36C25726Q0448.pdf
PDF 677 KB Posted
- Attached to
- Sterile Processing Service (SPS) Water Testing - STX VAMC Federal contract opportunity
- Solicitation number
- 36C25726Q0448
About this file
This is a Solicitation/Contract/Order for Commercial Products and Commercial Services (SF 1449) for sterile processing systems water testing, maintenance, and repair services.
The Department of Veterans Affairs, South Texas Veterans Healthcare System is soliciting proposals for comprehensive sterile processing services (SPS) water testing across four facilities: Audie Murphy, Dental (Data Point), Northwest Healthcare Center (State Hwy 151), and Kerrville. The contract is a 100% Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside with a budget of $19 million. The base year runs from June 30, 2026 through June 29, 2027, with four optional one-year extensions through June 29, 2031. The solicitation requires contractors to provide monthly water testing and maintenance per ANSI/AAMI ST108:2023 standards, including critical water sampling at multiple points of use, quarterly reverse osmosis system sanitization, filter replacements, in-line monitoring equipment installation, and emergency repair services (capped at $140,000 annually). Monthly invoicing is required via electronic submission through the Tungsten Network. Proposals are due June 5, 2026 at 10:00 AM CDT, submitted in two volumes (technical and price) via email to shawn.reinhart@va.gov. Evaluation criteria include technical capability, price, and past performance. The contract employs FAR Part 12 simplified acquisition procedures for commercial services and incorporates SDVOSB limitations on subcontracting (50% for services). Site visits are scheduled for May 15, 2026 at specified times across all four locations. Payment terms are Net 30 with discount incentives available.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25726Q0448 0001.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PAGE 1 OF 1. REQUISITION NO.
2. CONTRACT NO. 3. AWARD/EFFECTIVE DATE 4. ORDER NO. 5. SOLICITATION NUMBER 6. SOLICITATION ISSUE DATE
a. NAME b. TELEPHONE NO. (No Collect Calls) 8. OFFER DUE DATE/LOCAL
TIME
9. ISSUED BY CODE 10. THIS ACQUISITION IS UNRESTRICTED OR SET ASIDE: % FOR:
SMALL BUSINESS
HUBZONE SMALL
BUSINESS
SERVICE-DISABLED
VETERAN-OWNED
SMALL BUSINESS
WOMEN-OWNED SMALL BUSINESS
(WOSB) ELIGIBLE UNDER THE WOMEN-OWNED
SMALL BUSINESS PROGRAM
EDWOSB
8(A)
NAICS:
SIZE STANDARD:
11. DELIVERY FOR FOB DESTINA-
TION UNLESS BLOCK IS
MARKED
SEE SCHEDULE
12. DISCOUNT TERMS
13a. THIS CONTRACT IS A
RATED ORDER UNDER
DPAS (15 CFR 700)
13b. RATING
14. METHOD OF SOLICITATION
RFQ IFB RFP
15. DELIVER TO CODE 16. ADMINISTERED BY CODE
17a. CONTRACTOR/OFFEROR CODE FACILITY CODE 18a. PAYMENT WILL BE MADE BY CODE
TELEPHONE NO. UEI: EFT:
PHONE: FAX:
17b. CHECK IF REMITTANCE IS DIFFERENT AND PUT SUCH ADDRESS IN OFFER
18b. SUBMIT INVOICES TO ADDRESS SHOWN IN BLOCK 18a UNLESS BLOCK BELOW IS CHECKED
SEE ADDENDUM
19. 20. 21. 22. 23. 24.
ITEM NO. SCHEDULE OF SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT
(Use Reverse and/or Attach Additional Sheets as Necessary)
25. ACCOUNTING AND APPROPRIATION DATA 26. TOTAL AWARD AMOUNT (For Govt. Use Only)
27a. SOLICITATION INCORPORATES BY REFERENCE FAR 52.212-1, 52.212-4. FAR 52.212-3 AND 52.212-5 ARE ATTACHED. ADDENDA ARE ARE NOT ATTACHED.
27b. CONTRACT/PURCHASE ORDER INCORPORATES BY REFERENCE FAR 52.212-4. FAR 52.212-5 IS ATTACHED. ADDENDA ARE ARE NOT ATTACHED
28. CONTRACTOR IS REQUIRED TO SIGN THIS DOCUMENT AND RETURN _______________ 29. AWARD OF CONTRACT: REF. ___________________________________ OFFER COPIES TO ISSUING OFFICE. CONTRACTOR AGREES TO FURNISH AND DATED ________________________________. YOUR OFFER ON SOLICITATION DELIVER ALL ITEMS SET FORTH OR OTHERWISE IDENTIFIED ABOVE AND ON ANY (BLOCK 5), INCLUDING ANY ADDITIONS OR CHANGES WHICH ARE ADDITIONAL SHEETS SUBJECT TO THE TERMS AND CONDITIONS SPECIFIED SET FORTH HEREIN IS ACCEPTED AS TO ITEMS:
30a. SIGNATURE OF OFFEROR/CONTRACTOR 31a. UNITED STATES OF AMERICA (SIGNATURE OF CONTRACTING OFFICER)
30b. NAME AND TITLE OF SIGNER (TYPE OR PRINT) 30c. DATE SIGNED 31b. NAME OF CONTRACTING OFFICER (TYPE OR PRINT) 31c. DATE SIGNED
AUTHORIZED FOR LOCAL REPRODUCTION (REV. NOV 2021)
PREVIOUS EDITION IS NOT USABLE Prescribed by GSA - FAR (48 CFR) 53.212
7. FOR SOLICITATION
INFORMATION CALL:
STANDARD FORM 1449
SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES
OFFEROR TO COMPLETE BLOCKS 12, 17, 23, 24, & 30
36C25726Q0448 05-06-2026
Mr. Shawn R. Reinhart 254-421-6661 06-05-2026
10AM CDT
36C257
Department of Veterans Affairs Central Texas Veterans HCS 1901 Veterans Memorial Dr. Building #171 Temple, TX 76504
X 100
X
541380
$19 Million
NET 30
N/A
36C671
Department of Veterans Affairs South Texas Veterans HCS 7400 Merton Minter St.
San Antonio, TX 78229
36C257
Department of Veterans Affairs Central Texas Veterans HCS 1901 Veterans Memorial Dr. Building 171
This is accomplished through the Tungsten Network located at:
http://www.fsc.va.gov/einvoice.asp This is mandatory and the sole method for submitting invoices.
(877) 353-9791 (512) 460-5540
See CONTINUATION Page
The Contractor shall provide Sterile Processing Systems testing, maintenance, and repair of sterile processing water systems testing IAW the Statement of Work (SOW).
Acquisition is being conducted IAW FAR Part 12.
Periods of Performance Base Year: 30 June 2026 – 29 June 2027 1st Option Year: 30 June 2027 – 29 June 2028 2nd Option Year: 30 June 2028 – 29 June 2029 3rd Option Year: 30 June 2029 – 29 June 2030 4th Option Year: 30 June 2030 – 29 June 2031
Site Visits to be conducted on May 15, 2026 as follows (all times are Central Daylight Time):
Audie Murphy: 9 AM; Dental: 11 AM; NW 151: 12:30 PM;
NW 151: 12:30 PM; Kerrville: 3 PM
Refer to Instructions of Offerors and Evaluation Factors on pages 33 to 38 for additional details.
See CONTINUATION Page
X X
X 1
Mr. Shawn R. Reinhart Contracting Officer
36C25726Q0448
Table of Contents
SECTION A
A.1 SF 1449 SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL PRODUCTS AND
COMMERCIAL SERVICES
SECTION B - CONTINUATION OF SF 1449 BLOCKS
B.1 CONTRACT ADMINISTRATION DATA
B.2 PRICE/COST SCHEDULE
ITEM INFORMATION
B.3 DELIVERY SCHEDULE
B.4 PERFORMANCE WORK STATEMENT
SECTION C - CONTRACT CLAUSES
C.1 ADDENDUM to FAR 52.212-4 CONTRACT TERMS AND CONDITIONS –
COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES
SECTION D - CONTRACT DOCUMENTS, EXHIBITS, OR ATTACHMENTS
SECTION E - SOLICITATION PROVISIONS
E.1 52.252-1 SOLICITATION PROVISIONS INCORPORATED BY REFERENCE (FEB
1998)
E.2 52.209-7 INFORMATION REGARDING RESPONSIBILITY MATTERS (OCT 2018)
E.3 ADDENDUM to FAR 52.212-1 INSTRUCTIONS TO OFFERORS – COMMERCIAL
PRODUCTS AND COMMERCIAL SERVICES
E.4 52.212-2 EVALUATION - COMMERCIAL PRODUCTS AND COMMERCIAL
SERVICES (NOV 2021)
E.5 52.212-2 ADDENDUM to EVALUATION - COMMERCIAL PRODUCTS AND
COMMERCIAL SERVICES
E.6 52.216-1 TYPE OF CONTRACT (NOV 2025) (DEVIATION)
E.7 52.233-2 SERVICE OF PROTEST (SEP 2006)
E.8 VAAR 852.233-71 ALTERNATE PROTEST PROCEDURE (OCT 2018)
SECTION B - CONTINUATION OF SF 1449 BLOCKS
B.1 CONTRACT ADMINISTRATION DATA
1. Contract Administration: All contract administration matters will be handled by the following individuals:
a. CONTRACTOR:
b. GOVERNMENT: Contracting Officer 36C257 Department of Veterans Affairs Central Texas Veterans HCS 1901 Veterans Memorial Dr. Building #171
2. CONTRACTOR REMITTANCE ADDRESS: All payments by the Government to the contractor will be made in accordance with:
[X] 52.232-33, Payment by Electronic Funds Transfer—System For Award Management
3. INVOICES: Invoices shall be submitted in arrears:
a. Quarterly []
b. Semi-Annually []
c. Other [X] Monthly upon completion, inspection and acceptance
4. GOVERNMENT INVOICE ADDRESS: All Invoices from the contractor shall be submitted electronically in accordance with VAAR Clause 852.232-72 Electronic Submission of Payment Requests.
ACKNOWLEDGMENT OF AMENDMENTS: The offeror acknowledges receipt of amendments to the Solicitation numbered and dated as follows:
AMENDMENT NO DATE
B.2 PRICE/COST SCHEDULE
ITEM INFORMATION
ITEM
NUMBER
DESCRIPTION OF
SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT
12.00 MO ______________ ______________
Audie Murphy SPS - 7400 Merton Minter Blvd, San Antonio, TX.
Contract Period: Base POP Begin: 06-30-2026 POP End: 06-29-2027
Dental SPS - 8410 Data Point Rm 110, San Antonio, TX
Kerrville SPS - 3600 Memorial Blvd., Kerrville, TX
Northwest Healthcare Center SPS - 9939 State Hwy 151, San Antonio, TX
1.00 YR _______________ ______________
Emergency Services - Repairs and Associated Additional Testing required after emergency repairs. A quote will be submitted for this Line Item and MUST be approved by the CO/COR prior to any work being performed.
Contractor shall only bill for actuals.
This is a not to exceed amount per year of $140,000.00.
Contract Period: Base
Retained Services of Certified Water Treatment Specialist (Recommended per ST-108)
Contract Period: Base
10.00 EA ______________ ______________
Base Year Only. The installation of in-line continuous pH, Conductivity, TDS, Resistivity, Salinity, Temperature, Flow meter monitoring equipment system for all four (4) sites (Audie Murphy, Data Point, NWHCC and Kerrville).
In-line continuous pH, Conductivity, Flow monitoring equipment system (ALM, NWHCC-151, Data Point and KD)
Contract Period: Base
ITEM
NUMBER
DESCRIPTION OF
SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT
1.00 JB ______________ ______________
Base Year Only
Critical Water System Upgrades
• Upgrades to Kerrville SPS by installing new RO System and associated new distribution and return loop and test ports for all equipment.
• For Data Point, install RO distribution and return loop system, and test ports for all equipment.
• Add DI tanks, Carbon Filters tanks for Critical Water for ALM, Kerrville, Dental and Northwest 151.
Contract Period: Base
Contract Period: Option 1 POP Begin: 06-30-2027 POP End: 06-29-2028
1.00 YR ______________ ______________
after emergency repairs. A quote will be submitted for this Line Item and MUST be approved by the CO/COR prior to any work being performed.
Contractor shall only bill for actuals.
This is a not to exceed amount per year of $140,000.00.
Contract Period: Option 1
Retained Services of Certified Water Treatment Specialist
ITEM
NUMBER
DESCRIPTION OF
SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT
Audie Murphy SPS - 7400 Merton Minter Blvd, San Antonio, TX.
Contract Period: Option 2 POP Begin: 06-30-2028 POP End: 06-29-2029
Contract Period: Option 2 after emergency repairs. A quote will be submitted for this Line Item and MUST be approved by the CO/COR prior to any work being performed.
Contractor shall only bill for actuals.
This is a not to exceed amount per year of $140,000.00.
Contract Period: Option 2
Contract Period: Option 3 POP Begin: 06-30-2029 POP End: 06-29-2030
ITEM
NUMBER
DESCRIPTION OF
SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT
Contract Period: Option 3 POP Begin: 06-30-2029 after emergency repairs. A quote will be submitted for this Line Item and MUST be approved by the CO/COR prior to any work being performed.
Contractor shall only bill for actuals.
This is a not to exceed amount per year of $140,000.00.
Contract Period: Option 3
Contract Period: Option 4 POP Begin: 06-30-2030 POP End: 06-29-2031 after emergency repairs. A quote will be submitted for this Line Item and MUST be approved by the CO/COR prior to any work being performed.
Contractor shall only bill for actuals.
ITEM
NUMBER
DESCRIPTION OF
SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT
This is a not to exceed amount per year of $140,000.00.
Contract Period: Option 4 POP Begin: 06-30-2030 POP End: 06-29-2031
LOCAL STOCK NUMBER: CLIN 0005
GRAND TOTAL __________________
B.3 DELIVERY SCHEDULE
ITEM
NUMBER SHIPPING INFORMATION QUANTITY
DELIVERY
DATE
0001-
SEE SCHEDULE
B.2
SEE
SCHEDULE
B.2
06/30/2026 - 06/29/2031
B.4 PERFORMANCE WORK STATEMENT
Sterile Processing Services (SPS) Water Testing
1. BACKGROUND. South Texas Veterans Healthcare System facilities has a Sterile Processing Systems requirement for testing, maintenance, and repair of sterile processing water systems. SPS is a critical part of any Hospital as it ensures all clinical departments have a readily available supply of sterile equipment. One of the key pieces of equipment supporting any SPS is the direct critical water supply to SPS personnel and equipment.
1.1 The updated AAMI ST108:2023 Standard, which governs the processes and requirements for Sterile Processing, added requirements to the roster of locations needing monthly critical water sampling. Per the standard, the requirement to test critical water at “every point of use” has significantly raised the quantity of water samples needed each month. Current water sampling contracts only cover the bare minimum of testing locations at the source of Critical Water systems.
2. SCOPE OF WORK. The purpose of this service is to provide for the testing of water, maintenance, and repair of water systems to ensure effective water quality for processing medical devices. The testing shall include testing of utility water, critical water and steam per guidance published in ANSI/AAMI ST108:2023, Water for the Processing of Medical Devices. In the event that ST108 is updated during the life of the contract the Contractor shall use the most recent version unless informed differently.
2.1 ST108:2023 (ST108) covers the minimum requirements for the quality of water and steam purity necessary to effectively process medical devices. The VHA may require more stringent requirements or more frequent testing and maintenance of water systems for processing medical devices in addition to the minimum requirements called out in ST108; however, the ST108 is the current guidance used by the VHA.
2.1.1 The VHA prefers the Contractor schedule monthly work, testing at the beginning of the month.
Ideally, test within the first week of every month to enable more time during a particular month for any retesting that may be required.
2.2 PERIOD OF PERFORMANCE. The period of performance will be for a base year, with four
(4) option years.
Base Year: 30 June 2026 – 29 June 2027 1st Option Year: 30 June 2027 – 29 June 2028 2nd Option Year: 30 June 2028 – 29 June 2029 3rd Option Year: 30 June 2029 – 29 June 2030 4th Option Year: 30 June 2023 – 29 June 2031
3. CONTRACTOR RESPONSIBILITY. The Contractor shall maintain and repair the sterile processing equipment related to critical water production and the steam supported sterilization system equipment. The work shall include required maintenance, change of Deionized (DI) Tanks, system filters and Reverse Osmosis (RO) membrane changes and water testing per the frequencies noted in ST108. The Contractor shall perform quarterly RO system sanitization, Distribution Loop sanitization and replace RO membrane on quarterly basis. The locations for these services are listed below in paragraphs 3.2.1 through 3.2.4.
3.1 The Contractor shall provide all labor, materials, tools, equipment, applicable state licenses and permits to accomplish the requirements.
3.1.1 The Contractor shall provide all testing requirements as outlined by ST108 for testing quantity guides.
3.1.2 The Contractor shall provide a fully qualified Laboratory for processing of water samples to meet all metrics of ST108-2023. The Contractor shall ensure all laboratory certificates, credentials and capabilities are provided to the Contracting Officers Representative (COR).
3.1.3 The Contractor shall follow testing frequencies as described in ST108. For any testing completed, provide the results/reports back to the VHA as soon as possible after completion.
3.1.4 The Contractor shall install continuous in-line monitoring devices for pH, Conductivity and Flow Meters in the pump room for all sites at the critical water distribution loop out (Audie Murphy SPS, Dental SPS, Kerrville SPS and Northwest Healthcare Center SPS). The installed device shall be able to perform to the below table requirements.
In-Line Monitoring Device Table
Conductivity TDS Resistivity Salinity pH ORP/mV IN Temperature Ranges 0 µS - 200 mS 0 ppm - 200 ppt 10 KΩ - 40 MΩ 0 ppm - 200 ppt 0 - 14 pH ±2000 mV 0 - 250˚C
Accuracy ± 1% of reading ± 1% of reading ± 1% of reading ± 1% of reading ± 0.01 pH ± 2 mV ± 0.1˚C Resolution 0.01 (<100 µS)
0.1 (<1000 µS) 1 (<10,000 µS)
0.01 (<100 mS)
0.1 (≤200 mS)
0.01 (<100 ppm)
0.1 (<1000 ppm) 1 (<10,000 ppm)
0.01 (<100 ppt)
0.1 (≤200 ppt)
0.01 (<100 kΩ)
0.1 (<1000 kΩ)
0.01 (<10 MΩ)
0.1 (≤40 MΩ)
0.001 (<10 ppt)
0.01 (<100 ppt)
0.1 (≤200 ppt)
0.01 pH 1 mV 0.1˚C/F
Auto Temperature
Compensation 0-71˚C
32-160˚F 0-71˚C 32-160˚F 0-71˚C
32-160˚F 0-71˚C 32-160˚F 0-71˚C
32-160˚F - -
Adjustable Temperature
Compensation 0 - 10%/˚C 0 - 10%/˚C 0 - 10%/˚C 0 - 10%/˚C On/Off - -
Cond/TDS Ratios
Preprogrammed KCl, NaCl, 442™ KCl, NaCl, 442™ - KCl, NaCl, 442™ - - -
Adjustable Cond/TDS Ratio Factor
0.20-7.99 0.20-7.99 - 0.20-7.99 - - -
COND / RES 1 Conductivity, Resistivity, TDS, or Salinity Sensor Input COND / RES 2 Conductivity, Resistivity, TDS, or Salinity Sensor Input pH / ORP Myron L® Company model pH or ORP Sensor Input mV IN BNC Style mV Model Sensors FLOW SW Flow Switch Input 4-20 mA IN 4-20 mA Signal Input (<600Ω) FLOW / PULSE Flow Rate and Volume Totalizer/Pulse Counter/Frequency Counter
(0.5-50,000 Hz) RTD Temperature Sensor Input (1000 Ω RTD)
24 VAC / 12-24
VDC
Power Supply Input (1A Max)
RELAY #1 Normally Open or Normally Closed Relay Output (5A@30VDC, 8A@250VAC)
RELAY #2 Normally Open or Normally Closed Relay Output (5A@30VDC, 8A@250VAC)
RELAY #3 Normally Open or Normally Closed Relay Output (5A@30VDC, 8A@250VAC)
RA #1 Remote Alarm Output RA #2 Remote Alarm Output 4-20 mA OUT 4-20 mA Signal Output (20-36VDC) REC O/P 0-10 VDC Recorder Output (20mA Max) RS-485 ASCII Serial Communications Output
3.1.5 The Contractor shall install tank capacity alarms (e.g., red/green indicator lights) are required for both Carbon and DI for all site (Audie Murphy SPS, Dental SPS, Kerrville SPS and Northwest Healthcare Center SPS).
