"
1/2" O
3/4" A
1" V
1/2" A UP
3/4" A UP
3/4" O UP
1" O1" V
1 1/4" A
1 1/4" A
1" V
3/4" V UP
3/4" A UP
1" O UP
3/4" V UP
1" V UP
1" V
1/2" O UP
1" CA
3/4" CA
3/4" CA
3/8" CA
1/2" CA
1/2" CA
1" CA
1" O 3/4" A
ELEVATOR SHAFT
A02
1 1/2" V UP
1 1/2" V UP
1 1/2" A UP
MEDICAL GAS DEFICIENCY LIST
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE NFPA 70 2023 517.32(C), 517.35
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7NFPA 99 2024
GENERAL NOTES:
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD
VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:4
P
M
PG20B.3
BASEMENT LEVEL - AREA 3 -
MEDICAL GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
BASEMENT LEVEL - AREA 3 - MEDICAL GAS
UP
E
LE
V . 1
2.
S
LO
P
E D
O W
N
'-1 0"
FOUNDATION DF
PAD & GUTTER ON
GROUND FLOOR
3/4" V
1" V
1 1/2" A
1" V
2 1/2" VE UP
2 1/2" VE
1 1/2" A 2" V
2" AI
1 1/2" A
3/4" V UP
3/4" V UP
3/4" V UP
3/4" V UP
3/4" CA UP
1" CA
1" CA
1/2" CA UP
1/4" CA
1/4" CA UP
1/4" CA
3/8" CA
1/2" CA UP
1/2" CA
1/2" CA
1" CA
1/2" CA
1/2" CA UP
1/2" CA
1" CA
1/2" CA
STAIR
STORAGE
MECH RM
MEDICAL AIR COMPRESSOR
208V/3Ø
FED FROM P-4 CIRCUIT #2, 4, 6
MEDICAL VACUUM PUMP
208V/3Ø
FED FROM P-4 CIRCUIT #8, 10, 12
AIR COMPRESSOR
208V/3Ø
FED FROM P-4 CIRCUIT #13, 15, 17
AND #19, 21, 23
ABANDONED MEDICAL
VACUUM PUMP
2 4
APPLIES TO ALL PIPING
UPSTREAM OF THIS POINT
MVP-1
MAC-1
4" AI
4" AI UP
3" VE UP
3" VE
1 1/2" V
1 1/2" V
1 1/2" A
EQUIPMENT ACCESS PATH
#1 DOWN ELEVATOR
EQUIPMENT ACCESS PATH
#2 THROUGH COURTYARD
AND DOWN STAIRS
1 1/2" V
1 1/2" V
1 1/2" A
1 1/2" A
2" V
1 1/2" V
1 1/2" V
4" AI
MEDICAL GAS DEFICIENCY LIST
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE NFPA 70 2023 517.32(C), 517.35
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7NFPA 99 2024
GENERAL NOTES:
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD
VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:5
P
M
PG20B.4
BASEMENT LEVEL - AREA 4 -
MEDICAL GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
BASEMENT LEVEL - AREA 4 - MEDICAL GAS
S
S S
SS
S S
S
S S
S
S S
S S
S S S S S S S S S S S S S S S S S S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S S S
S S
S
S S
S S S S
S S S S
S S
S S S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
SS
S S S S
S S
S S S S
SS
S
S S
S S
S S
S S
S S
S S
S
S S S S
S S
S S
S S
S S
S S
S
S S S S
S S S S S S
S S S S
1-A-201
1-A-201 2
1-A-201
DN
UP
UP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:5
P
M
PG20G
GROUND LEVEL - OVERALL -
MEDICAL GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
1/16" = 1'-0"
GROUND LEVEL - OVERALL - MEDICAL GAS
S S S S S S S S S S S S S S S S S S S
S
S S
S S
S S
S S
S S
S S
S S
S S
S S S S
S S
S
S S
S S S S
S S S S
S S
S S S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S
S
UP
ASSUMED CAPPED
AT FLOOR
TO BULK
OXYGEN TANK
ASSUMED CAPPED
AT FLOOR
3/4" VAC DN
ASSUMED CAPPED
AT FLOOR
CRAWL SPACE
NO. 9
1 1/4" O UP
3/4" V DN
3/4" V DN
3/4" V UP
3/4" V DN
3/4" CA DN
1/2" CA UP
3/4" V UP/DN
1/2" CA UP/DN
STAIR=6
STORAGE
C17E
CHILLER RM
G03
MECH
C17B
MECH
C17B
SE1B
SE1
SE2
SPS LOCKER RM
MEDICAL GAS DEFICIENCY LIST
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE NFPA 70 2023 517.32(C), 517.35
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7NFPA 99 2024
GENERAL NOTES:
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD
VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:5
P
M
PG20G.1
GROUND LEVEL - AREA 1 - MEDICAL
GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
GROUND LEVEL - AREA 1 - MEDICAL GAS
S
S S
S S
S S S S S S S S S S S S S S S S S S S
S S
S S
S S S S
S S
S S S S
S S
ASSUMED CAPPED
AT FLOOR
FITNESS
CENTER
S6
MAIL ROOM
OFFICE
S8
3/4" V UP/DN
1/2" CA UP/DN
1/2" CA DN
1/2" CA UP/DN
1/2" V DN
3/4" V UP
1/2" O UP
1/2" A UP
1" V UP
1" V DN
1/2" A DN
1/2" O DN
1/2" CA UP/DN
3/4" V UP/DN
1/2" CA DN
3/4" A UP/DN
1/2" A UP/DN
3/4" O UP/DN
STAIR=6
SPS LOCKER RM
OFFICE OFFICE
S2
S3
STAIR - 4
POLICE OFFICE
S4
ARMORY
CORRIDOR
SOILED LINEN
S7
MAIL RM
S9
SPS DISPATCH
S1
S10
CRAWL SPACE NO. 8
DUMBWAITER - 3
1 1/2" V UP/DN
1 1/2" V UP/DN
1 1/2" A UP/DN
MEDICAL GAS DEFICIENCY LIST
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE NFPA 70 2023 517.32(C), 517.35
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7NFPA 99 2024
GENERAL NOTES:
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD
VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:5
P
M
PG20G.2
GROUND LEVEL - AREA 2 - MEDICAL
GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
GROUND LEVEL - AREA 2 - MEDICAL GAS
S
S S
SS
S S
S
S S
SS
S S
1-A-201
UP
ASSUMED CAPPED
AT FLOOR
3/4" VAC UP
IT OPERATORS
RM
N08
SOILED LINEN
CHUTE
N04
1/2" CA DN
3/4" A UP/DN
1/2" A UP/DN
3/4" O UP/DN
1/2" CA DN
3/4" V DN
3/4" V UP
3/4" A DN
1" O DN
3/4" V DN
3/4" V UP
1" V DN
3/4" A 1" O
1" V
1" O UP
3/4" O UP
1" V UP
3/4" A UP
3/4" A UP
3/4" V UP
3/4" V UP
1 1/2" DV
1 1/2" DV
1/2" O UP/DN
3/4" DA UP
1 1/2" DV UP
3/4" DA UP
1 1/2" DV UP
3/4" DV UP
1/2" DA UP
3/4" DA
3/4" DA 3/4" DA
STORAGE
N10
IT STORAGE
N11 IT OFFICE
N12
UNISEX TOILET
N13
STORAGE
OFFICE
N07
LOCKER
PATHOLOGY
N06 IT STORAGE
N5A
LOCKER RM
N05
CORRIDOR
MIKE SAFETY
M03
OFFICE
N02
WOMEN LOCKER
N14A
N14
SERVER RM
C01
ELEVATOR-1
ELEVATOR-2
ELEVATOR-3
MECH RM
STAIR=6
C5
S10
CRAWL SPACE NO. 6
CRAWL SPACE NO. 7
DUMBWAITER - 3
1 1/2" V UP/DN
1 1/2" V UP/DN
1 1/2" A UP/DN
MEDICAL GAS DEFICIENCY LIST
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE NFPA 70 2023 517.32(C), 517.35
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7NFPA 99 2024
GENERAL NOTES:
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD
VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:5
P
M
PG20G.3
GROUND LEVEL - AREA 3 - MEDICAL
GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
GROUND LEVEL - AREA 3 - MEDICAL GAS
S S S S
SS
S
S S
S S
S S
S S
S S
S S
S
S S S S
S S
S S
S S
S S
S S
S
