S06-Non-Structural Metal Framing Amentment 3 Attatchment.doc
DOC document 41 KB Posted
- Solicitation number
- 36C25922Q0573
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25922Q0573 0004.docx | DOCX document | |
| S05-Questions From Contractors.docx | DOCX document | |
| S06-Install Eye Glass Dispensing Station B45_C1.1 Amendment 3 attatchment.pdf | ||
| S06-Schedule for Finishes_Amendment 3 Attatchment.doc | DOC document | |
| 36C25922Q0573 0003.docx | DOCX document | |
| S06-Install Eye Glass Dispensing Station B45_C1 Amendment 3 attatchment.pdf | ||
| S06-Install Eye Glass Dispensing Station B45_C1.2 Amendment 3 attatchment.pdf | ||
| 36C25922Q0573 0002.docx | DOCX document | |
| 36C25922Q0573 0001.docx | DOCX document | |
| 36C25922Q0573_1.docx | DOCX document | |
| P01-Specifications.pdf | ||
| P01-Plan_Drawing.pdf |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
575-23-106 Install Eye Glass Dispensing Station
SECTION 09 22 16
NON-STRUCTURAL METAL FRAMING
PART 1 ‑ GENERAL
1.1 DESCRIPTION
This section specifies steel studs wall systems, ceiling suspended framing, wall furring, fasteners, and accessories for the screw attachment of gypsum board or other building boards.
1.2 RELATED WORK
Section 09 29 00, GYPSUM BOARD.
1.3 TERMINOLOGY
A.
Description of terms shall be in accordance with ASTM C754, ASTM C11, ASTM C841 and as specified.
1.4 SUBMITTALS
A.
Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B.
Manufacturer's Literature and Data:
1.
Studs, runners and accessories.
2.
Channels (Rolled steel).
3.
Screws, clips and other fasteners.
C.
Shop Drawings:
1.
Typical ceiling suspension system.
2.
Typical metal stud and furring construction system including details around openings and corner details.
3.
Typical fire rated assembly and column fireproofing showing details of construction same as that used in fire rating test.
D.
Test Results: Fire rating test designation, each fire rating required for each assembly.
1.5 DELIVERY, IDENTIFICATION, HANDLING AND STORAGE
In accordance with the requirements of ASTM C754.
1.6 APPLICABLE PUBLICATIONS
A.
The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.
B.
American Society For Testing And Materials (ASTM)
A641-09 Zinc-Coated (Galvanized) Carbon Steel Wire
C11-10 Terminology Relating to Gypsum and Related Building Materials and Systems
C635-07 Manufacture, Performance, and Testing of Metal Suspension System for Acoustical Tile and Lay‑in Panel Ceilings
C636-08 Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Lay‑in Panels
C645-09 Non-Structural Steel Framing Members
C754-11 Installation of Steel Framing Members to Receive Screw-Attached Gypsum Panel Products
C954-10 Steel Drill Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Steel Studs from 0.033 in. (0.84 mm) to 0.112 in. (2.84 mm) in Thickness
E580-11 Application of Ceiling Suspension Systems for Acoustical Tile and Lay-in Panels in Areas Requiring Moderate Seismic Restraint.
PART 2 ‑ PRODUCTS
2.1 PROTECTIVE COATING
Galvanize steel studs, runners (track and rigid (hat section) furring channels with coating designation of G-60 minimum, per ASTM 123.
2.2 STEEL STUDS AND RUNNERS (TRACK)
A.
ASTM C645, modified for thickness specified and sizes as shown.
1.
Use ASTM A525 steel, 0.8 mm (0.0329-inch) thick bare metal (33 mil).
2.
Runners same thickness as studs.
B.
Provide not less than two cutouts in web of each stud, approximately 300 mm (12 inches) from each end, and intermediate cutouts on approximately 600 mm (24‑inch) centers.
C.
Doubled studs for openings and studs for supporting concrete backer‑board.
D.
