Q and A RFQ 36C26024Q0780.pdf

PDF 4 MB Posted

Attached to
J061--Transformer Testing and cleaning- Small Business set aside Federal contract opportunity
Solicitation number
36C26024Q0780
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 20

About this file

This document contains a set of questions and answers related to RFQ 36C26024Q0780, a firm fixed price small business set-aside solicitation issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 20. The RFQ is for transformer testing and cleaning services. Key details include:

The solicitation has a question deadline of August 1, 2024 at 5:30 PM Pacific time. Questions must be submitted to Nicholas Price at Nicholas.Price@va.gov with the subject "RFQ 36C26024Q0780". The RFQ is a small business set-aside. The solicitation requires providing labor and materials to test and clean 28 liquid-cooled medium voltage transformers, including topping off transformer oil as needed. Specific details are provided about the transformer types, cooling liquids, and past oil test results. The VA will provide a credit for any transformer oil that ends up not being needed.

View the file

Other files for this federal contract opportunity

Other files attached to J061--Transformer Testing and cleaning- Small Business set aside, newest first.
File Type Posted
RFQ 36C26024Q0780 0001 amendment .pdf PDF
36C26024Q0780 0001.docx DOCX document
RFQ 36C26024Q0780 Wage Determintion Jackson county.pdf PDF
36C26024Q0780.docx DOCX document
RFQ 36C26024Q0780.pdf PDF
RFQ 36C26024Q0780 SOW.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1) we need to know what type of oil the transformers have so we can include supplying that oil to the jobsite for technicians to top-off. All transformer oil is different pricing wise. Also, I know it says in the SOW that the warehouse is not expecting to shutdown the transformers, but in order to top-off the oil the transformers must be de-energized. Please advise?

Answer: Mineral oil is the type referred to us by our typical service provider

“Transformer Services, Inc.” and is listed in out SPCC plan. Thank you for thoughtful question on shutdowns. If a shutdown is needed, we will accommodate it. But an action plan is required to be submitted 3 weeks prior, as the facility has to complete various memos.

2) Could you please provide the following detailed information about twenty‐eight

(28) liquid‐cooled medium voltage transformers:

What Type of Transformer?

Answer: Step down oil transformers from 12,450 VAC to 208 VAC, though two (XFMR “M” and “P”).

What Type of Liquid: Type of liquid used (e.g., mineral oil, silicone oil, ester-based fluid)

Answer: Mineral oil is the type referred to us by our typical service provider “Transformer Services, Inc.”.

Volume of liquid required (in liters)

Answer: Responder hesitates to answer this, as it seems to ask the volume of each transformer.

Offeror to apply the language of the SOW to his/her offer; i.e. top off all transformers as needed, but assume 2 will need oil replaced. If they end up not being needed, VA will received the offer amount back as a credit per the VAAR.

Specific brand or product name of the liquid, if applicable

Is the liquid provided, or do we need to supply it?

Answer: Contractor provides all labor and materials. Manufacturers recommendations supersede “industry standards” regarding brand of liquid.

3) Are previous oil test results available for all transformers?

Answer: They are available for some. Please see attached tests for 2010 and 2016.

We have newer transformers that have been installed since the last testing/service occurred, however.

4) What are the sizes of the 2 transformers that need oil replacement?

Answer: Please see answer 2.

5) What is the driver necessitating oil replacement in 2 transformers?

Answer: There is no specific driver, and it may not be needed. But it is easier for VA to have that in the offer and get the credit back than to add it as a change order.

6) Can you please provide a clear picture of each nameplate which will show what type of cooling liquid each transformer has and approximately/ballpark number of how much each one might need to be topped off with?

Answer: In lieu of a nameplate, would you kindly refer to the tabulated information given in answer 2. As for oil top off, the VA would not have that information, nor would we have control over how much oil the sampler removed which had to be topped off afterward. Past assumptions from our typical servicer indicated 1 gallon per transformer.

7) Line item 0002 says to replace cooling liquid in two transformers. Can you please provide a clear picture of the nameplate which should show the type of fluid used and how many gallons it contains?

Answer: In lieu of a nameplate, would you kindly refer to the tabulated information given in answer 2. We do not know which of up to 2 would need liquid replacement. In fact, it is unlikely that they will. But it is easier for the VA to have that assumption so it is covered.

TRANSFORMER TESTING & REPAIRS, INC. ®

COMPY: VA REHABILITATION

CITY, STATE: WHITE CITY, OR

[ SUBSTATION: A

OTHER:

VISUAL / SEDIMENT

CLEAR/ND

CLEAR/ND

CLEAR/ND

CLEAR/ND

CLEAR/ND

ID# 0810845

TAG# 1

DATE RESULTS (% BY WEIGHT)

11/08/10 0.36 10/04/00 0.40 09/22/99 0.38

09/20/94 0.37 08/09/93 0.37 COMMENTS: Acceptable.

TOTAL-GAS

80496 90750 93501 87999 93500

COMMENTS: All gases are within normal limits. Recommended retest time: ONE YEAR

LABORATORY SERVICES * FIELD REPAIRS & MAINTENANCE * PCB SERVICES HOT OIL RECONDITIONING

P0 BOX 2219, SUISUN CITY, CA 94585-5219 PHONE: (707) 421-9398 I FAX: (707) 421-9662

DIVISION: SOUTH OREGON WHITE CITY

REGION:

LOCATION: OUTDOORS/GROUND

EQUIPMENT NAMEPLATE DATA

UNIT: XFMR A

MFG: STANDARD PRIMARY: 12000 DELTA GALLONS: 122

SERIAL#: P1C1443 SECONDARY: 208Y/I20 FLUIDTYPE: OIL

KVA: 75 j CLASS/IMPED.: OA 3.86 COOLING: AIR

PHASE/CYCLE: 3/60 RATED TEMP: 65°C HV BUSHINGS: SIDE IN-CABINET

EQUIP. TYPE: TRANSFORMER DATE OF MFG: LV BUSHINGS: SIDE IN-CABINET

- ANNUAL INSPECTION & GAUGE SETTINGS AS OF: 10/22/10

HV BUSHINGS: CLEAN LV BUSHINGS: CLEAN FLUID-LEVEL: Good

LEAKS NONE FLUID-TEMP/PEAK:

PAINT COND: FAIR, PEELING/CHIPPED WINDING TEMP:

OTHER: PRES/VAC:

SERVICE NOTES: Filter press, internal inspection: 10/22/10.

TAP-SEflING: D

LIQUID SCREEN TEST INHIBITOR CONTENT

DIELECTRIC COLOR Spec-Gravity

0.874 0.880 0.870 0.880 0.880

DATE ACID (N/N) IFT

11/08/10 0.04 33.1 34 1.5 05/17/08 0.03 35.0 35 1.50 05/27/06 0.03 35.2 48 1.50 05/08/04 0.04 34.8 36 1.50 05/03/03 0.03 36.4 32 1.50

(,MMENTS: Acceptable: All screen test categories are Acceptable at this time. Retest One

DATE

11/01 / 10 05/17/08 05/27/06 05/08/04 05/03/03

DISSOLVED GAS-IN-OIL / GAS CHROMATOGRAPHY EXPRESSED IN PPM

CARBON CARBON - TOTAL

HYDROGEN OXYGEN NITROGEN METHANE MONOXIDE DIOXIDE ETHANE ETHYLENE ACETYLENE COMBUST

0 21515 58493 2 68 413 1 4 0 75 0 28638 61422 0 15 675 0 0 0 15 0 27745 65203 1 33 518 0 1 0 35 0 27373 60016 0 27 582 0 1 0 28 0 30082 62911 4 23 465 0 15 0 42

MOISTURE CONTENT /PPM: PCB IN

DATE PPM COMMENTS:

11/08/10 22 Acceptable.

07/20/09 30 05/17/08 40 05/27/06 29 05/08/04 20

NOTES:

PARTS I MILLION LIQUID POWER FACTOR %

TEST DATE CONTENT CLASS DATE 25°C 100° C COMMENTS:

08/09/93 3 NON-PCB 11/08/10 0.122 Questionable.

10/11/85 11 NON-PCB 05/08/04 0.385 12.340

08/09/82 1 NON-PCB 10/04/00 0.348 8.290

California Depart. Of Toxic Substances Control regulates 09/22/99 0.320 9.068 PCB> S ppm. CCR defines PCB’s as hazardous waste: I T,tI 21 fli,i,nn 1 c r 11, I. il.24. 09/20/94 0.260 5.750

COMMENTS: Not Tested.

. FURAN ANALYSIS—PARTS / BILLION

F1IAE SH2F 2FOL 2FAL 2ACF 5M2F TOTAL

0 24. 5LrTin, & Reoair,. b,.

