Questions

1. Who is removing the furniture in room G2-305 to include physical therapy equipment, lockers, and other objects that require removal prior to work being performed in room G2-305?

a. VA will remove all furniture from the room before flooring work is performed and VA will move furniture on an as needed basis for any other work.

2. Floor Drawing (08.AG.102, G2‐305 FLOORING PLAN) is referenced but not provided on SAM. Please provide drawing 08.AG.102 or a detailed floor plan with measurements of room G2-305.

a. See attached.

3. There appears to be contradictory locations for sliding barn door (Item # 2) – Please confirm location either closer to the door or on the far side of the PT walker.

a. See prosthetics layout drawing. Door should be on west side of room with the door sliding open towards the existing sink.

4. What is the basis of design for the sliding barn door and associated hardware listed with the following spec:

Install new sliding “barn door” style door that is rated for healthcare use.

a. See attached drawing for approximate location and correct placement/orientation of door within existing space.

b. Door must have the following features and capabilities:

i. Minimum 3’ wide and 7’ tall

ii. Classroom lock functionality

iii. Minimum STC rating of 20

iv. Seal to reduce sound and particulate transmission between rooms around entire system including door bottom

v. Door latching

vi. Soft self closer

vii. Match existing door finishes of campus doors

a. Healthcare (serenityslidingdoor.com)