36C26118B0040 C28 151211 593-15-103 Envrironmental Controls Construction Narrative.pdf

View the file

Other files

File Type Posted
36C26118C0029-000.docx DOCX document
36C26118B0040-00002000.docx DOCX document
36C26118B0040-00002001.pdf PDF
36C26118B0040-00001000.docx DOCX document
36C26118B0040-00001002.pdf PDF
36C26118B0040-00001001.pdf PDF
36C26118B0040-007.doc DOC document
36C26118B0040-010.docx DOCX document
36C26118B0040-001.docx DOCX document
36C26118B0040-002.pdf PDF
36C26118B0040-004.pdf PDF
36C26118B0040-008.pdf PDF
36C26118B0040-009.pdf PDF
36C26118B0040-006.pdf PDF
36C26118B0040-003.pdf PDF
36C26118B0040-000.docx DOCX document
Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DESIGN ENVIRONMENTAL CONTROLS AND MONITORING DEVICES

October 14, 100%

CONSTRUCTION DOCUMENTS

December 11, PROJECT NO. 593-15-103

Design Environmental Controls And Monitoring Devices December 16, 2015

TABLE OF CONTENTS

A. DESCRIPTION OF EXISTING SYSTEMS AND NEW SCOPE 3

B. ELECTRICAL 4

C. CODES AND STANDARDS 4

D. SYSTEM CONTROL HARDWARE CUT SHEETS 5-11

E. SPECIFICATION TABLE OF CONTENTS 12-20

5-14

11, December 16, 2015

VA Hospital Las Vegas- Environmental Control and Monitoring

A DESCRIPTION OF EXISTING SYSTEMS AND NEW SCOPE

Work shall include as the following:

1. Monitoring temperature, relative humidity, pressure, air flow (supply and exhaust air) for the operating rooms as indicted on the drawings.

2. Monitoring temperature, pressure, air flow (supply, return or exhaust air) for or other critical rooms as indicted on the drawings.

3. Controlling temperature, relative humidity for the operating rooms as indicted on the drawings.

4. Controlling temperature for all other critical rooms as indicted on the drawings.

5. Controlling and monitoring of sensitive rooms from nurse’s stations. And other rooms as indicated on the drawings.

Monitoring and control will be done locally by the following monitors:

1. Wall recessed mounted touch screen panels with 5.7” screen (LVIS-ME2000 Touch panel or equal) at the door of Isolation Rooms, rooms in radiology department and Pharmacy Department and other areas as indicated on the drawings will control and monitor.

a. Fifteen 15) locations on the first floor.

b. Two (2) on the second floor.

c. Six (6) on the third floor

d. Four (4) for four Airborne Infectious Isolation Rooms on the fifth floor.

e. Eight (8) for eight Airborne Infectious Isolation Rooms on the fifth floor.

2. Surface mounted touch screen with 27” screen (Asus Model ET2702IGTH or equal) for controlling and monitoring:

a. One (1) in OOTC LARGE Training Office on the second floor.

b. One (1) in Cath Lab on the third floor.

c. Eight (8) Operating Rooms (Operating Room No 1 through room No 8) located on the third floor.

In addition to local monitoring and controlling the monitoring and control will be from the following monitors and locations:

1. Surface wall mounted or Reach arm mounted Surface Pro Monitor (by Microsoft or equal) with 12” screen:

a. One (1) wall mounted in Phys Office 1D223 on the first floor.

b. One (1) Reach arm mounted in the Nurses Station 1A153 on the first floor.

c. One (1) wall mounted in Support Staff Workstation on the second floor.

d. One (1) mounted in the OOTC LARGE Training Office on the second floor.

e. One (1) Reach arm mounted in the Nurses Station 3D119 on the third floor.

f. One (1) Reach arm mounted in the Nurses Station 3D229 on the third floor.

g. One (1) Reach arm mounted in the Nurses Station 3D354 on the third floor.

h. One (1) Reach arm mounted in the Nurses Station 3D369 on the third floor.

i. One (1) Reach arm mounted in the Nurses Station 5D364 on the fifth floor.

j. One (1) Reach arm mounted in the Nurses Station 5D417 on the fifth floor.

k. One (1) Reach arm mounted in the Ward Clerk 6D146 on the sixth floor.

