36C26026Q0895 0001
5. PROJECT NUMBER (if applicable)
CODE
7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office.
is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER
16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer)
08-14-2026
None 36C260 NCO 20 Network Contracting Office
ATTN: V4CONT
1601 E. Fourth Plain Blvd Bldg.17, Suite B428 Vancouver WA 98661
36C260 NCO 20 Network Contracting Office
ATTN: V4CONT
1601 E. Fourth Plain Blvd Bldg.17, Suite B428 Vancouver WA 98661 To all Offerors/Bidders
36C26026Q0895 08-04-2026
X
The purpose of this amendment is to:
1. Answer all questions that were submitted by 08/12/2026 at 5:00pm EDT.
2. All other terms and conditions of the solicitation remain the same.
VA Contracting POC: Michael Borelli at Michael.Borelli@va.gov
Replies to Vendor Questions Re SPO VA Backflow RFQ
1. Hello, I am reaching out with questions regarding the contract for the VA in Spokane, WA. Is there a list available of all assembly: Makes, Models, and Sizes?
See Following Table
| Location |
| Serial # |
| Model |
| Manufacture |
| Type |
| Size |
| Parking Lot B & C Lawn Box |
| J7837 |
| 350 |
| WILKINS |
| DC |
| 2.5 |
| MRI 1st Floor Mechanical Rm |
| 336957 |
| 009M2QT |
| WATTS |
| RP |
| 1 |
| Lawn Box- 15 Ft S. West Xformer/Indepence Dr |
| H41908 |
| 850 |
| FEBCO |
| DC |
| 2 |
| Hot Box-Assembly@ Reserve |
| X24705 |
| 375A |
| WILKINS |
| RP |
| 8 |
| Hot Box-Welllsley @ Indepence |
| X18839 |
| 375A |
| WILKINS |
| RP |
| 8 |
| Bldg 7 Mechanical Room |
| A172164 |
| 007M1QT |
| WATTS |
| DC |
| 2 |
| Bldg 7 Mechanical Room |
| 363951 |
| 007M3QT |
| WATTS |
| RP |
| 0.75 |
| Bldg 41 North Private Vault |
| 8151248 |
| 850 |
| FEBCO |
| DC |
| 4 |
| Bldg 41 Mechanical Room |
| 361428 |
| RP40 |
| Apollo |
| RP |
| 0.75 |
| Bldg 41 Mechanical Room |
| 172766 |
| 3000SS |
| Ames |
| DCDA |
| 4 |
| Bldg 41 Mechanical Room |
| 51471 |
| 2000B |
| Ames |
| DC |
| 0.75 |
| Bldg 41 Mechanical Room |
| 238553 |
| RP40 |
| Apollo |
| RP |
| 2 |
| Bldg 40 Basement West Mechanical Room |
| 193531 |
| 909 |
| WATTS |
| RP |
| 3 |
| Bldg 40 Basement Fire Riser Room |
| 174987 |
| 3000ss |
| Ames |
| DCDA |
| 4 |
| Bldg 40 Basement Fire Riser Room |
| 66343 |
| 2000B |
| Ames |
| DC |
| 0.75 |
| Bldg 40 Basement East Mechanical Room |
| 78988 |
| 009m3QT |
| WATTS |
| RP |
| 0.75 |
| Bldg 33 Ladies Lockerroom |
| 11838 |
| 007M2QT |
| WATTS |
| DC |
| 1.25 |
| Bldg 31 Room 115 |
| EB-2168 |
| COLT200A |
| Ames |
| DC |
| 4 |
| Bldg 27 Mechanical Room |
| 356797 |
| 009m3QT |
