SOW Appendix A.pdf

PDF 158 KB Posted

Attached to
J044--Central Texas Mobile Boiler Compliance Upgrade
Solicitation number
36C25722Q0849
Issued by

About this file

This document contains a Statement of Work (SOW) appendix detailing the required products and services for the Central Texas Mobile Boiler Compliance Upgrade federal contract opportunity. The contractor shall provide labor, materials, and equipment to upgrade the mobile boiler system at the Central Texas Veterans Health Care Facility in Temple, Texas to meet VA compliance requirements. The SOW appendix lists 47 line items totaling various products needed, including level controls, gauges, valves, lights, relays, sensors, and a flame safeguard system. It also specifies services required such as installing gas valves, probes, alarms, test buttons, and damper switches. The contractor must complete all work and pass a final walkthrough with the Project Manager to receive payment for this turnkey project.

View the file

Other files

File Type Posted
36C25722Q0849 0002_1.docx DOCX document
SOW Appendix B.pdf PDF
36C25722Q0849 0001_1.docx DOCX document
36C25722Q0849_1.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Deficiency Line Item #

Qty Manufacturer Model Number Description

1 2 Gems / Warrick 16MC1A0 Level Control, Relay, Module, 120 V, w/ Power Out, Base Included 2 1 Gems / Warrick 3E3B Holder, 2" NPT, Brass, 3 Probe 3 2 Rod, 1/4", Stainless Steel, 6 Ft

4 1 Conbraco H24‐351‐03 Gauge glass valve set, 1/2" NPT, 250 PSI, with ball checks & composit handle

5 6 Redline A328‐300 Gauge Glass, Tube, Redline, Heavy Wall, 5/8" diameter x 24" long 6 4 Halmar H98SSR Guard Rods, 304 Stainless Steel, 3/16" diameter x 24 " long

7 1 Ernst Flow Industries not sure ‐ call for help Flow Indicator, Window Type, Threaded Connection, 1" ‐ FOR 150 psi water/steam drain monitoring

8 1 Ernst Flow Industries not sure ‐ call for help External Sight protection windows for above flow indicators 9 20 Apollo 75‐101‐01 Valve, Ball, Locking, Bronze Pad, 1/4" NPT 10 20 not specified not specified Keyed Alike Standard Shackle Padlocks to fit the ball valves above 11 4 Automation Direct GCX1231‐120L LED indicating light, 22mm, red, metal base, 120 VAC/VDC, full voltage

12 4 Automation Direct GCX1232‐120L LED indicating light, 22mm, green, metal base, 120 VAC/VDC, full voltage

13 4 Automation Direct GCX1233‐120L LED indicating light, 22mm, yellow, metal base, 120 VAC/VDC, full voltage

14 4 Automation Direct GCX1234‐120L LED indicating light, 22mm, blue, metal base, 120 VAC/VDC, full voltage

15 4 Automation Direct GCX1235‐120L LED indicating light, 22mm, white, metal base, 120 VAC/VDC, full voltage

16 3 Automation Direct GCX1110 Pushbutton, 22mm, momentary, (1) N.O. contact, metal base, metal bezel, Operator: black, extended, 30mm, round, plastic;.

17 3 Automation Direct GCX1111 Pushbutton, 22mm, momentary, (1) N.C. contact, metal base, metal bezel, Operator: red, extended, 30mm, round, plastic;.

18 5 Automation Direct GCX1113 Pushbutton, 22mm, momentary, (1) N.O. contact, metal base, metal bezel, Operator: yellow, extended, 30mm, round, plastic;.

19 10 Automation Direct 782‐2C‐120A Relay, socket mount, 120 VAC coil voltage, DPDT, 15A contact rating, 8‐pin 20 10 Automation Direct 782‐2C‐SKT Relay socket, 35mm DIN rail or panel mount 21 1 Edwards Signaling 340‐6N5 Bell, Continuous Sound, 120V AC Voltage, Decibels: 92 dB, Color: Gray

22 1 Federal Signaling 350‐120‐30 Horn, Continuous Sound, 120V AC Voltage, Decibels: 100 dB, Color: Gray

23 3 Hoffman E1PBG Enclosure, Pushbutton, 1 Hole, 22.5mm, Steel, Gray,Type 12 Series 24 1 Kunkle unknown yet Safety relief valve, 2" inlet, set @ 140 psi, capacity TBD 25 1 Kunkle unknown yet Safety relief valve, 2" inlet, set @ 145 psi, capacity TBD

Install missing gas valve POC 26 1 ASCO H10B620B5F1F26 120vActuator w/AuxSw & Prf Cls

Install VA Compliant gas valves 27 2 Maxon unknown yet Main Gas Valves with VA Compliant POC Switches, 2‐1/2" body

Install low and high water alarm probes and probe relays.

Install low and high water alarm relays, lights, alarm horn, and alarm bell, shunt switches and silence buttons. Install Test Buttons for Current Relays

Wrong range safety relief valves

Repair low water level cutoff not visable in sight glass

Add proper test points

Appendix A

Install 2nd pilot gas valve 28 2 ASCO K3A652V Pilot Gas Valves, 3/4", Normally Closed, 120V Coil with test ports, 0‐5 psi

Install pilot vent valve 29 1 ASCO 8215G23 Pilot Vent Valve, 1/2", Normally Open, 120V Coil with test ports, 0‐125 psi

30 1 Fireye YB110UVSC Flame Safeguard, Chassis with UV Self Check Aplifier, 120v 31 1 Fireye 45UV5‐1009 Scanner, UV Selfcheck, 8' leads, 1" NPT.

32 1 Fireye YP100 Programmer, non‐recycle, modulation, open damper proving, 4 second FFRT

33 1 Fireye BLV512 Display, 2 line X 16 characters, VFD, with cable, NEMA 4 34 1 Fireye 60‐2814‐1 Wiring base, open with terminal block, 4"W x 7"H

35 1 Fireye 129‐178‐8 Kit, remote mounting, BurnerLogix display, 8 ft. cable, NEMA 4 protection

36 1 Fireye YZ300 Interlock Annunciator Module, used with YB110 chassis/amplifier, 120 VAC

37 1 Fireye 60‐2874‐1 Wiring base, terminal blocks, open end 38 1 Fireye ED580‐4 YB110 to YZ300 interconnection cable in 4' length

Install damper position switches 39 5 Pepperl+Fuchs NBB2‐F1‐US Inductive Proximity Sensors, two wire

Install purge airflow switch 40 1 Cleveland Controls AFS‐222 Air Flow Switch, .05"‐12.0"w.c., 120V, SPDT Contact, 1/2 Psi Max Pressure

Install blower motor CT's 41 3 AcuAmp ACSL050‐AE‐S Current switch, split core, 0‐150A sensing range, 20‐50A adjustable trip point

Install pilot low gas switch 42 1 Honeywell C6097A3012 Switch, low gas, 1‐20", Break On Fall, Manual Reset, 1/4" NPT 43 1 Hays‐Cleveland A10050‐A0‐A04‐Z00 Oxygen Analyzer Electronics for use with A‐08562 Mini‐O2 Probe

44 1 Hays‐Cleveland A‐08562‐A0‐B01‐C00‐D01‐E01 Mini‐O2 Probe, complete with 20ft pre‐wired cable and 18” traverse tube

45 1 Fulflo VJ‐4R/HS/XS Oil relief valve, standard, V‐series, CI, screw connections, 3/4", BUNA, harden steel, 60‐175 psi yellow spring

46 1 Ernst Flow Industries EFI E‐57‐3 Flow Indicator, Window Type, Threaded Connection, 3/4" ‐ FOR OIL SERVICE

Install proper valves with POC 47 2 Siemens Combustion VOG15.011U1 Oil shutoff valve, 3/4", with proof of closure switch

Totals

Install proper UV Selfcheck Flame Supervision and Annunciator System

Install oil relief valve

Install low O2 Monitor

File details come from the government source that posted it. Updated .