A0004_Attachment B_Revised Design Drawings.pdf

PDF 22 MB Posted

Attached to
36C25623R0081 Amendment 0007_598-19-118 Replace 21 AHUs and Chiller for AHU-18 at NLR (VA-23-00058622)
Solicitation number
36C25623R0081
Issued by

About this file

This document is Attachment B - Revised Design Drawings related to Solicitation Number 36C25623R0081 for the replacement of 21 Air Handling Units and a Chiller for AHU 18 in Building 170 at the Eugene J. Towbin Veterans Affairs Medical Center in North Little Rock, Arkansas.

The solicitation is a 100% Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside. The anticipated contract award date is approximately 60 days or less after receipt of proposals, with a recommended period of performance of 300 calendar days after issuance of the Notice to Proceed. The construction cost range for this project is between $5,000,000.00 and $10,000,000.00. The applicable NAICS code is 238220 - Plumbing, Heating and Air-Conditioning Contractors, with a $19M small business size standard. Interested offerors must be registered in the System for Award Management (SAM) database and verified as a SDVOSB in the Small Business Association website.

View the file

Other files

File Type Posted
36C25623R0081 0007.pdf PDF
A0007_Attachment A_Revised Schedule of Offer Items 04.17.24.pdf PDF
A0006_Attachment A_Revised Schedule of Offer Items.pdf PDF
36C25623R0081 0006.pdf PDF
A0006_Attachment A_Revised Schedule of Offer Items.pdf PDF
A0006_Attachment A_Revised Schedule of Offer Items.pdf PDF
36C25623R0081 0006.pdf PDF
36C25623R0081 0005.pdf PDF
A0005_Attachment A_2nd Site Visit Attendance Sheet 04.01.24.pdf PDF
A0004_Attachment C_ASBESTOS INSPECTION Bldg 170.xlsx XLSX spreadsheet
36C25623R0081 0004.pdf PDF
A0004_Attachment A_598-19-118 RFI Updated Responses 03.20.24.pdf PDF
36C25623R0081 Amendment 0003.pdf PDF
36C25623R0081 Amendment 0002.pdf PDF
Attachment F - RFI Responses 598-19-118 Rplc 21 AHUs n Chillers Final.pdf PDF
36C25623R0081 Amendment 0001.pdf PDF
Attachment G - 598-19-118 ASBESTOS INSPECTION Bldg 170.xlsx XLSX spreadsheet
Attachment H - 598-19-118 Site Visit Attendance.pdf PDF
Attachment E - Contractor Evaluation Form.pdf PDF
Attachment A - 598-19-118 Replace AHUs at NLR Const SOW Final_01.docx DOCX document
Attachment B - 598-19-118 Replacement AHUs and Chiller CD Drawings.pdf PDF
Attachment C - 598-19-118 Replacement AHUs and Chiller CD Specifications.pdf PDF
Attachment D - WAGE DETERMINATION AR20230032 01062023_01.pdf PDF
36C25623R0081.docx DOCX document
Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL INSTALLATION WITH THE WORK OF OTHER

TRADES. FIELD MODIFICATIONS NEEDED DUE TO OBSTRUCTIONS OR INTERFERENCES SHALL BE

PROVIDED AT NO ADDITIONAL COST.

ALL WORK SHALL BE PERFORMED IN A NEAT AND WORKMANLIKE MANNER WITHIN STANDARD OF

CARE FOR PROFESSION. ALL LABOR, MATERIAL, TOOLS, PERMITS, INSPECTIONS, TESTING,

CERTIFICATION, ETC. REQUIRED FOR A COMPLETE AND SATISFACTORY INSTALLATION TO DESIGN INTENT SHALL BE FURNISHED BY CONTRACTOR. PROVIDE, AT NO ADDITIONAL COST, INCLUDING

INCIDENTAL ITEMS NOT SHOWN WHEN REQUIRED FOR TYPICAL COMPLETION OF WORK.

DRAWINGS NOT BEARING THE STAMP OR SEAL AND SIGNATURE OF A REGISTERED PROFESSIONAL

ENGINEER SHALL NOT BE USED FOR BIDDING OR CONSTRUCTION PURPOSES UNLESS EXPRESSLY

APPROVED IN WRITING BY THE ARCHITECT. THE CONTRACTOR SHALL BE RESPONSIBLE FOR

ENSURING THAT ALL DRAWINGS AND SPECIFICATIONS BEING USED FOR BIDDING AND

CONSTRUCTION PURPOSES ARE OF THE LATEST REVISION AVAILABLE AND ALL ADDENDUM

DOCUMENTS HAVE BEEN INCORPORATED EITHER BY REVISION RELEASE OF

DRAWINGS/SPECIFICATIONS OR ATTACHMENT OF SKETCHES OR OTHER ADDENDUM INFORMATION.

THE CONTRACTOR SHALL FURNISH AND INSTALL NEW PRODUCTS OF ESTABLISHED AND REPUTABLE

MANUFACTURERS. NO EQUIPMENT SUBSTITUTIONS SHALL BE MADE THAT WOULD LEAVE

INADEQUATE OPERATING OR SERVICE SPACE. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE

WITH MANUFACTURER'S RECOMMENDED INSTALLATION PROCEDURES AND IN AN ARRANGEMENT

THAT WILL GIVE THE GREATEST PRACTICAL EASE OF OPERATION AND SERVICE TO THE OWNER.

ALL EQUIPMENT WHICH IS INDICATED TO BE FURNISHED AND/OR INSTALLED BY OTHERS OR BY

OWNER IS INCLUDED FOR REFERENCE ONLY UNLESS NOTED OTHERWISE. CONTRACTOR SHALL BE

RESPONSIBLE FOR COORDINATING AND VERIFYING INSTALLATION REQUIREMENTS OF THIS

EQUIPMENT WITH THE APPLICABLE SUPPLIER OR THE OWNER. ANY DISCREPANCIES SHALL BE

BROUGHT TO THE ATTENTION OF THE ENGINEER.

ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF ALL APPLICABLE

CODES AND REGULATIONS INCLUDING BUT NOT LIMITED TO NATIONAL, CITY, STATE, LOCAL

ORDINANCES, AND UTILITY COMPANY REGULATIONS. ALL MATERIALS, INSTALLATION PROCEDURES, AND SYSTEM LAYOUTS SHALL BE APPROVED BY ALL APPLICABLE AUTHORITIES HAVING

JURISDICTION. THE CONTRACTOR SHALL PROVIDE ALL MATERIALS AND LABOR NECESSARY TO

COMPLY WITH THESE RULES, REGULATIONS, AND ORDINANCES. THESE CODES REPRESENT THE

MINIMUM ACCEPTABLE REQUIREMENTS, THEREFORE, WHERE DRAWINGS AND/OR SPECIFICATIONS

INDICATE MATERIALS OR CONSTRUCTION MORE STRINGENT THAT CODE REQUIREMENTS, THE

DRAWINGS AND/OR SPECIFICATIONS SHALL GOVERN.

IF COMPLIANCE WITH STANDARDS, CODES, REGULATIONS AND CONTRACT DOCUMENTS ESTABLISH DIFFERENT OR CONFLICTING REQUIREMENTS FOR MINIMUM QUANTITIES OR QUALITY LEVELS, REFER

CONFLICTING REQUIREMENTS TO ENGINEER FOR A DECISION BEFORE PROCEEDING.

WHERE CONTRACT DOCUMENTS NAME A SINGLE MANUFACTURER AND PRODUCT, PROVIDE THE

NAMED PRODUCT THAT COMPLIES WITH REQUIREMENTS. COMPARABLE PRODUCTS OR

SUBSTITUTIONS FOR CONTRACTOR'S CONVENIENCE WILL BE CONSIDERED. THE PROJECT.

CLOSEOUT SUBMITTALS SHALL INCLUDE, BUT NOT LIMITED TO, OPERATION AND MAINTENANCE

MANUALS AND RECORD DRAWINGS.

THE CONTRACTOR SHALL VISIT THE SITE OF THE BUILDING BEFORE SUBMITTING A PROPOSAL ON THIS WORK AND SHALL THOROUGHLY FAMILIARIZE HIMSELF WITH THE EXISTING CONDITIONS AND

OPERATIONS. FAILURE ON HIS PART TO DO THIS WILL NOT BE CAUSE OF EXTRAS AFTER THE

CONTRACT IS SIGNED, BY REASON OF UNFORESEEN CONDITIONS.

NO PERSON SHALL PERFORM ELECTRICAL WORK ON THE CONTRACT WITHOUT POSSESSING A

MASTER'S OR JOURNEYMAN'S LICENSE FROM THE STATE ELECTRICAL EXAMINERS BOARD. ALL

ELECTRICAL WORK AND APPRENTICE ELECTRICIANS SHALL BE SUPERVISED BY A MASTER

JOURNEYMAN ELECTRICIAN ON A ONE TO ONE RATIO.

PREPARE AND SUBMIT SUBMITTALS TO ARCHITECT.

ALL AREAS USED AS RETURN AIR PLENUMS SHALL BE CONSTRUCTED WITH FIRE RESISTANT

MATERIALS AND SHALL ONLY CONTAIN MATERIALS WHICH HAVE SMOKE DEVELOPED RATINGS NOT

GREATER THAN 50 AND FLAME SPREAD RATINGS NOT GREATER THAN 25.

