Questions & Answers for
RFP: 36C25919R0077, Replace Wander Guard System
(Q 1).) In the solicitation is states “This project shall consist of removal of all existing components including wiring and conduit. Contractor shall Install the new system including new wiring and conduit.” Is the existing conduit allowed to be reused? As conduit is not something that is traditionally replaced in all its entirely when updated/replacing a wander management system.
(A 1). Conduit will be allowed to be reused, any conduit that has been abandoned shall be removed.
(Q 2). In the solicitation is states the need of four (4) annunciators but there are only two (2) nurses stations.
(A 2). Only two annunciators will be required.
(Q 3). Which doors will annunciate to the nurse’s station(s)?
(A 3). ALL
(Q 4). Where will the “head end” be located, within the old or new CLC?
(A 4). The head end will be with the Old CLC in the Old location.
(last question – total of 4)