OEI VABM CHILLER REPLACEMENT REV MECH ELEC 120722.pdf
PDF 6 MB Posted
- Solicitation number
- 36C25723B0009
About this file
This is a solicitation for replacing chillers at the Energy Center in Bonham, Texas under project number 549A4-20-700. The solicitation is for upgrading the chillers and was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17. Offerors should propose solutions for replacing the existing chillers to meet the requirements outlined in the project specifications. Pricing and response dates are not provided in the solicitation details.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25723B0009 0008.docx | DOCX document | |
| 36C25723B0009 0007.docx | DOCX document | |
| 36C25723B0009 0006.docx | DOCX document | |
| 36C25723B0009 0005.docx | DOCX document | |
| 36C25723B0009 0004.docx | DOCX document | |
| Figure 2 - Chilled Water Plant Flow Diagram.pdf | ||
| 36C25723B0009 0003.docx | DOCX document | |
| 36C25723B0009 0002.docx | DOCX document | |
| S04 PreBid Sign in Sheet.pdf | ||
| 36C25723B0009 0001.docx | DOCX document | |
| 36C25723B0009_1.docx | DOCX document | |
| Appendix A 100 percent Drawings Sealed.pdf | ||
| Appendix B 100 percent Project Specifications Sealed.pdf |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
12/07/2022
SCALE: NONE1 CHILLED WATER FLOW DIAGRAM - DEMO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
REPLACE CHILLERS AT
ENERGY CENTER
BONHAM, TEXAS
Project Director
Revisions:
549-20-700
Approved: Project Director2340 E. TRIN ITY MILLS, STE. 220
CARROLLTON, TX 75006
972-233-2288
O'Brien Engineering, Inc.
Mr. Byron Rowland, COR Sam Rayburn Memorial Veterans Center Bonham, TX 75418 www.obrieneng.com
TEXAS ENGINEERING FIRM F-3758
ISSUE FOR BIDCONSULTANT
Revisions: Date:
FULLY SPRINKLERED
04.27.2021
1. RESPONSE TO PRE-BID RFI QUESTIONS 12/07/22 M-602
MECHANICAL DIAGRAMS
LRL LRL
SCALE: NONE1 CHILLED WATER FLOW DIAGRAM - NEW
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
REPLACE CHILLERS AT
ENERGY CENTER
BONHAM, TEXAS
Project Director
Revisions:
549-20-700
Approved: Project Director2340 E. TRIN ITY MILLS, STE. 220
CARROLLTON, TX 75006
972-233-2288
O'Brien Engineering, Inc.
Mr. Byron Rowland, COR Sam Rayburn Memorial Veterans Center Bonham, TX 75418 www.obrieneng.com
TEXAS ENGINEERING FIRM F-3758
ISSUE FOR BIDCONSULTANT
Revisions: Date:
FULLY SPRINKLERED
04.27.2021
1. RESPONSE TO PRE-BID RFI QUESTIONS 12/07/22 M-603
MECHANICAL DIAGRAMS
LRL LRL
ABBREVIATIONS
1PH SINGLE PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC FREQUENCY
CONTROL, OR AVAILABLE FAULT CURRENT
AFCI ARC-FAULT CURRENT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFIB ARC FAULT CIRCUIT INTERRUPTER CIRCUIT BREAKER.
AF/GF ARC FAULT AND GROUND FAULT CIRCUIT INTERRUPTER
Ah AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BRK RBREAKER
BYP BYPASS
C CONDUIT
CAB CABINET (MOUNTED)
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTRACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FINISHED
CF/CI CONTRACTOR FINISHED/CONTRACTOR INSTALLED
CFE CONTRACTOR FINISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
OR C/B
CLF CURRENT LIMITING FUSE
CLG CEILING
COAX COAX CABLE
COMM COMMUNICATION
COMPT COMPARTMENT
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CUR CURRENT
dB DECIBEL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELCIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR PNL DISTRIBUTION PANEL
DMR SW DIMMER SWITCH
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
EPRF EXPLOSION PROOF
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST OR (E) EXISTING
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FIXT FIXTURE
FLA FULL LOAD AMPS
FLUOR FLUORESCENT
FP FIRE PROTECTION
FSD FIRE SMOKE DAMPER
FT FEET OR FOOT
FU SW FUSED SWITCH
FVNR FULL VOTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G ELECTRICAL GROUND
GEN GENERATOR
GFI GROUND FAULT INTERRUPTER
GFIB GROUND FAULT CIRCUIT INTERRUPTER VIA CIRCUIT
BREAKER.
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IESNA ILLUMINATION ENGINEERING SOCIETY OF
NORTH AMERICA
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
kV KILOVOLT kVA KILOVOLT AMPERE kVAh KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWh KILOWATT HOUR kWhM KILOWATT HOUR METER
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MD MOTORIZED DAMPER
MECH MECHANICAL
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLA MAIN LUGS ONLY
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NEUT OR N NEUTRAL
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
P POLE
PB PULL BOX
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RCP REFLECTED CEILING PLAN
RE RELOCATED EXISTING
REC RECESSED
RECPT RECEPTACLE
RM ROOM
RMS ROOT MEAN SQUARE
REQD REQUIRED
SCC SHORT CIRCUIT CAPACITY
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TEL TELEPHONE
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
USB RECEPTACLE w/INTEGRATED UNIVERSAL SERIAL BUS
PORT
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
W WATT
WH WATER HEATER
WP WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
ELECTRICAL SYMBOLS
20 AMP DUPLEX RECEPTACLE (NEMA 5-20R) MOUNTED AT 18" AFF TO CENTER LINE OF OUTLET UNLESS NOTED OTHERWISE.
20 AMP QUADRUPLEX RECEPTACLE (NEMA 5-20R) MOUNTED AT 18" AFF TO CENTER LINE OF OUTLET UNLESS NOTED
OTHERWISE.
20 AMP DUPLEX RECEPTACLE (NEMA 5-20R) MOUNTED ABOVE COUNTER. REFER TO ARCHITECTURAL ELEVATIONS FOR
EXACT LOCATION AND MOUNTING HEIGHT.
20 AMP DUPLEX RECEPTACLE (NEMA 5-20R), RECESSED FLOOR MOUNTED. PROVIDE SQUARE BRUSHED NICKEL FINISH COVER PLATE WITH RECESS DEVICE, FLIP TOP COVER WITH NON-RECESS DEVICE WILL NOT BE ACCEPTED. FLOOR BOX
SHALL BE LISTED FOR PROPOSED LOCATION AS REQUIRED.
20 AMP DUPLEX RECEPTACLE (NEMA 5-20R) AND COMMUNICATIONS DUAL SERVICE FLOOR BOX, RECESSED FLOOR MOUNTED. PROVIDE 1" CONDUIT SLEEVE WITH PULL STRING, STUB INTO ACCESSIBLE CEILING SPACE. PROVIDE SQUARE BRUSHED NICKEL FINISH COVER PLATE WITH RECESS DEVICES, FLIP TOP COVER WITH NON-RECESS DEVICES WILL NOT BE
ACCEPTED. FLOOR BOX SHALL BE LISTED FOR PROPOSED LOCATION AS REQUIRED.
20 AMP QUADRUPLEX RECEPTACLE (NEMA 5-20R) AND COMMUNICATIONS DUAL SERVICE FLOOR BOX, RECESSED FLOOR MOUNTED. PROVIDE 1" CONDUIT SLEEVE WITH PULL STRING, STUB INTO ACCESSIBLE CEILING SPACE. PROVIDE SQUARE BRUSHED NICKEL FINISH COVER PLATE WITH RECESS DEVICES, FLIP TOP COVER WITH NON-RECESS DEVICES WILL NOT BE
ACCEPTED. FLOOR BOX SHALL BE LISTED FOR PROPOSED LOCATION AS REQUIRED.
SPECIAL PURPOSE POWER DEVICE, COORDINATE EXACT NEMA NUMBER DEVICE WITH EQUIPMENT PLUG UNLESS NOTED
OTHERWISE.
COMMUNICATIONS OUTLET. PROVIDE 1" CONDUIT SLEEVE WITH PULL STRING, STUB INTO ACCESSIBLE CEILING SPACE.
MOUNT AT 18" A.F.F. TO CENTER OF OUTLET UNLESS NOTED OTHERWISE.
RECEPTACLE AND COMMUNICATIONS OUTLET. PROVIDE (2) 1" CONDUIT SLEEVES WITH CABLING, STUB INTO ACCESSIBLE CEILING SPACE. COORDINATE MOUNTING HEIGHT OF BOX WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH IN. PROVIDE FOUR GANG, RECESSED MOUNTED STEEL BOX WITH VOLTAGE DIVIDER AND OPTIONAL COVER PLATE.
ARLINGTON TVBS613 OR EQUIVALENT.
TELEVISION OUTLET. PROVIDE 1" CONDUIT SLEEVE WITH PULL STRING, STUB INTO ACCESSIBLE CEILING SPACE. MOUNT AT
18" A.F.F. TO CENTER LINE OF OUTLET UNLESS NOTED OTHERWISE.TV
JUNCTION BOXJ
PROPOSED ROUTING OF LOW VOLTAGE WIRING FOR DIAGRAMMATIC PURPOSES ONLY.
SINGLE/DOUBE POLE LINE VOLTAGE MOTION SENSOR, PASSIVE (PIR)
SENSORSWITCH "CMR" SERIES. PROVIDE DOUBLE POLE WHEN (2) CONTROLLED CIRCUITS.
LINE VOLTAGE, MOTION/SOUND SENSOR, PASSIVE (PIR) AND ULTRASONIC (US) DUAL TECHNOLOGY. SENSORSWITCH "CMR-
PDT" SERIES.
SELF CONTAINED, PLENUM RATED, DUAL CIRCUIT POWER PACK WITH 20 AMP RATING. SENSORSWITCH "PP" SERIES.
ELECTRICAL PANELBOARD, SURFACE MOUNTED
FUSIBLE DISCONNECT SWITCH A = POLES, B= FRAME SIZE, C= FUSE RATING
GROUNDING ELECTRODE AND CONDUCTOR SYSTEM
TRANSFORMER
TELEPHONE WOOD BACKBOARD
THERMOSTAT LOCATION. REFER TO MECHANICAL DRAWINGS FOR MOUNTING HEIGHT AND SPECIFICATIONS. PROVIDE JUNCTION BOX IN WALL BEHIND THERMOSTAT WITH 1" CONDUIT SLEEVE WITH PULL STRING, STUB INTO ACCESSIBLE CEILING SPACE. CONDUIT AND BOXES SHALL BE CONCEALED / RECESSED IN CONCRETE BLOCK (CMU) WALLS.
GARAGE DOOR CONTROL SWITCH, PROVIDE CONNECTIONS ACCORDING TO MANUFACTURER RECOMMENDATIONS
GARAGE DOOR MOTION SENSOR, PROVIDE CONNECTIONS ACCORDING TO MANUFACTURER RECOMMENDATIONS
USED FOR CLARITY PURPOSES AS FOLLOWS:
TO CONNECT GROUPS OF MULTIPLE DEVICES/LIGHT FIXTURES IN DIFFERENT LOCATIONS TOGETHER ON THE SAME
BRANCH CIRCUIT AS INDICATED.
TO INDICATE BRANCH CIRCUIT USED IN DIFFERENT LOCATIONS, FOLLOW KEYNOTES AS INDICATED.
GENERAL FLOOR BOX NOTE:
REFER TO ARCHITECTURAL PLANS FOR DIMENSIONS AND FINAL LOCATIONS PRIOR TO ROUGH IN.
M
PP
T
20 AMP QUADRUPLEX RECEPTACLE (NEMA 5-20R), RECESSED FLOOR MOUNTED. PROVIDE SQUARE BRUSHED NICKEL FINISH COVER PLATE WITH RECESS DEVICES, FLIP TOP COVER WITH NON-RECESS DEVICES WILL NOT BE ACCEPTED. FLOOR BOX
SHALL BE LISTED FOR PROPOSED LOCATION AS REQUIRED.
20 AMP DUPLEX RECEPTACLE (NEMA 5-20R), CEILING MOUNTED.
COMMUNICATIONS OUTLET, CEILING MOUNTED.
TV TELEVISION OUTLET, CEILING MOUNTED.
ELECTRICAL PANELBOARD, RECESSED MOUNTED
NEMA
MS
B C A
T1
TV
20 AMP QUADRUPLEX RECEPTACLE (NEMA 5-20R), CEILING MOUNTED.
MULTI OUTLET HARD WIRED PLUG STRIP WITH USB CHARGING, 9" DEVICE SPACING, STEEL, ALUMINUM FINISH. MOUNT HIGH UP, UNDER COUNTER TOP UNLESS NOTED OTHERWISE. WIREMOLD 2000 SERIES OR EQUIVALENT WITH ALTERNATING
DEVICES. LENGTH PER PLAN.
LINE VOLTAGE MOTION SENSOR, PASSIVE (PIR), WET LOCATION RATED
ATLAS LIGHTING PRODUCTS "MS360WL" SERIESWP
M
LOW VOLTAGE MOTION SENSOR, PASSIVE (PIR)
SENSORSWITCH "CM" SERIES.
LV
MS
LOW VOLTAGE MOTION/SOUND SENSOR, PASSIVE (PIR) AND ULTRASONIC (US) DUAL TECHNOLOGY. SENSORSWITCH "CM-
PDT" SERIES
LV
M
EMERGENCY EXIT SIGN, WALL MOUNTED. EXIT SIGN SHALL BE MOUNTED WITHIN 6'-8" ABOVE TOP OF EGRESS DOOR FRAME.
EMERGENCY EXIT SIGN. FOR CEILING(S) WITH A HEIGHT LESS THAN OR EQUAL TO 6'-8" ABOVE TOP OF EGRESS DOOR FRAME, EXIT SIGN SHALL BE CEILING SURFACE MOUNTED. FOR CEILING(S) WITH A HEIGHT GREATER THAN 6'-8" ABOVE TOP OF EGRESS DOOR FRAME, EXIT SIGN SHALL BE CEILING SUSPENDED AT OR ABOVE THE LINE OF SIGHT.
GENERAL NOTES
1. GENERAL REQUIREMENTS
A. GENERAL
1. DESCRIPTION: FURNISH AND INSTALL ELECTRICAL SYSTEMS, MATERIALS, EQUIPMENT, AND ACCESSORIES IN ACCORDANCE WITH THE SPECIFICATIONS AND DRAWINGS.
CAPACITIES AND RATINGS OF MOTORS, TRANSFORMERS, CONDUCTORS AND CABLE, SWITCHBOARDS, SWITCHGEAR, PANELBOARDS, MOTOR CONTROL CENTERS, GENERATORS, AUTOMATIC TRANSFER SWITCHES, AND OTHER ITEMS AND ARRANGEMENTS FOR THE SPECIFIED ITEMS ARE SHOWN ON THE DRAWINGS.
2. ELECTRICAL SERVICE ENTRANCE EQUIPMENT AND ARRANGEMENTS FOR TEMPORARY AND PERMANENT CONNECTIONS TO THE ELECTRIC UTILITY COMPANY'S SYSTEM SHALL CONFORM TO THE ELECTRIC UTILITY COMPANY'S REQUIREMENTS. COORDINATE FUSES, CIRCUIT BREAKERS AND RELAYS WITH THE ELECTRIC UTILITY COMPANY'S SYSTEM, AND OBTAIN ELECTRIC UTILITY COMPANY APPROVAL FOR SIZES AND SETTINGS OF THESE DEVICES.
3. CONDUCTOR AMPACITIES SPECIFIED OR SHOWN ON THE DRAWINGS ARE BASED ON COPPER CONDUCTORS, WITH THE CONDUIT AND RACEWAYS SIZED PER NEC.
ALUMINUM CONDUCTORS ARE PROHIBITED.
4. THE LATEST INTERNATIONAL BUILDING CODE (IBC), UNDERWRITERS LABORATORIES, INC. (UL), INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE), AND NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) CODES AND STANDARDS ARE THE MINIMUM REQUIREMENTS FOR MATERIALS AND INSTALLATION.
5. THE DRAWINGS AND SPECIFICATIONS SHALL GOVERN IN THOSE INSTANCES WHERE REQUIREMENTS ARE GREATER THAN THOSE STATED IN THE ABOVE CODES AND
STANDARDS.
6. TEST STANDARDS: ALL MATERIALS AND EQUIPMENT SHALL BE LISTED, LABELED, OR CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) TO MEET UNDERWRITERS LABORATORIES, INC. (UL), STANDARDS WHERE TEST STANDARDS HAVE BEEN ESTABLISHED. MATERIALS AND EQUIPMENT WHICH ARE NOT COVERED BY UL STANDARDS WILL BE ACCEPTED, PROVIDING THAT MATERIALS AND EQUIPMENT ARE LISTED, LABELED, CERTIFIED OR OTHERWISE DETERMINED TO MEET THE SAFETY REQUIREMENTS OF A NRTL. MATERIALS AND EQUIPMENT WHICH NO NRTL ACCEPTS, CERTIFIES, LISTS, LABELS, OR DETERMINES TO BE SAFE, WILL BE CONSIDERED IF INSPECTED OR TESTED IN ACCORDANCE WITH NATIONAL INDUSTRIAL STANDARDS, SUCH AS ANSI, NEMA, AND NETA. EVIDENCE OF COMPLIANCE SHALL INCLUDE
CERTIFIED TEST REPORTS AND DEFINITIVE SHOP DRAWINGS.
7. MATERIALS AND EQUIPMENT PROTECTION: MATERIALS AND EQUIPMENT SHALL BE PROTECTED DURING SHIPMENT AND STORAGE AGAINST PHYSICAL DAMAGE, VERMIN, DIRT, CORROSIVE SUBSTANCES, FUMES, MOISTURE, COLD AND RAIN.
8. WORK PERFORMANCE
a. ALL ELECTRICAL WORK SHALL COMPLY WITH REQUIREMENTS OF THE LATEST NFPA 70 (NEC), NFPA 70B, NFPA 70E, NFPA 99, NFPA 110, OSHA PART 1910 SUBPART J -
GENERAL ENVIRONMENTAL CONTROLS, OSHA PART 1910 SUBPART K - MEDICAL AND FIRST AID, AND OSHA PART 1910 SUBPART S - ELECTRICAL, IN ADDITION TO OTHER
REFERENCES REQUIRED BY CONTRACT.
b. JOB SITE SAFETY AND WORKER SAFETY IS THE RESPONSIBILITY OF THE CONTRACTOR.
c. FOR WORK THAT AFFECTS EXISTING ELECTRICAL SYSTEMS, ARRANGE, PHASE AND PERFORM WORK TO ASSURE MINIMAL INTERFERENCE WITH NORMAL FUNCTIONING
OF THE FACILITY. REFER TO ARTICLE OPERATIONS AND STORAGE AREAS UNDER SECTION GENERAL REQUIREMENTS.
d. NEW WORK SHALL BE INSTALLED AND CONNECTED TO EXISTING WORK NEATLY, SAFELY AND PROFESSIONALLY. DISTURBED OR DAMAGED WORK SHALL BE REPLACED
OR REPAIRED TO ITS PRIOR CONDITIONS, AS REQUIRED BY SECTION GENERAL REQUIREMENTS.
e. COORDINATE LOCATION OF EQUIPMENT AND CONDUIT WITH OTHER TRADES TO MINIMIZE INTERFERENCE.