Studs 3600 mm (12 feet) or less in length shall be in one piece.
E.
Use a minimum of 1-5/8” X 3-5/8” steel studs.
(Addendum 1)
2.3 FURRING CHANNELS
A.
Rigid furring channels (hat shape): ASTM C645.
D.
Rolled Steel Channels: ASTM C754, cold rolled; or, ASTM C841, cold rolled.
2.4 FASTENERS, CLIPS, AND OTHER METAL ACCESSORIES
A.
ASTM C754, except as otherwise specified.
B.
For fire rated construction: Type and size same as used in fire rating test.
C.
Fasteners for steel studs thicker than 0.84 mm (0.033‑inch) thick. Use ASTM C954 steel drill screws of size and type recommended by the manufacturer of the material being fastened.
D.
Clips: ASTM C841 (paragraph 6.11), manufacturer’s standard items. Clips used in lieu of tie wire shall have holding power equivalent to that provided by the tie wire for the specific application.
E.
Concrete ceiling hanger inserts (anchorage for hanger wire and hanger straps): Steel, zinc‑coated (galvanized), manufacturers standard items, designed to support twice the hanger loads imposed and the type of hanger used.
F.
Tie Wire and Hanger Wire:
1.
ASTM A641, soft temper, Class 1 coating.
2.
Gage (diameter) as specified in ASTM C754 or ASTM C841.
G.
Attachments for Wall Furring:
1.
Manufacturers standard items fabricated from zinc‑coated (galvanized) steel sheet.
H.
Power Actuated Fasteners: Type and size as recommended by the manufacturer of the material being fastened.
2.5 SUSPENDED CEILING SYSTEM FOR GYPSUM BOARD (OPTION)
A.
Conform to ASTM C635, heavy duty, with not less than 35 mm (1-3/8 inch) wide knurled capped flange face designed for screw attachment of gypsum board.
B.
Wall track channel with 35 mm (1‑3/8 inch) wide flange.
PART 3 ‑ EXECUTION
3.1 INSTALLATION CRITERIA
A.
Where fire rated construction is required for walls, partitions, columns, beams and floor‑ceiling assemblies, the construction shall be same as that used in fire rating test.
B.
Construction requirements for fire rated assemblies and materials shall be as shown and specified, the provisions of the Scope paragraph (1.2) of ASTM C754 and ASTM C841 regarding details of construction shall not apply.
3.2 INSTALLING STUDS
A.
Install studs in accordance with ASTM C754, except as otherwise shown or specified.
B.
Space studs not more than 610 mm (24 inches) on center.
C.
Cut studs 6 mm to 9 mm (1/4 to 3/8‑inch) less than floor to underside of structure overhead when extended to underside of structure overhead.
D.
Where studs are shown to terminate above suspended ceilings, provide bracing as shown or extend studs to underside of structure overhead.
E.
Extend studs to underside of structure overhead for fire, rated partitions, smoke partitions, shafts, and sound rated partitions and insulated exterior wall furring.
G.
Openings:
1.
Frame jambs of openings in stud partitions and furring with two studs placed back to back or as shown.
2.
Fasten back to back studs together with 9 mm (3/8‑inch) long Type S pan head screws at not less than 600 mm (two feet) on center, staggered along webs.
3.
Studs fastened flange to flange shall have splice plates on both sides approximately 50 X 75 mm (2 by 3 inches) screwed to each stud with two screws in each stud. Locate splice plates at 600 mm (24 inches) on center between runner tracks.
H.
Fastening Studs:
1.
Fasten studs located adjacent to partition intersections, corners and studs at jambs of openings to flange of runner tracks with two screws through each end of each stud and flange of runner.
2.
Do not fasten studs to top runner track when studs extend to underside of structure overhead.
I.
Chase Wall Partitions:
1.
Locate cross braces for chase wall partitions to permit the installation of pipes, conduits, carriers and similar items.
2.
Use studs or runners as cross bracing not less than 63 mm (2‑1/2 inches wide).
J.
Form building seismic or expansion joints with double studs back to back spaced 75 mm (three inches) apart plus the width of the seismic or expansion joint.
K.
Form control joint, with double studs spaced 13 mm (1/2‑inch) apart.
3.3 INSTALLING WALL FURRING FOR FINISH APPLIED TO ONE SIDE ONLY
A.
In accordance with ASTM C754, or ASTM C841 except as otherwise specified or shown.
B.
Wall furring‑Stud System:
1.
Framed with 63 mm (2‑1/2 inch) or narrower studs, 600 mm (24 inches) on center.
2.
Brace as specified in ASTM C754 for Wall Furring‑Stud System or brace with sections or runners or studs placed horizontally at not less than three foot vertical intervals on side without finish.
3.
Securely fasten braces to each stud with two Type S pan head screws at each bearing.
3.4 INSTALLING SUPPORTS REQUIRED BY OTHER TRADES
A.
Provide for attachment and support of electrical outlets, plumbing, laboratory or heating fixtures, recessed type plumbing fixture accessories, access panel frames, wall bumpers, chalkboards, tackboards, wall‑hung casework, handrail brackets, recessed fire extinguisher cabinets and other items supported by stud construction.
B.
Provide additional studs where required. Install metal backing plates, or special metal shapes as required, securely fastened to metal studs.
3.6 INSTALLING SUSPENDED CEILINGS
A.
Install suspended ceilings in accordance with ASTM C754 or ASTM C841 except as otherwise specified or shown for screw attached gypsum board ceilings and for plaster ceilings or soffits.
1Space framing at 600 mm (24-inch) centers for gypsum board anchorage.
B.
Where bar joists or beams are more than 1200 mm (48 inches) apart, provide intermediate hangers so that spacing between supports does not exceed 1200 mm (48 inches). Use clips, bolts, or wire ties for direct attachment to steel framing.
C.
Existing concrete construction exposed or concrete on steel decking:
1.
Use power actuated fasteners either eye pin, threaded studs or drive pins for type of hanger attachment required.
2.
Install fasteners at approximate mid height of concrete beams or joists. Do not install in bottom of beams or joists.
E.
Steel decking without concrete topping:
1.
Do not fasten to steel decking 0.76 mm (0.0299‑inch) or thinner.
2.
Toggle bolt to decking 0.9 mm (0.0359‑inch) or thicker only where anchorage to steel framing is not possible.
F.
Installing suspended ceiling system for gypsum board (ASTM C635 Option):
1.
Install only for ceilings to receive screw attached gypsum board.
2.
Install in accordance with ASTM C636.
a.
Install main runners spaced 1200 mm (48 inches) on center.
b.
Install 1200 mm (four foot) tees not over 600 mm (24 inches) on center; locate for edge support of gypsum board.
c.
Install wall track channel at perimeter.
G.
Installing Ceiling Bracing System:
1.
Construct bracing of 38 mm (1‑1/2 inch) channels for lengths up to 2400 mm (8 feet) and 50 mm (2 inch) channels for lengths over 2400 mm (8 feet) with ends bent to form surfaces for anchorage to carrying channels and over head construction. Lap channels not less than 600 mm (2 feet) at midpoint back to back. Screw or bolt lap together with two fasteners.
2.
Install bracing at an approximate 45 degree angle to carrying channels and structure overhead; secure as specified to structure overhead with two fasteners and to carrying channels with two fasteners or wire ties.
3.
Brace suspended ceiling or soffit framing in seismic areas in accordance with ASTM E580.
3.7 TOLERANCES
A.
Fastening surface for application of subsequent materials shall not vary more than 3 mm (1/8‑inch) from the layout line.
B.
Plumb and align vertical members within 3 mm (1/8‑inch.)
C.
Level or align ceilings within 3 mm (1/8‑inch.)
‑ ‑ ‑ E N D ‑ ‑ ‑