This is a Sources Sought Notice (RFI) issued by the Department of Veterans Affairs, Network Contracting Office 16, for market research purposes to identify qualified contractors for chiller maintenance and monitoring services at the Michael E. DeBakey VA Medical Center in Houston, Texas. The solicitation number is 36C25626Q0399, with responses due by February 23, 2026, at 2:00 PM Central Time. The government anticipates awarding a one-time, Firm-Fixed Price contract and is specifically seeking Service Disabled Veteran Owned Small Businesses (SDVOSBs) and Veteran Owned Small Businesses (VOSBs) certified under NAICS code 238220, though all qualified firms are encouraged to respond if no SDVOSBs or VOSBs possess sufficient capacity.
The scope requires 24/7 remote monitoring, maintenance, inspection, and reporting for multiple chiller systems and associated equipment including nine centrifugal/air chillers (primarily YORK brand), cooling towers, condenser pumps, chiller pumps, tank pumps, and VFDs. The contractor must provide all labor, supervision, parts, equipment, supplies, materials, transportation, management, and OEM-trained personnel to perform full diagnostic services, preventative maintenance, routine repairs, and emergency repairs in accordance with manufacturer operation and maintenance manuals and industry standards. The equipment maintenance schedule requires annual, semi-annual, quarterly, and monthly inspections across multiple building locations (B104, B104A, B109, B100, and B108). Interested firms should submit a positive statement of interest, small business category identification, capability statement, company information including SAM UEI and CAGE number, and primary point of contact to Felicia Lovelady at felicia.lovelady@va.gov, limited to three pages. Responses to this RFI are for information purposes only and do not constitute a binding offer or commitment by the government.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SUBJECT*
Chiller System 24/7 Remote Monitoring, Maintenance and Inspection
GENERAL INFORMATION
| CONTRACTING OFFICE’S ZIP CODE* |
| 71306-9004 |
| SOLICITATION NUMBER* |
| 36C25626Q0399 |
| RESPONSE DATE/TIME/ZONE |
| 02-23-2026 14:00 CENTRAL TIME, CHICAGO, USA |
| ARCHIVE |
| 60 DAYS AFTER THE RESPONSE DATE |
| RECOVERY ACT FUNDS |
| N |
SET-ASIDE
| PRODUCT SERVICE CODE* |
| J041 |
| NAICS CODE* |
| 238220 |
| CONTRACTING OFFICE ADDRESS |
| ALEXANDRIA VA HEALTH CARE SYSTEM |
NETWORK CONTRACTING OFFICE 16
ALEXANDRIA VA HEALTH CARE SYSTEM
PO BOX 69004
ALEXANDRIA LA 71306-9004
POINT OF CONTACT*
FELICIA LOVELADY
FELICIA.LOVELADY@VA.GOV
PLACE OF PERFORMANCE
| ADDRESS |
| DEPARTMENT OF VETERANS AFFAIRS |
MICHAEL E DEBAKEY VAMC
2002 HOLCOMBE BLVD
HOUSTON TEXAS
| POSTAL CODE |
| 77030 |
| COUNTRY |
| USA |
ADDITIONAL INFORMATION
AGENCY’S URL
URL DESCRIPTION
AGENCY CONTACT’S EMAIL ADDRESS
EMAIL DESCRIPTION
DESCRIPTION
Sources Sought Notice for Chiller Maintenance and Monitoring Services at the Houston VAMC.
Sources Sought Notice Sources Sought Notice
| *= Required Field |
| Sources Sought Notice |
Sources Sought Notice
Released pursuant to Federal Acquisition Regulation (FAR) Part 10: Market Research, this is a Request for Information.
Purpose: Department of Veterans Affairs – Chiller Maintenance Services
In an effort to enhance opportunities for Service Disabled Veteran Owned Small Businesses (SDVOSB) as required by Public Law 109-461, specifically the Veterans First Contracting Program, NCO16 is performing preliminary market research to identify interested, qualified, capable, SDVOSB and VOSB firms possessing the capacity necessary to compete for a VHA procurement opportunity. In case no SDVOSBs or VOSBs possess the capacity, all firms possessing the necessary capacity are encouraged to provide a response.
Results of the preliminary market research will be used to determine the potential future solicitation’s set-aside requirement.
This source sought notice is issued solely for informational, market research, and planning purposes. It does not constitute an Invitation for Bid (IFB), Request for Quote (RFQ), Request for Proposal, or a promise to issue a subsequent RFQ/IFB/RFP. Currently, no solicitation document exists. Issuance of this notice does not establish any obligation on the part of the Government and is not to be construed as a commitment by the Government, implied or otherwise, to issue a solicitation or award a contract. In addition, respondents are advised that the United States Government is under no obligation to pay for any information or administrative cost incurred in response to this notice. At this time, proprietary information is not being requested. Respondents shall refrain from including proprietary information in responses to this notice.
The Department of Veterans Affairs anticipates awarding a one-time, Firm-Fixed Price (FFP) Contract.
1. Scope Summary:
The Department of Veterans Affairs, Network Contracting Office 16 (NCO 16) has a requirement for Chiller Maintenance Services for the Houston VAMC. Contractor shall provide all labor, supervision, parts, equipment, supplies, facilities, tools, materials, transportation, management, and personnel required for performing 24/7 remote monitoring, maintenance, inspection and reporting; according to the manufacturers Operation and Maintenance (O&M) manual's recommendation of the centrifugal/ air chillers, cooling towers, tower fans, condenser pumps, primary and secondary chiller pumps, cool water storage tank pumps, and VFDs (chiller system).
The contractor shall provide full diagnostic, maintenance, and limited routine and emergency repairs to include preventative maintenance for Government owned chiller systems located at the MEDVAMC in Houston, Texas. Service shall include all parts, labor, transportation, OEM trained personnel, supervision, materials, supplies, training and all other associated costs. Contractor shall inspect, test, calibrate and service the equipment, as required in accordance with OEM manufacturer, industry, and statutory requirements, in order to prevent premature equipment failures and to extend equipment life.
**SEE ATTACHED LIST OF EQUIPMENT**
Requested Information:
1. Please provide a positive statement of interest in submitting a quote based on the general scope summary above.
2. Please identify your firm’s small business category. If your firm is either SDVOSB or VOSB, please state whether you are currently certified as such on SBA.gov based upon North American Industry Classification System code (NAICS) 238220.
3. Please provide a capability statement. Describe your firm’s in-house capability and authorization from OEM to accomplish the summarized scope/goal.
4. Please state your firm's name, address, SAM UEI and CAGE number, and primary point of contact, including telephone number(s) and email address.
Response Submission:
Please submit your information via email to Felicia Lovelady, Contracting Officer at felicia.lovelady@va.gov, by the closing date and time listed. Please limit your responses to three (3) pages and please include the following as the subject line of your email: 36C25626Q0399 – CHILLER MAINTENANCE SERVICES - SOURCES SOUGHT RESPONSE
Please do not include advertising or promotional materials.
DISCLAIMER
This RFI is issued solely for information and planning purposes only and does not constitute a solicitation. All information received in response to this RFI that is marked as proprietary will be handled accordingly. Responses to this notice are not offers and cannot be accepted by the Government to form a binding contract. Responders are solely responsible for all expenses associated with responding to this RFI.
Page 1 of
Page 1 of
CHILLER EQUIPMENT MAINTENANCE SCHEDULE
Equipme nt
Location
Make
Model
SN
An n.
Se mi- An n.
Qu ar.
Mont hly
| Chiller #1 |
| Bl04 |
| YORK |
| YKPQPKl-CYG |
| SGBM- 006390 |
| X |
| X |
X
| Chiller #2 |
| Bl04 |
| YORK |
| YKPQPKl-CYG |
| SNXM- |
143460
| X |
| X |
X
| Chiller #3 |
| Bl04 |
| YORK |
| YKPQPKl-CYG |
| SNXM- 142730 |
| X |
| X |
X
| Chiller #4 |
| Bl04 |
| YORK |
| YKPQPKl-CYG |
| SNXM- 142920 |
| X |
| X |
X
| Chiller #5 |
| Bl04 |
| YORK |
| YKPQPKl-CYG |
| SNXM- |
143280
| X |
| X |
X
| Chiller #6 |
| B104 |
| YORK |
| YKPQPKl-CYG |
| SNXM- 14310 |
| X |
| X |
X
| Chiller #7 |
| B104 |
| YORK |
| YKPQPK 1-CYG |
| SMXM- |
142550
| X |
| X |
X
| Chiller #8 |
| Bl04A |
| YORK |
| HHHB J2DCES |
| SALM- |
613720
| X |
| X |
X
| Chiller #9 |
| B104A |
| YORK |
| HHHB J2DCES |
| SALM- 613850 |
| X |
| X |
X
| Chiller #1 |
| Bl09 |
| YORK |
| YKCFQ7CNF |
| SHPM- 928930 |
| X |
| X |
X
| Chiller #2 |
| Bl09 |
| YORK |
| YKEPERQ7-CNG |
| SFTM- |
990250
| X |
| X |
X
| Chiller #3 |
| Bl09 |
| YORK |
| SKPM-975570 |
| SKPM- |
975570
| X |
| X |
X
| OR Chiller #1 |
| Roof B100 |
YORK
| YCAS0140EC46 XGASDTXXBXX L |
| RKMM006 559 |
X
| OR Chiller #2 |
| Roof B100 |
YORK
YCAS0140EC46 XGASDTXXBXX
L
RKMM006 560
BIOS
Chiller #1
| B108 |
| YORK |
| YLAA0080SE46 XA |
| SGTM- 022950 |
| X |
| X |
X
BIOS
Chiller #2
| B108 |
| YORK |
| YLAA0150EE46 XCA |
| SGTM- 022951 |
| X |
| X |
X
| UPS Back Up AC |
| Tunnel BI00 |
| LIEBERT |
| ET0607RAEOTA 773 |
| Yl3LH500 92 |
| X |
| X |
X
| Chiller Pump #1 |
| Bldg. 104 |
| BALDOR |
| NA |
| Cl4030313 17 |
| X |
| X |
| X |
| X |
| Chiller Pump #2 |
| Bldg. 104 |
| BALDOR |
| NA |
| Cl3071513 62 |
| X |
| X |
| X |
| X |
| Chiller Pump #3 |
| Bldg. 104 |
| BALDOR |
| NA |
| Cl6042814 02 |
| X |
| X |
| X |
| X |
| Chiller Pump#4 |
| Bldg. 104 |
| BALDOR |
| NA |
| Cl6051014 37 |
| X |
| X |
| X |
| X |
| Chiller Pump#5 |
| Bldg 104 |
| BALDOR |
| NA |
| Cl3040513 27 |
| X |
| X |
| X |
| X |
| Chiller Pump #6 |
| Bldg 104 |
| BALDOR |
| NA |
| Cl3071513 57 |
| X |
| X |
| X |
| X |
| Chiller Pump #7 |
| Bldg 104 |
| A O Smith Century |
| NA |
| 135178304 |
| X |
| X |
| X |
| X |
| Chiller Pump#8 |
| Bldg 104A |
| A O Smith Century |
| NA |
| BX0I-M |
| X |
| X |
| X |
| X |
| Chiller Pump#9 |
| Bldg 104A |
| Toshiba |
| NA |
| S95049536 |
| X |
| X |
| X |
| X |
| Tank Pump#12 |
| Bldg 104 |
| Baldor |
| NA |
| C1011111118 |
| X |
| X |
| X |
| X |
Tank Pump #13
Bldg 104
Baldor
NA
K018- 2092185R0 27M
X
X
X
X
| Tank Pump#l4 |
| Bldg 104 |
| Baldor |
| NA |
| C13050213 17 |
| X |
| X |
| X |
| X |
| Tank Pump #15 |
| Bldg 104 |
| US Electric |
| NA |
| Cl6030313 32 |
| X |
| X |
| X |
| X |
2nd Chilled WP#8
Bldg 104
Baldor
NA
C16020313 47
X
X
X
X
2nd Chilled WP#9
Bldg 104
Baldor
NA
C08082001 45
X
X
X
X
2nd Chilled WP#l0
Bldg 104
Baldor
NA
Cl3050213 12
X
X
X
X
2nd Chilled WP#11
Bldg 104
Baldor
NA
CI6042514 17
X
X
X
X
| Condenser WP#1 |
| Cooling Tower 104 |
| Emerson |
Sulzer
NA
SI0- 02202659- l00F
X
X
| Condenser WP#2 |
| Cooling Tower 104 |
| Emerson |
Sulzer
NA
S06- 7489295-
X
X
X
X
| Condenser WP#3 |
| Cooling Tower 104 |
| Emerson Sulzer |
NA
S08- 7498814-
X
X
X
X
| Condenser WP#4 |
| Cooling Tower |
Emerson Sulzer
NA
N02- BF61A-M
X
X
X
X
| Condenser WP#5 |
| Cooling Tower 104 |
| Emerson |
Sulzer
NA
U05- 7560856-
X
X
X
X
| Condenser WP#6 |
| Cooling |
Tower 104 Emerson Sulzer
NA
M01-BF61A-M
X
X
X
X
| Condenser WP#7 |
| Cooling Tower |
Emerson Flow Serve
NA
M01- BF61A-M
X
X
X
X
| Condenser WP#8 |
| Cooling Tower 104 |
| U S Electric Flow Serve |
NA
F02- 01019752- L00R
X
X
X
X
| Condenser WP#9 |
| Cooling Tower |
U S Electric Flow Serve
NA
F02- 01019752- J00R
X
X
X
X
| Cooling Tower #1 |
| Cooling Tower |
Composite Cooling Tower
6FT-2421-60
SN9828R
X
X
X
X
| Cooling Tower #2 |
| Cooling |
Tower 104 Composite Cooling Tower
6FT-2421-60
SN9829R
X
X
X
X
| Cooling Tower #3 |
| Cooling Tower |
Composite Cooling Tower
6FT-2421-60
SN9830R
X
X
| X |
| X |
| Cooling Tower #4 |
| Cooling Tower 104 |
| Composite |
Cooling Tower
6FT-2421-60
SN9831R
X
X
X
X
| Cooling Tower #5 |
| Cooling Tower |
Composite Cooling Tower
6FT-2421-60
SN9832R
X
X
X
X
| Cooling Tower #6 |
| Cooling Tower 104 |
| Composite Cooling Tower |
6FT-2421-60
SN9833R
X
X
X
X
| Cooling Tower #7 |
| Cooling |
Tower 104 Composite Cooling Tower
6FT-2421-60
SN9834R
X
X
X
X
| Cooling Tower #8 |
| Cooling |
Tower 104 Ceramic Counter Flow
UL-2430-75-12P4
P500512
X
X
X
X
| Cooling Tower #9 |
| Cooling |
Tower 104 Ceramic Counter Flow
UL-2430-75-12P4
P500512
X
X
| X |
| X |
| Cooling Tower #1 |
| Cooling Tower 109 |
Evapco
USS-212-824
14-715194
X
X
X
X
| Cooling Tower #2 |
| Cooling Tower 109 |
| Evapco |
USS-212-824
5-275626
X
X
X
Chiller Pump #1
Bldg. 109
Baldor
EM2543T-C1
C1704240932
X
X
X
X
Chiller Pump #2
Bldg. 109
Baldor
EM4115T
C1803161427
X
X
X
X
Chiller Pump #3
Bldg. 109
U S Electric
286T Unknown
X
X
X
X
Condenser WP#1
Bldg. 109
Baldor
M2543T Z0806270106
X
X
X
X
| Condenser WP#2 |
| Bldg. 109 |
| Baldor |
EM2543T
C1110310852
X
X
X
X
Condenser WP#3
Bldg. 109 Marathon
PN324TTDR7026HN
01-92364-12/19/11
X
X
X
X
ACCH-1
Bldg. 108
York
YLAA0101YE46
SEDM-546050
Not Used
OR Chiller Pump #15
Bldg. 100
U S electric
215T
SN9830R
X
X
| X |
| X |
OR chiller Pump #16
Bldg. 100 U S Electric
215T
SN9831R
X
X
X
X
ABB VFD
B104
ABB
ACH550-VDR-059A-4
2144704316 2144703279
ABB VFD
B104
ABB
ACH550-BCR-045A-4+B055
2132500492
ABB VFD
ABB
ACH550-BCR-045A-4+B055
2132500477
ABB VFD
ABB
ACH550-BCR-045A-4+B055
2132500499
ABB VFD
ABB
ACH550-BCR-045A-4+B055
2132500424
| ABB VFD |
| Bl04 |
| ABB |
| ACH550-BCR- |
045A-4+B055
| 2132522412 |
| X |
| X |
| ABB VFD |
| B104 |
| ABB |
| ACH550-BDR- |
045A-4+B055
| 2132500448 |
| X |
| X |
| ABB VFD |
| B104 |
| ABB |
| ACH550-BDR- |
072A-4+B055
| 2120201616 |
| X |
| X |
| ABB VFD |
| B104 |
| ABB |
| ACH550-BDR- |
072A-4+B055
| 2120201587 |
| X |
| X |
| ABB VFD |
| B104 |
| ABB |
| ACH550-BDR- |
157A-4+B055
| 2120204083 |
| X |
| X |
| ABB VFD |
| B104 |
| ABB |
| ACH550-BDR- |
157A-4+B055
| 2120204233 |
| X |
| X |
| ABB VFD |
| B104 |
| ABB |
| ACH550-BDR- |
157A-4+B055
| 2120300012 |
| X |
| X |
| ABB VFD |
| Bl04 |
| ABB |
| ACH550-BDR- |
157A-4+B055 212020449
| X |
| X |
| ABB VFD |
| Bl04 |
| ABB |
| ACH550-UH- 157A-4 |
| 214410006 |
| X |
| X |
| ABB VFD |
| Bl04 |
| ABB |
| ACH550-UH- 157A-4 |
| 211020123 |
| X |
| X |
| ABB VFD |
| Bl04 |
| ABB |
| AYK550-UH- 157A-4+K465 |
| 205230075 |
| X |
| X |
| ABBVFD |
| Bl04 |
| ABB |
| AYK550-UH- 157A-4+K465 |
| 205440100 |
| X |
| X |
ABB VFD
Cooling Tower 104
ABB
ACH550-UH- 078A-4 tV944
209432515
ABBVFD
Cooling Tower 104
ABB
| ACH550-UH- 078A-4+V944 |
| 209430251 |
Cooling Tower
ABB
| ACI-!550-UH- 078A-4+V944 |
| 209430251 |
Cooling Tower 104
ABB
| ACH550-UH- 078A-4+V944 |
| 209430251 |
Cooling Tower 104
ABB
| ACH550-UH- 078A-4+V944 |
| 212130061 |
I
Cooling Tower
ABB
| ACH550-UH- 078A-4+V944 |
| 212130061 |
ABBVFD
Cooling Tower 104
ABB
| ACH550-BDR- 078A-4+B055 |
| 212020157 |
Cooling Tower 104
ABB
| ACH550-BDR- 097A-4+B055 |
| 212020124 |
Cooling Tower 104
ABB
| ACI-!550-BDR- 045A-4+B055 |
| 212020102 |
NOTE: All Maintenance shall be as per latest manufacturer recommendations I