S S S S
S S S S S S
S S S S
1-A-201 2
DN
UP
1/2" CA WITH HOSE
CONNECTION
1/2" CA WITH HOSE
CONNECTION
1/2" CA WITH HOSE
CONNECTION
TO BULK
OXYGEN TANK
ASSUMED CAPPED
IN WALL
EXISTING NON-MEDICAL
AIR COMPRESSOR
ASSUMED CAPPED
AT FLOOR
WOMENS
TOILET
SUPPLY
WAREHOUSE
C18
BIO MED
SHOP/OFFICE
C9
CANTEEN
STORAGE
C13
WAREHOUSE
STORAGE
C12A
WAREHOUSE
STORAGE
C12
WAREHOUSE
STORAGE
C11A
WAREHOUSE
STORAGE
C11
3/4" V UP/DN
3/4" V UP/DN
1 1/4" O UP
3/4" V DN
1/2" DA UP
3/4" DV UP
1/2" DA UP
3/4" DV UP
3/4" DA UP
1 1/2" DV UP
3/4" DA UP
1 1/2" DV UP
3/4" DV UP
1/2" DA UP
3/4" DV UP
1/2" DA UP
3/4" DV UP
1/2" DA UP
1" DV
3/4" DA
1" DV
3/4" DA 3/4" DA
1" DV
3/4" CA DN
3/4" CA UP
3/4" CA UP
1" CA
1" CA
1" CA DN
TO LAUNDRY
EQUIPMENT
1" CA
1/2" CA DN
1/2" CA UP
1/4" CA DN
3/4" V DN
1/2" CA DN
1/2" CA DN
1/2" CA UP
EQUIPM RM
NE3A
EQUIPM RM
NE3B
RESTROOM
MENS TOILET
LAUNDRY
1-NE3
NE2
OFFICE
NE1
LAUNDRY
1-NE3
STAIR=6
CANTEEN OFFICE
C6
STORAGE
C20
C5
MENS TOILET
C7
PROSTHETICS
C17A
ER SUPPLY
C16
C17
STORAGE
C15
STORAGE
C14
EMS STORAGE
C10
CANTEEN OFFICE
1-NE0
DENTAL VACUUM PUMP
208V/3Ø
FED FROM AC7A CIRCUITS #9,
11, 13 AND #10, 12, 14
DENTAL AIR COMPRESSOR
208V/3Ø
FED FROM AC7A CIRCUITS #
15, 17 AND #16, 18
AC7A
3" VE UP/DN
4" AI UP/DN
MEDICAL GAS DEFICIENCY LIST
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE NFPA 70 2023 517.32(C), 517.35
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7NFPA 99 2024
GENERAL NOTES:
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD
VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:5
P
M
PG20G.4
GROUND LEVEL - AREA 4 - MEDICAL
GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
GROUND LEVEL - AREA 4 - MEDICAL GAS
ELEVATOR
ELEVATOR
P1-1
S3-1
P2-1
EXIT TO OUTSIDE
EXIT TO OUTSIDE
EXIT TO OUTSIDE
EXIT TO OUTSIDE
EXIT TO OUTSIDE
EXIT TO OUTSIDE
S S
S
S S S
S S
SS
S S
S
S S
S
S S S S S
S S
S S
S S
S
TR
1-N118
LOBBY
1-001
CORR
1-C1COR.1
CORR
1-N1COR.1
OFFICE
1-N117
CASHIER
1-N116OFFICE
1-N115
VOLUNTEER
AREA
1-N121
1-A-201
1-A-201 2
1-A-201
UP
DN
UP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:5
P
M
PG201
FIRST LEVEL - OVERALL - MEDICAL
GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
1/16" = 1'-0"
FIRST LEVEL - OVERALL - MEDICAL GAS
1/2" O DN
1/2" CA DN
1/2" V DN
5/8" V 1/2" A 1/2" O
3/4" V DN
3/4" V UP
3/4" CA UP
3/4" V UP
1/2" CA DN
3/4" V DN
1/2" CA DN
1 1/4" O DN
1 1/4" O UP
STAIR - 6
IV DISPENSING
SE103
SE105
SE104
ACTIVE STORAGE
SE113
VACANT
SE108
CONFERENCE ROOM
SE106
SE109A
OFFICE
SE109
MD EXAM
SE126
EXAM RM
SE127
MD EXAM
SE143
MD EXAM
SE125
EXAM RM
SE124
EXAM RM
SE142
OFFICE
SE141
NURSE
SE128
NURSE
SE129
EXAM RM
SE121
REST RM
SE110
TOILET
SE111
CORRIDOR
SE122
EXAM RM
SE140
TOILET
SE139
ELECTRICAL
SE138
CLEAN UTILITY
SE130
CORRIDOR
SE123
MD EXAM
SE120
EXAM RM
SE119
MD EXAM
SE118
OUTPATIENT
SE114
OFFICE
SE137
OFFICE
SE136
EXAM RM
SE135
OFFICE
SE148
SE148A TOILET
SE147A
SOCIAL WORK
SE147
SE146
TELEMEDICINE
SE145
