ABBREVIATIONS
AFF = ABOVE FINISH FLOOR
AUX = AUXILIARY
AWG = AMERICAN WIRE GAUGE
CD = CANDELA
CI = CIRCUIT INTEGRITY
DB = DECIBELS
EOL = END OF LINE
ER = EXISTING DEVICE RELOCATED
EX = EXISTING DEVICE TO REMAIN
FACP = FIRE ALARM CONTROL PANEL
FATC = FIRE ALARM TERMINAL CAN
FSD = FIRE SMOKE DAMPER
NAC = NOTIFICATION APPLIANCE
CIRCUIT
NEC = NATIONAL ELECTRICAL CODE
NFPA = NATIONAL FIRE PROTECTION
ASSOCIATION
SLC = SIGNALING LINE CIRCUIT
WP = WEATHER PROOF
GENERAL NOTES
1. THE INSTALLATION OF THE FIRE ALARM SYSTEM SHALL COMPLY WITH NFPA 72, 2016
EDITION, AND NFPA 70 2016EDITION.
2. THE AUDIBILITY OF FIRE ALARM WARNING DEVICES SHALL BE AUDIBLE THROUGH THE
OCCUPANCY WITH A MINIMAL SOUND LEVEL OF 15 dB'S OVER THE AVERAGE AMBIENT
NOISE LEVEL AND 5dB OVER THE MAXIMUM NOISE LEVEL EXCEEDING 60 SECONDS.
3. ALL CONDUIT SIZES SHALL BE IN ACCORDANCE WITH NEC 2016 EDITION.
4. UPON COMPLETION OF THE INSTALLATION OF THE FIRE ALARM SYSTEM, A
SATISFACTORY TEST OF THE ENTIRE SYSTEM SHALL BE PERFORMED IN THE
PRESENCE OF THE ENFORCING AGENCY.
5. ALL CONDUIT PENETRATIONS THROUGH FIRE RATED PARTITIONS SHALL PREVENT THE
PASSAGE OF HEAT, SMOKE AND FIRE GASES. ALL PENETRATIONS SHALL COMPLY
WITH U.L. ASSEMBLY LISTINGS AS REQUIRED.
INSTALLATION NOTES
1. ALL TERMINATIONS MUST BE AT A TERMINAL STRIP.
2. ALL CONDUCTOR TERMINATIONS SHALL BE LABELED.
3. ALL DEVICES MUST HAVE SCREW TERMINALS.
4. PULL ALL CONDUCTORS SPLICE FREE. WHERE SPLICES ARE UNAVOIDABLE PROVIDE
INSULATED BARRIER TYPE TERMINAL STRIPS AT JUNCTION POINTS. THE USE OF WIRE
NUTS, CRIMPED CONNECTORS OR TWISTING OF CONDUCTORS IS PROHIBITED.
5. RUN ALL WIRING TO CONTROL PANELS IN THE VERTICAL OR HORIZONTAL PLANE, MAKE
ALL TURNS AT 90 DEGREE ANGLES, AND TIGHTLY BUNDLE AND WRAP ALL WIRE.
6. IDENTIFY ALL CONDUCTORS INDIVIDUALLY WITH PERMANENT MARKINGS.
7. INSTALL ALL WIRING IN METALLIC CONDUIT.
8. ALL WIRING MUST BE SOLID COPPER, EXCEPT FOR SPEAKER CIRCUITS OR CIRCUITS
REQUIRING SHIELDING.
9. ALL SIGNALING LINE AND INITIATING DEVICE CIRCUITS MUST BE A MINIMUM 16 GAUGE
WIRE.
10.PAINT ALL FIRE ALARM JUNCTION BOXES AND COVERS RED IN UNFINISHED AREAS (i.e., ABOVE CEILINGS, MECHANICAL ROOMS, ETC). IN FINISHED AREAS, CONDUIT AND
JUNCTION BOXES CAN BE PAINTED TO MATCH ROOM FINISH, THE INSIDE COVER OF
THE JUNCTION BOX MUST BE IDENTIFIED AS "FIRE ALARM" AND THE CONDUIT MUST
HAVE PAINTED RED BANDS 3/4 INCH (20 MM) WIDE AT 10 FOOT (3.0M) CENTERS AND AT
EACH SIDE OF A FLOOR, WALL OR CEILING PENETRATION.
11.REMOTE TEST FOR DUCT SMOKE DETECTOR SHALL BE INSTALLED ON CEILING BELOW
DUCT SMOKE DETECTOR.
12. ALL SMOKE DETECTORS SHALL MAINTAIN A 3' SEPARATION FROM ANY AIR REGISTER
OR THE TIP OF ANY CEILING FAN BLADE.
