Parking Garage - Fire Detection and Alarm.pdf

PDF 3 MB Posted

Attached to
H312--580-23-1-5129-0002 Fire Alarm and Sprinkler System Inspections
Solicitation number
36C25623Q0281
Issued by

View the file

Other files

File Type Posted
Fisher House 3 - 2017-02-14 Fire Alarm As-Built_FA1.pdf PDF
Fire Alarm System_Numbers of Devices.doc DOC document
Copy of Garage and Fisher House 1 2 and 3 Fire Devices.xlsx XLSX spreadsheet
36C25623Q0281_2.docx DOCX document
Attachment 1 - Fire and Sprinkler Inspection SOW.docx DOCX document
RFQ 36C25623Q0281_1.docx DOCX document
Attachment 3 - SAM Wage Determination.pdf PDF
Attachment 2 - Fire QASP 1 18 23.docx DOCX document
Attachment 4 - Technical Capability Questionnaire.docx DOCX document
36C25623Q0281.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2 0 0 0 S. D O U G L A S B L V D . |M I D W E S T C I T Y , O K 7 3 1 3 0 |P H O N E 4 0 5 -7 37 -7 5 8 8 |F A X 4 0 5 -8 6 9 -4 9 9 5

VA256-16-C-0116

CONSTRUCT PARKING GARAGE A

MICHAEL E DEBAKEY VA MEDICAL CENTER, HOUSTON, TX

SUBMITTAL TRANSMITTAL LETTER

Submittal Transmittal Letter

Name of Contractor: HGL Construction, Inc.

Contract Number: VA256-16-C-0116

Project Title: Construct Parking Garage A

Name of Medical Center: Michael E. Debakey VA Medical Center, Houston, TX

Specification Section: 28 31 00

Paragraph Number: 1.4 (Drawings, Manuals, Certifications)

Drawing Number: NA

Submittal Number: 1.R.1 Revised

Approval/Disapproval Stamp isoule isoule Highlight isoule Text Box 2017-06-23

Project: VA Garage

Customer: HGL Construction

Supplier: Firetron, Inc.

State License #ACR-01136

Manufacturer: Notifier

Governing Code Year: 2013

Date of Submittal: 1/18/2017

Date of Re-Submittal: 6/20/2017

Salesman: Andy Crate

Date: 6/20/2017

Project Designer: Mike Ayala

DN-7112:G • 12/19/2011 — Page 1 of 6

NFS-320(E)

Intelligent Addressable Fire Alarm System

Intelligent Fire Alarm Control Panels

DN-7112:G

NFS-320

ph o1

.jp g

General The NFS-320 intelligent Fire Alarm Control Panel is part of the ONYX® Series of Fire Alarm Controls from NOTIFIER.

In stand-alone or network configurations, ONYX Series products meet virtually every application requirement.

The NFS-320‘s modular design makes system planning easier.

The panel can be configured with just a few devices for small building applications, or networked with many devices to protect a large campus or a high-rise office block. Simply add additional peripheral equipment to suit the application.

For installations using NFS-320C, an optional ACM Series annunciator can be mounted in the same cabinet (up to 48 zones/points, order separately; see DN-60085).

The FireWatch Series internet monitoring modules IPDACT-2 and IPDACT-2UD permit monitoring of alarm signals over the Internet, saving the monthly cost of two dedicated business tele-phone lines. Although not required, the secondary telephone line may be retained providing backup communication over the public switched telephone line.

NOTE: Unless called out with a version-specific “R”, “C” or “E” at the end of the part number, “NFS-320” refers to models NFS-320, NFS-320R, NFS-320C, and NFS-320E.

Features

• Certified for seismic applications when used with the appro-priate seismic mounting kit.

• Approved for Marine applications when used with listed com-patible equipment (see DN-60688).

• One isolated intelligent Signaling Line Circuit (SLC) Style 4, 6 or 7.

• Up to 159 detectors (any mix of ion, photo, thermal, or multi-sensor) and 159 modules (Addressable pull stations, nor-mally open contact devices, two-wire smoke, notification, or relay). 318 devices maximum.

• Standard 80-character display.

• Network options:

– High-speed network for up to 200 nodes (NFS2-3030, NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC, ONYXWorks, NFS-3030, NFS-640, and NCA).

– Standard network for up to 103 nodes (NFS2-3030, NFS2-

640, NFS-320(C), NFS-320SYS, NCA-2, DVC, ONYX-

Works, NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP- 300/400, AFP-1010, and AM2020). Up to 54 nodes when DVC is used in network paging.

• 6.0 A power supply with four Class A/B built-in Notification Appliance Circuits (NAC). Selectable System Sensor, Wheelock, or Gentex strobe synchronization.

• Built-in Alarm, Trouble, Security, and Supervisory relays.

• VeriFire® Tools online or offline programming utility. Upload/

Download, save, store, check, compare, and simulate panel databases. Upgrade panel firmware.

• Autoprogramming and Walk Test reports.

• Optional universal 318-point DACT.

• 80-character remote annunciators (up to 32).

• EIA-485 annunciators, including custom graphics.

• Printer interface (80-column and 40-column printers).

• History file with 800-event capacity in nonvolatile memory, plus separate 200-event alarm-only file.

• Alarm Verification selection per point, with tally.

• Presignal/Positive Alarm Sequence (PAS).

• Silence inhibit and Auto Silence timer options.

• NAC coding functions:

– March time.

– Temporal.

– California two-stage coding.

– Canadian two-stage.

– Strobe synchronization.

• Field-programmable on panel or on PC, with VeriFire® Tools program check, compare, simulate.

• Full QWERTY keypad.

• Battery charger supports 18 – 200 AH batteries.

• Non-alarm points for lower priority functions.

• Remote ACK/Signal Silence/System Reset/Drill via monitor modules.

• Automatic time control functions, with holiday exceptions.

• Extensive, built-in transient protection.

• Powerful Boolean logic equations.

FLASHSCAN® INTELLIGENT FEATURES

• Poll up to 318 devices in less than two seconds.

• Activate up to 159 outputs in less than five seconds.

• Multicolor LEDs blink device address during Walk Test.

• Fully digital, high-precision protocol (U.S. Patent 5,539,389).

• Manual sensitivity adjustment — nine levels.

• Pre-alarm ONYX intelligent sensing — nine levels.

• Day/Night automatic sensitivity adjustment.

• Sensitivity windows:

– Ion – 0.5 to 2.5%/foot obscuration.

– Photo – 0.5 to 2.35%/foot obscuration.

– Laser (VIEW®) – 0.02 to 2.0%/foot obscuration.

– Acclimate® Plus™ – 0.5 to 4.0%/foot obscuration.

– IntelliQuad – 1.0 to 4.0%/foot obscuration.

– IntelliQuad™ PLUS – 1.0 to 4.0%/foot obscuration

• Drift compensation (U.S. Patent 5,764,142).

Page 2 of 6 — DN-7112:G • 12/19/2011

• Degraded mode — in the unlikely event that the NFS-320’s primary microprocessor fails, FlashScan detectors revert to degraded operation and can activate the control panel’s NAC circuits and alarm relay. Each of the four built-in panel circuits includes a Disable/Enable switch for this feature.

• Multi-detector algorithm involves nearby detectors in alarm decision (U.S. Patent 5,627,515).

• Automatic detector sensitivity testing (NFPA-72 compliant).

• Maintenance alert (two levels).

• Self-optimizing pre-alarm.

FSL-751 VIEW (VERY INTELLIGENT EARLY WARNING)

SMOKE DETECTION TECHNOLOGY

• Revolutionary spot laser design.

• Advanced ONYX intelligent sensing algorithms differentiate between smoke and non-smoke signals (U.S. Patent 5,831,524).

• Addressable operation pinpoints the fire location.

• No moving parts to fail or filters to change.

• Early warning performance comparable to the best aspiration systems at a fraction of the lifetime cost.

FAPT-851 ACCLIMATE® PLUS™

LOW-PROFILE INTELLIGENT MULTI-SENSOR

• Detector automatically adjusts sensitivity levels without oper-ator intervention or programming. Sensitivity increases with heat.

• Microprocessor-based technology; combination photo and thermal technology.

• FlashScan or CLIP (“classic”) mode compatible.

• Low-temperature warning signal at 40°F ± 5°F (4.44°C ±

2.77°C).

FSC-851 INTELLIQUAD

ADVANCED MULTI-CRITERIA DETECTOR

• Detects all four major elements of a fire (smoke, heat, CO, and flame).

• Automatic drift compensation of smoke sensor and CO cell.

• High nuisance-alarm immunity.

• Six sensitivity levels.

FCO-851 INTELLIQUAD™ PLUS

ADVANCED MULTI-CRITERIA FIRE/CO DETECTOR

• Detects all four major elements of a fire.

• Separate signal for life-safety CO detection.

• Optional addressable sounder base for Temp-3 (fire) or

Temp-4(CO) tone.

• Automatic drift compensation of smoke sensor and CO cell.

• High nuisance-alarm immunity.

• Six sensitivity levels.

Sample System Options

7112blok.wmf

NFS-320

RELEASING FEATURES

• Ten independent hazards.

• Sophisticated cross-zone (three options).

• Delay timer and Discharge timers (adjustable).

• Abort (four options).

• Low-pressure CO2 listed.

VOICE FEATURES

• Integrates with FireVoice-25/50 Series (see DN-7004).

• Integrates via serial connection with FireVoice-25/50ZS

Series (see DN-7003).

HIGH-EFFICIENCY OFFLINE SWITCHING

3.0 A POWER SUPPLY (6.0 A IN ALARM)

• 120 VAC (NFS-320/NFS-320C); 240 VAC (NFS-320E).

• Displays battery current/voltage on panel (with display).

DN-7112:G • 12/19/2011 — Page 3 of 6

FlashScan, Exclusive World-Leading Detector Protocol At the heart of the NFS-320 is a set of detection devices and device protocol — FlashScan (U.S. Patent 5,539,389). FlashS-can is an all-digital protocol that gives superior precision and high noise immunity.

In addition to providing quick identification of an active input device, this new protocol can also activate many output devices in a fraction of the time required by competitive protocols. This high speed also allows the NFS-320 to have the largest device per loop capacity in the industry — 318 points — yet every input and output device is sampled in less than two seconds. The microprocessor-based FlashScan detectors have bicolor LEDs that can be coded to provide diagnostic information, such as device address during Walk Test.

ONYX Intelligent Sensing Intelligent sensing is a set of software algorithms that provides the NFS-320 with industry-leading smoke detection capability.

These complex algorithms require many calculations on each reading of each detector, and are made possible by the high-speed microcomputer used by the NFS-320.

Drift Compensation and Smoothing: Drift compensation allows the detector to retain its original ability to detect actual smoke, and resist false alarms, even as dirt accumulates. It reduces maintenance requirements by allowing the system to automatically perform the periodic sensitivity measurements required by NFPA 72. Smoothing filters are also provided by software to remove transient noise signals, such as those caused by electrical interference.

Maintenance Warnings: When the drift compensation per-formed for a detector reaches a certain level, the performance of the detector may be compromised, and special warnings are given. There are three warning levels: (1) Low Chamber value;

(2) Maintenance Alert, indicative of dust accumulation that is near but below the allowed limit; (3) Maintenance Urgent, indica-tive of dust accumulation above the allowed limit.

Sensitivity Adjust: Nine sensitivity levels are provided for alarm detection. These levels can be set manually, or can change automatically between day and night. Nine levels of pre-alarm sensitivity can also be selected, based on predetermined levels of alarm. Pre-alarm operation can be latching or self-restoring, and can be used to activate special control functions.

Self-Optimizing Pre-Alarm: Each detector may be set for “Self- Optimizing” pre-alarm. In this special mode, the detector “learns” its normal environment, measuring the peak analog readings over a long period of time, and setting the pre-alarm level just above these normal peaks.

Cooperating Multi-Detector Sensing: A patented feature of ONYX intelligent sensing is the ability of a smoke sensor to con-sider readings from nearby sensors in making alarm or pre-alarm decisions. Without statistical sacrifice in the ability to resist false alarms, it allows a sensor to increase its sensitivity to actual smoke by a factor of almost two to one.

Field Programming Options Autoprogram. This timesaving feature is a special software rou-tine. The FACP “learns” what devices are physically connected and automatically loads them in the program with default values for all parameters. Requiring less than one minute to run, this routine allows the user to have almost immediate fire protection in a new installation, even if only a portion of the detectors are installed.

Keypad Program Edit (with KDM-R2) The NFS-320, like all NOTIFIER intelligent panels, has the exclusive feature of pro-gram creation and editing capability from the front panel keypad, while continuing to provide fire protection. The architecture of the NFS-320 software is such that each point entry carries its own program, including control-by-event links to other points.

This allows the program to be entered with independent per-point segments, while the NFS-320 simultaneously monitors other (already installed) points for alarm conditions.

VeriFire® Tools is an offline programming and test utility that can greatly reduce installation programming time, and increase con-fidence in the site-specific software. It is Windows®-based and provides technologically advanced capabilities to aid the installer. The installer may create the entire program for the NFS-320 in the comfort of the office, test it, store a backup file, then bring it to the site and download from a laptop into the panel.

Placement of Equipment in Chassis and Cabinet The following guidelines outline the NFS-320’s flexible system design.

Wiring: When designing the cabinet layout, consider separation of power-limited and non-power-limited wiring as discussed in the NFS-320 Installation Manual.

It is critical that all mounting holes of the NFS-320 are secured with a screw or standoff to ensure continuity of Earth Ground.

Networking: If networking two or more control panels, each unit requires a Network Control Module or High-Speed Network Control Module (HS-NCM can support two nodes; see “Net-working Options” on page 4). These modules can be installed in any option board position (see manual), and additional option boards can be mounted in front of them.

KDM-R2 Controls and Indicators Program Keypad: QWERTY type (keyboard layout).

12 LED Indicators: Power; Fire Alarm; Pre-Alarm; Security;

Supervisory; System Trouble; Signals Silenced; Points Dis-abled; Control Active; Abort; Pre-Discharge; Discharge.

Keypad Switch Controls: Acknowledge/Scroll Display; Signal Silence; Drill; System Reset; Lamp Test.

LCD Display: 80 characters (2 x 40) with long-life LED back-light.

Ordering Information

• “Configuration Guidelines” on page 3

• “Networking Options” on page 4

• “Auxiliary Power Supplies and Batteries” on page 4

• “Audio Options” on page 4

• “Compatible Devices, EIA-232 Ports” on page 4

• “Compatible Devices, EIA-485 Ports” on page 4

• “Compatible Intelligent Devices” on page 4

• “Enclosures, Chassis, and Dress Plates” on page 5

• “Other Options” on page 5

CONFIGURATION GUIDELINES

The NFS-320 system ships assembled; description and some options follow. See “Enclosures, Chassis, and Dress Plates” on page 5 for information about mounting peripherals.

NOTE: Stand-alone and network systems require a main display.

On stand-alone systems, the panel’s keypad provides the required display. On network systems (two or more networked fire panel nodes), at least one NCA-2, NCS, or ONYXWorks annunciation device is required.

NFS-320: The standard, factory-assembled NFS-320 system includes the following components: one control panel mounted on chassis (120 V operation — ships with grounding cable, bat-tery interconnect cables, and document kit); includes integral power supply mounted to the main circuit board; one primary display KDM-R2 keypad/display; and one cabinet for surface or

Page 4 of 6 — DN-7112:G • 12/19/2011 semi-flush mounting. Purchase batteries separately. One or two option boards may be mounted inside the NFS-320 cabinet;

additional option boards can be used in remote cabinets.

NFS-320R: Same as NFS-320 above, but in red enclosure.

NFS-320C: Based on NFS-320 above. NFS-320C supports installation of an optional ACM-series annunciator in the same cabinet. UL- and ULC-listed.

NOTE: For additional information on NFS-320C, see DN-60085.

NFS-320E: Same as NFS-320 above, but with 240 V operation.

TR-320: Trim ring for the NFS-320 cabinet.

NETWORKING OPTIONS

NCM-W, NCM-F: Standard Network Communications Modules.

Wire and multi-mode fiber versions available. See DN-6861.

HS-NCM-W/MF/SF/WMF/WSF/MFSF: High-speed network communications modules. Wire, single-mode fiber, multi-mode fiber, and media conversion models are available. See DN- 60454.

RPT-W, RPT-F, RPT-WF: Standard-network repeater board with wire connection (RPT-W), fiber connection (RPT-F), or allowing a change in media type between wire and fiber (RPT-WF). Not used with high-speed networks. See DN-6971.

ONYXWorks: UL-listed graphics PC workstation, software, and computer hardware. See DN-7048 for specific part numbers.

NFN-GW-EM-3: NFN Gateway, embedded.

AUXILIARY POWER SUPPLIES AND BATTERIES

ACPS-610: 6.0 A or 10 A addressable charging power supply.

See DN-60244.

APS2-6R: Auxiliary Power Supply. Provides up to 6.0 amperes of power for peripheral devices. Includes battery input and trans-fer relay, and overcurrent protection. Mounts on two of four posi-tions on a CHS-4L or CHS-4 chassis. See DN-5952.

FCPS-24S6/S8: Remote 6 A and 8 A power supplies with bat-tery charger. See DN-6927.

BAT Series: Batteries. NFS-320 uses two 12 volt, 18 to 200 AH batteries. See DN-6933.

AUDIO OPTIONS

NFV-25/50: 25 watt, 25 VRMS, emergency Voice Evacuation Control Panel (VECP) with integral commercial microphone, dig-ital message generator, and single-/dualchannel Class A or Class B speaker circuits. See DN-7004.

NFV-25/50DA: Single channel, 25 Watt, 25 VRMS, emergency voice evacuation panel. See DN-60048.

NFV-25/50DAZS: Single channel, 25 Watt, 25 Vrms, emergency voice evacuation panel. Can be automatically activated via the Zone System serial communication link from the NFV-25/50ZS.

See DN-60049.

NFV-25/50ZS: 25 watt, 25 Vrms, emergency Voice Evacuation Control Panel (VECP) with integral commercial microphone, dig-ital message generator, zone splitter module (ACC-ZSM), zone page module with keypad (ACC-ZPMK). See DN-7003

NFV-25/50ZST: 25 watt, 25 Vrms, emergency Voice Evacuation Control Panel (VECP) with integral commercial microphone, dig-ital message generator, zone splitter module (ACC-ZSM), zone page module with keypad (ACC-ZPMK). See DN-60337.

COMPATIBLE DEVICES, EIA-232 PORTS

PRN-6: 80-column printer. See DN-6956.

VS4095/5: Printer, 40-column, 24 V. Mounted in external back-box. See DN-3260.

DPI-232: Direct Panel Interface, specialized modem for extend-ing serial data links to remotely located FACPs and/or peripher-als; mount on NFS-320 chassis. See DN-6870.

COMPATIBLE DEVICES, EIA-485 PORTS

ACM-24AT: ONYX Series ACS annunciator – up to 96 points of annunciation with Alarm or Active LED, Trouble LED, and switch per circuit. Active/Alarm LEDs can be programmed (by pow-ered-up switch selection) by point to be red, green, or yellow; the Trouble LED is always yellow. See DN-6862.

AEM-24AT: Same LED and switch capabilities as ACM-24AT, expands the ACM-24AT to 48, 72, or 96 points. See DN-6862.

ACM-48A: ONYX Series ACS annunciator – up to 96 points of annunciation with Alarm or Active LED per circuit. Active/Alarm LEDs can be programmed (by powered-up switch selection) in groups of 24 to be red, green, or yellow. Expandable to 96 points with one AEM-48A. See DN-6862.

AEM-48A: Same LED capabilities as ACM-48A, expands the ACM-48A to 96 points. See DN-6862.

ACM-8R: Remote Relay Module with eight Form-C contacts.

Can be located up to 6,000 ft. (1828.8 m) from panel on four wires. See DN-3558.

LCD-80: ACS mode. 80-character, backlit LCD display. Mounts up to 6,000 ft. (1828.8 m) from panel. Up to 32 per FACP. See

LCD-80/-80TM (DN-3198).

FDU-80: Terminal mode. 80-character, backlit LCD display.

Mounts up to 6,000 ft. (1828.8 m) from panel. Up to 32 per FACP. See DN-6820.

LCD2-80: Terminal mode. 80-character, backlit LCD display.

Mounts up to 6,000 ft. (1828.8 m) from panel. Up to 32 per FACP. See DN-60548.

LDM: Lamp Driver Modules LDM-32, LDM-E32, and LDM-R32;

remote custom driver modules. See DN-0551.

SCS: Smoke control stations SCS-8, SCE-8, with lamp drivers SCS-8L, SCE-8L; eight (expandable to 16) circuits. See DN- 4818.

TM-4: Transmitter Module. Includes three reverse-polarity cir-cuits and one municipal box circuit; mount on NFS-320 chassis or remotely. See DN-6860.

UDACT: Universal Digital Alarm Communicator Transmitter, 636 channel. See DN-4867.

UDACT-2: Universal Digital Alarm Communicator Transmitter, 636 channel. See DN-60686.

UZC-256: Programmable Universal Zone Coder provides posi-tive non-interfering successive zone coding. Microprocessor-controlled, field-programmable from IBM®-compatible PCs (requires optional programming kit). Mounts in BB-UZC. See

DN-3404.

COMPATIBLE INTELLIGENT DEVICES

BEAMHK: Heating kit for transmitter/receiver unit of FSB-200(S) below. See DN-6985.

BEAMHRK: Heating kit for use with the reflector of FSB-200(S) below. See DN-6985.

BEAMLRK: Long-range accessory kit, FSB-200(S) below. See

DN-6985.

BEAMMRK: Multi-mount kit, FSB-200(S) below. See DN-6985.

BEAMSMK: Surface-mount kit, FSB-200(S) below. See DN- 6985.

FSB-200: Intelligent beam smoke detector. See DN-6985.

FSB-200S: Intelligent beam smoke detector with integral sensi-tivity test. See DN-6985

FSC-851: FlashScan IntelliQuad Advanced Multi-Criteria Detec-tor. See DN-60412.

FCO-851: FlashScan IntelliQuad PLUS Advanced Multi-Criteria Fire/CO Detector. See DN-60689 .

FSI-851: Low-profile FlashScan ionization detector. See DN- 6934.

DN-7112:G • 12/19/2011 — Page 5 of 6

FSP-851: Low-profile FlashScan photoelectric detector. See

DN-6935.

FSP-851T: Low-profile FlashScan photoelectric detector with 135°F (57°C) thermal. See DN-6935.

FSP-851R: Remote-test capable photoelectric detector for use with DNR(W) duct detector housings. See DN-6935.

FST-851: FlashScan thermal detector 135°F (57°C). See

DN-6936.

FST-851R: FlashScan thermal detector 135°F (57°C) with rate-of-rise. See DN-6936.

FST-851H: FlashScan 190°F (88°C) high-temperature thermal detector. See DN-6936.

FAPT-851: FlashScan Acclimate Plus low-profile multi-sensor detector. See DN-6937.

FSL-751: FlashScan VIEW laser photo detector. See DN-6886.

DNR: InnovairFlex low-flow non-relay duct-detector housing (order FSP-851R separately). Replaces FSD-751PL/FSD- 751RPL. See DN-60429.

DNRW: Same as above with NEMA-4 rating, watertight. See

DN-60429.