December 16, 2015

l. One (1) Reach arm mounted in the Comm Station Nurse C 6D229 on the sixth floor.

m. One (1) Reach arm mounted in the Ward Clerk 6D360 on the sixth floor.

n. One (1) Reach arm mounted in the Comm Station Nurse D 6D437 on the sixth floor.

In addition to above monitoring the Building Automation System located in the central plant will monitor and control all the critical rooms through interface with the existing Johnson Control System.

B. ELECTRICAL

1. 120 volt AC Electrical power will be provided from existing electrical panels located in each floor through junction boxes in each floor for touch screens and DDC control panels. Transformers at each junction box will provide 24 volt power to touch screen required.

C. CODES AND STANDARDS

1. 2012 International Building Code (IBC).

2. 2012 International Mechanical Code (IMC).

3. 2012 International Plumbing Code (IPC).

4. 2012 International Electrical Code (IEC).

5. Rules and Regulations of the State Fire Marshal.

6. American Gas Association (AGA).

7. American Society of Heating, Refrigeration and Air Conditioning Engineers

(ASHRAE).

- ASHRAE Standard 62.1-2007

- ASHRAE Standard 90.1, 2007 and 2010

- ASHRAE Equipment

8. DVA Facilities Management HVAC Design Manual, PG-10, 2013

9. DVA Physical Security Design Manual for Mission Critical and Life Safety

Protection Facilities.

10. DVA Seismic Design Requirement, H18-8, February 2013

11. National Fire Protection Association (NFPA), including the California Edition of the National Electric Code (NEC).

12. Sheet Metal and Air Conditioning Contractors National Association (SMACNA).

13. DOE

ASUS All-in-one Touch Screen PC 27” – ASUS Model ET2702IGTH

Operating System Windows 8 Pro Windows 8

Display 27.0"(68.47cm), 16:9, Wide Screen, WQHD 2560x1440, LED-backlight, IPS, 178° wide viewing angle

Touch Screen Multi-touch (10 Fingers Touch)

Processor Intel® Core™ i7 4770 Processor Intel® Core™ i5 4430 Processor

Chipset Intel® B85

Graphic

AMD® Radeon HD8890A 2GB

Memory 4 GB Up to 32 GB DDR3 at 1600MHz 4 x SO-DIMM

Storage 1TB Up to 3TB SATA Hard Drive ASUS Hyper Storage:

1TB HDD+128GB SSD

Optical Drive Tray-in Supermulti DVD RW Blu-Ray Disc Combo Blu-ray Writer

Wireless Data Network

802.11 b/g/n/ac Bluetooth V4.0

LAN

10/100/1000 Mbps

Camera 2 M Pixel

Audio SonicMaster Premium

Speaker 4 x 3 W

Built-in Mic

Yes Side I/O Ports

4 x USB 3.0 1 x 3 -in-1 Card Reader 1 x Headphone 1 x Microphone 1 x Line out

Back I/O Ports 2 x USB 2.0 1 x HDMI-In 1 x HDMI-Out 1 x RJ45 LAN 1 x TV Jack (Optional) 1 x Kensington Lock 2 x Thunderbolt port (Optional) 1 x Subwoofer jack (2.5mm) 1 x Power input

Card Reader

3-in-1: SD/SDHC/MMC Power Supply

180 W Power adaptor Dimensions

660 x 508 x 233 mm (WxHxD) Weight

13.5 kg Color

Black Accessories

Keyboard+Mouse (Optional), AC Adaptor Power Cord Warranty Card ASUS Certified Wall Mount Adapter (sold separately) ASUS Certified Wall Mount Screws Device Share cable (Optional) Remote Control (Optional) Quick Start Guide

