- Solicitation number
- 36C25624Q1298
About this file
This document is a Request for Quotation (RFQ) for the annual inspection and re-certification of backflow preventers at the Southeast Louisiana Veterans Healthcare System in New Orleans, LA. The VA is seeking a service-disabled veteran-owned small business contractor to provide comprehensive testing and certification of the backflow preventers located at the New Orleans Replacement VA facility. The contractor will be responsible for all labor, materials, and travel necessary to complete the annual inspections. Quotes are due by August 27th, 2024 and should be submitted electronically to the Contracting Officer, Marcus Sidney. The NAICS code for this requirement is 238220 (Plumbing, Heating, and Air-Conditioning Contractors) with a size standard of $19.0 million. This is a 100% set-aside for service-disabled veteran-owned small businesses.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25624Q1298 0001_1.docx | DOCX document | |
| 36C25624Q1298 0001.pdf | ||
| 36C25624Q1298_1.docx | DOCX document | |
| 36C25624Q1298.pdf | ||
| NOLA VA Wage Determination.txt | TXT text file |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| Building ID | Room ID | Location Description | Description | Size ( in Inches) | Type BP Present (Reduced Pressure/RP, Spill Resistant Vacuum Breaker/ SRVB, Double Check Backflow Preventer/DC) | Manufacturer | Model No. | Serial No. |
| E 2nd Floor+A2:F10A2:H63 | 2E108 | Mechanical room | Hot water supply | 3/4” | RP | Watts | LF009M3QT | 108919 |
| E 2nd Floor | 2E109 | A/C closet | Water to AC/Chiller ; needs key from MRI | 1” | RP | Wilkins | 975XL2 | 4116535 |
| E 2nd Floor | 2E137 | Housekeeping Closet | Water to AC/Chiller | 1” | RP | Wilkins | 975XL2 | 4116635 |
| E 4th Floor | 4E138 | Microbiology | Autoclave; disconnected | 1” | RP | Wilkins | 975XL2 | 4104588 |
| E 3rd Floor | 3E222 | Operating Room back hallway | Autoclave | 1 1/2" | RP | Wilkins | 975XL2 | 792513 |
| M 1st Floor | 1M115A | Pool Mech Room | Saltwater Pool | 2” | RP | Wilkins | 975XL2 | 4168588 |
| CEP 1st Floor | 1N101 | Filtration Room | Irrigation line and fire tank | 4” | RP | Watts | 957 | OC-0202 |
| F 2nd Floor | 2F107 | Mechanical Room | Condensate booster | 3/4" | RP | Watts | LF009M3QT | 108898 |
| G 2nd Floor | 2G110 | Mechanical Room | Condensate Booster | 3/4" | RP | Watts | LF009M3QT | 96562 |
| G 2nd Floor | 2G129 | None | Water to AC/Chiller ; needs key from MRI needs A/C key and must use platform | 2” | RP | Wilkins | 975XL2 | 4142299 |
| G 2nd Floor | 2G172 | Housekeeping Closet | Water to AC/Chiller | 2” | RP | Wilkins | LF009M2QT | 59014 |
| G 2nd Floor | 2G303 | Mechanical room | Condensate Booster | 3/4" | RP | Watts | LF009M3QT | 8897 |
| CEP 2nd Floor | 2N125 | Mechanical Room | Domestic water to process water | 2” | RP | Watts | LF909M1QT | 3737 |
| CEP 2nd Floor | 2N125 | Mechanical Room | Domestic water to process water | 2” | RP | Watts | LF909M1QT | 3738 |
| CEP 2nd Floor | 2N125 | Boiler Room | Non-potable to Domestic water | 8” | RP | Watts | LF909M1 | 3122 |
| CEP 2nd Floor | 2N125 | Boiler Room | Non-potable to Domestic Water | 8” | RP | Watts | LF909M1 | 3126 |
| C 3rd Floor | 3C114 | None | Dialysis | 2” | RP | Wilkins | 975XL2 | 3935212 |
| F 3rd Floor | 3F215 | Housekeeping Closet | Water to AC/Chiller | 1” | RP | Watts | LF009M2QT | 89282 |
| C 4th Floor | 4C132 | Mechanical room | Hot water supply | 1 1/2" | RP | Wilkins | 975XL2 | 3934693 |
| D 4th Floor | 4D111 | SPS | Sterilizers | 3/4" | RP | Wilkins | 975XL2 | 3934850 |
| D 4th Floor | 4D111 | SPS | Sterilizers | 3/4" | RP | Wilkins | 975XL2 | 4116455 |
| D 4th Floor | 4D111 | SPS | Sterilizers | 3/4" | RP | Wilkins | 975XL2 | 4116452 |
| D 4th Floor | 4D203B | SPS | Ultrasonic cleaner directly attached to unprotected water supply. RP Backflow Preventer installed in 4D203C | 3/4" | RP | Watts | LF909QT | 39470 |
| D 4th Floor | 4D203B | Detergent room | Water for Reverse Osmosis | 1 1/2" | RP | Wilkins | 975XL2 | 4255091 |
| D 4th Floor | 4D203C | SPS | Ultrasonic cleaner directly attached to unprotected water supply. RP Backflow Preventer installed in 4D203C | 3/4" | RP | Watts | LF909QT | 38236 |
| D 4th Floor | 4D203C | SPS | Ultrasonic cleaner directly attached to unprotected water supply. RP Backflow Preventer installed in 4D203C | 3/4" | RP | Watts | LF909QT | 39479 |
| D 4th Floor | 4D222 | Housekeeping Closet inside of SPS | No water is connected; need ladder | 1 1/2" | RP | Wilkins | 975XL2 | 3935763 |
| F 4th Floor | 4F133A | Pathology/Histology | Specimen table closest to door/Garbage Disposal | 1/2" | SRVB | Watts | LF008PCQT | 13134 |
| F 4th Floor | 4F133A | Pathology/Histology | Specimen table 2nd closest to door/Garbage Disposal | 1/2" | SRVB | Watts | LF008PCQT | 13135 |
| F 4th Floor | 4F133A | Pathology/Histology | Specimen table far side/Garbage Disposal | 1/2" | SRVB | Watts | LF008PCQT | 10743 |
| F 4th Floor | 4F133A | Pathology/Histology | Specimen table/Garbage Disposal | 1/2" | SRVB | Watts | LF008PCQT | 10742 |
| F 4th Floor | 4F133A | Pathology/Histology | Specimen Table/Garbage Disposal | 1/2" | SRVB | Watts | LF008PCQT | 10741 |
| F 4th Floor | 4F133A | Pathology/Histology | Specimen Table/Garbage Disposal | 1/2" | SRVB | Watts | LF008PCQT | 10708 |
| J 4th Floor | 4J301 | Mechanical Room | Vacuum pump | 3/4" | RP | Wilkins | 975XL2 | 4116454 |
| M 4th Floor | 4M116 | Mechanical Room | Domestic water | 4” | RP | Wilkins | 375MS | L92771 |
| M 4th Floor | 4M116 | Mechanical Room | Heater make up water; need ladder | 3/4" | RP | Wilkins | 975XL2 | 4116453 |
| M 4th Floor | 4M116 | Mechanical Room | Domestic water | 4” | RP | Wilkins | 375MS | L92770 |
| C 5th Floor | 5C100 | Mechanical room | Dialysis | 1 1/2" | RP | Wilkins | 975XL2 | 3935876 |
| C 5th Floor | 5C100 | Mechanical room | Domestic water; need ladder | 6” | RP | Wilkins | 375MS | L89860 |
| C 5th Floor | 5C100 | Mechanical room | Domestic water | 6” | RP | Wilkins | 375MS | L89859 |
| J 5th Floor | 5J301 | Mechanical Room | Domestic water | 6” | RP | Wilkins | 375MS | L92662 |
| J 5th Floor | 5J301 | Mechanical Room | Domestic water | 6” | RP | Wilkins | 375MS | L92664 |
| J 5th Floor | 5J301 | Mech room | Hot water supply | 1 1/2" | RP | Wilkins | 975XL2 | 4135136 |
| D 6th Floor | 6D100 | Mechanical room | Domestic main line | 8” | RP | Wilkins | 375MS | L92776B |
| D 6th Floor | 6D100 | Mechanical room | Domestic to non-potable | 6” | RP | Wilkins | 375MS | L92663 |
| D 6th Floor | 6D100 | Mechanical room | Tempered water | 1 1/2" | RP | Wilkins | 975XL2 | 4135138 |
| D 6th Floor | 6D100 | Mechanical room | Domestic main line | 8” | RP | Wilkins | 375MS | 392776A |
| D 6th Floor | 6D100 | Mechanical room | Domestic to non-potable | 6” | RP | Wilkins | 375MS | L92661 |
| Pan Am Building Basement | BQ101 | Basement of the Pan Am Building against the wall | Main Domestic Waterline from Rocheblave | 2” | RP | Watts | LF909M1QT | 466236 |
| Pan Am Building Basement | BQ101 | Basement | Domestic water | 2” | RP | Watts | LF909M1QT | 466240 |
| Pan Am Building Basement | BQ105 | None | Water to AC/Chiller | 2” | RP | Watts | LF909M1QT | 466235 |
| Pan Am Building Basement | BQ105A | Basement Fire Pump Room | Fire Protection Sprinkler | 6” | DC | AmesColt | 200 | NB0473 |
| Main Water Line - Galvez | None | Outside of CEP/Corner of Tulane and Galvez | Main Domestic Water to Complex | 10” | RP | Watts | 957 | QA-2209 |
| Main Water Line - Canal | None | Front Lawn | Main Domestic Water to Complex; insulated | 10” | RP | Watts | 957 | MK-5199 |
| Dixie 2nd Floor | 2P157B | Adjacent to Sterilizer (Clean) Room | Reduced Pressure Backflow Preventer for sterilizer attached to water supply | 3/4" | RP | Watts | LMF009M3QT | 1008895 |
| Dixie 1st Floor | Loading Dock | Right side of the loading dock area | Main domestic water; was off, not tested | 4” | RP | Wilkins | 375 | L98862 |
| Dixie 1st Floor | Loading Dock | Right side of the loading dock area | Main domestic line; was off, not tested | 4” | RP | Wilkins | 375 | L100445 |
| Dixie 2nd Floor | 153 | 1st Center Hallway | Reduced Pressure Backflow Preventer for ice machine attached to water supply | 1/2" | RP | Watts | LF009QT | 130223 |
| Dixie 2nd Floor | 2nd Center Hallway | Center hallway on Rocheblave side of building | Reduced Pressure Backflow Preventer for ice machine attached to water supply | 1/2" | RP | Watts | LF009M2QT | 130246 |
| Dixie 2nd Floor | 2nd Floor Sterilizer Mechanical Room | Adjacent to Sterilizer (Clean) Room | Reduced Pressure Backflow Preventer for sterilizer attached to water supply | 3/4" | RP | Wilkins | LMF009M3QT | 108920 |
| Dixie Building 2nd Floor | 2P157A | Sterilizer room near elevator | Reduced Pressure Backflow Preventer for ice machine attached to water supply | 1/2" | RP | Watts | LF009QT | 130245 |
| Dixie Building 3rd Floor | 1st Center Hallway | Center Hallway next to sterilizer | Reduced Pressure Backflow Preventer for ice machine attached to water supply | 1/2" | RP | Watts | LF009QT | 130229 |
| Dixie Building 3rd Floor | 2nd Center Hallway | Rocheblave side of hallway | Reduced Pressure Backflow Preventer for ice machine attached to water supply | 1/2" | RP | Watts | LF009QT | 125592 |
| Dixie Building 4th Floor | 4P159 | Autopsy table | Spill Resistant Backflow Preventer for autopsy table attached to water supply | 1/2" | SRVB | Watts | LF 008PCQT | 17315 |
| Dixie Building 4th Floor | 2nd Center Hallway | Rocheblave side of the building | Reduced Pressure Backflow Preventer for ice machine attached to water supply. By 4P169 | 1/2" | RP | Watts | LF009QT | 130247 |
| Dixie Building 5th Floor | Penthouse | Mechanical Room | Reduced Pressure Backflow Preventer for potable water attached to non-potable water | 2” | RP | Wilkins | 975XL2 | 4306796 |
| Dixie Building 5th Floor | Mechanical Room | Mechanical Room | Domestic water for hot water application | 2” | RP | Wilkins | 975XL2 | 4321014 |
| Dixie Building 5th Floor | Mechanical Room | Mechanical Room | Reduced Pressure Backflow Preventer for domestic water feeding a steam generator | 2” | RP | Wilkins | 975XL2 | 4321026 |
| Main Building 7th Floor | 7L101 | 2.5” | RP | Wilkins | 375 | L99588 | ||
| Dixie Building 2nd Floor | 157A | 1/2" | RP | Watts | LF009QT | 30245 |