9. EQUIPMENT INSTALLATION AND REQUIREMENTS:
a. EQUIPMENT LOCATION SHALL BE AS CLOSE AS PRACTICAL TO LOCATIONS SHOWN ON THE DRAWINGS.
b. WORKING CLEARANCES SHALL NOT BE LESS THAN SPECIFIED IN THE NEC.
c. ELECTRICAL SERVICE ENTRANCE EQUIPMENT AND ARRANGEMENTS FOR TEMPORARY AND PERMANENT CONNECTIONS TO THE ELECTRIC UTILITY COMPANY'S SYSTEM
SHALL CONFORM TO THE ELECTRIC UTILITY COMPANY'S REQUIREMENTS. COORDINATE FUSES, CIRCUIT BREAKERS AND RELAYS WITH THE ELECTRIC UTILITY COMPANY'S SYSTEM, AND OBTAIN ELECTRIC UTILITY COMPANY APPROVAL FOR SIZES AND SETTINGS OF THESE DEVICES.
10. EQUIPMENT ID
a. IN ADDITION TO THE REQUIREMENTS OF THE NEC, INSTALL AN IDENTIFICATION SIGN WHICH CLEARLY INDICATES INFORMATION REQUIRED FOR USE AND MAINTENANCE
OF ITEMS SUCH AS SWITCHBOARDS AND SWITCHGEAR, PANELBOARDS, CABINETS, MOTOR CONTROLLERS, FUSED AND NON-FUSED SAFETY SWITCHES, GENERATORS, AUTOMATIC TRANSFER SWITCHES, SEPARATELY ENCLOSED CIRCUIT BREAKERS, INDIVIDUAL BREAKERS AND CONTROLLERS IN SWITCHBOARDS, SWITCHGEAR AND
MOTOR CONTROL ASSEMBLIES, CONTROL DEVICES AND OTHER SIGNIFICANT EQUIPMENT.
b. INSTALL ADHESIVE ARC FLASH WARNING LABELS ON ALL EQUIPMENT AS REQUIRED BY THE LATEST NFPA 70E. LABEL SHALL SHOW SPECIFIC AND CORRECT
INFORMATION FOR SPECIFIC EQUIPMENT BASED ON ITS ARC FLASH CALCULATIONS.
B. SUBMITTALS
1. SUBMIT SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES IN APPROPRIATE SUBMITTAL PACKAGES.
2. APPROVAL SHALL BE OBTAINED FOR ALL MATERIALS AND EQUIPMENT BEFORE DELIVERY TO THE JOB SITE. DELIVERY, STORAGE OR INSTALLATION OF MATERIALS AND
EQUIPMENT WHICH HAS NOT HAD PRIOR APPROVAL WILL NOT BE PERMITTED.
3. ALL SUBMITTALS SHALL INCLUDE SIX COPIES OF ADEQUATE DESCRIPTIVE LITERATURE, CATALOG CUTS, SHOP DRAWINGS, TEST REPORTS, CERTIFICATIONS, SAMPLES, AND OTHER DATA NECESSARY FOR THE TO ASCERTAIN THAT THE PROPOSED MATERIALS AND EQUIPMENT COMPLY WITH DRAWING AND SPECIFICATION REQUIREMENTS.
CATALOG CUTS SUBMITTED FOR APPROVAL SHALL BE LEGIBLE AND CLEARLY IDENTIFY SPECIFIC MATERIALS AND EQUIPMENT BEING SUBMITTED.
4. SUBMITTALS FOR INDIVIDUAL SYSTEMS AND EQUIPMENT ASSEMBLIES WHICH CONSIST OF MORE THAN ONE ITEM OR COMPONENT SHALL BE MADE FOR THE SYSTEM OR
ASSEMBLY AS A WHOLE. PARTIAL SUBMITTALS WILL NOT BE CONSIDERED FOR APPROVAL.
5. SUBMIT AS REQUIRED FOR SYSTEMS AND EQUIPMENT SPECIFIED IN THE TECHNICAL SECTIONS. FURNISH IN HARDCOVER BINDERS OR AN APPROVED EQUIVALENT.
6. APPROVALS WILL BE BASED ON COMPLETE SUBMISSION OF SHOP DRAWINGS, MANUALS, TEST REPORTS, CERTIFICATIONS, AND SAMPLES AS APPLICABLE.
7. WARRANTY
a. ALL WORK PERFORMED AND ALL EQUIPMENT AND MATERIAL FURNISHED UNDER THIS DIVISION SHALL BE FREE FROM DEFECTS AND SHALL REMAIN SO FOR A PERIOD
OF ONE YEAR FROM THE DATE OF ACCEPTANCE OF THE ENTIRE INSTALLATION.
2. LOW VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
A. GENERAL
1. DESCRIPTION: FURNISHING, INSTALLATION, CONNECTION, AND TESTING OF THE ELECTRICAL CONDUCTORS AND CABLES FOR USE IN ELECTRICAL SYSTEMS RATED 600 V
AND BELOW, INDICATED AS CABLE(S), CONDUCTOR(S), WIRE, OR WIRING IN THIS SECTION.
2. SUBMITTALS
a. SHOP DRAWINGS: SUBMIT SUFFICIENT INFORMATION TO DEMONSTRATE COMPLIANCE WITH DRAWINGS AND SPECIFICATIONS.
b. SHOP DRAWINGS: ELECTRICAL RATINGS AND INSULATION TYPE FOR EACH CONDUCTOR AND CABLE.
c. SUBMIT THE FOLLOWING DATA FOR APPROVAL: ELECTRICAL RATINGS AND INSULATION TYPE FOR EACH CONDUCTOR AND CABLE.
d. SUBMIT THE FOLLOWING DATA FOR APPROVAL: SPLICING MATERIALS AND PULLING LUBRICANT.
B. PRODUCTS
1. CONDUCTORS AND CABLES
a. CONDUCTORS AND CABLES SHALL BE IN ACCORDANCE WITH ASTM, NEMA, NFPA, UL, AS SPECIFIED, AND AS SHOWN ON THE DRAWINGS.
b. ALL CONDUCTORS SHALL BE COPPER.
c. SINGLE CONDUCTOR AND CABLE:
• NO. 12 AWG: MINIMUM SIZE, EXCEPT WHERE SMALLER SIZES ARE SPECIFIED HEREIN OR SHOWN ON THE DRAWINGS.
• NO. 8 AWG AND LARGER: STRANDED.
• NO. 10 AWG AND SMALLER: SOLID; EXCEPT SHALL BE STRANDED FOR FINAL CONNECTION TO MOTORS, TRANSFORMERS, AND VIBRATING EQUIPMENT.
• INSULATION: THHN-THWN AND XHHW-2. XHHW-2 SHALL BE USED FOR ISOLATED POWER SYSTEMS.
d. COLOR CODE:
• NO. 10 AWG AND SMALLER: SOLID COLOR INSULATION OR SOLID COLOR COATING.
• NO. 8 AWG AND LARGER: COLOR-CODED USING ONE OF THE FOLLOWING METHODS:
• SOLID COLOR INSULATION OR SOLID COLOR COATING.
• STRIPES, BANDS, OR HASH MARKS OF COLOR SPECIFIED.
• COLOR USING 19 MM (0.75 INCHES) WIDE TAPE.
e. FOR MODIFICATIONS AND ADDITIONS TO EXISTING WIRING SYSTEMS, COLOR CODING SHALL CONFORM TO THE EXISTING WIRING SYSTEM.
f. LIGHTING CIRCUIT "SWITCH LEGS", AND 3-WAY AND 4-WAY SWITCH "TRAVELING WIRES," SHALL HAVE COLOR CODING THAT IS UNIQUE AND DISTINCT (E.G., PINK AND
PURPLE) FROM THE COLOR CODING INDICATED ABOVE. THE UNIQUE COLOR CODES SHALL BE SOLID AND IN ACCORDANCE WITH THE NEC. COORDINATE COLOR
CODING IN THE FIELD CLIENT PROJECT REPRESENTATIVE.
g. COLOR CODE FOR ISOLATED POWER SYSTEM WIRING SHALL BE IN ACCORDANCE WITH THE NEC.
• 208/120V PHASE 480/277V
• BLACK A BROWN
• RED B ORANGE
• BLUE C YELLOW
• WHITE NEUTRAL GRAY*
• * OR WHITE WITH COLORED (OTHER THAN GREEN) TRACER.
2. SPLICES
a. SPLICES SHALL BE IN ACCORDANCE WITH NEC AND UL.
b. ABOVE GROUND SPLICES FOR NO. 10 AWG AND SMALLER:
• SOLDERLESS, SCREW_ON, REUSABLE PRESSURE CABLE TYPE, WITH INTEGRAL INSULATION, APPROVED FOR COPPER AND ALUMINUM CONDUCTORS.
• THE INTEGRAL INSULATOR SHALL HAVE A SKIRT TO COMPLETELY COVER THE STRIPPED CONDUCTORS.
• THE NUMBER, SIZE, AND COMBINATION OF CONDUCTORS USED WITH THE CONNECTOR, AS LISTED ON THE MANUFACTURER'S PACKAGING, SHALL BE STRICTLY
FOLLOWED.
c. ABOVE GROUND SPLICES FOR NO. 8 AWG TO NO. 4/0 AWG:
• COMPRESSION, HEX SCREW, OR BOLT CLAMP_TYPE OF HIGH CONDUCTIVITY AND CORROSION_RESISTANT MATERIAL, LISTED FOR USE WITH COPPER AND
ALUMINUM CONDUCTORS.
• INSULATE WITH MATERIALS APPROVED FOR THE PARTICULAR USE, LOCATION, VOLTAGE, AND TEMPERATURE. INSULATION LEVEL SHALL BE NOT LESS THAN THE
INSULATION LEVEL OF THE CONDUCTORS BEING JOINED.
• SPLICE AND INSULATION SHALL BE PRODUCT OF THE SAME MANUFACTURER.
• ALL BOLTS, NUTS, AND WASHERS USED WITH SPLICES SHALL BE ZINC-PLATED STEEL.
E-001
ELECTRICAL GENERAL NOTES &
ABBREVIATIONS
TM JM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
REPLACE CHILLERS AT
ENERGY CENTER
BONHAM, TEXAS
Project Director
Revisions:
549-20-700
Approved: Project Director2340 E. TRIN ITY MILLS, STE. 220
CARROLLTON, TX 75006
972-233-2288
O'Brien Engineering, Inc.
Mr. Byron Rowland, COR Sam Rayburn Memorial Veterans Center Bonham, TX 75418
TEXAS P.E. NO. 68486
TIMOTHY J. MUECK
INTERIM REVIEW AND ARE NOT
INTENDED FOR CONSTRUCTION,
BIDDING, OR PERMIT PURPOSES.
DATE: 12 APRIL 2021
THESE DOCUMENTS ARE FOR
www.obrieneng.com
TEXAS ENGINEERING FIRM F-3758
ISSUE FOR BIDCONSULTANT
Revisions: Date:
FULLY SPRINKLERED
04.27.2021
1. RESPONSE TO PRE-BID RFI QUESTIONS 12/07/22
3. CONNECTIONS:
a. MECHANICAL TYPE OF HIGH CONDUCTIVITY AND CORROSION_RESISTANT MATERIAL, LISTED FOR USE WITH COPPER AND ALUMINUM CONDUCTORS.
b. LONG BARREL COMPRESSION TYPE OF HIGH CONDUCTIVITY AND CORROSION_RESISTANT MATERIAL, WITH MINIMUM OF TWO COMPRESSION INDENTS PER WIRE, LISTED FOR USE WITH COPPER AND ALUMINUM CONDUCTORS.
c. ALL BOLTS, NUTS, AND WASHERS USED TO CONNECT CONNECTIONS AND TERMINATIONS TO BUS BARS OR OTHER TERMINATION POINTS SHALL BE ZINC-PLATED
STEEL.
4. CONTROL WIRING
a. UNLESS OTHERWISE SPECIFIED ELSEWHERE IN THESE SPECIFICATIONS, CONTROL WIRING SHALL BE AS SPECIFIED HEREIN, EXCEPT THAT THE MINIMUM SIZE SHALL
BE NOT LESS THAN NO. 14 AWG.
b. CONTROL WIRING SHALL BE SIZED SUCH THAT THE VOLTAGE DROP UNDER IN-RUSH CONDITIONS DOES NOT ADVERSELY AFFECT OPERATION OF THE CONTROLS
C. EXECUTION
1. GENERAL
a. INSTALLATION SHALL BE IN ACCORDANCE WITH THE NEC, AS SHOWN ON THE DRAWINGS, AND MANUFACTURER'S INSTRUCTIONS.
b. INSTALL ALL CONDUCTORS IN RACEWAY SYSTEMS.
c. SPLICE CONDUCTORS ONLY IN OUTLET BOXES, JUNCTION BOXES, PULLBOXES, MANHOLES, OR HANDHOLES.
d. CONDUCTORS OF DIFFERENT SYSTEMS (E.G., 120 V AND 277 V) SHALL NOT BE INSTALLED IN THE SAME RACEWAY.
e. INSTALL CABLE SUPPORTS FOR ALL VERTICAL FEEDERS IN ACCORDANCE WITH THE NEC. PROVIDE SPLIT WEDGE TYPE WHICH FIRMLY CLAMPS EACH INDIVIDUAL
CABLE AND TIGHTENS DUE TO CABLE WEIGHT.
f. IN PANELBOARDS, CABINETS, WIREWAYS, SWITCHES, ENCLOSURES, AND EQUIPMENT ASSEMBLIES, NEATLY FORM, TRAIN, AND TIE THE CONDUCTORS WITH
NON-METALLIC TIES.
g. FOR CONNECTIONS TO MOTORS, TRANSFORMERS, AND VIBRATING EQUIPMENT, STRANDED CONDUCTORS SHALL BE USED ONLY FROM THE LAST FIXED POINT OF
CONNECTION TO THE MOTORS, TRANSFORMERS, OR VIBRATING EQUIPMENT.
h. USE EXPANDING FOAM OR NON-HARDENING DUCT-SEAL TO SEAL CONDUITS ENTERING A BUILDING, AFTER INSTALLATION OF CONDUCTORS.
i. NO MORE THAN THREE BRANCH CIRCUITS SHALL BE INSTALLED IN ANY ONE CONDUIT.
2. SPLICES AND TERMINATIONS INSTALLATION: SPLICES AND TERMINATIONS SHALL BE MECHANICALLY AND ELECTRICALLY SECURE, AND TIGHTENED TO
MANUFACTURER'S PUBLISHED TORQUE VALUES USING A TORQUE SCREWDRIVER OR WRENCH.
3. CONDUCTOR IDENTIFICATION: WHEN USING COLORED TAPE TO IDENTIFY PHASE, NEUTRAL, AND GROUND CONDUCTORS LARGER THAN NO. 8 AWG, APPLY TAPE IN HALF-OVERLAPPING TURNS FOR A MINIMUM OF 75 MM (3 INCHES) FROM TERMINAL POINTS, AND IN JUNCTION BOXES, PULLBOXES, AND MANHOLES. APPLY THE LAST TWO LAPS OF TAPE WITH NO TENSION TO PREVENT POSSIBLE UNWINDING. WHERE CABLE MARKINGS ARE COVERED BY TAPE, APPLY TAGS TO CABLE, STATING SIZE AND
INSULATION TYPE.
4. FEEDER CONDUCTOR IDENTIFICATION: IN EACH INTERIOR PULLBOX AND EACH UNDERGROUND MANHOLE AND HANDHOLE, INSTALL BRASS TAGS ON ALL FEEDER CONDUCTORS TO CLEARLY DESIGNATE THEIR CIRCUIT IDENTIFICATION AND VOLTAGE. THE TAGS SHALL BE THE EMBOSSED TYPE, 40 MM (1-1/2 INCHES) IN DIAMETER
AND 40 MILS THICK. ATTACH TAGS WITH PLASTIC TIES.
5. EXISTING CONDUCTORS: UNLESS SPECIFICALLY INDICATED ON THE PLANS, EXISTING CONDUCTORS SHALL NOT BE REUSED.
6. CONTROL WIRING INSTALLATION: INSTALL A SEPARATE POWER SUPPLY CIRCUIT FOR EACH SYSTEM, EXCEPT WHERE OTHERWISE SHOWN ON THE DRAWINGS.
7. ACCEPTANCE CHECKS AND TESTS:
a. AFTER INSTALLATION BUT BEFORE CONNECTION TO UTILIZATION DEVICES, SUCH AS FIXTURES, MOTORS, OR APPLIANCES, TEST CONDUCTORS PHASE-TO-PHASE AND PHASE-TO-GROUND RESISTANCE WITH AN INSULATION RESISTANCE TESTER. EXISTING CONDUCTORS TO BE REUSED SHALL ALSO BE TESTED.
b. PERFORM PHASE ROTATION TEST ON ALL THREE-PHASE CIRCUITS
3. GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
A. GENERAL
1. DESCRIPTION: FURNISHING, INSTALLATION, CONNECTION, AND TESTING OF GROUNDING AND BONDING EQUIPMENT, INDICATED AS GROUNDING EQUIPMENT IN THIS
SECTION.
2. "GROUNDING ELECTRODE SYSTEM" REFERS TO GROUNDING ELECTRODE CONDUCTORS AND ALL ELECTRODES REQUIRED OR ALLOWED BY NEC, AS WELL AS MADE, SUPPLEMENTARY, AND LIGHTNING PROTECTION SYSTEM GROUNDING ELECTRODES.
3. THE TERMS "CONNECT" AND "BOND" ARE USED INTERCHANGEABLY IN THIS SECTION AND HAVE THE SAME MEANING.
4. SUBMITTALS
a. SHOP DRAWINGS:
• SUBMIT SUFFICIENT INFORMATION TO DEMONSTRATE COMPLIANCE WITH DRAWINGS AND SPECIFICATIONS.
• SUBMIT PLANS SHOWING THE LOCATION OF SYSTEM GROUNDING ELECTRODES AND CONNECTIONS, AND THE ROUTING OF ABOVEGROUND AND UNDERGROUND
GROUNDING ELECTRODE CONDUCTORS.
B. PRODUCTS
1. GROUNDING AND BONDING CONDUCTORS
a. EQUIPMENT GROUNDING CONDUCTORS SHALL BE INSULATED STRANDED COPPER, EXCEPT THAT SIZES NO. 10 AWG AND SMALLER SHALL BE SOLID COPPER.
INSULATION COLOR SHALL BE CONTINUOUS GREEN FOR ALL EQUIPMENT GROUNDING CONDUCTORS, EXCEPT THAT WIRE SIZES NO. 4 AWG AND LARGER SHALL BE
IDENTIFIED PER NEC.
b. BONDING CONDUCTORS SHALL BE BARE STRANDED COPPER, EXCEPT THAT SIZES NO. 10 AWG AND SMALLER SHALL BE BARE SOLID COPPER. BONDING CONDUCTORS SHALL BE STRANDED FOR FINAL CONNECTION TO MOTORS, TRANSFORMERS, AND VIBRATING EQUIPMENT.
c. CONDUCTOR SIZES SHALL NOT BE LESS THAN SHOWN ON THE DRAWINGS, OR NOT LESS THAN REQUIRED BY THE NEC, WHICHEVER IS GREATER.
d. INSULATION: THHN-THWN AND XHHW-2. XHHW-2 SHALL BE USED FOR ISOLATED POWER SYSTEMS.
2. GROUND RODS: CONCRETE ENCASED ELECTRODE SHALL BE NO. 4 AWG BARE COPPER WIRE, INSTALLED PER NEC.
3. GROUND CONNECTIONS:
a. BELOW GRADE:
• BELOW GRADE AND INACCESSIBLE LOCATIONS: EXOTHERMIC-WELDED TYPE CONNECTORS.
b. ABOVE GRADE:
• BONDING JUMPERS: LISTED FOR USE WITH ALUMINUM AND COPPER CONDUCTORS. FOR WIRE SIZES NO. 8 AWG AND LARGER, USE COMPRESSION-TYPE
CONNECTORS. FOR WIRE SIZES SMALLER THAN NO. 8 AWG, USE MECHANICAL TYPE LUGS. CONNECTORS OR LUGS SHALL USE ZINC-PLATED STEEL BOLTS, NUTS, AND WASHERS. BOLTS SHALL BE TORQUED TO THE VALUES RECOMMENDED BY THE MANUFACTURER.
• CONNECTION TO BUILDING STEEL: EXOTHERMIC-WELDED TYPE CONNECTORS.
• CONNECTION TO GROUNDING BUS BARS: LISTED FOR USE WITH ALUMINUM AND COPPER CONDUCTORS. USE MECHANICAL TYPE LUGS, WITH ZINC-PLATED STEEL
BOLTS, NUTS, AND WASHERS. BOLTS SHALL BE TORQUED TO THE VALUES RECOMMENDED BY THE MANUFACTURER.
• CONNECTION TO EQUIPMENT RACK AND CABINET GROUND BARS: LISTED FOR USE WITH ALUMINUM AND COPPER CONDUCTORS. USE MECHANICAL TYPE LUGS, WITH //ZINC-PLATED//CADMIUM-PLATED// STEEL BOLTS, NUTS, AND WASHERS. BOLTS SHALL BE TORQUED TO THE VALUES RECOMMENDED BY THE MANUFACTURER.
c. EQUIPMENT RACK AND CABINET GROUND BARS: PROVIDE SOLID COPPER GROUND BARS DESIGNED FOR MOUNTING ON THE FRAMEWORK OF OPEN OR
CABINET-ENCLOSED EQUIPMENT RACKS. GROUND BARS SHALL HAVE MINIMUM DIMENSIONS OF 6.3 MM (0.25 INCH) THICK X 19 MM (0.75 INCH) WIDE, WITH LENGTH AS
REQUIRED OR AS SHOWN ON THE DRAWINGS. PROVIDE INSULATORS AND MOUNTING BRACKETS.
d. GROUND TERMINAL BLOCKS: AT ANY EQUIPMENT MOUNTING LOCATION (E.G., BACKBOARDS AND HINGED COVER ENCLOSURES) WHERE RACK-TYPE GROUND BARS CANNOT BE MOUNTED, PROVIDE MECHANICAL TYPE LUGS, WITH ZINC-PLATED STEEL BOLTS, NUTS, AND WASHERS. BOLTS SHALL BE TORQUED TO THE VALUES
RECOMMENDED BY THE MANUFACTURER.
e. GROUNDING BUS BAR: PRE-DRILLED RECTANGULAR COPPER BAR WITH STAND-OFF INSULATORS, MINIMUM 6.3 MM (0.25 INCH) THICK X 100 MM (4 INCHES) HIGH IN CROSS-SECTION, LENGTH AS SHOWN ON THE DRAWINGS, WITH HOLE SIZE, QUANTITY, AND SPACING PER DETAIL SHOWN ON THE DRAWINGS. PROVIDE INSULATORS
AND MOUNTING BRACKETS.
C. EXECUTION
1. GENERAL
a. INSTALLATION SHALL BE IN ACCORDANCE WITH THE NEC, AS SHOWN ON THE DRAWINGS, AND MANUFACTURER'S INSTRUCTIONS.
b. SYSTEM GROUNDING
• SECONDARY SERVICE NEUTRALS: GROUND AT THE SUPPLY SIDE OF THE SECONDARY DISCONNECTING MEANS AND AT THE RELATED TRANSFORMER.
• SEPARATELY DERIVED SYSTEMS (TRANSFORMERS DOWNSTREAM FROM THE SERVICE ENTRANCE): GROUND THE SECONDARY NEUTRAL.
• ISOLATION TRANSFORMERS AND ISOLATED POWER SYSTEMS SHALL NOT BE SYSTEM GROUNDED.
c. EQUIPMENT GROUNDING: METALLIC PIPING, BUILDING STRUCTURAL STEEL, ELECTRICAL ENCLOSURES, RACEWAYS, JUNCTION BOXES, OUTLET BOXES, CABINETS, MACHINE FRAMES, AND OTHER CONDUCTIVE ITEMS IN CLOSE PROXIMITY WITH ELECTRICAL CIRCUITS, SHALL BE BONDED AND GROUNDED.
2. INACCESSIBLE GROUNDING CONNECTIONS
a. MAKE GROUNDING CONNECTIONS, WHICH ARE NORMALLY BURIED OR OTHERWISE INACCESSIBLE, BY EXOTHERMIC WELD.
3. SECONDARY VOLTAGE EQUIPMENT AND CIRCUITS
a. MAIN BONDING JUMPER: BOND THE SECONDARY SERVICE NEUTRAL TO THE GROUND BUS IN THE SERVICE EQUIPMENT.
b. METALLIC PIPING, BUILDING STRUCTURAL STEEL, AND SUPPLEMENTAL ELECTRODE(S)
c. PROVIDE A GROUNDING ELECTRODE CONDUCTOR SIZED PER NEC BETWEEN THE SERVICE EQUIPMENT GROUND BUS AND ALL METALLIC WATER PIPE SYSTEMS, BUILDING STRUCTURAL STEEL, AND SUPPLEMENTAL OR MADE ELECTRODES. PROVIDE JUMPERS ACROSS INSULATING JOINTS IN THE METALLIC PIPING.
d. PROVIDE A SUPPLEMENTAL GROUND ELECTRODE AS SHOWN ON THE DRAWINGS AND BOND TO THE GROUNDING ELECTRODE SYSTEM.
e. SWITCHGEAR, SWITCHBOARDS, UNIT SUBSTATIONS, PANELBOARDS, MOTOR CONTROL CENTERS, ENGINE-GENERATORS, AUTOMATIC TRANSFER SWITCHES, AND
OTHER ELECTRICAL EQUIPMENT:
f. CONNECT THE EQUIPMENT GROUNDING CONDUCTORS TO THE GROUND BUS.
g. CONNECT METALLIC CONDUITS BY GROUNDING BUSHINGS AND EQUIPMENT GROUNDING CONDUCTOR TO THE EQUIPMENT GROUND BUS.
h. EXTERIOR: EXTERIOR TRANSFORMERS SUPPLYING INTERIOR SERVICE EQUIPMENT SHALL HAVE THE NEUTRAL GROUNDED AT THE TRANSFORMER SECONDARY.
PROVIDE A GROUNDING ELECTRODE AT THE TRANSFORMER.
i. SEPARATELY DERIVED SYSTEMS (TRANSFORMERS DOWNSTREAM FROM SERVICE EQUIPMENT): GROUND THE SECONDARY NEUTRAL AT THE TRANSFORMER. PROVIDE
A GROUNDING ELECTRODE CONDUCTOR FROM THE TRANSFORMER TO THE NEAREST COMPONENT OF THE GROUNDING ELECTRODE SYSTEM OR THE GROUND BAR
AT THE SERVICE EQUIPMENT.
4. RACEWAY
a. CONDUIT SYSTEMS
• GROUND ALL METALLIC CONDUIT SYSTEMS. ALL METALLIC CONDUIT SYSTEMS SHALL CONTAIN AN EQUIPMENT GROUNDING CONDUCTOR.
• NON_METALLIC CONDUIT SYSTEMS, EXCEPT NON-METALLIC FEEDER CONDUITS THAT CARRY A GROUNDED CONDUCTOR FROM EXTERIOR TRANSFORMERS TO
INTERIOR OR BUILDING-MOUNTED SERVICE ENTRANCE EQUIPMENT, SHALL CONTAIN AN EQUIPMENT GROUNDING CONDUCTOR.
• METALLIC CONDUIT THAT ONLY CONTAINS A GROUNDING CONDUCTOR, AND IS PROVIDED FOR ITS MECHANICAL PROTECTION, SHALL BE BONDED TO THAT
CONDUCTOR AT THE ENTRANCE AND EXIT FROM THE CONDUIT.
• METALLIC CONDUITS WHICH TERMINATE WITHOUT MECHANICAL CONNECTION TO AN ELECTRICAL EQUIPMENT HOUSING BY MEANS OF LOCKNUT AND BUSHINGS OR
ADAPTERS, SHALL BE PROVIDED WITH GROUNDING BUSHINGS. CONNECT BUSHINGS WITH A EQUIPMENT GROUNDING CONDUCTOR TO THE EQUIPMENT GROUND
BUS.
• FEEDERS AND BRANCH CIRCUITS: INSTALL EQUIPMENT GROUNDING CONDUCTORS WITH ALL FEEDERS, AND POWER AND LIGHTING BRANCH CIRCUITS.
• BOXES, CABINETS, ENCLOSURES, AND PANELBOARDS: BOND THE EQUIPMENT GROUNDING CONDUCTOR TO EACH PULLBOX, JUNCTION BOX, OUTLET BOX, DEVICE
BOX, CABINETS, AND OTHER ENCLOSURES THROUGH WHICH THE CONDUCTOR PASSES (EXCEPT FOR SPECIAL GROUNDING SYSTEMS FOR INTENSIVE CARE UNITS
AND OTHER CRITICAL UNITS SHOWN).
• BOXES, CABINETS, ENCLOSURES, AND PANELBOARDS: PROVIDE LUGS IN EACH BOX AND ENCLOSURE FOR EQUIPMENT GROUNDING CONDUCTOR TERMINATION.
b. RECEPTACLES SHALL NOT BE GROUNDED THROUGH THEIR MOUNTING SCREWS. GROUND RECEPTACLES WITH A JUMPER FROM THE RECEPTACLE GREEN GROUND
TERMINAL TO THE DEVICE BOX GROUND SCREW AND A JUMPER TO THE BRANCH CIRCUIT EQUIPMENT GROUNDING CONDUCTOR.
c. GROUND LIGHTING FIXTURES TO THE EQUIPMENT GROUNDING CONDUCTOR OF THE WIRING SYSTEM. FIXTURES CONNECTED WITH FLEXIBLE CONDUIT SHALL HAVE A
GREEN GROUND WIRE INCLUDED WITH THE POWER WIRES FROM THE FIXTURE THROUGH THE FLEXIBLE CONDUIT TO THE FIRST OUTLET BOX.
5. CORROSION INHIBITORS: WHEN MAKING GROUNDING AND BONDING CONNECTIONS, APPLY A CORROSION INHIBITOR TO ALL CONTACT SURFACES. USE CORROSION
INHIBITOR APPROPRIATE FOR PROTECTING A CONNECTION BETWEEN THE METALS USED.
6. CONDUCTIVE PIPING: BOND ALL CONDUCTIVE PIPING SYSTEMS, INTERIOR AND EXTERIOR, TO THE GROUNDING ELECTRODE SYSTEM. BONDING CONNECTIONS SHALL BE
MADE AS CLOSE AS PRACTICAL TO THE EQUIPMENT GROUND BUS.
7. LIGHTNING PROTECTION SYSTEM: BOND THE LIGHTNING PROTECTION SYSTEM TO THE ELECTRICAL GROUNDING ELECTRODE SYSTEM.
8. MAIN ELECTRICAL ROOM GROUNDING: PROVIDE GROUND BUS BAR AND MOUNTING HARDWARE AT EACH MAIN ELECTRICAL ROOM WHERE INCOMING FEEDERS ARE
TERMINATED, AS SHOWN ON THE DRAWINGS. CONNECT TO PIGTAIL EXTENSIONS OF THE BUILDING GROUNDING RING, AS SHOWN ON THE DRAWINGS.
9. EXTERIOR LIGHT POLES: PROVIDE 6.1 M (20 FEET) OF NO. 4 AWG BARE COPPER COILED AT BOTTOM OF POLE BASE EXCAVATION PRIOR TO POUR, PLUS ADDITIONAL
UN-SPLICED LENGTH IN AND ABOVE FOUNDATION AS REQUIRED TO REACH POLE GROUND STUD.
10. GROUND ROD INSTALLATAION:
a. FOR OUTDOOR INSTALLATIONS, DRIVE EACH ROD VERTICALLY IN THE EARTH, UNTIL TOP OF ROD IS 610 MM (24 INCHES) BELOW FINAL GRADE.
b. FOR INDOOR INSTALLATIONS, LEAVE 100 MM (4 INCHES) OF EACH ROD EXPOSED.
c. WHERE BURIED OR PERMANENTLY CONCEALED GROUND CONNECTIONS ARE REQUIRED, MAKE THE CONNECTIONS BY THE EXOTHERMIC PROCESS, TO FORM SOLID
METAL JOINTS. MAKE ACCESSIBLE GROUND CONNECTIONS WITH MECHANICAL PRESSURE-TYPE GROUND CONNECTORS.
4. RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS
A. GENERAL
1. DESCRIPTION: FURNISHING, INSTALLATION, AND CONNECTION OF CONDUIT, FITTINGS, AND BOXES, TO FORM COMPLETE, COORDINATED, GROUNDED RACEWAY SYSTEMS. RACEWAYS ARE REQUIRED FOR ALL WIRING UNLESS SHOWN OR SPECIFIED OTHERWISE.
2. THE TERM CONDUIT, AS USED IN THIS SPECIFICATION, SHALL MEAN ANY OR ALL OF THE RACEWAY TYPES SPECIFIED.
3. SUBMITTALS
a. SHOP DRAWINGS: SIZE AND LOCATION OF MAIN FEEDERS, SIZE AND LOCATION OF PANELS AND PULL-BOXES, LAYOUT OF REQUIRED CONDUIT PENETRATIONS THROUGH STRUCTURAL ELEMENTS, RACEWAY TYPES AND SIZES, CONDUIT BODIES, CONNECTORS AND FITTINGS, JUNCTION AND PULL BOXES, TYPES AND SIZES.
B. PRODUCTS
1. MATERIALS:
a. CONDUIT SIZE: IN ACCORDANCE WITH THE NEC, BUT NOT LESS THAN 13 MM (0.5-INCH) UNLESS OTHERWISE SHOWN.
2. MATERIALS - CONDUIT:
a. SIZE: IN ACCORDANCE WITH THE NEC, BUT NOT LESS THAN 13 MM (0.5-INCH).
b. RIGID STEEL CONDUIT (RMC): SHALL CONFORM TO UL 6 AND NEMA C80.1.
c. RIGID INTERMEDIATE STEEL CONDUIT (IMC): SHALL CONFORM TO UL 1242 AND NEMA C80.6.
d. ELECTRICAL METALLIC TUBING (EMT): SHALL CONFORM TO UL 797 AND NEMA C80.3. MAXIMUM SIZE NOT TO EXCEED 105 MM (4 INCHES) AND SHALL BE
e. FLEXIBLE METAL CONDUIT: SHALL CONFORM TO UL 1.
f. LIQUID-TIGHT FLEXIBLE METAL CONDUIT: SHALL CONFORM TO UL 360.
g. DIRECT BURIAL PLASTIC CONDUIT: SHALL CONFORM TO UL 651 AND UL 651A, HEAVY WALL PVC OR HIGH DENSITY POLYETHYLENE (PE).
h. SURFACE METAL RACEWAY: SHALL CONFORM TO UL 5.
3. MATERIALS - CONDUIT FITTINGS
a. RIGID STEEL AND INTERMEDIATE METALLIC CONDUIT FITTINGS: FITTINGS SHALL MEET THE REQUIREMENTS OF UL 514B AND NEMA FB1.
b. FITTINGS SHALL MEET THE REQUIREMENTS OF UL 514B AND NEMA FB1.
c. STANDARD THREADED COUPLINGS, LOCKNUTS, BUSHINGS, CONDUIT BODIES, AND ELBOWS: ONLY STEEL OR MALLEABLE IRON MATERIALS ARE ACCEPTABLE.
INTEGRAL RETRACTABLE TYPE IMC COUPLINGS ARE ALSO ACCEPTABLE.
d. LOCKNUTS: BONDING TYPE WITH SHARP EDGES FOR DIGGING INTO THE METAL WALL OF AN ENCLOSURE.
e. BUSHINGS: METALLIC INSULATING TYPE, CONSISTING OF AN INSULATING INSERT, MOLDED OR LOCKED INTO THE METALLIC BODY OF THE FITTING. BUSHINGS MADE
ENTIRELY OF METAL OR NONMETALLIC MATERIAL ARE NOT PERMITTED.
f. ERICKSON (UNION_TYPE) AND SET SCREW TYPE COUPLINGS: APPROVED FOR USE IN CONCRETE ARE PERMITTED FOR USE TO COMPLETE A CONDUIT RUN WHERE
CONDUIT IS INSTALLED IN CONCRETE. USE SET SCREWS OF CASE-HARDENED STEEL WITH HEX HEAD AND CUP POINT TO FIRMLY SEAT IN CONDUIT WALL FOR
POSITIVE GROUND. TIGHTENING OF SET SCREWS WITH PLIERS IS PROHIBITED.
g. SEALING FITTINGS: THREADED CAST IRON TYPE. USE CONTINUOUS DRAIN-TYPE SEALING FITTINGS TO PREVENT PASSAGE OF WATER VAPOR. IN CONCEALED WORK, INSTALL FITTINGS IN FLUSH STEEL BOXES WITH BLANK COVER PLATES HAVING THE SAME FINISHES AS THAT OF OTHER ELECTRICAL PLATES IN THE ROOM.
h. ELECTRICAL METALLIC TUBING FITTINGS:
• FITTINGS AND CONDUIT BODIES SHALL MEET THE REQUIREMENTS OF UL 514B, NEMA C80.3, AND NEMA FB1.
• ONLY STEEL OR MALLEABLE IRON MATERIALS ARE ACCEPTABLE.
• COMPRESSION COUPLINGS AND CONNECTORS: CONCRETE-TIGHT AND RAIN-TIGHT, WITH CONNECTORS HAVING INSULATED THROATS.
• SETSCREW COUPLINGS AND CONNECTORS: USE SETSCREWS OF CASE-HARDENED STEEL WITH HEX HEAD AND CUP POINT, TO FIRMLY SEAT IN WALL OF CONDUIT
FOR POSITIVE GROUNDING.
• INDENT-TYPE CONNECTORS OR COUPLINGS ARE PROHIBITED.
• DIE-CAST OR PRESSURE-CAST ZINC-ALLOY FITTINGS OR FITTINGS MADE OF "POT METAL" ARE PROHIBITED.
i. FLEXIBLE METAL CONDUIT FITTINGS:
• CONFORM TO UL 514B. ONLY STEEL OR MALLEABLE IRON MATERIALS ARE ACCEPTABLE.
• CLAMP-TYPE, WITH INSULATED THROAT.
j. LIQUID_TIGHT FLEXIBLE METAL CONDUIT FITTINGS:
• FITTINGS SHALL MEET THE REQUIREMENTS OF UL 514B AND NEMA FB1.
• ONLY STEEL OR MALLEABLE IRON MATERIALS ARE ACCEPTABLE.
• FITTINGS MUST INCORPORATE A THREADED GROUNDING CONE, A STEEL OR PLASTIC COMPRESSION RING, AND A GLAND FOR TIGHTENING. CONNECTORS SHALL
HAVE INSULATED THROATS.
k. DIRECT BURIAL PLASTIC CONDUIT FITTINGS: FITTINGS SHALL MEET THE REQUIREMENTS OF UL 514C AND NEMA TC3.
l. SURFACE METAL RACEWAY FITTINGS: AS RECOMMENDED BY THE RACEWAY MANUFACTURER. INCLUDE COUPLINGS, OFFSETS, ELBOWS, EXPANSION JOINTS, ADAPTERS, HOLD-DOWN STRAPS, END CAPS, CONDUIT ENTRY FITTINGS, ACCESSORIES, AND OTHER FITTINGS AS REQUIRED FOR COMPLETE SYSTEM.
4.CONDUIT SUPPORTS
a. PARTS AND HARDWARE: ZINC_COAT OR PROVIDE EQUIVALENT CORROSION PROTECTION.
b. INDIVIDUAL CONDUIT HANGERS: DESIGNED FOR THE PURPOSE, HAVING A PRE_ASSEMBLED CLOSURE BOLT AND NUT, AND PROVISIONS FOR RECEIVING A HANGER
ROD.
c. MULTIPLE CONDUIT (TRAPEZE) HANGERS: NOT LESS THAN 38 MM X 38 MM (1.5 X 1.5 INCHES), 12-GAUGE STEEL, COLD-FORMED, LIPPED CHANNELS; WITH NOT LESS
THAN 9 MM (0.375-INCH) DIAMETER STEEL HANGER RODS.
5. OUTLET, JUNCTION, AND PULL BOXES:
a. COMPLY WITH UL-50 AND UL-514A.
b. RUSTPROOF CAST METAL WHERE REQUIRED BY THE NEC OR SHOWN ON DRAWINGS.
c. SHEET METAL BOXES: GALVANIZED STEEL, EXCEPT WHERE SHOWN ON DRAWINGS.
C. EXECUTION
1. PENETRATIONS
a. CUT HOLES THROUGH CONCRETE AND MASONRY IN NEW AND EXISTING STRUCTURES WITH A DIAMOND CORE DRILL OR CONCRETE SAW. PNEUMATIC HAMMERS, IMPACT ELECTRIC, HAND, OR MANUAL HAMMER-TYPE DRILLS ARE NOT ALLOWED, EXCEPT WHEN PERMITTED WHERE WORKING SPACE IS LIMITED.
b. FIRESTOP: WHERE CONDUITS, WIREWAYS, AND OTHER ELECTRICAL RACEWAYS PASS THROUGH FIRE PARTITIONS, FIRE WALLS, SMOKE PARTITIONS, OR FLOORS, INSTALL A FIRE STOP THAT PROVIDES AN EFFECTIVE BARRIER AGAINST THE SPREAD OF FIRE, SMOKE AND GASES AS SPECIFIED IN SECTION FIRESTOPPING.
c. WATERPROOFING: AT FLOOR, EXTERIOR WALL, AND ROOF CONDUIT PENETRATIONS, COMPLETELY SEAL THE GAP AROUND CONDUIT TO RENDER IT WATERTIGHT, AS
SPECIFIED WITH APPROVED JOINT SEALANTS.
GENERAL NOTES
2. INSTALLATION
a. IN ACCORDANCE WITH NEC, NEMA, UL, AS SHOWN ON DRAWINGS, AND AS SPECIFIED HEREIN.
b. INSTALL CONDUIT AS FOLLOWS:
• IN COMPLETE MECHANICALLY AND ELECTRICALLY CONTINUOUS RUNS BEFORE PULLING IN CABLES OR WIRES.
• UNLESS OTHERWISE INDICATED ON THE DRAWINGS OR SPECIFIED HEREIN, INSTALLATION OF ALL CONDUITS SHALL BE CONCEALED WITHIN FINISHED WALLS, FLOORS, AND CEILINGS.
• FLATTENED, DENTED, OR DEFORMED CONDUIT IS NOT PERMITTED. REMOVE AND REPLACE THE DAMAGED CONDUITS WITH NEW CONDUITS.
• ASSURE CONDUIT INSTALLATION DOES NOT ENCROACH INTO THE CEILING HEIGHT HEAD ROOM, WALKWAYS, OR DOORWAYS.
• CUT CONDUITS SQUARE, REAM, REMOVE BURRS, AND DRAW UP TIGHT.
• DO NOT USE SUSPENDED CEILINGS, SUSPENDED CEILING SUPPORTING MEMBERS, LIGHTING FIXTURES, OTHER CONDUITS, CABLE TRAY, BOXES, PIPING, OR DUCTS TO
SUPPORT CONDUITS AND CONDUIT RUNS.
• SUPPORT WITHIN 300 MM (12 INCHES) OF CHANGES OF DIRECTION, AND WITHIN 300 MM (12 INCHES) OF EACH ENCLOSURE TO WHICH CONNECTED.
• CLOSE ENDS OF EMPTY CONDUITS WITH PLUGS OR CAPS AT THE ROUGH_IN STAGE UNTIL WIRES ARE PULLED IN, TO PREVENT ENTRY OF DEBRIS.
• SECURE CONDUITS TO CABINETS, JUNCTION BOXES, PULL-BOXES, AND OUTLET BOXES WITH BONDING TYPE LOCKNUTS. FOR RIGID STEEL AND IMC CONDUIT
INSTALLATIONS, PROVIDE A LOCKNUT ON THE INSIDE OF THE ENCLOSURE, MADE UP WRENCH TIGHT. DO NOT MAKE CONDUIT CONNECTIONS TO JUNCTION BOX
COVERS.
• CONDUIT BODIES SHALL ONLY BE USED FOR CHANGES IN DIRECTION, AND SHALL NOT CONTAIN SPLICES.
c. CONDUIT BENDS: MAKE BENDS WITH STANDARD CONDUIT BENDING MACHINES, CONDUIT HICKEY MAY BE USED FOR SLIGHT OFFSETS AND FOR STRAIGHTENING
STUBBED OUT CONDUITS, BENDING OF CONDUITS WITH A PIPE TEE OR VISE IS PROHIBITED.
d. LAYOUT AND HOMERUNS: INSTALL CONDUIT WITH WIRING, INCLUDING HOMERUNS, AS SHOWN ON DRAWINGS.
3. CONCEALED WORK INSTALLATION
a. IN CONCRETE:
• CONDUIT: RIGID STEEL, IMC, OR EMT. DO NOT INSTALL EMT IN CONCRETE SLABS THAT ARE IN CONTACT WITH SOIL, GRAVEL, OR VAPOR BARRIERS.
1) INSTALLATION OF CONDUIT IN CONCRETE THAT IS LESS THAN 75 MM (3 INCHES) THICK IS PROHIBITED.
b. ABOVE FURRED OR SUSPENDED CEILINGS AND IN WALLS:
• CONDUIT FOR CONDUCTORS 600 V AND BELOW: RIGID STEEL, IMC, OR EMT. MIXING DIFFERENT TYPES OF CONDUITS IN THE SAME SYSTEM IS PROHIBITED.
1) ALIGN AND RUN CONDUIT PARALLEL OR PERPENDICULAR TO THE BUILDING LINES.
2) CONNECT RECESSED LIGHTING FIXTURES TO CONDUIT RUNS WITH MAXIMUM 1.8 M (6 FEET) OF FLEXIBLE METAL CONDUIT EXTENDING FROM A JUNCTION BOX TO THE
FIXTURE.
3) FOR CONDUITS RUNNING THROUGH METAL STUDS, LIMIT FIELD CUT HOLES TO NO MORE THAN 70% OF WEB DEPTH. SPACING BETWEEN HOLES SHALL BE AT LEAST
457 MM (18 INCHES). CUTS OR NOTCHES IN FLANGES OR RETURN LIPS SHALL NOT BE PERMITTED.
4. EXPOSED WORK INSTALLATION
a. UNLESS OTHERWISE INDICATED ON DRAWINGS, EXPOSED CONDUIT IS ONLY PERMITTED IN MECHANICAL AND ELECTRICAL ROOMS.
b. CONDUIT FOR CONDUCTORS 600 V AND BELOW: RIGID STEEL, IMC OR EMT. MIXING DIFFERENT TYPES OF CONDUITS IN THE SYSTEM IS PROHIBITED.
c. ALIGN AND RUN CONDUIT PARALLEL OR PERPENDICULAR TO THE BUILDING LINES.
d. INSTALL HORIZONTAL RUNS CLOSE TO THE CEILING OR BEAMS AND SECURE WITH CONDUIT STRAPS.
5. WET OR DAMP LOCATIONS
a. USE RIGID STEEL OR IMC CONDUITS UNLESS AS SHOWN ON DRAWINGS.
b. PROVIDE SEALING FITTINGS TO PREVENT PASSAGE OF WATER VAPOR WHERE CONDUITS PASS FROM WARM TO COLD LOCATIONS, I.E., REFRIGERATED SPACES, CONSTANT-TEMPERATURE ROOMS, AIR-CONDITIONED SPACES, BUILDING EXTERIOR WALLS, ROOFS, OR SIMILAR SPACES.
6. MOTORS AND VIBRATING EQUIPMENT
a. USE FLEXIBLE METAL CONDUIT FOR CONNECTIONS TO MOTORS AND OTHER ELECTRICAL EQUIPMENT SUBJECT TO MOVEMENT, VIBRATION, MISALIGNMENT, CRAMPED
QUARTERS, OR NOISE TRANSMISSION.
b. USE LIQUID_TIGHT FLEXIBLE METAL CONDUIT FOR INSTALLATION IN EXTERIOR LOCATIONS, MOISTURE OR HUMIDITY LADEN ATMOSPHERE, CORROSIVE ATMOSPHERE, WATER OR SPRAY WASH_DOWN OPERATIONS, INSIDE AIRSTREAM OF HVAC UNITS, AND LOCATIONS SUBJECT TO SEEPAGE OR DRIPPING OF OIL, GREASE, OR WATER.
c. PROVIDE A GREEN EQUIPMENT GROUNDING CONDUCTOR WITH FLEXIBLE AND LIQUID-TIGHT FLEXIBLE METAL CONDUIT.
7. CONDUIT SUPPORTS
a. SUPPORT MULTIPLE CONDUIT RUNS WITH TRAPEZE HANGERS. USE TRAPEZE HANGERS THAT ARE DESIGNED TO SUPPORT A LOAD EQUAL TO OR GREATER THAN THE SUM OF THE WEIGHTS OF THE CONDUITS, WIRES, HANGER ITSELF, AND AN ADDITIONAL 90 KG (200 LBS). ATTACH EACH CONDUIT WITH U_BOLTS OR OTHER APPROVED
FASTENERS.
b. SUPPORT CONDUIT INDEPENDENTLY OF JUNCTION BOXES, PULL-BOXES, FIXTURES, SUSPENDED CEILING T_BARS, ANGLE SUPPORTS, AND SIMILAR ITEMS.
c. VERTICAL SUPPORTS: VERTICAL CONDUIT RUNS SHALL HAVE RISER CLAMPS AND SUPPORTS IN ACCORDANCE WITH THE NEC AND AS SHOWN. PROVIDE SUPPORTS FOR
CABLE AND WIRE WITH FITTINGS THAT INCLUDE INTERNAL WEDGES AND RETAINING COLLARS.
8. BOX INSTALLATION
a. BOXES FOR CONCEALED CONDUITS:
• FLUSH-MOUNTED.
• PROVIDE RAISED COVERS FOR BOXES TO SUIT THE WALL OR CEILING, CONSTRUCTION, AND FINISH.
b. IN ADDITION TO BOXES SHOWN, INSTALL ADDITIONAL BOXES WHERE NEEDED TO PREVENT DAMAGE TO CABLES AND WIRES DURING PULLING-IN OPERATIONS OR WHERE
MORE THAN THE EQUIVALENT OF 4-90 DEGREE BENDS ARE NECESSARY.
c. LOCATE PULLBOXES SO THAT COVERS ARE ACCESSIBLE AND EASILY REMOVED. COORDINATE LOCATIONS WITH PIPING AND DUCTWORK WHERE INSTALLED ABOVE
CEILINGS.
d. OUTLET BOXES MOUNTED BACK_TO_BACK IN THE SAME WALL ARE PROHIBITED. A MINIMUM 600 MM (24 INCH) CENTER-TO-CENTER LATERAL SPACING SHALL BE
MAINTAINED BETWEEN BOXES.
e. FLUSH-MOUNTED WALL OR CEILING BOXES SHALL BE INSTALLED WITH RAISED COVERS SO THAT THE FRONT FACE OF RAISED COVER IS FLUSH WITH THE WALL.
SURFACE-MOUNTED WALL OR CEILING BOXES SHALL BE INSTALLED WITH SURFACE-STYLE FLAT OR RAISED COVERS.
f. MINIMUM SIZE OF OUTLET BOXES FOR GROUND FAULT CIRCUIT INTERRUPTER (GFCI) RECEPTACLES IS 100 MM (4 INCHES) SQUARE X 55 MM (2.125 INCHES) DEEP, WITH
DEVICE COVERS FOR THE WALL MATERIAL AND THICKNESS INVOLVED.
g. ON ALL BRANCH CIRCUIT JUNCTION BOX COVERS, IDENTIFY THE CIRCUITS WITH BLACK MARKER.
5. DISTRIBUTION SWITCHBOARDS
A. GENERAL
1. DESCRIPTION: FURNISHING, INSTALLATION, CONNECTION, AND TESTING OF THE LOW-VOLTAGE CIRCUIT-BREAKER DISTRIBUTION SWITCHBOARDS, INDICATED AS
SWITCHBOARD(S) IN THIS SECTION.
B. PRODUCTS
1. SHALL BE IN ACCORDANCE WITH IEEE, NEMA, NFPA, UL, AS SHOWN ON THE DRAWINGS, AND HAVE THE FOLLOWING FEATURES:
2. SWITCHBOARD SHALL BE A COMPLETE, GROUNDED, CONTINUOUS_DUTY, INTEGRAL ASSEMBLY, DEAD_FRONT, DEAD_REAR, SELF_SUPPORTING, INDOOR TYPE
SWITCHBOARD ASSEMBLY, TAMPERPROOF, WEATHERPROOF, OUTDOOR TYPE SWITCHBOARD ASSEMBLY AS DESIGNED. INCORPORATE DEVICES SHOWN ON THE DRAWINGS AND ALL RELATED COMPONENTS REQUIRED TO FULFILL OPERATIONAL AND FUNCTIONAL REQUIREMENTS.
3. RATINGS SHALL NOT BE LESS THAN SHOWN ON THE DRAWINGS. SHORT CIRCUIT RATINGS SHALL NOT BE LESS THAN THE AVAILABLE FAULT CURRENT SHOWN.
4. COORDINATE ALL REQUIREMENTS WITH THE ELECTRIC UTILITY COMPANY SUPPLYING ELECTRICAL SERVICE TO THE SWITCHBOARD. THE INCOMING ELECTRIC UTILITY
FEEDER AND REVENUE METERING INSTALLATION SHALL CONFORM TO THE REQUIREMENTS OF THE ELECTRIC UTILITY COMPANY.
5. TYPE 1: SWITCHBOARD SHALL BE FRONT ACCESSIBLE WITH THE FOLLOWING FEATURES:
6. TYPE 2: SWITCHBOARD SHALL BE REAR ACCESSIBLE WITH THE FOLLOWING FEATURES:
7. BUS BARS AND INTERCONNECTIONS
8. PROVIDE COPPER PHASE AND NEUTRAL BUSES, FULLY RATED FOR THE AMPERAGE AS SHOWN ON THE DRAWINGS FOR THE ENTIRE LENGTH OF THE SWITCHBOARD. BUS
LAMINATIONS SHALL HAVE A MINIMUM OF 6 MM (1/4 INCH) SPACING.
9. THE BUS AND BUS COMPARTMENT SHALL BE DESIGNED SO THAT THE ACCEPTABLE NEMA STANDARD TEMPERATURE RISES ARE NOT EXCEEDED.
10. MAIN BONDING JUMPER: AN UN-INSULATED COPPER BUS, SIZE AS SHOWN ON DRAWINGS, SHALL INTERCONNECT THE NEUTRAL AND GROUND BUSES, WHEN THE
SWITCHBOARD IS USED TO ESTABLISH THE SYSTEM COMMON GROUND POINT.
11. ALL BOLTS, NUTS, AND WASHERS SHALL BE ZINC-PLATED STEEL. BOLTS SHALL BE TORQUED TO THE VALUES RECOMMENDED BY THE MANUFACTURER.
12. MAKE PROVISIONS FOR FUTURE BUS EXTENSIONS BY MEANS OF BOLT HOLES OR OTHER APPROVED METHOD.
13. MAIN CIRCUIT BREAKERS
a. TYPE I OR TYPE II SWITCHBOARDS: PROVIDE MOLDED CASE MAIN CIRCUIT BREAKERS AS SHOWN ON THE DRAWINGS. CIRCUIT BREAKERS SHALL BE THE SOLID STATE
ADJUSTABLE TRIP TYPE.
E-002
ELECTRICAL GENERAL NOTES &
ABBREVIATIONS
TM JM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
REPLACE CHILLERS AT
ENERGY CENTER
BONHAM, TEXAS
Project Director
Revisions:
549-20-700
Approved: Project Director2340 E. TRIN ITY MILLS, STE. 220
CARROLLTON, TX 75006
972-233-2288
O'Brien Engineering, Inc.
Mr. Byron Rowland, COR Sam Rayburn Memorial Veterans Center Bonham, TX 75418
TEXAS P.E. NO. 68486
TIMOTHY J. MUECK
INTERIM REVIEW AND ARE NOT
INTENDED FOR CONSTRUCTION,
BIDDING, OR PERMIT PURPOSES.
DATE: 12 APRIL 2021
THESE DOCUMENTS ARE FOR
www.obrieneng.com
TEXAS ENGINEERING FIRM F-3758
ISSUE FOR BIDCONSULTANT
Revisions: Date:
FULLY SPRINKLERED
04.27.2021
14. FEEDER CIRCUIT BREAKERS
a. PROVIDE MOLDED CASE CIRCUIT BREAKERS AS SHOWN ON THE DRAWINGS.
b. NON-ADJUSTABLE TRIP MOLDED CASE CIRCUIT BREAKERS:
• MOLDED CASE CIRCUIT BREAKERS SHALL HAVE AUTOMATIC, TRIP FREE, NON-ADJUSTABLE, INVERSE TIME CHARACTERISTICS, AND INSTANTANEOUS MAGNETIC TRIP.
• BREAKER FEATURES SHALL BE AS FOLLOWS:
1. A RUGGED, INTEGRAL HOUSING OF MOLDED INSULATING MATERIAL.
2. SILVER ALLOY CONTACTS
3. ARC QUENCHERS AND PHASE BARRIERS FOR EACH POLE.
4. QUICK_MAKE, QUICK_BREAK, OPERATING MECHANISMS.
5. A TRIP ELEMENT FOR EACH POLE, THERMAL MAGNETIC TYPE WITH LONG TIME DELAY AND INSTANTANEOUS CHARACTERISTICS, A COMMON TRIP BAR FOR ALL
POLES AND A SINGLE OPERATOR.
6. ELECTRICALLY AND MECHANICALLY TRIP FREE.
7. AN OPERATING HANDLE WHICH INDICATES ON, TRIPPED, AND OFF POSITIONS.
8. LINE AND LOAD CONNECTIONS SHALL BE BOLTED.
9. AN OVERLOAD ON ONE POLE OF A MULTIPOLE BREAKER SHALL AUTOMATICALLY CAUSE ALL THE POLES OF THE BREAKER TO OPEN.
c. ADJUSTABLE TRIP MOLDED CASE CIRCUIT BREAKERS:
• PROVIDE MOLDED CASE, SOLID STATE ADJUSTABLE TRIP TYPE CIRCUIT BREAKERS.
• TRIP UNITS SHALL HAVE FIELD ADJUSTABLE TRIPPING CHARACTERISTICS AS FOLLOWS:
• LONG TIME PICKUP, LONG TIME DELAY, SHORT TIME PICKUP, SHORT TIME DELAY, INSTANTANEOUS, GROUND FAULT PICKUP, GROUND FAULT DELAY.
d. BREAKERS WITH SAME FRAME SIZE SHALL BE INTERCHANGEABLE WITH EACH OTHER.
15. ELECTRIC UTILITY COMPANY…