S06_504-19-106_Drawing Addendum 1.pdf
PDF 9 MB Posted
- Attached to
- Y1DB--504-19-106 Renovate Clinical Lab for Modernization (Construction) (VA-22-00043821)
- Solicitation number
- 36C25722B0016
About this file
This solicitation is for a construction project to renovate a clinical lab for modernization at the Amarillo VA Medical Center in Amarillo, Texas. Key details include renovating the existing lab space and constructing a temporary modular lab building. The solicitation requires demolition, mechanical, plumbing and electrical work. The estimated award value is $6 million. The performance period is 480 calendar days. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17. The response due date is July 25, 2022.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
750 W Hampden Ave, Suite #300
Englewood, CO 80110
Ph (720) 550-6307 www.ValhallaEngineering.com
ADDENDUM NO. 1
TO THE DRAWINGS AND SPECIFICATIONS FOR:
Renovate Clinical Lab for Modernization VAMC Project #504-19-106
AMARILLO VA MEDICAL CENTER
Amarillo, TX
July 14, 2022
I. GENERAL
A. This narrative addendum supplements and revises the drawings and specifications dated 02/03/2022, as noted within and shall become part of the contract documents.
B. Proposers shall acknowledge receipt of this addendum in the space provided on the proposal form. Failure to do so may subject proposer to disqualification.
C. Each holder of proposal documents registered with the construction manager will receive a copy of the addendum. Each prime proposer is responsible for distribution of information conveyed by this addendum to its sub-proposers and suppliers.
II. DESCRIPTION
A. Clarifications of lab equipment mechanical connections: Refer to revised sheet MQ601.
B. NFPA45 lab exhaust controls clarifications: Refer to revised sheet MI701 and MI702.
C. Clarifications of flexible shaft wrapping for exhaust ducts: Refer to revised sheet
MH112B.
D. Additional incubator and revised analyzer equipment in Temporary Lab, with associated revised plumbing, HVAC air quantities, and power provisions. Refer to revised drawings attached.
E. Additional lab air connections to analyzers. Refer to attached drawings.
F. Clarifications of lab equipment plumbing connections and water closet fixture tag: Refer to revised sheet PQ601.
G. Plumbing fixture mounting heights: revise specification 22 40 00 to mount fixtures at height per sheet GI003.
H. Additional blocking and power+data rough-ins for wall-mount televisions. Refer to attached revised drawings.
http://www.valhallaengineering.com/
I. Engineering Document Management Software (EDMS) requirements:
• Contractor shall provide the EDMS for the construction phase of the project.
• EDMS shall be web-based and accessible to project members as recommended and approved by the VHA COR.
• EDMS shall have separate portals for submitting construction RFIs, submittals, and other project documents as requested by the VHA COR.
• EDMS file portals shall have the capability to:
• Upload files up to 100MB
• Assign files to one or multiple project members for review and action by a stipulated due date, agreeable to all parties and per the contract documents.
• Reassign files as determined by assignees
• Update disposition of files by assignee such as reviewed, approved, rejected, etc
• Track dates and times of uploads, revisions, assignments, re-assignments, and reviews.
• Manage project submittals and RFIs through the EDMS. Strike references to email submissions thereof from the contract documents.
III. ATTACHMENTS
A. Revised Clouded Drawing Sheets:
• AE121A
• AE122B
• AE151A
• AE152B
• AE411B
• PQ601
• PG112B
• PP112A
• PW112A
• MQ601
• MI701
• MI702
• MH112A
• MH112B
• MP112A
• EP111A
• EP112B
• EP601
• ET112B
END ADDENDUM NARRATIVE
OS
OS
OS OS
3 3.2 4 5 6
B
C
D
E
F
8' - 0"
2263A
TEMP MULTI-LAB
8' - 0"
MECHANICAL
STORAGE
FOOD STORAGE
KITCHEN
2231A
HAC
ELECTRICAL
C1-5
CORRIDOR
TEMP LAB STORAGE
4' - 6" 6' - 11"
5'
6'
6'
6'
6'
6'
5'
2'
3'
1'
4' - 5" 6' - 6" 6' - 0" 6' - 0" 6' - 0"
1' - 0"
8' - 6"
8' - 6"
8' - 6"
STORAGE / FLEX
TEMP HISTOLOGY
TEMP HISTOLOGY
TEMP
MICROBIOLOGY
WORKSTATION
WORKSTATION
UNISEX RR
WORKSTATION
FIRE RISER
1. ALL CEILING HEIGHTS ARE AT 9'-0" AFF UNO.
CEILING HEIGHT
SUPPLY
RETURN / EXHAUST
TYPICAL LIGHT FIXTURE
SIZE VARIES
9'-0"
REFLECTED CEILING PLAN SYMBOLS LEGEND
OS
LINEAR PENDANT LIGHT
INDUSTRIAL STRIP LIGHT
CAN LIGHTACCESS PANEL
OCCUPANCY SENSOR
FIRE EXIT SIGN
SPRINKLER HEAD
S H E I L
A
F . HO
O T E N
S T A
T E
OF T
E
X A S
R E G
IS
TE
RED ARCH
IT
E C T
S H E I
LA
F . HO
O T E N
8 9 9
##KEYNOTES
KEY PLAN
GENERAL NOTES
P la n N or th
Tru e N or th
ORIG HOSP 1
W A
LK
E
R B
LV
D
W A
LK
E
R B
LV
D
WALKER BLVD
MAIN
HOSP 28
MED
ARTS
CLC
CLC
WALKER BLVD
LAB
MODULAR LAB
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
JUL 14, 2022
C :\U se rs
\V . A rc hi te ct
7\
D oc um en ts \2
1.
_A R
C H
_R
_p sa nd er s@ va lh al la en gi ne er in g.
co m .r vt 7/
/2
2:
:2
P M
AE121A
REFLECTED CEILING PLANS -
(INTERIM)
RENOVATE CLINICAL LAB FOR
MODERNIZATION
6010 W AMARILLO BLVD, AMARILLO, TX 79106
504-19-106
02/03/2022 SH PS
100% FINAL BID
DOCUMENTS
VEG 21.15
32'16'8'4'2'0'
P la n N or th
Tru e N or th
1/8" = 1'-0"
SECOND FLOOR RCP (INTERIM)
32'16'8'4'2'0'
P la n N or th
T ru e N or th
1/8" = 1'-0"
MODULAR BUILDING RCP (INTERIM)
1. EXHAUST HOOD
0 100% CONSTRUCTION DOCUMENTS 02/03/2022
1 ADDENDUM 1 07/14/2022
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS OS
OS
OS
OS
OS
OS
OS
OS OS OS
OS
OS OS OS OS
OS OS
OS
OS
OS
OS
OS
OS
3 3.2 4 5 6 7 8 9 10 10.3
B
C
D
E
F
2259 2257
2231A 2263
C1-4
22622260
2255E
2255F 2255
2255C
2255B 2255A
22402251B
C1-6
2239A 2221
2235 2234
2256A
2251A
2251C
2252B
2252A
C1-7
2238A
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
STAIR 3
STAIR 5
P-2
ELEV
P-1
ELEV
S-1
ELEV
STAIR 2
AE611
AE521B
TYP
AE521B
TYP
AE521B
TYP
AE521B
TYP
7' - 6"
8' - 6"
8' - 6"
8' - 6"
6'
5'
5'
8' - 0" 8' - 0" 6' - 10"
6' - 0" 6' - 0" 6' - 10"
2' - 10"
1'
3'
6' - 4"
5' - 1"
TYP
6' - 0"
TYP
6' - 0"
TYP
6' - 11"
4'
2'
7'
7'
4'
2' - 7"
8' - 0" 8' - 0" 8' - 0" 8' - 0" 8' - 0" 8' - 0" 8' - 0" 8' - 0" 8' - 0"
8'
8'
8'
4'
1"
8' - 0" 8' - 0"
5' - 11"
6'
6'
"2'
2'
0"
1'
6' - 0" 3' - 5"
7'
5' - 5" 6' - 0" 8' - 0"
1. ALL CEILING HEIGHTS ARE AT 9'-0" AFF UNO.
CEILING HEIGHT
SUPPLY
RETURN / EXHAUST
TYPICAL LIGHT FIXTURE
SIZE VARIES
9'-0"
REFLECTED CEILING PLAN SYMBOLS LEGEND
OS
LINEAR PENDANT LIGHT
INDUSTRIAL STRIP LIGHT
CAN LIGHTACCESS PANEL
OCCUPANCY SENSOR
FIRE EXIT SIGN
SPRINKLER HEAD
S H E I L
A
F . HO
O T E N
S T A
T E
OF T
E
X A S
R E G
IS
TE
RED ARCH
IT
E C T
S H E I
LA
F . HO
O T E N
8 9 9
##KEYNOTES
KEY PLAN
GENERAL NOTES
P la n N or th
Tru e N or th
ORIG HOSP 1
W A
LK
E
R B
LV
D
W A
LK
E
R B
LV
D
WALKER BLVD
MAIN
HOSP 28
MED
ARTS
CLC
CLC
WALKER BLVD
LAB
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
JUL 14, 2022
C :\U se rs
\V . A rc hi te ct
7\
D oc um en ts \2
1.
_A R
C H
_R
_p sa nd er s@ va lh al la en gi ne er in g.
co m .r vt 7/
/2
2:
:2
P M
AE122B
REFLECTED CEILING PLAN -
SECOND FLOOR (FINAL)
RENOVATE CLINICAL LAB FOR
MODERNIZATION
6010 W AMARILLO BLVD, AMARILLO, TX 79106
504-19-106
02/03/2022 SH PS
100% FINAL BID
DOCUMENTS
VEG 21.15
32'16'8'4'2'0'
P la n N or th
Tru e N or th
1/8" = 1'-0"
SECOND FLOOR NEW RCP
1. EXHAUST HOOD (NEW)
ROOM NUMBER KEY
NUMBER ROOM NAME
2221 BARBER SHOP
2225 MEN'S RR
2227 VENDING
2231 KITCHEN
2231A HAC
2234 MECHANICAL
2235 FLAMMABLE STORAGE
2236 MICROBIOLOGY
2237 LOCKERS
2238 STAFF TOILET
2238A STAFF TOILET
2239 HISTOLOGY
2239A GROSS SPECIMEN
2240 PATHOLOGIST
2241 LAB TECH OFFICE
2242 SUPERVISOR
2243 HAC
2244 CUBICLE OFFICE
2245 PREFAB MORTUARY
2246 TELE
2247 STORAGE
2248 ELECTRICAL
2249 STORAGE
2250 ELECTRICAL
2251A RECEPTION
2251B MED RECORDS
2251C STORAGE
2252 BLOOD COLLECTION
2252A RESTROOM
2252B RESTROOM
2253 PHLEB OFFICE
2254 CHIEF
2255 LABORATORY
2255A LAB TECH
2255B ACCESSIONING
2255C REFRIG STORAGE
2255D BLOOD BANK
2255E MULTIPURPOSE CONF RM
2255F EMPL URINE
2256 STORAGE
2256A REFUSE STORAGE
2257 STORAGE
2258 HAC
2259 MECHANICAL
2260 TELE
2261 CANTEEN STORAGE
2262 ELECTRICAL
2263 CANTEEN OFFICE
2264 FOOD STORAGE
2267 STORAGE CLOSET
C1-4 CORRIDOR
C1-5 CORRIDOR
C1-6 CORRIDOR
C1-7 CORRIDOR
0 100% CONSTRUCTION DOCUMENTS 02/03/2022
1 ADDENDUM 1 07/14/2022
3 3.2 4 5 6
B
C
D
E
F
MECHANICAL
STORAGE
FOOD STORAGE
KITCHEN
2231A
HAC
ELECTRICAL
C1-5
CORRIDOR
C1-4
CORRIDOR
2263A
TEMP MULTI-LAB
TEMP LAB STORAGE
67 64
LOCKERS, REF SPECS
143136
STORAGE / FLEX
TEMP HISTOLOGY
TEMP HISTOLOGY
TEMP
MICROBIOLOGY
WORKSTATION
WORKSTATION 0009
UNISEX RR
WORKSTATION
AE211A 7AE211A6
AE211A3 2
11864119
109 109
66 66
150149
FIRE RISER
1. ALL EQUIPMENT IS GF/GI (GOV. FURNISHED, GOV. INSTALLED), UNLESS
OTHERWISE NOTED.
2. ANY FFE ITEMS NOT TAGGED AND SCHEDULED ARE COUNTERTOPS,
CASEWORK, OR FURNITURE.
3. ALL FURNITURE IS GF/GI.
S H E I L
A
F . HO
O T E N
S T A
T E
OF T
E
X A S
R E G
IS
TE
RED ARCH
IT
E C T
S H E I
LA
F . HO
O T E N
8 9 9
##KEYNOTES
KEY PLAN
GENERAL NOTES
P la n N or th
Tru e N or th
ORIG HOSP 1
W A
LK
E
R B
LV
D
W A
LK
E
R B
LV
D
WALKER BLVD
MAIN
HOSP 28
MED
ARTS
CLC
CLC
WALKER BLVD
LAB
MODULAR LAB
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
JUL 14, 2022
C :\U se rs
\V . A rc hi te ct
7\
D oc um en ts \2
1.
_A R
C H
_R
_p sa nd er s@ va lh al la en gi ne er in g.
co m .r vt 7/
/2
2:
:2
P M
AE151A
EQUIPMENT PLANS - (INTERIM) RENOVATE CLINICAL LAB FOR
MODERNIZATION
6010 W AMARILLO BLVD, AMARILLO, TX 79106
504-19-106
02/03/2022 SH PS
100% FINAL BID
DOCUMENTS
VEG 21.15
32'16'8'4'2'0'
P la n N or th
Tru e N or th
1/8" = 1'-0"
SECOND FLOOR EQUIPMENT PLAN (INTERIM)
32'16'8'4'2'0'
P la n N or th
T ru e N or th
1/8" = 1'-0"
MODULAR BUILDING EQUIPMENT PLAN (INTERIM)
INTERIM EQUIPMENT SCHEDULE
ITEM # ITEM DESCRIPTION
53 Printer, Microbiology
54 Sink Station
55 Gene Analyzer
56 Gene Analyzer
57 Microscope
60 Biohazard Rectangle
62 Biohazard Safety Cabinet
63 Sofia
64 Refrigerator
65 Refrigerator
66 Refrigerator
67 Freezer
80 Bio Safety Cabinet (CFCI)
90 Laboratory Exhaust Hood (CFCI)
100 Specimen Drop Off
101 Biohazard Rectangle
102 Printer
103 MS Analyzer
104 Stainer
105 MD Viewer
106 Co2 Tank
107 Stryker Saw and Console
108 Grossing Station
109 Cryostat
110 Cover Slipper
INTERIM EQUIPMENT SCHEDULE
ITEM # ITEM DESCRIPTION
1 Pneumatic Centrifuge
4 Toso
5 Hematology Analyzer
6 Slide Stainer
7 Slide Drawers
8 Microscope
9 Sedrate
10 Auto Urine Analyzer
11 Blood Coagulation Analyzer
12 Avantus Urine Analyzer
13 Centrifuge, Electric Only
14 Centrifuge
15 Osometer
16 Blood Gas Analyzer
22 Refrigerator
23 UC Freezer
24 Water Filter
28 Platelet
29 Label Printer
30 Plasma Thawer
31 Agglutination Viewer
32 Washer
33 Scale
34 Heat Block
52 Veritor
INTERIM EQUIPMENT SCHEDULE
ITEM # ITEM DESCRIPTION
111 Slide Stainer
112 IHC
113 Special Stainer
114 New IHC
116 Embedding Station
117 Processor
118 Processor
119 Storo Cart
120 Wax Dispenser
121 BD Proc
122 Printer
123 Incubator Scale
124 Incubator Scale
125 Incubator Scale
126 Incubator
127 Incubator
136 DxC700 AU
140 Diasorin Liaison XL
143 DXL
148 Slide Stainer
149 Microtome
150 Cold Plate
151 Water Bath
152 Abbott M2000 & Accessory
153 Abbott M2000 & Accessory
154 Biofire
155 Incubator, Bacteriology
167 Lockers - 12x12x48 (CFCI)
168 Incubator
169 Incubator
0 100% CONSTRUCTION DOCUMENTS 02/03/2022
UP
3 3.2 4 5 6 7 8 9 10 10.3
B
C
D
E
F
MECHANICAL
STORAGE
2255F
EMPL URINE
2255E
MULTIPURPOSE
CONF RM
HAC
STORAGE
FOOD
STORAGE
KITCHEN
2231A
HAC
CANTEEN
OFFICE
ELECTRICAL
STORAGE
VENDING 2246
TELE 2243
HAC
MEN'S RR
2239A
GROSS
SPECIMEN
BARBER
SHOP
HISTOLOGY
2238A
STAFF
TOILET
MICROBIOLOGY
MECHANICAL
FLAMMABLE
STORAGE
TELE
ELECTRICAL
2252A
RESTROOM
2255C
REFRIG
STORAGE 2255B
ACCESSIONING
2255A
LAB TECH
CHIEF
SUPERVISOR
PATHOLOGIST
2251B
MED RECORDS
BLOOD
COLLECTION
PHLEB OFFICE
2252B
RESTROOM
C1-4
CORRIDOR
C1-7
CORRIDOR
C1-6
CORRIDOR
2251A
RECEPTION
LAB TECH OFFICE
LOCKERS
STAFF
TOILET
2256A
REFUSE STORAGE
CUBICLE OFFICE
C
S T
O R
A G
E
39 39
40 40 40
44 44
40 49
68 69
144 145 146
143142141143142
136 136 136
137 91
138 139 140
66 66 65
119 64 118 117
STAIR 3
STAIR 5
P-2
ELEV
P-1
ELEV
S-1
ELEV
STAIR 2
LABORATORY
51 51 51
50 50 50
133 132 61
166 166
166 166
166166
150151
134 (U/C)
1 1
0 0
1. ALL EQUIPMENT IS GF/GI (GOV. FURNISHED, GOV. INSTALLED), UNLESS
OTHERWISE NOTED.
2. ANY FFE ITEMS NOT TAGGED AND SCHEDULED ARE COUNTERTOPS,
CASEWORK, OR FURNITURE.
3. ALL FURNITURE IS GF/GI.
S H E I L
A
F . HO
O T E N
S T A
T E
OF T
E
X A S
R E G
IS
TE
RED ARCH
IT
E C T
S H E I
LA
F . HO
O T E N
8 9 9
##KEYNOTES
KEY PLAN
GENERAL NOTES
P la n N or th
Tru e N or th
ORIG HOSP 1
W A
LK
E
R B
LV
D
W A
LK
E
R B
LV
D
WALKER BLVD
MAIN
HOSP 28
MED
ARTS
CLC
CLC
WALKER BLVD
LAB
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
JUL 14, 2022
C :\U se rs
\V . A rc hi te ct
7\
D oc um en ts \2
1.
_A R
C H
_R
_p sa nd er s@ va lh al la en gi ne er in g.
co m .r vt 7/
/2
2:
:3
P M
AE152B
EQUIPMENT PLAN - SECOND
FLOOR (FINAL)
RENOVATE CLINICAL LAB FOR
MODERNIZATION
6010 W AMARILLO BLVD, AMARILLO, TX 79106
504-19-106
02/03/2022 SH PS
100% FINAL BID
DOCUMENTS
VEG 21.15
32'16'8'4'2'0'
P la n N or th
Tru e N or th
1/8" = 1'-0"
EQUIPMENT PLAN - SECOND FLOOR (FINAL)
FINAL EQUIPMENT SCHEDULE
ITEM # ITEM DESCRIPTION
2 Centrifuge, Large
4 Toso
8 Microscope
14 Centrifuge
22 Refrigerator
29 Label Printer
31 Agglutination Viewer
33 Scale
39 Shelving (CFCI)
40 Shelving (CFCI)
41 Shelving (CFCI)
42 Lab Slides
43 Closet
44 Cart
45 Medical Palette
46 Biohazard
47 Closet
48 Cabinet
49 Dolly
FINAL EQUIPMENT SCHEDULE
ITEM # ITEM DESCRIPTION
50 Blood Draw
51 Blood Draw
55 Gene Analyzer
56 Gene Analyzer
60 Biohazard Rectangle
61 Scanner Printer
64 Refrigerator
65 Refrigerator
66 Refrigerator
67 Freezer
68 Barcode Printer
69 Printer
70 P Thawer
71 T.Bath
72 Analysis Viewer
73 Incubator, P
74 Cell Washer
75 Microscope
76 Blood Bank Ref
FINAL EQUIPMENT SCHEDULE
ITEM # ITEM DESCRIPTION
80 Bio Safety Cabinet (CFCI)
90 Laboratory Exhaust Hood (CFCI)
91 Iris Urinalysis
92 Iris UA Computer
100 Specimen Drop Off
101 Biohazard Rectangle
102 Printer
103 MS Analyzer
104 Stainer
105 MD Viewer
106 Co2 Tank
107 Stryker Saw and Console
108 Grossing Station
109 Cryostat
110 Cover Slipper
111 Slide Stainer
112 IHC
113 Special Stainer
114 New IHC
FINAL EQUIPMENT SCHEDULE
ITEM # ITEM DESCRIPTION
116 Embedding Station
117 Processor
118 Processor
119 Storo Cart
120 Wax Dispenser
121 BD Proc
122 Printer
123 Incubator Scale
124 Incubator Scale
125 Incubator Scale
126 Incubator
127 Incubator
128 Calculator
129 Money Scale
130 Money Machine
131 Safe
132 Copy Printer
133 Network Printer
134 Dishwasher (CFCI)
FINAL EQUIPMENT SCHEDULE
ITEM # ITEM DESCRIPTION
135 Refrigerator w/ Ice and Water Disp
136 DxC700 AU
137 DxH900
138 AUTOMATION POWER Output C25994
139 Storage 6.5k
140 Diasorin Liaison XL
141 DXL CONSOLE
142 DXL PRINTER
143 DXL
144 DUAL CENTRIFUGE
145 AUTOMATION POWER INPUT
146 DxA Server Console B62967
147 AUTOMATION LINE
148 Slide Stainer
149 Microtome
150 Cold Plate
151 Water Bath
152 Abbott M2000 & Accessory
153 Abbott M2000 & Accessory
166 Shelving (CFCI)
167 Lockers - 12x12x48 (CFCI)
0 100% CONSTRUCTION DOCUMENTS 02/03/2022
1. PROVIDE BLOCKING FOR TV MOUNT AS REQ'D. VERIFY FINAL LOCATION
WITH COR.
T
T
UP
D
A
B
2252A
RESTROOM
2252B
RESTROOM
1'
T Y
P
1'
1'
S1
A4
9'
/4
F3
F3
A3
A3
A3
7' - 0 3/4"
7' - 10"1' - 2"
F3
F3
1' - 6"
S1
AE211B
AE601
A4
2'
/4
AE211B7
3' - 8" CLR. 3' - 8" CLR.
2238A2238
2238A
STAFF TOILET
STAFF TOILET
A3
F3F3 F3F3
A3A3
A1
A3
2'
3' - 10" 3' - 11"
A3 A3
E3'
1'
1"
7' - 0"
5' - 0"
A4
A4 A4
A1
A1
A1
D
2' - 0"
1'
2' - 9 1/2"
5'
/8
3'
/8
2'
3' - 0" ø 5' - 6"
A1A1 A1
A1
A3
A3 A3 A3
F2
A1
F2
F2
E
AE211B
AE431B
AE431B
2'
2'
0"
8" 2' - 0" 3' - 9"
4" 8"
4" 8"
F1
F1
F1
EXIST CONC. ROOF SLAB
EXIST TAPERED INSULATION
EXIST ROOFING MEMBRANE;
CONTRACTOR TO VIF CONDITIONS
BUILT-UP TREATED 2X6 WOOD CURB TO
HEIGHT OF (E) TAPERED INSULATION
SELF-ADHERED ROOFING MEMBRANE; LAP UP
& OVER CURB ASSEMBLY
REPLACE RIGID INSULATION AS REQ.
SHEET MTL CAP FLASHING
SEALANT, EA SIDE
6" COLD-FORMED METAL FRAMED MECHANICAL
CURB; LAG-BOLT TO T.O. WOOD CURB
ANCHOR-BOLT TO (E) CONC. SLAB;
3/8" ANCHOR BOLT, MIN. 3" PENETRATION
5/8" GYP EXTERIOR SHEATHING;
EA. SIDE
SPLICE & LAP NEW SELF-ADHERED ROOFING
MEMBRANE OVER EXISTING ROOF MEMBRANE
NOTE: COORDINATE WITH
MECHANICAL ROOF PLAN FOR
LOCATIONS
1'
AE211B15 16
6'
1/ 2"
6'
1/ 2"
2' - 4"2' - 4"
36" RAMP
RE: MECH
2" MIN. AIR GAP
FLOOR SLAB
6 MIL POLYETHYLENE
FLOOR MEMBRANE
COLD STORAGE DOOR;
RE: MNFR
COLD STORAGE WALL;
RE: MNFR
COLD STORAGE FLOOR;
RE: MNFR
PREPARE EXIST CONC FLOOR
& WATERPROOF PER
COLD STORAGE MNFR
SCHEDULED WALL;
RE: PLAN
RE: PLAN
3'
SCHEDULED WALL;
RE: PLAN
COORDINATE WALL
OPENING FOR DOOR W/
COLD STORAGE MNFR
R E
: M E
C H
2" M
IN
. A
IR
G
A P
RE: MECH
2" MIN. AIR GAP
6" LAY-IN INSULATION
WALL (BEYOND);
RE: PLAN
1. ALL TOILET ACCESSORIES ARE VA-FURNISHED, VA-INSTALLED.
2. ALL WALLS SURROUNDING TOILET ROOMS TO RECEIVE SOUND BATT
INSULATION TO ACHEIVE MIN. 45 STC.
D
CLR
12' - 7"
C
LR
CLR
9' - 11"
C
LR
4'
RE: WALK-IN COOLER MNFR
AE411B
S H E I L
A
F . HO
O T E N
S T A
T E
OF T
E
X A S
R E G
IS
TE
RED ARCH
IT
E C T
S H E I
LA
F . HO
O T E N
8 9 9
##KEYNOTES
KEY PLAN
GENERAL NOTES
P la n N or th
Tru e N or th
ORIG HOSP 1
W A
LK
E
R B
LV
D
W A
LK
E
R B
LV
D
WALKER BLVD
MAIN
HOSP 28
MED
ARTS
CLC
CLC
WALKER BLVD
LAB
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
JUL 14, 2022
C :\U se rs
\V . A rc hi te ct
7\
D oc um en ts \2
1.
_A R
C H
_R
_p sa nd er s@ va lh al la en gi ne er in g.
co m .r vt 7/
/2
2:
:3
P M
AE411B
ENLARGED PLANS AND DETAILS -
(FINAL)
RENOVATE CLINICAL LAB FOR
MODERNIZATION
6010 W AMARILLO BLVD, AMARILLO, TX 79106
504-19-106
02/03/2022 SH PS
100% FINAL BID
DOCUMENTS
VEG 21.15
1. FILLER AT EACH END OF LOCKERS
2. ABAAS-COMPLIANT FIXED LOCKER ROOM BENCH - VA FURNISHED, VA
INSTALLED
3. LOCKERS - VA FURNISHED, VA INSTALLED
4. PAPER TOWEL DISPENSER / DISPOSAL
5. COAT HOOK
6. ACCESSIBLE MIRROR
7. SOAP DISPENSER
8. ABAAS GRAB BAR
9. SEAT COVER DISPENSER
10. TOILET PAPER DISPENSER
11. SANITARY DISPOSAL
3/8" = 1'-0"
ENLARGED PT RESTROOM
3/8" = 1'-0"
ENLARGED STAFF RESTROOM
3/8" = 1'-0"
ENLARGED PLAN - BLOOD COLLECTION ENTRY
3/8" = 1'-0"
ENLARGED VIEW - LOCKER ROOM
3/8" = 1'-0"
RECEPTION WEST
1 1/2" = 1'-0"
DETAIL - ROOF CURB
3/8" = 1'-0"
ENLARGED VIEW - CUBICLES
1 1/2" = 1'-0"
SECTION - WALK-IN COOLER ENCLOSURE
3/8" = 1'-0"
ENLARGED VIEW - WALK-IN COOLER ENCLOSURE
1 ADDENDUM 1 07/14/2022
0 100% CONSTRUCTION DOCUMENTS 02/03/20221 ADDENDUM 1 07/14/2022
0 100% CONSTRUCTION DOCUMENTS 02/03/2022
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
NOT FOR
CONSTRUCTION
Date:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\V . M
. E . 1
9\ D oc um en ts
\2 1.
_M
E C
H _P
LU
M
_R
_m bi bl e2
H X
D 7.
rv t
7/
/2
2:
:3
P
M
PQ601
EQUIPMENT AND FIXTURE
SCHEDULES
RENOVATE CLINICAL LAB FOR
MODERNIZATION
6010 W AMARILLO BLVD, AMARILLO, TX 79106
504-19-106
02/03/2022 MB RL
100% FINAL BID
DOCUMENTS
VEG 21.15
PLUMBING FIXTURE SCHEDULE
MARK DESCRIPTION
CW CONNECTION
(IN)
HW CONNECTION
(IN)
WASTE
CONNECTION (IN)
VENT CONNECTION
(IN)
REMARKS
FD-J LAB FLUSHING DRAIN 3/4 - 3 2 1
FD-T LAB FUNNEL DRAIN - - 3 2 1
FD-W OPEN SIGHT HUB DRAIN - - 2 2 1
FD-X LAB GENERAL DRAIN - - 3 2 1
P-107 WATER CLOSET 1 - 4 2 1
P-408 LAVATORY, WALL MOUNT 1/2 1/2 1 1/2 1 1/2 1
P-517 SINK, SS, TWO-COMPARTMENT, FREE STANDING 1/2 1/2 1 1/2 1 1/2 1
P-524 SINK, SS, TWO-COMPARTMENT, COUNTER MOUNT 1/2 1/2 1 1/2 1 1/2 1
P-526 SINK, COUNTER-MOUNTED,DI, DEEP 1/2 1/2 1 1/2 1 1/2 1,3
P-528 HAND SINK, COUNTER-MOUNTED 1/2 1/2 1 1/2 1 1/2 1
P-529 SINK, DI 1/2 1/2 1 1/2 1 1/2 1,3
P-605 BOTTLE FILLING STATION, REFRIGERATED 1/2 - 1 1/2 1 1/2 1
P-707 COMBINATION EMERGENCY SHOWER AND EYE WASH 1 1/4 1 1/4 1 1/2 1 1/2 1
P-708 EMERGENCY EYE WASH 3/4 3/4 1 1/2 1 1/2 1
P-807 REAGENT WATER GRADE FAUCET 1/2 - - - 1,2
P-812 WATER SUPPLY BOX UNIT 1/2 - - - 1
P-M1 SAME AS P-408
P-M2 SAME AS P-107
SCHEDULE REMARKS:
1. REFER ALSO TO SPECIFICATIONS
22 40 00 AND 22 13 00.
2. SCHEDULED CW CONNECTION IS
RW.
3. SCHEDULED CW CONNECTION IS
BOTH DCW AND RW.
SCHEDULE REMARKS:
1. ONLY EQUIPMENT REQUIRING
PLUMBING PROVISIONS ARE
SCHEDULED HERE. REFER TO
ARCHITECTURAL FOR DETAILED
EQUIPMENT REQUIREMENTS AND
FOR REMAINING EQUIPMENT
DESCRIPTIONS.
0 100% FINAL BID DOCUMENTS 02/03/2022
1 ADDENDUM 1 07/14/2022
LAB EQUIPMENT PLUMBING CONNECTION SCHEDULE
EQUIPMENT
MARK DESCRIPTION BASIS OF DESIGN
DCW RW
FD &
SS CRP
LAB GASES
REMARKS
CONNECTION
(IN)
CONNECTION
(IN) TYPES
CONNECTION
(IN)
1 PNEUMATIC CENTRIFUGE
(E) BECKMAN COULTER AIR
ULTRACENTRIFUGE
- - - LA,LV 1/2,3/4 1
10 AUTO URINE ANALYZER (E) ICHEM VELOCITY 700-7177-001 - - YES - - 1
19 COBAS (E) COBAS 8000 & GWT WATER FILTER - 1/2 YES - - 1
21 CHEMISTRY ANALYZER (E) BECKMAN COULTER DXI 600 REF EQ-88 1/2 YES - - 1
24 WATER FILTER (E) ELGA LA621 1/2 - - - - 1
62 MOBILE FUME HOOD (E) PURAIR PCR-24 1/2 1/2 YES - - 1
80 BIO SAFETY CABINET (HOOD) REF 11 53 53 1/2 1/2 YES LA,LV,N,O 1/2,3/4,1/2,1/2 1
90 FUME HOOD WITH CUP SINK REF 11 53 13 1/2 1/2
YES, 1-1/2" INDIRECT DRAIN
FROM CUP SINK THERETO
LA,LV,N,O 1/2,3/4,1/2,1/2 1
91 IRIS URINALYSIS (E) ICHEM VELOCITY 700-7177-001 - - YES - - 1
108 GROSSING STATION (E) MOPEC 1/2 - - - - 1
111 SLIDE STAINER (E) HOLOGIC THINPREP 2000 1/2 - YES - - 1
134 DISHWASHER TBD 1/2 - - - - 1
135 REFRIGERATOR TBD 1/2 - - - - 1
136 CHEMISTRY ANALYZER - AUTOMATED BECKMAN COULTER DXC700AU OR EQUAL 1/2 1/2 YES - - 1
137 AUTOMATION - DXH900 BECKMAN COULTER DXH900 OR EQUAL - - YES - - 1
139 AUTOMATION - STORAGE BECKMAN COULTER STORAGE OR EQUAL - - YES - - 1
140 AUTOMATION - LIASON UTILITIES
BECKMAN COULTER LIASON UTILITY OR
EQUAL
- - YES - - 1
143 AUTOMATION - DXL BECKMAN COULTER DXL OR EQUAL - - YES - - 1
3 3.2 4 5 6 7 8 9 10 10.3
B
C
D
E
F
C1-5
2255E
2255F
2255D
2256A
2231A
C1-4
2252A
2252B
2255C 2255B
C1-7
2225 2239A 2221
C1-6
2251B
2251C 2251A
2255A
2238 2238A
1/ 2" ø N
1/ 2" ø O
3/4"ø LA
3/4"ø LV
1/2"ø N
1/2"ø O
3/4"ø LA 3/4"ø LV
3/4"ø LA 3/4"ø LV
1/2"ø N 1/2"ø O
3/4"ø LA 3/4"ø LV
1/2"ø N 1/2"ø O
1/2"ø O
1/2"ø N
3/4"ø LV
3/4"ø LA
3/ 4" ø L
V
3/ 4" ø L
A
1/2"ø O
1/2"ø N
3/4"ø LV
3/4"ø LA3
1/ 2" ø O
1/ 2" ø N
3/ 4" ø L
V
3/ 4" ø L
A
3/4"ø LV
3/4"ø LA
STAIR 5
S-1
ELEV
P-1
ELEV
P-2
ELEV
STAIR 3
STAIR 2
3/ 4" ø L
A
3/ 4" ø L
V
A. REFER TO P-001 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL
NOTES.
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO GI SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
D. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT
PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING
HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED.
ABATEMENT WILL BE PERFORMED BY THE VHA OUTSIDE OF THIS CONTRACT.
E. REFER TO GC SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.
F. WATER AND MED GAS HORIZONTAL PIPING IS ABOVE THE CEILING UNO.
SANITARY SEWER AND STORM DRAINAGE HORIZONTAL PIPING IS UNDER
FLOOR UNO. VENT HORIZONTAL PIPING IS ABOVE CEILING UNO. REFER TO
GC111 FOR RATED CONSTRUCTION ON FIRST FLOOR.
##KEYNOTES
KEY PLAN
GENERAL NOTES
P la n N or th
Tru e
Nor th
ORIG HOSP 1
W A
LK
E
R B
LV
D
W A
LK
E
R B
LV
D
WALKER BLVD
MAIN
HOSP 28
MED
ARTS
CLC
CLC
WALKER BLVD
LAB
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
NOT FOR
CONSTRUCTION
Date:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\V . M
. E . 1
9\ D oc um en ts
\2 1.
_M
E C
H _P
LU
M
_R
_m bi bl e2
H X
D 7.
rv t
7/
/2
2:
:4
P
M
PG112B
MED GAS PLAN - SECOND FLOOR
(FINAL)
RENOVATE CLINICAL LAB FOR
MODERNIZATION
6010 W AMARILLO BLVD, AMARILLO, TX 79106
504-19-106
02/03/2022 MB RL
100% FINAL BID
DOCUMENTS
VEG 21.15
32'16'8'4'2'0'
P la n N or th
Tru e
Nor th
1/8" = 1'-0"
MED GAS PLAN - SECOND FLOOR (FINAL)
1. PROVIDE LAB GAS VALVE ENCLOSURE IN WALL FACED TO CORRIDOR.
INCLUDE SHUTOFF VALVES FOR LAB AIR, LAB VACUUM, OXYGEN, AND
NITROGEN. PROVIDE NEW PRESSURE SENSORS, EXTENDED AND
RE-CONNECTED TO EXISTING TUBING AND WIRING. RE-ENABLE EXISTING
ALARMS. REF DEMO PLAN.
2. STANDALONE CO2 CANISTERS FOR INCUBATOR. SHOWN FOR REFERENCE
ONLY. CANISTERS AND CONNECTIONS TO EQUIPMENT BY VHA.
3. PROVIDE DROPS AND WALL OUTLET BOX FOR GENERAL USE.
4. VALVED AND CAPPED FOR FUTURE EXTENSION.
5. PROVIDE QTY 2 VALVED 1/2" LA RUNOUTS TO "POWERLINK" EQUIPMENT
UNITS, FINAL LOCATION TBD. ASSUME UP TO 25' DISTANCE FROM TAKEOFF.
ROOM NUMBER KEY
NUMBER ROOM NAME
2221 BARBER SHOP
2225 MEN'S RR
2227 VENDING
2231 KITCHEN
2231A HAC
2234 MECHANICAL
2235 FLAMMABLE STORAGE
2236 MICROBIOLOGY
2237 LOCKERS
2238 STAFF TOILET
2238A STAFF TOILET
2239 HISTOLOGY
2239A GROSS SPECIMEN
2240 PATHOLOGIST
2241 LAB TECH OFFICE
2242 SUPERVISOR
2243 HAC
2244 CUBICLE OFFICE
2245 PREFAB MORTUARY
2246 TELE
2247 STORAGE
2248 ELECTRICAL
2249 STORAGE
2250 ELECTRICAL
2251A RECEPTION
2251B MED RECORDS
2251C STORAGE
2252 BLOOD COLLECTION
2252A RESTROOM
2252B RESTROOM
2253 PHLEB OFFICE
2254 CHIEF
2255 LABORATORY
2255A LAB TECH
2255B ACCESSIONING
2255C REFRIG STORAGE
2255D BLOOD BANK
2255E MULTIPURPOSE CONF RM
2255F EMPL URINE
2256 STORAGE
2256A REFUSE STORAGE
2257 STORAGE
2258 HAC
2259 MECHANICAL
2260 TELE
2261 CANTEEN STORAGE
2262 ELECTRICAL
2263 CANTEEN OFFICE
2264 FOOD STORAGE
2267 STORAGE CLOSET
C1-4 CORRIDOR
C1-5 CORRIDOR
C1-6 CORRIDOR
C1-7 CORRIDOR
0 100% FINAL BID DOCUMENTS 02/03/2022
3 3.2 4 5 6
C
D
E
2263A
TEMP MULTI-LAB
FOOD STORAGE
KITCHEN
TEMP LAB STORAGE
P-524
1"ø DHWR
2"ø DHW
3"ø DCW
2256J
BREAKROOM
1/
2" ø
R W
U F
BFP, TYP 2
1/2"ø DCW UF
1/ 2" ø D
C W
U F
1/
2" ø
D H
W U
F
1/
2" ø
D C
W U
F
FD-T
1/
4" ø
D C
W U
F 1 1/4"ø DCW UF
FD-T FD-T
FD-T
FD-X
3/4"ø RW UF
3/4"ø RWR UF
1 1/2"ø RW UF
3/ 4" ø R
W U
F
3/4"ø RW UF
1/
4" ø
D H
W U
F
3/ 4" ø D
C W
U F
1/
4" ø
D H
W R
U F
P-707
3/ 4" ø R
W U
F
1/
4" ø
D H
W U
F
P-807
2256I
SPECIMEN
ACCESSIONING
3/ 4" ø R
W R
10 10 12
15 16
FD-T
A. REFER TO P-001 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL
NOTES.
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO GI SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
D. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT
PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING
HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED.
ABATEMENT WILL BE PERFORMED BY THE VHA OUTSIDE OF THIS CONTRACT.
E. REFER TO GC SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.
F. WATER AND MED GAS HORIZONTAL PIPING IS ABOVE THE CEILING UNO.
SANITARY SEWER AND STORM DRAINAGE HORIZONTAL PIPING IS UNDER
FLOOR UNO. VENT HORIZONTAL PIPING IS ABOVE CEILING UNO. REFER TO
GC111 FOR RATED CONSTRUCTION ON FIRST FLOOR.
TEMP
MICROBIOLOGY
STORAGE / FLEX
TEMP HISTOLOGY
TEMP HISTOLOGY
P-107
P-M1
P-707
P-524 P-524
P-524
P-807
P-807
P-807
FD-X
66 66
109 109
116117118
123 125
##KEYNOTES
KEY PLAN
GENERAL NOTES
P la n N or th
Tru e
Nor th
ORIG HOSP 1
W A
LK
E
R B
LV
D
W A
LK
E
R B
LV
D
WALKER BLVD
MAIN
HOSP 28
MED
ARTS
CLC
CLC
WALKER BLVD
LAB
MODULAR LAB
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
NOT FOR
CONSTRUCTION
Date:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\V . M
. E . 1
9\ D oc um en ts
\2 1.
_M
E C
H _P
LU
M
_R
_m bi bl e2
H X
D 7.
rv t
7/
/2
2:
:4
P
M
PP112A
DOMESTIC WATER PLANS
(INTERIM)
RENOVATE CLINICAL LAB FOR
MODERNIZATION
6010 W AMARILLO BLVD, AMARILLO, TX 79106
504-19-106
02/03/2022 MB RL
100% FINAL BID
DOCUMENTS
VEG 21.15
32'16'8'4'2'0'
P la n N or th
Tru e
Nor th
1/8" = 1'-0"
DOMESTIC WATER PLAN - SECOND FLOOR (INTERIM)
1. PROVIDE DCW AND RW TO RELOCATED EXISTING HOOD. PROVIDE BFP'S
PER SPECIFICATION SECTION 22 05 23 GENERAL DUTY VALVES FOR
PLUMBING PIPING.
2. REFER TO PQ-SERIES SHEET SCHEDULES AND MODULAR LAB
PERFORMANCE SPECIFICATION 13 34 41. PROVIDE PREFABRICATED
INTERNAL PLUMBING IN ACCORDANCE THEREWITH. REFER TO PS-SERIES
SHEETS FOR SITE UTILITY CONNECTIONS.
3. ALL WORK SHOWN AS NEW IN THE INTERIM PHASE SHALL, AFTER
COMPLETION OF THE FINAL LAB AND OWNER MOVE-OUT OF THE
TEMPORARY SPACE, BE DEMO'D COMPLETELY BACK TO INTERIM TAKEOFF
VALVES AND CAPPED.
4. PROVIDE TP-1 TRAP PRIMER. ROUTE 1/2" DCW PIPING TO TRAP PRIMER
CONNECTIONS ON ALL FLOOR DRAINS IN ACCORDANCE WITH
SPECIFICATIONS 22 13 00 AND MANUFACTURER INSTRUCTIONS. ENGAGE
ELECTRICAL FOR 120V/1Φ POWER SERVICE.
32'16'8'4'2'0'
P la n N or th
T ru e N or th
1/8" = 1'-0"
DOMESTIC WATER PLAN - MODULAR LAB (INTERIM)
0 100% FINAL BID DOCUMENTS 02/03/2022
A. REFER TO P-001 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL
NOTES.
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO GI SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
D. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT
PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING
HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED.
ABATEMENT WILL BE PERFORMED BY THE VHA OUTSIDE OF THIS CONTRACT.
E. REFER TO GC SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.
F. WATER AND MED GAS HORIZONTAL PIPING IS ABOVE THE CEILING UNO.
SANITARY SEWER AND STORM DRAINAGE HORIZONTAL PIPING IS UNDER
FLOOR UNO. VENT HORIZONTAL PIPING IS ABOVE CEILING UNO. REFER TO
GC111 FOR RATED CONSTRUCTION ON FIRST FLOOR.
3 3.2 4 5 6
C
D
E
2263A
TEMP MULTI-LAB
FOOD STORAGE
KITCHEN
TEMP LAB STORAGE
P-524
FD-T
10 105
FD-T
FD-T FD-T
P-707
FD-X
3"ø SS CRP
3"ø SS CRP
3" ø
S S
C R
P
3"ø SS CRP3"ø SS CRP
2" ø
V C
R P
2" ø
V C
R P
2"ø V CRP 2"ø V CRP
2" ø
V C
R P
2" ø
V C
R P
3" ø
S S
C R
P
2231A
HAC
ELECTRICAL
ELECTRICAL
2"ø V CRP
3"ø SS CRP
CO
8 67
11 57
65 22
FD-T
3"ø SS CRP
TEMP
MICROBIOLOGY
STORAGE / FLEX
TEMP HISTOLOGY
TEMP HISTOLOGY
6666 65
109 109
118 117
120 112
P-M1
P-107
P-707
P-524 P-524
P-524
FD-X
##KEYNOTES
KEY PLAN
GENERAL NOTES
P la n N or th
Tru e
Nor th
ORIG HOSP 1
W A
LK
E
R B
LV
D
W A
LK
E
R B
LV
D
WALKER BLVD
MAIN
HOSP 28
MED
ARTS
CLC
CLC
WALKER BLVD
LAB
MODULAR LAB
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
NOT FOR
CONSTRUCTION
Date:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\V . M
. E . 1
9\ D oc um en ts
\2 1.
_M
E C
H _P
LU
M
_R
_m bi bl e2
H X
D 7.
rv t
7/
/2
2:
:4
P
M
PW112A
DRAIN-WASTE-VENT PLANS
(INTERIM)
RENOVATE CLINICAL LAB FOR
MODERNIZATION
6010 W AMARILLO BLVD, AMARILLO, TX 79106
504-19-106
02/03/2022 MB RL
100% FINAL BID
DOCUMENTS
VEG 21.15
32'16'8'4'2'0'
P la n N or th
Tru e
Nor th
1/8" = 1'-0"
DRAIN-WASTE-VENT - SECOND FLOOR (INTERIM)
1. REFER TO PQ SHEET SERIES SCHEDULES AND MODULAR LAB
PERFORMANCE SPECIFICATIONS. PROVIDE PREFABRICATED INTERNAL
PLUMBING IN ACCORDANCE THEREWITH. REFER TO PS SHEET SERIES FOR
SITE UTILITY CONNECTIONS.
2. KEEP DOWNSTREAM EXISTING SS CRP IN SERVICE UNTIL NEW 3" SS CRP IN
APPROXIMATE SAME LOCATION IS COMPLETE AND CONNECTED TO MAIN
STACK (REF FINAL PW SHEET SERIES). MOVE CONNECTION TO NEW SS CRP
THEREAFTER AND COMPLETE DEMO PER PD SHEET SERIES.
3. ALL WORK SHOWN AS NEW IN THE INTERIM PHASE SHALL, AFTER
COMPLETION OF THE FINAL LAB AND OWNER MOVE-OUT OF THE
TEMPORARY SPACE, BE DEMO'D COMPLETELY BACK TO INTERIM TAKEOFF
VALVES AND CAPPED.
32'16'8'4'2'0'
P la n N or th
T ru e N or th
1/8" = 1'-0"
DRAIN-WASTE-VENT PLAN - MODULAR LAB (INTERIM)
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
NOT FOR
CONSTRUCTION
Date:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\V . M
. E . 1
9\ D oc um en ts
\2 1.
_M
E C
H _P
LU
M
_R
_m bi bl e2
H X
D 7.
rv t
7/
/2
2:
:4
P
M
MQ601
EQUIPMENT SCHEDULES RENOVATE CLINICAL LAB FOR
MODERNIZATION
6010 W AMARILLO BLVD, AMARILLO, TX 79106
504-19-106
02/03/2022 MB RL
100% FINAL BID
DOCUMENTS
VEG 21.15
TERMINAL UNIT (TU) SCHEDULE
MARK TYPE
UNIT
SIZE
MAX
CFM
MIN
CFM
MAX
TOTAL
APD
(IN WG)
REHEAT COIL
SINGLE POINT
ELECTRICAL
BOD MFGR
AND MODEL REMARKS
HEATING
CFM
EAT
(°F)
LAT
(°F) MBH GPM
EWT
(°F)
WPD
(FT WG) VAC/PH
MAX
LOAD
28-TU-4-2 SINGLE DUCT HW REHEAT 8 640 640 1 640 55 85 21.1 1.4 180 0.19 24 / 1 15 VA TITUS DESV 1
28-TU-4-3 SINGLE DUCT HW REHEAT 6 300 300 1 300 55 85 9.9 0.7 180 0.08 24 / 1 15 VA TITUS DESV 1, 2
28-TU-5-1 SINGLE DUCT HW REHEAT 8 550 550 1 550 55 85 18.2 1.2 180 0.15 24 / 1 15 VA TITUS DESV 1
28-TU-5-4 SINGLE DUCT HW REHEAT 10 1170 1170 1 1170 55 85 38.6 2.6 180 0.10 24 / 1 15 VA TITUS DESV 1
28-TU-5-5 SINGLE DUCT HW REHEAT 6 340 340 1 340 55 85 11.2 0.7 180 0.08 24 / 1 15 VA TITUS DESV 1
28-TU-5-6 SINGLE DUCT HW REHEAT 10 1130 1130 1 1130 55 85 37.3 2.5 180 0.26 24 / 1 15 VA TITUS DESV 1
28-TU-5-7 SINGLE DUCT HW REHEAT 6 270 270 1 270 55 85 8.9 0.6 180 0.95 24 / 1 15 VA TITUS DESV 1, 2
28-TU-5-8 SINGLE DUCT HW REHEAT 8 880 440 1 440 55 85 14.5 1.0 180 0.19 24 / 1 15 VA TITUS DESV 1, 2
28-TU-5-9 SINGLE DUCT HW REHEAT 6 300 150 1 150 55 85 5.0 0.5 180 0.20 24 / 1 15 VA TITUS DESV 1, 2
28-TU-5-10 SINGLE DUCT HW REHEAT 4 170 120 1 120 55 85 4.0 0.5 180 0.08 24 / 1 15 VA TITUS DESV 1, 2
28-TU-5-11 SINGLE DUCT HW REHEAT 6 370 185 1 185 55 85 6.1 0.5 180 0.08 24 / 1 15 VA TITUS DESV 1
28-TU-5-12 SINGLE DUCT HW REHEAT 8 840 840 1 840 55 85 27.7 1.8 180 0.30 24 / 1 15 VA TITUS DESV 1, 2
28-TU-5-13A SINGLE DUCT HW REHEAT 12 1300 1300 1 1300 55 85 42.9 2.9 180 0.14 24 / 1 15 VA TITUS DESV 1
28-TU-5-13B SINGLE DUCT HW REHEAT 12 1300 1300 1 1300 55 85 42.9 2.9 180 0.14 24 / 1 15 VA TITUS DESV 1
28-TU-5-13C SINGLE DUCT HW REHEAT 12 1390 1390 1 1390 55 85 45.9 3.1 180 0.12 24 / 1 15 VA TITUS DESV 1
28-TU-5-14 SINGLE DUCT HW REHEAT 6 275 130 1 130 55 85 4.3 0.5 180 0.08 24 / 1 15 VA TITUS DESV 1, 2
28-TU-5-15 SINGLE DUCT HW REHEAT 4 100 100 1 100 55 85 3.3 0.5 180 0.07 24 / 1 15 VA TITUS DESV 1, 2
28-TU-5-16 SINGLE DUCT HW REHEAT 6 250 125 1 125 55 85 4.1 0.5 180 0.08 24 / 1 15 VA TITUS DESV 1, 2
28-TU-5-17 SINGLE DUCT HW REHEAT 4 100 70 1 70 55 85 2.3 0.5 180 0.08 24 / 1 15 VA TITUS DESV 1, 2
28-TU-5-18 SINGLE DUCT HW REHEAT 6 400 400 1 400 55 85 13.2 0.9 180 0.1 24 / 1 15 VA TITUS DESV 1, 2
28-TU-5-19 SINGLE DUCT HW REHEAT 4 200 200 1 200 55 85 6.6 0.5 180 0.08 24 / 1 15 VA TITUS DESV 1, 2
28-TU-5-20 SINGLE DUCT HW REHEAT 6 400 400 1 400 55 85 13.2 0.9 180 0.09 24 / 1 15 VA TITUS DESV 1, 2
28-TU-5-21 SINGLE DUCT HW REHEAT 6 500 500 1 500 55 85 16.5 1.1 180 0.12 24 / 1 15 VA TITUS DESV 1
28-TU-5-22 SINGLE DUCT HW REHEAT 8 820 410 1 410 55 85 13.5 0.9 180 0.22 24 / 1 15 VA TITUS DESV 1, 2
28-TU-5-23 SINGLE DUCT HW REHEAT 6 210 210 1 210 55 85 6.9 0.5 180 0.20 24 / 1 15 VA TITUS DESV 1, 2
28-TU-5-INT-1 SINGLE DUCT HW REHEAT 12 1680 1680 1 1680 55 85 52.1 3.5 180 0.19 24 / 1 15 VA TITUS DESV 1
28-TU-5-INT-2 SINGLE DUCT HW REHEAT 12 1680 1680 1 1680 55 85 52.1 3.5 180 0.19 24 / 1 15 VA TITUS DESV 1
28-TU-5-INT-3 SINGLE DUCT HW REHEAT 8 600 270 1 270 55 85 8.9 0.6 180 0.26 24 / 1 15 VA TITUS DESV 1
EXHAUST FAN (EF) SCHEDULE
MARK LOCATION AREA SERVED
AIRFLOW
(CFM)
ESP
(IN WG)
FAN MOTOR
BAS
CONTROLS
BOD MFGR AND
MODEL REMARKSTYPE DRIVE
DUTY RPM
% OF MAX
ELECTRICAL SPEED
CONTROLHP VAC Φ MCA MOCP
28-EF25
MECH RM
LABORATORY 4680 1 CENTRIFUGAL - INLINE DIRECT 90 1.5 480 3 3.75 15
VFD -
REMOTE
VARIABLE
SPEED
GREENHECK SQ 1,5
28-EF-5
BLDG 28
ROOF
MICROBIOLOGY 1350 2
CENTRIFUGAL - HIGH
PLUME
DIRECT 90 1 480 3 2.7 15
VFD -
REMOTE
VARIABLE
SPEED
GREENHECK
VK-H-13-8
1,2,5
28-EF-6
BLDG 28
ROOF
HISTOLOGY
FUME HOOD
775 1
CENTRIFUGAL - HIGH
PLUME
DIRECT 90 0.75 480 3 2 15
VFD -
REMOTE
VARIABLE
SPEED
GREENHECK
VK-H-10-6
1,2,4,5,6
28-EF-7
BLDG 28
ROOF
MICROBIOLOGY
FUME HOOD
775 1
CENTRIFUGAL - HIGH
PLUME
DIRECT 90 0.75 480 3 2 15
VFD -
REMOTE
VARIABLE
SPEED
GREENHECK
VK-H-10-6
1,2,3,5,6
28-EF-14
BLDG 28
ROOF
BREAKROOM 460 1 CENTRIFUGAL - UTILITY DIRECT 90 1 480 3 3 15
VFD -
REMOTE
VARIABLE
SPEED
GREENHECK
USF-12
1,5
28-EF-17
BLDG 28
ROOF
HISTOLOGY 1610 2
CENTRIFUGAL - HIGH
PLUME
DIRECT 90 1.5 480 3 3.8 15
VFD -
REMOTE
VARIABLE
SPEED
GREENHECK
VK-H-14-9
1,2,4,5
28-EF-2235
MECH RM
FLAMMABLE
STORAGE
500 0.3 CENTRIFUGAL - INLINE DIRECT 90 0.25 208 3 3 15
VFD -
REMOTE
VARIABLE
SPEED
GREENHECK SQ 1,4,5
28-EF-INT1
BLDG 28
ROOF
INTERIM LAB
SPACE
3640 1
POWER WALL
VENTILATOR
DIRECT 90 3 208 3 10.6 15
VFD -
REMOTE
VARIABLE
SPEED
GREENHECK
CUE-240HP-B
1,5,7
28-EF-INT2
BLDG 28
ROOF
INTERIM FUME
HOOD
500 2
CENTRIFUGAL - HIGH
PLUME
DIRECT 90 1.5 480 3 3.8 15
VFD -
REMOTE
VARIABLE
SPEED
GREENHECK VK 1,2,4,5
AIR DEVICE SCHEDULE
MARK TYPE DESCRIPTION MOUNTING
PANEL / FRAME
SIZE
NECK SIZE MAX CFM
MAX NC
MAX APD
(IN WG)
BOD MFGR &
MODEL REMARKS
6"Ø 6"X6"
8"Ø 8"X8"
10"Ø 10"X10"
12"Ø 12"X12"
14"Ø 14"X14"
E3-A
EXHAUST - PERFORATED
FACE
CEILING 24"X24" 125 220 345 500 600 20 0.10 TITUS PAR ALL
R3-A
RETURN - PERFORATED
FACE
CEILING 24"X24" 125 220 345 500 600 20 0.10 TITUS PAR ALL
S1-A
SUPPLY - SQUARE,
LOUVER, FULLY
ADJUSTABLE PATTERN
CEILING 24"X24" 120 230 350 525 700 20 0.05 TITUS TMS ALL
S4-D
SUPPLY - SLOT
DIFFUSER/PLENUM
CEILING
48"L, SINGLE 1"
SLOT
100 275 315 -1 -1 25 0.15 TITUS FL ALL
S6-A SUPPLY - REGISTER WALL 18"WX6"H 130 240 360 540 725 20 0.05 TITUS 300FL ALL
SCHEDULE REMARKS:
1. UNIT IS EXISTING TO REMAIN.
DATA SHOWN IS FROM
EQUIPMENT SUBMITTAL
PROVIDED BY THE VHA AND IS
PRESENTED FOR REFERENCE
AND TAB/CONTROLS
COORDINATION PURPOSES
ONLY.
A. FOR ALL SCHEDULED EQUIPMENT, PROVIDE BASIS OF DESIGN OR APPROVED
EQUAL. REFER TO SPECIFICATIONS 01 33 23 AND 23 05 11 FOR FURTHER
REQUIREMENTS.
B. SELECT EQUIPMENT FOR SCHEDULED PERFORMANCE AT 3700 FT ELEVATION.
SCHEDULE REMARKS:
1. REFER ALSO TO SPECIFICATION
23 36 00.
2. REPROGRAM AND REUSE
EXISTING TERMINAL UNIT OF
MATCHING SIZE. REFER TO MD
SHEET SERIES. VERIFY SIZE IN
FIELD.
SCHEDULE REMARKS:
1. REFER ALSO TO SPECIFICATION
23 34 00.
2. PROVIDE INTAKE PLENUM FOR
HORIZONTAL DUCT
CONNECTION.
3. PROVIDE HEPA FILTER AT
DISCHARGE.
4. SPARK RESISTANT
CONSTRUCTION.
5. PROVIDE VFD WITH BYPASS.
6. DO NOT ORDER UNTIL
ACCOMPANYING HOOD IS
SUBMITTED AND APPROVED.
7. PROVIDE WITH FLANGED CURB
AND HARDWARE FOR THRU-
WALL INSTALLATION.
SCHEDULE REMARKS:
1. REFER ALSO TO SPECIFICATION
23 37 00.
2. MATCH RUN-OUT TO NECK SIZE
UNLESS OTHERWISE TAGGED.
3. BLACK SHADED CELLS INDICATE
NECK SIZES NOT APPLICABLE TO
GIVEN AIR DEVICE.
EXISTING AIR HANDLING UNIT (AHU) SCHEDULE
MARK LOCATION
AREA AND/OR
BLDG SERVED
SUPPLY
AIRFLOW
(CFM)
OUTSIDE
AIRFLOW
(CFM)
PRE-
FILTER
AFTER-
FILTER
HEAT
RECOVERY
PREHEAT
COIL
COOLING
COIL
REHEAT
COIL HUMIDIFIER REMARKS
(E)
28-AHU5
MECH RM
LAB 14,750 14,750 YES NO NO
HW 1,077 MBH; 73 GPM
140°F-110°F WATERSIDE;
14,750 CFM 7°F-67°F AIRSIDE
CHW 871 MBH; 124 GPM 45°F-59°F
WATERSIDE; 14,750 CFM
97°F/71°F-51°F/51°F AIRSIDE
NO
MPS 257
LB/HR
REFRIGERATION UNIT (RU) SCHEDULE
MARK TYPE LOCATION
AREA AND/OR
BLDG SERVED
SUCTION
TEMP
(°F)
AMBIENT
AIR/ROOM
DESIGN TEMP
(°F)
CAPACITY
(MBH)
MAX
CONDENSING
TEMP (°F)
SUPPLY
AIRFLOW
(CFM)
SINGLE POINT POWER
BOD MFGR &
MODEL REMARKSVAC/PH MCA MOCP
28-RU-I-1
INDOOR UNIT - WALL
MOUNT UNIT COOLER
2255C
2255C REFRIG
STORAGE
15 36 12 - 1,300 120/1 2 15
CHANDLER
RLC
28-RU-O-1
OUTDOOR UNIT - AIR
COOLED CONDENSER
BLDG 28
ROOF
28-RIU-2255C 15 105 12 110 - 480 7.1 15
EMERSON
FFAP
1,2,3
SCHEDULE REMARKS:
1. REFER ALSO TO SPECIFICATION
13 21 29.
2. PROVIDE DUPLEXED
REDUNDANT COMPRESSORS.
3. PROVIDE NEMA 3R 30A/3P 600V
DISCONNECT FACTORY
MOUNTED ON UNIT.
0 100% FINAL BID DOCUMENTS 02/03/2022
1 ADDENDUM 1 07/14/2022
SCHEDULE REMARKS:
1. ONLY EQUIPMENT REQUIRING
MECHANICAL PROVISIONS ARE
SCHEDULED HERE. REFER TO
ARCHITECTURAL FOR DETAILED
EQUIPMENT REQUIREMENTS AND
FOR REMAINING EQUIPMENT
DESCRIPTIONS. BALANCE
EXHAUST DUCT DROPS TO
EQUIPMENT TO TOTAL SCHEDULED
CFM. CONFIRM WITH FINAL
INSTALLED EQUIPMENT. PROVIDE
MANUFACTURER APPROVED
ADAPTER FOR CONNECTION TO
MACHINE PORT.
LAB EQUIPMENT MECHANICAL CONNECTION SCHEDULE
EQUIPMENT
MARK DESCRIPTION BASIS OF DESIGN
EXHAUST
CFM REMARKS
80 BIO SAFETY CABINET (HOOD) REF 11 53 53 775 1
90 FUME HOOD WITH CUP SINK REF 11 53 13 775 1
108 GROSSING STATION (E) MOPEC 500 1
110 COVER SLIPPER (E) TISSUE-TEK FILM-A1 30 1
SOUND ATTENUATING DEVICE (SAD) SCHEDULE
MARK LOCATION
SYSTEM
AND/OR
SERVICE TYPE
AIRFLOW
(CFM)
MAX APD
(IN WG)
INLET
SIZE
(IN)
LENGTH
(IN)
OCTAVE BAND DYNAMIC INSERTION LOSS (DB)
REMARKS63 125 250 500 1000 2000 4000 8000
28-SAD-5-4 2236 28-TU-5-4 PACKLESS - ROUND 1200 0.10 12 36 11 8 15 72 14 11 9 7 1
SCHEDULE REMARKS:
1. REFER ALSO TO SPECIFICATION
23 31 00.
M NO
TTTT MT
M
NO
V F
D
PR
SF
C H
W
M
NC
M
NO
H W
LP
S
H U
M
AFMD
MT TT
MT TT
PDT
AF
TE
R-
FI
LT
ER
V F
D
PR
EF AFMD
PDT
PR
E-
FI
LT
ER
PSH PT
OA SA
EA RA
TT TT
M NO TT
M
NO
T
H
WSA SA
AFMD
P&ID CONTROL POINT LEGEND
XXXX
XXXX
POINT ID (REFERENCE POINT LIST). '#'
INDICATES TYPICAL OF SEVERAL AS
SHOWN 'SIM' IN P&ID.
DEVICE MARK (REF CONTROL
DEVICE SCHEDULE). '---' DENOTES
DEVICE OR EQUIPMENT BY OTHERS
IN SCOPE OF GENERAL CONTRACT.
CONTROL DEVICE (SHADED
INDICATES BY BASC)
CONTROL
POINT/CONNECTION
(HARDWIRED OR NETWORK,
REF POINT LIST)
GENERAL/GLOBAL
CONTROL POINTS
FA.ST
BASD-01D
ZN.T.CLR
PTS.ST
BASD-05
DPR.OA
BASD-10B
PHT.ET
BASD-54
CV.CC
SF.ST
SF.SPD
BASD-A
SF.SS
BASD-09A
SA.RH
BASD-10A
SA.T
BASD-54
CV.HUM
BASD-13B
SA.FL
BASD-54
CV.PHT
BASD-09A
RA.RH
BASD-10A
RA.ET
BASD-09A
OA.RH
BASD-10A
OA.T
BASD-12B
SA.P.LMT
BASD-12A
SA.SP
BASD-11
FPD.SA
EF.ST
EF.SPD
BASD-A
EF.SS
BASD-13B
RA.FL
1. UPDATE EXISTING SEQUENCE OF OPERATION AS
FOLLOWS:
2. UNIT SHALL BE IN "OCCUPIED" MODE BASED ON AN
OPERATOR DEFINED SCHEDULE OR LOCAL ZONE
OVERRIDE SIGNAL. OTHERWISE THE UNIT SHALL BE IN
"UNOCCUPIED" MODE.
3. BUILDING FIRE ALARM OR OTHER SAFETY SIGNAL SHALL
SHUT DOWN THE UNIT IN OVERRIDE OF THE BAS.
4. WHEN IN OCCUPIED MODE:
A. INITIALIZATION:
a. OUTSIDE AIR (OA) DAMPER SHALL OPEN.
b. SUPPLY AIR (SA) FAN SHALL ENERGIZE.
c. RA FAN SHALL ENERGIZE.
B. SETPOINT CONTROL:
a. ACTIVE DUCT REMOTE STATIC PRESSURE
SETPOINT SHALL BE MODULATED BETWEEN 2.0
AND 3.0 IN WG* TO MAINTAIN THE MOST OPEN
TERMINAL UNIT (TU) DAMPER AT 95% OPEN.
b. ACTIVE SUPPLY AIR TEMPERATURE (SAT)
SETPOINT: SAT SETPOINT SHALL BE MODULATED
FROM 52°F* TO THE ACTIVE UPPER SAT LIMIT TO
MAINTAIN HIGHEST TU CFM AT 50%* OF DESIGN
FLOW (OR 110% OF MINIMUM FLOW, WHICHEVER
IS HIGHER). ACTIVE UPPER SAT LIMIT SHALL BE
RESET FROM 55°F* TO 70°F* AS OA DEWPOINT
VARIES FROM 57°F* TO 55°F*.
c. THE RA CFM SETPOINT SHALL BE EQUAL TO 110%*
OF THE ACTIVE MEASURED SA CFM, LESS THE
ACTIVE EF25 CFM.
C. CONTROL OUTPUTS:
a. SA FAN CONTROL: MODULATE FAN SPEED TO
MAINTAIN THE ACTIVE DUCT REMOTE STATIC
PRESSURE SETPOINT.
b. RA FAN CONTROL: MODULATE FAN SPEED TO
MAINTAIN THE ACTIVE RA CFM SETPOINT.
c. CHILLED WATER (CHW) CONTROL VALVE:
MODULATE TO MAINTAIN SAT AT THE ACTIVE SAT
SETPOINT.
d. HEATING HW VALVE: MODULATE TO MAINTAIN SAT
AT THE ACTIVE SAT SETPOINT, MINUS 5°F*.
e. HUMIDIFIER STEAM VALVE: MODULATE TO
MAINTAIN RA RELATIVE HUMIDITY AT 40%*.
5. WHEN IN UNOCCUPIED MODE:
A. FANS SHALL DE-ENERGIZE.
B. COOLING COIL, HEATING COIL, OA DAMPER, AND EA
DAMPER SHALL FULL CLOSE.
C. IF ANY ZONE TEMPERATURE FALLS BELOW
UNOCCUPIED SETBACK TEMPERATURE OF 55°F* OR
ABOVE UNOCCUPIED SETUP TEMPERATURE OF 85°F*,
ENABLE AHU AND CONTROL AS IN OCCUPIED MODE
EXCEPT THAT:
a. ZONE SETPOINTS SHALL BE SETBACK AND SETUP
TEMPERATURES ABOVE.
6. ALARMS AND SAFETIES:
A. RETAIN EXISTING ALARMS AND SAFETIES WITH
ADDITION OF THE FOLLOWING.
B. SEND ALARM UPON DUCT HIGH PRESSURE LIMIT TRIP.
*-INDICATES SETPOINT TO BE ADJUSTABLE.
SEQUENCE OF OPERATIONS PROCESS & INSTRUMENTATION
DIAGRAM (P&ID)
BASD-11
FPD.OA
BASD-10B
CC.ET
BASD-10B
CC.LT
HALFTONE INDICATES
EXISTING TO REMAIN, TYP
BLACK INDICATES NEW
ADDED DEVICES, TYP
PER NFPA45, ENSURE FIRE DETECTION
AND ALARM SYSTEMS ARE NOT
INTERLOCKED TO AUTOMATICALLY
SHUT DOWN LABORATORY EXHAUST
FANS.
ENSURE OA DAMPER OVERRIDES TO OPEN IF FA
IS TRIPPED IN ORDER TO PROVIDE INTAKE PATH
FOR CONTINUED LAB EXHAUST AS REQUIRED
BY NFPA45
BASD-05
DPR.TU
BASD-54
CV.TU.RH
BASD-01A
ZN.T
ZN.ADJ
ZN.OVRD
BASD-10A
TU.T
TU.FL
1. UNIT SHALL BE IN "OCCUPIED" MODE BASED ON AN OPERATOR
DEFINED SCHEDULE OR LOCAL ZONE OVERRIDE SIGNAL.
OTHERWISE THE UNIT SHALL BE IN "UNOCCUPIED" MODE.
2. WHEN IN OCCUPIED MODE:
A. INITIALIZATION: TERMINAL UNIT (TU) DAMPER SHALL OPEN
TO MINIMUM POSITION AS PRESET IN THE CONTROLLER
PER THE EQUIPMENT SCHEDULE.
B. SETPOINT CONTROL:
a. ACTIVE ZONE COOLING TEMPERATURE SETPOINT:
COMPUTE FROM A BASE SETPOINT OF 75°F* ± UP TO 5°
F* BASED ON LOCAL THERMOSTAT ADJUSTMENT IN
APPLICABLE SPACES.
b. ACTIVE ZONE HEATING TEMPERATURE SETPOINT:
COMPUTE FROM ACTIVE COOLING SETPOINT MINUS 5°F*
DEADBAND.
c. COOLING DEMAND %: COMPUTE BASED ON PID
RESPONSE TO THE ACTIVE ZONE COOLING SETPOINT
AND THE ZONE TEMPERATURE.
d. HEATING DEMAND %: COMPUTE BASED ON PID
RESPONSE TO THE ACTIVE ZONE HEATING SETPOINT
AND THE ZONE TEMPERATURE.
e. ACTIVE CFM SETPOINT: RESET BETWEEN SCHEDULED
MINIMUM AND DESIGN CFM AS COOLING DEMAND
VARIES FROM 0%-100%.
C. CONTROL OUTPUTS:
a. PRIMARY AIR DAMPER: MODULATE TO MAINTAIN THE
PRIMARY AIR CFM AT THE ACTIVE CFM SETPOINT.
b. HEATING WATER (HW) VALVE: MODULATE EQUAL TO THE
HEATING DEMAND %.
3. WHEN IN UNOCCUPIED MODE:
A. DAMPER SHALL CLOSE TO 10%* OPEN POSITION TO AVOID
AHU DEAD-HEAD AT START-UP.
B. HW SHALL FULL CLOSE.
C. IF ZONE TEMPERATURE FALLS BELOW UNOCCUPIED
SETBACK TEMPERATURE OF 60°F* OR ABOVE UNOCCUPIED
SETUP TEMPERATURE OF 80°F*, ENABLE TU AND CONTROL
AS IN OCCUPIED MODE EXCEPT THAT ZONE SETPOINTS
SHALL BE SETBACK AND SETUP TEMPERATURES ABOVE.
*-INDICATES SETPOINT TO BE ADJUSTABLE.
SEQUENCE OF OPERATIONS PROCESS & INSTRUMENTATION
DIAGRAM (P&ID)
BASD-01A
ZN.T
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
NOT FOR
CONSTRUCTION
Date:Revisions:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
Number:
C :\U se rs
\V . M
. E . 1
9\ D oc um en ts
\2 1.
_M
E C
H _P
LU
M
_R
_m bi bl e2
H X
D 7.
rv t
7/
/2
2:
:4
P
M
MI701
CONTROLS & INSTRUMENTATION
DETAILS
RENOVATE CLINICAL LAB FOR
MODERNIZATION
6010 W AMARILLO BLVD, AMARILLO, TX 79106
504-19-106
02/03/2022 MB RL
100% FINAL BID
DOCUMENTS
VEG 21.15
CONTROL DEVICE SCHEDULE
GENERAL NOTES:
A. REFER TO PROCESS &
INSTRUMENTATION
DIAGRAMS (P&IDs) AND
POINT LISTS FOR DEVICE
QUANTITIES AND
SCHEMATIC LOCATIONS.
B. REFER TO SPECIFICATION
23 09 23 FOR DETAILED
DEVICE REQUIREMENTS.
A. UNLESS OTHERWISE NOTED, REFER TO MECHANICAL EQUIPMENT
SCHEDULES FOR QUANTITIES OF EACH SYSTEM TYPE TO
RECEIVE CONTROLS.
B. "HARDWIRED" POINTS REQUIRE INDIVIDUAL PHYSICAL
CONNECTION FROM BAS CONTROLLER INPUT/OUTPUT
TERMINALS TO SENSORS, DEVICES, OR EQUIPMENT AS NOTED.
C. "NETWORK" POINTS ARE POINTS SENT TO OR RECEIVED FROM
EQUIPMENT FACTORY CONTROLS VIA BACNET, OR THE LIKE,
INTERFACE. COORDINATE WITH EQUIPMENT SUPPLIER
REQUIREMENTS FOR COMM GATEWAY TO INTERFACE WITH BAS
AS NECESSARY PRIOR TO BID. UNLESS OTHERWISE NOTED,
REQUISITE GATEWAYS SHALL BE FURNISHED WITH RESPECTIVE
EQUIPMENT BY EQUIPMENT MFGR.
D. NETWORK POINTS INDICATED AS BOTH READ AND WRITE IN
POINT LISTS SHALL BE NORMALLY CONTROLLED BY EQUIPMENT
FACTORY CONTROLS, BUT OVERRIDABLE FROM THE BAS.
E. BAS CONTRACTOR SHALL PROVIDE CONTROL DEVICES IN POINT
LISTS AND RESPECTIVE P&IDs, AND AS SCHEDULED ON CONTROL
DEVICE SCHEDULE AND SPECIFIED IN SPECIFICATION 23 09 23.
F. ALL I/O POINTS IN THE POINTS LIST(S), AS WELL AS ALL
SOFTWARE POINTS SUCH AS SETPOINTS AND ALARMS, SHALL BE
DISPLAYED AND OVERRIDABLE VIA THE BAS FRONT-END
GRAPHIC FOR THE EQUIPMENT.
G. "START/STOP" AS NOTED IN POINT LISTS HEREIN IS SYNONYMOUS
WITH "ENABLE/DISABLE". START/STOP COMMANDS FROM THE
BAS SHALL BE SUBJECT TO EQUIPMENT INTERNAL CHECKS AND
SAFETIES PRIOR TO PHYSICAL START OR STOP OF THE
RESPECTIVE EQUIPMENT.
BAS POINT LIST GENERAL NOTES
POINT LIST GENERAL NOTES:
REFER TO BAS POINT LIST
GENERAL NOTES ON SHEET
MI701.
POINT LIST FOOTNOTES:
REFER TO BAS POINT LIST
FOOTNOTES ON SHEET MI701.
BAS POINT LIST FOOTNOTES
GENERAL BAS SCHEDULES, NOTES, AND CONTROL POINTS1
1. REFER TO MECHANICAL PLANS FOR TSTAT LOCATIONS. MOUNT
48" AFF UNLESS OTHERWISE NOTED.
2. INSTALL SENSOR IN SPACE NEXT TO TSTAT.
3. INSTALL SENSOR ON EXTERIOR WALL. REFER TO MECHANICAL
PLANS FOR LOCATION.
4. INSTALL AT 2/3 OF MAIN DUCT RUN. LABEL CEILING GRID BELOW
PER SPECIFICATION 23 05 11.
5. DUAL REDUNDANT VFDs BY DIV 23 WITH REMOTE
PRIME/STANDBY SWITCHOVER SIGNAL CAPABILITY.
6. HARDWIRE TO FAN SAFETY CIRCUIT(S).
7. WIRE HUMIDIFIER VALVE POWER THROUGH NO SUPPLY AIR
MOISTURE HIGH-LIMIT SWITCH.
8. VFD SPEED % COMMAND SHALL BE PERCENT OF FULL DESIGN
HZ, AS DETERMINED DURING TAB AND SET AT THE DRIVE BY THE
BASC, AND MAY BE GREATER THAN OR LESS THAN 60 HZ.
9. NOTE NOT USED.
10. ENGAGE AND COORDINATE WITH FIRE ALARM CONTRACTOR TO
PROVIDE ALARM OUTPUT FROM BLDG FA SYSTEM FOR
MONITORING IN BAS. FIRE ALARM SIGNAL SHALL DISABLE ALL
AIR MOVING EQUIPMENT CONTROLLED BY THE BAS. DISPLAY
FIRE ALARM STATUS ON ALL EQUIPMENT GRAPHICS.
11. PROVIDE LCD READOUT OF AFMD AT THE HOOD AND LABEL
WITH ENGRAVED PHENOLIC NAMEPLATE PER SPECIFICATION 23
05 11.
GENERAL/GLOBAL AND MISCELLANEOUS BAS I/O POINT LIST
POINT DESCRIPTION
P&ID POINT
ID
HARDWIRED
CONTROLLER I/O's
NETWORK
POINTS
T R
E N
D
FOOT
NOTESDI DO AI AO R
E A
D
W R
IT
E
GLOBAL FIRE ALARM SIGNAL FA.ST ● 10
WALK-IN COOLER TEMPERATURE ZN.T.CLR ● ● 10
PNEUMATIC TUBE SYSTEM
STATUS
PTS.ST ● 10
(REF: P&IDs AND I/O POINT LISTS. BY BASC UNO.)
CONTROL DEVICE SCHEDULE
DEVICE
MARK DEVICE DESCRIPTION
BASD-01A
ZONE/SPACE TEMPERATURE SENSOR WITH LOCAL SETPOINT ADJUSTMENT
AND OCCUPANCY OVERRIDE
BASD-01D
LOW TEMP ZONE/SPACE TEMPERATURE SENSOR, MONITORING ONLY,
ACCURATE TO 0°F
BASD-05 CONTROL DAMPER & ACTUATOR
BASD-09A DUCT HUMIDITY SENSOR
BASD-10A DUCT AIR TEMPERATURE SENSOR
BASD-10B DUCT/COIL AIR AVERAGING TEMPERATURE SENSOR
BASD-11 AIR FILTER BANK DIFFERENTIAL PRESSURE TRANSMITTER
BASD-12A DUCT STATIC PRESSURE TRANSMITTER
BASD-12B DUCT PRESSURE HIGH LIMIT CUT-OUT SWITCH
BASD-13B AIRFLOW MEASURING DEVICE, ELECTRONIC THERMAL TYPE
BASD-14
ZONE/SPACE BI-DIRECTIONAL, THROUGH-THE-WALL DIFFERENTIAL
PRESSURE SENSOR
BASD-15 MAGNETIC CONTACT DOOR SWITCH
BASD-54 CONTROL VALVE & ACTUATOR
BASD-A PILOT RELAY/FRACTIONAL HP (1/3 OR SMALLER) MOTOR CONTACTOR
EXISTING AHU-52
POINT LIST GENERAL
NOTES:
REFER TO BAS POINT LIST
GENERAL NOTES ON SHEET
MI701.
POINT LIST FOOTNOTES:
REFER TO BAS POINT LIST
FOOTNOTES ON SHEET
MI701.
100% OA SDVAV CHW/STEAM AHU BAS I/O POINT LIST
POINT DESCRIPTION
P&ID POINT
ID
HARDWIRED
CONTROLLER I/O's
NETWORK
POINTS
T R
E N
D
FOOT
NOTESDI DO AI AO R
E A
D
W R
COOLING COIL ENTERING AIR TEMPERATURE CC.ET ● ●
COOLING COIL LEAVING AIR TEMPERATURE CC.LT ● ●
COOLING COIL CHW VALVE COMMAND (%) CV.CC ● ●
HUMIDIFIER STEAM VALVE COMMAND (%) CV.HUM ● ●
PRE-HEAT COIL HW VALVE COMMAND (%) CV.PHT ● ●
OUTSIDE AIR DAMPER COMMAND (%) DPR.OA ● ●
EXHAUST FAN VFD SPEED COMMAND (%) EF.SPD ● ●
EXHAUST FAN VFD START/STOP EF.