LABORATORY SERVICES FIELD REPAIRS & MAINTENANCE PCB SERVICES r HOT OIL RECONDITIONING

P0 BOX 2219, SUISUN CITY, CA 94585-5219 PHONE: (707) 421-9398 I FAX: (7fl7) 421-q662

COMPANY: VA REHABILITATION

ç CITY, STATE: WHITE CITY, OR

SUBSTATION: NEAR BLDG #201 -L

OTHER:

DIVISION: SOUTH OREGON WHITE CITY ID# 0810845

REGION: TAG# 2

LOCATION: OUTDOORS/GROUND UNIT: XFMR L

EQUIPMENT NAMEPLATE DATA

MFG: STANDARD PRIMARY: 12000 DELTA GALLONS: 166

SERIAL#: PIC1357 SECONDARY: 208Y/120 FLUID TYPE: OIL

KVA: 225 CLASS/IMPED.: OA 5.06 COOLING: AIR

PHASE/CYCLE: 3/60 RATED TEMP: 65°C HV BUSHINGS: SIDE IN-CABiNET

EQUIP. TYPE: TRANSFORMER - DATE OF MFG: LV BUSHINGS: SIDE IN-CABINET

ANNUAL INSPECTION & GAUGE SETTINGS AS OF: 10/22/10

HV BUSHINGS: DUSTY LV BUSHINGS: DUSTY FLUID-LEVEL: GOOD-No Gauge

LEAKS NONE FLUID-TEMP/PEAK: N/A

PAINT COND: FAIR WINDING TEMP: N/A

OTHER: PRES/VAC: *

SERVICE NOTES: Replaced H1B, H2B, & H3B inserts, filter press, inspection: 10/8/10. TAP-SETTING: D

LIQUID SCREEN TEST INHIBITOR CONTENT

DATE ACID (N/N) IFT DIELECTRIC COLOR Spec-Gtavity VISUAL / SEDIMENT DATE RESULTS (% BY WEIGHT)

11/08/10 0.11 30.1 56 2.5 0.880 CLEAR/ND ill/08/l0 0.28 05/17/08 0.05 34.0 45 2.50 0.880 CLEAR/ND i10/04/00 0.31

05/27/06 0.05 34.9 44 2.00 0.880 CLEAR/ND 09/22/99 0.29

05/08/04 0.05 35.3 37 1.50 0.885 CLEAR/ND 11/19/98 0.30

05/03/03 0.05 34.1 31 1.50 0.880 CLEAR/ND :09/20/94 0.33

OMMENTS: Questionable: Oxidation by-products have formed and are trapped in the paper COMMENTS: Acceptable.

sulation. Retest One Year.

DISSOLVED GAS-IN-OIL I GAS CHROMATOGRAPHY EXPRESSED IN PPM

CARBON CARBON TOTAL

DATE HYDROGEN OXYGEN NITROGEN METHANE MONOXIDE DIOXIDE ETHANE ETHYLENE ACETYLENE COMBUST

PARTS / MILLION

CONTENT CLASS

4 NON-PCB

5 NON-PCB

2 NON-PCB

California Depart. Of Toxic Substances Control regulates CB> 5 ppm. CCR defines PCB’s as hazardous waste:

FilIe 22. Division 4.5. Chapter 11. Article 3, 66261.24.

NOTES: —

exists to install missing pressure/vacuum gauge & N2 gas filler valve.

DATE 25°C 100°C COMMENTS:

11/08/10 0.054 Acceptable.

05/17/08 0.036 2.321 05/27/06 0.058 2.175

1 05/08/04 0.353 9.742 I 10/04/00 0.353 7.780

DATE 5H2F 2FOL 2FAL 2ACF 5M2F TOTAL

COMMENTS: Not Tested.

11/01/10 0 16838 60278 1 94 808 1 05/17/08 3 23701 52545 1 27 718 0 05/27/06 0 27214 65438 1 40 800 0 05/08/04 0 29069 63867 0 24 537 0 05/03/03 0 28281 59249 1 16 446 0

COMMENTS: All gases are within normal limits. Recommended retest time: ONE YEAR

MOISTURE CONTENT !PP PCB IN

COMMENTS: TEST DATE

Acceptable. 08/09/93

DATE

11/08/10 07/20/09 05/17/08 05/27/06 05/08/04

TOTAL-GAS

12 0 108 78032 5 0 36 77000 7 0 48 93500 3 0 27 93500 4 0 21 87997

LIQUID POWER FACTOR %

PPM

10/11/85 08/09/82

FURAN ANALYSIS—PARTS

UU4.I1,,tm & liv.

/ BILLION

MOISTURE CONTENT IPPMD PCB IN

COMMENTS: TEST DATE

Acceptable. 05128196 08/09/93 (‘)RIflQIR2

NOTES:

*Recess exists to install missing pressure/vacuum gauge & N2 gas filler

PARTS / MILLION

CONTENT CLASS

4 NON-PCB

5 NON-PCB

1 NON-PCR

:ATflRY SERVICES FIELD REPAIRS & MAINTENANCE * PCB SERVICES * HOT OIL RECONDITIONING

..i ‘I WI IN CITY, CA 94585-5219 I PHONE: (707)421-93981 FAX: (707)421-9662

COMPANY: VA REHABILITATION

CITY, STATE: WHITE CITY, OR

[-SUBSTATION: NEAR BLDG #211-N

OTHER:

DIVISION: SOUTH OREGON WHITE CITY

REGION:

LOCATiON: OUTDOORS/GROIJND

EQUIPMENT NAMEPLATE DATA

IID# 0810845

:TAG# 3

UNIT: XFMR N

MFG: STANDARD PRIMARY: 12000 DELTA GALLONS: 227

SERIAL#: PID1726 SECONDARY: 208Y/120 FLUID TYPE: OIL

KVA: 500 CLASS/IMPED.: OA 5.76 COOLING: AIR

PHASE/CYCLE: 3/60 RATED TEMP: 65°C HV BUSHINGS: SIDE 11J-CAB1NET

EQUIP. TYPE: TRANSFORMER DATE OF MFG: LV BUSHINGS: SIDE IN-CABINET

ANNUAL INSPECTION & GAUGE SETTINGS AS OF 10/22/10

HV BUSHINGS: CLEAN LV BUSHINGS: CLEAN FLUID-LEVEL: GOOD-No Gauge

LEAKS NONE FLUID-TEMP/PEAK: N/A

PAINT COND: FAIR WINDING TEMP: N/A

OTHER: PRES/VAC: *

SERVICE NOTES: Filter press, internal inspection: 10/8/10. — TAPSEHING: D

LIQUID SCREEN TEST INHIBITOR CONTENT

DATE ACID (N/N) IFT DIELECTRIC COLOR Spec-Gravity VISUAL / SEDIMENT [DATE RESULTS (% BY WEIGHT)

11/08/10 0.05 34.6 50 2.0 0.880 CLEAR/ND 111/08/10 0.66

05/17/08 0.04 35.4 50 1.50 0.880 CLEAR/ND 05/17/08 0.69

05/27/06 0.04 36.0 49 1.50 0.880 CLEAR/ND 05/27/06 0.78

05/08/04 0.04 36.7 39 1.50 0.880 CLEAR/ND 05/08/04 0.79

05/03/03 0.04 39.1 40 1.50 0.880 CLEAR/ND 05/03/03 0.73

COMMENTS: Acceptable: All screen test categories are Acceptable at this time. Retest One COMMENTS: Acceptable.

r’ear.

[ DISSOLVED GAS-IN-OIL / GAS CHROMATOGRAPHY EXPRESSED IN PPM

CARBON CARBON

DATE HYDROGEN OXYGEN NITROGEN METHANE MONOXIDE DIOXIDE ETHANE ETHYLENE ACETYLENE COMBUST TOTAL-GAS

11/02/10 0 18483 54573 2 61 550 2 7 0 72 73678 05/I7/08 0 26662 57857 0 35 693 0 2 0 37 85249 05/27/06 0 30015 68161 2 61 757 0 4 0 67 99000 05/08/04 0 28189 61939 1 23 596 0 2 0 26 90750 05/03/03 0 30849 64954 I 12 434 0 1 0 14 96251

TOTAL

COMMENTS: All gases are within normal limits. Recommended retest time: ONE YEAR

DATE

11/08/10 07/20/09 05/17/08 05/27/06 05/08/04

PPM

LIQUID POWER FACTOR %

DATE

11/08/10 05/17/08 05/27/06

7 05/08/04 I 05/03/03

(J

25° C

0.016 0.014 0.041 0.040 0.109

1000 C COMMENTS:

Acceptable.

1.101 1.046 0.744California Depart. Of Toxic Substances Control regulates

PCB>5 ppm. CCR defines PCB’s as hazardous waste:

22. F ac.i rll,Acle3,6626l.24. . 1.654

FURAN ANALYSIS—PARTS / BILLION

k I DATE SH2F 2FOL 2FAL 2ACF 5M2F TOTAL

.05/17/08 0 0 47 0 0 47 05/27/06 0 0 43 0 0 43

COMMENTS: Retest One Year. NOT TESTED BY HR. RESULT

MINIMALLY CHANGED FROM LAST TEST. NORMAL

RESULT FOR HEALTHY EQUIPMENT.

© 2004 Tmosforrnor & Rooir Inc.