TELEHEALTH
SE144
CONFERENCE RM
SE155
SE154
TOILET
SE153A
SOCIAL WORKER
SE152
TOILET
SE152ASE151A
TRIAGE
SE151
HAC
SE150
CHEIF PHARMACY
SVC
SE107
SOILED
UTILITY
SE131
NUTRITION
CLINIC
SE134
MINOR
TREATMENT
SE153
AMBULANCE
ENTRANCE
SE156
O2-SE144-1
VAC-SE144-1
MA-SE144-1
ZV-SE145
MEDICAL GAS DEFICIENCY LIST
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE NFPA 70 2023 517.32(C), 517.35
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7NFPA 99 2024
GENERAL NOTES:
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD
VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:5
P
M
PG201.1
FIRST LEVEL - AREA 1 - MEDICAL
GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
NO SCALE
FIRST LEVEL - AREA 1 - MEDICAL GAS
EXIT TO OUTSIDE
EXIT TO OUTSIDE
S S
S
S S S S S
S S
S S
S S
S
UP
3/4" V DN
1/2" CA DN
3/4" V DN
1/2" O DN
1/2" A DN
1" V DN
1/2" CA DN
3/4" V DN
1/2" CA UP
1/2" A UP/DN
3/4" A UP/DN
3/4" O UP/DN
STAIR - 6
MALE TOILET
S111
WOMENS TOILET
S110
INPATIENT
SE102
SE101
MD EXAM
SE118
OUTPATIENT
SE114
PRESCRIPTIONS
SE115
CORRIDOR
SE100
VACANT
SE117
S108
ELIGIBILITY
SE133
CORRIDOR
SE156
SW119
TOILET
SW118
TOILET
SW117
STAIR - 5
TOILET
SW115A
EXAM RM
SW114
EXAM RM
SW113
SW110
EXAM RM
SW109
SW108
EXAM RM
SW107
EXAM RM
SW106
EXAM RM
SW105
NURSE STATION
SW103
TREATMENT
SW102B
RECEPTION
SW102A
OFFICE
SE148
SE148A TOILET
SE147A
TRIAGE
SE151
HAC
SE150
STAIR - 4
POLICE
ELEVATOR
WAITING
WAITING
ADVOCATE
OFFICE
S109
PATIENT
RECEIVING
SE119
NUTRITION
CLINIC
SE134
CLINICAL
PHARMACIST
SW116
PROVDER
STATION
SW104
AREA ALARM PANEL
120V/1Ø
FED FROM H-AC CIRCUIT #6
1 1/2" A UP/DN
1 1/2" V UP/DN
1 1/2" V UP/DN
MEDICAL GAS DEFICIENCY LIST
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE NFPA 70 2023 517.32(C), 517.35
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7NFPA 99 2024
GENERAL NOTES:
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD
VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:5
P
M
PG201.2
FIRST LEVEL - AREA 2 - MEDICAL
GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
NO SCALE
FIRST LEVEL - AREA 2 - MEDICAL GAS
S S
S
S S S
S S
SS
S S
S
S S
S S
S S
S
1-A-201
1/2" CA UP
1/2" A UP/DN
3/4" A UP/DN
3/4" O UP/DN
3/4" V 3/4" O
3/4" V
1" V 1" O
3/4" V 3/4" O
3/4" O
3/4" V
3/4" A 1" V
1" O3/4" V DN
3/4" V UP
1" O DN
3/4" O UP/DN
1" V DN
3/4" A UP/DN
3/4" A DN
3/4" V UP/DN
3/4" V DN
3/4" V UP
3/4" V UP/DN
1/2" O DN
1/2" O
1/2" O3/4" DV DN
1/2" DA DN
TREATMENT
NE101
RECEPTION
NE113
WAITING
N112 OFFICE
N114
OFFICE
N115
OFFICE
N116
CASHIER
N117 N118
STAIR - 3
PATIENT EDUCATION
N107
OFFICE
N106
MALE TOILET
N105
N104 OFFICE
N103
CANTEEN
N102
EXAM RM
NW116
EXAM RM
NW115
NURSE STATION
NW114
EXAM RM
NW102
EXAM RM
NW103
EXAM RM
NW104
EXAM RM
NW113
TOILET
NW111A CLEAN LINEN
NW112
EXAM RM
NW111
SOILED UTILITY
NW110
CLEAN UTILITY
NW109
TOILET
NW108A
EXAM RM
NW108
EXAM RM
NW106
EXAM RM
NW107
TOILET
NW107A
O2 STORAGE
NW105
STAIR - 1
CORRIDOR
NW1COR-001
NW118
STOR.
CORRIDOR
NW1COR-001
CANTEEN
LOBBY
IT CLOSET
ELEVATOR
P1-1
ELEVATOR
S3-1
ELEVATOR
P2-1
CLINIC
PHARMACIST
NW117
CLINIC
PHARMACIST
NW101
O2-NW106-1
VAC-NW106-1
O2-NW107-1
VAC-NW107-1O2-NW108-1
VAC-NW108-1
VAC-NW110-1
MA-NW110-1
AREA ALARM PANEL
120V/1Ø
FED FROM L11 CIRCUIT #5
L11
1 1/2" A UP/DN
1 1/2" V UP/DN
1 1/2" V UP/DN
ZV-NW114
ZV-NE113
MEDICAL GAS DEFICIENCY LIST
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE NFPA 70 2023 517.32(C), 517.35
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7NFPA 99 2024
GENERAL NOTES:
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD
VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:0
P
M
PG201.3
FIRST LEVEL - AREA 3 - MEDICAL
GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
NO SCALE
FIRST LEVEL - AREA 3 - MEDICAL GAS
S
1-A-201 2
DN
UP
1/2" O
1/2" DA DN
3/4" DV DN
1/2" DA DN
3/4" DV DN
1 1/2" DV DN
3/4" DA DN
3/4" DA DN
1 1/2" DV DN
1/2" O
(INACTIVE)1/2"
1/2" O
1/2" O
3/4" DV DN
1/2" DA DN
3/4" DV DN
1/2" DA DN
3/4" DV DN
1/2" DA DN
3/4" CA DN
3/4" CA DN1/2" CA 3/4" V DN
ASSUMED CAPPED
AT FLOOR
3/4" V DN
ASSUMED
CAPPED
AT FLOOR
OFFICE
NE107
OFFICE
NE106
SUPPLY
NE104
SOILED
NE105
TREATMENT
NE103
TREATMENT
NE102
TREATMENT
NE101
X-RAY
NE110
LAB
NE109
HAC
NE108
CORRIDOR
NE1COR-001
NE111
NE112
RECEPTION
NE113
IT CLOSET
C101
C116
C115
C101A
HAC
C109
WASH RM
C110
STORAGE
C111
FREEZER
C112
MALE TOILET
C107
STORAGE
C106
WOMENS TOILET
C104
FREEZER
C103
FREEZER
C113A
VEG RM
C101E
FOOD STORAGE
C115
FREEZER
C102A
FREEZER
C102
C108
ELEVATOR
C102B
CONFERENCE RM
C101D
OFFICE
C101E
HAC
TEL
STAIR - 6
LINEN
CLOSET
C105
O2-NE102-1
AREA ALARM PANEL
120V/1Ø
FED FROM L11 CIRCUIT #5
O2-NE103-1 O2-NE111-1
O2-NE112-1
1/2" CA UP/DN
1/2" CA DN
1/2" CA UP
3" VE UP/DN
4" AI UP/DN
ZV-NE113
MEDICAL GAS DEFICIENCY LIST
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE NFPA 70 2023 517.32(C), 517.35
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7NFPA 99 2024
GENERAL NOTES:
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD
VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:0
P
M
PG201.4
FIRST LEVEL - AREA 4 - MEDICAL
GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
NO SCALE
FIRST LEVEL - AREA 4 - MEDICAL GAS
S S
S S
S
S S S
S S
S S
S S
S S
S S
S S
S
S S S S S S S
S S
1-A-201
SS
S S
S
UP
DN
AUDIOLOGY
OFFICE
NW201
AUDIOLOGY
EXAM
NW202
WOMENS
RESTROOM
N214
MENS
RESTROOM
N215
VOL SVS
KITCHEN
C203B
SOILED
UTILITY
S210
EQUIPMENT
STORAGE
S211A
VASCULAR
PROCEDURE RM
SW212
MENS
TOILET
SE203
WOMENS
TOILET
SE206
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:0
P
M
PG202
SECOND LEVEL - OVERALL -
MEDICAL GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
1/16" = 1'-0"
SECOND LEVEL - OVERALL - MEDICAL GAS
3/4" CA
3/4" V
3/4" V DN
3/4" CA DN
3/4" V DN
3/4" V UP
1 1/4" O UP/DN
C207
STAIR
NO-6
LAB
SE201
OFFICE
SE207
OFFICE
SE208
WAITING
MENS
TOILET
SE203
WOMENS
TOILET
SE206
MECH
SE202A
ELECTRICAL
SE202
OFFICE
SE205D
SE205SE204
VAC-SE205-1
VAC-SE205-2
CA-SE205-1
CA-SE205-2
MEDICAL GAS DEFICIENCY LIST
