S06 - Updated Air Flow Room List 26 Q1 032526.xlsx
XLSX spreadsheet 65 KB Posted
- Attached to
- H241--Air Flow and Pressure Balance Testing at Central Arkansas Veterans Healthcare System (CAVHS)
- Solicitation number
- 36C25626Q0445
About this file
This is an updated Air Flow Room List for Q1 2026 that documents the air flow and pressure balance testing requirements for rooms across the Central Arkansas Veterans Healthcare System (CAVHS) facility.
The spreadsheet identifies approximately 400+ rooms requiring air flow testing, organized by location and floor (e.g., 1A, 1B, 1C through 7D and specialty areas). Each room entry specifies the room number, functional designation (e.g., storage, isolation, operating room, medical supply), required pressure classification (positive or negative), room volume in cubic feet, and required air changes per hour (RCH/AC/Hr). Supply CFH, return CFH, and exhaust CFH columns are included but largely unpopulated in this document. Testing frequency requirements are indicated through columns for quarterly results, annual results, and pass dates. The list includes standard clinical spaces (storage, utility, linen, soiled utility, clean equipment rooms), specialized areas (operating rooms 1-16, MICU, SICU, cardiac catheterization labs, bronchoscopy suites, autopsy), and pharmacy/medical supply areas. Additional entries cover new air-handling modules (APM01-APM29) and newly listed renovation (NLR) areas. Rooms designated as negative pressure include isolation rooms, soiled utility rooms, and biohazard storage areas requiring 6 to 12 air changes per hour, while positive pressure rooms such as clean supplies, operating rooms, and medical supply areas typically require 4 to 20 air changes per hour, with operating rooms requiring the highest standard of 20 air changes per hour.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S06 - PWS Air Flow Updated 032526.docx | DOCX document | |
| 36C25626Q0445 0001_1.docx | DOCX document | |
| S06 - 36C25626Q0445 0001.pdf | ||
| S06 - Technical Questions _ 36C25626Q0445 _ Air Flow and Pressure Balance Testing.pdf | ||
| Air Flow Room List 26 Q1 030626.xlsx | XLSX spreadsheet | |
| WD 2015-5117 Rev 29.pdf | ||
| 36C25626Q0445_1.docx | DOCX document | |
| S02 - 36C25626Q0445.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| Air Flow Room List 26 Q1 | PRESSURE | Results | Quarterly | Annually | Rm Volume | RCH | Required AC/Hr | Temp | Humidity | Sup CFH | Ret CFH | Exh CFH | Pass | Date | RPM'S ON INSIGHT | 67 |
| 1A-102 STORAGE | POS. | X | 624 | 4 | RPM'S ON TRANE | 99 | ||||||||||
| 1A-110 TRASH | NEG. | X | 1126 | 10 | Isolation Rooms | 27 | ||||||||||
| 1A-111 SOILED LINEN | NEG. | X | 1040 | 6 | Room Number needed. | 0 | ||||||||||
| 1B116 SOILED UTILITY/DIRTY EQUIPMENT | NEG. | X | 1200 | 6 | Current Room Total | 436 | ||||||||||
| 1C112A/1C127 CLEAN LINES, SPD SUPPLY, PPE SETUP | POS. | X | 762 | 4 | Annual Test Total | 284 | ||||||||||
| 1C125 BIOHAZARD STORAGE | NEG. | X | 742 | 6 | Quarterly Test Total | 65 | ||||||||||
| 1C143 ENT STORAGE/Speech Pathology | POS. | X | 1728 | 4 | Unknown | 87 | ||||||||||
| 1C147A AUDIO STORAGE/Speech Pathology | POS. | X | 1723 | 4 | ||||||||||||