| WATTS |
| RP |
| 0.75 |
| Bldg 27 Mechanical Room |
| 569990 |
| 950XLT |
| WILKINS |
| DC |
| 0.75 |
| Bldg 27 Fire Closet |
| 9707281237 |
| 850 |
| FEBCO |
| DC |
| 3 |
| Bldg 2 -BoilerRoom |
| 18918 |
| LF909 |
| WATTS |
| RP |
| 4 |
| Bldg 2 -BoilerRoom |
| 22825 |
| LF009M2QT |
| WATTS |
| RP |
| 2.,0 |
| Bldg 2 -BoilerRoom |
| 10630 |
| 009M2QT |
| WATTS |
| RP |
| 1.25 |
| Bldg 15 East Lawn Box |
| 3930541 |
| 950XLT2 |
| WILKINS |
| DC |
| 2 |
| Bldg 14 Room 104 |
| 70685 |
| H-9505 |
| MUELLER |
| DC |
| 4 |
| Bldg 12 Room 201 Mechanical Rm |
| A82798 |
| 009M2QT |
| WATTS |
| RP |
| 1 |
| Bldg 12 Room 110 |
| A82759 |
| 009M2QT |
| WATTS |
| RP |
| 1 |
| Bldg 1E- Vault NW Corner |
| 3062470XLD |
| 950XL |
| WILKINS |
| DC |
| 0.75 |
| Bldg 1 Room C316 Outside Mechanical Room |
| 881798 |
| 975XL |
| WILKINS |
| RP |
| 0.75 |
| Bldg 3 Ground Shop Loose/Portable |
| 32315 |
| LF009M2QT |
| WATTS |
| RP |
| 2 |
| Bldg 1 Mechanical Room Room B252 |
| 236964 |
| 825Y |
| FEBCO |
| RP |
| 1 |
| Bldg 1 Mechanical Room |
| JC-1683 |
| 957 |
| Ames |
| RP |
| 3 |
| Bldg 1 Mechanical Room |
| 3105766XLTCU |
| 975XL |
| WILKINS |
| RP |
| 0.75 |
| Bldg 1 Basement Room D008A Mechanical Room |
| 185640 |
| 009m3QT |
| WATTS |
| RP |
| 0.75 |
| Bldg 1 Basement Room B008 Hot Romm Cooling Line |
| 363950 |
| 009m3QT |
| WATTS |
| RP |
| 0.75 |
| Bldg 1 Basement Room B005A Server Room |
| 402413 |
| 009QT |
| WATTS |
| RP |
| 0.5 |
| Bldg 1 Basement- Crawl Space Employee Uniform |
| 15604A |
| 350AST |
| Ames |
| DCVA |
| 6 |
| Bldg 1 9th Floor Mechanical Room |
| A164315 |
| 805Y |
| FEBCO |
| DC |
| 0.75 |
| Bldg 1 9th Floor Mechanical Room |
| 12526 |
| LF007M3QT |
| WATTS |
| DC |
| 0.75 |
| Bldg 1 8th Floor Scrub Room Surgery |
| 052353 |
| 009M2QT |
| WATTS |
| RP |
| 1 |
| Bldg 1 6th Floor Janitors Closet |
| 284534 |
| RP40 |
| Apollo |
| RP |
| 0.75 |
| Bldg 1 5th Floor Soil/ Waste Room |
| 72460 |
| 007QT |
| WATTS |
| DC |
| 0.5 |
| Bldg 1 1st Floor Soil/Waste Room |
| 72330 |
| 007QT |
| WATTS |
| DC |
| 0.5 |
| Bldg 1 1st Floor Cafteria Under Pop Machine |
| 398574 |
| 009QT |
| WATTS |
| RP |
| 0.5 |
| Bldg 1 Basement |
| 396448 |
| 007M1QT |
| WATTS |
| DC |
| 1 |
| Bldg 40 Basement West Mechanical Room |
| 193530 |
| 909 |
| WATTS |
| RP |
| 3 |
| Bldg 2 Boiler Plant West Wall |
| 089987 |
| LF009M2QT |
| WATTS |
| RP |
| 1 |
| Bldg 40 Basement East Mechanical Room |
| 354860 |
| 009m3QT |
| WATTS |
| RP |
| 0.75 |
| Bldg 1-Vault NW Corner #1E |
| V20873 |
| 350ADA |
| WILKINS |
| DCDA |
| 6 |
| Bldg 5 -Lawn Box South |
| H44801 |
| 850 |
| FEBCO |
| DC |
| 2 |
| Bldg 1 Room 3rd Floor Room C316 |
| 91998 |
| LF009M3QT |
| WATTS |
| RP |
| 0.75 |
| Bldg 10 SouthWest Wall |
| 86193 |
| LF009M3QT |
| WATTS |
| RP |
| 0.75 |
| BLdg 1 2nd Floor SPD Washroom |
| 576 |
| LF909M1QT |
| WATTS |
| RP |
| 1.5 |
| BLdg 1 2nd Floor SPD Washroom |
| 001401 |
| LF909M1QT |
| WATTS |
| RP |
| 2 |
| BLdg 1 2nd Floor SPD Washroom |
| 608723 |
| LF909M1QT |
| WATTS |
| RP |
| 1 |
| BLdg 1 2nd Floor SPD Washroom |
| 608721 |
| LF909M1QT |
| WATTS |
| RP |
| 1 |
| BLdg 1 2nd Floor SPD Washroom |
| 00602 |
| LF909M1QT |
| WATTS |
| RP |
| 1.5 |
| BLdg 1 2nd Floor SPD Washroom |
| 001397 |
| LF909M1QT |
| WATTS |
| RP |
| 2 |
| BLdg 1 2nd Floor SPD Washroom |
| 002905 |
| LF909M1QT |
| WATTS |
| RP |
| 0.75 |
| BLdg 1 2nd Floor SPD Washroom |
| 002951 |
| LF909M1QT |
| WATTS |
| RP |
| 0.75 |
| BLdg 1 2nd Floor SPD Washroom |
| 14930 |
| LF909M3QT |
| WATTS |
| RP |
| 0.75 |
| BLdg 1 2nd Floor STERIS Room |
| 008726 |
| LF909M1QT |
| WATTS |
| RP |
| 1 |
| BLdg 1 2nd Floor STERIS Room |
| 608728 |
| LF909M1QT |
| WATTS |
| RP |
| 1 |
| BLdg 1 2nd Floor STERIS Room |
| 608725 |
| LF909M1QT |
| WATTS |
| RP |
| 1 |
| BLdg 1 2nd Floor STERIS Room |
| 608724 |
| LF909M1QT |
| WATTS |
| RP |
| 1 |
| BLdg 1 2nd Floor STERIS Room |
| 608729 |
| LF909M1QT |
| WATTS |
| RP |
| 1 |
| Metal Lawn Box S.W Entrance by Tree |
| J48120 |
| 350 |
| WILKINS |
| DC |
| 2.5 |
| Lawn Box East of Bldg 4 |
| 3057845 |
| 950XLT |
| WILKINS |
| DC |
| BLdg 1 2nd Floor STERIS Room |
| 608722 |
| LF909M1QT |
| WATTS |
| RP |
| 1 |
| Bldg 6 Water Closet |
| 103710 |
| LF009-QT |
| WATTS |
| RPBA |
| 0.5 |
| BLdg 1 Specialty Care Basement |
| 002952 |
| LF909M1QT |
| WATTS |
| RP |
| 0.75 |
| BLdg 1 Specialty Care Basement |
| 002945 |
| LF909M1QT |
| WATTS |
| RP |
| 0.75 |
| Bldg 6 West Mechanical |
| 113686 |
| LF009-QT |
| WATTS |
| RPBA |
| 0.5 |
| Bldg 2 -BoilerRoom |
| 023059 |
| LF009M2QT |
| WATTS |
| RP |
| 1.5 |
| Bldg 1E- Basement Rm E018 |
| UF-2160 |
| 957 |
| WATTS |
| RP |
| 3 |
| Bldg 1 9th Floor Mechanical Room |
| A84658 |
| 009M3QT |
| WATTS |
| RP |
| 0.75 |
| BLdg 1 2nd Floor SPD Washroom |
| 00576 |
| LF909M1QT |
| WATTS |
| RP |
| 1.5 |
| Bldg 1 Basement- Room C002 |
| B378867 |
| 375XL |
| WILKINS |
| RP |
| 0.5 |
2. Is there a list of assemblies: size, manufacture, location (in vault, mechanical room, etc)? Please also share (if available) which ones if any are premise isolation. Campus isolation backflow devices.