3.1.6 The contractor shall provide all submittal for material and equipment installation for VA approval prior to installation. The contractor shall ensure that all installed equipment, devices meet ST 108 requirements.
3.1.7 When there is an increase in HPC, bacteria, or endotoxin, or fail test in any Point of use (POU), the contractor shall perform a re-test of that POU only within 7 Calander days.
3.1.8 Whenever there is intensive growth of bacteria or endotoxin in the system from pervious test that was performed, the Contractor shall perform Ozone Sanitization and three (3) days of testing within (five) calendar days.
3.1.9 The Contractor shall install additional sample test ports at locations marked “X” on Table 1- Audie Murphy SPS Location, Table 2- Dental (Datapoint) SPS Location, Table 3- Northwest Healthcare Center SPS Location and Table 4- Kerrville SPS location.
3.1.10 Whenever there is a modification to the system, the contractor shall perform sanitization and three days of testing for all points of use (POUs).
3.1.11 The Contractor shall provide all test results within (five) calendar days after testing.
3.2 The Contractor shall conduct a monthly water monitoring program as described for the following locations:
3.2.1 Audie Murphy SPS - 7400 Merton Minter Blvd, San Antonio, TX.
• Perform all testing per the reference tables in ST108.
• Perform all tests to comply with the frequencies required and listed in the associated ST108 tables.
• Maintain the VA’s RO system and all supplied distribution equipment.
• Provide DI and carbon tanks, scale inhibitor monthly.
• Perform quarterly RO system sanitization, Distribution Loop sanitization and replace RO membrane on quarterly basis.
• Provide DI service tanks for the sanitary sinks within SPS monthly.
• Provide monthly quality report when tanks are exchanged.
• Provide monthly testing and service report.
• Replace all filters (pre & post) quarterly.
• Provide the filter replacement requirement information.
• Provide Endotoxin Filter as required annually.
• Provide monthly maintenance service for RO System and Distribution loop as required by
ST108.
3.2.2 Dental SPS - 8410 Data Point Rm 110, San Antonio, TX.
• Perform all testing per the reference tables in ST108.
• Perform all tests to comply with the frequencies required and listed in the associated ST108 tables.
• Maintain the VA’s RO system and all supplied distribution equipment.
• Provide DI and carbon tanks, scale inhibitor monthly.
• Perform quarterly RO system sanitization, Distribution Loop sanitization and replace RO membrane on quarterly basis.
• Provide DI service tanks for the sanitary sinks within SPS monthly.
• Provide monthly quality report when tanks are exchanged.
• Provide monthly testing and service report.
• Replace all filters (pre & post) quarterly.
• Provide the filter replacement requirement information.
• Provide Endotoxin Filter as required annually.
3.2.3 Kerrville SPS - 3600 Memorial Blvd., Kerrville, TX
• Perform all tests to comply with the frequencies required and listed in the associated ST108 tables.
• Maintain the VA’s RO system and all supplied distribution equipment.
• Provide DI and carbon tanks, scale inhibitor monthly.
• Perform quarterly RO system sanitization, Distribution Loop sanitization and replace RO membrane on quarterly basis.
• Provide DI service tanks for the sanitary sinks within SPS monthly.
• Provide monthly quality report when tanks are exchanged.
• Provide monthly testing and service report.
• Replace all filters (pre & post) quarterly.
• Provide the filter replacement requirement information.
• Provide Endotoxin Filter as required annually.
3.2.4 Northwest Healthcare Center SPS - 9939 State Hwy 151, San Antonio, TX
• Perform all tests to comply with the frequencies required and listed in the associated ST108 tables.
• Maintain the VA’s RO system and all supplied distribution equipment.
• Provide DI and carbon tanks, scale inhibitor monthly.
• Perform quarterly RO system sanitization, Distribution Loop sanitization and replace RO membrane on quarterly basis.
• Provide DI service tanks for the sanitary sinks within SPS monthly.
• Provide monthly quality report when tanks are exchanged.
• Provide monthly testing and service report.
• Replace all filters (pre & post) quarterly.
• Provide the filter replacement requirement information.
• Provide Endotoxin Filter as required annually.
• Provide monthly maintenance service for RO System and Distribution loop as required by
ST108.
3.3 CRITICAL WATER TEST POINTS OF USE BY LOCATION
3.3.1 Audie Murphy Location. Rows noted with an “X” under the column “Location where Sample needs to be Collected” indicate sample location for collection requirements based off the “Frequency” column. Rows noted with an “X” under the column “Additional Sample Port Install Required to Collect Sample” indicates a sample port installation required for collection.
Table 1 – Audie Murphy SPS Location
No of Sample
Location
Type
Location where
Sample needs to be Collected
Additional Sample
Port Install Required to
Collect Sample
Critical Water System Updates
Frequency of Testing for each port
1 Sink 1 - Cold
Utility X Quarterly
2 Sink 1 - Hot Utility X Quarterly 3 Sink 1
Critical Critical X Monthly
4 Sink 2 - Cold
Utility X Quarterly
5 Sink 2 - Hot Utility X Quarterly 6 Sink 2 -
Critical Critical X Monthly
7 Sink 3 - Cold
Utility X Quarterly
8 Sink 3 - Hot Utility X Quarterly 9 Sink 3 -
Critical Critical X Monthly
10 Sink 4 - Cold
Utility X Quarterly
11 Sink 4 - Hot Utility X Quarterly 12 Sink 4 -
Critical Critical X Monthly
13 Washer 1 - Cold
Utility X X Quarterly
14 Washer 1 - Hot
Utility X X Quarterly
15 Washer 1 - Critical
Critical X Monthly
16 Washer 2 - Cold
Utility X X Quarterly
17 Washer 2 - Hot
Utility X X Quarterly
18 Washer 2 - Critical
Critical X Monthly
19 Cart Washer 1- Cold
Utility X X Quarterly
20 Cart Washer
- Hot
Utility X X Quarterly
21 Cart Washer
- Critical
Critical
X Monthly
22 Rm. K112 - Sink Cold
Utility X Quarterly
23 Rm. K112 - Sink Hot
Utility X Quarterly
24 Rm. K112.1
AER
Utility
X Quarterly
3.3.2 Datapoint Location (Dental Services). Rows noted with an “X” under the column “Location where Sample needs to be Collected” indicate sample location for collection requirements based off the “Frequency” column. Rows noted with an “X” under the column “Additional Sample Port Install Required to Collect Sample” indicates a sample port installation required for collection.