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE NFPA 70 2023 517.32(C), 517.35
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7NFPA 99 2024
GENERAL NOTES:
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD
VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:0
P
M
PG202.1
SECOND LEVEL - AREA 1 - MEDICAL
GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
SECOND LEVEL - AREA 1 - MEDICAL GAS
S S S S S S
S
SS
S S
S
3/4" V UP
1/2" CA
1/2" A UP/DN
3/4" A UP/DN
3/4" O UP/DN
1/2" CA DN
OFFICE
S202
S201
STAIR
NO-6
O AND P LAB
C200
GAIT RM
S211B
OFFICE
S211
CORRIDOR
N2C0R-001
TREATMENT
S203
KITCHEN
S203A THERAPY
S204
LAB STORAGE
SE201A
STORAGE
S209
SOILED
UTILITY
S210
EQUIPMENT
STORAGE
S211A
WAITING
SW213A
CHECKING
SW213A
VASCULAR
PROCEDURE RM
SW212
X-RAY
SW211
X-RAY
SW204
WORK RM
SW205
STAIR
NO-2
BREAK RM
SW210
CONTROL RM
SW209
X-RAY
SW207
TOILET
SW206
SW208
SW203
MECH
SW202
LAB
SE201
HVAC
S205
TOILET
SW201A
ULTRASOUND
SW201
WAITING
S208
LAB STORAGE
S207
CONFERENCE RM
S206A
LOCKER
S206
STAIR
NO-4
OFFICE
SE208
ABANDONED AREA
ALARM PANEL
3/4"
1 1/2" V
1" A
1 1/2" V
1 1/2" A UP/DN
1 1/2" V UP/DN
1 1/2" V UP/DN
MEDICAL GAS DEFICIENCY LIST
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE NFPA 70 2023 517.32(C), 517.35
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7NFPA 99 2024
GENERAL NOTES:
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD
VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:0
P
M
PG202.2
SECOND LEVEL - AREA 2 - MEDICAL
GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
SECOND LEVEL - AREA 2 - MEDICAL GAS
S S
S S
S
S S S
S S
S S
S S
S S
S S
S S
S
S S S S
3/4" O 3/4" V
3/4" V DN
3/4" V DN
3/4" V DN
3/4" V DN
3/4" O DN
3/4" A DN
3/4" O 3/4" A
3/4" V DN
1/2" A 1/2" O
3/4" V 3/4" O
3/4" O 3/4" V
PROCEDURE
NE212
SOILED HOLD
NE201
STAIR
N213
STORAGE
N213
HAC
N209
EXAM
N210
EXAM
N211
EXAM
N207
EXAM
N206
EXAM
N205
EXAM
N204
STORAGE
NW211
EXAM
NW210
EXAM
NW209
EXAM
NW208
AUDIOLOGY
NW203
OFFICE
NW205
WAITING
NW205C
NW205A
TREATMENT RM
NW205B
TREATMENT RM
NW206
TREATMENT RM
NW207
TOILET
NW207A
STAIR
NO-1
BOOTH
AUDIOLOGY
N203
AUDIOLOGY
OFFICE
NW201
AUDIOLOGY
EXAM
NW202
WAITING RM
N202
RECEPTION
N201
OPEN BELOW
CORRIDOR
N202
S201
ELEVATOR
ELEVATOR
ELEVATOR
IT CLOSET
N201
O AND P LAB
C200AREA ALARM PANEL
120V/1Ø
FED FROM CAN CIRCUIT #19
AREA ALARM PANEL
120V/1Ø
FED FROM L32 CIRCUIT #14
1 2
O2-NW206-1
O2-NW206-2
MA-NW206-1
MA-NW206-2
O2-NW205B-1
MA-NW205B-1
O2-NW205A-1
MA-NW205A-1
O2-N212-1
VAC-N212-1
3/4"
1 1/2" V
1" A
1 1/2" V
3/4" V 3/4" O
ZV-NW205
ZV-NE212
MEDICAL GAS DEFICIENCY LIST
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE NFPA 70 2023 517.32(C), 517.35
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7NFPA 99 2024
GENERAL NOTES:
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD
VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:1
P
M
PG202.3
SECOND LEVEL - AREA 3 - MEDICAL
GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
SECOND LEVEL - AREA 3 - MEDICAL GAS
