This document is an Amendment (0001) to a Request for Quote (RFQ) for Annual Boiler Maintenance at the Eastern Colorado Healthcare System (ECHCS). The solicitation is a 100% small business set-aside for NAICS code 238220, seeking a firm-fixed price contract for boiler maintenance with a base year and four option years. The Department of Veterans Affairs, Veterans Health Administration, Network Contracting Office 19 is seeking a contractor to perform maintenance on boilers located at the Rocky Mountain Regional VA Medical Center in Aurora, Colorado.
Key details include a site visit scheduled for November 6, 2025, at 10:00 AM MT, with the quote response deadline extended to November 13, 2025, at 14:00 MT. The scope of work involves comprehensive boiler maintenance, including testing and potential replacement of eight relief valves with specific pressure requirements (135 and 140 PSI), and adherence to National Board Inspection Code standards. Vendors must submit questions by November 7, 2025, at 08:00 MT via email to the contract specialists, and must follow strict communication guidelines to remain eligible for award.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| P09_SOW_Annual Boiler Maint_with contracting 11.13.2025.doc | DOC document | |
| 36C25926Q0011 0002.docx | DOCX document | |
| 36C25926Q0011 0003.docx | DOCX document | |
| P09_SOW_Annual Boiler Maint_with contracting 10.24.doc | DOC document | |
| VHA Directive 1810.pdf | ||
| Past Performance Questionnaire.docx | DOCX document | |
| P09_SOW_Annual Boiler Maint_with contracting 10.06.doc | DOC document | |
| 36C25926Q0011.docx | DOCX document | |
| S02 SAM Wage Determination.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Amendment to a Previous Combined Solicitation
Amendment to a Previous Combined Solicitation
| SUBJECT* |
| ANNUAL BOILER Maintenance Base Plus 4 Option Years for ECHCS |
GENERAL INFORMATION
| CONTRACTING OFFICE’S ZIP CODE* |
| 80111 |
| SOLICITATION NUMBER* |
| 36C25926Q0011 |
| RESPONSE DATE/TIME/ZONE |
| 11-13-2025 14:00 MOUNTAIN TIME, DENVER, USA |
| ARCHIVE |
| 15 DAYS AFTER THE RESPONSE DATE |
| RECOVERY ACT FUNDS |
| N |
| SET-ASIDE |
| SBA |
| PRODUCT SERVICE CODE* |
| J045 |
| NAICS CODE* |
| 238220 |
| CONTRACTING OFFICE ADDRESS |
| Department of Veterans Affairs |
Network Contracting Office
NCO 19
6162 South Willow Drive, Suite 300 Greenwood Village CO 80111
POINT OF CONTACT*
Contract Specialist Natasha Holland natasha.holland@va.gov 303.712.5753
PLACE OF PERFORMANCE
| ADDRESS |
| Department of Veteran Affairs |
Eastern Colorado Healthcare System
Rocky Mountain Regional VA Medical Center
1700 N. Wheeling Street
Aurora CO
| POSTAL CODE |
| 80045 |
| COUNTRY |
| USA |
ADDITIONAL INFORMATION
AGENCY’S URL
URL DESCRIPTION
AGENCY CONTACT’S EMAIL ADDRESS
EMAIL DESCRIPTION
DESCRIPTION
The purpose of this Amendment 0001 to Request for quote (RFQ) 36C25926Q0011 is to provide for a site visit, answer questions, post updated Statement of Work (SOW) and extend the due date.
The deadline for quotes is hereby extended to November 13, 2025, at 14:00 MT.
The date for the Site Visit will be November 06, 2025 at 10:00 AM MT. The site visit meeting will begin outside the Patriot Brew of the main building at 1700 N. Wheeling Street Aurora, CO 80045. If your company is planning to attend please confirm via email to natasha.holland@va.gov and thaddeus.gray@va.gov with the name and phone number before Nov 03, 2025 at 15:00 MT.
The deadline for all questions is extended due to site visit. Questions are due 08:00 AM MT Nov 07, 2025. They must be submitted by email to natasha.holland@va.gov and thaddeus.gray@va.gov. Participants must not ask questions of onsite VA employees. All questions answered outside of this requirement of this solicitation may disqualify a vendor from award. Any questions submitted after this deadline will not be answered.
Vendor Questions and Answers Amendment 0001 Q1. Could you please clarify what is meant by “Service Hours for H Stamp Welding, Testing, and Certification” in the SOW page 1? Our understanding is that this refers to the ASME certification for heating boiler manufacturers, which is typically not a requirement for service companies. Can you confirm if this interpretation is correct?
A1. This interpretation is correct. It is a requirement for working on the boiler if welding needs to be done.
Q2. Could you provide details on the relief valves to be replaced? Specifically:
How many relief valves are required?
A2. Eight (8) total (2 valves are required each boiler per VHA Boiler Safety Device Testing Manual). The valves will be tested and certified if they pass. If they do not pass, they will need to be replaced.
Q3. What are the set pressures for each valve?
A3. 135 pounds per square inch (PSI) and 140 PSI Q4. What are their capacities?
A4. At 135 PSI the capacity is 19,834 pounds (lbs.)/hr.) at approximately 85 percent of total boiler requirement. At 40 psi the Capacity is at 25,848 lbs./hr. at approximately 110 percent of total boiler requirement.
Q5. What would be more for repairs of the unit that would be covered under unscheduled repair. What do we need to specifically supply for that objective?
A5. Repairs due to unexpected failures would constitute unscheduled repairs Q6. The SOW references “Current issue of the National Board Inspection Code, Part RB”. Part RB has not been used in the NBIC for many years. The current NBIC section addressing inspections is Part 2. Please clarify.
A6. Update the RB to Part 2.
Q7. The SOW refers to an unscheduled emergency repairs section, please provide additional clarification since we are not located in the area to attend emergencies calls A7. Maintenance should be scheduled but repairs due to unexpected failures would constitute unscheduled repairs. This will be a not to exceed item to cover any unplanned maintenance that needs to be completed as seen in the unscheduled CLINS. Offerors just need to confirm that they understand that there might be times additional unplanned maintenance is involved and that those repairs will not exceed the contracted limit.
See attached document: P09_SOW_Annual Boiler Maint_with contracting 10.24.
| *= Required Field |
| Amendment to a Previous Combined Solicitation |
Page 1 of