ALL ELECTRICAL EQUIPMENT, SUCH AS SWITCHES, CIRCUIT BREAKERS, ETC. SHALL BE TESTED BY

OPERATING THE DEVICE TO VERIFY THAT THE MECHANICAL PORTIONS OF THE DEVICE ARE

FUNCTIONING.

THE CONTRACT SHALL ASSIST ALL OTHER TRADES IN PERFORMING ROTATIONAL TESTS ON ALL

MOTORS PROVIDED UNDER THIS CONTRACT.

ALL EXPOSED CONDUIT SHALL BE GALVANIZED RIGID STEEL, SIZED AS SCHEDULED.

WIRE SIZE PER CODE UNLESS NOTED ELSEWHERE:

WIRE SIZE 120V WIRE SIZE 277V

A. #12 LESS THAN 75 FEET LESS THAN 150 FEET

B. #10 BETWEEN 75-150 FEET BETWEEN 150-300 FEET

C. #8 BETWEEN 150-250 FEET BETWEEN 300-450 FEET

D. #6 BETWEEN 250-375 FEET BETWEEN 450-700 FEET

LEGEND

FUSED/NON-FUSED DISCONNECT. "F" AS NUMBER IS FUSE RATING, "S" AS NUMBER IS SWITCH RATING.

MOUNT DISCONNECT ABOVE WIREWAY.

NEMA INDUCTION MOTOR - VERIFY THE SIZE WITH ACTUAL EQUIPMENT FURNISHED. "HP" AS A NUMBER IF PRESENT REPRESENTS NEMA HORSE POWER RATING. "E" INDICATES EXISTING MOTOR. IF BLANK, MOTOR

RATING IS SCHEDULED BY DIV 23.

COMBINATION HOA MAGNETIC STARTER/FUSIBLE DISCONNECT SWITCH, NUMBER "S" IS HP RATING "E" FOR

EXISTING.

HP

S

VV VFD FUSED WITH INTEGRAL DISCONNECT/NON-FUSED-NO-DISCONNECT VFD PER DIV 23 SCHEDULE

BY DIV 23. MOUNT VFD ABOVE WIREWAY

ECM MOTOR - VERIFY THE SIZE WITH ACTUAL EQUIPMENT FURNISHED. "HP" AS A NUMBER

IF PRESENT REPRESENTS NEXT LARGER NEMA HORSE POWER RATING OF FLA-RATED ECM MOTOR. "E"

INDICATES EXISTING MOTOR. IF BLANK, MOTOR RATING IS SCHEDULED BY DIV 23.

HP

E

FS MCC BUCKET: FUSED SWITCH "F", NUMBER IS FUSE RATING, OR HOA COMBINATION STARTER "S", NUMBER IS HP RATING, "E" FOR EXISTING.

S

F

U.S. Department of Veterans Affairs

CONSULTANTS ARCHITECT/ENGINEER OF RECORDSTAMP Office of Construction and Facilities Management

Drawing Title

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Building Number

Drawing Number

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

Revisions: Date:

VA FORM 08 - 6231

FULLY SPRINKLERED

MISSION CRITICAL

/1

5/

0:

:0

AM

BI

M

-0

B

AH

U

R ep la ce m en ts /2

0-

B1

A

H U

R ep la ce m en ts M

EP

M od el

R vt

0.

rv t

ELECTRICAL GENERAL NOTES AND

LEGEND

REPLACE AHUS AND CHILLER

FOR AHU

EJT VAMC NORTH LITTLE ROCK

598-19-118

E001

JDA PROJECT #: D-19-09

A/E

2200 N. RODNEY PARHAM ROAD

SUITE 210

LITTLE ROCK, AR 72212

501-404-4811 jda@JohnsonDanforth.com

JohnsonDanforth & Associates

MEP ENGINEER

INSIGHT ENGINEERING, PLLC

201 S. CHESTER, SUITE B

LITTLE ROCK, AR 72201

COMMISSIONING

BERNHARD

BUILDING 2, 1 ALLIED DRIVE

SUITE 260

LITTLE ROCK, AR 72202

FIRE PROTECTION

FP&C CONSULTANTS KC, LLC

1330 Burlington Street, Ste. 200 North Kansas City, MO 64116

REVISED CONSTRUCTION DOCUMENTS

REVISED CONSTRUCTION

DOCUMENTS

2024.02.02 MPH MPH

1 Addendum #1 2024-02-02

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text U

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text Z

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text

INSIGHT

AutoCAD SHX Text

ENGINEERING, PLLC

AutoCAD SHX Text No. 3523

AutoCAD SHX Text

ARKANSAS

AutoCAD SHX Text

ENGINEER

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text

REGISTERED

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text

NO. 5822

X-AC-1

X-RF-1

X-AC-1A

X-RF-1A

GE114A-170

OFFICE

X-AC-1B

X-RF-1B

X-AC-8

X-RF-8

X-AC-19

X-AC-10

X-RF-10

U.S. Department of Veterans Affairs

CONSULTANTS ARCHITECT/ENGINEER OF RECORDSTAMP Office of Construction and Facilities Management

Drawing Title

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Building Number

Drawing Number

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

Revisions: Date:

VA FORM 08 - 6231

FULLY SPRINKLERED

MISSION CRITICAL

/1

5/

0:

:1

AM

BI

M

-0

B

AH

U

R ep la ce m en ts /2

0-

B1

A

H U

R ep la ce m en ts M

EP

M od el

R vt

0.

rv t

ELECTRICAL DEMOLITION REPLACE AHUS AND CHILLER

FOR AHU

EJT VAMC NORTH LITTLE ROCK

598-19-118

ED101

JDA PROJECT #: D-19-09

DEMOLITION KEYED NOTES

DISCONNECT ELECTRICAL FEEDER CONNECTION TO AIR

HANDLING UNIT / MOTORS AND DEMOLISH BACK TO EXISTING

VFD/DISCONNECT. EXISTING VFD/DISCONNECTS, FEEDER

CONDUCTORS AND CONDUITS SHALL REMAIN FOR REUSE.

A/E

2200 N. RODNEY PARHAM ROAD

SUITE 210

LITTLE ROCK, AR 72212

501-404-4811 jda@JohnsonDanforth.com

JohnsonDanforth & Associates

MEP ENGINEER

INSIGHT ENGINEERING, PLLC

201 S. CHESTER, SUITE B

LITTLE ROCK, AR 72201

COMMISSIONING

BERNHARD

BUILDING 2, 1 ALLIED DRIVE

SUITE 260

LITTLE ROCK, AR 72202

FIRE PROTECTION

FP&C CONSULTANTS KC, LLC

1330 Burlington Street, Ste. 200 North Kansas City, MO 64116

1/4" = 1'-0"D1 GROUND LEVEL PLAN (GE122) - ELECTRICAL DEMOLITION

1/4" = 1'-0"C4 GROUND LEVEL PLAN (GA105) - ELECTRICAL DEMOLITION

1/4" = 1'-0"

C6 GROUND LEVEL PLAN (GA106) - ELECTRICAL DEMOLITION

1/4" = 1'-0"F1 GROUND LEVEL PLAN (GL107) - ELECTRICAL DEMOLITION

1/4" = 1'-0"F4 GROUND LEVEL PLAN (GJ101/GJ100EA) - ELECTRICAL DEMOLITION

KEY PLANKEY PLAN

BLDG 170

NGJ100EA,

GJ101

GA105

GL107

GA106

GE122

REVISED CONSTRUCTION DOCUMENTS

REVISED CONSTRUCTION

DOCUMENTS

2024.02.02 MPH MPH

1 Addendum #1 2024-02-02

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text U

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text Z

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text

INSIGHT

AutoCAD SHX Text

ENGINEERING, PLLC

AutoCAD SHX Text No. 3523

AutoCAD SHX Text

ARKANSAS

AutoCAD SHX Text

ENGINEER

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text

REGISTERED

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text T

X-AC-2

X-RF-2

X-RF-3

X-AC-3

X-AC-15

X-RF-15

X-AC-11A

X-RF-11A

X-AC-11B

X-RF-11B

X-AC-11C

X-RF-11C

X-AC-11D

X-RF-11D

U.S. Department of Veterans Affairs

CONSULTANTS ARCHITECT/ENGINEER OF RECORDSTAMP Office of Construction and Facilities Management

Drawing Title

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Building Number

Drawing Number

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

Revisions: Date:

VA FORM 08 - 6231

FULLY SPRINKLERED

MISSION CRITICAL

/1

5/

0:

:1

AM

BI

M

-0

B

AH

U

R ep la ce m en ts /2

0-

B1

A

H U

R ep la ce m en ts M

EP

M od el

R vt

0.

rv t

ELECTRICAL DEMOLITION REPLACE AHUS AND CHILLER

FOR AHU

EJT VAMC NORTH LITTLE ROCK

598-19-118

ED102

JDA PROJECT #: D-19-09

A/E

2200 N. RODNEY PARHAM ROAD

SUITE 210

LITTLE ROCK, AR 72212

501-404-4811 jda@JohnsonDanforth.com

JohnsonDanforth & Associates

MEP ENGINEER

INSIGHT ENGINEERING, PLLC

201 S. CHESTER, SUITE B

LITTLE ROCK, AR 72201

COMMISSIONING

BERNHARD

BUILDING 2, 1 ALLIED DRIVE

SUITE 260

LITTLE ROCK, AR 72202

FIRE PROTECTION

FP&C CONSULTANTS KC, LLC

1330 Burlington Street, Ste. 200 North Kansas City, MO 64116

1/4" = 1'-0"F1 GROUND LEVEL PLAN (GB111) - ELECTRICAL DEMOLITION

1/4" = 1'-0"C3 GROUND LEVEL PLAN (GA001) - ELECTRICAL DEMOLITION

1/4" = 1'-0"C6 GROUND LEVEL PLAN (GA002) - ELECTRICAL DEMOLITION

1/4" = 1'-0"E3 FIRST LEVEL PLAN (1A002) - ELECTRICAL DEMOLITION

1/4" = 1'-0"E6 FIRST LEVEL PLAN (1A003) - ELECTRICAL DEMOLITION

BLDG 170

NGA001

GA002

GB111

1A002

1A003

KEY PLAN

DEMOLITION KEYED NOTES

DISCONNECT ELECTRICAL FEEDER CONNECTION TO AIR

HANDLING UNIT / MOTORS AND DEMOLISH BACK TO EXISTING

VFD/DISCONNECT. EXISTING VFD/DISCONNECTS, FEEDER

CONDUCTORS AND CONDUITS SHALL REMAIN FOR REUSE.

REVISED CONSTRUCTION DOCUMENTS

REVISED CONSTRUCTION

DOCUMENTS

2024.02.02 MPH MPH

1 Addendum #1 2024-02-02

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text U

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text Z

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text

INSIGHT

AutoCAD SHX Text

ENGINEERING, PLLC

AutoCAD SHX Text No. 3523

AutoCAD SHX Text

ARKANSAS

AutoCAD SHX Text

ENGINEER

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text

REGISTERED

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text T

X-AC-11E

X-RF-11E

X-ACF-11F

X-RF-11F

X-AC-11H

X-AC-11G

X-RF-11G

X-AC-12

X-RF-12

U.S. Department of Veterans Affairs

CONSULTANTS ARCHITECT/ENGINEER OF RECORDSTAMP Office of Construction and Facilities Management

Drawing Title

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Building Number

Drawing Number

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

Revisions: Date:

VA FORM 08 - 6231

FULLY SPRINKLERED

MISSION CRITICAL

/1

5/

0:

:1

AM

BI

M

-0

B

AH

U

R ep la ce m en ts /2

0-

B1

A

H U

R ep la ce m en ts M

EP

M od el

R vt

0.

rv t

ELECTRICAL DEMOLITION REPLACE AHUS AND CHILLER

FOR AHU

EJT VAMC NORTH LITTLE ROCK

598-19-118

ED103

JDA PROJECT #: D-19-09

A/E

2200 N. RODNEY PARHAM ROAD

SUITE 210

LITTLE ROCK, AR 72212

501-404-4811 jda@JohnsonDanforth.com

JohnsonDanforth & Associates

MEP ENGINEER

INSIGHT ENGINEERING, PLLC

201 S. CHESTER, SUITE B

LITTLE ROCK, AR 72201

COMMISSIONING

BERNHARD

BUILDING 2, 1 ALLIED DRIVE

SUITE 260

LITTLE ROCK, AR 72202

FIRE PROTECTION

FP&C CONSULTANTS KC, LLC

1330 Burlington Street, Ste. 200 North Kansas City, MO 64116

1/4" = 1'-0"C1 SECOND LEVEL PLAN (2A002) - ELECTRICAL DEMOLITION

1/4" = 1'-0"C4 SECOND LEVEL PLAN (2A003) - ELECTRICAL DEMOLITION

1/4" = 1'-0"C6 PENTHOUSE LEVEL PLAN (PH - A) - ELECTRICAL DEMOLITION

1/4" = 1'-0"E1 THIRD LEVEL PLAN (3A002) - ELECTRICAL DEMOLITION

1/4" = 1'-0"E4 GROUND LEVEL PLAN (GG102) - ELECTRICAL DEMOLITION

KEY PLAN

SCALE: 1/4" = 1'-0"

0 2' 4' 8'

BLDG 170

N

GG102

PH - A

2A002

2A003 3A002

DEMOLITION KEYED NOTES

DISCONNECT ELECTRICAL FEEDER CONNECTION TO AIR

HANDLING UNIT / MOTORS AND DEMOLISH BACK TO EXISTING

VFD/DISCONNECT. EXISTING VFD/DISCONNECTS, FEEDER

CONDUCTORS AND CONDUITS SHALL REMAIN FOR REUSE.

REVISED CONSTRUCTION DOCUMENTS

REVISED CONSTRUCTION

DOCUMENTS

2024.02.02 MPH MPH

1 Addendum #1 2024-02-02

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text U

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text Z

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text

INSIGHT

AutoCAD SHX Text

ENGINEERING, PLLC

AutoCAD SHX Text No. 3523

AutoCAD SHX Text

ARKANSAS

AutoCAD SHX Text

ENGINEER

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text

REGISTERED

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text T

X-AC-13

X-RF-13

X-AC-14

X-RF-14

X-AC-20

X-AC-9

X-RF-9

X-TUR-16

U.S. Department of Veterans Affairs

CONSULTANTS ARCHITECT/ENGINEER OF RECORDSTAMP Office of Construction and Facilities Management

Drawing Title

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Building Number

Drawing Number

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

Revisions: Date:

VA FORM 08 - 6231

FULLY SPRINKLERED

MISSION CRITICAL

/1

5/

0:

:1

AM

BI

M

-0

B

AH

U

R ep la ce m en ts /2

0-

B1

A

H U

R ep la ce m en ts M

EP

M od el

R vt

0.

rv t

ELECTRICAL DEMOLITION REPLACE AHUS AND CHILLER

FOR AHU

EJT VAMC NORTH LITTLE ROCK

598-19-118

ED104

JDA PROJECT #: D-19-09

A/E

2200 N. RODNEY PARHAM ROAD

SUITE 210

LITTLE ROCK, AR 72212

501-404-4811 jda@JohnsonDanforth.com

JohnsonDanforth & Associates

MEP ENGINEER

INSIGHT ENGINEERING, PLLC

201 S. CHESTER, SUITE B

LITTLE ROCK, AR 72201

COMMISSIONING

BERNHARD

BUILDING 2, 1 ALLIED DRIVE

SUITE 260

LITTLE ROCK, AR 72202

FIRE PROTECTION

FP&C CONSULTANTS KC, LLC

1330 Burlington Street, Ste. 200 North Kansas City, MO 64116

1/4" = 1'-0"C1 GROUND LEVEL PLAN (GN109) - ELECTRICAL DEMOLITION

1/4" = 1'-0"C4 GROUND LEVEL PLAN (GK104) - ELECTRICAL DEMOLITION

1/4" = 1'-0"C6 GROUND LEVEL PLAN (GH125) - ELECTRICAL DEMOLITION

1/4" = 1'-0"F1 GROUND LEVEL PLAN (GK106) - ELECTRICAL DEMOLITION

1/4" = 1'-0"F5 GROUND LEVEL PLAN (GE101) - ELECTRICAL DEMOLITION

KEY PLAN

SCALE: 1/4" = 1'-0"

0 2' 4' 8'

BLDG 170

N

GK104

GH125

GN109

GE101

DEMOLITION KEYED NOTES

DISCONNECT ELECTRICAL FEEDER CONNECTION TO AIR

HANDLING UNIT / MOTORS AND DEMOLISH BACK TO EXISTING

VFD/DISCONNECT. EXISTING VFD/DISCONNECTS, FEEDER

CONDUCTORS AND CONDUITS SHALL REMAIN FOR REUSE.

REVISED CONSTRUCTION DOCUMENTS

REVISED CONSTRUCTION

DOCUMENTS

2024.02.02 MPH MPH

1 Addendum #1 2024-02-02

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text U

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text Z

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text

INSIGHT

AutoCAD SHX Text

ENGINEERING, PLLC

AutoCAD SHX Text No. 3523

AutoCAD SHX Text

ARKANSAS

AutoCAD SHX Text

ENGINEER

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text

REGISTERED

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text T

F V

KEYED NOTES:

1 FEED TO REMAIN AND REUSED

FEED TO SUPPLY FAN

FEED TO RETURN FAN

EXISTING DISCONNECT TO REMAIN AND REUSED

NEW VFD TO NEW MOTOR AS SCHEDULED BY DIV 23

NEW MOTOR FEED PER GENERAL NOTES, TO NEW MOTORS AS

SCHEDULED BY DIV 23

NEW 30A/30AF DISCONNECT TO MOTOR DISCONNECTS

NEW 30A/10AF DISCONNECT TO MOTORS

INSTALL NEW 100A 3P BREAKER IN PANELBOARD D/GL-7,9,11

INSTALL NEW 80A 3P BREAKER IN PANELBOARD D/GJ-1,3,5

INSTALL NEW #4 IN 1-1/4 EMT

REMOVE THE 60A 3P DISCONNECT AND INSTALL A NEW 100A

3P DISCONNECT WITH 80A FUSES

F V

EXISTING CONDITIONS

1 3

1. THESE ARE DIAGRAMATIC FOR WIRING. APPROXIMATE RELATIVE POSITION

OF DISCONNECTS AND VFDS IS PER SHEETS EP101, EP102, EP103, EP104.

2. MOTORS BY DIV 23 INTEGRAL TO AHU, AND VFD ARE STAND ALONE WITH

INTEGRAL FUSED DISCONNECTS, BY DIV 23. VFD CHANGE-OUT,

DISCONNECT CHANGE-OUT, ELECTRICAL INSTALLATION, NEW OR

REWORKED WIREWAY, AND WIRE CONNECTIONS, ALL BY DIV 26.

CONTROLS AND CONTROL WIRING BY DIV 23.

3. EXISTING WIREWAYS TO BE REUSED TO PROVIDE PATHWAY FOR

INTERCONNECTS OF DISCONNECTS, VFDS, AND MOTORS. ADDITIONAL

WIREWAY, TO SUIT FINAL MECHANICAL CONDITIONS, MUST BE INSTALLED

TO PREVENT OVERCROWDING.

4. CONSULT MECHANICAL SHEETS FOR EXISTING ARRANGEMENT OF

DISCONNECTS, VFDS, AND STARTERS.

5. ALL 30A DISCONNECTS MUST RECEIVE 20A FUSES UNLESS NOTED

OTHERWISE.

6. ALL WIRING FROM DISCONNECTS TO VFD LINE-SIDE LUGS, AND VFD

LOAD-SIDE LUGS TO MOTORS, SHALL BE #10 UNLESS NOTED OTHERWISE

7. NEW 30A FUSED DISCONNECTS MAY BE SQUARED H361, OR ABB

FJ301-3PB6B FOR CLASS J FUSES, OR ABB FC301-3PB6B FOR CLASS CC

FUSES TO SUIT SPACE CONSTRAINTS.

8. NEW 120V 20A CIRCUIT SCHEDULE FOR AHU LIGHTS. PROVIDE A SWITCH

FOR EACH UV AND WORK LIGHT.

DEVICE CIRCUIT ROOM

AHU-1 EL/GE-13 GE118

AHU-1A EL/GE-13 GE107

AHU-1B EL/GA-6 GA107

AHU-20 EL/GH-16 GA107

AHU-2 EL/GB-9 GB113

AHU-3 EL/GB-11 GB113

AHU-8 EL/GL-14 GL116

AHU-10 EL/GJ-15 GJ103

AHU-11A EL/GF-14 GE103

AHU-11B EL/GF-13 GE103

AHU-11C EL/1F-17 1F111

AHU-11D EL/1F-19 1F111

AHU-11E EL/2F-17 2F116

AHU-11F EL/2F-19 2F116

AHU-11G EL/3F-12 3F116

AHU-12 EL/GF-15 GE103

F V V

RENOVATION

F V

60A/50AF

6 6

F V F V

EXISTING CONDITIONS

2 1 3

RENOVATION

F V F V

1 6 1 6 5 5

4 4

V V

EXISTING CONDITIONS

2 3

RENOVATION

V7

51 6 1 55 6 65 6 5 6

V V

EXISTING CONDITIONS

2 3

30 10 F V4

81 6 1 5

8 6 68 6

10 10

V V V V

2 2 2 2

E E

E E

RENOVATION

V

EXISTING CONDITIONS

2 3

RENOVATION

F V4

51 6 1 5

5 6 65 6 5 6

V V V V

2 2 2 2

E

E

100A/100AF

F V F V

EXISTING CONDITIONS

2 1 3

80 V V

RENOVATION

F V12

11 6

100A/80AF

6 6

EXISTING CONDITIONS

2 3

RENOVATION

F V

6 6

F

F

F

HP

F1

V

EXISTING CONDITIONS

2 3

RENOVATION

F V

6 6

F

FF

V F

F

HP

F1

V V

F V F V

EXISTING CONDITIONS

2 1 3

RENOVATION

F F V

1 6 1 6

4 4

HP

8 6 8 6

10 10

HP HP HP HP HP

GENERAL NOTES:

V

NOT TO SCALE:D1 AHU-8 ELECTRICAL

NOT TO SCALE:C1 AHU-1 ELECTRICAL

NOT TO SCALE:C3 AHU-1A, 1B, 20 ELECTRICAL

NOT TO SCALE:C3 AHU-2,3 ELECTRICAL

NOT TO SCALE:D6 AHU-11A, 11B ELECTRICAL

NOT TO SCALE:D4 AHU-10 ELECTRICAL

NOT TO SCALE:F1 AHU-11C ELECTRICAL

NOT TO SCALE:F3 AHU-11D, 11E, 11F, 11G ELECTRICAL

NOT TO SCALE:F5 AHU-12 ELECTRICAL

(NOTE: AHU-20 HAS NO RETURN FAN)

322 3

2 2 3 2 3

32 2 3 2 2 2 2 2 3

HPHPHPHPHPHPHPHPHP

HP HP HP HP HP HP HP HP HP HP

HP HP HP

U.S. Department of Veterans Affairs

CONSULTANTS ARCHITECT/ENGINEER OF RECORDSTAMP Office of Construction and Facilities Management

Drawing Title

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Building Number

Drawing Number

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

Revisions: Date:

VA FORM 08 - 6231

FULLY SPRINKLERED

MISSION CRITICAL

/1

5/

0:

:0

AM

BI

M

-0

B

AH

U

R ep la ce m en ts /2

0-

B1

A

H U

R ep la ce m en ts M

EP

M od el

R vt

0.

rv t

ELECTRICAL DETAILS AND

DIAGRAMS

REPLACE AHUS AND CHILLER

FOR AHU

EJT VAMC NORTH LITTLE ROCK

598-19-118

EJ201

JDA PROJECT #: D-19-09

A/E

2200 N. RODNEY PARHAM ROAD

SUITE 210

LITTLE ROCK, AR 72212

501-404-4811 jda@JohnsonDanforth.com

JohnsonDanforth & Associates

MEP ENGINEER

INSIGHT ENGINEERING, PLLC

201 S. CHESTER, SUITE B

LITTLE ROCK, AR 72201

COMMISSIONING

BERNHARD

BUILDING 2, 1 ALLIED DRIVE

SUITE 260

LITTLE ROCK, AR 72202

FIRE PROTECTION

FP&C CONSULTANTS KC, LLC

1330 Burlington Street, Ste. 200 North Kansas City, MO 64116

REVISED CONSTRUCTION DOCUMENTS

REVISED CONSTRUCTION

DOCUMENTS

2024.02.02 MPH MPH

1 Addendum #1 2024-02-02

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text U

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text Z

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text

INSIGHT

AutoCAD SHX Text

ENGINEERING, PLLC

AutoCAD SHX Text No. 3523

AutoCAD SHX Text

ARKANSAS

AutoCAD SHX Text

ENGINEER

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text

REGISTERED

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text T

FEED TO REMAIN AND REUSED

FEED TO SUPPLY FAN

FEED TO RETURN FAN

EXISTING DISCONNECT TO REMAIN AND REUSED

NEW VFD TO NEW MOTOR AS SCHEDULED BY DIV 23

NEW MOTOR FEED PER GENERAL NOTES, TO NEW MOTORS AS

SCHEDULED BY DIV 23

NEW 30A/30AF DISCONNECT TO MOTOR DISCONNECTS

NEW 30A/10AF DISCONNECT TO MOTORS

INSTALL NEW 100A 3P BREAKER IN PANELBOARD D/GL-7,9,11

INSTALL NEW 80A 3P BREAKER IN PANELBOARD D/GJ-1,3,5

INSTALL NEW #4 IN 1-1/4 EMT

REMOVE THE 60A 3P DISCONNECT AND INSTALL A NEW 100A

3P DISCONNECT WITH 80A FUSES

EXISTING CONDITIONS

30 10 V4

81 6 1 5

8 6 68 6 8 6

10 10 10

RENOVATION

V V

EXISTING CONDITIONS

2 3

30 10 V7

81 6 1 5

8 6 68 6

10 10

RENOVATION

EXISTING CONDITIONS

2 1 3

RENOVATION

V

1 6 1 6

4 4

S

HP

EXISTING CONDITIONS

2 31

V

2 HP

S S

V V

1 2 1 3

60A/30AF

F F

F

8 6

V

HP

4 4

F

F F F

F

FF

F

FF

EXISTING CONDITIONS

RENOVATION

1 6

HP

F

100A/20AF

F V

1. THESE ARE DIAGRAMATIC FOR WIRING. APPROXIMATE RELATIVE POSITION

OF DISCONNECTS AND VFDS IS PER SHEETS EP101, EP102, EP103, EP104.

2. MOTORS BY DIV 23 INTEGRAL TO AHU, AND VFD ARE STAND ALONE WITH

INTEGRAL FUSED DISCONNECTS, BY DIV 23. VFD CHANGE-OUT,

DISCONNECT CHANGE-OUT, ELECTRICAL INSTALLATION, NEW OR

REWORKED WIREWAY, AND WIRE CONNECTIONS, ALL BY DIV 26.

CONTROLS AND CONTROL WIRING BY DIV 23.

3. EXISTING WIREWAYS TO BE REUSED TO PROVIDE PATHWAY FOR

INTERCONNECTS OF DISCONNECTS, VFDS, AND MOTORS. ADDITIONAL

WIREWAY, TO SUIT FINAL MECHANICAL CONDITIONS, MUST BE INSTALLED

TO PREVENT OVERCROWDING.

4. CONSULT MECHANICAL SHEETS FOR EXISTING ARRANGEMENT OF

DISCONNECTS, VFDS, AND STARTERS.

5. ALL 30A DISCONNECTS MUST RECEIVE 20A FUSES UNLESS NOTED

OTHERWISE.

6. ALL WIRING FROM DISCONNECTS TO VFD LINE-SIDE LUGS, AND VFD

LOAD-SIDE LUGS TO MOTORS, SHALL BE #10 UNLESS NOTED OTHERWISE

7. NEW 30A FUSED DISCONNECTS MAY BE SQUARED H361, OR ABB

FJ301-3PB6B FOR CLASS J FUSES, OR ABB FC301-3PB6B FOR CLASS CC

FUSES TO SUIT SPACE CONSTRAINTS.

8. NEW 120V 20A CIRCUIT SCHEDULE FOR AHU LIGHTS. PROVIDE A SWITCH

FOR EACH UV AND WORK LIGHT.

DEVICE CIRCUIT ROOM

AHU-11H EL/3H-12 3H116

AHU-13 EL/GK-15 GK105

AHU-14 EL/GM-14 GK102

AHU-15 EL/GB-12 BG113

AHU-19 EL/GJ-16 GJ103

GENERAL NOTES:

KEYED NOTES:

NOT TO SCALE:B1 AHU-11H ELECTRICAL

NOT TO SCALE:B5 AHU-13 ELECTRICAL

NOT TO SCALE:D1 AHU-14 ELECTRICAL

NOT TO SCALE:D3 AHU-15 ELECTRICAL

NOT TO SCALE:D5 AHU-19 ELECTRICAL

2 2 2 2 2 3 2 2 2 2HP HP HP HP HP HP HP HP HP HP

HP

U.S. Department of Veterans Affairs

CONSULTANTS ARCHITECT/ENGINEER OF RECORDSTAMP Office of Construction and Facilities Management

Drawing Title

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Building Number

Drawing Number

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

Revisions: Date:

VA FORM 08 - 6231

FULLY SPRINKLERED

MISSION CRITICAL

/1

5/

0:

:0

AM

BI

M

-0

B

AH

U

R ep la ce m en ts /2

0-

B1

A

H U

R ep la ce m en ts M

EP

M od el

R vt

0.

rv t

ELECTRICAL DETAILS AND

DIAGRAMS

REPLACE AHUS AND CHILLER

FOR AHU

EJT VAMC NORTH LITTLE ROCK

598-19-118

EJ202

JDA PROJECT #: D-19-09

A/E

2200 N. RODNEY PARHAM ROAD

SUITE 210

LITTLE ROCK, AR 72212

501-404-4811 jda@JohnsonDanforth.com

JohnsonDanforth & Associates

MEP ENGINEER

INSIGHT ENGINEERING, PLLC

201 S. CHESTER, SUITE B

LITTLE ROCK, AR 72201

COMMISSIONING

BERNHARD

BUILDING 2, 1 ALLIED DRIVE

SUITE 260

LITTLE ROCK, AR 72202

FIRE PROTECTION

FP&C CONSULTANTS KC, LLC

1330 Burlington Street, Ste. 200 North Kansas City, MO 64116

REVISED CONSTRUCTION DOCUMENTS

REVISED CONSTRUCTION

DOCUMENTS

2024.02.02 MPH MPH

1 Addendum #1 2024-02-02

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text U

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text Z

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text

INSIGHT

AutoCAD SHX Text

ENGINEERING, PLLC

AutoCAD SHX Text No. 3523

AutoCAD SHX Text

ARKANSAS

AutoCAD SHX Text

ENGINEER

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text

REGISTERED

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text T

AC-1

RF-1

AC-1A

RF-AC-1A

AC-1B

RF-AC-1B

AC-8

RF-AC-8

1 2

AC-19

AC-10

RF-AC-10

U.S. Department of Veterans Affairs

CONSULTANTS ARCHITECT/ENGINEER OF RECORDSTAMP Office of Construction and Facilities Management

Drawing Title

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Building Number

Drawing Number

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

Revisions: Date:

VA FORM 08 - 6231

FULLY SPRINKLERED

MISSION CRITICAL

/1

5/

0:

:2

AM

BI

M

-0

B

AH

U

R ep la ce m en ts /2

0-

B1

A

H U

R ep la ce m en ts M

EP

M od el

R vt

0.

rv t

ELECTRICAL POWER REPLACE AHUS AND CHILLER

FOR AHU

EJT VAMC NORTH LITTLE ROCK

598-19-118

EP101

JDA PROJECT #: D-19-09

A/E

2200 N. RODNEY PARHAM ROAD

SUITE 210

LITTLE ROCK, AR 72212

501-404-4811 jda@JohnsonDanforth.com

JohnsonDanforth & Associates

MEP ENGINEER

INSIGHT ENGINEERING, PLLC

201 S. CHESTER, SUITE B

LITTLE ROCK, AR 72201

COMMISSIONING

BERNHARD

BUILDING 2, 1 ALLIED DRIVE

SUITE 260

LITTLE ROCK, AR 72202

FIRE PROTECTION

FP&C CONSULTANTS KC, LLC

1330 Burlington Street, Ste. 200 North Kansas City, MO 64116

KEYED NOTES

KEY PLANKEY PLAN

BLDG 170

NGJ100EA,

GJ101

GA105

GL107

GA106

GE122

1/4" = 1'-0"D2 GROUND LEVEL PLAN (GE122) - ELECTRICAL INSTALLATION

1/4" = 1'-0"C5 ELECTRICAL INSTALLATION

1/4" = 1'-0"C7 ELECTRICAL INSTALLATION

1/4" = 1'-0"F2 ELECTRICAL INSTALLATION 1/4" = 1'-0"F5 GROUND LEVEL PLAN (GJ101/GJ100EA) - ELECTRICAL INSTALLATION

DIV 26 MAKE ALL FINAL CONNECTIONS

INCLUDING FROM EXISTING FEEDERS AND

DISCONNECTS TO NEW VFDS BY DIV 23 OR TO

ECM MOTORS WITHOUT VFDS BY DIV 23 PER

SHEETS E201 AND E202

DIV 26 PROVIDE 120A 20A CIRCUIT AND MAKE

FINAL CONNECTIONS TO UV & WORK LIGHTS PER

SHEETS E201 & E202

REVISED CONSTRUCTION DOCUMENTS

REVISED CONSTRUCTION

DOCUMENTS

2024.02.02 MPH MPH

GROUND LEVEL PLAN (GA105) - GROUND LEVEL PLAN (GA106) -

GROUND LEVEL PLAN (GL107) -

1 Addendum #1 2024-02-02

AutoCAD SHX Text

511 GE122-170 MECH ROOM

AutoCAD SHX Text

82 GE119B-170 STORAGE

AutoCAD SHX Text

78 GE119A-170 OFFICE

AutoCAD SHX Text

516 GE113-170 PHARMACY

AutoCAD SHX Text

276 GE113A-170 STORAGE

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text U

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text Z

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text

INSIGHT

AutoCAD SHX Text

ENGINEERING, PLLC

AutoCAD SHX Text No. 3523

AutoCAD SHX Text

ARKANSAS

AutoCAD SHX Text

ENGINEER

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text

REGISTERED

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text T

RF-AC-2

AC-2

RF-AC-3

AC-3

RF-AC-15

2AC-15

AC-11A

RF-AC-11A

1 2

RF-AC-11B

AC-11B

1 2

AC-11C

RF-AC-11C

AC-11D

RF-AC-11D

U.S. Department of Veterans Affairs

CONSULTANTS ARCHITECT/ENGINEER OF RECORDSTAMP Office of Construction and Facilities Management

Drawing Title

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Building Number

Drawing Number

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

Revisions: Date:

VA FORM 08 - 6231

FULLY SPRINKLERED

MISSION CRITICAL

/1

5/

0:

:2

AM

BI

M

-0

B

AH

U

R ep la ce m en ts /2

0-

B1

A

H U

R ep la ce m en ts M

EP

M od el

R vt

0.

rv t

ELECTRICAL POWER REPLACE AHUS AND CHILLER

FOR AHU

EJT VAMC NORTH LITTLE ROCK

598-19-118

EP102

JDA PROJECT #: D-19-09

A/E

2200 N. RODNEY PARHAM ROAD

SUITE 210

LITTLE ROCK, AR 72212

501-404-4811 jda@JohnsonDanforth.com

JohnsonDanforth & Associates

MEP ENGINEER

INSIGHT ENGINEERING, PLLC

201 S. CHESTER, SUITE B

LITTLE ROCK, AR 72201

COMMISSIONING

BERNHARD

BUILDING 2, 1 ALLIED DRIVE

SUITE 260

LITTLE ROCK, AR 72202

FIRE PROTECTION

FP&C CONSULTANTS KC, LLC

1330 Burlington Street, Ste. 200 North Kansas City, MO 64116

BLDG 170

NGA001

GA002

GB111

1A002

1A003

KEY PLAN

1/4" = 1'-0"F2

GROUND LEVEL PLAN (GB111) -

ELECTRICAL INSTALLATION

1/4" = 1'-0"C4

GROUND LEVEL PLAN (GA001) -

ELECTRICAL INSTALLATION

1/4" = 1'-0"C7

GROUND LEVEL PLAN (GA002) -

ELECTRICAL INSTALLATION

1/4" = 1'-0"F5

FIRST LEVEL PLAN (1A002) -

ELECTRICAL INSTALLATION

1/4" = 1'-0"F7

FIRST LEVEL PLAN (1A003) -

ELECTRICAL INSTALLATION

KEYED NOTES

DIV 26 MAKE FINAL CONNECTIONS FROM

EXISTING FEEDERS AND DISCONNECTS TO

NEW VFDS BY DIV 23 OR TO ECM MOTORS

WITHOUT VFDS BY DIV 23 PER SHEETS E201

AND E202

DIV 26 PROVIDE 120A 20A CIRCUIT AND MAKE

FINAL CONNECTIONS TO UV & WORK LIGHTS

PER SHEETS E201 & E202

REVISED CONSTRUCTION DOCUMENTS

REVISED CONSTRUCTION

DOCUMENTS

2024.02.02 MPH MPH

1 Addendum #1 2024-02-02

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text U

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text Z

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text

INSIGHT

AutoCAD SHX Text

ENGINEERING, PLLC

AutoCAD SHX Text No. 3523

AutoCAD SHX Text

ARKANSAS

AutoCAD SHX Text

ENGINEER

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text

REGISTERED

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text T

AC-11F

AC-11F

1 2

AC-11H

AC-11G

AC-12

RF-AC-12

U.S. Department of Veterans Affairs

CONSULTANTS ARCHITECT/ENGINEER OF RECORDSTAMP Office of Construction and Facilities Management

Drawing Title

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Building Number

Drawing Number

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

Revisions: Date:

VA FORM 08 - 6231

FULLY SPRINKLERED

MISSION CRITICAL

/1

5/

0:

:2

AM

BI

M

-0

B

AH

U

R ep la ce m en ts /2

0-

B1

A

H U

R ep la ce m en ts M

EP

M od el

R vt

0.

rv t

ELECTRICAL POWER REPLACE AHUS AND CHILLER

FOR AHU

EJT VAMC NORTH LITTLE ROCK

598-19-118

EP103

JDA PROJECT #: D-19-09

A/E

2200 N. RODNEY PARHAM ROAD

SUITE 210

LITTLE ROCK, AR 72212

501-404-4811 jda@JohnsonDanforth.com

JohnsonDanforth & Associates

MEP ENGINEER

INSIGHT ENGINEERING, PLLC

201 S. CHESTER, SUITE B

LITTLE ROCK, AR 72201

COMMISSIONING

BERNHARD

BUILDING 2, 1 ALLIED DRIVE

SUITE 260

LITTLE ROCK, AR 72202

FIRE PROTECTION

FP&C CONSULTANTS KC, LLC

1330 Burlington Street, Ste. 200 North Kansas City, MO 64116

KEY PLAN

BLDG 170

N

GG102

PH - A

2A002

2A003 3A002

1/4" = 1'-0"C2

SECOND LEVEL PLAN (2A002) -

ELECTRICAL INSTALLATION

1/4" = 1'-0"C4

SECOND LEVEL PLAN (2A003) -

ELECTRICAL INSTALLATION

1/4" = 1'-0"E2

PENTHOUSE LEVEL PLAN (PH - A) -

ELECTRICAL INSTALLATION

1/4" = 1'-0"C7

THIRD LEVEL PLAN (3A002) -

ELECTRICAL INSTALLATION

1/4" = 1'-0"F6

GROUND LEVEL PLAN (GG102) -

ELECTRICAL INSTALLATION

KEYED NOTES

DIV 26 MAKE FINAL CONNECTIONS FROM

EXISTING FEEDERS AND DISCONNECTS TO

NEW VFDS BY DIV 23 OR TO ECM MOTORS

WITHOUT VFDS BY DIV 23 PER SHEETS E201

AND E202

DIV 26 PROVIDE 120A 20A CIRCUIT AND MAKE

FINAL CONNECTIONS TO UV & WORK LIGHTS

PER SHEETS E201 & E202

REVISED CONSTRUCTION DOCUMENTS

REVISED CONSTRUCTION

DOCUMENTS

2024.02.02 MPH MPH

1 Addendum #1 2024-02-02

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text U

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text Z

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text

INSIGHT

AutoCAD SHX Text

ENGINEERING, PLLC

AutoCAD SHX Text No. 3523

AutoCAD SHX Text

ARKANSAS

AutoCAD SHX Text

ENGINEER

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text

REGISTERED

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text T

AC-13

RF-AC-13

1 21 2

AC-14

RF-AC-14

1 2

1 2

AC-20

ST-GE101J

ST-GE101I

ST-GE101H

ST-GE101E

ST-GE101F

ST-GE101G

U.S. Department of Veterans Affairs

CONSULTANTS ARCHITECT/ENGINEER OF RECORDSTAMP Office of Construction and Facilities Management

Drawing Title

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Building Number

Drawing Number

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

Revisions: Date:

VA FORM 08 - 6231

FULLY SPRINKLERED

MISSION CRITICAL

REVISED CONSTRUCTION DOCUMENTS

/1

5/

0:

:3

AM

BI

M

-0

B

AH

U

R ep la ce m en ts /2

0-

B1

A

H U

R ep la ce m en ts M

EP

M od el

R vt

0.

rv t

ELECTRICAL POWER REVISED CONSTRUCTION

DOCUMENTS

REPLACE AHUS AND CHILLER

FOR AHU

EJT VAMC NORTH LITTLE ROCK

2024.02.02 MPH MPH

598-19-118

EP104

JDA PROJECT #: D-19-09

A/E

2200 N. RODNEY PARHAM ROAD

SUITE 210

LITTLE ROCK, AR 72212

501-404-4811 jda@JohnsonDanforth.com

JohnsonDanforth & Associates

MEP ENGINEER

INSIGHT ENGINEERING, PLLC

201 S. CHESTER, SUITE B

LITTLE ROCK, AR 72201

COMMISSIONING

BERNHARD

BUILDING 2, 1 ALLIED DRIVE

SUITE 260

LITTLE ROCK, AR 72202

FIRE PROTECTION

FP&C CONSULTANTS KC, LLC

1330 Burlington Street, Ste. 200 North Kansas City, MO 64116

KEY PLAN

BLDG 170

N

GK104

GH125

GN109

GE101

1/4" = 1'-0"C2

GROUND LEVEL PLAN (GN109) -

ELECTRICAL INSTALLATION

1/4" = 1'-0"E2

GROUND LEVEL PLAN (GK104) -

ELECTRICAL INSTALLATION

1/4" = 1'-0"C6

GROUND LEVEL PLAN (GH125) -

ELECTRICAL INSTALLATION

1/4" = 1'-0"F6 GROUND LEVEL PLAN (GE101) - ELECTRICAL INSTALLATION

KEYED NOTES

DIV 26 MAKE FINAL CONNECTIONS FROM

EXISTING FEEDERS AND DISCONNECTS TO

NEW VFDS BY DIV 23 OR TO ECM MOTORS

WITHOUT VFDS BY DIV 23 PER SHEETS

E201 AND E202

DIV 26 PROVIDE 120A 20A CIRCUIT AND

MAKE FINAL CONNECTIONS TO UV & WORK

LIGHTS PER SHEETS E201 & E202

1 Addendum #1 2024-02-02

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text U

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text Z

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text

INSIGHT

AutoCAD SHX Text

ENGINEERING, PLLC

AutoCAD SHX Text No. 3523

AutoCAD SHX Text

ARKANSAS

AutoCAD SHX Text

ENGINEER

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text

REGISTERED

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text T

100A 3P

PANEL ED/GK EXISTING

277/480V 225A 3P 4W

NEMA TYPE 1

ROOM GK105-170

NEW CHILLER

AND PUMP

SYSTEM

DIV 23

100A 3P NEMA TYPE 3R

(1) SET OF (3) #2+#8G 1-1/2"C

(1) SET OF (3) #2+#8G 1-1/2"C

1 40A 3P1

120/208

(1) SET OF (3) #8+#8G 1"C

MPZ1 SQUARED MPZB15T2T

15KW MINI POWER-ZONE

UNIT SUBSTATION

GROUND TO BUILDING

STEEL PER CODE

20A1P

20A1P

CKT 3 TO LIGHTING CONTROLLER LC1

"STEINEL 80208 DCS" WITH PHOTOCELL

CKT 1 TO SSTV CAMERA

CONTROLLER

20A1P

CKT 5 TO WP GFI 120V

CONVENIENCE RECEPTACLE

AT CHILLER

GENERAL NOTES:

1.

2.

KEYED NOTES:

ANY FINAL WIRE AND CONDUIT CONNECTIONS MAY BE WITH

FLEXIBLE METAL CONDUIT AS NECESSARY

SUBMIT ANY SHOP-MADE SHEET METAL BOXES TO COR FOR JOINT

REVIEW WITH ARCHITECT/ENGINEER. SUCH BOXES MAY FOR

PULLING AND/OR TURNING OF CONDUCTORS INSTEAD OF

CONDULETS, ELBOWS, OR SWEEPS.

NEW 480V 100A BREAKER IN ED/GK RM GK105

APPROX LOCATION OF NEW CHILLER, SEE DIV 23 DRAWINGS

INSTALL NEW 120V WP GFI RECEPTACLE AT NEW CHILLER FED FROM

MPZ1-5

MATERIAL MGMNT OFFICE

GK118-170

OFFICE

GK106A-170

MECH ROOM

GK106-170

PLUMBING SHOP/MECH ROOM

GK107-170

TELEPHONE

EQUIP ROOM

GK105-170

ELECTRICAL

CGN2-170

VESTIBULE

EXIT

EXIT

MPZ1

LC1

100A 3P NEMA TYPE 3R

EXISTING

PANEL

EMERG.

ED/GK

GK118-170

OFFICE

GK107-170

TELEPHONE

EQUIP ROOM

GK105-170

ELECTRICAL

EX

IT

MPZ1

LC1 EXISTING

PANEL

EMERG.

ED/GK

1/8" = 1'-0"

ELECTRICAL: PANEL ED/GK AND MPZ1 LOCATIONSF2

NOT TO SCALE:

ELECTRICAL DIAGRAMB2

1/8" = 1'-0"

ELECTRICAL: RELATIVE LOCATION OF ROOM GK105 AND NEW CHILLERC2

U.S. Department of Veterans Affairs

CONSULTANTS ARCHITECT/ENGINEER OF RECORDSTAMP Office of Construction and Facilities Management

Drawing Title

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Building Number

Drawing Number

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

Revisions: Date:

VA FORM 08 - 6231

FULLY SPRINKLERED

MISSION CRITICAL

REPLACE AHUS AND CHILLER

FOR AHU

EJT VAMC NORTH LITTLE ROCK

598-19-118

EP105

KEY PLAN

BLDG 170

NGJ100EA,

GJ101

GA105

GL107

GA106

GE122

ELECTRICAL POWER REPLACE AHUS AND CHILLER

FOR AHUA/E

2200 N. RODNEY PARHAM ROAD

SUITE 210

LITTLE ROCK, AR 72212

501-404-4811 jda@JohnsonDanforth.com

JohnsonDanforth & Associates

MEP ENGINEER

INSIGHT ENGINEERING, PLLC

201 S. CHESTER, SUITE B

LITTLE ROCK, AR 72201

COMMISSIONING

BERNHARD

BUILDING 2, 1 ALLIED DRIVE

SUITE 260

LITTLE ROCK, AR 72202

FIRE PROTECTION

FP&C CONSULTANTS KC, LLC

1330 Burlington Street, Ste. 200 North Kansas City, MO 64116

REVISED CONSTRUCTION DOCUMENTS

REVISED CONSTRUCTION

DOCUMENTS

2024.02.02 MPH MPH

1 Addendum #1 2024-02-02

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text U

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text Z

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text

INSIGHT

AutoCAD SHX Text

ENGINEERING, PLLC

AutoCAD SHX Text No. 3523

AutoCAD SHX Text

ARKANSAS

AutoCAD SHX Text

ENGINEER

AutoCAD SHX Text

PROFESSIONAL

AutoCAD SHX Text

REGISTERED

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text T

X-AC-1MECH ROOM

GE122-170

R A

"x

R A

"x

O A

"x

1 1

RA 62"x24"

R A

"x

X-RF-1

GE113A-170

GE114A-170

RA 62"x24"

RA 62"x24"

SA 56"x24"

EXISTING

DISCONNECT

EXISTING RELIEF

AIR LOUVER

X -A

C -1

A

MECH ROOM

GA105-170

TELEPHONE

GA104-170

X -R

F -1

A

RA 12"x10"

R A

"x

RA 48"x24"

R A

"x

R A

"x

R A

"x

1 1

X T

U R

-1

SA 8"ø

S A

"x

OA 36"x12"RA 24"x14"

S A

"x

SA 24"x20"

EXISTING DISCONNECT

EXISTING RELIEF

AIR LOUVER

X -A

C -1

B

MECH ROOM

GA106-170

ELECTRICAL

GA107-170

R A

"x

X -R

F -1

B

RA 48"x24"

R A

"x

O A

"x

R A

"x

SA 24"x20"

S A

"x

S A

"x

SA 14"x8"

SA8"ø

EXISTING DISCONNECT

EXISTING DISCONNECT

EXISTING RELIEF

AIR LOUVER

X-AC-8

X-RF-8

MECH ROOM

GL107-170

RA 60"x36"

R A

"x

1 1

EXISTING RELIEF

AIR LOUVER

OA 86"x20"

SA 60"x26" RA 60"x36"

X-AC-19

X-AC-10

MECH ROOM

GJ101-170

MECH ROOM

GJ100EA-170

SA 24"x16" S

A "x

X-RF-10

RA 48"x24"RA 48"x24"

R A

"x

O A

60"x24"

OA 60"x24"

SA 72"x18"

R A

"x

OA 60"x24"

RA 24"x72"

RA 60"x20"

OA 32"x24"

SA 24"x16"

EXISTING INTAKE

AIR LOUVER

EXISTING RELIEF

AIR LOUVER

SA 20"x20"

EXISTING

DISCONNECT

XFD

XFD

EXISTING DISCONNECT

EXISTING DISCONNECT

SYMBOL

H-1

NEW DUCT/PIPING

EXISTING DUCT/PIPING TO REMAIN

NEW EQUIPMENT

DESCRIPTION

HVAC EQUIPMENT DESIGNATION

EXISTING EQUIPMENT TO REMAIN

EXISTING EQUIPMENT TO BE DEMOLISHED

EXISTING DUCT/PIPING TO BE DEMOLISHED

CONNECT TO EXISTING

POINT OF DEMOLITION

SUPPLY DIFFUSER

RETURN GRILLE

EXHAUST GRILLE

MANUAL VOLUME DAMPER

STREAMLINE TAP WITH MANUAL VOLUME DAMPER

CAPPED PIPE

THERMOSTAT WIRE

T THERMOSTAT

LEGEND

U.S. Department of Veterans Affairs

CONSULTANTS ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

Drawing Title

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Building Number

Drawing Number

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

Revisions: Date:

VA FORM 08 - 6231

FULLY SPRINKLERED

MISSION CRITICAL

CONSTRUCTION DOCUMENTS

/5

/2

:1

:3

P M

A u to d e s k D o c s

/2 -0

B

A H

U R e p la c e m e n ts /2

-0

B

A

H U

R e p la c e m e n ts

M E

P M o d e l R v t

.r v t

HVAC DUCTWORK DEMOLITION CONSTRUCTION DOCUMENTS REPLACE AHUS AND CHILLER

FOR AHU

EJT VAMC NORTH LITTLE ROCK

2024-02-02 KCK CJC

598-19-118

MD101

JDA PROJECT #: D-19-09

DEMOLITION KEYED NOTES

EXISTING VARIABLE FREQUENCY DRIVE TO BE DEMOLISHED.

EXISTING HVAC CONTROLLER TO REMAIN IN PLACE.

A/E

2200 N. RODNEY PARHAM ROAD

SUITE 210

LITTLE ROCK, AR 72212

501-404-4811 jda@JohnsonDanforth.com

JohnsonDanforth & Associates

MEP ENGINEER

INSIGHT ENGINEERING, PLLC

201 S. CHESTER, SUITE B

LITTLE ROCK, AR 72201

COMMISSIONING

BERNHARD

BUILDING 2, 1 ALLIED DRIVE

SUITE 260

LITTLE ROCK, AR 72202

FIRE PROTECTION

FP&C CONSULTANTS KC, LLC

1330 Burlington Street, Ste. 200 North Kansas City, MO 64116

KEY PLAN

SCALE: 1/4" = 1'-0"

0 2' 4' 8'

BLDG 170

N

GJ100EA,

GJ101

GA105

GL107

GA106

GE122

1/4" = 1'-0"D1

GROUND LEVEL PLAN (GE122) - HVAC DEMOLITION

SLAB ELEVATION = 287.73'

1/4" = 1'-0"C4

GROUND LEVEL PLAN (GA105) - HVAC DEMOLITION

1/4" = 1'-0"C7

GROUND LEVEL PLAN (GA106) - HVAC DEMOLITION

1/4" = 1'-0"F1

GROUND LEVEL PLAN (GL107) - HVAC DEMOLITION

1/4" = 1'-0"F4

GROUND LEVEL PLAN (GJ101/GJ100EA) - HVAC DEMOLITION

SLAB ELEVATION = 287.73' SLAB ELEVATION = 287.73'

SLAB ELEVATION = 287.73' SLAB ELEVATION = 287.73'

GENERAL NOTES

1. EXISTING AC UNITS AND RETURN FANS TO BE DEMOLISHED. DEMOLISH

EXISTING DUCTWORK TO THE EXTENT NECESSARY TO REPLACE

EQUIPMENT. RETAIN EXISTING HUMIDIFIERS.

2. DEMOLISH PIPING TO THE EXTENT NECESSARY TO REPLACE EQUIPMENT.

RETAIN EXISTING ISOLATION VALVES.

3. IF AN EXISTING MOTORIZED BALANCING DAMPER IS REMOVED DUE TO

DUCTWORK REMOVAL, REPLACE THE DAMPER WITH A NEW MOTORIZED

DAMPER IN THE APROXIMATE LOCATION OF THE EXISTING DAMPER, AS

CLOSE AS POSSIBLE. INSTALL PER MANUFACTURER’S RECOMMENDATIONS

AND REQUIREMENTS. REFER TO CONTROL DIAGRAMS.

1 Addendum #1 2024-02-02

AN

SKR A

A S

C E R T

IF

IC

AT

EO

FAUTHOR

IZ

AT

IO

N

INSIGHT

ENGINEERING, PLLC

No. 3523

NO. 12022

ARKANSAS

ENGINEER

PROFESSIONAL

REGISTERED

OFETA

S T

K

IM

B

ERLY CLA I

R

K O C H

2024-02-02

MECH ROOM

GB111-170

STORAGE

GB104A-170

STORAGE

GB104B-170

CORRIDOR

CGB3-170

CORRIDOR

CGB5-170

POWER ROOM

GB114-170

X-AC-2

X-RF-2

X-AC-3

X-AC-15

X-RF-15

SA 20"x20"

SA 34"x20"

RA 32"x24"

X-RF-3

RA 32"x24"

R A

"x

R A

"x

RA 24"x16" RA 28"x16"

RA 36"x20"

RA 28"x16"

RA 34"x20"

RA 32"x24"

SA 34"x20"

RA 28"x16"

SA 34"x20"

SA 32"x24"

RA 32"x14"

S A

"x

R A

"x

SA 28"x18" SA28"x18"

R A

"x

R A

"x

SA32"x24"

EXISTING

OUTSIDE

AIR INTAKE

LOUVER

EXISTING

OUTSIDE

AIR INTAKE

LOUVER

EXISTING

RELIEF

AIR LOUVER

EXISTING

OUTSIDE

AIR INTAKE

LOUVER

RA 60"x18"

OA 60"x24"

OA 60"x18"RA 60"x18"

RA 66"x22"

RA 28"x16"

RA 20"x20"

RA 36"x20"

R A

"x

EXISTING

DISCONNECT

EXISTING

DISCONNECT

EXISTING

DISCONNECT

OA 60"x24"

MECH ROOM

GA001-170

CHASE

X -A

C -1

A

R A

"x

X -R

F -1

A

R A

"x

S A

"x

OA 24"x24"

RA 14"x14"

RA 14"x32"

CHASE

MECH ROOM

GA002-170

X -A

C -1

B

X -R

F -1

B

R A

"x

S A

"x

R A

"x

RA 14"x14"

RA 40"x14"

OA 24"x24"

MECH ROOM

1A002-170

CHASE

X -A

C -1

C

S A

"x

R A

"x

X -R

F -1

C

R A

"x

RA 14"x14"

OA 24"x24"

RA 14"x32"

MECH ROOM

1A003-170

CHASE

X -A

C -1

D

X -R

F -1

D

R A

"x

R A

"x

SA 24"x14"

RA 14"x14"

RA 14"x32"

OA 24"x24"

EXISTING DISCONNECT

EXISTING DISCONNECT

SYMBOL

H-1

NEW DUCT/PIPING

EXISTING DUCT/PIPING TO REMAIN

NEW EQUIPMENT

DESCRIPTION

HVAC EQUIPMENT DESIGNATION

EXISTING EQUIPMENT TO REMAIN

EXISTING EQUIPMENT TO BE DEMOLISHED

EXISTING DUCT/PIPING TO BE DEMOLISHED

CONNECT TO EXISTING

POINT OF DEMOLITION

SUPPLY DIFFUSER

RETURN GRILLE

EXHAUST GRILLE

MANUAL VOLUME DAMPER

STREAMLINE TAP WITH MANUAL VOLUME DAMPER

CAPPED PIPE

THERMOSTAT WIRE

T THERMOSTAT

LEGEND

U.S. Department of Veterans Affairs

CONSULTANTS ARCHITECT/ENGINEER OF RECORD STAMP Office of Construction and Facilities Management

Drawing Title

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Building Number

Drawing Number

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

Revisions: Date:

VA FORM 08 - 6231

FULLY SPRINKLERED

MISSION CRITICAL

CONSTRUCTION DOCUMENTS

/5

/2

:1

:3

P M

A u to d e s k D o c s

/2 -0

B

A H

U R e p la c e m e n ts /2

-0

B

A

H U

R e p la c e m e n ts

M E

P M o d e l R v t

.r v t

HVAC DUCTWORK DEMOLITION CONSTRUCTION DOCUMENTS REPLACE AHUS AND CHILLER

FOR AHU

EJT VAMC NORTH LITTLE ROCK

2024-02-02 KCK CJC

598-19-118

MD102

JDA PROJECT #: D-19-09

A/E

2200 N. RODNEY PARHAM ROAD

SUITE 210

LITTLE ROCK, AR 72212

501-404-4811 jda@JohnsonDanforth.com

JohnsonDanforth & Associates

MEP ENGINEER

INSIGHT ENGINEERING, PLLC

201 S. CHESTER, SUITE B

LITTLE ROCK, AR 72201

COMMISSIONING

BERNHARD

BUILDING 2, 1 ALLIED DRIVE

SUITE 260

LITTLE ROCK, AR 72202

FIRE PROTECTION

FP&C CONSULTANTS KC, LLC

1330 Burlington Street, Ste. 200 North Kansas City, MO 64116

1/4" = 1'-0"F1

GROUND LEVEL PLAN (GB111) - HVAC DEMOLITION

1/4" = 1'-0"C4

GROUND LEVEL PLAN (GA001) - HVAC DEMOLITION

1/4" = 1'-0"C6

GROUND LEVEL PLAN (GA002) - HVAC DEMOLITION

1/4" = 1'-0"F4

FIRST LEVEL PLAN (1A002) - HVAC DEMOLITION

1/4" = 1'-0"F6

FIRST LEVEL PLAN (1A003) - HVAC DEMOLITION

KEY PLAN

SCALE: 1/4" = 1'-0"

0 2' 4' 8'

SLAB ELEVATION = 287.73' SLAB ELEVATION = 287.73'

SLAB ELEVATION = 287.73' SLAB ELEVATION = 303.00' SLAB ELEVATION = 303.00'

BLDG 170

N

GA001

GA002

GB111

1A002

1A003

GENERAL NOTES

1. EXISTING AC UNITS AND RETURN FANS TO BE DEMOLISHED. DEMOLISH

EXISTING DUCTWORK TO THE EXTENT NECESSARY TO REPLACE

EQUIPMENT. RETAIN EXISTING HUMIDIFIERS.

2. DEMOLISH PIPING TO THE EXTENT NECESSARY TO REPLACE EQUIPMENT.

RETAIN EXISTING ISOLATION VALVES.

3. IF AN EXISTING MOTORIZED BALANCING DAMPER IS REMOVED DUE TO

DUCTWORK REMOVAL, REPLACE THE DAMPER WITH A NEW MOTORIZED

DAMPER IN THE APROXIMATE LOCATION OF THE EXISTING DAMPER, AS

CLOSE AS POSSIBLE. INSTALL PER MANUFACTURER’S RECOMMENDATIONS

AND REQUIREMENTS. REFER TO CONTROL DIAGRAMS.

DEMOLITION KEYED NOTES

EXISTING VARIABLE FREQUENCY DRIVE TO BE DEMOLISHED.

EXISTING HVAC CONTROLLER TO REMAIN IN PLACE.

1 Addendum #1 2024-02-02

AN

SKR A

A S

C E R T

IF

IC

AT

EO

FAUTHOR

IZ

AT

IO

N

INSIGHT

ENGINEERING, PLLC

No. 3523

NO. 12022

ARKANSAS

ENGINEER

PROFESSIONAL

REGISTERED

OFETA

S T

K

IM

B

ERLY CLA I

R

K O C

2A002-170

CHASE

R A

"x

R A

"x

RA 14"x14"

X -R

F -1

E

R A

"x

S A

"x

X -A

C -1

E

O A

"x

MECH ROOM

2A003-170

CHASE

R A

"x

X -R

F -1

F

X -A

C F

-1 F

R A

"x

S A

"x

RA 14"x14"

O A

"x

X-AC-11H

X-RF-11H

R A

"x

RA 34"x30" RA 34"x30"

SA 48"x24"

OA 48"x22"

RA 34"x30"

PENTHOUSE

PH-A

EXISTING RELIEF

AIR LOUVER

EXISTING RELIEF

AIR LOUVER

EXISTING INTAKE

AIR LOUVER

MECH ROOM

3A002-170

CHASE

X -A

C -1

G

X -R

F -1

G

R A

"x

S A

"x

R A

"x

RA 14"x14"

O A

"x

AC SHOP

GG102A-170

ELEC EQUIP REPAIR /

MECH ROOM

GG102-170

CORRIDOR

CGG1-170

X-AC-12

R A

"x

X-RF-12

S A

"x

OA 32"x86"

OA 30"x30"

OA 96"x60"

RA 36"x36"

RA 36"x36"

SA 30"x30"

SA 30"x30"

SA 26"x24"

RA 36"x24"

EXISTING DISCONNECT

XFD

RA 30"x30"

O A

"x

O A

"x

EXISTING INTAKE

AIR LOUVER

EXISTING RELIEF

AIR LOUVER

SYMBOL

H-1

NEW DUCT/PIPING

EXISTING DUCT/PIPING TO REMAIN

NEW EQUIPMENT

DESCRIPTION

HVAC…

This is the start of the file's text. The full file is on GovTribe.