Location
Type
Location where
Sample needs to be Collected
Additional Sample
Port Install Required to
Collect Sample
Critical Water System Updates for each port
(alternate the 2)
25 Rm. E120
AER
Utility X Quarterly
26 RO Dist Loop Out
Critical X Monthly
27 RO Dist Loop In
Critical X Monthly
28 Steam Condensate #1 (House)
Steam
29 Sterilizer #4 (House Steam)
30 Sterilizer #5 (House Steam)
31 Sterilizer #13 (Self Made)
Quarterly
32 Sterilizer #12 (Self Made)
33 Ultra Sonic Washer #1
Critical X Monthly
34 Ultra Sonic Washer #1
Utility X Quarterly
35 Ultra Sonic Washer #2
Critical X Monthly
36 Ultra Sonic Washer #2
Utility X Quarterly
37 Ultra Sonic Washer #3
Critical X Monthly
38 Ultra Sonic Washer #3
Utility X Quarterly
39 Ultra Sonic Washer #4
Critical X Monthly
40 Ultra Sonic Washer #4
Utility X Quarterly
Table 2 – Dental (Datapoint) SPS Location
3.3.3 Northwest Health Care Center – 151. Rows noted with an “X” under the column “Location where Sample needs to be Collected” indicate sample location for collection requirements based off the “Frequency” column. Rows noted with an “X” under the column “Additional Sample Port Install Required to Collect Sample” indicates a sample port installation required for collection.
Table 3 – Northwest Healthcare Center SPS Location
Sample
Sample Location
Sample Type
Location where
Sample needs to be Collected
Additional Sample Port
Install Required to
Collect Sample
Critical Water System
Updates?
for each port
1 Washer - Cold
Utility X X Quarterly
2 Washer - Hot
Utility X X Quarterly
3 Washer - Critical
Critical X X Monthly
4 Ultrasonic 1
- Cold
Utility X X Quarterly
5 Ultrasonic 1
- Hot
Utility X X Quarterly
6 Ultrasonic 1
- Critical
Critical X X Monthly
7 Ultrasonic 2
- Cold
Utility X X Quarterly
8 Ultrasonic 2
- Hot
Utility X X Quarterly
9 Ultrasonic - Critical
Critical X X Monthly
10 Sink - Cold Utility X X Quarterly 11 Sink - Hot Utility X X Quarterly 12 Sink -
Critical Critical X X Monthly
13 Sterilizer #1 (Stand Alone)
Steam X Quarterly
14 Sterilizer #2 (Standalone)
Steam X Quarterly
Loop Out Prior to Equipment
X X Monthly
16 RO Machine Port
Critical X X Monthly
No of Sample
Sample Location
Sample Type
Location where
Sample needs to be Collected
Additional Sample Port Install
Required to Collect Sample
Critical Water System Updates
Frequency of Testing for each port
1 Sink 1 - Cold
Utility X Quarterly
2 Sink 1 - Hot Utility X Quarterly 3 Sink 1
Critical Critical X Monthly
4 Sink 2 - Cold
Utility X Quarterly
5 Sink 2 - Hot Utility X Quarterly 6 Sink 2 -
Critical Critical X Monthly
7 Washer 1 - Cold
Utility X X Quarterly
8 Washer 1 - Hot
Utility X X Quarterly
9 Washer 1 - Critical
Critical X X Monthly
10 Washer 2 - Cold
Utility X X Quarterly
11 Washer 2 - Hot
Utility X X Quarterly
12 Washer 2 - Critical
Critical X X Monthly
13 Cart Washer - Cold
Utility X X Quarterly
14 Cart Washer - Hot
Utility X X Quarterly
15 Cart Washer -
16 Ultrasonic - Cold
Utility X X Quarterly
17 Ultrasonic - Hot
Utility X X Quarterly
18 Ultrasonic - Critical
Critical X Monthly
19 RO
Machine Point of Generation
20 RO Loop Sample (In Pump Rm.)
Monthly
No of Sample
Sample Location
Sample Type
Location where
Sample needs to be Collected
Additional Sample Port Install
Required to Collect Sample
Critical Water System Updates
Frequency of Testing for each port
21 Loop Test Point near Ultrasonic
X
Monthly
22 Sterilizer # (Processed
RO)
23 Sterilizer # (Processed
RO)
3.3.4 Kerrville Division. Rows noted with an “X” under the column “Location where Sample needs to be Collected” indicate sample location for collection requirements based off the “Frequency” column. Rows noted with an “X” under the column “Additional Sample Port Install Required to Collect Sample” indicates a sample port installation required for collection.
Table 4 – Kerrville SPS Location
Sample
Sample Location
Sample Type
Location where
Sample needs to be Collected
Additional Sample
Location Port Install Required
Critical Water System
Updates?
Frequen cy of
Testing for each port 1 Sink 1 -
Cold Utility X
2 Sink 1 - Hot Utility X Quarterly 3 Sink 1
Critical Critical X Monthly
4 Sink 2 - Cold
Utility X Quarterly
5 Sink 2 - Hot Utility X Quarterly 6 Sink 2 -
Critical Critical X Monthly
7 AER #1 Utility X X Quarterly 8 AER #2 Utility X X Quarterly 9 Ultrasonic Utility X X Quarterly 10 Washer -
Cold Utility X X Quarterly
11 Washer - Hot
Utility X X Quarterly
12 Washer -
Critical X X Monthly
No of Sample
Sample Location
Sample Type
Location where
Sample needs to be Collected
Additional Sample
Location Port Install Required
Critical Water System
Updates?
Frequen cy of
Testing for each port 13 Test Port
After DI SysteM
14 Sterilizer #1 Steam X Quarterly 15 Sterilizer #2 Steam X Quarterly
3.4 The Contractor shall provide a consolidated monthly report of all sample locations, results, parameters on a single report.
3.5 The Contractor shall provide immediate notification of any positive samples over the bacteria and endotoxin threshold per ST108.
3.6 The Contractor shall provide an annual balance of Emergency / On-call tests for any locations that require re-testing or per direction of VA.
3.7 The Contractor shall ensure Contractor staff adhere to all PPE requirements when testing in PPE required areas.
3.8 The Contractor shall ensure Contractor staff conduct a thorough test-location wipe down with alcohol wipes and utilizes latex or vinyl gloves to avoid accidental contamination of sample.
3.9 The Contractor shall ensure contracted staff personnel conduct flushing and sampling per Annex H, paragraph H.5. of ST-108.
3.10 The Contractor shall enforce a strict chain of custody of sampling so that samples are secured and shipped by one dedicated technician.
3.11 The Contractor shall immediately notify VA of any breach in chain of custody or shipping issues that would render the samples un-usable.
3.12 The Contractor shall coordinate with VA on providing re-tests.
3.13 The Contractor shall verify all existing utility installations and take appropriate action prior to working in the vicinity of utility services (electrical, plumbing, HVAC equipment).
3.14 The Contractor’s policies and procedures shall comply with VA Privacy and Security policy, the Privacy Act and Health Insurance Portability and Accountability Act (HIPAA).
3.15 The Contractor’s personnel shall obtain a short-term identification badge issued by the VA designee.
3.16 The badge shall be worn by the individual and prominently displayed while on VA property.
3.17 No employee of the Contractor shall enter the project site without a valid identification badge issued by the VA.
3.18 To obtain a short-term identification badge, Contractor personnel shall present to the VA designee a valid (non-expired) photo identification issued by a US federal, State, or local government agency.
3.19 The Contractor shall deliver sufficient technical documentation with all data deliverables to permit the VA to use the data.
3.20 The Contractor shall include Certified Water Treatment Specialist for supporting integration, qualification and validation of water treatment equipment and testing.
3.21 The Contractor shall install additional Sampling ports for water sample collections specified under each site location in each table under section 3.2.
3.23 The Contractor shall only follow guidance as provided by the Contracting Officer assigned and coordinate all work with the Contracting Officer’s Representative (COR).
4. CONTRACTOR AVAILABILITY AND RESPONSE. The Contractor shall be available for servicing equipment 24 hours a day/7 day a week. The Contractor shall promptly reply and respond within 24 hours of initial telephone call notification placed for any of the SPS facilities. For equipment that belongs to the VA, the Contractor shall have no obligation to repair or replace parts that fail due to external causes, accidents not attributed to the Contractor, vandalism, natural disaster, power failures; abuse, misuse, or neglect of accessories; usage not in accordance with the product instructions; or servicing or repair not authorized by the Contractor.
5. MAJOR REPAIRS/DISRUPTION. Following any non-routine, major repairs/maintenance work where the distribution loop or key equipment has been disrupted, disconnected/replaced - the Contractor shall be required to thoroughly sanitize any supply lines, and perform RO sanitization service and distribution loop sanitization service (Ozone Storage and Sanitization, Set-up, and oxygen) on the sterile processing system. The Contractor shall perform three (3) consecutive validation tests after any major maintenance or disruptions of services to confirm the bacteria count is following ST108 water quality standards. The Contractor shall perform bacteria tests three (3) consecutive days, day one (1) test followed by two (2) more validation tests for day two (2), day three (3) to ensure the system is ready to use for sterile processing.
6. SAMPLING REQUIREMENTS. The Contractor shall refer to the tables above for sampling requirements required by ST108 testing for utility water, critical water, and steam.
6.1 Three (3) categories of water quality per ST 108. Three (3) categories of water quality in terms of the characteristics that are important for medical device processing and the level of treatment that may be needed.
6.1.1 Utility Water: Water as it comes from the tap that can require further treatment at the facility to achieve water quality measurement values outlined in Table 1. This water is mainly used for flushing, washing, and intermediate rinsing (e.g., rinsing between cleaning and disinfection).
6.1.2 Critical Water: Water that meets the water quality measurement values detailed in Table 1; to achieve these values, the water generally requires extensive treatment by a multi-step process that can include a pretreatment, does include primary treatment (e.g., RO and/or DI), storage, distribution, and can include final treatment to provide a level of assurance that microorganisms and inorganic and organic material are removed from the water. This water is mainly used for the final rinse after high-level disinfection, for the final rinse for critical devices prior to sterilization and feedwater for process steam production.
6.1.3 Steam: vaporized water that is produced by a centralized boiler or a generator/heat exchanger near the sterilizer. When the steam is tested as a condensate, it should meet the specified criteria as defined in Table 5 in ST108.
6.1.4 Utility Water is predominantly used for medical device processing, except for final rinse, where Critical Water is recommended. At the point of production, Utility Water and Critical Water shall meet the requirements as specified in Table 2. Tap water can require treatment to meet these requirements. The bacteria level for Critical Water in Table 2 (< 10 CFU/mL [< 10,000 CFU/L]) is consistent with the Clinical & Laboratory Standards Institute (CLSI) guidelines.
6.2 Water Quality and Equipment Maintenance.
6.2.1 The Contractor shall ensure water quality and equipment maintenance requirements are compliant with the guidelines and parameters per ST108.
6.2.2 The Contractor shall provide for a monitoring and maintenance process to ensure compliance with the defined compliance parameters and associated frequencies as defined in Table 6 in ST108.
6.3 The Contractor shall provide for water quality monitoring frequency as defined in Table 7 in
ST108.
6.4 The Contractor shall provide for water quality monitoring frequency at point-of-water as defined in Table 8 in ST108.
7. SAMPLING PER ST108 GUIDANCE.
7.1 Sample Collection: Critical Water samples, or other types of water when indicated, shall be collected from several locations within the distribution system to provide a representative microbial water quality of the system. In general, samples shall be collected at the beginning and end of the water distribution loop. A point-of-use in the distribution loop is a location where water enters equipment utilized to process medical devices. Where any storage tank is used, water shall be sampled at the end of the purification process and the exit of the storage tank. Samples shall always be collected before disinfection of the water treatment system. If repeat cultures are performed after the system has been chemically disinfected (e.g., with hydrogen peroxide, chlorine, or peracetic acid), the system shall be flushed completely before samples are collected. Before samples are collected, the storage tanks and distribution system shall be drained and flushed until residual disinfectant is no longer detected. For new systems, the water shall be cultured weekly until an established pattern has been determined. For established systems, the water shall be cultured monthly unless a greater frequency is dictated by historical data at a given institution.
7.1.1 Water samples shall be collected directly from outlet taps situated in different parts of the water distribution system. In general, the sample taps shall be opened, and the water shall run for at least 60 seconds (per ST-108) before a sample is aseptically collected in a sterile, endotoxin- free container.
The South Texas VA Health Care Center recommends flushing points-of-use at least 120 seconds prior to drawing samples. The collection container shall not be made of polypropylene, as polypropylene has been shown to inhibit endotoxin detection [78]. At least 100 to 300 mL of water shall be collected. Sample taps shall be treated with a general disinfectant (e.g., alcohol) prior to sampling and shall be completely dried to prevent contamination of the collected sample disinfectant residual from the sample tap. Bleach or other disinfectant solutions shall never be used. Bacterial replication is prevented by holding the sample on ice, or at 4 °C, until it is delivered to the laboratory for testing.
7.1.2 For bacteria test samples, sample analysis shall be initiated as soon as possible after collection to minimize changes in the bacterial population. The recommended maximum elapsed time between collection and analysis is 8 hours (maximum transit time 6-hours, maximum processing time 2-hours). When analysis cannot begin within 8 hours, the Contractor shall maintain sample at a temperature below 4 °C but do not freeze. Maximum elapsed time between collection and analysis shall not exceed 24 hours.
7.2 Water sampling technique. Sampling shall be consistent in procedure and sampling locations to ensure the accurate monitoring of water quality.
7.3 Flushing. Sample points shall be flushed commensurate to the size of the water system and distribution loop. Biofilms can develop throughout the water system, including infrequently used valves or downstream connectors between the distribution loop and equipment. Flushing these areas with a high flow velocity across these surfaces can shear off fragile tops of biofilms possibility growing in these areas. A standardized flush before sampling can limit the microbial contribution from the sampling points. For consistent testing results, the Contractor shall thoroughly flush points of use test locations for at least 120 seconds.
7.4 Sampling containers. The appropriate sampling container shall be used to collect the water sample. The container shall be of the required quality not to introduce contamination into the test sample. For example, samples used in the sampling for bacterial endotoxin shall be of the appropriate quality (e.g., pyrogen-free).
7.5 Sampling technique. Valves/taps/hoses used for sampling shall be of the appropriate design to not contaminate the sample. For example, sampling locations do not provide a stagnant water environment when not in use and is accessible to the distribution loop disinfection process. Prior to sampling the sampling surfaces (e.g., valves, hoses) shall be disinfected both externally and internally to reduce microbial contamination. Aseptic technique shall be used for water collection.
7.6 Results exceeding specifications. When detecting microbial quality levels exceeding specification, the Contractor shall perform a repetition of the disinfection and sampling at the location to confirm the results. Upon confirmation of the exceedance, the Contractor shall take immediate action as required to reduce the microbial contamination.
7.6.1 The distribution loop shall be disinfected using methods described in ST108, Annex E, to ensure the microbial contamination is not being introduced through the distribution system.
Automated instrument re-processors (e.g., washer–disinfectors, washer–decontaminators, AERs) shall be flushed with 1,000 ppm of a chlorine-releasing agent after the first instance of persistent unacceptable microbial levels is detected. Other agents that could be considered for flushing include chlorine dioxide, peracetic acid, hydrogen peroxide, and super oxidized water. Before the unit is flushed with any of these agents, the Contractor shall confirm with the re-processor manufacturer that the components of the machine are compatible with the disinfectant to be used in its intended concentration. The levels shall be monitored weekly by repeat testing until two (2) successive counts show that baseline levels have been achieved.
8. HOURS OF OPERATION. Normal duty hours are 8:00 a.m. through 4:30 p.m., Monday through Friday, not including federal holidays. The contractor can also schedule to perform maintenance work on weekend at Audie Murphy and Kerrville SPS site.
The Government observes the listed days as holidays. If the holiday falls on a Saturday, the Friday before is the holiday. If the holiday falls on a Sunday, the Monday after is the holiday:
New Year's Day January 1st Martin Luther King's Birthday Third Monday in January Washington’s Birthday Third Monday in February Memorial Day Last Monday in May Juneteenth June 19th Independence Day July 4th Labor Day First Monday in September Columbus Day Second Monday in October Veterans Day November 11th Thanksgiving Day Fourth Thursday in November Christmas December 25th
In addition to the days designated as holidays, the Government observes the following days:
• Any other day designated by Federal Statute
• Any other day designated by Executive Order
• Any other day designated by the President’s Proclamation
The observance of such days by Contractor personnel shall not otherwise be a reason for an additional period of performance, or entitlement of compensation. In the event the Contractor’s personnel work during the holiday, they may be reimbursed by the Contractor, however, no form of holiday or other premium compensation will be reimbursed either as a direct or indirect cost, other than their normal compensation for the time worked.
9. CONTRACTING OFFICERS REPRESENTATIVE. The Contracting Officer will delegate a Contracting Officer’s Representative upon contract award.
10. SAFETY PLAN. The Contractor shall be required to provide a safety plan for the work to be performed under this contract before starting physical work. The plan shall include an Activity Hazard Analysis (AHA) focused on the essential areas of work where risks must be addressed. The Contractor shall provide Personal Protective Equipment (PPE) for the Contractor’s employees and ensure all Contractor employees to include sub-contractors have and properly use the PPE. Protective lab coveralls, head covers (Bouffant caps), shoe covers, procedure masks and gloves are available from the VA, at each of the site locations; Contractors can use these items as supplied on-site by the VA for entering the Decontamination areas of the Sterile Processing Service. These items shall always be worn by all Contractor, sub-contractor personnel at each site location. The Contractor shall follow all OSHA (Office of Safety and Health Administration) and VHA Safety Guidelines and ensure their contracted personnel and all sub-contractors adhere to OSHA safety guidelines. The contractor shall be responsible to follow OSHA guidelines
11. TUBERCULOSIS (TB) SCREENING.
11.1 The Contractor shall provide written certification that all Contractor employees assigned to the worksite have had a pre-placement negative tuberculin screening within 90 days prior to assignment.
11.2 The Contractors shall be required to show documentation of negative TB screening for any additional workers who are added after the 90-day requirement before Contractor employees are allowed to work on the work site. NOTE: This can be the Center for Disease Control (CDC) and Prevention and two-step skin testing or a Food and Drug Administration (FDA)-approved blood test.
11.3 Contractor employees manifesting positive screening reactions to the tuberculin shall be examined according to current CDC guidelines prior to working on VHA property. If a Contractors employee is found without evidence of active (infectious) pulmonary TB, a statement documenting examination by a physician shall be on file with the Contractor noting that the employee with a positive tuberculin screening test is without evidence of active (infectious) pulmonary TB. If the employee is found with evidence of active (infectious) pulmonary TB, the Contractor employee shall be required to obtain treatment with a subsequent statement to the fact on file with the employer before being allowed to return to work on VHA property.
(END STATEMENT OF WORK)
(END OF SECTION B)
SECTION C - CONTRACT CLAUSES
C.1 ADDENDUM to FAR 52.212-4 CONTRACT TERMS AND CONDITIONS –
COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES
FAR 52.252-2 CLAUSES INCORPORATED BY REFERENCE (FEB 1998)
This contract incorporates one or more clauses by reference, with the same force and effect as if they were given in full text. Upon request, the Contracting Officer will make their full text available. Also, the full text of a clause may be accessed electronically at this/these address(es):
https://www.acquisition.gov/far-overhaul https://www.va.gov/oal/library/vaar/
FAR 52.203-17 CONTRACTOR EMPLOYEE WHISTLEBLOWER RIGHTS (NOV 2023)
FAR 52.203-19 PROHIBITION ON REQUIRING CERTAIN INTERNAL (JAN 2017)
CONFIDENTIALITY AGREEMENTS OR STATEMENTS
FAR 52.204-9
PERSONAL IDENTITY VERIFICATION OF
CONTRACTOR PERSONNEL (JAN 2011)
FAR 52.204-13 SYSTEM FOR AWARD MANAGEMENT - MAINTENANCE (OCT 2018)
FAR 52.226-8 ENCOURAGING CONTRACTOR POLICIES TO BAN TEXT (MAY 2024)
MESSAGING WHILE DRIVING
FAR 52.222-50 COMBATING TRAFFICKING IN PERSONS (DEVIATION) (NOV 2025)
FAR 52.232-40 PROVIDING ACCELERATED PAYMENTS TO SMALL (MAR 2023)
BUSINESS SUBCONTRACTORS
FAR 52.233-3 PROTEST AFTER AWARD (DEVIATION) (NOV 2025)
FAR 52.233-4 APPLICABLE LAW FOR BREACH OF CONTRACT CLAIM (NOV 2025)
(DEVIATION)
VAAR 852.203-70 COMMERCIAL ADVERTISING (MAY 2018)
VAAR 852.222-71 COMPLIANCE WITH EXECUTIVE ORDER 13899 (NOV 2025)
(DEVIATION)
VAAR 852.242-71 ADMINISTRATIVE CONTRACTING OFFICER (OCT 2020)
(End of clause)
FAR 52.217-8 OPTION TO EXTEND SERVICES (NOV 1999)
The Government may require continued performance of any services within the limits and at the rates specified in the contract. These rates may be adjusted only as a result of revisions to prevailing labor rates provided by the Secretary of Labor. The option provision may be exercised more than once, but the total extension of performance hereunder shall not exceed 6 months.
The Contracting Officer may exercise the option by written notice to the Contractor within 15 days.
(End of clause)
FAR 52.222-42 STATEMENT OF EQUIVALENT RATES FOR FEDERAL HIRES (MAY
2014) In compliance with the Service Contract Labor Standards statute and the regulations of the Secretary of Labor ( 29 CFR Part 4), this clause identifies the classes of service employees expected to be employed under the contract and states the wages and fringe benefits payable to each if they were employed by the https://www.acquisition.gov/far-overhaul https://www.va.gov/oal/library/vaar/ contracting agency subject to the provisions of 5 U.S.C.5341 or 5332. This Statement is for Information Only: It is not a Wage Determination
Employee Class Monetary Wage-Fringe Benefits See Bexar County WD in Section D See Kerr County WD in Section D
(End of clause)
FAR 52.252-6 AUTHORIZED DEVIATIONS IN CLAUSES (NOV 2020)
(a) The use in this solicitation or contract of any Federal Acquisition Regulation (48 CFR Chapter 1) clause with an authorized deviation is indicated by the addition of "(DEVIATION)" after the date of the clause.
(b) The use in this solicitation or contract of any VA Acquisition Regulation (VAAR) (48 CFR Chapter 8) clause with an authorized deviation is indicated by the addition of "(DEVIATION)" after the name of the regulation.
(End of clause)
852.219-73 VA NOTICE OF TOTAL SET-ASIDE FOR VERIFIED SERVICE-
DISABLED VETERAN-OWNED SMALL BUSINESSES (NOV 2022)
(a) Definition. for the Department of Veterans Affairs, “Service-disabled Veteran-owned small business concern or SDVOSB”:
(1) Means a small business concern -
(i) Not less than 51 percent of which is owned by one or more service-disabled Veterans or, in the case of any publicly owned business, not less than 51 percent of the stock of which is owned by one or more service-disabled Veterans or eligible surviving spouses (see VAAR802.101, Surviving Spouse definition);
(ii) The management and daily business operations of which are controlled by one or more service-disabled Veterans (or eligible surviving spouses) or, in the case of a service-disabled Veteran with permanent and severe disability, the spouse or permanent caregiver of such Veteran;
(iii) The business meets Federal small business size standards for the applicable North American Industry Classification System (NAICS) code identified in the solicitation document;
(iv) The business has been verified for ownership and control pursuant to 38 CFR part 74 and is listed in VA's Vendor Information Pages (VIP) database at https://www.vetbiz.va.gov/vip/; and
(v) The business will comply with VAAR subpart 819.70 and Small Business Administration (SBA) regulations regarding small business size and government contracting programs at 13 CFR parts 121 and 125, provided that any reference therein to a service-disabled veteran-owned small business concern or SDVO SBC, is to be construed to apply to a VA verified and VIP-listed SDVOSB, unless otherwise stated in this clause.
(2) The term “Service-disabled Veteran” means a Veteran, as defined in 38 U.S.C. 101(2), with a disability that is service-connected, as defined in 38 U.S.C. 101(16).
(3) The term “small business concern” has the meaning given that term under section 3 of the Small Business Act (15 U.S.C. 632).
(4) The term “small business concern owned and controlled by Veterans with service-connected disabilities” has the meaning given the term “small business concern owned and controlled by service-disabled veterans” under section 3(q)(2) of the Small Business Act (15 U.S.C.
632(q)(2)), except that for a VA contract the firm must be listed in the VIP database (see paragraph (a)(1)(iv) of this clause).
(b) General.
(1) Offers are solicited only from VIP-listed SDVOSBs. Offers received from entities that are not VIP-listed SDVOSBs at the time of offer shall not be considered.
(2) Any award resulting from this solicitation shall be made to a VIP-listed SDVOSB who is eligible at the time of submission of offer(s) and at the time of award.
(3) The requirements in this clause apply to any contract, order or subcontract where the firm receives a benefit or preference from its designation as an SDVOSB, including set-asides, sole source awards, and evaluation preferences.
(c) Representation. Pursuant to 38 U.S.C. 8127(e), only VIP-listed SDVOSBs are considered eligible to receive award of a resulting contract. By submitting an offer, the prospective contractor represents that it is an eligible SDVOSB as defined in this clause, 38 CFR part 74, and VAAR subpart 819.70.
(d) Agreement. When awarded a contract action, including orders under multiple-award contracts, an SDVOSB…
This is the start of the file's text. The full file is on GovTribe.