DN
1 1/4" O UP/DN
3/4" V 3/4" O
1/2" CA UP
EXAM
NE205
EXAM
NE204
TOILET
NE203
PROCEDURE
NE202
STORAGE
NE209
STAFF
NE210
EXAM
NE208
EXAM
NE207
LINEN
NE206
NE2COR
SUPPLY
NE211
TOILET
NE212A
PROCEDURE
NE212
SOILED HOLD
NE201
IT CLOSET
N201
CAPLAIN
C201
STORAGE
C202A
CHAPEL
C202
CAPLIN
C202B VOL SERVICES
C203AVOL SVS
KITCHEN
C203B
MECH
C220 RESTROOM
C221
CLEAN LINEN
C217
STORAGE
C222
PT RM
C214
OFFICE
C211
OFFICE
C212
OFFICE
C208
STORAGE
C213
C207
OFFICE
C210
OFFICE
C209
RECREATION HALL
C203
CORRIDOR
C2C0R-001
STAIR
NO-6
O2-N202-1
VAC-N202-1
1/2" CA UP
1/2" CA DN
3" VE UP/DN
4" AI UP/DN
3/4" V 3/4" O
3/4" V 3/4" O
ZV-NE212
MEDICAL GAS DEFICIENCY LIST
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE NFPA 70 2023 517.32(C), 517.35
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7NFPA 99 2024
GENERAL NOTES:
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD
VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:1
P
M
PG202.4
SECOND LEVEL - AREA 4 - MEDICAL
GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
SECOND LEVEL - AREA 4 - MEDICAL GAS
ELEVATOR
STAIR
STAIRSTAIR
STAIR
S3-3
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
TR
1-S302
CORR
1-S3COR.1
C O
R R
1- S
E 3C
O R
.1
1-A-201
DN
UP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:1
P
M
PG203
THIRD LEVEL - OVERALL - MEDICAL
GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
1/16" = 1'-0"
THIRD LEVEL - OVERALL - MEDICAL GAS
1/2" A 3/4" V 1/2" O
3/4" V 3/4" A 3/4" O
3/4" V DN
3/4" V DN
1 1/4" O UP/DN
1-BED
SE302
NURSE
SE310
2-BED
SE304
2-BED
SE305
2-BED
SE307
STORAGE
SE306
TOILET
SE304A
TOILET
SE305A
TOILET
SE307A
TOILET
SE308A
2-BED
SE308
CORRIDOR
SE3CORA
CORRIDOR
SE3COR
HANDWASH/
ALCOVE
SE303
LIFT
SE309
MED'S
SE310A
O2-SE305-1
O2-SE305-2
VAC-SE305-1
VAC-SE305-2
MA-SE305-1
MA-SE305-2
O2-SE307-1
O2-SE307-2
VAC-SE307-1
VAC-SE307-2
MA-SE307-1
MA-SE307-2
O2-SE304-1
O2-SE304-2
VAC-SE304-1
VAC-SE304-2
MA-SE304-1
MA-SE304-2
O2-SE308-1
VAC-SE308-1
MA-SE308-1
O2-SE302-1
VAC-SE302-1
MA-SE302-13/4" O
1" V 1/2" O
1/2" A 3/4" V
1/2" O 3/4" V 1/2" A
1/2" O 3/4" V 1/2" A
1/2" O 3/4" V 1/2" A
3/4" V 1/2" A 1/2" O
1/2" A 3/4" V 1/2" O
MEDICAL GAS DEFICIENCY LIST
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE NFPA 70 2023 517.32(C), 517.35
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7NFPA 99 2024
GENERAL NOTES:
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD
VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle, Omaha, NE 68134
MEDICAL GAS SYSTEM
INSPECTION AND ASSESSMENT100% SUBMITTAL
B
IM
/2
V A
O m a h a a n d
G ra n d
I s la n d
/B
V
A O m a h a a n d
G ra n d
I s la n d
M
E P
.r v t
/2
/2
:3
:2
P
M
PG203.1
THIRD LEVEL - AREA 1 - MEDICAL
GAS
2201 N BROADWELL AVE, GRAND ISLAND, NE 68803
36C26323Q1052
01/28/2024 RJH HLP
1/8" = 1'-0"
THIRD LEVEL - AREA 1 - MEDICAL GAS
STAIR
STAIR
S S
S S
S S
S S
S S
3/4" V DN
3/4" V 3/4" A 3/4" O
3/4" V 3/4" O
3/4" A1 1/4" V 3/4" A 3/4" O
1 1/4" V 3/4" A 3/4" O
3/4" O 3/4" A 3/4" V
3/4" V 3/4" A 3/4" O
1 1/4" V
