00_Combined.pdf

PDF 7 MB Posted

Attached to
Z2DA--MCC Panel BF118 and ATS Replacement Federal contract opportunity
Solicitation number
36C25924R0103
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19

About this file

This document appears to be a set of technical drawings and specifications for the replacement of MCC Panel BF118 and the Automatic Transfer Switch (ATS) at the Oklahoma City VA Health Care System. The key details are:

The project involves replacing the existing MCC panel BF118 and the existing ATS-6 with a new 600A, 480Y/277V, 3-phase, 4-wire motor control center (EMCC-1) and a new 600A, 480Y/277V, 4-pole ATS-6 with isolation bypass. New conduit, conductors, and supporting equipment will be installed. The work will be done in phases to maintain operations, with a temporary 400A panel used during the transition. Existing branch circuit loads will be de-energized, disconnected, and reconnected to the new EMCC-1. This project is part of VA solicitation number 36C25924R0103 issued by the Department of Veterans Affairs - Veterans Integrated Service Network 19.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--MCC Panel BF118 and ATS Replacement, newest first.
File Type Posted
round two questions.pdf PDF
36C25924R0103 0003.docx DOCX document
36C25924R0103 0002.docx DOCX document
36C25924R0103 0001.docx DOCX document
635-21-118_100 CD Specifications.pdf PDF
S22- 852.219-75 LOS Certification.docx DOCX document
S02-3-10-2021 Past Performance Questionnaire_Blank_Fillable PDF.pdf PDF
36C25924R0103_1.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

PROJECT NUMBERCONSULTANTS:

DRAWING #

U.S. DEPARTMENT OF VETERANS AFFAIRS

VA HEALTH CARE SYSTEM APPROVAL:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. CA02295 EXP. 06/30/2025

ENGR REG. NO. CA7127 EXP. 06/30/2025

ELECTRICAL ENGINEER

SPUR DESIGN

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

DRAWING NUMBER

BUILDING NUMBER

/1

/2

:2 :2

P

M

COVER SHEET

CAB 1 OF 9BKM

100% CONSTRUCTION DOCUMENTS

REPLACE MCC PANEL BF118

VA PROJECT NUMBER: 635-23-118

REPLACE MCC PANEL BF118

03/18/2024

635-23-118

OKLAHOMA CITY VAHCS

921 NE 13TH STREET

OKLAHOMA CITY, OK 73104

OKLAHOMA CITY VAHCS

921 NE 13TH STREET

OKLAHOMA CITY, OK 73104

100% CONSTRUCTION DOCUMENTS

GI000

SPUR #: 2093.05

SHEET INDEX

SEQUENCE NUMBER SHEET NAME

[01] GENERAL

1 GI000 COVER SHEET

2 GI001 GENERAL INFORMATION

ELECTRICAL

3 E-000 ELECTRICAL SYMBOLS & ABBREVIATIONS

4 E-100 ELECTRICAL REFERENCE PLAN - BASEMENT LEVEL

5 ED101 ELECTRICAL POWER DEMOLITION PLAN

6 EP101 ELECTRICAL POWER FLOOR PLAN

7 E-501 ELECTRICAL SCHEDULES & DETAILS

8 E-601 ELECTRICAL ONE-LINE DIAGRAM - TEMPORARY & DEMOLITION CONFIGURATION

9 E-602 ELECTRICAL ONE-LINE DIAGRAM - NEW CONFIGURATION

TOTAL SHEETS: 9

LOCATION

PLAN

AREA

PLAN

N N

NE 13TH ST

N K

E

LL

E Y

A V

E

N L

IN

D

S A

Y A

V E

NE 16TH ST

NE 14TH ST

NE 15TH ST

NE 13TH ST

NE 10TH ST

N L

IN

C

O

LN

A V

E

N L

O T

T

IE

A V

E

NE 16TH ST

N K

E

LL

E Y

A V

E

PROJECT

LOCATION

No. REVISION DESCRIPTION DATE

ABBREVIATIONS CODES STANDARDS AND EXECUTIVE ORDERS

4' -0

M

A X

4' -0

M

A X

2' -1

0" M

A X

2' -3

M

IN

1'-6" MIN

1. GENERAL CONTRACTOR TO PROVIDE METAL SUPPORT

BLOCKING FOR ALL WALL MOUNTED ACCESSORIES,

FIXTURES, AND EQUIPMENT.

2. PROVIDE ADA SUPPORT BRACKETS PLACED AT ALL OPEN

COUNTERTOPS @ 36"-48" MAX ON CENTER.

3. SPECIFIED MAXIMUMS ARE MEASURED FROM AFTER

FINISHED FLOOR TO THE OPERABLE PART OF THE FIXTURE.

4. FIXTURES SHOWN ARE REPRESENTATIONAL ONLY. NOT ALL

FIXTURES MAY BE USED. REFER TO SPECIFICATIONS FOR

FIXTURE TYPES USED IN THIS PROJECT.

5. FIXTURES MAY OVERLAP WAINSCOT. WHERE APPLICABLE,

BACKING TO BE PROVIDED AS SHIM FOR FLUSH

APPLICATION. SHIM TO MATCH SCHEDULED WALL FINISH.

6" MAX

9" M

IN

SHOWER

VA TOILET ROOM

TURNING RADIUS

DRINKING

FOUNTAIN

PAPER TOWEL

DISPENSER

SANITARY

NAPKIN

DISPENSER

4' -0

"M A

X

WASTE

RECEPTACLE

LAVATORY

WITH MIRROR

ON CENTER

WALL

4' -0

M

A X

SOAP

DISPENSER

2' -1

0" M

A X

T O

B .O

. R E

F

LE

C T

IV

E

S U

R F

A C

E

3' -4

"M A

X

17 MIN

2' -3

M

IN

3' -0

M

A X

1'-6" MIN

WALL

2' -9

3' -0

3' -2

4' -0

2'-0" MIN

8" MIN

WALL

LAVATORY

WITH APRON

1' -5

M

A X

1'-6" MIN

URINAL

WALL

1'-5" - 1'-7" (AMBULATORY)

1'-4" - 1'-6" (WHEELCHAIR)

CLEAR FLOOR

5'-6"

CLEAR FLOOR

6'-0"

3'-0" MIN

2' -9

3' -0

1'-0" MIN

3'-6" MIN 1'-0"MAX

4'-6" MIN

1' -5

'-7

1' -6

M

IN

A N

S I I

C C

A

7.

1)

1' -3

M

IN

A D

A /A

B A

2' -9

3' -0

WALL

WALL

4' -0

M

A X

WALL HOOK

7' -0

CLOCK

WALL

FINISHED FLOOR

FIRE EXTINGUISHER

CABINET

WEIGHT > 40LBS

FIRE EXTINGUISHER

CABINET

WEIGHT < 40LBS

4' -0

"M A

X

4' -0

M

A X

TOILET SEAT

COVER

DISPENSER

BABY

CHANGING

STATION

CLEAR FLOOR SPACE

@ WATER CLOSET

5'-6"

2'-6"

4' -0

2'-6"

4' -0

HANDRAILS AND

BUMPER GUARDS

FIXTURE MOUNTING HEIGHTS AND CLEARANCES

18" MIN

M

IN

FRONT APPROACH,

PULL SIDE

36" MIN

M

IN

HINGE APPROACH,

PULL SIDE

HINGE APPROACH,

PULL SIDE

*12" MIN48

M

IN

FRONT APPROACH,

PUSH SIDE

M

IN

HINGE APPROACH,

PUSH SIDE

22" MIN 24" MIN

*4 8"

M

IN

LATCH APPROACH,

PULL SIDE

24" MIN*4

2"

M

IN

LATCH APPROACH,

PUSH SIDE

*IF BOTH CLOSER

AND LATCH ARE

PROVIDED

*54" MIN IF CLOSER

IS PROVIDED

*48" IF CLOSER IS

PROVIDED

FRONT APPROACH,

PUSH SIDE

M

IN

42" MIN

DOOR AND FIXTURE CLEARANCES

MATERIALS LEGEND

PURPOSE: THE PUBLIC BUILDINGS AMENDMENT ACT OF 1988, PUBLIC LAW (PUB. L.) 100-678 REQUIRES FEDERAL AGENCIES TO FOLLOW NATIONAL RECOGNIZED "MODEL" BUILDING CODES. THE FEDERAL PARTICIPATION IN THE DEVELOPMENT AND USE OF VOLUNTARY STANDARDS, OFFICE OF MANAGEMENT AND BUDGET (OMB) CIRCULAR A-119, REQUIRES ALL EXECUTIVE AGENCIES TO RELY ON VOLUNTARY STANDARDS, BOTH DOMESTIC AND INTERNATIONAL, WHENEVER FEASIBLE, AND TO PARTICIPATE IN

VOLUNTARY STANDARD BODIES.

GENERAL: VA HAS ADOPTED THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS AS A MINIMUM FOR ALL PROJECTS PERFORMED IN THE MODERNIZATION, ALTERATION, ADDITION, OR IMPROVEMENT OF ITS REAL PROPERTY AND THE CONSTRUCTION OF NEW STRUCTURES. VA DESIGN MANUALS AND MASTER SPECIFICATIONS SPECIFY OTHER CODES AND STANDARDS THAT VA FOLLOWS ON ITS PROJECTS. REFERENCE RELEVANT ADDENDA FOR EACH OF THE ADOPTED CODES AND STANDARDS:

• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL

INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).