See Following Table
| Hot Box-Assembly@ Reserve |
| X24705 |
| 375A |
| WILKINS |
| RP |
| 8 |
| Hot Box-Wellsley @Indepence |
| X18839 |
| 375A |
| WILKINS |
| RP |
| 8 |
3. Are all 100 assemblies in the main building, or spread throughout the campus?
Spead out throughout the campus
4. From a logistical standpoint, given that this is a medical facility, will testing (and repairs) need to be scheduled for weekend/after hours? I do see that point 8 at the bottom of page 5 calls for work to be completed during normal hours.
Work will be performed during regular work hours only.
5. However, in our experience with large medical facilities, testing can sometimes be forced to after hours as water shutoff occurs. It is helpful to know this in advance for proper bidding.
Work will be performed during regular work hours only.
6. Are you able to share who previously held this contract?
No
7. Is there an updated inventory or log of the 100 backflow prevention devices, including details such as type, manufacturer, model, and installation date? Yes .
The requirement is for 100 assemblies . See Following Table.
| Location |
| Serial # |
| Model |
| Manufacture |
| Type |
| Size |
| Parking Lot B & C Lawn Box |
| J7837 |
| 350 |
| WILKINS |
| DC |
| 2.5 |
| MRI 1st Floor Mechanical Rm |
| 336957 |
| 009M2QT |
| WATTS |
| RP |
| 1 |
| Lawn Box- 15 Ft S. West Xformer/Indepence Dr |
| H41908 |
| 850 |
| FEBCO |
| DC |
| 2 |
| Hot Box-Assembly@ Reserve |
| X24705 |
| 375A |
| WILKINS |
| RP |
| 8 |
| Hot Box-Wellsley @Indepence |
| X18839 |
| 375A |
| WILKINS |
| RP |
| 8 |
| Bldg 7 Mechanical Room |
| A172164 |
| 007M1QT |
| WATTS |
| DC |
| 2 |
| Bldg 7 Mechanical Room |
| 363951 |
| 007M3QT |
| WATTS |
| RP |
| 0.75 |
| Bldg 41 North Private Vault |
| 8151248 |
| 850 |
| FEBCO |
| DC |
| 4 |
| Bldg 41 Mechanical Room |
| 361428 |
| RP40 |
| Apollo |
| RP |
| 0.75 |
| Bldg 41 Mechanical Room |
| 172766 |
| 3000SS |
| Ames |
| DCDA |
| 4 |
| Bldg 41 Mechanical Room |
| 51471 |
| 2000B |
| Ames |
| DC |
| 0.75 |
| Bldg 41 Mechanical Room |
| 238553 |
| RP40 |
| Apollo |
| RP |
| 2 |
| Bldg 40 Basement West Mechanical Room |
| 193531 |
| 909 |
| WATTS |
| RP |
| 3 |
| Bldg 40 Basement Fire Riser Room |
| 174987 |
| 3000ss |
| Ames |
| DCDA |
| 4 |
| Bldg 40 Basement Fire Riser Room |
| 66343 |
| 2000B |
| Ames |
| DC |
| 0.75 |
| Bldg 40 Basement East Mechanical Room |
| 78988 |
| 009m3QT |
| WATTS |
| RP |
| 0.75 |
| Bldg 33 Ladies Lockerroom |
| 11838 |
| 007M2QT |
| WATTS |
| DC |
| 1.25 |
| Bldg 31 Room 115 |
| EB-2168 |
| COLT200A |
| Ames |
| DC |
| 4 |
| Bldg 27 Mechanical Room |
| 356797 |
| 009m3QT |
| WATTS |
| RP |
| 0.75 |