DATE

11/08/10 07/20/09 05/17/08 05/27/06 05/08/04

PPM

NOTES:

TRANSFORMER TESTING & REPAIRS, INC. ®

ATORY SERVICES * FIELD REPAIRS & MAINTENANCE * PCB SERVICES * HOT OIL RECONDITIONING

H .19, SUISUN CITY, CA94585-’1 PHflNE: (7fl7)1Q398 FAX:(707)421-9662

COMPY: VA REHABILITATION DIVISION: SOUTH OREGON WHITE CITY ID# 0810845

CITY, STATE: WHITE CITY, OR REGION: TAG# 4

SUBSTATION: BLDG 200-K LOCATION: OUTDOORS/GROUI’4D UNIT: )(pf’,fl K

OTHER:

EQUIPMENT NAMEPLATE DATA

w

MFG: STANDARD PRIMARY: 12000 DELTA GALLONS: 122

SERIAL#: P1C1444 SECONDARY: 208Y/120 FLUID TYPE: OIL

KVA: 75 CLASS/IMPED.: OA 3.92 COOLING: AIR

PHASE/CYCLE: 3/60 RATED TEMP: 65°C HV BUSHINGS: SIDE IN-CABINET

EQUIP. TYPE: TRANSFORMER DATE OF MFG: LV BUSHINGS: SIDE IN-CABINET

ANNUAL INSPECTION & GAUGE SETTINGS AS OF: 10/22/10

HV BUSHINGS: CLEAN LV BUSHINGS: CLEAN FLUID-LEVEL:

LEAKS NONE FLUID-TEMP/PEAK: N/A

PAINT COND: OLD, PEELING/CHIPPED WINDING TEMP: N/A

OTHER: PRES/VAC: N/A

SERVICE NOTES: Filter press, internal inspection: 10/22/10. TAP-SETFING: D

LIQUID SCREEN TEST INHIBITOR CONTENT

DATE ACID (N/N) IFT DIELECTRIC COLOR Spec-Gravity VISUAL / SEDIMENT

11/08/10 0.10 31.4 51 2.5 0.876 CLEAR/ND

05/17/08 0.04 33.6 48 2.50 0.880 CLEAR/ND

05/27/06 0.05 34.2 43 2.00 0.880 CLEAR/ND

05/08/04 0.05 34.8 36 2.00 0.880 CLEAR/ND

05/03/03 0.06 34.2 37 2.00 0.880 CLEAR/ND

COMMENTS: H nII: Acid and/or IFT test(s) indicate oxidation by-products are orming. Retest One Year.

DATE RESULTS (% BY WEIGHT)

11/08/10 0.35 10/04/00 0.36 09/22/99 0.34 11/19/98 0.36 09/20/94 0.38 COMMENTS: Acceptable.

ETHYLENE

ACETYLENE

F ffiOLVED GAS-IN-OIL / GAS CHROMATOGRAPHY EXPRESSED IN PPM

CARBON CARBON

DATE HYDROGEN OXYGEN NITROGEN METHANE MONOXIDE DIOXIDE ETHANE

11/02/10 0 11340 47181 3 73 668 0 05/17/08 0 27918 59581 2 28 469 0 05/27/06 1 28370 69973 1 51 602 0 05/08/04 0 28310 64539 0 38 609 0 05/03/03 0 28319 59214 1 19 441 0 COMMENTS: All gases are within normal limits: Recommended retest time: ONE YEAR

MOISTURE CONTENT /PPM PCB IN LIQUID POWER FACTOR %

COMMENTS: TEST DATE

Acceptable. 08/09/93 08/09/82

TOTAL

COMBUST

TOTAL-GAS

59278 88000 99001 93499 87998

PARTS / MILLION -

CONTENT CLASS DATE 25° C 100° C COMMENTS

*6 NON-PCB 1 1/08/10 0.068 Acce

3 NON-PCB 05/17/08 0.037 2.441

re.05/27/06 0.082 2.486 *California Depart. Of Toxic Substances Control regulates I 05/08/04 0.346 5.722 PCB >5 ppm. CCR defines PCB’s as hazardous waste: I ii.: t1.24. I; 10/04/00 0.33 1 8.460

FURAN ANALYSIS—PARTS I BILLION

TE 5H2F 2FOL 2FAL 2ACF 5M2F TOTAL

© 2004. Tra,,sforrner Ttin & Rcoair. Inc.

Ii

I’ -j-”-..I COMMENTS: Not Tested.

TEST DATE CONTENT CLASS DATE

08/09/93 4 NON-PCB 11/08/10

08/09/82 3 NON-PCB 05/17/08

0 5/2 7/06 *California Depart. Of Toxic Substances Control regulates 05/08/04 PCB >5 ppm. CCR defines PCB’s as hazardous waste:

Ti -- riLA ;. 09/20/94

TRANSFORMER TESTING & REPAIRS, INC. ®

LA!ORAT0RY SERVICES FIELD REPAIRS & MAINTENANCE * PCB SERVICES * HOT OIL RECONDITION INt

PC Y 2219, SUISUN CITY, CA 94585-5219 PflNE: (707)421-9398 I FAX: (7fl7) 421 $(;(H

COMPANY: VA REHABILITATION DIVISION: SOUTH OREGON WHITE CITY

\ CITY, STATE: WHITE CITY, OR REGION:

SUBSTATION: XFMR F LOCATION: OUTDOORS/GROUND UNIT: XFMR F

OTHER: SPARE

JD# 0810845

TAG# 5

EQUIPMENT NAMEPLATE DATA

MFG: STANDARD PRIMARY: 12000 DELTA GALLONS: 137

SERIAL /: PlC 1404 SECONDARY: 208Y/120 FLUID TYPE: OIL

KVA: 150 CLASS/IMPED.: OA 5.06 COOLING: AIR

PHASE/CYCLE: 3/60 RATED TEMP: 65°C HV BUSHINGS: SIDE IN-CABINET

EQUIP. TYPE: TRANSFORMER DATE OF MFG: LV BUSHINGS: SIDE IN-CABINET

ANNUAL INSPECTION & GAUGE SETTINGS AS OF: 10/22/10

HV BUSHINGS: DIRTY LV BUSHINGS: DIRTY FLUID-LEVEL: Good

LEAKS NONE FLUID-TEMP/PEAK: N/A

PAINT COND: FAIR WINDING TEMP: N/A

OTHER: PRES/VAC: *

SERVICE NOTES: Filter press, internal inspection: 10/8/10. TAP-SETTING: D

LIQUID SCREEN TEST INHIBITOR CONTENT

DATE ACID (N/N) IFT DIELECTRIC COLOR Spec-Gravity VISUAL / SEDIMENT DATE RESULTS (% BY WEIGHT)

11/08/10 0.04 36.4 55 1.5 0.876 CLEAR/ND 11/08/10 0.32

05/17/08 0.03 36.0 50 1.50 0.880 CLEAR/ND 09/20/94 0.35

05/27/06 0.03 36.2 46 1.50 0.880 CLEAR/ND 08/09/93 0.35

05/08/04 0.04 35.3 38 1.50 0.890 CLEAR/ND

05/03/03 0.05 36.2 42 1.50 0.880 CLEAR/ND

(çOMMENTS: Acceptable: All screen test categories are Acceptable at this time. Retest One COMMENTS: Acceptable.

ear.

DISSOLVED GAS-IN-OIL / GAS CHROMATOGRAPHY EXPRESSED IN PPM

HYDROGEN

DATE

:11/02/10 05/17/08 05/27/06 05/08/04 05/03/03

OXYGEN

10072 27891

CARBON

METHANE MONOXIDE

3 109

NITROGEN

48711 59678 60233 60122 59423

1 25854 0 29706 0 26975

CARBON

DIOXIDE

0 22 401 0 7

ETHANE ETHYLENE ACETYLENE

0 7

58 1842 49 1111

2 45 1545 0 Il COMMENTS: All gases are within normal limits. Recommended retest time: ONE YEAR

0 11 0 10

TOTAL

COMBUST TOTAL-GAS

119 59392 29 87999 71 88000 60 90999 58 88001

COMMENTS:

Acceptable.

DATE

11/08/10 05/17/08 05/27/06 05/08/04 05/03/03

PPM

MOISTURE CONTENT IPPr PCB IN PARTS / MILLION LIQUID POWER FACTOR %

NOTES:

100° C COMMENTS:

Acceptable.

*Recess exists to install missing pressure/vacuum gauge & N2 gas filler valve.

250 C

0.074 0.046 0.082 0.306 0.202

1.982 2.899 5.136 6.000

FURAN ANALYSIS—PARTS / BILLION

E 5H2F 2FOL 2FAL 2ACF 5N12F TOTAL

COMMENTS: NotTested. I © 2004. Trmoform,r To,tine & Reom,o. mo.

TRANSFORMER TESTING_& REPAIRS, INC. ®

COMPANY: VA REHABILITATION

CITY, STATE: WHITE CITY, OR

SUBSTATION: NEAR BLDG #236-D

OTHER:

DATE RESULTS (% BY WEIGHT)

ll/08/lO 0.53 05/08/04 0.56

05/03/O3 0.59

!.;o8/os/o2 0.53 ‘04/13/02 0.43 COMMENTS: Acceptable.

TOTAL

COMBUST TOTAL-GAS

71 63570 9 74248

26 99000 16 92502 6 96252

LABORATORY SERVICES FIELD REPAIRS & MAINTENANCE * PCB SERVICES * HOT OIL RECONDITION 1N:

P0 BOX 2219, SUISUN CITY, CA94585-5219 PHONE: (7flT ‘1 q398 TAl. (7fl7)A7I..c:(:c:)

DIVISION: SOUTH OREGON WHITE CITY ID# 0810845

REGION: TAG# 6

LOCATION: OUTDOORS/GROUND UNIT: )(J’f4J D

EQUIPMENT NAMEPLATE DATA

MFG: STANDARD PRIMARY: 12000 DELTA GALLONS: 227

SERIAL#: P1D1704 SECONDARY: 208Y/120 FLUIDTYPE: OIL

KVA: 500 CLASS/IMPED.: OA 5.76 COOLING: AIR

PHASE/CYCLE: 3/60 RATED TEMP: 65°C HV BUSHINGS: SIDE IN-CABINET

EQUIP. TYPE: TRANSFORMER DATE OF MFG: LV BUSHINGS: SIDE IN-CABINET

ANNUAL INSPECTION & GAUGE SETTINGS AS OF: 10/22/10

HV BUSHINGS: CLEAN LV BUSHINGS: CLEAN FLUID-LEVEL: No Gauge

LEAKS NONE FLUID-TEMP/PEAK: N/A

PAINT COND: PEELING/CHIPPED WINDING TEMP: N/A

OTHER: PRES/VAC: *

SERVICE NOTES: Filter press, internal inspection: 10/22/10. =

TAP-SETTING: D

LIQUID SCREEN TEST INHIBITOR CONTENT

DATE ACID (N/N) lET DIELECTRIC COLOR Spec-Gravity VISUAL / SEDIMENT

11/08/10 0.02 40.6 47 1.5 0.880 CLEAR/ND

05/17/08 0.02 40.6 38 2.00 0.880 CLEAR/ND

05/27/06 0.02 42.0 49 1.50 0.880 CLEAR/ND

05/08/04 0.02 40.1 41 2.00 0.880 CLEAR/ND

05/03/03 0.03 43.9 40 1.50 0.880 CLEAR/ND

COMMENTS: Acceptable: All screen test categories are Acceptable at this time. Retest One Year.

DISSOLVED GAS-IN-OIL / GAS CHROMATOGRAPHY EXPRESSED IN PPM

CARBON CARBON

DATE HYDROGEN OXYGEN NITROGEN METHANE MONOXIDE DIOXIDE ETHANE ETHYLENE ACETYLENE

11/02/10 0 12407 50612 6 61 479 0 4 0 05/17/08 0 23647 50162 0 9 430 0 0 0

?05/27/06 5 25795 72845 1 19 334 0 1 0 05/08/04 0 29585 62449 0 14 452 0 2 0 05/03/03 0 31135 64704 1 5 407 0 0 0 COMMENTS: All gases are within normal limits. Recommended retest time: ONE YEAR

MOISTURE CONTENT fPP

PPM COMMENTS:

28 Acceptable.

DATE

11/08/10 07/20/09 05/17/08 05/27/06 05/08/04

TEST DATE

PCB IN PARTS / MILLION

04/13/02 05/28/96 09/20/94

NOTES:

CONTENT CLASS DATE

*6

LIQUID POWER FACTOR %

NON-PCB

NON-PCB

NON-PCB

25°C 100° C

*Recess exists to install missing pressure/vacuum gauge & N2 gas filler valve.

11/08/10 05/17/08 0 5/2 7/06 05/08/04 05/03/03

0.034 0.007 0.036 0.080

0.03 1

*California Depart. Of Toxic Substances Control regulates PCB >5 ppm. CCR defines PCB’s as hazardous waste:

T . Division 4.5, C It. 6261.24.

- I FURAN ANALYSIS—PARTS

0.83 1 1.265 1.582 0.796

COMMENTS:

Acceptable.

/ BILLION

I

DATE

v3

© 2t04. Tm ormerTmtum & Romr,. In

II

5112F 2FOL 2FAL 2ACF 5M2F TOTAL.

0 0 23 0 0 23 0 0 9 0 0 9

COMMENTS: Relest One Year. NOT TESTED BY TTR. RESULT

MINIMALLY CHANGED FROM LAST TEST. NORMAL

;ULT FOR HEALTHY EQUIPMENT.

LABORATORY SERVICES FIELD REPAIRS & MAINTENANCE * PCB SERVICES * HOT OIL RECONDITIONIN

OTHER:

P0 BOX 2219, SUISUN CITY, cA94585-F91trHnNE: (7fl7)t’..q398 rX: (7fl7)421$

DIVISION: SOUTH OREGON WHITE CITY

REGION:

LOCATION: OUTDOORS/GROUND UNIT: XFMR H

EQUIPMENT NAMEPLATE DATA

DATE

11/02/10 05/17/08 05/2 7/06 05/08/04 05/03/03

PPM

NOTES:

*Recess exists to install missing pressure/vacuum gauge & N2 gas filler valve. Unit not adequately Anchored Seismically).

TEST DATE CONTENT CLASS DATE

NON -PCB 11/08/10

NON-PCB 05/17/08

0 5/2 7/06 05/08/04 10/04/00

OMMENTS: Not Tested.

61689 17 85249 54 93501

0 24 93500 32 93498

1.975 1.685

0.164 5.668

0.194 6.070 cc COMPANY: VA REHABILITATION

CITY, STATE: WHITE CITY, OR

SUBSTATION: XFMR H

ID# 0810845

TAG# 7

MFG: STANDARD PRIMARY: 12000 DELTA GALLONS: 166

SERIAL#: PLC0529 SECONDARY: 208Y/l20 FLUIDTYPE: OIL

KVA: 225 CLASS/IMPED.: OA 4.90 COOLING: AIR

PHASE/CYCLE: 3/60 RATED TEMP: 65°C HV BUSHINGS: SIDE IN-CABINET

EQUIP. TYPE: TRANSFORMER DATE OF MFG: LV BUSHINGS: SIDE IN-CABINET

ANNUAL INSPECTION & GAUGE SETTINGS AS OF: 10/22/10

HV BUSHINGS: CLEAN LV BUSHINGS: CLEAN FLUID-LEVEL: No Gauge

LEAKS NONE FLUID-TEMP/PEAK: N/A

PAINT COND: PEELING/CHIPPED WINDING TEMP: N/A

OTHER: PRES/VAC: *

SERVICE NOTES: Filter press, internal inspection: 10/22/10.

TAP-SETTING: D

LIQUID SCREEN TEST INHIBITOR CONTENT

DATE ACID (N/N) IFT DIELECTRIC COLOR Spec-Gravity VISUAL / SEDIMENT DATE RESULTS (% BY WEIGHT)

1 1/08/10 0.08 32.8 44 2.5 0.880 CLEAR / ND Ni 1/08/10 0.39

05/17/08 0.04 35.6 50 2.00 0.880 CLEAR/ND 10/04/00 0.47

05/27/06 0.04 35.2 49 2.00 0.880 CLEAR/ND 09/22/99 0.46

05/08/04 0.04 36.7 40 2.00 0.890 CLEAR/ND 11/19/98 0.46

05/03/03 0.06 36.0 38 2.00 0.880 CLEAR/ND 09/20/94 0.46

COMMENTS: QuUioiiahI: Acid and/or IFT test(s) indicate oxidation by-products are COMMENTS: Acceptable.

.. est One Year.

DISSOLVED GAS-IN-OIL / GAS CHROMATOGRAPHY EXPRESSED IN PPM

CARBON

HYDROGEN OXYGEN NITROGEN METHANE MONOXIDE

0 13326 47710 3 65 0 26690 58343 0 15 1 27195 65626 1 50 0 29289 63800 0 22 0 28987 64055 3 19

CARBON TOTAL

DIOXIDE ETHANE ETHYLENE ACETYLENE COMBUST TOTAL-GAS,

579 0 7 0 75 199 0 2 626 0 2 387 0 2 424 0 10

COMMENTS: All gases are within normal limits. Recommended retest time: ONE YEAR

MOISTURE CONTENT /PPT’ PCB IN PARTS / MILLION

COMMENTS:

Acceptable.

DATE

11/08/10 07/20/09 05/17/08 05/27/06 05/08/04

08/09/93 08/09/82

LIQUID POWER FACTOR %

25° C 100° C COMMENTS:

*California Depart. Of Toxic Substances Control regulates PCB >5 ppm. CCR defines PCB’s as hazardous waste:

Title 22, Division 4 - — -. Article 3, §66261.24.

0.043 0.025 0.042

Acceptable.

I

II

rr

© 2004. Tm former Tootle, & Reooiro. Inc.

FURAN ANALYSIS—PARTS I BILLION

DATE 5112F 2FOL 2FAL 2ACF 5M2F TO’IAL

LABORATORY SERVICES * FIELD REPAIRS & MAINTENANCE * PCB SERVICES * I-lOT OIL RECONDITIONING P0 BOX 2219, SUISUN CITY, CA 94585-5219 I PHONE: (707) 421-9398 I FAX: (707) 421-9662

COMPANY: VA REHABILITATION DIVISION: SOUTH OREGON WHITE CITY

CITY, STATE: WHITE CITY, OR

SUBSTATION: ON GOLF COURSE-P LOCATION: OUTDOORS/GROUND

OTHER:

EQUIPMENT NAMEPLATE DATA

REGION:

ID# 0810845

TAG# 8

UNIT: XFMR P

MFG: STANDARD PRIMARY: 12000 DELTA GALLONS: 119

SERIAL#: P1C1355 SECONDARY: 408Y/277 FLUID TYPE: OIL

KVA: 112.5 CLASS/IMPED.: OA 371 COOLING: AIR

PHASE/CYCLE: 3/60 RATED TEMP: 65°C HV BUSHINGS: SIDE IN-CABINET

EQUIP. TYPE: TRANSFORMER DATE OF MFG: LV BUSHINGS: SIDE IN-CABINET

ANNUAL INSPECTION & GAUGE SETTINGS AS OF: 10/22/10

NV BUSHINGS: DIRTY LV BUSHINGS: DIRTY FLUID-LEVEL: No Gauge

LEAKS NONE FLUID-TEMP/PEAK: N/A

PAINT COND: GOOD WINDING TEMP: N/A

OTHER: PRES/VAC: *

SERVICE NOTES: Filter press, internal inspection: 10/22/10. TAP-SETTING:

LIQUID SCREEN TEST INHIBITOR CONTENT

DATE ACID(N/N) IFT DIELECTRIC COLOR Spec-Gravity VISUAL/SEDIMENT DATE

11/08/10 0.05 35.3 51 1.5 0.880 CLEAR/ND :l 1/08/10 0.58

05/17/08 0.03 39.8 34 1.50 0.880 CLEAR/ND 04/21/0I 0.62

05/08/06 0.03 39.9 48 1.50 0.880 CLEAR/ND 1110/04/00 0.47

05/08/04 0.03 38.9 36 1.50 0.890 CLEAR/ND 09/22/99 0.44

05/03/03 0.03 41.1 36 1.50 0.880 CLEAR/ND 11/19/98 0.43

RESULTS (% BY WEIGHT)

“OMMENTS: Acceptable: All screen test categories are Acceptable at this time. Retest One COMMENTS: Acceptable.

, (ear.

DISSOLVED GAS-IN-OIL / GAS CHROMATOGRAPHY EXPRESSED IN PPM

CARBON CARBON

DATE HYDROGEN OXYGEN NITROGEN METHANE MONOXIDE DIOXIDE ETHANE ETHYLENE ACETYLENE TOTAL-GAS

11/02/10 49 6936 50050 5 124 784 0 8 0 186 57957 05/17/08 3 24600 54498 0 24 622 0 2 0 29 79749 05/27/06 0 26781 65955 1 50 711 0 3 0 54 93501 ‘05/08/04 0 24604 57110 2 36 745 2 2 0 42 82501 05/03/03 0 27432 60103 1 21 441 0 3 0 25 88001

TOTAL

COMBUST

COMMENTS: All gases are within normal limits. Recommended retest time: ONE YEAR

MOISTURE CONTENT [PPM PCB IN

COMMENTS:DATE

11/08/10 07/20/09 05/17/08 05/27/06 05/08/04

PPM

TEST DATE

10/04/00 08/09/93

111/1 1/RS

PARTS / MILLION LIQUID POWER FACTOR %

CONTENT CLASS DATE

*7 NON-PCB 11/08/10

6 NON-PCB 04/21/01

17 NON-PCB 10/04/00

1 09/22/99 (11/19/98

*California Depart. Of Toxic Substances Control regulates PCB >5 ppm. CCR defines PCB’s as hazardous waste:

TtI r II, Article 3, 6626l.24.

NOTES:

*Recess exists to install missing pressure/vacuum gauge & N2 gas filler valve. Grounding is Corroded.

25° C

0.0 18 0.007 0.205 0.150 0.292

1000 C

0.7 14 5.400 6.380

FURAN ANALYSIS—PARTS / BILLION

DATE 5H2F 2FOL 2FAL 2ACF SM2F TOTAL

© 2004. Tmosformer Tc©i.rn & Roirs. Inc

WE I D IVIANri WEIDMANN ELECTRICAL TECHNOLOGY TEST REPORT

5305 COMMERCE SQUARE DRIVE + INDIANAPOLIS, IN + 46237 01-6975889-525330-00

3178887288+3178882577 P 1 f2

Q WtMN.WEIDMANN-DIAGNOSTICS.COM age o

Electrical Testing Serial#: PIC-1443 Mfr: STANDARD Control#: 6975889

ELECTRIC

145 TOWER DRIVE Location: BLD 231 XFMR A kV: 12 Order#: 525330 UNIT 9 Equipment: TRANSFORMER kVA: 75 Account: 2465 BURR RIDGE, IL 60527 US Compartment: MAIN(BOTTOM) Year Mfd: Received: 11/23/2016 ATTN: SCOTT DUDE Breathing: SEAL Syringe ID: 52003629 Reported: 12/08/2016 PO#: DOVA 1601 Bank: Phase: 3 Bottle ID: XFMR A Project ID: DOVA 1601 Fluid: MIN USGaI: 122 Sampled By:

Customer ID:

Lab Control Number: 6975889

Date Sampled: 11/15/2016

Order Number: 525330

Oil Temp: 22 Dissolved Gas Analysis (DGA) Hydrogen (H2) (1JLIL): <2 ASTM Methane (CH4) (pLIL): <1 D-361 25,6 Ethane (C2H6) (pUL): <1

Ethylene (C2H4) (pLIL): <1

Acetylene (C2H2) (pLJL): <1 Carbon Monoxide (CO) (pLIL): 34 Carbon Dioxide (C02) (pLIL): 545

Nitrogen (N2) (pLJL): 51419

Oxygen (02) (pLJL): 22483 Total Dissolved Gas (TDG) (pUL): 74481

Total Dissolved Combustible Gas (TDCG) (pUL): 34

Equivalent TCG (%): 0.0388 flGA DGA Keys Gas I Interpretive Method: Hydrogen within condition I limits (100 pL/L).

inostics PER IEEE C57.104-2008 Methane within condition 1 limits (120 PUL).

fr (most recent sample) Ethane within condition 1 limits (65 pL/L).

Ethylene within condition 1 limits (50 JLJL).

Acetylene within condition 1 limits (1 pLJL).

Carbon Monoxide within condition 1 limits (350 pLIL).

Carbon Dioxide within condition 1 limits (2500 pL/L).

TDCG within condition 1 limits (720 pLJL).

DGA TDCG Rate Interpretive Method: No previous sample available.

PER IEEE C57.104-2008

(two most recent sample)

DGA Cellulose (Paper) Insulation: C02/CO Ratio not applicable - at least one gas doesn’t exceed its limit.

WDS DGA Condition Code: NORMAL

WDS Recommended Action: Continue normal operation. Resample for testing within one year.

Comment:

General Oil Quality (GOQ)

ASTM D-15335’6 Moisture in Oil (mglkg): 26 ASTM D-9711 lnterfacial Tension (mNIm): 30.81 ASTM D-9741 Acid Number (mg KOH/g): 0.034 ASTM D-15001 Color Number (ASTM): L2.0 ASTM D-1524 Visual Exam. (Relative): PASS

CLR&BRIGHT

ASTM D-1524t Sediment Exam. (Relative): ND ASTM D-8771 Dielectric Breakdown (kV): 52 ASTM D-924t Power Factor c 25°C (Routine) (%): 0.098 ASTM D-40521 Density @15°C (gImL): 0.8786 STM D-266856 Oxidation Inhibitor (wt. %) 0.257

()5 1 fy ISO/lEG 17025 2005 dt d LA 6 A r dt d C At t N mb L2303 03 2 Th t t d d by b S ct dl b t ry 3 S 6 6 cl dl b I ryh d ISO St d d 17025 dl S I A I t 5

- Ii conducted by Weidrnann Loborotory other than Primary Lab, 6. Weidrnarrn Laboratory has received ISO Standard 17025 acmedrt050n toethis test. 7. Imported Sample: WEIOMANN Elechical Technology ouuepts no responsibility for these renults, eatidon status does not apply to these renuttn. 6. Imported Equipment 10. mg/kg yg/g, frg/mL, pUL = ppm, pg/I. = ppb, erN/m = dynen/cm, mmr/s = cSt

Accreetron applies to current analysis only. The anolyses, opinions or interprotatons contained in this report are bosed upon material and intormof on supplied by the client. WEIDMANN Eleobical Technology does not imply that the contents of the sample received by this laboratory ore the same as all such material in the environment Sum which the sample was taken. Our test results relate only lathe sample or samples tested. dary interpretations or opinions expressed represent the best judgment of IDMANN Electrical Technology. VdEIDMANN Elecbical Technology assumes no responsibility and makes no warranty or representation, eopressed or implied as to the cosdilon. prodsctivily or proper operaf us of any eqaipmeot or other property to, winch this report may be used or relied upon for any reason oxiralsoever. This test report shall ncr be reproduced except in full, without wnrllen appr000l at the laboratory.

A Member of the WICOR Group

WEIDMANN

Electrical Testing

145 TOWER DRIVE

UNIT 9

BURR RIDGE, IL 60527 US

ATTN: SCOTT DUDE

PO#: DOVA 1601

Project ID: DOVA 1601

ID:

Serial#: PIC-1443

Location: BLD 231 XFMR A

Equipment: TRANSFORMER

Compartment: MAIN(BOTTOM)

Breathing: SEAL

Bank: Phase: 3

Fluid: MIN USGaI: 122

Mt r: STANDARD

ELECTRIC

kV: 12 kVA: 75

Year Mf’d:

Syringe ID: 52003629

Bottle ID: XFMR A

Sampled By:

TEST REPORT

01-6975889-525330-00

Page 2 of2

Control#: 6975889

Order#: 525330

Account: 2465

Received: 11/23/2016

Reported: 12/08/2016

Particle Count >= 4 pm(c)ImL: 429 ASTM D-67865 > 6 pm(c)ImL: 35

> 10 pm(c)/mL: 8 > 14 pm(c)/mL: 3

>= 21 pm(c)/mL: 1

> 38 pm(c)/mL: 0

> 70 pm(c)/mL: 0

ISO CODE: 16/12/>=9

Diagnostics: Particle Count Normal Comment:

End of Test Report

Authorized By:

AMY TURK

REGIONAL MANAGER

QI: 1.Aealysiu is ISOIIEC 17025:2005 acmedlted, L-A-BAcmodded cethocate Number U303.03 2. This test is sonduuted by a subconbacted laboratory. 3. Subconuauted laboratory has reuetsed ISO Standard 17025 aucned,labon tar thu test. 5.

is conducted by Weid,nann Laboratory otherthaa Primary lab. 8. Wejdrnaon Laboratoryhas received ISO Standard 17025 accred,taton torthis test. 7. Imported Sample: WEII)MPrNN Eleuhiuel Technology accepts no responsibil’ty for those renal/u;

erilellear staIns does not applyto these results. 8. Imported Equipment 10. mg.tbg ,pg/g. pg/rnL, pL/L = ppm, ygiL ppb, mN/m = dynes/cm. mrrrr/s = cSt

Acae&ation applies to current analysis only. The analyses, opinions or interpretabons cantained in this report are based upon matenal and informaOcn supplied by Ore client. WEIDMAIdN Elecisinal Teotrnology does not imply that the Contents of the sample received by this laboratory are the same as all such material in the enoironment tram winch the sample was taken. Oar test results re late only lathe sample or samples tested. My interpretations or opinions expressed represent the best judgment at WFIDMANN Electrical Technology. WEIDMANN Electrical Tecirnology assumes no responsibility and makes no warranty or ropresenlation, expressed or implied onto the condition, productivity on proper operation ot any equipment or other property far which this report may be used or relied upon tar any reason wtrats000er. This test report shall not be reproduced eocept in full, without written approval ot the laboratory.

WEIDMANN ELECTRICAL TECHNOLOGY

5305 COMMERCE SQUARE DRIVE + INDIANAPOLIS, IN ÷ 46237

317 888 7288 + 317 888 2577

.WJW.WEIDMANN-DIAGNOSTICS.COM

Lab Control Number: 6975889

Date Sampled: 11/15/2016

Order Number: 525330

Oil Temp: 22

GOQ Diagnostics Moisture in Oil: Acceptable for in-service oil (35 mg/kg max).

PER IEEE C57.106-2006 Interfacial Tension: Acceptable for in-service oil (25 mN/rn mm).

(most recent sample) Acid Number: Acceptable for in-service oil (0.2 mg KOH/g max).

Color Number and Visual: Diagnostic not applicable. Diagnostic not applicable.

Dielectric Breakdown ASTM D-877: Diagnostic not applicable.

Power Factor @ 25°C (Routine): Acceptable for in-service oil (0.5% max).

Oxidation Inhibitor: Diagnostic not applicable for type 1 oil. Acceptable for in-service oil type 2 (0.09% mm).

Comment:

Furanic Compound 2-Furaldehyde (pgIL): 191 ASTM D-58375 5-Hydroxy-methyl-furaldehyde (pgIL): < 10

2-Acetylfuran (pgIL): < 10

5-Methyl-2-furaldehyde (pgIL): 71

2-Furyl alcohol (pgIL): 50

M.u+rati,sn.

3nic Compound Diagnostics (most recent sample):

gii New insulation with a high degree of mechanical strength will typically have a Degree of Polymerization (DP) of 1000-1300. “Middle Aged” paper is approximately 500 and paper with less than 250 is in its “Old Age.” Severely degraded insulation with a DP of 150 or less will have very little mechanical strength and may result in a transformer failure. The above estimations are based on a study by Chendong of GSU transformers filled with mineral oil.

Estimated Average Degree of Polymerization (DP): 637

Estimated Operating Age of the Equipment: 19.2

Ca Electrical Testing

145 TOWER DRIVE

UNIT 9

BURR RIDGE, IL 60527 US

ATTN: SCOTT DUDE

PO#: DOVA 1601

Project ID: DOVA 1601

Customer ID:

Serial#: 09J249142

Location: BLDG 252 XFMR C

Equipment: TRANSFORMER

Compartment: MAIN(BOTTOM)

Breathing: SEAL

Bank: Phase: 3

Fluid: MIN USGaI: 236

Mfr: ABB kV: 12.47 kVA: 500

Year MI d: 2009

Syringe ID: 2000753

Bottle ID: XFMR C

Sampled By:

TEST REPORT

01-6975890-525330-00

Control#: 6975890

Order#: 525330

Account: 2465

Received: 11)23)2016

Reported: 12/08/2016

Carbon Dioxide: Condition 3 Significant Indications of overheated cellulose insulation (4000 pLIL).

TDCG: Condition 2 Levels exceed normal concentrations. Fault may be oresent (720 uLIL).

DGA TDCG Rate Interpretive Method: No previous sample available.

PER IEEE C57.104-2008

(two most recent sample)

DGA Cellulose (Paper) Insulation: Normal decomposition of cellulose insulation.

General Oil Quality (GOQ)

ASTM D-15335’6

ASTM D-9711

ASTM D-9741

ASTM D1 5001

ASTM D-15241

WDS DGA Condition Code: WARNING

WDS Recommended Action: Resamole at earliest oooortunitv to establish cas aeneration rate.

(Relative):

(kV):

(gImL):

36.44

0.002

L0.5

PASS

CLR&BRIGHT

TRACE

0.007

0.883

WEIDMANN ELECTRICAL TECHNOLOGY

5305 COMMERCE SQUARE DRIVE + INDIANAPOLIS, IN + 46237

317 888 7288 + 317 888 2577

WMN.WEIDMANN-DIAGNOSTICS.COM

Lab Control Number: 6975890

Date Sampled: 11/15/2016

Order Number: 525330

Oil Temp: 23 Dissolved Gas Analysis (DGA) Hydrogen (H2) (pLIL): 28 ASTM Methane (CH4) (pLIL): 27 D-361256 Ethane (C2H6) (pLIL): 4

Ethylene (C2H4) (IJLIL): 14

Acetylene (C2H2) (1JLIL): 3 Carbon Monoxide (CO) (pLIL): 844

Carbon Dioxide (C02) (pLJL): 5672 Nitrogen (N2) (pL)L): 58034 Oxygen (02) (pLIL): 9082

Total Dissolved Gas (TDG) (pLIL): 73708 Total Dissolved Combustible Gas (TDCG) (1JLIL): 920

Equivalent TCG (%): 1.0445

DGA

rgnostics

DGA Keys Gas I Interpretive Method:

PER IEEE C57.104-2008

(most recent sample)

Hydrogen within condition 1 limits (100 iUL).

Methane within condition 1 limits (120 pLJL).

Ethane within condition 1 limits (65 pLJL).

Ethylene within condition 1 limits (50 IAJL).

Acetylene: Condition 2 Indications of arcing activity (1 pL/L).

Carbon Monoxide: Condition 3 Indications of significantly overheated cellulose insulation (570 pLIL).

Comment: DGA RESULT WAS VERIFIED BY REANALYSIS

(mg/kg):

(mNIm):

(mg KOHIg):

(ASTM):

(Relative):

Moisture in Oil

Interfacial Tension

Acid Number

Color Number

Visual Exam.

ASTM D-1524’ Sediment Exam.

ASTM D-877t Dielectric Breakdown

ASTM D-924t Power Factor 25°C (Routine)

‘TM D-40521 Density t15°C uns I Analysis is ISO/IEC 17025:2005 accredited, L-A.B Avuredited Certiticale Number 1.235303 2 This test is conducted by a subvontnacted laboratory. 3. Subcontracted laboratory has reoeived ISO Standard 17025 aooredit060n for Ibis test. 5.

mnt is conducted by Weidrnonn Laboratory other than Primary Lab 6. Weidrooen Laboratory has received ISO Standard 17025 aucreditaitan for this test. 7. Imported Sanrple. WEIDMANN Electrical Technology 000epts no responsibility for these results;

editation stotus does not apply to these results. 8. Innported Equipment 10. org/kg

, pg/n, yg/reL, pLlt_ = ppm, yg/L = ppb, erN/rn — dynes/crn, mmem/s = nSf

Pwaedmtabon applies to current analysis only The analyses, opinions or inlerprefattons contained in this report ore based upon material and infotmotion supplied by the client. WEIDMANN Eleotioal Tedmnnfogy dens not impty that the contents of the sample received by this laboratory are the same as all such matenal in the environment from which the sample was taken. Our test results relate only to the sample or somples tested. Airy interpretations er opinions eapressed represent the best judgment of IDMANN Electrical Technology. WEIDMANN Electrical Technology assumes no responsibility and makes no warranty or mepresentalion, eupressed or implied os to the condition, productivity or proper operation of any equipment or other property for edtfd. this report may be used or relied upon for any reason whatsoever. This test report shall nor be reproduced nocept in full, without written approval of the laboratomy e Electrical Testing

145 TOWER DRIVE

UNIT 9

BURR RIDGE, IL 60527 US

ATTN: SCOTT DUDE

PO#: DOVA 1601

Project ID: DOVA 1601

Customer ID:

Comment:

Serial#: 09J249142

Location: BLDG 252 XFMR C Equipment: TRANSFORMER

Compartment: MAIN(BOTTOM)

Breathing: SEAL

Bank: Phase: 3

Fluid: MIN USGaI: 236

Mfr: ABB kV: 12.47 kVA: 500

Year Mrd: 2009

Syringe ID: 2000753

Bottle ID: XFMR C

Sampled By:

TEST REPORT

01-6975890-525330-00

Page 2 012

Control#: 6975890

Order#: 525330

Account: 2465

Received: 11/2312016

Reported: 12/08/2016

Particle Count > 4 pm(c)ImL: 121 ASTM D-67865 > 6 pm(c)ImL: 19

> 10 pm(c)ImL: 4

> 14 pm(c)ImL: 1

> 21 pm(c)ImL: 0 > 38 pm(c)/mL: 0 > 70 iim(c)/mL: 0

ISO CODE: 141>=11I>=7

Diagnostics: Particle Count Normal Comment:

End of Test Report

Authorized By:

AMY TURK

REGIONAL MANAGER

Cinst I AnalysIs Is ISOIIEC t70252005 acwredried. LA-B Aonreted Ceficate Number L2303.03 2 This test is conducted by a subcontracted laboratory. 3. Subcontracted laboratory has recefoed ISO Standard 17025 accreditahon for this test 5 est is conducted by Weidrcann Laboratory other than Primary Lab. 6. Weidmann Laboratory has received ISO Standard 17025 aumeditultun forthis test. 7. Imported Saerple: WEIOMANN Electrical Technology veptunorasponsibility for these renulln;

accredllu5on status does not apply to these results. 0. Imparted Equipnrent 10. nrgltmg . ygtg, pg/meL. pIlL = ppm, ygfL = ppb, eN/rn = dynes/cnr, rnmrls oSt

Accanditahon applies to current analysis only. The analyses, opinions or interpretations contained fl thIs report are based upon material and informalion supplied by the dient. ViEIDMANN Electrical Technology does not Imply that the contents 01 tie sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results retule only lathe sample or samples tested. 0ny inlerpretasons or opinions eepressed represent lIre best judgment at WEIDMANN Electrical Technology. WEIOMANN Electrical Technology assumes no responslblllly and makes no warranty or repmnsentaton, eepressed or implied as lathe cae,lIboa, produchitoity or proper operabon 01 any equipment or other property tar which this report maybe used or relied upon tar any reason whatsoever. This test report shall cot be reproduced eacept in foil, without written approval of the laboralory

WEIDMANN ELECTRICAL TECHNOLOGY

5305 COMMERCE SQUARE DRIVE + INDIANAPOLIS, IN + 46237

317 888 7288 + 317 888 2577 tAWN.WEIDMANN-DIAGNOSTICS.COM

Lab Control Number: 6975890

Date Sampled: 11/15/2016

Order Number: 525330

Oil Temp: 23 ASTM D-26685’6 Oxidation Inhibitor (wt. %) 0.194 GOQ Diagnostics Moisture in Oil: Acceptable for in-service oil (35 mg/kg max).

PER IEEE C57.106-2006 Interlacial Tension: Acceptable for in-service oil (25 mN/m mm).

(most recent sample) Acid Number: Acceptable for in-service oil (0.2 mg KOH/g max).

Color Number and Visual: Diagnostic not applicable. Diagnostic not applicable.

Dielectric Breakdown ASTM D-877: Diagnostic not applicable.

Power Factor 25°C (Routine): Acceptable for in-service oil (0.5% max).

Oxidation Inhibitor Diagnostic not applicable for type 1 oil. Acceptable for in-service oil type 2 (0.09% mm).

Comment:

Furanic Compound 2-Furaldehyde (pgIL): 18 ASTM D-58375 5-Hydroxy-methyl-furaldehyde (pgIL): < 10

2-Acetylfuran (pgIL): < 10 5-Methyl-2-furaldehyde (pgIL): 65

2-Furyl alcohol (iJgIL): it 10

( ..nic Compound Diagnostics (most recent sample):

\ ,.d New insulation with a high degree of mechanical strength will typically have a Degree of Polymerization (DP) 011000-1300. rrMiddle Aged’ paper is approximately 500 and paper with less than 250 is in its “Old Age.” Severely degraded insulation with a DP of 150 or less will have very little mechanical strength and may result in a transformer failure. The above estimations are based on a study by Chendong of GSU transformers filled with mineral oil.

Estimated Average Degree of Polymerization (DP): 930 Estimated Operating Age of the Equipment: 1.5

Notations:

WE I DlviAN rJ WEIDMANN ELECTRICAL TECHNOLOGY

5305 COMMERCE SQUARE DRIVE + INDIANAPOLIS, IN + 46237

317 888 7288 + 317 888 2577

WN.WEIDMANN-DIAGNOSTICS.COM

.e Electrical Testing

145 TOWER DRIVE

UNIT 9

BURR RIDGE, IL 60527 US

ATTN: SCOTT DUDE

PO#: DOVA 1601

Project ID: DOVA 1601

Customer ID:

Serial#: 13JC62890001 Mfr: ABB Control#: 6975891 Location: BLDG 236AXFMRD kV: 1247 Order#: 525330

Equipment: TRANSFORMER kVA: 750 Account: 2465 Compartment: MAIN(BOTTOM) Year Mfd: 2013 Received: 11/2312016

Breathing: SEAL Syringe ID: 52004740 Reported: 12/08/2016 Bank: Phase: 3 Bottle ID: XFMR D

Fluid: FR3 IJSGaI: 341 Sampled By:

Lab Control Number: 6975891

Date Sampled: 11/15/2016

Order Number: 525330

Oil Temp: 22 Dissolved Gas Analysis (DGA) Hydrogen (H2) (pL)L): 20 ASTM Methane (CH4) (pLIL): 7 D-361256 Ethane(C2H6)(pLIL): 119

Ethylene (C2H4) (pLIL): 2 Acetylene (C2H2) (pUL): <1

Carbon Monoxide (CO) (IJUL): 64

Carbon Dioxide (C02) (IJUL): 739

Nitrogen (N2) (pLIL): 56982

Oxygen (02) (pLIL): <500

Total Dissolved Gas (TDG) (pLIL): 58391 Total Dissolved Combustible Gas (TDCG) (IJLIL): 212

Equivalent TCG (%): 0.1523

Hydrogen within normal limits (112 iUL)

Methane within normal limits (20 IJLJL) Ethane within normal limits (232 pLJL)

Ethylene within normal limits (18 pLJL)

Acetylene within normal limits (1 pUL)

Carbon Monoxide within normal limits (161 pLJL)

Carbon Dioxide within normal limits (5000 pLJL)

DGA Rate Interpretive Method No history, gas generation rate not applicable.

PER IEEE C57.155-2014

(two most recent sample)

DGA Cellulose (Paper) Insulation: CO2ICO Ratio not applicable - at least one gas doesn’t exceed its limit.

General Oil Quality (GOQ)

ASTM D-153356 Moisture in Oil (mglkg): 30 ASTM D-9711 Interfacial Tension (mNIm): 12.53 ASTM D-9741 Acid Number (mg KOHIg): 0.043 ASTM D-15001 Color Number (ASTM): L0.5 ASTM D-15241 Visual Exam. (Relative): PASS

CLR&BRIGHT

ASTM D-15241 Sediment Exam. (Relative): TRACE ASTM D-8771 Dielectric Breakdown (kV): 43 ASTM D-9241 Power Factor @ 25°C (Routine) (%): 0.216 ASTM D40521 Density t15°C (gImL): 0.9211 cnn: 1. Malysis is ISOIIEC 17025:2005 accredited. L-AB Accredited Ceritcete Number L2303.03 2 This test is conducted bye nvbconbataed laboratory. 3 Subcontracted laboratory ban received ISO Standard 17025 acmeditaion for thin test 5 ,ent is condonted by Weidmerrn Laboratory other than Primary Lab, 6. Weidnrerrn Laboratory has received ISO Standard t 7025 accraditason for thin test. 7. Imported Sample: WEIDIiIANN ElecOicel Technology avcapln no responsibility for these results, editabon stabs does not applyto these results. 8. Imparted Equipment 10. my/ky . yylg, yg.lreL, pLJL = ppm, yg/L = ppb, nrNlm dyson/cm, mm’ls = cSt

Aedlta6ao applies to crarrent analysis only The analyses, opinions or inlerprelatons contained in this report are based upon matenal and information supplied by the olient VdEIOMANN Eleclaicat Technoloyy does not imply that the contents of the sanrple received by this laboratory are the same as all such mate5l in the environment from which the sample was taken. Our test resufs relafe only to the sample or samples tested My interpretations nr opinions espressed represent the best judgment of 8IDMANN Etectrical Technology. WEIDMAJ’1N Elecbical Technology assumes nc responsibility and makes no warranty or representation, eopressed or implied as lathe ceedition, productivity or proper operaben at any equipment or ether property for wtddr this report may be used or relied upon for any reason whatsoever. This test report shell net be reproduced eacept in bill, without written approval of the laboratory.

