Equipment Information Final.xlsx

XLSX spreadsheet 15 KB Posted

Attached to
H145--Annual Inspection / Re-Certification of Backflow Preventers
Solicitation number
36C25624Q1298
Issued by

About this file

This document is a Request for Quotation (RFQ) for the annual inspection and re-certification of backflow preventers at the Southeast Louisiana Veterans Healthcare System in New Orleans, LA. The VA is seeking a service-disabled veteran-owned small business contractor to provide comprehensive testing and certification of the backflow preventers located at the New Orleans Replacement VA facility. The contractor will be responsible for all labor, materials, and travel necessary to complete the annual inspections. Quotes are due by August 27th, 2024 and should be submitted electronically to the Contracting Officer, Marcus Sidney. The NAICS code for this requirement is 238220 (Plumbing, Heating, and Air-Conditioning Contractors) with a size standard of $19.0 million. This is a 100% set-aside for service-disabled veteran-owned small businesses.

View the file

Other files

File Type Posted
36C25624Q1298 0001_1.docx DOCX document
36C25624Q1298 0001.pdf PDF
36C25624Q1298_1.docx DOCX document
36C25624Q1298.pdf PDF
NOLA VA Wage Determination.txt TXT text file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

Building IDRoom IDLocation DescriptionDescriptionSize ( in Inches)Type BP Present (Reduced Pressure/RP, Spill Resistant Vacuum Breaker/ SRVB, Double Check Backflow Preventer/DC)ManufacturerModel No.Serial No.
E 2nd Floor+A2:F10A2:H632E108Mechanical roomHot water supply3/4”RPWattsLF009M3QT108919
E 2nd Floor2E109A/C closetWater to AC/Chiller ; needs key from MRI1”RPWilkins975XL24116535
E 2nd Floor2E137Housekeeping ClosetWater to AC/Chiller1”RPWilkins975XL24116635
E 4th Floor4E138MicrobiologyAutoclave; disconnected1”RPWilkins975XL24104588
E 3rd Floor3E222Operating Room back hallwayAutoclave1 1/2"RPWilkins975XL2792513
M 1st Floor1M115APool Mech RoomSaltwater Pool2”RPWilkins975XL24168588
CEP 1st Floor1N101Filtration RoomIrrigation line and fire tank4”RPWatts957OC-0202
F 2nd Floor2F107Mechanical RoomCondensate booster3/4"RPWattsLF009M3QT108898
G 2nd Floor2G110Mechanical RoomCondensate Booster3/4"RPWattsLF009M3QT96562
G 2nd Floor2G129NoneWater to AC/Chiller ; needs key from MRI needs A/C key and must use platform2”RPWilkins975XL24142299
G 2nd Floor2G172Housekeeping ClosetWater to AC/Chiller2”RPWilkinsLF009M2QT59014
G 2nd Floor2G303Mechanical roomCondensate Booster3/4"RPWattsLF009M3QT8897
CEP 2nd Floor2N125Mechanical RoomDomestic water to process water2”RPWattsLF909M1QT3737
CEP 2nd Floor2N125Mechanical RoomDomestic water to process water2”RPWattsLF909M1QT3738
CEP 2nd Floor2N125Boiler RoomNon-potable to Domestic water8”RPWattsLF909M13122
CEP 2nd Floor2N125Boiler RoomNon-potable to Domestic Water8”RPWattsLF909M13126
C 3rd Floor3C114NoneDialysis2”RPWilkins975XL23935212
F 3rd Floor3F215Housekeeping ClosetWater to AC/Chiller1”RPWattsLF009M2QT89282
C 4th Floor4C132Mechanical roomHot water supply1 1/2"RPWilkins975XL23934693
D 4th Floor4D111SPSSterilizers3/4"RPWilkins975XL23934850
D 4th Floor4D111SPSSterilizers3/4"RPWilkins975XL24116455
D 4th Floor4D111SPSSterilizers3/4"RPWilkins975XL24116452
D 4th Floor4D203BSPSUltrasonic cleaner directly attached to unprotected water supply. RP Backflow Preventer installed in 4D203C3/4"RPWattsLF909QT39470
D 4th Floor4D203BDetergent roomWater for Reverse Osmosis1 1/2"RPWilkins975XL24255091
D 4th Floor4D203CSPSUltrasonic cleaner directly attached to unprotected water supply. RP Backflow Preventer installed in 4D203C3/4"RPWattsLF909QT38236
D 4th Floor4D203CSPSUltrasonic cleaner directly attached to unprotected water supply. RP Backflow Preventer installed in 4D203C3/4"RPWattsLF909QT39479
D 4th Floor4D222Housekeeping Closet inside of SPSNo water is connected; need ladder1 1/2"RPWilkins975XL23935763
F 4th Floor4F133APathology/HistologySpecimen table closest to door/Garbage Disposal1/2"SRVBWattsLF008PCQT13134
F 4th Floor4F133APathology/HistologySpecimen table 2nd closest to door/Garbage Disposal1/2"SRVBWattsLF008PCQT13135
F 4th Floor4F133APathology/HistologySpecimen table far side/Garbage Disposal1/2"SRVBWattsLF008PCQT10743
F 4th Floor4F133APathology/HistologySpecimen table/Garbage Disposal1/2"SRVBWattsLF008PCQT10742
F 4th Floor4F133APathology/HistologySpecimen Table/Garbage Disposal1/2"SRVBWattsLF008PCQT10741
F 4th Floor4F133APathology/HistologySpecimen Table/Garbage Disposal1/2"SRVBWattsLF008PCQT10708
J 4th Floor4J301Mechanical RoomVacuum pump3/4"RPWilkins975XL24116454
M 4th Floor4M116Mechanical RoomDomestic water4”RPWilkins375MSL92771
M 4th Floor4M116Mechanical RoomHeater make up water; need ladder3/4"RPWilkins975XL24116453
M 4th Floor4M116Mechanical RoomDomestic water4”RPWilkins375MSL92770
C 5th Floor5C100Mechanical roomDialysis1 1/2"RPWilkins975XL23935876
C 5th Floor5C100Mechanical roomDomestic water; need ladder6”RPWilkins375MSL89860
C 5th Floor5C100Mechanical roomDomestic water6”RPWilkins375MSL89859
J 5th Floor5J301Mechanical RoomDomestic water6”RPWilkins375MSL92662
J 5th Floor5J301Mechanical RoomDomestic water6”RPWilkins375MSL92664
J 5th Floor5J301Mech roomHot water supply1 1/2"RPWilkins975XL24135136
D 6th Floor6D100Mechanical roomDomestic main line8”RPWilkins375MSL92776B
D 6th Floor6D100Mechanical roomDomestic to non-potable6”RPWilkins375MSL92663
D 6th Floor6D100Mechanical roomTempered water1 1/2"RPWilkins975XL24135138
D 6th Floor6D100Mechanical roomDomestic main line8”RPWilkins375MS392776A
D 6th Floor6D100Mechanical roomDomestic to non-potable6”RPWilkins375MSL92661
Pan Am Building BasementBQ101Basement of the Pan Am Building against the wallMain Domestic Waterline from Rocheblave2”RPWattsLF909M1QT466236
Pan Am Building BasementBQ101BasementDomestic water2”RPWattsLF909M1QT466240
Pan Am Building BasementBQ105NoneWater to AC/Chiller2”RPWattsLF909M1QT466235
Pan Am Building BasementBQ105ABasement Fire Pump RoomFire Protection Sprinkler6”DCAmesColt200NB0473
Main Water Line - GalvezNoneOutside of CEP/Corner of Tulane and GalvezMain Domestic Water to Complex10”RPWatts957QA-2209
Main Water Line - CanalNoneFront LawnMain Domestic Water to Complex; insulated10”RPWatts957MK-5199
Dixie 2nd Floor2P157BAdjacent to Sterilizer (Clean) RoomReduced Pressure Backflow Preventer for sterilizer attached to water supply3/4"RPWattsLMF009M3QT1008895
Dixie 1st FloorLoading DockRight side of the loading dock areaMain domestic water; was off, not tested4”RPWilkins375L98862
Dixie 1st FloorLoading DockRight side of the loading dock areaMain domestic line; was off, not tested4”RPWilkins375L100445
Dixie 2nd Floor1531st Center HallwayReduced Pressure Backflow Preventer for ice machine attached to water supply1/2"RPWattsLF009QT130223
Dixie 2nd Floor2nd Center HallwayCenter hallway on Rocheblave side of buildingReduced Pressure Backflow Preventer for ice machine attached to water supply1/2"RPWattsLF009M2QT130246
Dixie 2nd Floor2nd Floor Sterilizer Mechanical RoomAdjacent to Sterilizer (Clean) RoomReduced Pressure Backflow Preventer for sterilizer attached to water supply3/4"RPWilkinsLMF009M3QT108920
Dixie Building 2nd Floor2P157ASterilizer room near elevatorReduced Pressure Backflow Preventer for ice machine attached to water supply1/2"RPWattsLF009QT130245
Dixie Building 3rd Floor1st Center HallwayCenter Hallway next to sterilizerReduced Pressure Backflow Preventer for ice machine attached to water supply1/2"RPWattsLF009QT130229
Dixie Building 3rd Floor2nd Center HallwayRocheblave side of hallwayReduced Pressure Backflow Preventer for ice machine attached to water supply1/2"RPWattsLF009QT125592
Dixie Building 4th Floor4P159Autopsy tableSpill Resistant Backflow Preventer for autopsy table attached to water supply1/2"SRVBWattsLF 008PCQT17315
Dixie Building 4th Floor2nd Center HallwayRocheblave side of the buildingReduced Pressure Backflow Preventer for ice machine attached to water supply. By 4P1691/2"RPWattsLF009QT130247
Dixie Building 5th FloorPenthouseMechanical RoomReduced Pressure Backflow Preventer for potable water attached to non-potable water2”RPWilkins975XL24306796
Dixie Building 5th FloorMechanical RoomMechanical RoomDomestic water for hot water application2”RPWilkins975XL24321014
Dixie Building 5th FloorMechanical RoomMechanical RoomReduced Pressure Backflow Preventer for domestic water feeding a steam generator2”RPWilkins975XL24321026
Main Building 7th Floor7L1012.5”RPWilkins375L99588
Dixie Building 2nd Floor157A1/2"RPWattsLF009QT30245

File details come from the government source that posted it. Updated .