This document appears to be a set of technical drawings and specifications for the replacement of MCC Panel BF118 and the Automatic Transfer Switch (ATS) at the Oklahoma City VA Health Care System. The key details are:
The project involves replacing the existing MCC panel BF118 and the existing ATS-6 with a new 600A, 480Y/277V, 3-phase, 4-wire motor control center (EMCC-1) and a new 600A, 480Y/277V, 4-pole ATS-6 with isolation bypass. New conduit, conductors, and supporting equipment will be installed. The work will be done in phases to maintain operations, with a temporary 400A panel used during the transition. Existing branch circuit loads will be de-energized, disconnected, and reconnected to the new EMCC-1. This project is part of VA solicitation number 36C25924R0103 issued by the Department of Veterans Affairs - Veterans Integrated Service Network 19.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| round two questions.pdf | ||
| 36C25924R0103 0003.docx | DOCX document | |
| 36C25924R0103 0002.docx | DOCX document | |
| 36C25924R0103 0001.docx | DOCX document | |
| 635-21-118_100 CD Specifications.pdf | ||
| S22- 852.219-75 LOS Certification.docx | DOCX document | |
| S02-3-10-2021 Past Performance Questionnaire_Blank_Fillable PDF.pdf | ||
| 36C25924R0103_1.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
U.S. DEPARTMENT OF VETERANS AFFAIRS
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. CA02295 EXP. 06/30/2025
ENGR REG. NO. CA7127 EXP. 06/30/2025
ELECTRICAL ENGINEER
SPUR DESIGN
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
/1
/2
:2 :2
P
M
COVER SHEET
CAB 1 OF 9BKM
100% CONSTRUCTION DOCUMENTS
REPLACE MCC PANEL BF118
VA PROJECT NUMBER: 635-23-118
REPLACE MCC PANEL BF118
03/18/2024
635-23-118
OKLAHOMA CITY VAHCS
921 NE 13TH STREET
OKLAHOMA CITY, OK 73104
OKLAHOMA CITY VAHCS
921 NE 13TH STREET
OKLAHOMA CITY, OK 73104
100% CONSTRUCTION DOCUMENTS
GI000
SPUR #: 2093.05
SHEET INDEX
SEQUENCE NUMBER SHEET NAME
[01] GENERAL
1 GI000 COVER SHEET
2 GI001 GENERAL INFORMATION
ELECTRICAL
3 E-000 ELECTRICAL SYMBOLS & ABBREVIATIONS
4 E-100 ELECTRICAL REFERENCE PLAN - BASEMENT LEVEL
5 ED101 ELECTRICAL POWER DEMOLITION PLAN
6 EP101 ELECTRICAL POWER FLOOR PLAN
7 E-501 ELECTRICAL SCHEDULES & DETAILS
8 E-601 ELECTRICAL ONE-LINE DIAGRAM - TEMPORARY & DEMOLITION CONFIGURATION
9 E-602 ELECTRICAL ONE-LINE DIAGRAM - NEW CONFIGURATION
TOTAL SHEETS: 9
LOCATION
PLAN
AREA
PLAN
N N
NE 13TH ST
N K
E
LL
E Y
A V
E
N L
IN
D
S A
Y A
V E
NE 16TH ST
NE 14TH ST
NE 15TH ST
NE 13TH ST
NE 10TH ST
N L
IN
C
O
LN
A V
E
N L
O T
T
IE
A V
E
NE 16TH ST
N K
E
LL
E Y
A V
E
PROJECT
LOCATION
No. REVISION DESCRIPTION DATE
ABBREVIATIONS CODES STANDARDS AND EXECUTIVE ORDERS
4' -0
M
A X
4' -0
M
A X
2' -1
0" M
A X
2' -3
M
IN
1'-6" MIN
1. GENERAL CONTRACTOR TO PROVIDE METAL SUPPORT
BLOCKING FOR ALL WALL MOUNTED ACCESSORIES,
FIXTURES, AND EQUIPMENT.
2. PROVIDE ADA SUPPORT BRACKETS PLACED AT ALL OPEN
COUNTERTOPS @ 36"-48" MAX ON CENTER.
3. SPECIFIED MAXIMUMS ARE MEASURED FROM AFTER
FINISHED FLOOR TO THE OPERABLE PART OF THE FIXTURE.
4. FIXTURES SHOWN ARE REPRESENTATIONAL ONLY. NOT ALL
FIXTURES MAY BE USED. REFER TO SPECIFICATIONS FOR
FIXTURE TYPES USED IN THIS PROJECT.
5. FIXTURES MAY OVERLAP WAINSCOT. WHERE APPLICABLE,
BACKING TO BE PROVIDED AS SHIM FOR FLUSH
APPLICATION. SHIM TO MATCH SCHEDULED WALL FINISH.
6" MAX
9" M
IN
SHOWER
VA TOILET ROOM
TURNING RADIUS
DRINKING
FOUNTAIN
PAPER TOWEL
DISPENSER
SANITARY
NAPKIN
DISPENSER
4' -0
"M A
X
WASTE
RECEPTACLE
LAVATORY
WITH MIRROR
ON CENTER
WALL
4' -0
M
A X
SOAP
DISPENSER
2' -1
0" M
A X
T O
B .O
. R E
F
LE
C T
IV
E
S U
R F
A C
E
3' -4
"M A
X
17 MIN
2' -3
M
IN
3' -0
M
A X
1'-6" MIN
WALL
2' -9
3' -0
3' -2
4' -0
2'-0" MIN
8" MIN
WALL
LAVATORY
WITH APRON
1' -5
M
A X
1'-6" MIN
URINAL
WALL
1'-5" - 1'-7" (AMBULATORY)
1'-4" - 1'-6" (WHEELCHAIR)
CLEAR FLOOR
5'-6"
CLEAR FLOOR
6'-0"
3'-0" MIN
2' -9
3' -0
1'-0" MIN
3'-6" MIN 1'-0"MAX
4'-6" MIN
1' -5
'-7
1' -6
M
IN
A N
S I I
C C
A
7.
1)
1' -3
M
IN
A D
A /A
B A
2' -9
3' -0
WALL
WALL
4' -0
M
A X
WALL HOOK
7' -0
CLOCK
WALL
FINISHED FLOOR
FIRE EXTINGUISHER
CABINET
WEIGHT > 40LBS
FIRE EXTINGUISHER
CABINET
WEIGHT < 40LBS
4' -0
"M A
X
4' -0
M
A X
TOILET SEAT
COVER
DISPENSER
BABY
CHANGING
STATION
CLEAR FLOOR SPACE
@ WATER CLOSET
5'-6"
2'-6"
4' -0
2'-6"
4' -0
HANDRAILS AND
BUMPER GUARDS
FIXTURE MOUNTING HEIGHTS AND CLEARANCES
18" MIN
M
IN
FRONT APPROACH,
PULL SIDE
36" MIN
M
IN
HINGE APPROACH,
PULL SIDE
HINGE APPROACH,
PULL SIDE
*12" MIN48
M
IN
FRONT APPROACH,
PUSH SIDE
M
IN
HINGE APPROACH,
PUSH SIDE
22" MIN 24" MIN
*4 8"
M
IN
LATCH APPROACH,
PULL SIDE
24" MIN*4
2"
M
IN
LATCH APPROACH,
PUSH SIDE
*IF BOTH CLOSER
AND LATCH ARE
PROVIDED
*54" MIN IF CLOSER
IS PROVIDED
*48" IF CLOSER IS
PROVIDED
FRONT APPROACH,
PUSH SIDE
M
IN
42" MIN
DOOR AND FIXTURE CLEARANCES
MATERIALS LEGEND
PURPOSE: THE PUBLIC BUILDINGS AMENDMENT ACT OF 1988, PUBLIC LAW (PUB. L.) 100-678 REQUIRES FEDERAL AGENCIES TO FOLLOW NATIONAL RECOGNIZED "MODEL" BUILDING CODES. THE FEDERAL PARTICIPATION IN THE DEVELOPMENT AND USE OF VOLUNTARY STANDARDS, OFFICE OF MANAGEMENT AND BUDGET (OMB) CIRCULAR A-119, REQUIRES ALL EXECUTIVE AGENCIES TO RELY ON VOLUNTARY STANDARDS, BOTH DOMESTIC AND INTERNATIONAL, WHENEVER FEASIBLE, AND TO PARTICIPATE IN
VOLUNTARY STANDARD BODIES.
GENERAL: VA HAS ADOPTED THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS AS A MINIMUM FOR ALL PROJECTS PERFORMED IN THE MODERNIZATION, ALTERATION, ADDITION, OR IMPROVEMENT OF ITS REAL PROPERTY AND THE CONSTRUCTION OF NEW STRUCTURES. VA DESIGN MANUALS AND MASTER SPECIFICATIONS SPECIFY OTHER CODES AND STANDARDS THAT VA FOLLOWS ON ITS PROJECTS. REFERENCE RELEVANT ADDENDA FOR EACH OF THE ADOPTED CODES AND STANDARDS:
• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL
INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).
• 2024 INTERNATIONAL BUILDING CODE (IBC) (ONLY WHEN SPECIFICALLY REFERENCED IN VA DESIGN DOCUMENTS, SEE NOTES BELOW)
• 2024 INTERNATIONAL EXISTING BUILDING CODE (IEBC) (IF APPLICABLE)
• 2024 NFPA 101 LIFE SAFETY CODE (SEE NOTES BELOW)
• 2024 NATIONAL FIRE CODES (NFPA)
• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.
• 2023 VA SEISMIC DESIGN REQUIREMENTS, H-18-8
• 2024 INTERNATIONAL MECHANICAL CODE
• 2023 NATIONAL ELECTRICAL CODE (NEC), NFPA 70
• 2024 INTERNATIONAL PLUMBING CODE (IPC)
• 2019 SAFETY CODE FOR ELEVATORS AND ESCALATORS, AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME) A 17.1.
• 2022 ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS INCLUDING VA SUPPLEMENT, VA BARRIER FREE DESIGN STANDARD (PG-18-13)
• 2022 ANSI ICC A117.1 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
• 2022 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE AND COMMENTARY, AMERICAN CONCRETE INSTITUTE AND COMMENTARY (ACI 318-19)
• 2023 STEEL CONSTRUCTION MANUAL (16TH EDITION), AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
• ENERGY POLICY ACT OF 2005 (EPACT)
• 2007 DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL, COMMERCIAL AND MULTI-FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND
NEW LOW-RISE RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434 AND 435.
• 2006 FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM OF UNDERSTANDING (MOU)
• 2018 EXECUTIVE ORDER 13834: EFFICIENT FEDERAL OPERATIONS
• 2021 THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL REQUIREMENTS SECTION 010000 OF THE VA MASTER CONSTRUCTION
SPECIFICATION.
• 2022 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE STANDARD 62.1
• 2022 SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE STANDARD 15
• 2023 PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL
LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES. HOWEVER, LOCAL AUTHORITIES SHOULD BE NOTIFIED ABOUT PLANNED PROJECTS AND GIVEN OPPORTUNITY TO REVIEW DRAWINGS PROVIDED THAT VA DOES NOT PAY FOR REVIEW OR INSPECTION FEES.
NOTES:
1. NFPA 101 PRIMARILY ADDRESSES LIFE SAFETY AND FIRE PROTECTION FEATURES WHILE THE IBC ADDRESSES A WIDE RANGE OF CONSIDERATIONS, INCLUDING, BUT
NOT LIMITED TO, STRUCTURAL STRENGTH, SEISMIC STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION, AND ENERGY CONSERVATION. VA BUILDINGS MUST MEET THE REQUIREMENTS OF NFPA 101 AND DOCUMENTS REFERENCED BY NFPA 101 IN ORDER TO COMPLY WITH THE ACCREDITATION REQUIREMENTS OF THE JOINT COMMISSION. THEREFORE, DESIGNS SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF NFPA 101 AND DOCUMENTS REFERENCED THEREIN.
DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE ADDRESSED ABOVE IN THIS PROGRAM GUIDE. FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES
EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT).
2. CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY SYSTEM WIDE.
ASHRAE 90.1 - 2019 EDITION
BUILDING LOCATION: OKLAHOMA CITY, OK
CLIMATE ZONE (TABLE ANNEX 1-1): ZONE 3A
INTERIOR DESIGN CONDITIONS:
THE INTERIOR DESIGN TEMPERATURES FOR HEATING AND COOLING AS DEPICTED IN THE PROJECT DESIGN CONDITIONS SCHEDULE IN THE MECHANICAL CONTROL DRAWINGS SHALL BE THE MAXIMUM
AND MINIMUM VALUES FOR THE ASSOCIATED TEMPERATURE CONTROL ZONES.
BUILDING ENVELOPE REQUIREMENTS (5.5 )
BUILDING ENVELOPE REQUIREMENTS FOR CLIMATE ZONE 3 (A,B,C)
ROOFS REQUIRED DESIGNED
INSULATION: R-25 c.i. EXISTING
METAL BUILDINGS: R-10 + R-19 FC EXISTING
ATTIC AND OTHER: R-38 EXISTING
WALLS, ABOVE GRADE
MASS: R-7.6 c.i. EXISTING METAL BUILDING: R-0 + R-9.8 c.i. EXISTING STEEL-FRAMED: R-13 + R-5 c.i. EXISTING
WOOD-FRAMED AND OTHER: R-13 EXISTING
WALL, BELOW GRADE
BELOW-GRADE WALL: NR EXISTING
FLOORS
MASS: R-10 c.i. EXISTING
STEEL-FRAMED: R-30 EXISTING
WOOD-FRAMED AND OTHER: R-30 EXISTING
SLAB-ON-GRADE FLOORS
UNHEATED SLABS: NR EXISTING
HEATED SLABS: R-15 for 24 in. EXISTING
OPAQUE DOORS
SWINGING: U-0.370 EXISTING
NONSWINGING: U-0.310 EXISTING
FENESTRATION (TABLE 5.5-4):
VERTICAL FENESTRATION, U-FACTOR
FIXED: U-0.42 EXISTING
OPERABLE: U-0.54 EXISTING
ENTRANCE DOOR: U-0.68 EXISTING
DEFINITIONS
c.i = CONTINUOUS INSULATION Ls = LINEAR SYSTEM
NR = NO (INSULATION) REQUIREMENT
ENERGY REQUIREMENTS
N
1. DRAWINGS ARE PART OF A COMPLETE DOCUMENTS SET. CONTRACTOR SHALL CONFIRM
ALL ITEMS REQUIRED BASED UPON THE OVERALL DESIGN INTENT OF THE ENTIRE
DOCUMENT SET.
2. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, PRIOR TO BEGINNING ANY WORK,
TO CONFIRM THE ACCURACY OF THE DRAWINGS AND REPORT ANY DISCREPANCIES TO
THE ARCHITECT. DO NOT SCALE THE DRAWINGS. FIELD VERIFY ALL DIMENSIONS AND
EXISTING STRUCTURAL CONDITIONS.
3. ALL AREAS NOT INVOLVED IN THE SCOPE OF WORK FOR THIS PROJECT SHALL BE KEPT
CLEAN AND FREE OF OBSTRUCTIONS AT ALL TIMES.
4. ERECT BARRICADES AND WARNING SIGNS TO DIVERT AND WARN PASSERS-BY OF THE
CONSTRUCTION WORK. PROVIDE DUST PROOFING ENCLOSURES TO SEPARATE WORK
AREAS FROM THE EXISTING FACILITIES.
5. ALL TRASH AND DEBRIS TO BE REMOVED ON A DAILY BASIS.
6. PROVIDE PROTECTION FOR ALL EXISTING SURFACES AND CONDITIONS TO REMAIN IN
PLACE DURING THE SCOPE OF WORK. SHOULD ANY DAMAGE OCCUR, PATCH AND REPAIR
ANY DAMAGE TO ADJACENT FINISHES TO MATCH EXISTING.
7. ANY DAMAGE CAUSED TO THE BUILDING OR OWNER EQUIPMENT SHALL BE REPAIRED OR
REPLACED BACK TO ITS ORIGINAL CONDITIONS AT NO ADDITIONAL COST TO THE OWNER.
8. COVER ALL RETURN AIR GRILLES WITHIN THE AREA OF CONSTRUCTION TO PREVENT
PARTICULATE MATERIAL FROM EXHAUSTING INTO SURROUNDING SPACES.
9. APPROPRIATE LIGHT FIXTURES SHALL BE TEMPORARILY SUSPENDED TO PROVIDE
ADEQUATE LIGHTING LEVELS FOR CONSTRUCTION.
10. CONTRACTOR AND SUBCONTRACTORS ARE REQUIRED TO COORDINATE WITH OTHER
DISCIPLINES TO INSTALL COMPLETE AND OPERATIONAL SYSTEMS. DRAWINGS, AS A
WHOLE, REPRESENT A COMPLETE SET AND DEPICT REQUIREMENTS FOR COMPLETE AND
OPERATIONAL SYSTEMS. INDIVIDUAL DRAWINGS MAY NOT DEPICT COMPLETE AND
ACCURATE INFORMATION TO COORDINATE COMPLETE AND OPERATIONAL SYSTEMS, BUT
DO SO AS AN ENTIRE DOCUMENT TO BE REFERENCED WITH OTHER INDIVIDUAL DRAWINGS.
CONTRACTOR AND SUBCONTRACTORS ARE REQUIRED TO REFERENCE OTHER SHEETS
AND SPECIFICATIONS AS AN ENTIRE SET OF CONSTRUCTION DOCUMENTS THAT REFLECT
WORK REQUIRED TO ACHIEVE A COMPLETE AND OPERATIONAL GOAL. LACK OF
COORDINATION AND REVIEW OF DRAWINGS AND SPECIFICATIONS AS AN ENTIRE
DOCUMENT TO INSTALL COMPLETE AND OPERATIONAL SYSTEMS, BEING OBVIOUS AND
TYPICAL INDUSTRY STANDARD, IDENTIFIED IN THE DRAWINGS AND SPECIFICATIONS, SHALL
NOT BE IN ANY WAY AN ADDITIONAL COST TO THE GOVERNMENT.
11. CONTRACTOR SHALL SUBMIT A REQUEST, IN WRITING, TO INTERRUPT ANY SERVICES,
SUCH AS WATER, GAS, STEAM, SEWERS, ELECTRICITY, FIRE PROTECTION, OR
COMMUNICATIONS SYSTEMS, TO COR (CONTRACTING OFFICER’S REPRESENTATIVE) 7
DAYS IN ADVANCE OF PROPOSED INTERRUPTION. REQUEST SHALL STATE REASON, DATE,
EXACT TIME OF, AND APPROXIMATE DURATION OF SUCH INTERRUPTION. MAJOR
INTERRUPTIONS OF ANY SYSTEM MUST BE REQUESTED, IN WRITING, AT LEAST 15
CALENDAR DAYS PRIOR TO THE DESIRED TIME AND SHALL BE PERFORMED AS DIRECTED
BY THE COR. MAJOR INTERRUPTIONS SHALL BE COORDINATED WITH OTHER MAJOR
INTERRUPTIONS AND MAY NOT BE SCHEDULED FOR ONE DISCIPLINE MORE THAN TWICE
THROUGHOUT THE OVERALL CONSTRUCTION SCHEDULE UNLESS REQUESTED IN WRITING
AND APPROVED BY THE COR. CONTRACTOR WILL BE ADVISED, IN WRITING, OF APPROVAL
OF REQUEST, OR OF WHICH OTHER DATE AND/OR TIME SUCH INTERRUPTION WILL CAUSE
THE LEAST INCONVENIENCE TO OPERATIONS OF THE MEDICAL CENTER. INTERRUPTION
TIME APPROVED BY THE MEDICAL CENTER MAY OCCUR AT TIMES OTHER THAN
CONTRACTOR'S NORMAL WORKING HOURS. SCHEDULE INTERRUPTION MAY BE ON
WEEKENDS OR LATE HOURS AND MAY NOT BE AN ADDITIONAL COST TO THE GOVERNMENT.
COORDINATE ALL INTERRUPTIONS THAT MAY AFFECT THE NORMAL OPERATION OF THE
FACILITY WITH THE COR WHEN SUBMITTING THE CONSTRUCTION SCHEDULE OR UPDATES
TO THE CONSTRUCTION SCHEDULE.
12. NO ASBESTOS CONTAINING MATERIALS ARE TO BE USED ON THIS PROJECT. SPUR DESIGN, THE A/E OF RECORD, CAN CERTIFY THAT NO ASBESTOS CONTAINING BUILDING MATERIALS
(ACBM) OR LEAD BASED PAINT (LBP) PRODUCTS WERE DESIGNED/SPECIFIED AS BUILDING
MATERIAL IN ANY OF THE CONSTRUCTION DOCUMENTS.
13. REFERENCE ELECTRICAL DRAWINGS FOR CONCRETE HOUSEKEEPING PAD DETAIL,
LOCATIONS OF FIRE RATED WALLS AND FIRE PROTECTION/ SPRINKLER HEAD REROUTING
INFORMATION.
14. PROVIDE FIRE STOPPING AROUND ALL PENETRATIONS THROUGH RATED WALLS.
REFERENCE SHEET E-100.
GENERAL NOTES
AREA NAME
150 SF
A101
A101
SIM
A
00.0
A101
1 1
A101
LEVEL NAME
00'-00"
00'-00" 4B
3A
FIBERGLASS BATT
INSULATION
RIGID INSULATION
CONCRETE / PRECAST
CONCRETE
EARTH / SOIL
SAND, EIFS FINISH, OR
PLASTER FINISH
GYPSUM BOARD FINISH
BRICK
CONCRETE MASONRY
UNIT
STONE / CAST STONE
GYPSUM BOARD SECTION
EXTERIOR SHEATHING
BOARD SECTION
PLYWOOD SECTION
CLEAN UTILITY
000A
/1 A101
X0000
6"2' -1
0"
'-2
ROOM TAG
AREA TAG
SPECIALTY EQUIPMENT TAG
DOOR TAG
KEYED NOTE TAG
WALL TAG
WINDOW TAG
A101
SIM
A101
SIM
A
ACB ACOUSTIC CEILING BAFFLE
ACP ACOUSTIC CEILING PANEL
ACST ACOUSTIC
ADA AMERICANS WITH DISABILITIES ACT
ACT ACOUSTICAL CEILING TILE
ADDL ADDITIONAL
ADDN ADDITION
ADJ ADJACENT, ADJOINING, OR
ADJUSTABLE
ADMIN ADMINISTRATION
AE ARCHITECT/ENGINEER
AF ACCESS FLOORING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AIA AMERICAN INSTITUTE OF
ARCHITECTS
ALT ALTERNATE
ALT NO ALTERNATE NUMBER
ALUM ALUMINIUM (TRIM)
AMT AMOUNT
APPROX APPROXIMATE
ARCH ARCHITECT
ASC ABOVE SUSPENDED CEILING
AT ACOUSTIC CEILING TILE
AVG AVERAGE
B
BD BOARD
BG BUMPER GUARD
BLDG BUILDING
BLKG BLOCKING
BLT IN BUILT-IN
BOS BOTTOM OF STEEL
BOT BOTTOM
BRKT BRACKET
BTWN BETWEEN
C
CAB CABINET
CAV CAVITY
CBB CONCRETE BACKER BOARD
CC CONTRACTOR PROVIDED /
CONTRACTOR INSTALLED
CD CONSTRUCTION DOCUMENTS
CFM CUBIC FEET PER MINUTE
CFS CUBIC FEET PER SECOND
CG CORNER GUARD
CH BD CHALKBOARD
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CLG HT CEILING HEIGHT
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CO CONTRACTING OFFICER
COL COLUMN
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUOUS
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CP CONTRACTOR PROVIDED
CPT CARPET/CARPET TILE
CS CONCRETE SEALED
CSWK CASEWORK
CT CERAMIC TILE
CTB CERAMIC TILE BASE
CTR CENTER
CU FT CUBIC FEET
D
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIR DIRECTION
DIST DISTANCE
DOC DOCUMENT
DR DOOR
DS DOWNSPOUT
DWG DRAWING
DWP DIMENSIONAL WALL PANEL
E
EA EACH
EJ EXPANSION JOINT
EL ELEVATION
ELEV ELEVATOR
ENTR ENTRANCE
EPY EPOXY FLOORING
EQ EQUAL
ETR EXISTING TO REMAIN
EX EXISTING
EXP EXPOSED
EXT EXTERIOR
F
FAB FABRIC
FED FEDERAL
FF FINISH FACE
FF EL FINISH FLOOR ELEVATION
FIN FINISH
FIN BS FINISH BOTH SIDES
FIN FLR FINISH FLOOR
FIN GR FINISH GRADE
FIXT FIXTURE
FLDG FOLDING
FLEX FLEXIBLE
FLG FLOORING
FLMT FLUSH MOUNT
FLR FLOOR
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FP FIRE PROTECTION
FR FIRE RESISTANT
FT FEET
FTG FOOTING
FV FIELD VERIFY
FWC FABRIC WALL COVERING
G
GDR GUARDRAIL
GL GLASS/GLAZING
GRAN GRANITE
GR FL GROUND FLOOR
GT GROUT
GSM GALVANIZED SHEET METAL
GYP BD GYPSUM BOARD
H
HDW HARDWARE
HEPA HIGH EFFICIENCY
PARTICULATE AIR (FILTER)
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HANDRAIL
HT HEIGHT
I
IBC INTERNATIONAL BUILDING CODE
INSUL INSULATION
INT INTERIOR
ILO IN LIEU OF
J
J-BOX JUNCTION BOX
L
LAV LAVATORY
LBS POUND
LDG LANDING
LF LINEAR FEET (FOOT)
LIN LINEAR
LN LINOLEUM
LOC LOCATION
LT LIGHT
LVR LOUVER
LVT LUXURY VINYL TILE
M
MAT CARPET MAT / WALK-OFF MAT
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MEMB MEMBRANE
MFR MANUFACTURER
MID MIDDLE
MIL STD MILITARY STANDARD
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MOD MODIFY
MTG MOUNTING
MTL METAL
MVBL MOVABLE
N
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
O
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
OPP OPPOSITE
OPR OPERABLE
ORD OVERFLOW ROOF DRAIN
ORIG ORIGINAL
P
P PAINT
PA PUBLIC ADDRESS
PBD PARTICLE BOARD
PCF POUNDS PER CUBIC FOOT
PCT PERCENT
PERF PERFORATED
PERIM PERIMETER
PERP PERPENDICULAR
PL PROPERTY LINE
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PNL PANEL
PR PAIR
PRB PROFILE BASE
PRKG PARKING
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PORCELAIN TILE
PWR POWER
Q
QA QUALITY ASSURANCE
QC QUALITY CONTROL
QTY QUANTITY
REFERENCE SYMBOLS IDENTIFICATION TAGS
NOTE: NOT ALL ABBREVIATIONS OR SYMBOLS WILL BE UTILIZED FOR THIS PROJECT.
GRID HEAD AND
LINE
LEVEL INDICATOR
MATCH LINE AND
VIEW REFERENCE
NORTH ARROW W/
PROJECT NORTH
SPOT ELEVATION
DETAIL
SECTION
**48" MIN IF BOTH CLOSER
AND LATCH PROVIDED
WALL
SECTION
BUILDING
SECTION
DETAIL
ELEVATION
INTERIOR
ELEVATION
BUILDING
ELEVATION
1 1
6'- 0"
5'- 6"
BARIATRIC TOILET ROOM
TURNING RADIUS
CLEAR FLOOR SPACE
@ ADA LAVATORY
CLEAR FLOOR SPACE @ ADA
DRINKING FOUNTAIN
4"
6"
3"
1' -6
6" MAX
7" - 9" 11" MIN
17" - 25"
M
IN
6' -0
(ANSI ICC A117.1)
39"- 41"
(A N
S I I
C C
A
7.
1)
M
IN
(A N
S I I
C C
A
7.
1)
1"
3' -6
M
A X
5' -0
M
A X
R
RAF RESILIENT ATHLETIC FLOORING
RB RUBBER BASE/RESILIENT BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REC RECESSED
REF REFERENCE
REM REMOVABLE
REP REPAIR
REPL REPLACE
REQ REQUIRE
REQD REQUIRED
RES RESINOUS FLOORING
RES-W RESINOUS / EPOXY WALL / CEILING
RF RUBBER FLOORING
RFG ROOFING
RM ROOM
RO ROUGH OPENING
RP RESIN PANEL
RSF RESILIENT SHEET FLOORING
RV ROOF VENT
RWC RIGID VINYL WALLCOVERING
S
SC SPECIALTY COATING
SD STATIC DISSIPATIVE FLOORING/TILE
SCHED SCHEDULE
SECT SECTION
SF SQUARE FOOT (FEET)
SGL SINGLE
SIM SIMILAR
SJ SCORED JOINT
SLNT SEALANT
SM SHEET METAL
SPEC SPECIFICATION
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SS SOLID SURFACE
ST STONE
STD STANDARD
STOR STORAGE
SV SHEET VINYL (ROLLED OR TILE)
T
TEL TELEPHONE
TEMP TEMPORARY
TER TERRAZZO
TOF TOP OF FOOTING/ FOUNDATION
TOM TOP OF MASONRY
TOS TOP OF SLAB/ STEEL
U
UNO UNLESS NOTED OTHERWISE
UTIL UTILITY
V
VAR VARIES
VC VA PROVIDED / CONTRACTOR
INSTALLED
VCT VINYL COMPOSITION TILE
VFAT VINYL-FACED ACOUSTICAL TILE
VP VENEERED PLASTER
VT VINYL TILE
VV VA PROVIDED / VA INSTALLED
VWC VINYL WALLCOVERING
VWF VINYL WALL FABRIC
W
W/ WITH
W/O WITHOUT
W/C WATER CLOSET
WC WHEELCHAIR
WD WOOD
WFAB WALL FABRIC
WPM WATERPROOF MEMBRANE
WSF WELDED SHEET FLOOR
X
X BRACE CROSS BRACE
TRUE
NORTH
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. CA02295 EXP. 06/30/2025
ENGR REG. NO. CA7127 EXP. 06/30/2025
ELECTRICAL ENGINEER
SPUR DESIGN
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
/1
/2
:2 :2
P
M
GENERAL INFORMATION
CAB 2 OF 9BKM
100% CONSTRUCTION DOCUMENTS
REPLACE MCC PANEL BF118
03/18/2024
635-23-118
OKLAHOMA CITY VAHCS
921 NE 13TH STREET
OKLAHOMA CITY, OK 73104
GI001
SPUR #: 2093.05No. REVISION DESCRIPTION DATE
UE
OE
M/G 400A/3P
M/G 400A/3P
C
PC
R
TS
T
100/3
100/3/70
100/3/70/1
100/3/CB
PP
J
GF
OR
OR
OR
EPO
AM
VM
DM
ST
KK
GFR
M
SPD
R
LP1
1,3,5
A1
LIGHT FIXTURE, CEILING MOUNTED
A1 = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT
FIXTURE SCHEDULE
a = SWITCHED BY SWITCH "a"
NL = NIGHT LIGHT
= ARROW INDICATES AIMING DIRECTION
a
LIGHTING TRACK WITH TRACK LIGHT FIXTURES
A1E = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT
FIXTURE SCHEDULE
a = SWITCHED BY SWITCH "a"
LIGHT FIXTURE, POLE MOUNTED
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
LIGHT FIXTURE, WALL MOUNTED
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
EMERGENCY BATTERY PACK LIGHT FIXTURE,
WALL MOUNTED
Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT
FIXTURE SCHEDULe
EMERGENCY BATTERY PACK LIGHT FIXTURE,
CEILING MOUNTED
Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT
FIXTURE SCHEDULE
EXIT SIGN, WALL MOUNTED, FACE/ARROWS AS INDICATED
X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT
FIXTURE SCHEDULE
EXIT SIGN, CEILING MOUNTED, FACE/ARROWS AS INDICATED
X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT
FIXTURE SCHEDULE
EMERGENCY LIGHT FIXTURE, CEILING MOUNTED
A1E = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT
FIXTURE SCHEDULE
a = SWITCHED BY SWITCH "a"
NL = NIGHT LIGHT
A1E a
A1 a
A1
A1
X1E
X1E
Y1E
Y1E
HOMERUN TO PANELBOARD
TICK MARKS INDICATE NUMBER OF CONDUCTORS.
DESIGNATIONS ARE PANELBOARD AND
CIRCUIT NUMBERS.
UNSWITCHED HOT CONDUCTORS SHOWN LEADING
NEUTRAL CONDUCTOR
NEUTRAL CONDUCTOR
SWITCHED HOT CONDUCTORS SHOWN TRAILING
GROUND CONDUCTOR
EQUIPMENT GROUNDING CONDUCTOR IN RACEWAY
ISOLATED GROUNDING CONDUCTOR IN RACEWAY
CONCEALED RACEWAY
EXPOSED RACEWAY
RACEWAY TURNING DOWN
RACEWAY TURNING UP
EQUIPMENT TERMINATION
LOW VOLTAGE CABLE (NOT ROUTED IN CONDUIT)
LIGHT FIXTURE, BOLLARD
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
A1
RECEPTACLE, SIMPLEX, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, NEMA 5-20R, UNO
RECEPTACLE, DOUBLE-DUPLEX, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, CEILING MOUNTED, NEMA 5-20R, UNO
RECEPTACLE, SPECIAL PURPOSE
RECEPTACLE, TWIST-LOCK
RECEPTACLE, DUPLEX, FLOOR MOUNTED, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, DROP CORD, NEMA 5-20R, UNO
RECEPTACLE, MOUNTED 6" ABOVE COUNTER,
TYPE AS INDICATED ABOVE
RECEPTACLE DESIGNATIONS AS FOLLOWS:
C = CLOCK HANGER
E = EMERGENCY POWER
GF = GROUND FAULT CIRCUIT INTERRUPTER
IG = ISOLATED GROUND
S = SWITCHED
TR = TAMPER RESITANT
WP = WEATHER PROOF COVER
WR = WEATHER RESISTANT
XP = EXPLOSION PROOF
SWITCH, SINGLE POLE
SWITCH DESIGNATIONS AS FOLLOWS:
2 = TWO-POLE WALL SWITCH
3 = THREE-WAY WALL SWITCH
4 = FOUR-WAY WALL SWITCH
D = DIMMER SWITCH
OS# = OCCUPANCY SENSOR WALL SWITCH, REFER
TO OCCUPANCY SENSOR AND SWITCH SCHEDULE
P = SINGLE-POLE, SINGLE-THROW PILOT LIGHT
WALL SWITCH
K = KEYED WALL SWITCH
M = MOTOR RATED SWITCH
WP = WEATHER PROOF SWITCH AND COVER
OCCUPANCY SENSOR, CEILING MOUNTED
OS# = CEILING MOUNTED OCCUPANCY SENSOR, REFER
TO OCCUPANCY SENSOR AND SWITCH SCHEDULE
POWER PACK FOR LIGHTING CONTROL
JUNCTION BOX
RECEPTACLE ON EMERGENCY POWER
RECEPTACLE, ISOLATED GROUND TYPE
MULTI-OUTLET, SURFACE RACEWAY, 24" ON CENTER,
NEMA 5-20R, UNO
SWITCHBOARD, MOTOR CONTROL CENTER OR DISTRIBUTION
PANELBOARD ON HOUSEKEEPING PAD
PANELBOARD, RECESS MOUNTED
PANELBOARD, SURFACE MOUNTED
TRANSFORMER
DISCONNECT SWITCH, NON-FUSED, 100/3 INDICATES
AMPERES/POLES, CB = CIRCUIT BREAKER TYPE
DISCONNECT SWITCH, FUSED, 100/3/70 INDICATES
AMPERES/POLES/FUSE, CB = CIRCUIT BREAKER TYPE
COMBINATION DISCONNECT SWITCH WITH MOTOR STARTER
100/3/70/1 INDICATES AMPERES/POLES/FUSE/ NEMA STARTER
SIZE, NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE
MAGNETIC MOTOR STARTER, NEMA SIZE AS NOTED,
3-POLE, UNO
CONTACTOR
PHOTOCELL
RELAY
TIME SWITCH
LOW-VOLTAGE TRANSFORMER
PUSH BUTTON, TYPE AS NOTED
VARIABLE FREQUENCY DRIVE WITH DISCONNECT SWITCH
100/3/70 INDICATES AMPERES/POLES/FUSE SIZE,
NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE
UNDERGROUND ELECTRIC LINE
MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
CABINET, RECESS MOUNTED
CABINET, SURFACE MOUNTED
RECEPTACLE, DUPLEX, GROUND-FAULT CIRCUIT
INTERRUPTER, NEMA 5-20R, UNO
MULTI-SERVICE POWER POLE WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
OVERHEAD ELECTRIC LINE
MUSHROOM TYPE PUSH BUTTON, TYPE AS NOTED
TRANSFER SWITCH, RATINGS AS INDICATED
ATS = AUTOMATIC TRANSFER SWITCH
MTS = MANUAL TRANSFER SWITCH
TX#
600AF
500AT
3P
400AS
3P
225AF
LPS-R
275KW STANDBY
480Y/277V, 3PH, 4W
GENERATOR, SEPARATELY DERIVED
SOURCE, TYPE AND RATINGS AS INDICATED
275KW STANDBY
480Y/277V, 3PH, 4W
GENERATOR, NON-SEPARATELY DERIVED
SOURCE, TYPE AND RATINGS AS INDICATED
DRAWOUT CIRCUIT
BREAKER, RATINGS
AS INDICATED
600AF
500AT
3P
CIRCUIT BREAKER,
RATINGS AS
INDICATED
FUSED DISCONNECT
SWITCH, RATINGS
AS INDICATED
400AS
3P
225AF
LPS-R
NEMA 1
COMBINATION FUSED
SWITCH AND STARTER,
RATINGS AS
INDICATED
PANELBOARD,
SINGLE-SECTION,
RATINGS PER
SCHEDULES
PANELBOARD,
MULTI-SECTION,
RATINGS PER
SCHEDULES
AMMETER
VOLTMETER
COMBINATION DIGITAL
AMMETER/VOLTMETER
SHUNT-TRIP RELAY
KIRK-KEY INTERLOCK
GROUND-FAULT RELAY
UTILITY METER
RELAY
SURGE PROTECTION
DEVICE
AUTOMATIC TRANSFER SWITCH WITH BYPASS
TYPE AND RATINGS AS INDICATED
VARIABLE FREQUENCY
DRIVE WITH
DISCONNECT, RATINGS
AS INDICATED
GROUND CONNECTION
POTENTIAL TRANSFORMER
CURRENT TRANSFORMER
GROUND CONNECTION
WITH TEST WELL
CONTACT, OPEN
CONTACT, CLOSED
MOTOR
FEEDER TAGCAPACITOR
SURGE ARRESTER
HEATER
225A 3P
NEMA 1
COMBINATION CIRCUIT
BREAKER AND
STARTER, RATINGS AS
INDICATED
225A 3P
200A 3P
ATS#
200A 3P
ATS#
TRANSFORMER
TX#
TRANSFORMER,
SHIELDED
200A DEAD-FRONT ELBOW
600A DEAD-FRONT ELBOW
DEAD-FRONT SPLITTER
FAULT INDICATOR
LIGHTNING PROTECTION AIR TERMINAL
LIGHTNING PROTECTION CABLE CONNECTION
LIGHTNING PROTECTION GROUND ROD
LIGHTNING PROTECTION CONDUCTOR
LIGHTNING PROTECTION SYMBOLS
ELECTRICAL ONE-LINE DIAGRAM SYMBOLS
LIGHTING SYMBOLS
POWER EQUIPMENT SYMBOLS
WIRING DEVICE SYMBOLS
CIRCUITING SYMBOLS
ES EMERGENCY SHUNT RELAY
MECHANICAL OR FIRE SPRINKLER PLAN NOTE CALL OUT
PLUMBING PLAN NOTE CALL OUT
ELECTRICAL, TECHNOLOGY, OR FIRE ALARM
PLAN NOTE CALL OUT
PLUMBING EQUIPMENT DESIGNATION
EQUIPMENT DESIGNATION TAG
OWNER FURNISHED, CONTRACTOR INSTALLED
EQUIPMENT DESIGNATION
NEW WORK TO EXISTING WORK CONNECTION POINT
DETAIL REFERENCE
SECTION CUT DESIGNATION
ELECTRICAL: (AFF, AFG UNLESS NOTED OTHERWISE)
EP-101
EP-101
AUDIBLE APPLIANCES (CENTERLINE)
ALARMS (TOP)
ANNUNCIATOR PANELS (TOP)
CLOCK OUTLETS (CENTERLINE)
CONTROLS (TOP)
EXIT SIGNS (WALL-MOUNTED, BOTTOM)
FIRE ALARM ANNUNCIATOR PANEL (DISPLAY)
FIRE ALARM BELL (EXTERIOR)
FIRE ALARM CONTROL PANEL/UNIT (DISPLAY)
GROUND BAR
INTERCOM (AFEA ONLY)
INTERCOMS (TOP)
PANELS & PANELBOARDS (TOP)
PULL STATIONS (TOP)
PHOTOCELLS
RECEPTACLES (BOTTOM)
RECEPTACLES, EXTERIOR (BOTTOM)
RECEPTACLES, GARAGES (BOTTOM)
RECEPTACLES IN EQUIPMENT ROOMS (TOP)
RECEPTACLES ABOVE COUNTERTOPS (TOP)
REMOTE INDICATING LIGHT, EQUIPMENT ROOMS (TOP)
REMOTE INDICATING LIGHT, FINISHED AREAS (TOP)
SAFETY SWITCHES & STARTERS
SWITCHES (TOP)
TELEPHONE/DATA/TV OUTLETS (BOTTOM)
VISIBLE APPLIANCES (CENTERLINE)
ANNOTATION STANDARD MOUNTING HEIGHTS
ABBREVIATIONS
1P SINGLE-POLE
1PH SINGLE-PHASE
3P THREE-POLE
3PH THREE-PHASE
3W THREE-WIRE
4W FOUR-WIRE
A OR AMP AMPERE
A/C AIR CONDITIONING
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED
CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, OR
AUTOMATIC FREQUENCY CONTROL,
OR AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
AIP ABANDONED IN PLACE
ALT ALTERNATE
AMB AMBIENT
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BLK BLOCK
BPIP BOILER PLANT INSTRUMENTATION PANEL
BRKR BREAKER
BYP BY-PASS
C CONDUIT
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
CD CONSTRUCTION DOCUMENTS OR
CANDELA
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED /
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED /
OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAXIAL CABLE
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUED
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMER. MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
ESMT EASEMENT
ETD EXISTING TO BE DEMOLISHED
ETR EXISTING TO REMAIN
ETL EXISTING TO BE RELOCATED
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCA FAULT CALCULATED AMPS
FI FILM ILLUMINATOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLUOR FLUORESCENT
FO FIBER-OPTIC
FP FIRE PROTECTION
FT FEET OR FOOT
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G GROUND OR GENERATOR
GND GROUND
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
HCM HORIZONTAL CABLE MANAGER
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IC INSULATION CONTACT
IESNA ILLUMINATION ENGINEERING SOCIETY
OF NORTH AMERICA
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
JB OR J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAH KILOVOLT-AMPERE-HOUR
KVAR KILOVOLT-AMPERE-REACTIVE
KW KILOWATT
KWH KILOWATT-HOUR
KWHM KILOWATT-HOUR METER
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LT LIGHT
LTCP LOCAL TEMPERATURE CONTROL PANEL
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MT MOUNT
MTD MOUNTED
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
N NEUTRAL
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NC NORMALLY CLOSED
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, OR PULL BOX, OR
PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
PNLBD PANELBOARD
POD POWER OPERATED DAMPER
POE POWER OVER ETHERNET
PP PATCH PANEL
PT POTENTIAL TRANSFORMER
PTRV POWER TYPE ROOF VENTILATION
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REC RECESSED
RELO RELOCATED
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RU RACK UNIT
SCC SHORT CIRCUIT CAPACITY
SD SMOKE DETECTOR
SES SERVICE ENTRANCE SECTION
SF SQUARE FEET (FOOT)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TC TIME CLOCK
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT-AMPERE
VAR VOLT-AMPERE-REACTIVE
VCM VERTICAL CABLE MANAGER
VFD VARIABLE FREQUENCY DRIVE
W WATT
WH WATER HEATER
WP WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
XP EXPLOSION PROOF
84" 48" 48" 84" 48" 80" 60"
120" 60" 72" 36" 48" 72" 48"
144" 18" 24" 26" 48" 44" 48"
CEILING
48" 48" 18" 84"
A
# E (CONTINUED) M (CONTINUED)
B
C
D
E
F
N
G
H
I
J
K
L
M
O
P
R
S
T
U
V
W
X
A. ELECTRICAL PLANS AND SECTIONS ARE INTENDED TO
ACCURATELY ILLUSTRATE THE SCOPE OF WORK, BUT ARE STILL
DIAGRAMMATIC IN NATURE.
B. ELECTRICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE
INSTALLED. THE CONTRACTOR IS RESPONSIBLE FOR ENSURING
THAT ALL SYSTEMS ARE FULLY FUNCTIONAL AND COMPLIANT
WITH APPLICABLE CODES.
C. ELECTRICAL DRAWINGS REFLECT COORDINATION EFFORTS
WITH BUILDING DISCIPLINES. HOWEVER, COORDINATION WITH
OTHER TRADES IS REQUIRED.
D. REFERENCE ARCHITECTURAL DRAWINGS FOR ADDITIONAL
INFORMATION REGARDING SCHEDULE AND PHASING
REQUIREMENTS. SCHEDULE WORK TO MINIMIZE DISRUPTION OF
SERVICES.
E. COORDINATE WITH SCHEDULE WITH THE CONTRACTING
OFFICER'S REPRESENTATIVE BEFORE THE START OF WORK.
F. PANELBOARDS AND OTHER ELECTRICAL EQUIPMENT REQUIRE
SHUTDOWN. COORDINATE SERVICE SHUTDOWN FOR ALL
EQUIPMENT WITH THE CONTRACTING OFFICER'S
REPRESENTATIVE.
G. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND
TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES
SHALL HAVE DIVIDERS BETWEEN DEVICES.
H. UPDATE ALL PANELBOARD SCHEDULES AFFECTED AT THE
COMPLETION OF THE PROJECT.
I. IF FIELD CONDITIONS VARY FROM THE DRAWINGS, THE
CONTRACTOR SHALL DOCUMENT THE VARIATION AND REPORT
IT TO THE GENERAL CONTRACTOR FOR RESOLUTION WITH THE
ENGINEER OF RECORD.
GENERAL NOTES
PROJECT CODES AND STANDARDS
A. ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS 2015
B. VA PG-18-13 VA BARRIER FREE DESIGN STANDARD 2018
(SUPPLEMENT TO ABA STANDARDS)
C. ASHRAE STANDARD 90.1-2019 – ENERGY STANDARD FOR
BUILDINGS EXCEPT LOW RISE RESIDENTIAL BUILDINGS
D. IBC 2021 – INTERNATIONAL BUILDING CODE
E. IEBC 2021 – INTERNATIONAL EXISTING BUILDING CODE
F. IECC 2021 – INTERNATIONAL ENERGY CONSERVATION CODE
G. JCAHO EC 7.40 – EMERGENCY ELECTRICAL POWER SYSTEM
INSPECTION, MAINTENANCE, AND TESTING
H. NFPA 70-2023 - NATIONAL ELECTRICAL CODE (NEC)
I. NFPA 99-2021 – HEALTH CARE FACILITIES CODE
J. NFPA 101-2021 – LIFE SAFETY CODE
K. NFPA 110-2022 – STANDARD FOR EMERGENCY AND STANDBY
POWER SYSTEMS
L. VA PG-18-10 ELECTRICAL DESIGN MANUAL, DECEMBER 2019
M. VA H-18-8 SEISMIC DESIGN REQUIREMENTS
N. VA PHYSICAL SECURITY & RESILIENCY DESIGN MANUAL 2020
(1 JAN 2024 REVISION)
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. CA02295 EXP. 06/30/2025
ENGR REG. NO. CA7127 EXP. 06/30/2025
ELECTRICAL ENGINEER
SPUR DESIGN
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
/1
/2
:5 :3
A
M
ELECTRICAL SYMBOLS &
ABBREVIATIONS
IGM 3 OF 9ES
100% CONSTRUCTION DOCUMENTS
REPLACE MCC PANEL BF118
03/18/2024
635-23-118
OKLAHOMA CITY VAHCS
921 NE 13TH STREET
OKLAHOMA CITY, OK 73104
E-000
SPUR #: 2093.05No. REVISION DESCRIPTION DATE
EP101
ED101
MECHANICAL ROOM
BF118
EMERGENCY GENERATOR
BF115
EP101
ED101
PNL EGP
(ETR)
EMCC-1 (NEW)
'ATS-6' (NEW)
ATS-6
DISCONNECT
SWITCH (ETR)
(TYP.)
(TYP.)
BASEMENT LEVEL KEY PLAN
N
BUILDING 1
MECH RM BF118
GEN RM BF115
PARTITION LEGEND
EXISTING 1 HOUR FIRE RATED
EXISTING 2 HOUR FIRE RATED
EXISTING 3 HOUR FIRE RATED
SMOKE PARTITION/BARRIER
NEW NON-RATED WALLS
EXISTING WALL TO REMAIN
EXISTING 1 HOUR FIRE
EXISTING 2 HOUR FIRE
NOTE: NOT ALL SYMBOLS MAY BE USED
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. CA02295 EXP. 06/30/2025
ENGR REG. NO. CA7127 EXP. 06/30/2025
ELECTRICAL ENGINEER
SPUR DESIGN
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
/1
/2
:5 :3
A
M
ELECTRICAL REFERENCE PLAN -
BASEMENT LEVEL
IGM 4 OF 9ES
100% CONSTRUCTION DOCUMENTS
REPLACE MCC PANEL BF118
03/18/2024
635-23-118
OKLAHOMA CITY VAHCS
921 NE 13TH STREET
OKLAHOMA CITY, OK 73104
E-100
SPUR #: 2093.05
N
1/16" = 1'-0"
ELECTRICAL REFERENCE PLAN - BASEMENT LEVEL1
ELECTRICAL KEYNOTES
1 PROVIDE 24" X 24" X 6" (MIN.) PULLBOX. PROVIDE PULLBOXES IN ACCESSIBLE LOCATIONS AND
DOCUMENT ON RECORD DRAWINGS EXACT SIZE AND LOCATION. REFER TO SHEET E-601 FOR
CONDUIT, WIRE SIZES, AND ADDITIONAL INFORMATION.
2 ROUTE CONDUIT ABOVE DROP CEILING TIGHT TO STRUCTURE. COORDINATE ROUTING WITH
EXISTING UTILITIES. ANY DAMAGE DONE TO EXISTING UTILITIES SHALL BE REPAIRED IN
ACCORDANCE WITH VA STANDARD CONSTRUCTION SPECIFICATIONS AT NO ADDITIONAL
COST.
3 PROVIDE FIRE STOPPING AROUND ALL PENETRATIONS THROUGH RATED WALLS.
4 REFER TO CONDUIT TRAPEZE MOUNTING DETAIL 1/E-501 FOR MOUNTING REQUIREMENTS.
5 PROVIDE (2) 3" CONDUIT TO CONNECT EXISTING 400A, 480V DISCONNECT SWITCH TO NEW
600A, 480V ATS-6. REFER TO SHEET E-601 & E-602 FOR MORE INFORMATION.
6 NEW PARALLEL CONDUCTORS FROM EXISTING ATS-6 DISCONNECT SWITCH IN EMERGENCY
GENERATOR ROOM BF115 TO NEW ATS-6 IN MECHANICAL ROOM BF118 ARE FOR TEMPORARY
THEN PERMANENT TERMINATION.
7 ROUTE NEW RACEWAYS IN EXPOSED SPACE TIGHT TO STRUCTURE. PROVIDE FINAL ROUTING
PLAN TO COR FOR APPROVAL.
A. ELECTRICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE
CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY
FUNCTIONAL AND COMPLIANT WITH APPLICABLE CODES.
B. ELECTRICAL DRAWINGS REFLECT COORDINATION EFFORTS WITH OTHER DISCIPLINES.
HOWEVER, COORDINATION WITH OTHER TRADES ARE REQUIRED.
C. DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF WORK.
REVIEW GENERAL NOTES AND PLANS FOR ADDITIONAL REQUIREMENTS THAT MAY NOT
BE SPECIFICALLY CALLED OUT IN THIS PORTION OF THE CONSTRUCTION DOCUMENTS.
NOTIFY THE CONTRACTING OFFICER'S REPRESENTATIVE (COR) OF ANY CONFLICTS OR
DISCREPANCIES PRIOR TO SUBMISSION OF BID.
D. REFER TO ONE-LINE DRAWING SHEETS FOR ADDITIONAL NOTES.
E. SHADED AREAS ARE OUT OF PROJECT SCOPE.
F. NO WORK ON ENERGIZED EQUIPMENT IS PERMITTED BY VA DIRECTIVE.
GENERAL NOTES:
EMCC-1 (ETD)
CHILLER
STARTER
(ETR)
EAST
HEATING
WATER #1
VFD (ETD)
WEST
HEATING
WATER #2
VFD (ETD)
SWITCHBOARD
'MDP' (ETR)
PANEL
'CHDP-2' (ETR)
750 KVA XFMR
(ETR)
MECHANICAL ROOM
BF118
(ABOVE)
VACUUM PUMP #2
DISCONNECT (ETR)
VACUUM PUMP #1
DISCONNECT (ETR)
HOT WATER
CIRCULATING PUMP
DISCONNECT (ETR)
ETD
XFMR LBIEB
(ETR)
PANEL LBIEB
(ETR)
PANEL B (ETR)
XFMR A (ETR)
PANEL A (ETR)
PANEL A1
(ETR)
CONCRETE
PAD (ETR)
CONCRETE
PAD (ETR)
CHWP (ETR)
EXHAUST
FAN (ETR)
S&C
SWITCHGEAR
(ETR)
PUMP DISCONNECT
(ETR)
ED101
EMERGENCY GENERATOR
BF115
GENERATOR
CONTROL
PANEL (ETR)PNL EGP
(ETR)
ATS-6
DISCONNECT
SWITCH (ETR)
500KW
GENERATOR
(ETR)
ELECT. HEATER
DISCONNECT
SWITCH (ETR)
ETR
DAY TANK
(ETR)
BASEMENT LEVEL KEY PLAN
N
BUILDING 1
MECH RM BF118
GEN RM BF115
PARTITION LEGEND
EXISTING 1 HOUR FIRE RATED
EXISTING 2 HOUR FIRE RATED
EXISTING 3 HOUR FIRE RATED
SMOKE PARTITION/BARRIER
NEW NON-RATED WALLS
EXISTING WALL TO REMAIN
EXISTING 1 HOUR FIRE
EXISTING 2 HOUR FIRE
NOTE: NOT ALL SYMBOLS MAY BE USED
CHILLER
STARTER
(ETR)
'ATS-6' (NEW)
CONCRETE
PAD (NEW)
EXHAUST
FAN (ETR)
EMCC-1 (ETD)
MECHANICAL ROOM
BF118
4 5
6 (TYP.)
3"
3'-6"
2'-1" th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. CA02295 EXP. 06/30/2025
ENGR REG. NO. CA7127 EXP. 06/30/2025
ELECTRICAL ENGINEER
SPUR DESIGN
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
/1
/2
:5 :3
A
M
ELECTRICAL POWER DEMOLITION PLAN
IGM 5 OF 9ES
100% CONSTRUCTION DOCUMENTS
REPLACE MCC PANEL BF118
03/18/2024
635-23-118
OKLAHOMA CITY VAHCS
921 NE 13TH STREET
OKLAHOMA CITY, OK 73104
ED101
SPUR #: 2093.05
N
1/4" = 1'-0" REF: 1/ E-100
ELECTRICAL DEMOLITION PLAN - MECHANICAL ROOM BF1181
A. LOCATIONS ARE APPROXIMATE. FIELD VERIFY EXACT DEVICE QUANTITIES LOCATIONS PRIOR TO
DEMOLITION.
B. WHERE PORTIONS OF CIRCUITS ARE REMOVED OR ABANDONED, RE-ESTABLISH CIRCUIT
CONTINUITY FOR REMAINING PORTION OF CIRCUITS AS REQUIRED TO MAINTAIN OPERATION.
C. SHADED AREAS INDICATE OUT OF PROJECT SCOPE.
D. NO WORK ON ENERGIZED EQUIPMENT IS PERMITTED BY VA DIRECTIVE.
GENERAL NOTES:
ELECTRICAL KEYNOTES
1 EXISTING HEATING WATER VFDS (NOT IN PROJECT SCOPE) SHALL BE DE-ENERGIZED,
DISCONNECTED, AND REMOVED BY THE VA IN ADVANCE OF THIS PROJECT.
2 PROVIDE NEW HOUSEKEEPING PAD AND NEW 4-POLE, 600A, 480Y/277V AUTOMATIC TRANSFER SWITCH (ATS-6) WITH ISOLATION BYPASS PRIOR TO DEMOLITION. SEE ELECTRICAL ONE-LINE FOR
MORE DETAILS AND PHASING PLAN.
3 PROVIDE A TEMPORARY 400A, 480Y/277V, 3-PH, 4W PANEL AND PROVIDE TEMPORARY CONNECTION
TO NEW ATS-6. TRANSFER LOADS FROM EXISTING EMCC-1 TO TEMPORARY PANEL. SEE
ELECTRICAL ONE-LINE DIAGRAM ON SHEETS E-601 AND E-602 FOR SEQUENCE OF WORK PHASING
REQUIREMENTS.
4 DE-ENERGIZE, DISCONNECT, AND REMOVE EXISTING EMCC-1 AND UPSTREAM CONDUIT AND
CONDUCTORS. SEE ELECTRICAL ONE-LINE DIAGRAM ON SHEETS E-601 AND E-602 FOR SEQUENCE
OF WORK PHASING REQUIREMENTS.
5 EXISTING BRANCH CIRCUIT LOADS SHALL BE DE-ENERGIZED. DISCONNECT AND REMOVE EXISTING
BRANCH CIRCUIT CONDUCTORS AND CONDUIT BACK TO NEAREST ACCEPTABLE POINT
(J-BOX/COUPLING). VERIFY EXISTING CONDUCTORS AND CONDUIT CONDITION ARE DEEMED
ACCEPTABLE WITH OKC VAMC ENGINEERS. STORE AND PROTECT EXISTING CONDUCTORS AND
CONDUIT FOR RE-INSTALLATION TO NEW EMCC-1.
6 VERIFY EXISTING EMCC-1 STARTER SIZES FOR BRANCH LOADS AND PROVIDE TEMPORARY
EXTERNAL STARTERS. SEE ELECTRICAL ONE-LINE DIAGRAM ON SHEETS E-601 AND E-602 FOR
SEQUENCE OF WORK PHASING REQUIREMENTS.
7 PROVIDE CONCRETE HOUSEKEEPING PAD FOR NEW ATS-6 AND PAINT YELLOW. MATCH NEW
HOUSEKEEPING PAD HEIGHT WITH EXISTING CONCRETE PAD. SEE DETAIL 2/E-501 FOR MORE
INFORMATION.
N
1/4" = 1'-0" REF: 1/ E-100
ELECTRICAL DEMOLITION PLAN - EMERGENCY GENERATOR ROOM BF1152
No. REVISION DESCRIPTION DATE
N
1/2" = 1'-0" REF: 1/ ED101
ELECTRICAL TEMPORARY PLAN - MECHANICAL ROOM BF1183
CHILLER
STARTER
(ETR)
SWITCHBOARD
'MDP' (ETR)
PANEL
'CHDP-2' (ETR)
750 KVA XFMR
(ETR)
MECHANICAL ROOM
BF118
EMCC-1 (NEW)
XFMR LBIEB
(ETR)
PANEL LBIEB
(ETR)
(ABOVE)
VACUUM PUMP #2
DISCONNECT (ETR)
VACUUM PUMP #1
DISCONNECT (ETR)
PANEL A1
(ETR)
PANEL A (ETR)
PANEL B (ETR)
XFMR A (ETR)
HOT WATER
CIRCULATING PUMP
DISCONNECT (ETR)
GFCI
'ATS-6' (NEW)
Y1E
Y1E
PANEL B
CONCRETE
PAD (ETR)
CONCRETE
PAD (ETR)
CHWP 2 (ETR)
EXHAUST
FAN (ETR)
S&C
SWITCHGEAR
(ETR)
EP101
CONCRETE
PAD (NEW)
PUMP DISCONNECT
(ETR)
500KW
GENERATOR
(ETR)
ELECT. HEATER
DISCONNECT
SWITCH (ETR)
GENERATOR
CONTROL
PANEL (ETR)PNL EGP
(ETR)
EMERGENCY GENERATOR
BF115
ATS-6
DISCONNECT
SWITCH (ETR)
ETR
DAY TANK
(ETR)
BASEMENT LEVEL KEY PLAN
N
BUILDING 1
MECH RM BF118
GEN RM BF115
EMCC-1 (NEW)
'ATS-6' (NEW)
CHILLER
STARTER
(ETR)
CONCRETE
PAD (ETR)
CONCRETE
PAD (NEW)
7 (TYP.)
EXHAUST
FAN (ETR)
MECHANICAL ROOM
BF118
PARTITION LEGEND
EXISTING 1 HOUR FIRE RATED
EXISTING 2 HOUR FIRE RATED
EXISTING 3 HOUR FIRE RATED
SMOKE PARTITION/BARRIER
NEW NON-RATED WALLS
EXISTING WALL TO REMAIN
EXISTING 1 HOUR FIRE
EXISTING 2 HOUR FIRE
NOTE: NOT ALL SYMBOLS MAY BE USED
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. CA02295 EXP. 06/30/2025
ENGR REG. NO. CA7127 EXP. 06/30/2025
ELECTRICAL ENGINEER
SPUR DESIGN
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
/1
/2
:0 :0
A
M
ELECTRICAL POWER FLOOR PLAN
IGM 6 OF 9ES
100% CONSTRUCTION DOCUMENTS
REPLACE MCC PANEL BF118
03/18/2024
635-23-118
OKLAHOMA CITY VAHCS
921 NE 13TH STREET
OKLAHOMA CITY, OK 73104
EP101
SPUR #: 2093.05
N
1/4" = 1'-0"
ELECTRICAL POWER PLAN - MECHANICAL ROOM BF1181
A. ELECTRICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE CONTRACTOR
IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY FUNCTIONAL AND COMPLIANT
WITH APPLICABLE CODES.
B. ELECTRICAL DRAWINGS REFLECT COORDINATION EFFORTS WITH OTHER DISCIPLINES.
HOWEVER, COORDINATION WITH OTHER TRADES ARE REQUIRED.
C. DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF WORK. REVIEW
GENERAL NOTES AND PLANS FOR ADDITIONAL REQUIREMENTS THAT MAY NOT BE SPECIFICALLY
CALLED OUT IN THIS PORTION OF THE CONSTRUCTION DOCUMENTS. NOTIFY THE CONTRACTING
OFFICER'S REPRESENTATIVE (COR) OF ANY CONFLICTS OR DISCREPANCIES PRIOR TO
SUBMISSION OF BID.
D. REFER TO ONE-LINE DRAWING SHEETS FOR ADDITIONAL NOTES.
E. SHADED AREAS ARE OUT OF PROJECT SCOPE.
F. NO WORK ON ENERGIZED EQUIPMENT IS PERMITTED BY VA DIRECTIVE.
GENERAL NOTES:
ELECTRICAL KEYNOTES
1 PROVIDE A NEW 600A, 480V, 3-PH, 4W MOTOR CONTROL CENTER (EMCC-1). SEE ELECTRICAL
ONE-LINE DIAGRAM ON SHEETS E-601 AND E-602 FOR SEQUENCE OF WORK PHASING
REQUIREMENTS.
2 CONTRACTOR TO PROVIDE AUXILIARY DRIP PAN PROTECTIONS BELOW WATER, SANITARY, OR
SPRINKLER PIPING IN THE EVENT THEY ARE MEASURED TO BE IN THE AREA DIRECTLY ABOVE
DEDICATED ELECTRICAL SPACE OF THE EQUIPMENT AFTER INSTALLATION PER NFPA
110.26(E)(1)(a-c). IF THOSE SYSTEMS ARE MEASURED TO BE WITHIN THE DEDICATED SPACE, THEY ARE TO BE REROUTED OUTSIDE THE ACCEPTABLE SPACE CLEARANCES AND THEN THE PREVIOUSLY NOTED PROTECTIONS MAY STILL APPLY. PROVIDE AUXILIARY DRIP PANS WITH LEAK DETECTION AND
TIE BACK TO CAMPUS BAS.
3 USE EXISTING 20A, 277V, 1-POLE CIRCUIT BREAKER IN PANEL B FOR EMERGENCY BATTERY PACK
WALL MOUNTED LIGHT FIXTURE.
4 PROVIDE NEW GFCI RECEPTACLE AND RE-USE EXISTING CIRCUIT.
5 REQUIRED CLEARANCES, AREA TO REMAIN FREE FROM DEBRIS PER NEC 110.26.
6 REMOVE TEMPORARY PANEL AFTER NEW EMCC-1 IS IN SERVICE. SEE ELECTRICAL ONE-LINE
DIAGRAM ON SHEETS E-601 AND E-602 FOR SEQUENCE OF WORK PHASING REQUIREMENTS.
7 REMOVE TEMPORARY EXTERNAL STARTERS AFTER NEW EMCC-1 IS IN SERVICE. SEE ELECTRICAL
ONE-LINE DIAGRAM ON SHEETS E-601 AND E-602 FOR SEQUENCE OF WORK PHASING
REQUIREMENTS.
N
1/4" = 1'-0" REF: 1/ E-100
ELECTRICAL POWER PLAN - EMERGENCY GENERATOR ROOM BF1152
No. REVISION DESCRIPTION DATE
N
1/2" = 1'-0" REF: 1/ EP101
NEW WORK CONFIGURATION - MECHANICAL ROOM BF1183
CONDUIT CLAMP. SIZE
AS REQUIRED
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
REFER TO PLANS FOR
QUANTITY & SIZE OF
CONDUITS
GENERAL NOTES:
1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL
LONGER THAN 915mm (36") SHALL BE INSTALLED WITH A
CENTER SUPPORT ROD.
2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED
METHOD PER SPECIFICATION 26 05 33, RACEWAY AND BOXES
FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT CONDITIONS.
3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER TO
SPECIFICATION SECTION 13 05 41, SEISMIC RESTRAINT
REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.
LENGTH AS REQUIRED
LOCKING SQUARE
WASHER & LOCKNUT
9.52mm (3/8") MIN
GALVANIZED THREADED
ROD, TYP.
WASHER &
LOCKNUT
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
1 1/2" CLR. 1 1/2" CLR.1'-0" TYP. 1'-0" TYP.
3/ 4"
ROUGHEN SURFACE TO 1/4" DEPTH. CLEAN
AND APPLY EPOXY BONDING COMPOUND
PRIOR TO PLACING NEW CONCRETE.
DRILL AND EPOXY #4 DOWELS AT
4'-0" O.C. (TYP. AT PERIMETER
MIN. 4 EA. PAD)
4"
#4 AT 6"
O.C. E.W.
CONCRETE PAD TO BE PAINTED YELLOW.
TOP OF HANDLE
6'-6" AFF MAXIMUM
4'-0" +/- AFF
FRONT VIEWSIDE VIEW
DISCONNECT SWITCH, CIRCUIT
BREAKER ENCLOSURE, OR
MOTOR CONTROLLER
CHANNEL STRUT POST BASE W
(4) 1/4" EXPANSION ANCHORS.
(TYPICAL)
PROVIDE RIGID CONDUIT TO
MECHANICAL/PLUMBING
EQUIPMENT. CONVERT TO
FLEXIBLE CONDUIT WITH BOND
WIRE FOR FINAL CONNECTION TO
EQUIPMENT.
FLOOR
STRUCTURAL CEILING
CHANNEL STRUT SUPPORT
FRAME.
1'-7" (MIN.)
OPTION 3: CHANNEL STRUT
ANGLE BRACKET SUPPORT
FOR EACH SUPPORT LEG WITH
1/2" FLOOR EXPANSION
ANCHOR.
PROVIDE RIGID CONDUIT BACK
TO ELECTRICAL SOURCE.
NOTE:
1. DISCONNECT SWITCHES, CIRCUIT BREAKER ENCLOSURES, MOTOR CONTROLLERS & VARIABLE FREQUENCY DRIVES, AND CONTROL CABINETS MAY BE DIRECTLY MOUNTED TO STRUCTURAL WALLS, OR TO MECHANICAL EQUIPMENT
WHEN PERMITTED BY THE MECHANICAL EQUIPMENT MANUFACTURER AND WHERE IT DOES NOT BLOCK ACCESS OR
OPERATION OF THE EQUIPMENT. WHERE A SUITABLE STRUCTURAL WALL IS NOT AVAILABLE, PROVIDE SUPPORT FRAME AND
CONNECT THE SUPPORT FRAME WITH A MINIMUM OF (4) POINTS OF CONTACT TO THE BUILDING STRUCTURE TO PROVIDE A
RIGID ASSEMBLY. OPTION 1, 2, OR 3 MAY BE UTILIZED TO PROVIDE THE…