• 2024 INTERNATIONAL BUILDING CODE (IBC) (ONLY WHEN SPECIFICALLY REFERENCED IN VA DESIGN DOCUMENTS, SEE NOTES BELOW)

• 2024 INTERNATIONAL EXISTING BUILDING CODE (IEBC) (IF APPLICABLE)

• 2024 NFPA 101 LIFE SAFETY CODE (SEE NOTES BELOW)

• 2024 NATIONAL FIRE CODES (NFPA)

• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.

• 2023 VA SEISMIC DESIGN REQUIREMENTS, H-18-8

• 2024 INTERNATIONAL MECHANICAL CODE

• 2023 NATIONAL ELECTRICAL CODE (NEC), NFPA 70

• 2024 INTERNATIONAL PLUMBING CODE (IPC)

• 2019 SAFETY CODE FOR ELEVATORS AND ESCALATORS, AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME) A 17.1.

• 2022 ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS INCLUDING VA SUPPLEMENT, VA BARRIER FREE DESIGN STANDARD (PG-18-13)

• 2022 ANSI ICC A117.1 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES

• 2022 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE AND COMMENTARY, AMERICAN CONCRETE INSTITUTE AND COMMENTARY (ACI 318-19)

• 2023 STEEL CONSTRUCTION MANUAL (16TH EDITION), AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)

• ENERGY POLICY ACT OF 2005 (EPACT)

• 2007 DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL, COMMERCIAL AND MULTI-FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND

NEW LOW-RISE RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434 AND 435.

• 2006 FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM OF UNDERSTANDING (MOU)

• 2018 EXECUTIVE ORDER 13834: EFFICIENT FEDERAL OPERATIONS

• 2021 THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL REQUIREMENTS SECTION 010000 OF THE VA MASTER CONSTRUCTION

SPECIFICATION.

• 2022 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE STANDARD 62.1

• 2022 SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE STANDARD 15

• 2023 PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL

LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES. HOWEVER, LOCAL AUTHORITIES SHOULD BE NOTIFIED ABOUT PLANNED PROJECTS AND GIVEN OPPORTUNITY TO REVIEW DRAWINGS PROVIDED THAT VA DOES NOT PAY FOR REVIEW OR INSPECTION FEES.

NOTES:

1. NFPA 101 PRIMARILY ADDRESSES LIFE SAFETY AND FIRE PROTECTION FEATURES WHILE THE IBC ADDRESSES A WIDE RANGE OF CONSIDERATIONS, INCLUDING, BUT

NOT LIMITED TO, STRUCTURAL STRENGTH, SEISMIC STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION, AND ENERGY CONSERVATION. VA BUILDINGS MUST MEET THE REQUIREMENTS OF NFPA 101 AND DOCUMENTS REFERENCED BY NFPA 101 IN ORDER TO COMPLY WITH THE ACCREDITATION REQUIREMENTS OF THE JOINT COMMISSION. THEREFORE, DESIGNS SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF NFPA 101 AND DOCUMENTS REFERENCED THEREIN.

DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE ADDRESSED ABOVE IN THIS PROGRAM GUIDE. FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES

EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT).

2. CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY SYSTEM WIDE.

ASHRAE 90.1 - 2019 EDITION

BUILDING LOCATION: OKLAHOMA CITY, OK

CLIMATE ZONE (TABLE ANNEX 1-1): ZONE 3A

INTERIOR DESIGN CONDITIONS:

THE INTERIOR DESIGN TEMPERATURES FOR HEATING AND COOLING AS DEPICTED IN THE PROJECT DESIGN CONDITIONS SCHEDULE IN THE MECHANICAL CONTROL DRAWINGS SHALL BE THE MAXIMUM

AND MINIMUM VALUES FOR THE ASSOCIATED TEMPERATURE CONTROL ZONES.

BUILDING ENVELOPE REQUIREMENTS (5.5 )

BUILDING ENVELOPE REQUIREMENTS FOR CLIMATE ZONE 3 (A,B,C)

ROOFS REQUIRED DESIGNED

INSULATION: R-25 c.i. EXISTING

METAL BUILDINGS: R-10 + R-19 FC EXISTING

ATTIC AND OTHER: R-38 EXISTING

WALLS, ABOVE GRADE

MASS: R-7.6 c.i. EXISTING METAL BUILDING: R-0 + R-9.8 c.i. EXISTING STEEL-FRAMED: R-13 + R-5 c.i. EXISTING

WOOD-FRAMED AND OTHER: R-13 EXISTING

WALL, BELOW GRADE

BELOW-GRADE WALL: NR EXISTING

FLOORS

MASS: R-10 c.i. EXISTING

STEEL-FRAMED: R-30 EXISTING

WOOD-FRAMED AND OTHER: R-30 EXISTING

SLAB-ON-GRADE FLOORS

UNHEATED SLABS: NR EXISTING

HEATED SLABS: R-15 for 24 in. EXISTING

OPAQUE DOORS

SWINGING: U-0.370 EXISTING

NONSWINGING: U-0.310 EXISTING

FENESTRATION (TABLE 5.5-4):

VERTICAL FENESTRATION, U-FACTOR

FIXED: U-0.42 EXISTING

OPERABLE: U-0.54 EXISTING

ENTRANCE DOOR: U-0.68 EXISTING

DEFINITIONS

c.i = CONTINUOUS INSULATION Ls = LINEAR SYSTEM

NR = NO (INSULATION) REQUIREMENT

ENERGY REQUIREMENTS

N

1. DRAWINGS ARE PART OF A COMPLETE DOCUMENTS SET. CONTRACTOR SHALL CONFIRM

ALL ITEMS REQUIRED BASED UPON THE OVERALL DESIGN INTENT OF THE ENTIRE

DOCUMENT SET.

2. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, PRIOR TO BEGINNING ANY WORK,

TO CONFIRM THE ACCURACY OF THE DRAWINGS AND REPORT ANY DISCREPANCIES TO

THE ARCHITECT. DO NOT SCALE THE DRAWINGS. FIELD VERIFY ALL DIMENSIONS AND

EXISTING STRUCTURAL CONDITIONS.

3. ALL AREAS NOT INVOLVED IN THE SCOPE OF WORK FOR THIS PROJECT SHALL BE KEPT

CLEAN AND FREE OF OBSTRUCTIONS AT ALL TIMES.

4. ERECT BARRICADES AND WARNING SIGNS TO DIVERT AND WARN PASSERS-BY OF THE

CONSTRUCTION WORK. PROVIDE DUST PROOFING ENCLOSURES TO SEPARATE WORK

AREAS FROM THE EXISTING FACILITIES.

5. ALL TRASH AND DEBRIS TO BE REMOVED ON A DAILY BASIS.

6. PROVIDE PROTECTION FOR ALL EXISTING SURFACES AND CONDITIONS TO REMAIN IN

PLACE DURING THE SCOPE OF WORK. SHOULD ANY DAMAGE OCCUR, PATCH AND REPAIR

ANY DAMAGE TO ADJACENT FINISHES TO MATCH EXISTING.

7. ANY DAMAGE CAUSED TO THE BUILDING OR OWNER EQUIPMENT SHALL BE REPAIRED OR

REPLACED BACK TO ITS ORIGINAL CONDITIONS AT NO ADDITIONAL COST TO THE OWNER.

8. COVER ALL RETURN AIR GRILLES WITHIN THE AREA OF CONSTRUCTION TO PREVENT

PARTICULATE MATERIAL FROM EXHAUSTING INTO SURROUNDING SPACES.

9. APPROPRIATE LIGHT FIXTURES SHALL BE TEMPORARILY SUSPENDED TO PROVIDE

ADEQUATE LIGHTING LEVELS FOR CONSTRUCTION.

10. CONTRACTOR AND SUBCONTRACTORS ARE REQUIRED TO COORDINATE WITH OTHER

DISCIPLINES TO INSTALL COMPLETE AND OPERATIONAL SYSTEMS. DRAWINGS, AS A

WHOLE, REPRESENT A COMPLETE SET AND DEPICT REQUIREMENTS FOR COMPLETE AND

OPERATIONAL SYSTEMS. INDIVIDUAL DRAWINGS MAY NOT DEPICT COMPLETE AND

ACCURATE INFORMATION TO COORDINATE COMPLETE AND OPERATIONAL SYSTEMS, BUT

DO SO AS AN ENTIRE DOCUMENT TO BE REFERENCED WITH OTHER INDIVIDUAL DRAWINGS.

CONTRACTOR AND SUBCONTRACTORS ARE REQUIRED TO REFERENCE OTHER SHEETS

AND SPECIFICATIONS AS AN ENTIRE SET OF CONSTRUCTION DOCUMENTS THAT REFLECT

WORK REQUIRED TO ACHIEVE A COMPLETE AND OPERATIONAL GOAL. LACK OF

COORDINATION AND REVIEW OF DRAWINGS AND SPECIFICATIONS AS AN ENTIRE

DOCUMENT TO INSTALL COMPLETE AND OPERATIONAL SYSTEMS, BEING OBVIOUS AND

TYPICAL INDUSTRY STANDARD, IDENTIFIED IN THE DRAWINGS AND SPECIFICATIONS, SHALL

NOT BE IN ANY WAY AN ADDITIONAL COST TO THE GOVERNMENT.

11. CONTRACTOR SHALL SUBMIT A REQUEST, IN WRITING, TO INTERRUPT ANY SERVICES,

SUCH AS WATER, GAS, STEAM, SEWERS, ELECTRICITY, FIRE PROTECTION, OR

COMMUNICATIONS SYSTEMS, TO COR (CONTRACTING OFFICER’S REPRESENTATIVE) 7

DAYS IN ADVANCE OF PROPOSED INTERRUPTION. REQUEST SHALL STATE REASON, DATE,

EXACT TIME OF, AND APPROXIMATE DURATION OF SUCH INTERRUPTION. MAJOR

INTERRUPTIONS OF ANY SYSTEM MUST BE REQUESTED, IN WRITING, AT LEAST 15

CALENDAR DAYS PRIOR TO THE DESIRED TIME AND SHALL BE PERFORMED AS DIRECTED

BY THE COR. MAJOR INTERRUPTIONS SHALL BE COORDINATED WITH OTHER MAJOR

INTERRUPTIONS AND MAY NOT BE SCHEDULED FOR ONE DISCIPLINE MORE THAN TWICE

THROUGHOUT THE OVERALL CONSTRUCTION SCHEDULE UNLESS REQUESTED IN WRITING

AND APPROVED BY THE COR. CONTRACTOR WILL BE ADVISED, IN WRITING, OF APPROVAL

OF REQUEST, OR OF WHICH OTHER DATE AND/OR TIME SUCH INTERRUPTION WILL CAUSE

THE LEAST INCONVENIENCE TO OPERATIONS OF THE MEDICAL CENTER. INTERRUPTION

TIME APPROVED BY THE MEDICAL CENTER MAY OCCUR AT TIMES OTHER THAN

CONTRACTOR'S NORMAL WORKING HOURS. SCHEDULE INTERRUPTION MAY BE ON

WEEKENDS OR LATE HOURS AND MAY NOT BE AN ADDITIONAL COST TO THE GOVERNMENT.

COORDINATE ALL INTERRUPTIONS THAT MAY AFFECT THE NORMAL OPERATION OF THE

FACILITY WITH THE COR WHEN SUBMITTING THE CONSTRUCTION SCHEDULE OR UPDATES

TO THE CONSTRUCTION SCHEDULE.

12. NO ASBESTOS CONTAINING MATERIALS ARE TO BE USED ON THIS PROJECT. SPUR DESIGN, THE A/E OF RECORD, CAN CERTIFY THAT NO ASBESTOS CONTAINING BUILDING MATERIALS

(ACBM) OR LEAD BASED PAINT (LBP) PRODUCTS WERE DESIGNED/SPECIFIED AS BUILDING

MATERIAL IN ANY OF THE CONSTRUCTION DOCUMENTS.

13. REFERENCE ELECTRICAL DRAWINGS FOR CONCRETE HOUSEKEEPING PAD DETAIL,

LOCATIONS OF FIRE RATED WALLS AND FIRE PROTECTION/ SPRINKLER HEAD REROUTING

INFORMATION.

14. PROVIDE FIRE STOPPING AROUND ALL PENETRATIONS THROUGH RATED WALLS.

REFERENCE SHEET E-100.

GENERAL NOTES

AREA NAME

150 SF

A101

A101

SIM

A

00.0

A101

1 1

A101

LEVEL NAME

00'-00"

00'-00" 4B

3A

FIBERGLASS BATT

INSULATION

RIGID INSULATION

CONCRETE / PRECAST

CONCRETE

EARTH / SOIL

SAND, EIFS FINISH, OR

PLASTER FINISH

GYPSUM BOARD FINISH

BRICK

CONCRETE MASONRY

UNIT

STONE / CAST STONE

GYPSUM BOARD SECTION

EXTERIOR SHEATHING

BOARD SECTION

PLYWOOD SECTION

CLEAN UTILITY

000A

/1 A101

X0000

6"2' -1

0"

'-2

ROOM TAG

AREA TAG

SPECIALTY EQUIPMENT TAG

DOOR TAG

KEYED NOTE TAG

WALL TAG

WINDOW TAG

A101

SIM

A101

SIM

A

ACB ACOUSTIC CEILING BAFFLE

ACP ACOUSTIC CEILING PANEL

ACST ACOUSTIC

ADA AMERICANS WITH DISABILITIES ACT

ACT ACOUSTICAL CEILING TILE

ADDL ADDITIONAL

ADDN ADDITION

ADJ ADJACENT, ADJOINING, OR

ADJUSTABLE

ADMIN ADMINISTRATION

AE ARCHITECT/ENGINEER

AF ACCESS FLOORING

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING JURISDICTION

AIA AMERICAN INSTITUTE OF

ARCHITECTS

ALT ALTERNATE

ALT NO ALTERNATE NUMBER

ALUM ALUMINIUM (TRIM)

AMT AMOUNT

APPROX APPROXIMATE

ARCH ARCHITECT

ASC ABOVE SUSPENDED CEILING

AT ACOUSTIC CEILING TILE

AVG AVERAGE

B

BD BOARD

BG BUMPER GUARD

BLDG BUILDING

BLKG BLOCKING

BLT IN BUILT-IN

BOS BOTTOM OF STEEL

BOT BOTTOM

BRKT BRACKET

BTWN BETWEEN

C

CAB CABINET

CAV CAVITY

CBB CONCRETE BACKER BOARD

CC CONTRACTOR PROVIDED /

CONTRACTOR INSTALLED

CD CONSTRUCTION DOCUMENTS

CFM CUBIC FEET PER MINUTE

CFS CUBIC FEET PER SECOND

CG CORNER GUARD

CH BD CHALKBOARD

CIP CAST-IN-PLACE

CJ CONTROL JOINT

CL CENTERLINE

CLG CEILING

CLG HT CEILING HEIGHT

CLR CLEAR

CMU CONCRETE MASONRY UNIT

CO CONTRACTING OFFICER

COL COLUMN

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUOUS

COORD COORDINATE

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CP CONTRACTOR PROVIDED

CPT CARPET/CARPET TILE

CS CONCRETE SEALED

CSWK CASEWORK

CT CERAMIC TILE

CTB CERAMIC TILE BASE

CTR CENTER

CU FT CUBIC FEET

D

DBL DOUBLE

DEMO DEMOLITION

DEPT DEPARTMENT

DET DETAIL

DIA DIAMETER

DIR DIRECTION

DIST DISTANCE

DOC DOCUMENT

DR DOOR

DS DOWNSPOUT

DWG DRAWING

DWP DIMENSIONAL WALL PANEL

E

EA EACH

EJ EXPANSION JOINT

EL ELEVATION

ELEV ELEVATOR

ENTR ENTRANCE

EPY EPOXY FLOORING

EQ EQUAL

ETR EXISTING TO REMAIN

EX EXISTING

EXP EXPOSED

EXT EXTERIOR

F

FAB FABRIC

FED FEDERAL

FF FINISH FACE

FF EL FINISH FLOOR ELEVATION

FIN FINISH

FIN BS FINISH BOTH SIDES

FIN FLR FINISH FLOOR

FIN GR FINISH GRADE

FIXT FIXTURE

FLDG FOLDING

FLEX FLEXIBLE

FLG FLOORING

FLMT FLUSH MOUNT

FLR FLOOR

FOC FACE OF CONCRETE

FOM FACE OF MASONRY

FP FIRE PROTECTION

FR FIRE RESISTANT

FT FEET

FTG FOOTING

FV FIELD VERIFY

FWC FABRIC WALL COVERING

G

GDR GUARDRAIL

GL GLASS/GLAZING

GRAN GRANITE

GR FL GROUND FLOOR

GT GROUT

GSM GALVANIZED SHEET METAL

GYP BD GYPSUM BOARD

H

HDW HARDWARE

HEPA HIGH EFFICIENCY

PARTICULATE AIR (FILTER)

HM HOLLOW METAL

HORIZ HORIZONTAL

HR HANDRAIL

HT HEIGHT

I

IBC INTERNATIONAL BUILDING CODE

INSUL INSULATION

INT INTERIOR

ILO IN LIEU OF

J

J-BOX JUNCTION BOX

L

LAV LAVATORY

LBS POUND

LDG LANDING

LF LINEAR FEET (FOOT)

LIN LINEAR

LN LINOLEUM

LOC LOCATION

LT LIGHT

LVR LOUVER

LVT LUXURY VINYL TILE

M

MAT CARPET MAT / WALK-OFF MAT

MATL MATERIAL

MAX MAXIMUM

MECH MECHANICAL

MEMB MEMBRANE

MFR MANUFACTURER

MID MIDDLE

MIL STD MILITARY STANDARD

MIN MINIMUM

MISC MISCELLANEOUS

MO MASONRY OPENING

MOD MODIFY

MTG MOUNTING

MTL METAL

MVBL MOVABLE

N

NA NOT APPLICABLE

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NTS NOT TO SCALE

O

OA OVERALL

OC ON CENTER

OD OUTSIDE DIAMETER

OPNG OPENING

OPP OPPOSITE

OPR OPERABLE

ORD OVERFLOW ROOF DRAIN

ORIG ORIGINAL

P

P PAINT

PA PUBLIC ADDRESS

PBD PARTICLE BOARD

PCF POUNDS PER CUBIC FOOT

PCT PERCENT

PERF PERFORATED

PERIM PERIMETER

PERP PERPENDICULAR

PL PROPERTY LINE

PLAM PLASTIC LAMINATE

PLBG PLUMBING

PNL PANEL

PR PAIR

PRB PROFILE BASE

PRKG PARKING

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PORCELAIN TILE

PWR POWER

Q

QA QUALITY ASSURANCE

QC QUALITY CONTROL

QTY QUANTITY

REFERENCE SYMBOLS IDENTIFICATION TAGS

NOTE: NOT ALL ABBREVIATIONS OR SYMBOLS WILL BE UTILIZED FOR THIS PROJECT.

GRID HEAD AND

LINE

LEVEL INDICATOR

MATCH LINE AND

VIEW REFERENCE

NORTH ARROW W/

PROJECT NORTH

SPOT ELEVATION

DETAIL

SECTION

**48" MIN IF BOTH CLOSER

AND LATCH PROVIDED

WALL

SECTION

BUILDING

SECTION

DETAIL

ELEVATION

INTERIOR

ELEVATION

BUILDING

ELEVATION

1 1

6'- 0"

5'- 6"

BARIATRIC TOILET ROOM

TURNING RADIUS

CLEAR FLOOR SPACE

@ ADA LAVATORY

CLEAR FLOOR SPACE @ ADA

DRINKING FOUNTAIN

4"

6"

3"

1' -6

6" MAX

7" - 9" 11" MIN

17" - 25"

M

IN

6' -0

(ANSI ICC A117.1)

39"- 41"

(A N

S I I

C C

A

7.

1)

M

IN

(A N

S I I

C C

A

7.

1)

1"

3' -6

M

A X

5' -0

M

A X

R

RAF RESILIENT ATHLETIC FLOORING

RB RUBBER BASE/RESILIENT BASE

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

REC RECESSED

REF REFERENCE

REM REMOVABLE

REP REPAIR

REPL REPLACE

REQ REQUIRE

REQD REQUIRED

RES RESINOUS FLOORING

RES-W RESINOUS / EPOXY WALL / CEILING

RF RUBBER FLOORING

RFG ROOFING

RM ROOM

RO ROUGH OPENING

RP RESIN PANEL

RSF RESILIENT SHEET FLOORING

RV ROOF VENT

RWC RIGID VINYL WALLCOVERING

S

SC SPECIALTY COATING

SD STATIC DISSIPATIVE FLOORING/TILE

SCHED SCHEDULE

SECT SECTION

SF SQUARE FOOT (FEET)

SGL SINGLE

SIM SIMILAR

SJ SCORED JOINT

SLNT SEALANT

SM SHEET METAL

SPEC SPECIFICATION

SQ SQUARE

SQ IN SQUARE INCH

SQ YD SQUARE YARD

SS SOLID SURFACE

ST STONE

STD STANDARD

STOR STORAGE

SV SHEET VINYL (ROLLED OR TILE)

T

TEL TELEPHONE

TEMP TEMPORARY

TER TERRAZZO

TOF TOP OF FOOTING/ FOUNDATION

TOM TOP OF MASONRY

TOS TOP OF SLAB/ STEEL

U

UNO UNLESS NOTED OTHERWISE

UTIL UTILITY

V

VAR VARIES

VC VA PROVIDED / CONTRACTOR

INSTALLED

VCT VINYL COMPOSITION TILE

VFAT VINYL-FACED ACOUSTICAL TILE

VP VENEERED PLASTER

VT VINYL TILE

VV VA PROVIDED / VA INSTALLED

VWC VINYL WALLCOVERING

VWF VINYL WALL FABRIC

W

W/ WITH

W/O WITHOUT

W/C WATER CLOSET

WC WHEELCHAIR

WD WOOD

WFAB WALL FABRIC

WPM WATERPROOF MEMBRANE

WSF WELDED SHEET FLOOR

X

X BRACE CROSS BRACE

TRUE

NORTH

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

PROJECT NUMBERCONSULTANTS:

DRAWING #

VA HEALTH CARE SYSTEM APPROVAL:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. CA02295 EXP. 06/30/2025

ENGR REG. NO. CA7127 EXP. 06/30/2025

ELECTRICAL ENGINEER

SPUR DESIGN

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

DRAWING NUMBER

BUILDING NUMBER

/1

/2

:2 :2

P

M

GENERAL INFORMATION

CAB 2 OF 9BKM

100% CONSTRUCTION DOCUMENTS

REPLACE MCC PANEL BF118

03/18/2024

635-23-118

OKLAHOMA CITY VAHCS

921 NE 13TH STREET

OKLAHOMA CITY, OK 73104

GI001

SPUR #: 2093.05No. REVISION DESCRIPTION DATE

UE

OE

M/G 400A/3P

M/G 400A/3P

C

PC

R

TS

T

100/3

100/3/70

100/3/70/1

100/3/CB

PP

J

GF

OR

OR

OR

EPO

AM

VM

DM

ST

KK

GFR

M

SPD

R

LP1

1,3,5

A1

LIGHT FIXTURE, CEILING MOUNTED

A1 = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT

FIXTURE SCHEDULE

a = SWITCHED BY SWITCH "a"

NL = NIGHT LIGHT

= ARROW INDICATES AIMING DIRECTION

a

LIGHTING TRACK WITH TRACK LIGHT FIXTURES

A1E = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT

FIXTURE SCHEDULE

a = SWITCHED BY SWITCH "a"

LIGHT FIXTURE, POLE MOUNTED

A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT

FIXTURE SCHEDULE

LIGHT FIXTURE, WALL MOUNTED

A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT

FIXTURE SCHEDULE

EMERGENCY BATTERY PACK LIGHT FIXTURE,

WALL MOUNTED

Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT

FIXTURE SCHEDULe

EMERGENCY BATTERY PACK LIGHT FIXTURE,

CEILING MOUNTED

Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT

FIXTURE SCHEDULE

EXIT SIGN, WALL MOUNTED, FACE/ARROWS AS INDICATED

X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT

FIXTURE SCHEDULE

EXIT SIGN, CEILING MOUNTED, FACE/ARROWS AS INDICATED

X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT

FIXTURE SCHEDULE

EMERGENCY LIGHT FIXTURE, CEILING MOUNTED

A1E = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT

FIXTURE SCHEDULE

a = SWITCHED BY SWITCH "a"

NL = NIGHT LIGHT

A1E a

A1 a

A1

A1

X1E

X1E

Y1E

Y1E

HOMERUN TO PANELBOARD

TICK MARKS INDICATE NUMBER OF CONDUCTORS.

DESIGNATIONS ARE PANELBOARD AND

CIRCUIT NUMBERS.

UNSWITCHED HOT CONDUCTORS SHOWN LEADING

NEUTRAL CONDUCTOR

NEUTRAL CONDUCTOR

SWITCHED HOT CONDUCTORS SHOWN TRAILING

GROUND CONDUCTOR

EQUIPMENT GROUNDING CONDUCTOR IN RACEWAY

ISOLATED GROUNDING CONDUCTOR IN RACEWAY

CONCEALED RACEWAY

EXPOSED RACEWAY

RACEWAY TURNING DOWN

RACEWAY TURNING UP

EQUIPMENT TERMINATION

LOW VOLTAGE CABLE (NOT ROUTED IN CONDUIT)

LIGHT FIXTURE, BOLLARD

A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT

FIXTURE SCHEDULE

A1

RECEPTACLE, SIMPLEX, NEMA 5-20R, UNO

RECEPTACLE, DUPLEX, NEMA 5-20R, UNO

RECEPTACLE, DOUBLE-DUPLEX, NEMA 5-20R, UNO

RECEPTACLE, DUPLEX, CEILING MOUNTED, NEMA 5-20R, UNO

RECEPTACLE, SPECIAL PURPOSE

RECEPTACLE, TWIST-LOCK

RECEPTACLE, DUPLEX, FLOOR MOUNTED, NEMA 5-20R, UNO

RECEPTACLE, DUPLEX, DROP CORD, NEMA 5-20R, UNO

RECEPTACLE, MOUNTED 6" ABOVE COUNTER,

TYPE AS INDICATED ABOVE

RECEPTACLE DESIGNATIONS AS FOLLOWS:

C = CLOCK HANGER

E = EMERGENCY POWER

GF = GROUND FAULT CIRCUIT INTERRUPTER

IG = ISOLATED GROUND

S = SWITCHED

TR = TAMPER RESITANT

WP = WEATHER PROOF COVER

WR = WEATHER RESISTANT

XP = EXPLOSION PROOF

SWITCH, SINGLE POLE

SWITCH DESIGNATIONS AS FOLLOWS:

2 = TWO-POLE WALL SWITCH

3 = THREE-WAY WALL SWITCH

4 = FOUR-WAY WALL SWITCH

D = DIMMER SWITCH

OS# = OCCUPANCY SENSOR WALL SWITCH, REFER

TO OCCUPANCY SENSOR AND SWITCH SCHEDULE

P = SINGLE-POLE, SINGLE-THROW PILOT LIGHT

WALL SWITCH

K = KEYED WALL SWITCH

M = MOTOR RATED SWITCH

WP = WEATHER PROOF SWITCH AND COVER

OCCUPANCY SENSOR, CEILING MOUNTED

OS# = CEILING MOUNTED OCCUPANCY SENSOR, REFER

TO OCCUPANCY SENSOR AND SWITCH SCHEDULE

POWER PACK FOR LIGHTING CONTROL

JUNCTION BOX

RECEPTACLE ON EMERGENCY POWER

RECEPTACLE, ISOLATED GROUND TYPE

MULTI-OUTLET, SURFACE RACEWAY, 24" ON CENTER,

NEMA 5-20R, UNO

SWITCHBOARD, MOTOR CONTROL CENTER OR DISTRIBUTION

PANELBOARD ON HOUSEKEEPING PAD

PANELBOARD, RECESS MOUNTED

PANELBOARD, SURFACE MOUNTED

TRANSFORMER

DISCONNECT SWITCH, NON-FUSED, 100/3 INDICATES

AMPERES/POLES, CB = CIRCUIT BREAKER TYPE

DISCONNECT SWITCH, FUSED, 100/3/70 INDICATES

AMPERES/POLES/FUSE, CB = CIRCUIT BREAKER TYPE

COMBINATION DISCONNECT SWITCH WITH MOTOR STARTER

100/3/70/1 INDICATES AMPERES/POLES/FUSE/ NEMA STARTER

SIZE, NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE

MAGNETIC MOTOR STARTER, NEMA SIZE AS NOTED,

3-POLE, UNO

CONTACTOR

PHOTOCELL

RELAY

TIME SWITCH

LOW-VOLTAGE TRANSFORMER

PUSH BUTTON, TYPE AS NOTED

VARIABLE FREQUENCY DRIVE WITH DISCONNECT SWITCH

100/3/70 INDICATES AMPERES/POLES/FUSE SIZE,

NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE

UNDERGROUND ELECTRIC LINE

MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

CABINET, RECESS MOUNTED

CABINET, SURFACE MOUNTED

RECEPTACLE, DUPLEX, GROUND-FAULT CIRCUIT

INTERRUPTER, NEMA 5-20R, UNO

MULTI-SERVICE POWER POLE WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

OVERHEAD ELECTRIC LINE

MUSHROOM TYPE PUSH BUTTON, TYPE AS NOTED

TRANSFER SWITCH, RATINGS AS INDICATED

ATS = AUTOMATIC TRANSFER SWITCH

MTS = MANUAL TRANSFER SWITCH

TX#

600AF

500AT

3P

400AS

3P

225AF

LPS-R

275KW STANDBY

480Y/277V, 3PH, 4W

GENERATOR, SEPARATELY DERIVED

SOURCE, TYPE AND RATINGS AS INDICATED

275KW STANDBY

480Y/277V, 3PH, 4W

GENERATOR, NON-SEPARATELY DERIVED

SOURCE, TYPE AND RATINGS AS INDICATED

DRAWOUT CIRCUIT

BREAKER, RATINGS

AS INDICATED

600AF

500AT

3P

CIRCUIT BREAKER,

RATINGS AS

INDICATED

FUSED DISCONNECT

SWITCH, RATINGS

AS INDICATED

400AS

3P

225AF

LPS-R

NEMA 1

COMBINATION FUSED

SWITCH AND STARTER,

RATINGS AS

INDICATED

PANELBOARD,

SINGLE-SECTION,

RATINGS PER

SCHEDULES

PANELBOARD,

MULTI-SECTION,

RATINGS PER

SCHEDULES

AMMETER

VOLTMETER

COMBINATION DIGITAL

AMMETER/VOLTMETER

SHUNT-TRIP RELAY

KIRK-KEY INTERLOCK

GROUND-FAULT RELAY

UTILITY METER

RELAY

SURGE PROTECTION

DEVICE

AUTOMATIC TRANSFER SWITCH WITH BYPASS

TYPE AND RATINGS AS INDICATED

VARIABLE FREQUENCY

DRIVE WITH

DISCONNECT, RATINGS

AS INDICATED

GROUND CONNECTION

POTENTIAL TRANSFORMER

CURRENT TRANSFORMER

GROUND CONNECTION

WITH TEST WELL

CONTACT, OPEN

CONTACT, CLOSED

MOTOR

FEEDER TAGCAPACITOR

SURGE ARRESTER

HEATER

225A 3P

NEMA 1

COMBINATION CIRCUIT

BREAKER AND

STARTER, RATINGS AS

INDICATED

225A 3P

200A 3P

ATS#

200A 3P

ATS#

TRANSFORMER

TX#

TRANSFORMER,

SHIELDED

200A DEAD-FRONT ELBOW

600A DEAD-FRONT ELBOW

DEAD-FRONT SPLITTER

FAULT INDICATOR

LIGHTNING PROTECTION AIR TERMINAL

LIGHTNING PROTECTION CABLE CONNECTION

LIGHTNING PROTECTION GROUND ROD

LIGHTNING PROTECTION CONDUCTOR

LIGHTNING PROTECTION SYMBOLS

ELECTRICAL ONE-LINE DIAGRAM SYMBOLS

LIGHTING SYMBOLS

POWER EQUIPMENT SYMBOLS

WIRING DEVICE SYMBOLS

CIRCUITING SYMBOLS

ES EMERGENCY SHUNT RELAY

MECHANICAL OR FIRE SPRINKLER PLAN NOTE CALL OUT

PLUMBING PLAN NOTE CALL OUT

ELECTRICAL, TECHNOLOGY, OR FIRE ALARM

PLAN NOTE CALL OUT

PLUMBING EQUIPMENT DESIGNATION

EQUIPMENT DESIGNATION TAG

OWNER FURNISHED, CONTRACTOR INSTALLED

EQUIPMENT DESIGNATION

NEW WORK TO EXISTING WORK CONNECTION POINT

DETAIL REFERENCE

SECTION CUT DESIGNATION

ELECTRICAL: (AFF, AFG UNLESS NOTED OTHERWISE)

EP-101

EP-101

AUDIBLE APPLIANCES (CENTERLINE)

ALARMS (TOP)

ANNUNCIATOR PANELS (TOP)

CLOCK OUTLETS (CENTERLINE)

CONTROLS (TOP)

EXIT SIGNS (WALL-MOUNTED, BOTTOM)

FIRE ALARM ANNUNCIATOR PANEL (DISPLAY)

FIRE ALARM BELL (EXTERIOR)

FIRE ALARM CONTROL PANEL/UNIT (DISPLAY)

GROUND BAR

INTERCOM (AFEA ONLY)

INTERCOMS (TOP)

PANELS & PANELBOARDS (TOP)

PULL STATIONS (TOP)

PHOTOCELLS

RECEPTACLES (BOTTOM)

RECEPTACLES, EXTERIOR (BOTTOM)

RECEPTACLES, GARAGES (BOTTOM)

RECEPTACLES IN EQUIPMENT ROOMS (TOP)

RECEPTACLES ABOVE COUNTERTOPS (TOP)

REMOTE INDICATING LIGHT, EQUIPMENT ROOMS (TOP)

REMOTE INDICATING LIGHT, FINISHED AREAS (TOP)

SAFETY SWITCHES & STARTERS

SWITCHES (TOP)

TELEPHONE/DATA/TV OUTLETS (BOTTOM)

VISIBLE APPLIANCES (CENTERLINE)

ANNOTATION STANDARD MOUNTING HEIGHTS

ABBREVIATIONS

1P SINGLE-POLE

1PH SINGLE-PHASE

3P THREE-POLE

3PH THREE-PHASE

3W THREE-WIRE

4W FOUR-WIRE

A OR AMP AMPERE

A/C AIR CONDITIONING

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED

CABLE

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

ADO AUTOMATIC DOOR OPENER

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, OR

AUTOMATIC FREQUENCY CONTROL,

OR AVAILABLE FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

AIP ABANDONED IN PLACE

ALT ALTERNATE

AMB AMBIENT

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BAT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISH FLOOR

BIL BASIC INSULATION LEVEL

BLDG BUILDING

BLK BLOCK

BPIP BOILER PLANT INSTRUMENTATION PANEL

BRKR BREAKER

BYP BY-PASS

C CONDUIT

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

CD CONSTRUCTION DOCUMENTS OR

CANDELA

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED /

CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED /

OWNER INSTALLED

CFE CONTRACTOR FURNISHED EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CLF CURRENT LIMITING FUSE

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAXIAL CABLE

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUED

CONTR CONTRACTOR

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR DISTRIBUTION

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

EC EMPTY CONDUIT

EG EQUIPMENT GROUND

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMCP EMER. MONITORING CONTROL PANEL

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

ESMT EASEMENT

ETD EXISTING TO BE DEMOLISHED

ETR EXISTING TO REMAIN

ETL EXISTING TO BE RELOCATED

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST EXISTING

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABL FIRE ALARM BELL

FABX FIRE ALARM BOX

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FCA FAULT CALCULATED AMPS

FI FILM ILLUMINATOR

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE METALLIC CONDUIT

FLUOR FLUORESCENT

FO FIBER-OPTIC

FP FIRE PROTECTION

FT FEET OR FOOT

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G GROUND OR GENERATOR

GND GROUND

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

HCM HORIZONTAL CABLE MANAGER

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

IC INSULATION CONTACT

IESNA ILLUMINATION ENGINEERING SOCIETY

OF NORTH AMERICA

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

JB OR J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAH KILOVOLT-AMPERE-HOUR

KVAR KILOVOLT-AMPERE-REACTIVE

KW KILOWATT

KWH KILOWATT-HOUR

KWHM KILOWATT-HOUR METER

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LT LIGHT

LTCP LOCAL TEMPERATURE CONTROL PANEL

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MLO MAIN LUGS ONLY

MOCP MAXIMUM OVERCURRENT PROTECTION

MT MOUNT

MTD MOUNTED

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT

N NEUTRAL

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NC NORMALLY CLOSED

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

P POLE

PA PUBLIC ADDRESS

PB PANELBOARD, OR PULL BOX, OR

PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PCB POLYCHLORINATED BIPHENYL

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

PNLBD PANELBOARD

POD POWER OPERATED DAMPER

POE POWER OVER ETHERNET

PP PATCH PANEL

PT POTENTIAL TRANSFORMER

PTRV POWER TYPE ROOF VENTILATION

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REC RECESSED

RELO RELOCATED

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RU RACK UNIT

SCC SHORT CIRCUIT CAPACITY

SD SMOKE DETECTOR

SES SERVICE ENTRANCE SECTION

SF SQUARE FEET (FOOT)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SURF SURFACE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TC TIME CLOCK

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V VOLT

VA VOLT-AMPERE

VAR VOLT-AMPERE-REACTIVE

VCM VERTICAL CABLE MANAGER

VFD VARIABLE FREQUENCY DRIVE

W WATT

WH WATER HEATER

WP WEATHERPROOF

XFER TRANSFER

XFMR TRANSFORMER

XP EXPLOSION PROOF

84" 48" 48" 84" 48" 80" 60"

120" 60" 72" 36" 48" 72" 48"

144" 18" 24" 26" 48" 44" 48"

CEILING

48" 48" 18" 84"

A

# E (CONTINUED) M (CONTINUED)

B

C

D

E

F

N

G

H

I

J

K

L

M

O

P

R

S

T

U

V

W

X

A. ELECTRICAL PLANS AND SECTIONS ARE INTENDED TO

ACCURATELY ILLUSTRATE THE SCOPE OF WORK, BUT ARE STILL

DIAGRAMMATIC IN NATURE.

B. ELECTRICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE

INSTALLED. THE CONTRACTOR IS RESPONSIBLE FOR ENSURING

THAT ALL SYSTEMS ARE FULLY FUNCTIONAL AND COMPLIANT

WITH APPLICABLE CODES.

C. ELECTRICAL DRAWINGS REFLECT COORDINATION EFFORTS

WITH BUILDING DISCIPLINES. HOWEVER, COORDINATION WITH

OTHER TRADES IS REQUIRED.

D. REFERENCE ARCHITECTURAL DRAWINGS FOR ADDITIONAL

INFORMATION REGARDING SCHEDULE AND PHASING

REQUIREMENTS. SCHEDULE WORK TO MINIMIZE DISRUPTION OF

SERVICES.

E. COORDINATE WITH SCHEDULE WITH THE CONTRACTING

OFFICER'S REPRESENTATIVE BEFORE THE START OF WORK.

F. PANELBOARDS AND OTHER ELECTRICAL EQUIPMENT REQUIRE

SHUTDOWN. COORDINATE SERVICE SHUTDOWN FOR ALL

EQUIPMENT WITH THE CONTRACTING OFFICER'S

REPRESENTATIVE.

G. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND

TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES

SHALL HAVE DIVIDERS BETWEEN DEVICES.

H. UPDATE ALL PANELBOARD SCHEDULES AFFECTED AT THE

COMPLETION OF THE PROJECT.

I. IF FIELD CONDITIONS VARY FROM THE DRAWINGS, THE

CONTRACTOR SHALL DOCUMENT THE VARIATION AND REPORT

IT TO THE GENERAL CONTRACTOR FOR RESOLUTION WITH THE

ENGINEER OF RECORD.

GENERAL NOTES

PROJECT CODES AND STANDARDS

A. ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS 2015

B. VA PG-18-13 VA BARRIER FREE DESIGN STANDARD 2018

(SUPPLEMENT TO ABA STANDARDS)

C. ASHRAE STANDARD 90.1-2019 – ENERGY STANDARD FOR

BUILDINGS EXCEPT LOW RISE RESIDENTIAL BUILDINGS

D. IBC 2021 – INTERNATIONAL BUILDING CODE

E. IEBC 2021 – INTERNATIONAL EXISTING BUILDING CODE

F. IECC 2021 – INTERNATIONAL ENERGY CONSERVATION CODE

G. JCAHO EC 7.40 – EMERGENCY ELECTRICAL POWER SYSTEM

INSPECTION, MAINTENANCE, AND TESTING

H. NFPA 70-2023 - NATIONAL ELECTRICAL CODE (NEC)

I. NFPA 99-2021 – HEALTH CARE FACILITIES CODE

J. NFPA 101-2021 – LIFE SAFETY CODE

K. NFPA 110-2022 – STANDARD FOR EMERGENCY AND STANDBY

POWER SYSTEMS

L. VA PG-18-10 ELECTRICAL DESIGN MANUAL, DECEMBER 2019

M. VA H-18-8 SEISMIC DESIGN REQUIREMENTS

N. VA PHYSICAL SECURITY & RESILIENCY DESIGN MANUAL 2020

(1 JAN 2024 REVISION)

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

PROJECT NUMBERCONSULTANTS:

DRAWING #

VA HEALTH CARE SYSTEM APPROVAL:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. CA02295 EXP. 06/30/2025

ENGR REG. NO. CA7127 EXP. 06/30/2025

ELECTRICAL ENGINEER

SPUR DESIGN

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

DRAWING NUMBER

BUILDING NUMBER

/1

/2

:5 :3

A

M

ELECTRICAL SYMBOLS &

ABBREVIATIONS

IGM 3 OF 9ES

100% CONSTRUCTION DOCUMENTS

REPLACE MCC PANEL BF118

03/18/2024

635-23-118

OKLAHOMA CITY VAHCS

921 NE 13TH STREET

OKLAHOMA CITY, OK 73104

E-000

SPUR #: 2093.05No. REVISION DESCRIPTION DATE

EP101

ED101

MECHANICAL ROOM

BF118

EMERGENCY GENERATOR

BF115

EP101

ED101

PNL EGP

(ETR)

EMCC-1 (NEW)

'ATS-6' (NEW)

ATS-6

DISCONNECT

SWITCH (ETR)

(TYP.)

(TYP.)

BASEMENT LEVEL KEY PLAN

N

BUILDING 1

MECH RM BF118

GEN RM BF115

PARTITION LEGEND

EXISTING 1 HOUR FIRE RATED

EXISTING 2 HOUR FIRE RATED

EXISTING 3 HOUR FIRE RATED

SMOKE PARTITION/BARRIER

NEW NON-RATED WALLS

EXISTING WALL TO REMAIN

EXISTING 1 HOUR FIRE

EXISTING 2 HOUR FIRE

NOTE: NOT ALL SYMBOLS MAY BE USED

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

PROJECT NUMBERCONSULTANTS:

DRAWING #

VA HEALTH CARE SYSTEM APPROVAL:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. CA02295 EXP. 06/30/2025

ENGR REG. NO. CA7127 EXP. 06/30/2025

ELECTRICAL ENGINEER

SPUR DESIGN

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

DRAWING NUMBER

BUILDING NUMBER

/1

/2

:5 :3

A

M

ELECTRICAL REFERENCE PLAN -

BASEMENT LEVEL

IGM 4 OF 9ES

100% CONSTRUCTION DOCUMENTS

REPLACE MCC PANEL BF118

03/18/2024

635-23-118

OKLAHOMA CITY VAHCS

921 NE 13TH STREET

OKLAHOMA CITY, OK 73104

E-100

SPUR #: 2093.05

N

1/16" = 1'-0"

ELECTRICAL REFERENCE PLAN - BASEMENT LEVEL1

ELECTRICAL KEYNOTES

1 PROVIDE 24" X 24" X 6" (MIN.) PULLBOX. PROVIDE PULLBOXES IN ACCESSIBLE LOCATIONS AND

DOCUMENT ON RECORD DRAWINGS EXACT SIZE AND LOCATION. REFER TO SHEET E-601 FOR

CONDUIT, WIRE SIZES, AND ADDITIONAL INFORMATION.

2 ROUTE CONDUIT ABOVE DROP CEILING TIGHT TO STRUCTURE. COORDINATE ROUTING WITH

EXISTING UTILITIES. ANY DAMAGE DONE TO EXISTING UTILITIES SHALL BE REPAIRED IN

ACCORDANCE WITH VA STANDARD CONSTRUCTION SPECIFICATIONS AT NO ADDITIONAL

COST.

3 PROVIDE FIRE STOPPING AROUND ALL PENETRATIONS THROUGH RATED WALLS.

4 REFER TO CONDUIT TRAPEZE MOUNTING DETAIL 1/E-501 FOR MOUNTING REQUIREMENTS.

5 PROVIDE (2) 3" CONDUIT TO CONNECT EXISTING 400A, 480V DISCONNECT SWITCH TO NEW

600A, 480V ATS-6. REFER TO SHEET E-601 & E-602 FOR MORE INFORMATION.

6 NEW PARALLEL CONDUCTORS FROM EXISTING ATS-6 DISCONNECT SWITCH IN EMERGENCY

GENERATOR ROOM BF115 TO NEW ATS-6 IN MECHANICAL ROOM BF118 ARE FOR TEMPORARY

THEN PERMANENT TERMINATION.

7 ROUTE NEW RACEWAYS IN EXPOSED SPACE TIGHT TO STRUCTURE. PROVIDE FINAL ROUTING

PLAN TO COR FOR APPROVAL.

A. ELECTRICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE

CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY

FUNCTIONAL AND COMPLIANT WITH APPLICABLE CODES.

B. ELECTRICAL DRAWINGS REFLECT COORDINATION EFFORTS WITH OTHER DISCIPLINES.

HOWEVER, COORDINATION WITH OTHER TRADES ARE REQUIRED.

C. DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF WORK.

REVIEW GENERAL NOTES AND PLANS FOR ADDITIONAL REQUIREMENTS THAT MAY NOT

BE SPECIFICALLY CALLED OUT IN THIS PORTION OF THE CONSTRUCTION DOCUMENTS.

NOTIFY THE CONTRACTING OFFICER'S REPRESENTATIVE (COR) OF ANY CONFLICTS OR

DISCREPANCIES PRIOR TO SUBMISSION OF BID.

D. REFER TO ONE-LINE DRAWING SHEETS FOR ADDITIONAL NOTES.

E. SHADED AREAS ARE OUT OF PROJECT SCOPE.

F. NO WORK ON ENERGIZED EQUIPMENT IS PERMITTED BY VA DIRECTIVE.

GENERAL NOTES:

EMCC-1 (ETD)

CHILLER

STARTER

(ETR)

EAST

HEATING

WATER #1

VFD (ETD)

WEST

HEATING

WATER #2

VFD (ETD)

SWITCHBOARD

'MDP' (ETR)

PANEL

'CHDP-2' (ETR)

750 KVA XFMR

(ETR)

MECHANICAL ROOM

BF118

(ABOVE)

VACUUM PUMP #2

DISCONNECT (ETR)

VACUUM PUMP #1

DISCONNECT (ETR)

HOT WATER

CIRCULATING PUMP

DISCONNECT (ETR)

ETD

XFMR LBIEB

(ETR)

PANEL LBIEB

(ETR)

PANEL B (ETR)

XFMR A (ETR)

PANEL A (ETR)

PANEL A1

(ETR)

CONCRETE

PAD (ETR)

CONCRETE

PAD (ETR)

CHWP (ETR)

EXHAUST

FAN (ETR)

S&C

SWITCHGEAR

(ETR)

PUMP DISCONNECT

(ETR)

ED101

EMERGENCY GENERATOR

BF115

GENERATOR

CONTROL

PANEL (ETR)PNL EGP

(ETR)

ATS-6

DISCONNECT

SWITCH (ETR)

500KW

GENERATOR

(ETR)

ELECT. HEATER

DISCONNECT

SWITCH (ETR)

ETR

DAY TANK

(ETR)

BASEMENT LEVEL KEY PLAN

N

BUILDING 1

MECH RM BF118

GEN RM BF115

PARTITION LEGEND

EXISTING 1 HOUR FIRE RATED

EXISTING 2 HOUR FIRE RATED

EXISTING 3 HOUR FIRE RATED

SMOKE PARTITION/BARRIER

NEW NON-RATED WALLS

EXISTING WALL TO REMAIN

EXISTING 1 HOUR FIRE

EXISTING 2 HOUR FIRE

NOTE: NOT ALL SYMBOLS MAY BE USED

CHILLER

STARTER

(ETR)

'ATS-6' (NEW)

CONCRETE

PAD (NEW)

EXHAUST

FAN (ETR)

EMCC-1 (ETD)

MECHANICAL ROOM

BF118

4 5

6 (TYP.)

3"

3'-6"

2'-1" th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

PROJECT NUMBERCONSULTANTS:

DRAWING #

VA HEALTH CARE SYSTEM APPROVAL:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. CA02295 EXP. 06/30/2025

ENGR REG. NO. CA7127 EXP. 06/30/2025

ELECTRICAL ENGINEER

SPUR DESIGN

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

DRAWING NUMBER

BUILDING NUMBER

/1

/2

:5 :3

A

M

ELECTRICAL POWER DEMOLITION PLAN

IGM 5 OF 9ES

100% CONSTRUCTION DOCUMENTS

REPLACE MCC PANEL BF118

03/18/2024

635-23-118

OKLAHOMA CITY VAHCS

921 NE 13TH STREET

OKLAHOMA CITY, OK 73104

ED101

SPUR #: 2093.05

N

1/4" = 1'-0" REF: 1/ E-100

ELECTRICAL DEMOLITION PLAN - MECHANICAL ROOM BF1181

A. LOCATIONS ARE APPROXIMATE. FIELD VERIFY EXACT DEVICE QUANTITIES LOCATIONS PRIOR TO

DEMOLITION.

B. WHERE PORTIONS OF CIRCUITS ARE REMOVED OR ABANDONED, RE-ESTABLISH CIRCUIT

CONTINUITY FOR REMAINING PORTION OF CIRCUITS AS REQUIRED TO MAINTAIN OPERATION.

C. SHADED AREAS INDICATE OUT OF PROJECT SCOPE.

D. NO WORK ON ENERGIZED EQUIPMENT IS PERMITTED BY VA DIRECTIVE.

GENERAL NOTES:

ELECTRICAL KEYNOTES

1 EXISTING HEATING WATER VFDS (NOT IN PROJECT SCOPE) SHALL BE DE-ENERGIZED,

DISCONNECTED, AND REMOVED BY THE VA IN ADVANCE OF THIS PROJECT.

2 PROVIDE NEW HOUSEKEEPING PAD AND NEW 4-POLE, 600A, 480Y/277V AUTOMATIC TRANSFER SWITCH (ATS-6) WITH ISOLATION BYPASS PRIOR TO DEMOLITION. SEE ELECTRICAL ONE-LINE FOR

MORE DETAILS AND PHASING PLAN.

3 PROVIDE A TEMPORARY 400A, 480Y/277V, 3-PH, 4W PANEL AND PROVIDE TEMPORARY CONNECTION

TO NEW ATS-6. TRANSFER LOADS FROM EXISTING EMCC-1 TO TEMPORARY PANEL. SEE

ELECTRICAL ONE-LINE DIAGRAM ON SHEETS E-601 AND E-602 FOR SEQUENCE OF WORK PHASING

REQUIREMENTS.

4 DE-ENERGIZE, DISCONNECT, AND REMOVE EXISTING EMCC-1 AND UPSTREAM CONDUIT AND

CONDUCTORS. SEE ELECTRICAL ONE-LINE DIAGRAM ON SHEETS E-601 AND E-602 FOR SEQUENCE

OF WORK PHASING REQUIREMENTS.

5 EXISTING BRANCH CIRCUIT LOADS SHALL BE DE-ENERGIZED. DISCONNECT AND REMOVE EXISTING

BRANCH CIRCUIT CONDUCTORS AND CONDUIT BACK TO NEAREST ACCEPTABLE POINT

(J-BOX/COUPLING). VERIFY EXISTING CONDUCTORS AND CONDUIT CONDITION ARE DEEMED

ACCEPTABLE WITH OKC VAMC ENGINEERS. STORE AND PROTECT EXISTING CONDUCTORS AND

CONDUIT FOR RE-INSTALLATION TO NEW EMCC-1.

6 VERIFY EXISTING EMCC-1 STARTER SIZES FOR BRANCH LOADS AND PROVIDE TEMPORARY

EXTERNAL STARTERS. SEE ELECTRICAL ONE-LINE DIAGRAM ON SHEETS E-601 AND E-602 FOR

SEQUENCE OF WORK PHASING REQUIREMENTS.

7 PROVIDE CONCRETE HOUSEKEEPING PAD FOR NEW ATS-6 AND PAINT YELLOW. MATCH NEW

HOUSEKEEPING PAD HEIGHT WITH EXISTING CONCRETE PAD. SEE DETAIL 2/E-501 FOR MORE

INFORMATION.

N

1/4" = 1'-0" REF: 1/ E-100

ELECTRICAL DEMOLITION PLAN - EMERGENCY GENERATOR ROOM BF1152

No. REVISION DESCRIPTION DATE

N

1/2" = 1'-0" REF: 1/ ED101

ELECTRICAL TEMPORARY PLAN - MECHANICAL ROOM BF1183

CHILLER

STARTER

(ETR)

SWITCHBOARD

'MDP' (ETR)

PANEL

'CHDP-2' (ETR)

750 KVA XFMR

(ETR)

MECHANICAL ROOM

BF118

EMCC-1 (NEW)

XFMR LBIEB

(ETR)

PANEL LBIEB

(ETR)

(ABOVE)

VACUUM PUMP #2

DISCONNECT (ETR)

VACUUM PUMP #1

DISCONNECT (ETR)

PANEL A1

(ETR)

PANEL A (ETR)

PANEL B (ETR)

XFMR A (ETR)

HOT WATER

CIRCULATING PUMP

DISCONNECT (ETR)

GFCI

'ATS-6' (NEW)

Y1E

Y1E

PANEL B

CONCRETE

PAD (ETR)

CONCRETE

PAD (ETR)

CHWP 2 (ETR)

EXHAUST

FAN (ETR)

S&C

SWITCHGEAR

(ETR)

EP101

CONCRETE

PAD (NEW)

PUMP DISCONNECT

(ETR)

500KW

GENERATOR

(ETR)

ELECT. HEATER

DISCONNECT

SWITCH (ETR)

GENERATOR

CONTROL

PANEL (ETR)PNL EGP

(ETR)

EMERGENCY GENERATOR

BF115

ATS-6

DISCONNECT

SWITCH (ETR)

ETR

DAY TANK

(ETR)

BASEMENT LEVEL KEY PLAN

N

BUILDING 1

MECH RM BF118

GEN RM BF115

EMCC-1 (NEW)

'ATS-6' (NEW)

CHILLER

STARTER

(ETR)

CONCRETE

PAD (ETR)

CONCRETE

PAD (NEW)

7 (TYP.)

EXHAUST

FAN (ETR)

MECHANICAL ROOM

BF118

PARTITION LEGEND

EXISTING 1 HOUR FIRE RATED

EXISTING 2 HOUR FIRE RATED

EXISTING 3 HOUR FIRE RATED

SMOKE PARTITION/BARRIER

NEW NON-RATED WALLS

EXISTING WALL TO REMAIN

EXISTING 1 HOUR FIRE

EXISTING 2 HOUR FIRE

NOTE: NOT ALL SYMBOLS MAY BE USED

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

PROJECT NUMBERCONSULTANTS:

DRAWING #

VA HEALTH CARE SYSTEM APPROVAL:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. CA02295 EXP. 06/30/2025

ENGR REG. NO. CA7127 EXP. 06/30/2025

ELECTRICAL ENGINEER

SPUR DESIGN

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

DRAWING NUMBER

BUILDING NUMBER

/1

/2

:0 :0

A

M

ELECTRICAL POWER FLOOR PLAN

IGM 6 OF 9ES

100% CONSTRUCTION DOCUMENTS

REPLACE MCC PANEL BF118

03/18/2024

635-23-118

OKLAHOMA CITY VAHCS

921 NE 13TH STREET

OKLAHOMA CITY, OK 73104

EP101

SPUR #: 2093.05

N

1/4" = 1'-0"

ELECTRICAL POWER PLAN - MECHANICAL ROOM BF1181

A. ELECTRICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE CONTRACTOR

IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY FUNCTIONAL AND COMPLIANT

WITH APPLICABLE CODES.

B. ELECTRICAL DRAWINGS REFLECT COORDINATION EFFORTS WITH OTHER DISCIPLINES.

HOWEVER, COORDINATION WITH OTHER TRADES ARE REQUIRED.

C. DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF WORK. REVIEW

GENERAL NOTES AND PLANS FOR ADDITIONAL REQUIREMENTS THAT MAY NOT BE SPECIFICALLY

CALLED OUT IN THIS PORTION OF THE CONSTRUCTION DOCUMENTS. NOTIFY THE CONTRACTING

OFFICER'S REPRESENTATIVE (COR) OF ANY CONFLICTS OR DISCREPANCIES PRIOR TO

SUBMISSION OF BID.

D. REFER TO ONE-LINE DRAWING SHEETS FOR ADDITIONAL NOTES.

E. SHADED AREAS ARE OUT OF PROJECT SCOPE.

F. NO WORK ON ENERGIZED EQUIPMENT IS PERMITTED BY VA DIRECTIVE.

GENERAL NOTES:

ELECTRICAL KEYNOTES

1 PROVIDE A NEW 600A, 480V, 3-PH, 4W MOTOR CONTROL CENTER (EMCC-1). SEE ELECTRICAL

ONE-LINE DIAGRAM ON SHEETS E-601 AND E-602 FOR SEQUENCE OF WORK PHASING

REQUIREMENTS.

2 CONTRACTOR TO PROVIDE AUXILIARY DRIP PAN PROTECTIONS BELOW WATER, SANITARY, OR

SPRINKLER PIPING IN THE EVENT THEY ARE MEASURED TO BE IN THE AREA DIRECTLY ABOVE

DEDICATED ELECTRICAL SPACE OF THE EQUIPMENT AFTER INSTALLATION PER NFPA

110.26(E)(1)(a-c). IF THOSE SYSTEMS ARE MEASURED TO BE WITHIN THE DEDICATED SPACE, THEY ARE TO BE REROUTED OUTSIDE THE ACCEPTABLE SPACE CLEARANCES AND THEN THE PREVIOUSLY NOTED PROTECTIONS MAY STILL APPLY. PROVIDE AUXILIARY DRIP PANS WITH LEAK DETECTION AND

TIE BACK TO CAMPUS BAS.

3 USE EXISTING 20A, 277V, 1-POLE CIRCUIT BREAKER IN PANEL B FOR EMERGENCY BATTERY PACK

WALL MOUNTED LIGHT FIXTURE.

4 PROVIDE NEW GFCI RECEPTACLE AND RE-USE EXISTING CIRCUIT.

5 REQUIRED CLEARANCES, AREA TO REMAIN FREE FROM DEBRIS PER NEC 110.26.

6 REMOVE TEMPORARY PANEL AFTER NEW EMCC-1 IS IN SERVICE. SEE ELECTRICAL ONE-LINE

DIAGRAM ON SHEETS E-601 AND E-602 FOR SEQUENCE OF WORK PHASING REQUIREMENTS.

7 REMOVE TEMPORARY EXTERNAL STARTERS AFTER NEW EMCC-1 IS IN SERVICE. SEE ELECTRICAL

ONE-LINE DIAGRAM ON SHEETS E-601 AND E-602 FOR SEQUENCE OF WORK PHASING

REQUIREMENTS.

N

1/4" = 1'-0" REF: 1/ E-100

ELECTRICAL POWER PLAN - EMERGENCY GENERATOR ROOM BF1152

No. REVISION DESCRIPTION DATE

N

1/2" = 1'-0" REF: 1/ EP101

NEW WORK CONFIGURATION - MECHANICAL ROOM BF1183

CONDUIT CLAMP. SIZE

AS REQUIRED

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

REFER TO PLANS FOR

QUANTITY & SIZE OF

CONDUITS

GENERAL NOTES:

1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL

LONGER THAN 915mm (36") SHALL BE INSTALLED WITH A

CENTER SUPPORT ROD.

2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED

METHOD PER SPECIFICATION 26 05 33, RACEWAY AND BOXES

FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT CONDITIONS.

3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER TO

SPECIFICATION SECTION 13 05 41, SEISMIC RESTRAINT

REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.

LENGTH AS REQUIRED

LOCKING SQUARE

WASHER & LOCKNUT

9.52mm (3/8") MIN

GALVANIZED THREADED

ROD, TYP.

WASHER &

LOCKNUT

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

1 1/2" CLR. 1 1/2" CLR.1'-0" TYP. 1'-0" TYP.

3/ 4"

ROUGHEN SURFACE TO 1/4" DEPTH. CLEAN

AND APPLY EPOXY BONDING COMPOUND

PRIOR TO PLACING NEW CONCRETE.

DRILL AND EPOXY #4 DOWELS AT

4'-0" O.C. (TYP. AT PERIMETER

MIN. 4 EA. PAD)

4"

#4 AT 6"

O.C. E.W.

CONCRETE PAD TO BE PAINTED YELLOW.

TOP OF HANDLE

6'-6" AFF MAXIMUM

4'-0" +/- AFF

FRONT VIEWSIDE VIEW

DISCONNECT SWITCH, CIRCUIT

BREAKER ENCLOSURE, OR

MOTOR CONTROLLER

CHANNEL STRUT POST BASE W

(4) 1/4" EXPANSION ANCHORS.

(TYPICAL)

PROVIDE RIGID CONDUIT TO

MECHANICAL/PLUMBING

EQUIPMENT. CONVERT TO

FLEXIBLE CONDUIT WITH BOND

WIRE FOR FINAL CONNECTION TO

EQUIPMENT.

FLOOR

STRUCTURAL CEILING

CHANNEL STRUT SUPPORT

FRAME.

1'-7" (MIN.)

OPTION 3: CHANNEL STRUT

ANGLE BRACKET SUPPORT

FOR EACH SUPPORT LEG WITH

1/2" FLOOR EXPANSION

ANCHOR.

PROVIDE RIGID CONDUIT BACK

TO ELECTRICAL SOURCE.

NOTE:

1. DISCONNECT SWITCHES, CIRCUIT BREAKER ENCLOSURES, MOTOR CONTROLLERS & VARIABLE FREQUENCY DRIVES, AND CONTROL CABINETS MAY BE DIRECTLY MOUNTED TO STRUCTURAL WALLS, OR TO MECHANICAL EQUIPMENT

WHEN PERMITTED BY THE MECHANICAL EQUIPMENT MANUFACTURER AND WHERE IT DOES NOT BLOCK ACCESS OR

OPERATION OF THE EQUIPMENT. WHERE A SUITABLE STRUCTURAL WALL IS NOT AVAILABLE, PROVIDE SUPPORT FRAME AND

CONNECT THE SUPPORT FRAME WITH A MINIMUM OF (4) POINTS OF CONTACT TO THE BUILDING STRUCTURE TO PROVIDE A

RIGID ASSEMBLY. OPTION 1, 2, OR 3 MAY BE UTILIZED TO PROVIDE THE…