| Bldg 27 Mechanical Room |
| 569990 |
| 950XLT |
| WILKINS |
| DC |
| 0.75 |
| Bldg 27 Fire Closet |
| 9707281237 |
| 850 |
| FEBCO |
| DC |
| 3 |
| Bldg 2 -BoilerRoom |
| 18918 |
| LF909 |
| WATTS |
| RP |
| 4 |
| Bldg 2 -BoilerRoom |
| 22825 |
| LF009M2QT |
| WATTS |
| RP |
| 2.,0 |
| Bldg 2 -BoilerRoom |
| 10630 |
| 009M2QT |
| WATTS |
| RP |
| 1.25 |
| Bldg 15 East Lawn Box |
| 3930541 |
| 950XLT2 |
| WILKINS |
| DC |
| 2 |
| Bldg 14 Room 104 |
| 70685 |
| H-9505 |
| MUELLER |
| DC |
| 4 |
| Bldg 12 Room 201 Mechanical Rm |
| A82798 |
| 009M2QT |
| WATTS |
| RP |
| 1 |
| Bldg 12 Room 110 |
| A82759 |
| 009M2QT |
| WATTS |
| RP |
| 1 |
| Bldg 1E- Vault NW Corner |
| 3062470XLD |
| 950XL |
| WILKINS |
| DC |
| 0.75 |
| Bldg 1 Room C316 Outside Mechanical Room |
| 881798 |
| 975XL |
| WILKINS |
| RP |
| 0.75 |
| Bldg 3 Ground Shop Loose/Portable |
| 32315 |
| LF009M2QT |
| WATTS |
| RP |
| 2 |
| Bldg 1 Mechanical Room Room B252 |
| 236964 |
| 825Y |
| FEBCO |
| RP |
| 1 |
| Bldg 1 Mechanical Room |
| JC-1683 |
| 957 |
| Ames |
| RP |
| 3 |
| Bldg 1 Mechanical Room |
| 3105766XLTCU |
| 975XL |
| WILKINS |
| RP |
| 0.75 |
| Bldg 1 Basement Room D008A Mechanical Room |
| 185640 |
| 009m3QT |
| WATTS |
| RP |
| 0.75 |
| Bldg 1 Basement Room B008 Hot Romm Cooling Line |
| 363950 |
| 009m3QT |
| WATTS |
| RP |
| 0.75 |
| Bldg 1 Basement Room B005A Server Room |
| 402413 |
| 009QT |
| WATTS |
| RP |
| 0.5 |
| Bldg 1 Basement- Crawl Space Employee Uniform |
| 15604A |
| 350AST |
| Ames |
| DCVA |
| 6 |
| Bldg 1 9th Floor Mechanical Room |
| A164315 |
| 805Y |
| FEBCO |
| DC |
| 0.75 |
| Bldg 1 9th Floor Mechanical Room |
| 12526 |
| LF007M3QT |
| WATTS |
| DC |
| 0.75 |
| Bldg 1 8th Floor Scrub Room Surgery |
| 052353 |
| 009M2QT |
| WATTS |
| RP |
| 1 |
| Bldg 1 6th Floor Janitors Closet |
| 284534 |
| RP40 |
| Apollo |
| RP |
| 0.75 |
| Bldg 1 5th Floor Soil/ Waste Room |
| 72460 |
| 007QT |
| WATTS |
| DC |
| 0.5 |
| Bldg 1 1st Floor Soil/Waste Room |
| 72330 |
| 007QT |
| WATTS |
| DC |
| 0.5 |
| Bldg 1 1st Floor Cafteria Under Pop Machine |
| 398574 |
| 009QT |
| WATTS |
| RP |
| 0.5 |
| Bldg 1 Basement |
| 396448 |
| 007M1QT |
| WATTS |
| DC |
| 1 |
| Bldg 40 Basement West Mechanical Room |
| 193530 |
| 909 |
| WATTS |
| RP |
| 3 |
| Bldg 2 Boiler Plant West Wall |
| 089987 |
| LF009M2QT |
| WATTS |
| RP |
| 1 |
| Bldg 40 Basement East Mechanical Room |
| 354860 |
| 009m3QT |
| WATTS |
| RP |
| 0.75 |
| Bldg 1-Vault NW Corner #1E |
| V20873 |
| 350ADA |
| WILKINS |
| DCDA |
| 6 |
| Bldg 5 -Lawn Box South |
| H44801 |
| 850 |
| FEBCO |
| DC |
| 2 |
| Bldg 1 Room 3rd Floor Room C316 |
| 91998 |
| LF009M3QT |