| 1D115 CLEAN EQUIPMENT | POS. | X | 722 | 4 | ||||||||||||
| 1D125 ER CLEAN SUPPLIES ROOM, OMNICELL, PIXUS, MED ROOM | POS. | X | 612 | 4 | ||||||||||||
| 1D-126 MED ROOM | POS. | X | 512 | 4 | ||||||||||||
| 1D-127B 2 | NEG. | X | 12 | |||||||||||||
| 1D-127H ED 8 | NEG. | X | 1510 | 12 | ||||||||||||
| 1D-127K ED 10 | NEG. | X | 1152 | 12 | ||||||||||||
| 1D128 SOILED UTILITY | NEG. | X | 503 | 6 | ||||||||||||
| 1D131 CLEAN UTILITY | POS. | X | 317 | 4 | ||||||||||||
| 1D143 IR STORAGE ANGIO | POS. | X | 1360 | 4 | ||||||||||||
| 1D147B ER SOILED | NEG. | X | 272 | 6 | ||||||||||||
| 1D147E MED ROOM | POS. | X | 636 | 4 | ||||||||||||
| 1D147I CLEAN LINEN | POS. | - | X | - | 4 | |||||||||||
| 1E-117 SOILED UTILITY | NEG. | X | 855 | 6 | ||||||||||||
| 1E-177 IR Room | POS. | X | 4840 | 6 | ||||||||||||
| 1E-177B CLEAN ROOM | POS. | X | 517 | 4 | ||||||||||||
| 1E178 IR STORAGE | POS. | X | 244 | 4 | ||||||||||||
| 1E181 SUPPLY STORAGE | POS. | X | 145 | 4 | ||||||||||||
| 1E-184 Lounge/Quality Control | POS. | X | 2000 | 4 | ||||||||||||
| 1E-185 STORAGE | POS. | X | 187 | 4 | ||||||||||||
| 1E200A MEDICAL SUPPLY | POS. | X | 4 | |||||||||||||
| 1F103 STORAGE, EQUIPMENT | POS. | X | 8680 | 4 | ||||||||||||
| 1F-111 MICU | NEG. | X | 1908 | 12 | ||||||||||||
| 1F-132 MICU | NEG. | X | 740 | 12 | ||||||||||||
| 1F137 SOILED LINEN | NEG. | X | 1001 | 6 | ||||||||||||
| 1F139 STORAGE, GENERAL, EQUIPMENT/Consultation Room | POS. | X | 847 | 6 | ||||||||||||
| 1F144A Linen Room | POS. | X | 917 | 4 | ||||||||||||
| 1F145 UTILITY ROOM, CLEAN SUPPLIES | POS. | X | 1444 | 4 | ||||||||||||
| 1F-146 SOILED UTILITY | NEG. | X | 916 | 6 | ||||||||||||
| 2A-100 SOILED CART | NEG. | X | 1962 | 6 | ||||||||||||
| 2A-124 SPD CLEAN DISPATCH ROOM | POS. | X | 2833 | 4 | ||||||||||||
| 2A-126 SOILED UTILITY | NEG. | X | 1568 | 6 | ||||||||||||
| 2A-127 TRASH | NEG. | X | 1024 | 10 | ||||||||||||
| 2B-112 OR 1 CC | POS. | X | 3800 | 20 | ||||||||||||
| 2B-113 OR 2 CC | POS. | X | 3841 | 20 | ||||||||||||
| 2B-116 OR 3 CC | POS. | X | 6280 | 20 | ||||||||||||
| 2B-119 OR 4 CC | POS. | X | 5440 | 20 | ||||||||||||
| 2B-120 OR 5 CC | POS. | X | 5774 | 20 | ||||||||||||
| 2B-122 OR 6 CC/STORAGE | POS. | X | 4710 | 20 | ||||||||||||
| 2B-125 OR 7 CC | POS. | X | 3836 | 20 | ||||||||||||
| 2B-126 OR 8 CC | POS. | X | 3836 | 20 | ||||||||||||
| 2B-128B CLEAN LINEN | POS. | X | 288 | 4 | ||||||||||||
| 2B-132 OR 9 CC | POS. | X | 5740 | 20 | ||||||||||||
| 2B-134 OR 11 CC (Storage) | POS. | X | 3183 | 20 | ||||||||||||
| 2B-136 OR DECON | POS. | X | 1375 | 4 | ||||||||||||
| 2B-136 STERILE INTRUMENTS | POS. | N/A | X | N/A | 4 | |||||||||||
| 2B-138 ANESTHESIA WORK ROOM | POS. | X | 4839 | 4 | ||||||||||||
| 2B-142 OR CLEAN CORE NORTH | POS. | X | 10694 | 4 | ||||||||||||
| 2B-142 OR CLEAN CORE SOUTH | POS. | X | 10694 | 4 | ||||||||||||
| 2B-146 EQUIPMENT STORAGE | POS. | X | 786 | 4 | ||||||||||||
| 2B-147 MEDICINE STORAGE | POS. | X | 675 | 4 | ||||||||||||
| 2B-150 MED ROOM | POS. | X | 1003 | 4 | ||||||||||||
| 2B-183 CLEAN EQUIPMENT | POS. | X | 1346 | 4 | ||||||||||||
| 2B-185 SOILED UTILITY | NEG. | X | 585 | 6 | ||||||||||||
| 2B-186 EMS CLOSET IN PACU | POS. | X | 250 | 4 | ||||||||||||
| 2B-191 CLEAN LINEN | POS. | X | 270 | 4 | ||||||||||||
| 2B-193 MED ROOM | POS. | X | 573 | 4 | ||||||||||||
| 2C115 SOILED LINEN/UTILITY | NEG. | X | 742 | 6 | ||||||||||||
| 2C116 CLEAN EQUPMENT | POS. | X | 2620 | 4 | ||||||||||||
| 2C117 CLEAN LINEN | POS. | X | 457 | 4 | ||||||||||||
| 2C-136 SICU (BED 15) | NEG. | X | 1422 | 12 | ||||||||||||
| 2C139 CLEAN STORAGE | POS. | X | 1980 | 4 | ||||||||||||
| 2E-108 AUTOPSY | NEG. | X | 5050 | 12 | ||||||||||||
| 2E-114 MICROBIOLOGY | NEG. | X | - | 6 | ||||||||||||
| 2E-123 BSL 3 - TB LAb | NEG. | X | 2580 | 6 | ||||||||||||
| 2E156 K SOILED UTILITY | NEG. | X | 444 | 6 | ||||||||||||
| 2E156 S CLEAN LINEN AND O2 | POS. | X | 492 | 4 | ||||||||||||
| 2E-162 OR 13 | POS. | X | 3132 | 20 | ||||||||||||
| 2E-165 OR 14 | POS. | X | 3157 | 20 | ||||||||||||
| 2E-166 OR 15 | POS. | X | 3132 | 20 | ||||||||||||
| 2E-169 OR 16 | POS. | X | 3132 | 20 | ||||||||||||
| 4A124 MSD SUPPLIES | POS. | X | 4672 | 4 | ||||||||||||
| 4A127 Trash | NEG. | 689 | 10 | |||||||||||||
| 4A128 SOILED LINEN | NEG. | X | 832 | 6 | ||||||||||||
| 4B107 CLEAN EQUIPMENT | POS. | X | 4446 | 4 | ||||||||||||
| 4B109 SOILED UTILITY | NEG. | X | 787 | 6 | ||||||||||||
| 4B120 LINEN | POS. | X | 356 | 4 | ||||||||||||
| 4B120A LINEN | POS. | X | 347 | 4 | ||||||||||||
| 4B160 SUPPLY STORAGE | POS. | X | 311 | 4 | ||||||||||||
| 4C103 SUPPLY STORAGE | POS. | X | 350 | 4 | ||||||||||||
| 4C 108 (A) | Neg | X | 12 | |||||||||||||
| 4C 112 (A) | Neg | X | 12 | |||||||||||||
| 4C 120 (A) | Neg | X | 12 | |||||||||||||
| 4C 126 (A) | Neg | X | 12 | |||||||||||||
| 4C142 LINEN | POS. | X | 486 | 4 | ||||||||||||
| 4C144 SOILED UTILITY | NEG. | X | 1664 | 6 | ||||||||||||
| 4D109 SOILED UTILITY | NEG. | X | 853 | 6 | ||||||||||||
| 4D-116 - AIRBORNE ISOLATION | NEG. | X | 1745 | 12 | ||||||||||||
| 4D-117- AIRBORNE ISOLATION | NEG. | X | 1745 | 12 | ||||||||||||
| 4D120 LINEN | POS. | X | 344 | 4 | ||||||||||||
| 4D120A CLEAN STORAGE | POS. | X | 344 | 4 | ||||||||||||
| 4D-123- AIRBORNE ISOLATION | NEG. | X | 2116 | 12 | ||||||||||||
| 4D-127- AIRBORNE ISOLATION | NEG. | X | 2116 | 12 | ||||||||||||
| 4D136 CLEAN EQUIPMENT | POS. | X | 2904 | 4 | ||||||||||||
| 4D160 UROLOGY MEDICAL SUPPLY | POS. | X | 311 | 4 | ||||||||||||
| 4E142A CLEAN SUPPLIES | POS. | X | 336 | 4 | ||||||||||||
| 5A108 RESPIRATORY STORAGE | POS. | X | 797 | 4 | ||||||||||||
| 5A126 MSD SUPPLIES | POS. | X | 4655 | 4 | ||||||||||||
| 5A128 SOILED LINEN | NEG. | X | 512 | 4 | ||||||||||||
| 5A129 TRASH ROOM | NEG. | X | 693 | 10 | ||||||||||||
| 5B -117 BRONCHOSCOPY/PROCEDURE #6 | NEG. | X | 2545 | 12 | ||||||||||||
| 5B-115 MEDICAL SUPPLY | POS. | X | 2054 | 4 | ||||||||||||
| 5B124 SCOPES/5B118A Scope | POS. | X | 7000 | 4 | ||||||||||||
| 5B-129 BRONCHOSCOPY FLUORO | NEG. | X | 4167 | 12 | ||||||||||||
| 5B159 SOILED UTILITY | NEG. | X | 368 | 6 | ||||||||||||
| 5B-161 RECOVERY/ISO ROOM | NEG. | X | 1010 | 12 | ||||||||||||
| 5B169 LINEN | POS. | X | 287 | 4 | ||||||||||||
| 5C-104 CATH LAB/Cardiac Procedure | POS. | X | 4825 | 15 | ||||||||||||
| 5C111A SUPPLY STORAGE | POS. | X | 860 | 4 | ||||||||||||
| 5C120 SUPPLY STORAGE | POS. | X | 751 | 4 | ||||||||||||
| 5C124 CLEAN EQUIPMENT | POS. | X | 909 | 4 | ||||||||||||
| 5C-130 EP LAB | POS. | X | 4330 | 4 | ||||||||||||
| 5C-140 CATH LAB | POS. | X | 5884 | 15 | ||||||||||||
| 5D129 VENTILATOR STORGE | POS. | X | 221 | 4 | ||||||||||||
| 5D132 STORAGE/Exam Treatment | POS. | X | 969 | 4 | ||||||||||||
| 5D145 SOILED UTILITY/Supply Room | Neg/Pos | X | 976 | 6 | ||||||||||||
| 5D148 STORAGE (PAPER, ICE MACHINE) | Neg/Pos | X | 1830 | 4 | ||||||||||||
| 5D149 PUMPS/House keeping aid | Neg/Pos | X | 452 | 4 | ||||||||||||
| 5E101 | Neg | X | 12 | |||||||||||||
| 5E104 MED ROOM | POS. | X | 540 | 4 | ||||||||||||
| 5E105 | Neg | X | 12 | |||||||||||||
| 5E107 | Neg | X | 12 | |||||||||||||
| 5E109 CLEAN EQUIPMENT ROOM | POS. | X | 1728 | 4 | ||||||||||||
| 5E112 | Neg | X | 12 | |||||||||||||
| 5E129 STORAGE | POS. | X | 604 | 4 | ||||||||||||
| 5E137 CLEAN STORAGE/PATIENT SHOWER | POS. | X | 2102 | 4 | ||||||||||||
| 5E141 OMNICELL/MEDICAL SUPPLY | POS. | X | 1120 | 4 | ||||||||||||
| 5E142 LINEN CLEAN EQUIPMENT | POS. | X | 472 | 4 | ||||||||||||
| 5E144 SOILED UTILITY | NEG. | X | 565 | 6 | ||||||||||||
| 6A127 TRASH ROOM | NEG. | X | 676 | 10 | ||||||||||||
| 6A128 SOILED LINEN | NEG. | X | 740 | 6 | ||||||||||||
| 6B120 SOILED UTILITY | NEG. | X | 596 | 6 | ||||||||||||
| 6B122 CLEAN UTILITY | POS. | X | 301 | 4 | ||||||||||||
| 6B128 MEDICAL SUPPLY | POS. | X | 564 | 4 | ||||||||||||
| 6B129 PIXUS | POS. | X | 592 | 4 | ||||||||||||
| 6B131 MED SUPPLY, CLEAN STORAGE | POS. | X | 595 | 4 | ||||||||||||
| 6C103 IV SUPPLY STORAGE | POS. | X | 320 | 4 | ||||||||||||
| 6C104 MED ROOM | POS. | X | 650 | 4 | ||||||||||||
| 6C111 CLEAN EQUIPMENT/DIRTY EQUIPMENT | POS. | X | 1104 | 4 | ||||||||||||
| 6C142 CLEAN UTILITY | POS. | X | 340 | 4 | ||||||||||||
| 6C144 SOILED UTILITY | NEG. | X | 850 | 6 | ||||||||||||
| 6C 146 B | Neg | X | 12 | |||||||||||||
| 6C 146 C | Neg | X | 12 | |||||||||||||
| 6D108A EQUIPMENT, SOME SUPPLY | POS. | X | 612 | |||||||||||||
| 6D109 SOILED UTILITY | NEG. | X | 964 | 6 | ||||||||||||
| 6D119 OMNICELL/PIXUS | POS. | X | 1169 | 4 | ||||||||||||
| 6D120 CLEAN UTILITY | POS. | X | 365 | 4 | ||||||||||||
| 6D134 CLEAN EQUIPMENT | POS. | X | 3600 | 4 | ||||||||||||
| 6D-150- AIRBORNE ISOLATION | NEG. | X | 1479 | 12 | patient | |||||||||||
| 6D-153- AIRBORNE ISOLATION | NEG. | X | 1479 | 12 | patient | |||||||||||
| 6D-157- AIRBORNE ISOLATION | NEG. | X | 1479 | 12 | patient | |||||||||||
| 6D160 IV SUPPLY STORAGE | POS. | X | 320 | 4 | ||||||||||||
| 6D-161- AIRBORNE ISOLATION | NEG. | X | 1479 | 12 | patient | |||||||||||
| 6E104A MED ROOM | POS. | X | 320 | 4 | ||||||||||||
| 6E142 CLEAN LINEN | POS. | X | 350 | 4 | ||||||||||||
| 6E142A FAMILY LAUNDRY | POS. | X | 350 | 4 | ||||||||||||
| 6E144 SOILED UTILITY | NEG. | X | 858 | 6 | ||||||||||||
| 7A-124 CLEAN UTILITY/LIVER PROGRAM | POS. | X | 1221 | 4 | ||||||||||||
| 7A-135 TRASH ROOM | NEG. | X | 676 | 10 | ||||||||||||
| 7A-136 SOILED UTILITY | NEG. | X | 846 | 6 | ||||||||||||
| 7A140 SOILED UTILITY | NEG. | X | 831 | 6 | ||||||||||||
| 7B-121 CLEAN UTILITY, SUPPLIES | POS. | X | 510 | 4 | ||||||||||||
| 7C104 SOILED UTILITY | NEG. | X | 846 | 6 | ||||||||||||
| 7C119 CLEAN SUPPLIES | POS. | X | 575 | 4 | ||||||||||||
| GA-101 SOILED UTILITY | NEG. | X | 1411 | 6 | ||||||||||||
| GA-108 TRASH ROOM | Neg/Pos | X | 1687 | 10 | ||||||||||||
| GD-102 CLEAN STORAGE | POS. | X | 3978 | 6 | ||||||||||||
| GD-136 | X | 7318 | ||||||||||||||
| GD-137 SOILED UTILITY | NEG. | X | 1336 | 6 | ||||||||||||
| Pharmacy LR | ||||||||||||||||
| 1B123 PIXUS/CLEAN EQUIPMENT/CLEAN UTILITY | POS. | X | 624 | 4 | x | x | ||||||||||
| 1B152 MED SUPPLY ROOM | POS. | X | 681 | 4 | x | x | ||||||||||
| 1C184A/1C126 CLEAN UTILITY | POS. | X | 464 | 4 | x | x | ||||||||||
| LR1C180XT | x | x | x | |||||||||||||
| LR1C224XT | x | x | x | |||||||||||||
| LR1E100CXT | x | x | x | |||||||||||||
| LR1E168XT | x | x | x | |||||||||||||
| 1E177E.RPM-A | x | x | x | |||||||||||||
| 1E177E.RPM-B | x | x | x | |||||||||||||
| 1E177F.RPM-A | x | x | x | |||||||||||||
| 1E177F.RPM-B | x | x | x | |||||||||||||
| LR1E184AXT | x | x | x | |||||||||||||
| LR1F153XT | x | x | x | |||||||||||||
| 1F157 MEDS, OMNICELL | POS. | X | 875 | 4 | x | x | ||||||||||
| LR2B186XT | x | x | x | |||||||||||||
| 2C138 MED ROOM | POS. | X | 945 | 4 | x | x | ||||||||||
| LR2D122XT | x | x | x | |||||||||||||
| LR2D145XT | x | x | x | |||||||||||||
| 2E157 F CLEAN MED/EQUIPMENT | POS. | X | 680 | 4 | x | x | ||||||||||
| 2F206.RPM1 | x | x | x | |||||||||||||
| 2F206.RPM2 | x | x | x | |||||||||||||
| LR2F225XT | x | x | x | |||||||||||||
| 4B136 OMNICELL/PIXUS | POS. | X | 1496 | 4 | x | x | ||||||||||
| 4B159 MED ROOM | POS. | X | 480 | 4 | x | x | ||||||||||
| 4C104 MED ROOM | POS. | X | 400 | 4 | x | x | ||||||||||
| 4C141 OMNICELL/PIXUS | POS. | X | 1143 | 4 | x | x | ||||||||||
| LR4D105XT | x | x | x | |||||||||||||
| 4D108 MED ROOM | POS. | X | 972 | 4 | x | x | ||||||||||
| LR5B117XT | x | x | x | |||||||||||||
| 5B137 MSD SUPPLIES | POS. | X | 255 | 4 | x | x | ||||||||||
| 5B158 MED ROOM | POS. | X | 553 | 4 | x | x | ||||||||||
| LR5C119AXT | x | x | x | |||||||||||||
| LR5C127XT | x | x | x | |||||||||||||
| LR5C135XT | x | x | x | |||||||||||||
| LR5D144AXT | x | x | x | |||||||||||||
| 6B134 MED ROOM | POS. | X | 620 | 4 | x | x | ||||||||||
| 6C141 OMNICELL/PIXUS | POS. | X | 1140 | 4 | x | x | ||||||||||
| LR6D136AXT | x | x | x | |||||||||||||
| 6D159 MED ROOM | POS. | X | 320 | 4 | x | x | ||||||||||
| 6E141 CLEAN EQUIPMENT | POS. | X | 677 | 4 | x | x | ||||||||||
| 6E141A OMNICELL/PIXUS | POS. | X | 462 | 4 | x | x | ||||||||||
| 7A111 | x | x | x | |||||||||||||
| 2B135 ANES1 | x | x | x | |||||||||||||
| 2B135 ANES2 | x | x | x | |||||||||||||
| 2B135 ANES3 | x | x | x | |||||||||||||
| ED 1D126 | x | x | x | |||||||||||||
| ED 1D105 | x | x | x | |||||||||||||
| LRGB154XT | x | x | x | |||||||||||||
| GC189A.RPM | x | x | x | |||||||||||||
| GC189B.RPM | x | x | x | |||||||||||||
| 7D126 | x | x | x | |||||||||||||
| OR 2B150 | x | x | x | |||||||||||||
| 7D129 | x | x | x | |||||||||||||
| 7D137 | x | x | x | |||||||||||||
| 7D133 | Pos | x | 20 | x | x | |||||||||||
| 7D133A | Pos | x | 30 | x | x | |||||||||||
| 7D132 | Pos | x | 30 | x | x | |||||||||||
| 7D132A | Neg | x | 30 | x | x | |||||||||||
| 7D125 | Neg | x | 12 | x | x | |||||||||||
| 7D124 | Pos | x | 30 | x | x | |||||||||||
| 7D124A | Neg | x | 30 | x | x | |||||||||||
| GB189 | x | x | x | |||||||||||||
| GB126 | x | x | x | |||||||||||||
| 1D101 | x | x | x | |||||||||||||
| 1D100 | x | x | x | |||||||||||||
| New | ||||||||||||||||
| APM01 - GD122 ENTRY | x | |||||||||||||||
| APM02 - GD124 | x | |||||||||||||||
| APM03 - GE113 MAIN ENTRY | x | |||||||||||||||
| APM04 - GD125 ENTRY | x | |||||||||||||||
| APM05 - GE114 | x | |||||||||||||||
| APM06 - GE113 SIDE ENTRY | x | |||||||||||||||
| APM07 - GE113B STERILE DURABLES | x | |||||||||||||||
| APM08 - GE112A | x | |||||||||||||||
| APM09 - GE112 | x | |||||||||||||||
| APM10 - GE111 MAIN ENTRY | x | |||||||||||||||
| APM11 - GE110A | x | |||||||||||||||
| APM12 - GE114 JANITOR | x | |||||||||||||||
| APM13 - GE114 LOADING DOCK | x | |||||||||||||||
| APM14 - GE107 TO GE111 | x | |||||||||||||||
| APM15 - GE111 SIDE ENTRY | x | |||||||||||||||
| APM16 - GE110 | x | |||||||||||||||
| APM17 - GE109 ENTRY | x | |||||||||||||||
| APM18 - GE108 ENTRY | x | |||||||||||||||
| APM19 - GE107F | x | |||||||||||||||
| APM20 - GE107F MENS RR | x | |||||||||||||||
| APM21 - GE107E | x | |||||||||||||||
| APM22 - GE107 ENTRY | x | |||||||||||||||
| APM23 - GE107 | x | |||||||||||||||
| APM24 - GE107B ENTRY | x | |||||||||||||||
| APM25 - GE107B | x | |||||||||||||||
| APM26 - GE107C | x | |||||||||||||||
| APM27 - GE111 TO GE112 | x | |||||||||||||||
| APM28 - GE107 TO GE112 | x | |||||||||||||||
| APM29 - GE107E TO GE111 | x | |||||||||||||||
| 5A130 | x | |||||||||||||||
| 5B ALCOVE RM APM | x | |||||||||||||||
| 5B DECON TRANSFER APM | x | |||||||||||||||
| 5B HALL TRANSFER APM | x | |||||||||||||||
| 5B SCOPE PROCESSING APM | x | |||||||||||||||
| 5B SCOPE STORAGE APM | x | |||||||||||||||
| 5B SCOPE STORAGE TRANSFER APM | x | |||||||||||||||
| 5C143 | x | |||||||||||||||
| 6C103A | x | |||||||||||||||
| 4D125 | x | |||||||||||||||
| 5D128 | x | |||||||||||||||
| 5D133 | x | |||||||||||||||
| 5D140 | x | |||||||||||||||
| 5D168 | x | |||||||||||||||
| 5D169 | x | |||||||||||||||
| 5D171 | x | |||||||||||||||
| 4C108.RPM | x | |||||||||||||||
| 4C108A.RPM | x | |||||||||||||||
| 4C112.RPM | x | |||||||||||||||
| 4C112A.RPM | x | |||||||||||||||
| 4C120.RPM | x | |||||||||||||||
| 4C120A.RPM | x | |||||||||||||||
| 4C126.RPM | x | |||||||||||||||
| 4C126A.RPM | x | |||||||||||||||
| 6C146C.RPM | x | |||||||||||||||
| 6C146D.RPM | x | |||||||||||||||
| 1E182RPMA | x | |||||||||||||||
| 1E182RPMB | x | |||||||||||||||
| 1E177E.RPM-A | x | |||||||||||||||
| 1E177E.RPM-B | x | |||||||||||||||
| 1E177F.RPM-A | x | |||||||||||||||
| 1E177F.RPM-B | x | |||||||||||||||
| 1F113.RPM | x | |||||||||||||||
| 1F131.RPC | x | |||||||||||||||
| 2F201.RPM2 | x | |||||||||||||||
| 2F CORRODOR.RPM | x | |||||||||||||||
| 2F229.RPM2 | x | |||||||||||||||
| 2F227.RPM2 | x | |||||||||||||||
| 2F213.RPM1 | x | |||||||||||||||
| 2F211.RPM1 | x | |||||||||||||||
| 2F201.RPM1 | x | |||||||||||||||
| 2F229.RPM1 | x | |||||||||||||||
| 2F227.RPM1 | x | |||||||||||||||
| 2F CORRODOR1.RPM | x | |||||||||||||||
| 2F213.RPM2 | x | |||||||||||||||
| 2F111.RPM2 | x | |||||||||||||||
| 2B-132 OR 9 SC | POS. | x | 20 | |||||||||||||
| 2B-116 OR 3 SC | POS. | x | 20 | |||||||||||||
| 2B-119 OR 4 SC | POS. | x | 20 | |||||||||||||
| 2B-120 OR 5 SC | POS. | x | 20 | |||||||||||||
| 2B-112 OR 1 SC | POS. | x | 20 | |||||||||||||
| 2B-113 OR 2 SC | POS. | x | 20 | |||||||||||||
| 2B-122 OR 6 SC/STORAGE | POS. | x | 20 | |||||||||||||
| 2B-125 OR 7SC | POS. | x | 20 | |||||||||||||
| 2B-126 OR 8 SC | POS. | x | 20 | |||||||||||||
| 2B-134 OR 11 SC (Storage) | POS. | x | 20 | |||||||||||||
| 2B-116 OR 3 SC CONTROL ROOM | POS. | x | 20 | |||||||||||||
| 2B-119 OR 4 SC PUMP TECH | POS. | x | 20 | |||||||||||||
| NLR | ||||||||||||||||
| 170 1B127 Supply Room | POS. | X | 613 | 4 | ||||||||||||
| 170 1B140A Soiled Utility (BioHaz) | NEG. | X | 380 | 6 | ||||||||||||
| 170 1B165 Linen Room | POS. | X | 1053 | 4 | ||||||||||||
| 170 1C140A Soiled Utility (BioHaz) | NEG. | X | 525 | 6 | ||||||||||||
| 170 1D102 Supply Room | POS. | X | 1577 | 4 | ||||||||||||
| 170 1D120 Soiled Utility (BioHaz) | NEG. | X | 408 | 6 | ||||||||||||
| 170 1D147 Linen Room | POS. | X | 470 | 4 | ||||||||||||
| 170 1E112 Linen Room | POS. | X | 1258 | 4 | ||||||||||||
| 170 1E120 Soiled Utility (BioHaz) | NEG. | X | 6 | |||||||||||||
| 170 1E124 Supply Room | POS. | X | 610 | 4 | ||||||||||||
| 170 1H114 Soiled Utility (BioHaz) | NEG. | X | 6 | |||||||||||||
| 170 1H141 Unit Supply | POS. | X | 4 | |||||||||||||
| 170 1H143 Clean Linen | POS. | X | 360 | 4 | ||||||||||||
| 170 1J143 Storage (clean) | POS. | X | 370 | 4 | ||||||||||||
| 170 2B102 | POS. | X | 1300 | 4 | patient | |||||||||||
| 170 2B104 | POS. | X | 1473 | 4 | ||||||||||||
| 170 2B104A | POS. | X | 1440 | 4 | patient | |||||||||||
| 170 2B108 | POS. | X | 1440 | 4 | ||||||||||||
| 170 2B113 Supply Room | POS. | X | 2790 | 4 | ||||||||||||
| 170 2B116 Soiled Utility (BioHaz) | NEG. | X | 902 | 6 | ||||||||||||
| 170 2B122 Clean Utility | POS. | X | 1305 | 4 | ||||||||||||
| 170 2B124 | POS. | X | 4000 | 4 | ||||||||||||
| 170 2B125 | POS. | X | 1645 | 4 | ||||||||||||
| 170 2B127 | POS. | X | 1956 | 4 | ||||||||||||
| 170 2B130 | POS. | X | 2760 | 4 | ||||||||||||
| 170 2B131 | POS. | X | 1805 | 4 | ||||||||||||
| 170 2B132 | POS. | X | 2387 | 4 | ||||||||||||
| 170 2B135 | NEG | X | 2130 | 4 | ||||||||||||
| 170 2B138 | POS. | X | 4160 | 4 | ||||||||||||
| 170 2B139 | POS. | X | 927 | 4 | ||||||||||||
| 170 2B141 | POS. | X | 4360 | 4 | ||||||||||||
| 170 2B141A(OFFICE) | POS. | X | 3878 | 4 | ||||||||||||
| 170 2B142 | POS. | X | 3572 | 4 | patient | |||||||||||
| 170 2B145 | POS. | X | 1524 | 4 | ||||||||||||
| 170 2B147 | POS. | X | 1995 | 4 | ||||||||||||
| 170 2B148 | POS. | X | 2810 | 4 | ||||||||||||
| 170 2B150 | POS. | X | 2717 | 4 | ||||||||||||
| 170 2B151 | POS. | X | 1756 | 4 | ||||||||||||
| 170 2B153 | POS. | X | 1586 | 4 | ||||||||||||
| 170 2B156 | POS. | X | 3572 | 4 | patient | |||||||||||
| 170 2C139 Linen | POS. | X | 370 | 4 | ||||||||||||
| 170 2E120 Unit Supply | POS. | X | 490 | 4 | ||||||||||||
| 170 2E139 Linen | POS. | X | 370 | 4 | ||||||||||||
| 170 2J141 Unit Supply | POS. | X | 370 | 4 | ||||||||||||
| 170 2J143 Linen Room | POS. | X | 370 | 4 | ||||||||||||
| 170 2K143 Linen Room | POS. | X | 370 | 4 | ||||||||||||
| 170 2L139 Unit Supply | POS. | X | 370 | 4 | ||||||||||||
| 170 2L141 Clean Linen | POS. | X | 370 | 4 | ||||||||||||
| 170 3B123 Soiled Utility | Neg/Pos | X | 753 | 6 | ||||||||||||
| 170 3B125 Clean Supply | POS. | X | 861 | 4 | ||||||||||||
| 170 3C137 Soiled Utility (BioHaz) | Neg/Pos | X | 404 | 6 | ||||||||||||
| 170 3C139 Clean Linen | POS. | X | 402 | 4 | ||||||||||||
| 170 3C141 Omni Cell Supply | POS. | X | 1129 | 4 | ||||||||||||
| 170 3D124(a) Speech Pathology (scopes) | POS. | X | 1546 | 4 | ||||||||||||
| 170 3D141 Clean Supply | POS. | X | 475 | 4 | ||||||||||||
| 170 3D144 Soiled Utility | NEG. | X | 835 | 6 | ||||||||||||
| 170 3E134A Storage (general) - no sign | POS. | X | 425 | 4 | ||||||||||||
| 170 3E144 Clean Utility (supply) | POS. | X | 600 | 4 | ||||||||||||
| 170 3E156 Soiled Linen (BioHaz) | NEG. | X | 512 | 6 | ||||||||||||
| 170 3H141 Clean Linen | POS. | X | 325 | 4 | ||||||||||||
| 170 3H143 Supply Room | POS. | X | 325 | 4 | ||||||||||||
| 170 3J141 Storage (clean supply) | POS. | X | 325 | 4 | ||||||||||||
| 170 3J156 Specimin Processing Lab | POS. | X | 4337 | 4 | ||||||||||||
| 170 3K141 Unit Supply | POS. | X | 360 | 4 | ||||||||||||
| 170 3K143 Clean Linen | POS. | X | 372 | 4 | ||||||||||||
| 170 3L121 Soiled Utility (BioHaz) | NEG. | X | 403 | 6 | ||||||||||||
| 170 3L139 Unit Supply | POS. | X | 369 | 4 | ||||||||||||
| NLR SPS | ||||||||||||||||
| 170 GK 120 SPS RESTROOM | NEG. | X | 558 | 10 | ||||||||||||
| 170 GK125 SPS Decon | NEG. | X | 1081 | 6 | ||||||||||||
| 170 GK126 SPS Prep | POS. | X | 535 | 4 | ||||||||||||
| 170 GK121 SPS ANTE | POS. | X | 1381 | 4 | ||||||||||||
| NLR Pharmacy | ||||||||||||||||
| 1B120 | x | x | x | |||||||||||||
| 1C144 | x | x | x | |||||||||||||
| 1C166 | x | x | x | |||||||||||||
| 1D145 | x | x | x | |||||||||||||
| 1E140. | x | x | x | |||||||||||||
| 1H101 | x | x | x | |||||||||||||
| 1H120 | x | x | x | |||||||||||||
| 1L116 | x | x | x | |||||||||||||
| 2B154 | x | x | x | |||||||||||||
| 2D138 | x | x | x | |||||||||||||
| 2J120 | x | x | x | |||||||||||||
| 3B-151 | x | x | x | |||||||||||||
| 3D-147 | x | x | x | |||||||||||||
| 3E136. | x | x | x | |||||||||||||
| 3K-101 | x | x | x | |||||||||||||
| 3K-120 | x | x | x | |||||||||||||
| 66-RM-108 | x | x | x | |||||||||||||
| 66-RM-23 | x | x | x | |||||||||||||
| 66-RM-45 | x | x | x | |||||||||||||
| 66-RM-45 | x | x | x | |||||||||||||
| GB-105B | x | x | x | |||||||||||||
| 3F-111 | x | x | x | |||||||||||||
| 2F-111 | x | x | x | |||||||||||||
| 3L-141 | x | x | x | |||||||||||||
| 1C-119 | x | x | x | |||||||||||||
| GE-114a | ||||||||||||||||
| GE-114B | x | x | x | |||||||||||||
| 2G-103A | x | x | x | |||||||||||||
| 3L-141 | x | x | x | |||||||||||||
| 2C-120 | x | x | x | |||||||||||||
| 66-RM-149 | x | x | x | |||||||||||||
| 66-RM-150 | x | x | x | |||||||||||||
| B 66 NLR | ||||||||||||||||
| B66 Room 10 (eye clinic) | POS. | X | 997 | 4 | ||||||||||||
| B66 Room 139 (podiatry) Soiled Utility (BioHaz) | NEG. | X | 715 | 6 | ||||||||||||
| B66 Room 141 (podiatry) Medical Supply | POS. | X | 1240 | 4 | ||||||||||||
| B66 Room 18 (eye clinic) Procedure Room | POS. | X | 1202 | 4 | ||||||||||||
| B66 Room 6 (eye clinic) Houskeeping Aid Closet (Biohaz) | NEG. | X | 308 | 4 |