Q: Are the buildings fully sprinkler protected? If not, approximately what percentage, are / are not sprinkler protected?

A: For the most part, we are sprinklered. I would say approximately 90%. The Boiler Plant is not sprinklered. There are also some modulars that are not sprinklered; however, they are scheduled for demolition.

Q: What are the Life Safety Code occupancies of the buildings included (business, ambulatory, healthcare, mixed?)

A: The occupancies are mixed. We have business, healthcare, suites, and ambulatory