This is Amendment Four to Solicitation 36C26226Q0508, issued by the Department of Veterans Affairs, Veterans Health Administration, Veterans Integrated Service Network 22 (Mesa Annex), responding to additional vendor questions regarding the rental of a temporary steam boiler. The amendment extends the offer submission deadline to April 16, 2026, at 1:00 PM MST, with offers to be submitted via email to Felicia Simpson, Contract Specialist. All offerors must submit complete documentation per Section E and acknowledge receipt of all amendments; failure to do so will result in rejection without evaluation.

The Questions and Answers address key technical and operational specifications: the boiler must be a minimum of 700 HP but can be larger (up to 1,160 BHP is acceptable) provided it meets footprint requirements and all operational, safety, and regulatory standards; the mobile office must meet ADA requirements with 30-amp, 2-phase electrical power supplied by VA to a point 10 feet from the equipment; substitutes for the Cleaver Brooks manufacturer are acceptable; the boiler must comply with San Diego Air Pollution Control District (APCD) emissions standards; engineering drawings and layout details will be provided by the architect-engineer upon award; and the contract start date is flexible as long as the boiler is procured, on-site, and ready for connection by Notice to Proceed. Vendors must obtain and maintain all necessary APCD and local jurisdiction permits, with monthly invoicing through the Tungsten Network electronic system.

View the file

Other files

File Type Posted
36C26226Q0508 0003.docx DOCX document
36C26226Q0508 0002.docx DOCX document
36C26226Q0508 0001.docx DOCX document
FMS Vendor File Update Request Form.pdf PDF
W9 Request for Taxpayer Identification Number and Certification.pdf PDF
VA10091 Vendor Request Form.pdf PDF
36C26226Q0508_2.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

5. PROJECT NUMBER (if applicable)

CODE

7. ADMINISTERED BY

2. AMENDMENT/MODIFICATION NUMBER

CODE

6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR

4. REQUISITION/PURCHASE REQ. NUMBER

3. EFFECTIVE DATE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED

PAGE OF PAGES

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED

BPA NO.

1. CONTRACT ID CODE

FACILITY CODE

CODE

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

E. IMPORTANT:

is extended,

(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.

12. ACCOUNTING AND APPROPRIATION DATA

(REV. 11/2016)

is required to sign this document and return ___________ copies to the issuing office.

is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.

15C. DATE SIGNED

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER

Contractor

16C. DATE SIGNED

14. DESCRIPTION OF AMENDMENT/MODIFICATION

16B. UNITED STATES OF AMERICA

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER

16A. NAME AND TITLE OF CONTRACTING OFFICER

15B. CONTRACTOR/OFFEROR

STANDARD FORM 30

PREVIOUS EDITION NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)

(If required)

(SEE ITEM 11)

(SEE ITEM 13)

(X)

CHECK

ONE

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

(Signature of person authorized to sign) (Signature of Contracting Officer) 4/14/2026 664-26-2-5033-0019 None 36C262

NCO 22

Department of Veterans Affairs NCO 22 - Mesa Annex 4135 S. Power Rd #103 RM 116 Mesa AZ 85212 36C262

NCO 22

Department of Veterans Affairs NCO 22 - Mesa Annex 4135 S. Power Rd #103 RM 116 Mesa AZ 85212 To all Offerors/Bidders

TBD

36C26226Q0508 03-26-2026

X X X X The purpose for this amendment is to respond to additional questions received from vendors.

All offers are due NLT April 16, 2026, at 1:00 PM MST. Offerors shall be submitted via email to: Felicia Simpson, Contract Specialist at Felicia.Simpson@va.gov.

ALL OFFERS SHALL SUBMIT ALL DOCUMENTATION UNDER SECTION E and all AMENDMENTS, failure to provide any required document and acknowledgment of all amendments will result in the offer not being accepted and will not be evaluated.

CONTINUATION PAGE

Questions and Answers 36C26226Q0508 Rental Boiler and 36C26226Q0515 Boiler Service

1. Does the mobile office require a 42” door?

ANSWER: Must meet ADA Requirements.

2. Is the mobile office going to get electrical power from the existing plant?

ANSWER: Yes, will provide 30amp 2 phase

3.Who is responsible for the electrical connections for the mobile office and temporary boiler?

ANSWER: Electrical Connections must be 10ft from the mobile office and temporary boiler to the point of feed connection from the Central Utility Plant. Separate Construction Site Prep. will provide 30amp single 2 phase to the mobile office and depending on the selected vendor’s submittal on their Boiler VA will review and approval via submittal approval process.

4. Cleaver Brooks is listed as the manufacturer. Are substitutes acceptable?

ANSWER: Yes, the current construction site preparation piping was intended for Cleaver Brooks. (Refer to the Services Contract SOW, pg. 38 of 80).

5. The scope of work calls out 800HP, but on section A (6) it calls 31,050 lbs/hr which is a 900 HP Steam boiler equivalent. Please confirm size.

ANSWER: At minimum a 700 HP Boiler is required.

6. Please confirm distance from rental location to piping connections for all services to central plant.

ANSWER: The Central Utility Plant connection point is located 10 ft from the rental boiler connection point.

7. It was mentioned that the boiler needed to meet VHA directive 1810 which includes extensive semi-annual calibrations per the VHA Boiler and Associated Plant Safety Device Testing manual which are not specifically called out in the scope. Please confirm this is required.

ANSWER: As per VA HEFP the temporary boiler must comply with state regulations for Steam Boilers. (Or further directions are delegated by VA HEFP).

8. Will a larger boiler with a similar footprint and weight be acceptable?

ANSWER: Yes

9. Is the start date flexible?

ANSWER: Yes, but Rental Boiler must be procured, onsite, and ready for connection at NTP by VA Contracting.

10. The boilers currently installed at the SDVA are 700HP boilers. Will the VA accept a 700HP boiler instead of a 800HP? If a smaller boiler is not acceptable will a 1000HP boiler be acceptable?

ANSWER: Please refer to question No. 5 above. A 1000HP Boiler will be acceptable if it meets the VA’s requested footprint.

11. One of our suppliers has indicated that an ~800 HP unit is not currently available; however, they do have a 40,000 PPH water tube boiler (approximately 1,160 BHP) available for the required period. In this regard, we respectfully request confirmation on whether a boiler of approximately 1,160 BHP be considered acceptable, provided it meets all operational, safety, and regulatory requirements?

ANSWER: Yes, boiler of approximately 1,160 BHP be considered acceptable, provided it meets all operational, safety, and regulatory requirements (All applicable requirements including designated footprint of an 800 HP fire tube boiler)

12. Can we receive the drawings from the engineers regarding the layout and piping?

ANSWER:VA will provide drawings from the AE DOR upon award to the selected Vendor.

13. What is the required NOx emission limit for this project in the San Diego area?

ANSWER: NOx emission limit for this project must comply with San Diego APCD.

14. Must the boiler comply with local AQMD or other regulatory thresholds (e.g., sub-9 PPM NOx)?

ANSWER: Boiler must comply with San Diego APCD.

15. Would the Government consider a boiler system utilizing an SCR (Selective Catalytic Reduction) unit to achieve compliant NOx levels?

ANSWER: Boiler must comply with San Diego APCD.

16. Are there any specific permitting or emissions compliance requirements that must be met prior to installation and operation?

ANSWER: Boiler must comply with San Diego APCD.

AMENDMENT FOUR RESPONDING TO QUESTIONS