36C26120Q0099-0001029.xlsx
XLSX spreadsheet Posted
- Attached to
- Building Safety Inspection Services for the San Francisco Veterans Affairs Health Care System (SFVAHCS).
- Solicitation number
- 36C26120Q0099
About this file
36C26120Q0099 0001 Example Format for documenting discrepancies (Question and Answer attachment).xlsx
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26120Q0099-0002000.docx | DOCX document | |
| 36C26120Q0099-0001028.pdf | ||
| 36C26120Q0099-0001027.docx | DOCX document | |
| 36C26120Q0099-0001026.pdf | ||
| 36C26120Q0099-0001025.docx | DOCX document | |
| 36C26120Q0099-005.docx | DOCX document | |
| 36C26120Q0099-003.docx | DOCX document | |
| 36C26120Q0099-006.xls | XLS spreadsheet | |
| 36C26120Q0099-004.pdf | ||
| 36C26120Q0099-007.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Findings
| No. | Fl | Room/Location | Reference | Finding | Recommended Action(s) |
| 1 | 1 | Dorm Bldg - 2 Gas Furnace Rms | NFPA 101 (12) 32.3.3.2.2 32.3.3.6.6 | Though smoke detectors have been installed in these two rooms, the walls and doors surrounding these two hazardous areas not fire resistance/protected rated and their doors are equipped with louvers | Separate both rooms from adjacent areas by 1 hr fire resistance rated construction and replace the existing doors with 45-minute rated self-closing and latching doors without louvers (Note: it is recognized that at this juncture, it may be impractical to construct 1 hr rated construction around the two rooms and seal the louvers especially if there is no economical way to vent the two rooms, but this was an NFPA/VA requirement when the facility was constructed and the VA needs to decide if and how to address this issue) |
| 2 | 1 | Kitchen | NFPA 96 (11) 11.2.4, 11.3.2 & 11.4; NFPA 17 (09) 7.3.3 | Wet chemical fire extinguishing system protecting the kitchen cooking surfaces has not be serviced in over a year | Have the wet chemical fire extinguishing system serviced semi-annually by a certified or licensed contractor per the manufacturer's instructions; semi-annual service needs to include inspecting grease build-up and replacing fusible links |
Facility Name/Address/POC - Ukiah Recovery Ctr, 201 Brush St, Ukiah, CA (Clover Martin) Date - 7/2/19
Sprinklers - QRS in Dorm and Admin Bldgs. FA -Firelite w-24 VDC SD Area - 8,122 sq ft Beds (Tot/VA) - 40/4 Occ - LRBC