This file is a Questions and Answers document with photos for RFQ 36C227Q0089 addressing a condensate pump replacement project. The document provides clarifications and visual references to support vendor responses to the Request for Quote issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22 for replacing a failed condensate pressure pump and its associated components. The Q&A format allows potential bidders to gain clarity on technical specifications, installation requirements, and other procurement details related to restoring efficiency to the steam and condensate systems. The accompanying photos serve as visual aids to help vendors understand the existing equipment configuration, failure conditions, or installation constraints relevant to the condensate pump replacement and component specifications required for this solicitation.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFQ 36C26227Q0089: Q&A and Photos
Do you have the pump information? Yes
Required pump flow rate (GPM) and total head (feet). <500 PPH capacity; not sure of the total head, the lift is approximately 3 feet with a 20-foot run.
Electrical power available, including voltage and single- or three-phase service, if applicable. None is required
Total boiler horsepower operating at any given time.
Total boiler horsepower; 15 BHP for the building.
Existing pump and receiver manufacturer/model information, nameplate photographs, and receiver capacity. Spirax Sarco 66160 pressure power pump, cast iron.
Pipe connection sizes and required inlet and reduced outlet steam pressures for the pressure-reducing station. Condensate inlet and outlet 1.5” x 1” nipple. Steam inlet ½” x 1” nipple. Vent N/A. There is no PRV one needs to be installed to reduce steam to approx. 20 psi.
Photos of existing equipment: material requirements are forged steel or cast steel.
Photo 1: Name plate data
Photo 2: Condensate Inlet
Photo 3: Front View
Photo 4: Run from Pump
Photo 5: Steam in and Condensate out
Photo 6: Condensate leaving building
Photo 7: Condensate leaving pump showing check valve and union
Photo 8: Condensate leaving pump image4.jpeg image5.jpeg image6.jpeg image7.jpeg image8.jpeg image1.jpeg image2.jpeg image3.jpeg