Software Anti-Virus Trial Adobe Acrobat Reader Arcsoft *1 ASUS Launcher ASUS WebStorage

Ai Charger ll Freshpaint Fingertapps Instrument MaxxAudio Office trial

SKYPE

Note *1: bundled with optional TV Tuner www.loytec.com106

Ac ce ss or ie s

In te rf ac es Ro ut er s, N

IC

L-

D A

LI

L-

VI

S, L -S

TA

T

G at ew ay s L-

IO

B

L-

IN

X L-

RO

C

L- W

EB

Fu nc tio ns L‑

VI

S, L ‑S

TA

T

LVIS‑ME200

L‑VIS Touch Panel

L-VIS Touch Panels for BACnet networks are ideally suited for visualization and operation of various applications in building automation. L-VIS Touch Panels visu-alize building systems, can be used as room operator panels, in hospital operation or isolation rooms, conference and reception areas. The fully customizable user screens can show dynamic pages that are easy to navigate. L-VIS Touch Panels make use of an extremely low power embedded controller platform utilizing an embedded operating system. This makes L-VIS resistant against problems when re-booting after power outage and also against any viruses.

L-VIS impresses with its timeless design, harmonic integration into modern and historical architecture, and with its extremely user friendly concept. The shallow installation depth and low thermal power loss allow mounting in almost any location.

Dynamic Graphical Pages

The graphical pages may consist of multiple dynamic graphical controls that show the current plant status in real time. It is also possible to access decentralized schedules, alarm servers, or trends. The graphical projects are designed with the L-VIS/ L-WEB configuration tool free of charge. Without any know-how in HTML or Java, user specific graphical pages can be created. Dynamic information is shown through value or text controls, changing symbols, bar charts, trend views, alarm and event lists, or schedule controls. The L-VIS/ L-WEB configuration tool allows for using most of the pixel graphic formats (GIF, JPG, BMP, TIFF, PNG, MNG, ICO), vector graphics (SVG) and alpha blending.

Automatic Page Generation

Pages including data point names and values, alarm views, schedules, or trends can be created automatically by the L-VIS/ L-WEB configuration tool. This signifi-cantly reduces engineering time and cost.

Connectivity and Data Points

The L-VIS Touch Panels support connectivity to BACnet/ IP and BACnet MS/ TP and implement the BACnet Building Controller (B-BC) profile. They include a fully fea-tured built-in BACnet/ IP to MS/ TP router with BBMD and slave proxy functional-ity. In addition, the L-VIS Touch Panels provide connectivity to Modbus TCP via Ethernet/ IP and to Modbus RTU via RS-485.

Math objects can calculate any kind of formula using data points available on the device. The resulting data point value can then be either shown on the page or provided via a BACnet object. All BACnet server objects are automatically mapped to OPC XML-DA data points that can be accessed via web services.

The L-VIS devices provide fully featured AST™ functionality (Alarming, Scheduling, and Trending) and can be integrated perfectly into the L-WEB Building Management System.

BACnet Modbus CEA-709 M-Bus

KNX OPC

OPC

XML-DABACnet serial

15 16 174 5 6

+- DC

AC

statuspower

12-35 VDC INPUT or 12-24 VAC, 40-70 Hz

ACT

LINK

ACT

100Base-T100Base-T

Made in Austria

LOYTEC

www.loytec.com

1 2 3

RS-485RS-485

AB

FT

RNI

PLC CNIP

LINX-110

Automation ServerL-INX

VNC

y=f(x)

BACnet

Modbus

Datasheet #89017317 buildings under controlwww.loytec.com 107

Functions L-W

EB

L-RO

C

L-IN

X

L-IO

B G atew ays

L-VIS, L-STAT

L-D

A

LI

Routers, N

IC

Interfaces Accessories

L‑VIS, L‑STAT

BACnet Modbus CEA-709 M-Bus

KNX OPC LVIS‑ME200

• High resolution TFT touch display with dimmable backlight

• Anodized aluminum front frame

• Flush-mounting in combination with the mounting frame

• Stores customized graphical pages

• Visualization of customized graphical pages through built-in Touch Panel, LWEB-900 (building management) and LWEB-802/ 803

