SPS Ventilation Report Womens Clinic- Example report.pdf

PDF 410 KB Posted

Attached to
Ventilation Monitoring and Mainenance Women's Clinic Loma Linda
Solicitation number
36C26225Q0128
Issued by

About this file

This is a ventilation report template for monitoring air changes per hour (ACH) and pressure differential measurements in sterile storage areas of the Women's Clinic. The report includes columns for room location, room number, volume, CFM (cubic feet per minute), required and actual air changes per hour, and required and actual pressure differential measurements.

The example shows data from a Cardiology room (4E-55) with volume of 2217, CFM of 310, required ACH of 4 and actual ACH of 8, and pressure differential requirements of POS (0.01) with actual reading of POS (0.004). The Women's GYN section lists rooms RM012, RM013, RM031, and RM032, each requiring 4 air changes per hour and POS (0.01) pressure differential, with data fields remaining to be populated for volume, CFM, and actual pressure readings. The template indicates that volume and CFM measurements must be entered to automatically calculate the actual ACH, while actual pressure differential readings need to be manually entered.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Location room # volume CFM Required Actual Required Actual

Cardiology 4E-55 2217 310 4 8 POS (0.01) POS (0.004)

Women's GYN RM012 4 #DIV/0! POS (0.01)

RM013 4 #DIV/0! POS (0.01)

RM031 4 #DIV/0! POS (0.01)

RM032 4 #DIV/0! POS (0.01)

Data required to be entered is the Actual Pressure diferential Women's Clinic

Data required to be entered is the Volume and CFM - that automatically generates the Actual ACH

2025 SPS Ventilation Report Women's Clinic (Sterile Storage) Air Changes/Hour (ACH) Pressure Differential

Example From MAIN Building: