OM Manual - manual-us-ipex-endura - Edited.pdf

PDF 761 KB Posted

Attached to
S222--Grease Trap Cleaning and Maintenance Grand Junction VA Medical Center
Solicitation number
36C25926Q0252
Issued by

About this file

This is a technical manual for IPEX Endura® Grease Management Plumbing Systems, specifically Volume VI covering Hydromechanical Grease Interceptors (HGI). The manual provides comprehensive guidance for installers, designers, and engineers on the proper installation, operation, and maintenance of Endura grease interceptor products.

The Endura product line includes HGI units ranging from 7 to 150 GPM, manufactured from corrosion-resistant engineered thermoplastics (polypropylene for 7-50 GPM models and polyethylene for 75-150 GPM XL models). All units are certified to performance standards ASME A112.14.3, PDI G-101, or CSA B481 and carry NSF, UPC, and other regulatory certifications. Key design features include quick-access latching systems, removable internal baffles for easy cleaning, integrated flow control devices with air intake mechanisms, and the ability to support various installation configurations (in-floor, on-floor, semi-recessed, or below-grade). The XL models (75-150 GPM) support remote pump-out configurations and optional monitoring systems with high liquid level probes and grease depth sensors. Maximum grease capacities range from 31.95 pounds (7 GPM) to 1,097 pounds (150 GPM). The manual emphasizes critical maintenance requirements, including regular cleaning based on grease accumulation rates, proper use of flow control devices, and adherence to kitchen best management practices to prevent system failures and fines. The manufacturer provides a Limited Lifetime Warranty covering defects in materials and workmanship, excludes installation and repair labor costs, and requires professional installation by licensed plumbers with strict compliance to written instructions and local codes.

View the file

Other files

File Type Posted
36C25926Q0252 0001.docx DOCX document
OM Manual - GT2701 - 3Bay Sink 3rd Floor Kitchen.pdf PDF
36C25926Q0252.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

IPEX Endura® Grease Management I

VOLUME VI:

ENDURA®

GREASE

MANAGEMENT

PLUMBING

SYSTEMS

MECHANICAL

TECHNICAL MANUAL SERIES

H Y D R O M E C H A N I C A L G R E A S E I N T E R C E P T O R S ( H G I )

7 to 50 GPM Models

XL 75 to 150 GPM Models

XL Sampling Well

Solids Interceptors

Rethinking Grease Interception

II IPEX Endura® Grease Management

Endura® Grease Management

Plumbing Systems

Mechanical Technical Manual Series, Vol. VI

© 2021 by IPEX. All rights reserved. No part of this book may be used or reproduced in any manner whatsoever without prior written permission. For information contact: IPEX Inc., Marketing, 1425 North Service Road East, Unit 3, Oakville, Ontario, Canada, L6H 1A7

The information contained here within is based on current information and product design at the time of publication and is subject to change without notification. IPEX does not guarantee or warranty the accuracy, suitability for particular applications, or results to be obtained therefrom.

IPEX Endura® Grease Management III

ABOUT IPEX

At IPEX, we have been manufacturing non-metallic pipe and fittings since 1951. We formulate our own compounds and maintain strict quality control during production. Our products are made available for customers thanks to a network of regional stocking locations throughout North America. We offer a wide variety of systems including complete lines of piping, fittings, valves and custom-fabricated items.

More importantly, we are committed to meeting our customers’ needs. As a leader in the plastic piping industry, IPEX continually develops new products, modernizes manufacturing facilities and acquires innovative process technology. In addition, our staff take pride in their work, making available to customers their extensive thermoplastic knowledge and field experience. IPEX personnel are committed to improving the safety, reliability and performance of thermoplastic materials. We are involved in several standards committees and are members of and/or comply with the organizations listed on this page.

For specific details about any IPEX product, contact our customer service department.

IV IPEX Endura® Grease Management

Endura® Grease Management products are an effective, efficient and trusted component of our injection molded product family and have demonstrated exceptional performance over the decades.

Endura products are multi-patented and built to withstand the toughest environments, providing the flexibility of in-floor, on-floor, and semi-recessed applications. We have been instrumental in changing the traditional practices regarding the installation of grease management solutions; plastic alternatives to metal interceptors are now substantially accepted Nationwide as the new standard for grease management in commercial foodservice applications.

Endura products are thermoplastic Hydromechanical grease interceptor (HGI) designed to provide exceptional grease management solutions for plumbing and food service professionals. HGIs are manufactured in an ISO 9001 and 14001 registered facility. Sizes range from 7 through to 150 GPM units constructed of either Polypropylene (PP) or Polyethylene (PE) compound.

This manual provides installers, designers and engineers with guidance to help ensure the proper usage of Endura products. Readers are encouraged to consult with the Manufacturer or local representative for any additional clarification before using Endura to ensure a successful installation.

At Endura, we think the best way to protect municipalities and our waterways is to put proactive interception practices into place. It’s about more than providing better technology and materials—it’s about rethinking the entire process. From installation, to maintenance, to durability, we provide a complete solution that is both innovative and proactive.

If you need additional copies of any instructions, or if you have questions about the safe and proper installation of

Endura products, contact Endura Toll Free (Canada: 1-800-461-1771) or (USA: 1-888-461-5307).

For the most up-to-date information on Endura products, email: tech-support@endurainterceptor.com

IPEX Endura® Grease Management V

As a plumbing appurtenance your Endura® grease interceptor MUST be isolated from the drainage system in the event that final drain testing or other system pressure testing is required.

DO NOT under any circumstances subject your interceptor to pressure test (AIR, WATER OR OTHERWISE). This action will result in damage to the unit, invalidate your warranty and could cause serious bodily injury.

NOTICE

DO NOT PRESSURE TEST. RISK OF SERIOUS INJURY

WARNINGWARNING

GREASE INTERCEPTORS ARE HAZARDOUS

ENVIRONMENTS AND MUST NEVER BE LEFT

UNCOVERED AND UNATTENDED, EVEN DURING

MAINTENANCE.

• All access covers MUST be fully and completely secured

• All required bolts MUST at all times be in place and well tightened

• Missing bolts MUST be reported to management and replaced immediately

• Covers MUST meet the required load rating for the application (see the Technical Information section)

• Do NOT use alternate covers

If installed under a sink, make sure there is at least 15” clearance (21” for 50 GPM model) to remove the baffles for cleaning and maintenance. If this is not practical, semi-recessing the tank is an option (Note: 25 GPM Lo- PRO is mean for on floor installation only).

NOTICE

NOTICE

Failure to maintain the grease Interceptor can result in heavy fines from the local authority having jurisdiction and/or flooding as a result of the system backing up

If there is an obstruction in the line, make sure the plugs are installed in the sinks or the recommended upstream ball valve is closed before accessing the waste piping.

This is the safety alert symbol. It is used to alert you to potential personal injury hazards.

Obey all safety messages that follow this symbol to avoid personal injury or death.

The use of the word “NOTE” signifies special instructions which are important but are not related to hazards.

CAUTION

“CAUTION” Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.

NOTICE

“NOTICE” Indicates a hazardous situation which, if not avoided, may result in system failure and / or property damage.

SAFETY ALERTS

Engineered thermoplastics are safe inert materials that do not pose any significant safety or environmental hazards during handling or installation. However, improper installation or use can result in personal injury and/or property damage. It is important to be aware of and to recognize safety alert messages as they appear in this manual. The types of safety alert messages are described below.

ENDURA® SAFETY ALERTS

WARNING

“WARNING” Indicates a hazardous situation which, if not avoided, could result in severe injury or death.

1 IPEX Endura® Grease Management

G E

N E

R A

L

IN

F O

R M

A T

IO

N

OVERVIEW

The grease management industry has developed significantly in the past decade with the continuous advancement of product design, progression of performance standards, and the emergence of HGIs as a mainstream, progressive solution for the future.

Traditionally, the term “Grease Trap” has been used in the industry. In recent years this term is progressively disappearing from vocabulary and technical references based on an industry-wide recognition that the term “trap” would suggest the presence of a water seal integrally located within the interceptor, leading to potential confusion of the function of a grease interceptor. This practice ceased many years ago, modern interceptors being designed to be installed in conjunction with external water seal traps as a standard part of the system.

In addition to this clarification, with publication of the 2006 UPC plumbing code, three generic types of grease interceptors were introduced and have since become the industry standard for designating the type of interceptor being considered.

GREASE INTERCEPTOR (GI):

“A plumbing appurtenance or appliance that is installed in a sanitary drainage system to intercept nonpetroleum fats, oil, and grease (FOG) from a wastewater discharge.”

Specific characteristics further classify GI’s into one of the three types:

HYDROMECHANICAL GREASE

INTERCEPTOR (HGI):

An HGI is sized by flow rate (GPM) and qualified separation/retention efficiency, validated against National performance Standards. An HGI incorporates a defined means of flow control, acts to entrain air to influent, includes interior baffling, or barriers in combination or separately, working to promote hydromechanical separation. HGI’s may be installed inside the facility they serve or outside the building, above or below grade.

GRAVITY GREASE INTERCEPTOR (GGI):

A GGI is characterized by volume, minimum 20 minute retention time, baffle(s), not less than two compartments, a total volume of not less than 350 gallons, and gravity separation. If not recognized by an official body, a GGI will be designed by a registered professional engineer. GGI’s are generally installed outside the building they serve and buried below grade.

GREASE REMOVAL DEVICE (GRD):

A GRD is a hydromechanical grease interceptor that mechanically removes nonpetroleum FOG from the separation chamber, the control of which is either automatic or manually initiated and involves maintaining a liquefied state of intercepted FOG by heating. GRD’s are installed inside the facility they serve.

SECTION ONE: GENERAL INFORMATION

IPEX Endura® Grease Management 2

E

N E

R A

L

IN

F O

R M

A T

IO

N

Selection of the appropriate size HGI is critical to the performance of the system. HGIs are sized based on flow rate and their grease carrying capacity. Flow control devices must be installed per plumbing code to ensure the waterflow does not exceed the certified flow rate of the HGI. HGI’s are performance tested to National Standards (such as PDI G-101, ASME A112.14.3, CSA B481) offering the end user confidence that the minimum level of efficiency will be achieved.

All models of the Endura grease interceptors employ a similar process to effectively separate grease. An uncontrolled discharge passing through a flow control device (A) which is designed with an integral orifice to manage the flow of discharge into the interceptor, before or at the inlet of the interceptor. Orifice openings are calibrated for each certified unit based on the results of the performance testing during certification. The fluid experiences a Venturi effect as a result of passing through the constricted section of the fitting. After passing the orifice (A), the fluid experiences a drop in pressure due to the Venturi effect which draws air into the inlet flow via the air intake (B), promoting laminar flow after the point of restriction. The inlet baffle (C) slows the velocity of the influent and further promotes the establishment of laminar flow. Next, the integral ramp (D) will direct the wastewater stream upwards to promote the rise of FOG into the retention area of the tank (E). The diameter of grease globules formed, differences in specific gravity and viscosity of the fluids, and the temperature of the grease and water helps the grease efficiently rise to the surface.

Treated effluent within discharge FOG concentration limits will exit (F) into the municipal network while separated grease will be retained in the grease retention area. As the volume of grease stored reaches the capacity of the unit, the lid can be manually removed for regular maintenance and cleaning.

HOW DOES IT WORK?

By definition, an HGI is designed to use managed flow, air entrainment, and specifically designed features to provide an enhanced level of separation efficiency, removing non petroleum FOG (Fats, Oil and Grease) from a transition flow of wastewater generated by commercial foodservice activities (Restaurants, cafeterias, institutional kitchens , sandwich shops and coffee houses, for example).

Example of an Endura® grease interceptor 25 GPM unit, Flow Control Device (FCD)

A B C

D

E

F

Air Intake

Patented Baffle Design

3 IPEX Endura® Grease Management

E

N E

R A

L

IN

F O

R M

A T

IO

N

DURABILITY

• Fewer installations and replacements result in lower lifetime costs & less landfill waste

• Injection molded in engineered thermoplastics, ENDURA® GREASE INTERCEPTORS will not corrode, chip, or peel even under the most hostile / corrosive conditions

• Endura® units are guaranteed to last, provided with a Limited Lifetime Warranty.

FULLY CERTIFIED – Endura and Endura XL HGIs are certified to PDI G-101, CSA B481 or ASME A112.14.3 model codes.

LOWER INSTALLATION COSTS – in addition to lower material costs than traditional grease interceptor materials, Endura units can significantly reduce labor and transportation costs on a typical installation.

EASY MAINTENANCE – easy access with convenient cover latches, removable internal components and a smooth internal surface.

ENGINEERED MATERIALS – Endura products are manufactured using engineered thermoplastics that will not corrode, chip or peel. Durability provides consistent operation – no compromise of effectiveness due to deterioration of key parts, ensuring lower maintenance costs. The Endura units are immune to damage from naturally corrosive soil conditions.

LIGHTWEIGHT – compared to traditional grease interceptors of equivalent capacities, Endura offers a significantly lighter alternative.

SIZE RANGE – offered from 7 GPM models through to

150 GPM.

INSIDE OR OUTSIDE BUILDING –Endura units can be used for indoor or outdoor installations, in-floor or on-floor, as well as below grade. Depending on the application, modular riser extensions may simplify installation.

REMOTE PUMP XL MODELS - Endura XL models are designed to support the installation of a remote pump-out configuration.

COMPLETE LINE - Endura offers a complete line of grease interceptors and accessories to satisfy most application. This includes solids interceptors, sample wells, and extensions.

GREEN BY DESIGN

• Lightweight but durable Endura grease interceptor units enable smaller carbon footprints and low-emissions transport

• Injection and rotationally molded thermoplastic requires less energy to produce than metal grease interceptors

• Endura Interceptors are manufactured using up to 100% recycled* recompounded material

*Endura utilizes up to 100% of recompounded material during the manufacturing process.

FEATURES AND BENEFITS

49 IPEX Endura® Grease Management

S Y

S T

E M

O P

E R

A T

IO

N

M

A

IN

T E

N A

N C

E A

N D

R E

P A

IR

S

KITCHEN BEST MANAGEMENT PRACTICES

RECOMMENDED BEST MANAGEMENT PRACTICES (BMP’s) for FOOD SERVICE ESTABLISHMENTS* Owners and operators of food service establishments are encouraged to implement the following BMP’s to help improve the quality of wastewater discharged to drains and sewers. Please check with your municipal plumbing code or wastewater department policies to determine conformance criteria for the proper handling of wastewater.

1. Put signs in the kitchen, particularly over the sink, telling staff what can and what cannot go down the drains.

2. Do not pour oil, grease or large amounts of oily liquids such as gravies, sauces or salad dressings down the drain.

Collect this material in a secure waste-grease container for disposal at approved locations.

3. Scrape off greasy trays and pans into a waste-grease container before putting them into a sink or dishwasher.

4. Scrape food waste from pots, pans and dishes into a garbage bin before putting them into a sink or dishwasher.

5. Put a fine basket strainer in sink drains to catch solids as well as dishwasher discharge to catch items such as rice and corn.

6. Install a special-purpose solids interceptor upstream of the grease interceptor to capture solid particles.

Solids take up space and interfere with oil and grease separation. Also, food-waste solids that collect in a grease interceptor will decay and cause odor problems.

7. Do not pour coffee grounds or tea leaves down the drain.

8. Develop and implement a plan to reduce, reuse and recycle waste

• Use a recycling service for your used cooking oil. Used cooking oil can be recycled into useful products such as soap, animal feed and biodiesel products.

• Separate out food waste for delivery to a centralized composting site.

9. Cleaning grease off kitchen exhaust systems. Grease that builds up on exhaust hoods, filters, ducts and fans is usually removed and cleaned to the bare metal by a certified service company. The following cleaning procedure is recommended:

• Use hand scrapers to remove as much grease as possible from the exhaust system. Collect and store the grease in a separate container labeled “waste grease.”

• Wash the exhaust system with a caustic cleaning solution, collecting the water in a bucket.

• Neutralize the wash water in the bucket by adding a weak acid such as lemon juice, citric acid or a little vinegar.

• Skim off any grease floating in the bucket and store it in the waste-grease container.

• Pour the neutralized water from the bucket into a drain that is connected to a grease interceptor. Be careful not to pour the solids at the bottom of the bucket into the drain.

Store the solids in the waste-grease container.

* Greater Vancouver Regional District (GVRD), “Best Management Practices & Code Practices for Waste Water Management at Food Sector Establishments”, Nov. 2001, pp 8, 10.

CLEANING & MAINTENANCE

All grease interceptors must be cleaned regularly to maintain efficient operation. Endura® recommends a licensed and locally approved service provider manage the regular removal, cleaning and disposal of the fats, oil and grease that is captured in your interceptor.

For point of use units (7 GPM – 50 GPM) that will be maintained by Food Service Establishment FSE staff, make sure training is provided in:

• proper function, operation and maintenance of grease interceptors outlined in this manual

• proper storage, handling and disposal of wastes

• proper separation and storage of materials

• proper use and handling of cleaning aids

• proper housekeeping

• local code requirements and Best Management Practices for food sector facilities.

CAUTION

Failure to maintain the grease interceptor can result in back-ups, flooding and property damage.

SECTION FIVE: SYSTEM OPERATION, MAINTENANCE AND REPAIRS

IPEX Endura® Grease Management 50

Y

S T

E M

O P

E R

A T

IO

N

M

A

IN

T E

N A

N C

E A

N D

R E

P A

IR

S

MAINTENANCE FREQUENCY

The frequency of grease removal is dependent upon a variety of factors; the type of food served, the capacity of the grease interceptor and the concentration of grease in the water. Increasing the frequency of cleaning will reduce odor problems associated with grease interceptors and improve retention efficiency.

For tools to help determine the optimal maintenance frequency, visit enduracalculator.com.

Once an optimal grease removal interval has been established for a specific installation, regular cleaning at this interval is necessary to maintain the rated efficiency of the interceptor. Some municipalities require cleaning logs be maintained and kept for a minimum of 2 years.

Unit Part Number US Gallons Per Minute

GPM (L/Sec)

Maximum Grease Capacity lb (kg)

Maximum Grease Height in.

Endura® 7 3907A02 7 (0.44) 31.95 (14.49) 5

Endura 10 3910A02 10 (0.63) 38.07 (17.27) 7

Endura 15 3915A02 15 (0.94) 35.14 (15.94) 3

Endura 20 3920A02 20 (1.26) 76.40 (34.65) 5

Endura 25 LO-PRO 3925A02LO 25 LO (1.6) 62.59 (28.39) 3

Endura 25 3925XTA02 (2”)

3925XTA03 (3”)

25 (1.6) 72.55 (32.91)

73.01 (33.12)

Endura 35 3935A03 (3”)

3935A04 (4”)

35 (2.2) 138.50 (62.82) 5

Endura 50 3950A03 (3”)

3950A04 (4”)

50 (3.2) 122.07 (55.37) 6

Endura 75 4075A04

4075A04M

75 (4.74) 559.00 (253.56) 12.25

Endura 100 40100A04

40100A04M

100 (6.3) 1058.00 (479.90) 17.5

Endura 150 40150A04

40150A04M

150 (9.5) 1097.00 (497.59) 18

MEASURING GREASE LEVELS USING A DIP TUBE

A commercially available core sampler may be used to measure the grease depth of the unit. The depth found may be used to determine maintenance frequency when compared to Maximum Grease Height.

The maximum depth of grease allowed to accumulate prior to servicing shall not exceed max rated capacity per Table below.

ENDURA XL MONITORING SYSTEM

The Endura XL Monitoring System is available for installation into grease interceptors 75, 100, and 150 gpm. The monitor has a high liquid level probe to alert the user of potential backups and a grease sensor that can alarm when grease depth reaches a pre-determined level in the tank.

DanAnderson Rectangle

51 IPEX Endura® Grease Management

Y

S T

E M

O P

E R

A T

IO

N

M

A

IN

T E

N A

N C

E A

N D

R E

P A

IR

S

3. REMOVE COVER

Open latches to remove cover, ensure the seal recessed in the underside of the cover remains in place.

4. PUMPING AND CLEANING

All solids, grease, and water must be removed at every cleaning.

5. BAFFLES

Remove all internal baffles and wash with low pressure warm water.

Replace when done.

6. REFILL INTERCEPTOR

Re-insert baffles and refill interceptor with water to prepare for operation.

7. SECURE COVER

Secure cover and fasten.

MAINTENANCE PROCEDURES 7-50 GPM

1. SAFETY FIRST!

It is recommended that protective gloves, eyewear and a mask are worn during maintenance activities.

2. ACCESSIBILITY

It is the responsibility of the restaurant operator to maintain safe, clear and unobstructed access to the interceptor at all times.

CAUTION

If there is an obstruction in the line, make sure the sinks are plugged or, if equipped, the upstream ball valve is closed before accessing the waste piping.

Ensure adequate room for removal of baffles while allowing room for piping connections and inspections

55 IPEX Endura® Grease Management

F R

E Q

U E

N T

LY

A

S K

E D

Q U

E S

T

IO

N

A

D

T R

O U

B

LE

S H

O O

T

IN

G

DO ENDURA® XL TANKS NEED TO BE

DIRECTLY VENTED?

Unless specifically mandated by local code or bylaw, Endura® XL tanks DO NOT require direct venting. Venting is required on the downstream drain like most plumbing appliances and fixtures.

DO I NEED TO INSTALL A CLEAN OUT BEFORE

OR AFTER AN INTERCEPTOR?

Most plumbing codes require an upstream and downstream cleanout immediately before and after the interceptor.

DO I HAVE TO INSTALL THE FLOW CONTROL

DEVICE?

The Flow Control is essential to the performance of the interceptor. It must be installed as indicated. Without it, the interceptor does not meet the requirements of the applicable standards.

MY JURISDICTION REQUIRES EFFLUENT

SAMPLING VIA A DOWNSTREAM ACCESS.

WHAT DO I DO?

For those jurisdictions that require the capability to sample, Endura XL incorporates a sampling port within the outlet assembly. This is accessed by the removal of the air balance/sample port cap allowing water quality samples to be taken for analysis. Some AHJ’s may require a separate downstream sampling point. The Endura sampling well can provide a flexible solution for these applications.

WHAT FIXTURES SHOULD BE CONNECTED

TO THE INTERCEPTOR?

A grease interceptor should never receive sanitary wastewater discharge. Wastewater discharge to a grease interceptor will be from foodservice activities only. The requirements for appliances and fixtures that must and must not be connected to a grease interceptor is typically defined by your local plumbing codes and or jurisdictional by-laws.

HOW OFTEN SHOULD AN INTERCEPTOR BE

CLEANED?

Cleaning frequency depends on several factors. We recommend using the maintenance interval calculator at enduracalculator.com to help anticipate cleaning frequency.

HOW MUCH WILL IT COST TO MAINTAIN MY

ENDURA XL INSTALLATION?

Endura XL units are significantly more compact (less internal volume) than their equivalent GGI counterparts. Pumping is typically charged by the volume of gallons removed, so the ongoing maintenance will be proportionally less as well.

Rates will vary significantly by region and by contractor.

Always use a licensed or approved contractor to maintain your interceptor.

CAN I INSTALL MORE THAN ONE ENDURA

XL UNIT IF MY JURISDICTION NEEDS A

MINIMUM CAPACITY BY CODE?

Depending on your jurisdiction, Endura XL may be installed in parallel and series installations. Consult local requirements.

I HEARD THAT PLASTIC TANKS CAN FLOAT

IN HIGH WATER TABLE AREAS, PARTICULARLY

WHEN PUMPED OUT FOR CLEANING.

IS THIS TRUE?

Yes it is, however Endura® XL is specifically designed to address this challenge. The Endura XL tanks are narrower at the top than the bottom and feature corrugations along the sides. The broad base provides stability and substantial resistance to being forced upward by water or freeze-thaw action. These features anchor the tank in the ground once backfilled. For areas of particular concern, an 8” concrete slab can be poured around the base to introduce further resistance.

SECTION SIX: FREQUENTLY ASKED QUESTIONS AND TROUBLESHOOTING

IPEX Endura® Grease Management 56

F R

E Q

U E

N T

LY

A

S K

E D

Q U

E S

T

IO

A

D

T R

O U

B

LE

S H

O O

T

IN

G

Troubleshooting

Symptoms Cause Corrective Actions

Strong pungent odor • Cover not replaced and/or properly secured

• Cover seal missing or damaged

• Insufficient or incorrect venting

• Insufficient cleaning frequency

• Secure cover fully - check that there is no dirt/ debris in the threaded insert

• Replace appropriate seal

• Verify installation is made per manufacturer’s in structions and local plumbing code

• Reduce interval between cleaning – 6 to 8 weeks is typical for extended capacity, but each installation is different

Sink or drain has backed up with water

• Interceptor maintenance is overdue

• Accumulation of grease/debris between kitchen and interceptor

• The flow control orifice is blocked

• The flow control and grease trap is improperly sized

• The grease trap is full of solids and/or grease

• The grease trap close to, at or beyond its capacity of solids and/or grease, clean and service grease interceptor

• Seek emergency plumbing assistance to remove restriction/blockage

• Isolate drain, access flow control and clear blockage

• Close the ball valve or plug the sink then remove the obstruction via the flow control access lid

• Replace with a properly sized grease interceptor

• Increase cleaning frequency or consider the addition of a solids interceptor upstream

I think I have missing components

• Parts have been removed or lost during prior servicing

• Check exploded drawing in the installation guide to confirm the parts that are supposed to make up your interceptor model

• If missing parts are identified, order replacements

Excessive solids or grease accumulation

• The grease interceptor is full/requires cleaning

• Food waste on pots, plates & utensils are not being scraped into the garbage & is being flushed down the sink. This food waste accumulates on the bottom of the tank

• Grease interceptor has not been in operation for a period of time

• Increase cleaning frequency

• Provide Good Kitchen Practice training for food service staff

• Install a solids interceptor upstream of the interceptor.

• Use screens on floor drains and sinks

• Contact a licensed service professional to re-commission your interceptor

My indirect connection leaks all over the floor when I empty the sink(s)

• Incorrectly installed/located flow control device

• Move flow control device to a location upstream of the indirect connection

The XL inlet baffle is not working/is broken

• Damaged/broken parts • For technical assistance email tech-support@endurainterceptor.com

I can’t get the bolts to thread back in.

• Bolt cross threaded

• Grit / debris in threaded insert

• Examine and clear and debris in threaded insert.

Use light lubricating oil as applicable

• If thread is damaged, replace insert

57 IPEX Endura® Grease Management

P

E C

IF

IC

A T

IO

N

S

S P

E C

IF

IC

A T

IO

N

S

SECTION SEVEN: SPECIFICATIONS

7-50 GPM ENDURA® INTERCEPTORS

MATERIAL

• The body, lid and internal components shall be made of corrosion resistant, high impact PP compound that can withstand operational temperatures up to 220 degree F

CONNECTIONS

• Shall be no-hub mechanical joint PP end connectors, IPS spigot PP end connectors or female NPT threaded PP end connectors

DESIGN FEATURES

• Lid shall utilize a quick access latching system and be rated to support 300lbs

• Internal features shall be removable or allow access for easy cleaning

• Risers shall allow for below grade installations of 15 – 50 GPM interceptors to be extended to grade, up to a maximum of 18”

• A flow control device with integrated air intake shall be provided with the interceptor for external flow control type installations

EFFICIENCY RATING

• All interceptors shall be rated to an average efficiency per ASME A112.14.3

• The maximum grease capacity of each grease interceptor shall be provided per ASME A112.14.3

MARKINGS

• All interceptors shall be marked with the manufacturers name or trademark, model number, rated flow(s), “inlet” and “outlet”, nominal inlet size, applicable standard designations, access cover load classification, efficiency at the minimum grease capacity per ASME A112.14.3, and flow control model number for external flow control type installations

STANDARDS AND LISTING

• All interceptors shall be certified to ASME A112.14.3, PDI-G101, or CSA B481.1, and have UPC listing

75-150 GPM ENDURA XL INTERCEPTORS

MATERIAL

• The body, lid and internal components shall be made of corrosion resistant thermoplastics that can withstand operational temperatures up to 160 degree F.

• The interceptor body shall be constructed of high density polyethylene

CONNECTIONS

• Shall be hub mechanical joint PP end connectors or female NPT threaded PP end connectors

DESIGN FEATURES

• Lids shall be Special duty traffic rated Type ‘S’ to support 10,000lbs or Medium duty (light vehicular traffic) rated Type ‘M’ to support 2,000lbs, per CSA B481.0 or Cast iron ASTM A48 30B lids meeting H20 loading standards

• Internal features shall be removable or allow access for easy cleaning

• Risers shall allow for below grade installations of 75 – 150 GPM interceptors to be extended to grade, up to a maximum of 72”

• A flow control device with integrated air intake shall be provided with the interceptor for external flow control type installations

EFFICIENCY RATING

• All interceptors shall be rated to an average efficiency per ASME A112.14.3

• The maximum grease capacity of each grease interceptor shall be provided per ASME A112.14.3

MARKINGS

• All interceptors shall be marked with the manufacturers name or trademark, model number, rated flow(s), “inlet” and “outlet”, nominal inlet size, applicable standard designations, access cover load classification, efficiency at the minimum grease capacity per ASME A112.14.3, and flow control model number for external flow control type installations

STANDARDS AND LISTING

• All interceptors shall be certified to ASME A112.14.3, PDI-G101, or CSA B481.1, and have UPC listing

DanAnderson Line

IPEX Endura® Grease Management 58

W A

R R

A N

T Y

WARRANTY AND LIMITATION OF LIABILITY REG/INFO

Limited Lifetime Warranty

Effective March 16, 2020, Canplas® Industries Ltd. (“Manufacturer”) guarantees to the original purchaser (“Purchaser”) or to a subsequent owner of the Endura® Grease Management Products manufactured by the Manufacturer (“Products”) that Manufacturer will, at its discretion, replace, refund or repair any such Products that were purchased after the effective date and that are defective in materials or workmanship, subject to the limitations detailed herein.

THIS EXPRESS WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES, WHETHER EXPRESSED, IMPLIED OR STATUTORY, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. THIS EXPRESS WARRANTY SPECIFICALLY EXCLUDES INSTALLATION AND/OR REPAIR COSTS, INCLUDING LABOR.

The Products have a Limited Lifetime Warranty (the “Warranty”) against defects in workmanship and materials from the date of purchase of the Products for the lifetime of the plumbing system in which the Products are originally installed. Within ten (10) days of discovery of an alleged defect, the Purchaser or the subsequent owner must notify the Manufacturer and promptly return the Product believed to be defective to the Manufacturer facility located at 31 Patterson Road, Barrie, Ontario, Canada L4N 3V9 with freight prepaid. At Manufacturers’ sole discretion, an on-site inspection may be arranged.

Warranty and Liability Limitations

This Warranty applies provided that: (i) within 90 days from the date of purchase, Manufacturer has received from the Purchaser or from the subsequent owner a proof of purchase of the Product and a duly completed Warranty Registration Card. The Warranty Registration Card is reproduced below and can also be found included with the Products or on Manufacturer’s website; (ii) the Products have been installed and used in strict compliance with Manufacturer’s written instructions as published and updated from time to time by Manufacturer, with the state of the art industry standards and practices, with all local codes and standards as well as with all applicable laws and regulations; (iii) the Products have passed all of the installation tests referred to in the Manufacturer’s written instructions as published and updated from time to time by Manufacturer; (iv) the Products were installed by a licensed plumber and (v) the Products were not modified, repaired or altered without Manufacturer’s authorization or do not show any evidence of disassembly or tampering.

ANY LIABILITY IN RESPECT TO THE PRODUCTS IS STRICTLY LIMITED TO THE REFUND, REPAIR OR REPLACEMENT OF THE PRODUCT AND THERE SHALL NOT, IN ANY EVENT, BE ANY LIABILITY FOR ANY LABOR CHARGES (INCLUDING THOSE REQUIRED FOR FIELD REPAIR, REPLACEMENT OR REMOVAL OF THE PRODUCTS) OR DAMAGES INCLUDING, WITHOUT LIMITATION, DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, SPECIAL OR PUNITIVE DAMAGES.

In addition, and without limiting the generality of the foregoing, there shall be no Warranty or Liability for damages or defects relating to or resulting from:

• misuse (e.g. by running a pressure test) or abuse;

• the Products having been used in more than one installation, installed in improper applications or in a place susceptible to damages from traffic exceeding intended loads per lid load rating specified in Manufacturer’s written instructions as published and updated from time to time by Manufacturer;

• normal wear and tear, discoloration, UV degradation, extreme temperature or pH levels, freeze-related damage;

• acts of nature (e.g. fire, hail, hurricane, etc.), incidents (e.g. building settling, structural failures of walls or foundations) or accidents;

• improper or faulty installation, storage, handling or maintenance;

• failure to properly care for and maintain the Products or the plumbing system where the Products are installed;

• failure to abide by Manufacturer’s warnings, safety instructions, or other precautionary guidelines;

• any other cause outside the control of Manufacturer.

Manufacturer reserves the right to discontinue or modify any of its Products at its absolute discretion, and shall not be liable as a result of such discontinuation or modification. Manufacturer shall not be liable in the event that replacement Products vary in color in comparison to the original Product or as a result of normal weathering.

SECTION EIGHT: WARRANTY

NOTICE

This warranty is offered by the Manufacturer. No claim should be placed upon the Installer or Service Company if properly installed and serviced.

61 IPEX Endura® Grease Management

Endura® is a registered trademark

SALES AND CUSTOMER SERVICE

IPEX INC.

Toll free: (866) 473-9462 ipexna.com

About the IPEX Group of Companies

As leading suppliers of thermoplastic piping systems, the IPEX

Group of Companies provides our customers with some of the largest and most comprehensive product lines. All IPEX products are backed by more than 50 years of experience. With state-of-the-art manufacturing facilities and distribution centres across North America, we have earned our reputation for product innovation, quality, end-user focus and performance.

Markets served by the IPEX Group of Companies include:

• Electrical systems

• Telecommunications and utility piping systems

• Industrial process piping systems

• Municipal pressure and gravity piping systems

• Plumbing and mechanical piping systems

• Electrofusion systems for gas and water

• Industrial, plumbing and electrical cements

• Irrigation systems

• PVC, CPVC, PP, PVDF, PE, ABS, and PEX pipe and fittings

This literature is published in good faith and is believed to be reliable.

However, it does not represent and/or warrant in any manner the information and suggestions contained in this brochure. Data presented is the result of laboratory tests and field experience.

A policy of ongoing product improvement is maintained. This may result in modifications of features and/or specifications without notice.

MNMEEDIP220316U ©2022 IPEX