This document contains questions and answers regarding a solicitation for a generator return fuel pump repair. The solicitation is for a new return fuel pump installation on a Kohler 350REOZV generator located at the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22. The generator does not currently have a return fuel pump. The required flow for the new pump is 25 gpm at atmospheric pressure, using #2 diesel fuel. Electrical requirements are 120/208V 3-phase 4-wire at 60 amps. An existing underground storage tank will be removed and replaced with a new 1,500 gallon aboveground tank adjacent to the generator. Responses for the solicitation are due by March 29, 2024.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFQ 36C26224Q0668 GENERATOR RETURN FUEL PUMP
Q1. what kind of generator information you would be able to provide so I can quote you a return fuel pump. Is this an additional pump or is this replacing a current pump already installed on the generator?
A1. Generator is Kohler 350REOZV. Generator does not have a return fuel pump, new install.
Q2. To facilitate our precise offer, we seek clarification on the following details:
· Flow Required (GPM)
· Discharge Pressure (PSI)
· Type of Fuel
· Drive Options/AC Requirements A2.
· 25 gpm
· This would be an open-ended return fuel line, not be pressurized.
· #2 Diesel
· 120/208V, 3 Phase, 4 wire, 60 amp
Q3. B107 courtyard generator (need to confirm which tank and for which generator)?
A3. Will be removing UST and replacing with new 1500-gallon Hoover Vault AST, to be installed in courtyard, adjacent to Kohler 350REOZV generator.
Q4. The SOW appears to be a new install with an addition pump that is not there now. Please confirm if it’s a new install or a replacement?
A4. Generator does not have return fuel pump, new install.
Q5. If it’s a replacement, then we need the current pump part number for cross referencing.
A5. N/A. Generator does not have return fuel pump, new install.
Q6. Is there a cost estimate, budget or ballpark figure for the project listed? Is there an actual start date for the project?
A6. Please provide the Federal Government you best estimate for this requirement. There is an anticipated date to have this awarded and started by March 29, 2024.