• Device configuration and graphical page creation with the L-VIS/L-WEB configuration tool free of charge

• Supports all popular graphic file formats such as GIF, JPG, BMP, TIFF, PNG, MNG, ICO

• Support of SVG vector graphics

• Supports alpha blending

• Supports popular font types such as TrueType, Type-1, BDF, PCF, and OTF

• Supports Unicode text

• Built-in OPC XML-DA server

• Built-in OPC XML-DA client

• Alarming, Scheduling, and Trending (AST™)

• Event-driven e-mail notification

• Math objects to execute mathematical operations on data points

• Compliant with ANSI/ ASHRAE 135-2012 and ISO 16484-5:2012 standard

• Supports BACnet MS/ TP and BACnet/ IP

• BACnet Client Function (Write Property, Read Property, COV Subscription)

• BACnet Client Configuration with configuration tool (scan and EDE import)

• B-BC (BACnet Building Controller)

• Integrated BACnet/ IP to BACnet MS/ TP Router

• BBMD (BACnet Broadcast Management Device)

• Modbus TCP and Modbus RTU (Master or Slave)

• Integrated web server for device configuration and monitoring data points

• Access to network statistics

• Configurable via Ethernet/ IP

Features

L‑VIS Touch Panel

Alarming Scheduling

Trending E-Mail OPC XML-DA

Server y=f(x)

GraphicsWeb Interface

Digital Input 0

Digital Input 1

DIGIN1DIGIN0

VISUALIZATION

Backlight

Touch L-TEMP1 Sensors

V1.2.8

Data Point Abstraction Layer

5.7’’

BACnet/IP

RO

UT

ER

BACnet

MS/TP

Modbus

RTU

Ethernet / IP

Modbus

TCP

LVIS-ME200

OPC XML-DA

Client www.loytec.com108

Ac ce ss or ie s

In te rf ac es Ro ut er s, N

IC

L-

D A

LI

L-

VI

S, L -S

TA

T

G at ew ay s L-

IO

B

L-

IN

X L-

RO

C

L- W

EB

Fu nc tio ns L‑

VI

S, L ‑S

TA

T

L‑VIS Touch Panel

Specifications Type LVIS‑ME200

Screen size 5.7” (145 mm)

Dimensions (mm) 210 x 164 x 63 (L x W x H), DIM001

Dimensions cut-out (mm) 180 x 150 x 57 (L x W x H)

Display resolution 320 x 240, 256 colors

Interfaces 1 x Ethernet (100Base-T):

OPC XML-DA (server, client), BACnet/ IP, HTTP, FTP, SMTP, NTP, VNC, Modbus TCP (Master or Slave)

1 x RS-485 (ANSI TIA/ EIA-485):

BACnet MS/ TP or Modbus RTU (Master or Slave)

2 x Digital Input 1 x Digital interface for up to 4 L-TEMP1 sensors

Power supply 20-35 V DC / 24 V AC ±10 % typ. 3 W, backlight on: 8 W

Operating conditions +10 °C to 40 °C, 10-90 % RH @ 50 °C, non condensing

Degree of protection Front: IP54 / back: IP10

Tools L-VIS/L-WEB Configurator

Resource limits OPC data points 2 000

Modbus data points 2 000

VNC clients 16

BACnet server objects 512

BACnet calendar objects 25

BACnet scheduler objects 100 (64 data points per object)

BACnet notification classes 32

E-mail templates 100

Math objects 500

Alarm logs 10

Trend logs 100 (390 000 entries, ≈ 6 MB)

Total trended data points 256

Connections (Local/Global) 1 000/250

Number of L-WEB clients 15 (simultaneously)