1. INTENT, PURPOSE & REASON:
FIRE ALARM INITIATING AND NOTIFICATION DEVICES TO BE INSTALLED ON EXISTING
FIRE ALARM SYSTEM AS REQUIRED BY CODE. FIRE ALARM NOTIFICATION DEVICES
PROVIDED TO ALERT OCCUPANTS OF FIRE DANGER THROUGHOUT TENANT
IMPROVEMENT.
2. SCOPE:
SYSTEM SHALL PROVIDE FULL OCCUPANT NOTIFICATION THROUGHOUT REMODELED
AREA. REMOVE AND REPLACE EXISTING SMOKE DETECTOR, AND NEW DUCT
DETECTORS FOR NEW AIR HANDLING UNITS
3. TYPE OF FIRE ALARM SYSTEM:
THE EXISTING SYSTEM IS A MANUAL AND AUTOMATIC SYSTEM.
SCOPE OF WORK
CABLE LEGEND
SYMBOL
B AUDIO APPLIANCE CIRCUIT
DESCRIPTION TYPE COLOR
BLK/RED IN RED JACKET
V VISUAL APPLIANCE CIRCUIT ORG/BRN(2) #12 AWG THHN
16/2 FPLR
MANUAL PULL
STATION*
AREA SMOKE
DETECTOR*
FIRE
PROTECTION
SUPERVISORY
SWITCH
FACP POWER
FAIL & LOW
BATTERY
SYSTEM
TROUBLES
EXISTING SEQUENCE OF OPERATIONS
ELEVATOR
MACHINE
ROOM SMOKE
DETECTOR*
* NOTE: THE ACTIVATION OF ANY FIRE ALARM SIGNAL SHALL INITIATE THE FOLLOWING: 1. SHUTDOWN AIR HANDLER ON RESPECTIVE FLOOR
** NOTE: AUDIBLE AND VISUAL SIGNALING DEVICES WILL AUTOMATICALLY ACTIVATE ON THE FLOOR OF ALARM.
FIRE
PROTECTION
WATER FLOW
SWITCH
DUCT SMOKE
DETECTOR
ELEVATOR
SHUNT TRIP
120v POWER
LOSS
LOW WATER
LEVEL IN
WATER TANK
ANNUNCIATE ALARM AT FIRE
CONTROL PANEL
ANNUNCIATE TROUBLE AT
FIRE CONTROL PANEL
ANNUNCIATE SUPERVISORY
AT FIRE CONTROL PANEL
ACTIVATE AUDIBLE/VISUAL
ALARM SIGNAL ON
ASSOCIATED FLOOR**
TO CENTRAL MONITORING
STATION
TRANSMIT TROUBLE SIGNALS
TO CENTRAL MONITORING
STATION
TRANSMIT SUPERVISORY
SIGNALS TO CENTRAL
MONITORING STATION
PRIMARY ELEVATOR RECALL
ALTERNATE ELEVATOR
RECALL
FIREFIGHTER'S SERVICE
VISUAL INDICATOR
SHUNT ELEVATOR POWER
SHUT DOWN ASSOCIATED
AIR HANDLER UNIT
TRANSMIT ALARM SIGNALS
RELEASE DOOR HOLDERS
1st FLOOR
ELEVATOR
LOBBY SMOKE
DETECTOR*
2nd-6TH
FLOOR
ELEVATOR
LOBBY SMOKE
DETECTOR*
DEVICE:
ACTION:
FIRE PUMP
RUNNING
FIRE PUMP
TROUBLE
D SIGNALING LINE CIRCUIT BLK/RED IN RED JACKET16/2 FPLR
NPS
QTY SYMBOL DEVICE DESCRIPTION MODEL NUMBER MANUFACTURER
FIRE ALARM LIST OF MATERIALS
BACKBOXES
NOTIFICATION APPLIANCE CIRCUIT
POWER SUPPLY
N/ABPS6A
GENESIS MULTI-CANDELA CEILING SPEAKER STROBE
(# = CANDELA) GCHFWF-S2VMC
EDWARDS
EDWARDS
4 SQUARE W/
EXTENSION RING
ER
4 SQUARE W/
3o EXTENSION RING
EXISTING SMOKE DETECTOR
WITH STANDARD BASE
SIGA-PS
SIGA-SB EDWARDS1
FACP
CEILING
CONDUIT
AUDIO/VISUAL DEVICE
@48" O.C. OF
OPERATING
HANDLE A.F.F.
BOTTOM OF LENS
@+80"-93" A.F.F.
72"
FLOOR/ ROOF ABOVE
INTERIOR
INTERSTITIAL SPACE
PULL STATION
FLUSH MOUNTING AUDIO/VISUAL DEVICE TO
CEILING USING A STANDARD 4"
DEEP SQUARE BOX W/EXTENSION RING
12" MAXTOP OF DETECTOR
ACCEPTABLE HERE
FINISHED
FLOOR
SCALE: NONE
FIRE ALARM MOUNTING HEIGHT
STUB CONDUIT INTO ATTIC SPACE
FOR OPEN WIRE APPLICATIONS
FIRE
F I R E
CONDUIT
CEILING
TOP OF AUDIBLE ONLY DEVICE TO BE
GREATER THAN 90" A.F.F. AND NO CLOSER
THAN 6" FROM CEILING
INTERSTITIAL SPACE
F I R E
NPS
72"
DETECTOR SHALL BE MOUNTED A DISTANCE
OF AT LEAST 3' FROM ANY MECHANICAL
DIFFUSER AND 12" FROM ANY SPRINKLER HEAD
NOTE: ALL CABLE IS IN 3/4" EMT UNLESS OTHERWISE NOTED.
GENESIS MULTI-CANDELA CEILING STROBE
(# = CANDELA) GCF-VM EDWARDS
4 SQUARE W/
EXTENSION RING
ADDRESSABLE DUCT SMOKE DETECTOR HOUSING
WITH ADDRESSABLE SMOKE DETECTOR
N/ASIGA-DH
SIGA-PS
EDWARDS
2 HIGH POWERED CONTROL RELAY SIGA-CRH EDWARDS
CR
4 SQUARE W/
EXTENSION RING
EXISTING DEVICE TO BE REMOVED AND RELOCATEDER
EXISTING DEVICE TO BE REMAINEX
M
N
N.25
N.5
CR
CR
J
2D
2D
2D
EX
AC
EXISTING
AC-58
SLC POINT OF
CONNECTION
AC
SUPPLY
RETURN
1/4W 15cd
N1-02 ER
1/4W 95cd
N1-03
1/4W 30cd
N1-04
15cd
N1-05ER
NIC
2B,2V
2B,2V
2V
N
M
N.25
N.5
1/4W 15cd
N1-06
EOL-N1
ER
1/4W 75cd
N1-01
ER
J
B,V
B,V B,V
EXISTING POINT OF
CONNECTION
ER
1/4W 15cd
N1-02
ER
1/4W 95cd
N1-03
1/4W 30cd
N1-04
15cd
N1-05
FROM NEAREST
INITIATING DEVICE
FROM NEAREST
INITIATING DEVICE
CRCR
EX
AC
AC
2D
DD
1/4W 15cd
N1-06
EOL-N1
ER
1/4W 75cd
N1-01
ER
NPS
EX
3.0 Amps available at
Amps available overall.
each output NAC. 6.5
Battery
IN
Trouble COM
NC
Sense 2
OUT
COM
NO
IN
Sense 1 COM
OUT
NOTE: CUT JUMPER
JP4 IF USING LESS
THAN 10AH BATTERIES
JP4
AUX
NAC #1 (OUT)
NAC #3 (OUT)
NAC #2 (OUT)
NAC #4 (OUT)
SPEAKER
STROBE SPEAKER
NAC CIRCUIT 1
EOL 15K
BATTERIES
WIRED IN SERIES
12V 7AH
SEALED
LEAD-ACID
BATTERY
12V 7AH
SEALED
LEAD-ACID
BATTERY
EXISTING120vac 20 AMP
DEDICATED CIRCUIT BREAKER.
IDENTIFIED "FIRE ALARM"
BREAKER SHALL BE LOCK ON
TYPE AND WIRING TO BE
PROVIDED BY ELECTRICAL
CONTRACTOR.
FROM EXISTING
AUDIO DEVICE
NPS# 1
FROM PREVIOUS
EXISTING DEVICE
STROBE
SENSE TRIGGER FROM
EXISTING NPS
SPARE
SPARE
TO DDC
STATUS
(BY OTHERS)
SD-TRK
REMOTE TEST
STATION
N C
N C
C
N O
C
N O
SIGA-CRH
HIGH POWER
RELAY
MODULE-+ - +
SIGA-SB
STANDARD BASE
TO SHUTDOWN
AIR HANDLING
UNIT
TO NEXT
EXISTING DEVICE
AUDIO CIRCUIT
EOL 15K
| FA-001 |
| FA-001 |
| Layout1 |
| FA-101 |
| FA-101 |
| Layout1 |
| FA-501 |
| FA-501 |
| Layout1 |