TEST REPORT

01-6975891-525330-00

DGA

gnostics

DGA Keys Gas I Interpretive Method:

PER IEEE C57.155-2014

(most recent sample)

Comment:

WDS DGA Condition Code:

WDS Recommended Action:

NORMAL

Continue normal ooeration. Resamole for testiria within one year.

GOQ Diagnostics

‘R IEEE C57.147-2008

Moisture in Oil: Acceptable for in-service oil (400 mg/kg max).

Interfacial Tension: Diagnostic not applicable.

. Electrical Testing

145 TOWER DRIVE

UNIT

BURR RIDGE, IL 60527 US

ATTN: SCOTT DUDE

PO#: DOVA 1601

Project ID: DOVA 1601

Customer ID:

Serial#: 13JC62890001 Mfr: ABB Control#: 6975891

Location: BLDG 236AXFMR D kV: 12.47 Order#: 525330

9 Equipment: TRANSFORMER kVA: 750 Account: 2465

Compartment: MAIN(BOTTOM) YearMf’d: 2013 Received: 11/23/2016

Breathing: SEAL Syringe ID: 52004740 Reported: 12/08/2016

Bank: Phase: 3 Bottle ID: XFMR 0

Fluid: FR3 IJSGaI: 341 Sampled By:

Lab Control Number: 6975891

Date Sampled: 11/15/2016

Order Number: 525330

Oil Temp: 22

(most recent sample) Acid Number: Acceptable for in-service oil (0.3 mg KOH/g max).

Color Number and Visual: Color acceptable for in-service oil (1.5 max). Diagnostic not applicable.

Dielectric Breakdown ASTM D-877: Diagnostic not applicable.

Power Factor t 25°C (Routine): Acceptable for in-service oil (3% max).

Comment:

Furanic Compound 2-Furaldehyde (jigIL): 11

ASTM D-58375 5-Hydroxy-methyl-furaldehyde (pgIL): < 10

2-Acetylfuran (pgIL): < 10

5-Methyl-2-furaldehyde (JgIL): 65

2-Furyl alcohol (iJgIL) 56 Furanic Compound Diagnostics (most recent sample):

New insulation with a high degree of mechanical strength will typically have a Degree of Polymerization (DP) of 1000-1 300. “Middle Aged” paper is approximately 500 and paper with less than 250 is in its ‘Old Age.” Severely degraded insulation with a DP of 150 or less will have very little mechanical strength and may result in a transformer failure. The above estimations are based on a study by Chendong of GSU transformers filled with mineral oil.

/ , Estimated Average Degree of Polymerization (DP): 991

(JJ Estimated Operating Age of the Equipment: <1.0 \ rations:

comment:

Particle Count >= 4 pm(c)ImL: 1451

ASTM D-67865 > 6 pm(c)ImL: 472

> 10 pm(c)/mL: 117

> 14 pm(c)ImL: 39

>= 21 pm(c)ImL: 8

> 38 pm(c)ImL: 0

> 70 pm(c)/mL: 0

ISO CODE: 18/16/12

Diagnostics: Particle count diagnostic only applicable to main tank of mineral oil transformers.

Comment:

End of Test Report

Qs:

1.Ms4s is ISEc l75OOhacreedted. L-A.BAwrredited cewhoate Number L2303.03 2. This test is conducted by a subvonfracted laboratory. 3. Subcontracted laboratory has reoeived ISO Standard 17025 acoreditahon for this test. 5.

-. is conducted by Weidmairn Laboiatmyotheeffiorr Primary l.ab. 6. Weidrnann Laboratory has received ISO Standard 17025 acceeditahoo for this test. 7. lorported Saeepte: WEIDMANN Elecsicul Teohrology accepts no responsibility for these results:

edtahon stable does not orpIyto these results. 8. reported Eqoipnrent 10. rogltrg , p01g. rglmL, plJL ppm, pg/I. = ppb. mnN/m = dynesloar, mmls = cSt

Accredt.tlcn apptes to crerentanulysls only. The analyses, opinions or interpretahons contained in this report are based opon material ard informafon supplied by the client. WEIOMANN Eiecthcai Technology does not imply that the contents of Ore sample recelned by this Iaborstonj are the seine as at Such material in the enoiranment from which the sample was taken. Our test results relate only to the sample or samples tested. My interpretations or opinions eopressed represent the best judgment of WEIDMANN EIsaldcal Technology. ‘IVEIOMANN Electrical Technology assumes no responsibility and makes no warranty or representation, eapressed or implied as to the candihon, productivity or proper operaitoo stacy equipmeot or other properly for which this repoit hwy be used or rated opos for any reason wtratsaener. This test report shall not be reproduced nosept in hrll, without written approval 01 the laboratory.

WEIDMANN ELECTRICAL TECHNOLOGY

5305 COMMERCE SQUARE DRIVE + INDIANAPOLIS, IN + 46237

317 888 7288 + 317 888 2577

\M1.WEIDMANN-DIAGNOSTICS.COM

TEST REPORT

01-6975891-525330-00

Authorized By:

AMY TURK

REGIONAL MANAGER

W E I WEIDMANN ELECTRICAL TECHNOLOGY TEST REPORT

5305 COMMERCE SQUARE DRIVE + INDIANAPOLIS, IN + 46237 01-6975892-525330-00

3178887288+3178882577 Pagel of2

\W.WEIDMANN-DIAGNOSTICS.COM

Electrical Testing Serial#: PNJ-0658 Mt r: BALTEAU Control#: 6975892 145 TOWER DRIVE Location: BLDG 221 AND 222 kV: 12 Order#: 525330

XFMR E

UNIT 9 Equipment: TRANSFORMER kVA: 300 Account: 2465 BURR RIDGE, IL 60527 US Compartment: MAIN(BOTTOM) Year Mf’d: Received: 11/23/2016 ATTN: SCOTT DUDE Breathing: SEAL Syringe ID: 52003188 Reported: 12/08/2016 PO#: DOVA 1601 Bank: Phase: 3 Bottle ID: XFMR E Project ID: DOVA 1601 Fluid: MIN IJSGaI: 140 Sampled By:

Customer ID:

Lab Control Number: 6975892

Date Sampled: 11/15/2016

Order Number: 525330

Oil Temp: 30 Dissolved Gas Analysis (DGA) Hydrogen (H2) (pLIL): 7 ASTM Methane (CH4) (pUL): 7 D36125,6 Ethane (C2H6) (pLIL): 2

Ethylene (C2H4) (pLIL): 48 Acetylene (C2H2) (pLIL): <1

Carbon Monoxide (CO) (jiLIL): 427 Carbon Dioxide (C02) (pUL): 5673

Nitrogen (N2) (pUL): 55429

Oxygen (02) (pUL): 16007

Total Dissolved Gas (TDG) (pUL): 77600 Total Dissolved Combustible Gas (TDCG) (pUL): 491

Equivalent TCG (%): 0.5038

DGA Keys Gas I Interpretive Method: Hydrogen within condition 1 limits (100 pLiL), ( nostics PER IEEE C57.104-2008 Methane within condition 1 limits (120 pL1L).

(most recent sample) Ethane within condition 1 limits (65 pLIL).

Ethylene within condition 1 limits (50 JLJL).

Acetylene within condition 1 limits (1 pLJL).

Carbon Monoxide: Condition 2 Indications of overheated cellulose insulation (350 pLIL).

Carbon Dioxide: Condition 3 Significant Indications of overheated cellulose insulation (4000 pLIL).

TDCG within condition 1 limits (720 pLJL).

DGA TDCG Rate Interpretive Method: No previous sample available.

PER IEEE C57.104-2008

(two most recent sample

DGA Cellulose (Paper) Insulation: CO2/CO Ratio not applicable - at least one gas doesn’t exceed its limit.

WDS DGA Condition Code: CAUTION

WDS Recommended ActionS Resample at earliest opportunity to establish gas generation rate.

Comment:

General Oil Quality (GOQ)

ASTM D-153358 Moisture in Oil (mglkg): 10 ASTM D.971t Interfacial Tension…

This is the start of the file's text. The full file is on GovTribe.