LVIS‑ME200

Order number Product description LVIS-ME200 BACnet Touch Panel with 5.7” display (Aluminium frame with anodized finish), B-BC

LVIS-FRAME1 Mounting frame for 5.7” Touch Panels

L-TEMP1 External temperature sensor

Surface Pro 3

Technical Specifications

Size

11.5” x 7.93” x 0.36”

(292.1mm x 201.4mm x 9.1mm)

Weight

1.76lbs

(800 grams)

Display

Screen: 12” ClearType Full HD Plus

Resolution: 2160 x 1440

Aspect Ratio: 3:2

Touch: Multi-touch

Battery Life

Up to 9 hours of web browsing1

Storage2/RAM

64GB or 128GB storage with 4GB RAM

256GB or 512GB storage with 8GB RAM

Processor o Intel Core i3

Intel Core i5

Intel Core i7 o Clock Speed

1.5GHz

1.9GHz

1.7GHz o CPU Max

1.5GHz

2.9GHz

(w/ turbo)

3.3GHz

(w/ turbo) o Graphics

Intel 4200

Intel 4400

Intel 5000 o TPM chip for enterprise security

Network

Wireless: Wi-Fi 802.11ac/802.11 a/b/g/n

Bluetooth® 4.0 Low Energy technology

Location

Digital Compass

Ports

Full-size USB 3.0 microSD™ card reader

Headset jack

Mini DisplayPort

Cover port

Software

Windows 8.1 Pro

Cameras, Video and Audio

5.0 megapixel rear-facing camera

5.0 megapixel front-facing camera

Stereo microphones

Stereo speakers with Dolby® sound

Sensors

Ambient light sensor

Accelerometer

Gyroscope

Magnetometer

Kickstand positions

Multiple

What's in the box

Surface Pro 3

Surface Pen

36W Power supply

Quick Start Guide

Safety and warranty documents

Microsoft – Surface USB to Ethernet Adapter

Specifications

Specs: Details:

Warranty Terms - Parts 1 year limited

Warranty Terms - Labor Not Available

Color Category Black

Compatibility Microsoft Surface

Quantity 1

Cable Adapter Type Surface Ethernet Adapter

End 1 Connector Type USB

End 2 Connector Type Ethernet

UPC 885370804577

Department of Veterans Affairs Environmental Controls VA Southern Nevada Healthcare System VA Project #593-15-103 Las Vegas, Nevada Construction Documents (Final)

00 00 10-1

TABLE OF CONTENTS

Section 00 01 10

DIVISION 01 – GENERAL REQUIREMENTS

01 00 00 General Requirements 01 33 23 Shop Drawings, Product Data, and Samples 01 35 26 Safety Requirements 01 42 19 Reference Standards

DIVISION 02 – EXISTING CONDITIONS

02 41 00 Demolition

DIVISION 07 – THERMAL AND MOISTURE PROTECTION

07 92 00 Joint Sealants

DIVISION 08 – OPENINGS

08 31 13 Access Doors and Frames

DIVISION 09 - FINISHES

09 22 16 Non-Structural Metal Framing 09 29 00 Gypsum Board 09 51 00 Acoustical Ceilings 09 91 00 Painting

DIVISION 23 – HEATING, VENTILATING, AND AIR

CONDITIONING (HVAC)

23 05 11 Common Work Results for HVAC 23 05 93 Testing, Adjusting, and Balancing for HVAC 23 07 11 HVAC Insulation 23 08 00 Commissioning of HVAC Systems 23 09 23 Direct-Digital Control System for HVAC 23 31 00 HVAC Ducts and Casings

DIVISION 26 - ELECTRICAL

26 05 11 Requirements for Electrical Installations 26 05 19 Low-Voltage Electrical Power Conductors and Cables 26 05 26 Grounding and Bonding for Electrical Systems 26 05 33 Raceway and Boxes for Electrical Systems 26 27 26 Wiring Devices