3/4" 3/4" 3/4"
1 1/4" V
1/2" A 1/2" O
SPD
C301
TR
S302
1-BED ISOLATION
S303
TOILET
S303A
TOILET
S304A
1-BED
S304
TUB/SHOWER
S306
CORRIDOR
S3COR
HANDWASH
S315
ALCOVE
S305
TOILET
S316A
TOILET
S317A
2-BED
S317
2-BED
S316
SOILED
UTILITY
S314
OBSERVATION
SW313
O2
SW312
1-BED
SW311
LIFT
S313
NURSE
SW301
2-BED
SW302
TOILET
SW311A
TOILET
SW309A
2-BED
SW309
2-BED
SW303
TOILET
SW302A
TOILET
SW303A
ALCOVE
SW310
HANDWASH
SW308
2-BED
SW304
CORRIDOR
SW3COR
2-BED
SW307
TOILET
SW307A TOILET
SW306A
TOILET
SW304A TOILET
SW305A
2-BED
SW306
2-BED
SW305
CLEAN STORAGE
S308
HANDWASH
S307
ALCOVE
S309
STAFF TOILET
S311A
2-BED
S311
PATIENT
LOUNGE
S310
TOILET
SE302A
NOURISHMENT
SE301
NURSE
SE310
LIFT
S313
STAFF TOILET
S312
O2-S303-1
VAC-S303-1
MA-S303-1O2-S302-1
VAC-S302-1
MA-S302-1
O2-S304-1
VAC-S304-1
MA-S304-1
O2-S311-1 O2-S311-2
VAC-S311-1
VAC-S311-2
MA-S311-1
MA-S311-2
O2-S316-1 O2-S316-2
VAC-S316-1
VAC-S316-2
MA-S316-1
MA-S316-2
O2-S317-1 O2-S317-2
VAC-S317-1
VAC-S317-2
MA-S317-1
MA-S317-2
O2-SE302-1
VAC-SE302-1
MA-SE302-1
O2-SW302-1
O2-SW302-2
VAC-SW302-1
VAC-SW302-2
MA-SW302-1
MA-SW302-2
O2-SW303-1
O2-SW303-2
VAC-SW303-1
VAC-SW303-2
MA-SW303-1
MA-SW303-2
O2-SW304-1
O2-SW304-2
VAC-SW304-1
VAC-SW304-2
MA-SW304-1
MA-SW304-2
O2-SW305-1
O2-SW305-2
VAC-SW305-1
VAC-SW305-2
MA-SW305-1
MA-SW305-2O2-SW306-1
O2-SW306-2
VAC-SW306-1
VAC-SW306-2
MA-SW306-1
MA-SW306-2
O2-SW309-1
O2-SW309-2
VAC-SW309-1
VAC-SW309-2
MA-SW309-1
MA-SW309-2
O2-SW307-1
VAC-SW307-1
MA-SW307-1
O2-SW311-1
VAC-SW311-1
MA-SW311-1
3/4" O
1" V
3/4" V
1/2" O 1/2" A
1/2" A 3/4" V 1/2" O
1" O 1" A
1" O 1" A
1 1/2" V UP/DN
1 1/2" V DN
1 1/2" A DN
1" O
1 1/2" V 1" A
1" V
3/4" V
3/4" V 1/2" O
1/2" A
3/4" V 1/2" O 1/2" A
1/2" A
1/2" O 3/4" V
1/2" A
1/2" O 3/4" V
1/2" O 3/4" V 1/2" A
1/2" O 3/4" V 1/2" A
1/2" A 3/4" V 1/2" O
1/2" O 3/4" V 1/2" A
1/2" A 3/4" V 1/2" O
1/2" O 3/4" V 1/2" A
1/2" O 3/4" V 1/2" A
1/2" O 3/4" V 1/2" A
1/2" O 3/4" V 1/2" A
1/2" A
3/4" V
1/2" O
1/2" A 3/4" V 1/2" O
1/2" A
1/2" O 3/4" V
ZV-S302
MEDICAL GAS DEFICIENCY LIST
ITEM # DEFICIENCY CODE / GUIDELINE
REFERENCE
SECTION
1 EQUIPMENT NOT FED FROM APPROPRIATE EMERGENCY POWER SOURCE NFPA 70 2023 517.32(C), 517.35
2 EQUIPMENT ELECTRICAL SOURCE LABEL MISSING VA SPECIFICATIONS 26 0511
3 EQUIPMENT ALARM NOT FUNCTIONAL NFPA 99 2024 SEVERAL
4 COMPRESSOR SHALL BE LOCATED IN AREA NOT TO EXCEED 100°F AMBIENT TEMPERATURE VA PLUMBING DESIGN MANUAL 8.2.2.2
5 PIPING IS NOT COPPER WITH BRAZED COPPER-TO-COPPER JOINTS 5.1.10.4.1.7NFPA 99 2024
GENERAL NOTES:
1. MEDICAL GAS PIPING, EQUIPMENT, ELECTRICAL CONNECTIONS, AND ACCESSORIES SHOWN IS BASED ON FIELD
VERIFICATION PERFORMED BY HEALTHCARE COMPLIANCE TESTING AND DELTA ELECTRIC IN NOVEMBER 2023. ALL
MEDICAL GAS WORK PERFORMED AFTER THIS DATE IS NOT REFLECTED IN THESE PLANS.
2. MEDICAL GAS PIPING SHOWN WAS VERIFIED THROUGH NON-DESTRUCTIVE FIELD OBSERVATION. DESTRUCTIVE
MEASURES WERE NOT TAKEN TO VERIFY PIPING WITHIN WALLS, SHAFTS, AND CHASES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison…