S05 - RFIs and Responses.pdf

PDF 259 KB Posted

Attached to
Z2DA--442-24-016 Repair Chilled Water Cistern & Heat Exchanger
Solicitation number
36C25924R0011
Issued by

About this file

This document contains responses to requests for information (RFIs) regarding Solicitation Number 36C25924R0011 from the Department of Veterans Affairs for repair work to a chilled water cistern and heat exchanger at the Buffalo VA Medical Center. The responses indicate that for the limited scope of this project, a single individual may serve as the superintendent, site safety and health officer, and contractor quality control manager provided they are qualified for each role. No asbestos is expected to be encountered during the work but the contractor should notify the VA if any is suspected. New roofing components will be installed to match the existing roof over the cistern. This is a design-bid-build project, not a design-build project.

View the file

Other files

File Type Posted
36C25924R0011 0004.docx DOCX document
S04 - Site Visit Attendance_Repair Chilled Water Cistern _ Heat Exchanger.pdf PDF
36C25924R0011 0003.docx DOCX document
36C25924R0011 0002.docx DOCX document
36C25924R0011 0001.docx DOCX document
S02 - 442-24-016_CONSTRUCTION DRAWINGS.pdf PDF
S02 - 442-24-016_SPECIFICATIONS.pdf PDF
S02 - Past Performance Questionnaire.docx DOCX document
36C25924R0011_1.docx DOCX document
S22- 852.219-75 LOS Certificate - ST.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project: 442-24-016 Repair Chilled Water Cistern & Heat Exchanger

RFIs and Responses

1. Will the prime contractor be required to have a separate SSHO for this project or can the SSHO work on multiple projects?

A: No, please see response to Question #5 for additional detail.

2. Is the SSHO required to be onsite full time with no other duties?

A: SSHO to be on site while work is being performed but may have other duties. Please see response to Question #5 for additional detail.

3. Does the CQCM have to be on site full time?

A: CQCM to be on site while work is being performed but may have other duties. Please see response to Question #5 for additional detail.

4. Can the CQCM be the superintendent?

A: Yes, please see response to Question #5 for additional detail.

5. Can the Superintendent be the SSHO and CQCM?

A: Given the limited scope for this project a single individual may act as Superintendent, Site Safety and Health Officer (SSHO) and Contractor Quality Control Manager (CQCM) providing they are qualified to perform each position/all duties. That individual will be required to be on site while work is being performed.

6. Is this a design build project?

A: No.

7. Is this a design/bid/build project?

A: Yes.

8. Does the VA want to a new roof over the cistern or remove and reinstall?

A: New roofing components shall be installed like in kind.

9. Is there any asbestos present in work area?

A: No asbestos is anticipated. All facility asbestos studies have found no asbestos present in the Buffalo building (constructed in 1989) where this work is being performed. If the contractor suspects asbestos, please notify the VA COR and additional testing will be performed.