| WATTS |
| RP |
| 0.75 |
| Bldg 10 SouthWest Wall |
| 86193 |
| LF009M3QT |
| WATTS |
| RP |
| 0.75 |
| BLdg 1 2nd Floor SPD Washroom |
| 576 |
| LF909M1QT |
| WATTS |
| RP |
| 1.5 |
| BLdg 1 2nd Floor SPD Washroom |
| 001401 |
| LF909M1QT |
| WATTS |
| RP |
| 2 |
| BLdg 1 2nd Floor SPD Washroom |
| 608723 |
| LF909M1QT |
| WATTS |
| RP |
| 1 |
| BLdg 1 2nd Floor SPD Washroom |
| 608721 |
| LF909M1QT |
| WATTS |
| RP |
| 1 |
| BLdg 1 2nd Floor SPD Washroom |
| 00602 |
| LF909M1QT |
| WATTS |
| RP |
| 1.5 |
| BLdg 1 2nd Floor SPD Washroom |
| 001397 |
| LF909M1QT |
| WATTS |
| RP |
| 2 |
| BLdg 1 2nd Floor SPD Washroom |
| 002905 |
| LF909M1QT |
| WATTS |
| RP |
| 0.75 |
| BLdg 1 2nd Floor SPD Washroom |
| 002951 |
| LF909M1QT |
| WATTS |
| RP |
| 0.75 |
| BLdg 1 2nd Floor SPD Washroom |
| 14930 |
| LF909M3QT |
| WATTS |
| RP |
| 0.75 |
| BLdg 1 2nd Floor STERIS Room |
| 008726 |
| LF909M1QT |
| WATTS |
| RP |
| 1 |
| BLdg 1 2nd Floor STERIS Room |
| 608728 |
| LF909M1QT |
| WATTS |
| RP |
| 1 |
| BLdg 1 2nd Floor STERIS Room |
| 608725 |
| LF909M1QT |
| WATTS |
| RP |
| 1 |
| BLdg 1 2nd Floor STERIS Room |
| 608724 |
| LF909M1QT |
| WATTS |
| RP |
| 1 |
| BLdg 1 2nd Floor STERIS Room |
| 608729 |
| LF909M1QT |
| WATTS |
| RP |
| 1 |
| Metal Lawn Box S.W Entrance by Tree |
| J48120 |
| 350 |
| WILKINS |
| DC |
| 2.5 |
| Lawn Box East of Bldg 4 |
| 3057845 |
| 950XLT |
| WILKINS |
| DC |
| BLdg 1 2nd Floor STERIS Room |
| 608722 |
| LF909M1QT |
| WATTS |
| RP |
| 1 |
| Bldg 6 Water Closet |
| 103710 |
| LF009-QT |
| WATTS |
| RPBA |
| 0.5 |
| BLdg 1 Specialty Care Basement |
| 002952 |
| LF909M1QT |
| WATTS |
| RP |
| 0.75 |
| BLdg 1 Specialty Care Basement |
| 002945 |
| LF909M1QT |
| WATTS |
| RP |
| 0.75 |
| Bldg 6 West Mechanical |
| 113686 |
| LF009-QT |
| WATTS |
| RPBA |
| 0.5 |
| Bldg 2 -BoilerRoom |
| 023059 |
| LF009M2QT |
| WATTS |
| RP |
| 1.5 |
| Bldg 1E- Basement Rm E018 |
| UF-2160 |
| 957 |
| WATTS |
| RP |
| 3 |
| Bldg 1 9th Floor Mechanical Room |
| A84658 |
| 009M3QT |
| WATTS |
| RP |
| 0.75 |
| BLdg 1 2nd Floor SPD Washroom |
| 00576 |
| LF909M1QT |
| WATTS |
| RP |
| 1.5 |
| Bldg 1 Basement- Room C002 |
| B378867 |
| 375XL |
| WILKINS |
| RP |
| 0.5 |
8. Are there any known issues, recurring problems, or historical performance concerns with specific units that we should be aware of prior to testing?
No
9. Are there any existing records, inspection histories, or deficiency reports that identify specific repairs needed for the up to 20 devices referenced in the SOW?
No
10. Have any prior repairs or replacements been performed on these devices, and if so, could you provide relevant documentation?
No