B224RB: Low-profile relay base. See DN-60054.

B224BI: Isolator base for low-profile detectors. See DN-60054.

B210LP: Low-profile base. Standard U.S. style. Replaces B710LP. See DN-60054.

B501: European-style, 4" (10.16 cm) base. See DN-60054.

B200S: Intelligent programmable sounder base, capable of pro-ducing a variety of tone patterns including ANSI Temporal 3.

Compatible with sychronization protocol. See DN-60054.

B200SR: Sounder base, Temporal 3 or Continuous tone. See

DN-60054.

FMM-1: FlashScan monitor module. See DN-6720.

FDM-1: FlashScan dual monitor module. See DN-6720.

FZM-1: FlashScan two-wire detector monitor module. See DN- 6720.

FMM-101: FlashScan miniature monitor module. See DN-6720.

FCM-1: FlashScan NAC control module. See DN-6724.

FCM-1-REL: FlashScan releasing control module. See DN- 60390.

FRM-1: FlashScan relay module. See DN-6724.

FDRM-1: FlashScan dual monitor/dual relay module. See DN- 60709.

NBG-12LX: Manual pull station, addressable. See DN-6726.

ISO-X: Isolator module. See DN-2243.

XP6-C: FlashScan six-circuit supervised control module. See

DN-6924.

XP6-MA: FlashScan six-zone interface module; connects intelli-gent alarm system to two-wire conventional detection zone. See

DN-6925.

XP6-R: FlashScan six-relay (Form-C) control module. See DN- 6926.

XP10-M: FlashScan ten-input monitor module. See DN-6923.

ENCLOSURES, CHASSIS, AND DRESS PLATES

MARINE-EQ System: Protects equipment in shipboard and waterfront applications. For a full list of required and optional equipment, see DN-60688.

BB-UZC: Backbox for housing the UZC-256. Required for NFS- 320 applications. Black. For red, order BB-UZC-R.

NFS-LBB: Battery Box (required for batteries larger than 26

AH).

NFS-LBBR: Same as above, but red.

SEISKIT-320/B26: Seismic mounting kit. Required for seismic-certified applications with NFS-320 and BB-26. Includes battery bracket for two 26 AH batteries.

SEISKIT-BB25: Seismic mounting kit for the BB-25. Includes battery bracket for two 26 AH batteries.

SEISKIT-LBB: Seismic kit for the NFS-LBB. Includes battery bracket for two 55 AH batteries.

SEISKIT-PS/2/4: Seismic mounting kit for the FCPS-24S6/S8 and CAB-PS1. Includes battery bracket for two 7 AH or 12 AH batteries.

OTHER OPTIONS

411: Slave Digital Alarm Communicator. See DN-6619.

411UDAC: Digital Alarm Communicator. See DN-6746.

IPDACT-2/2UD, IPDACT Internet Monitoring Module: Con-nects to primary and secondary DACT telephone output ports for internet communications over customer-provided ethernet connection. Requires compatible Teldat VisorALARM Central Station Receiver. Can use DHCP or static IP. See DN-60408.

IPSPLT: Y-adaptor option allow connection of both panel dialer outputs to one IPDACT-2/2UD cable input.

IPENC: External enclosure for IPDACT, includes IPBRKT mounting bracket; Red. For Black order IPENC-B.

IPGSM-DP: Internet and Digital Cellular Fire Alarm Communi-cator. Provides selectable configurable paths: cellular only, IP only, or IP primary with cellular backup. Connects to the primary and secondary ports of a DACT. Replaces IPGSM-COM. See

DH-60695.

VeriFire-TCD: VeriFire Tools CD-ROM. Contains programming software for the ONYX Series. Includes local panel connection cable. See DN-6871.

VeriFireUG-TCD: VeriFire Tools upgrade software.

NFS-320-RB: Replacement CPU. NOTE: Keypad must be removed before shipping old unit out for repair.

• NFS-320-RBE: Replacement CPU, Export.

• NFS-320-RBC-FR: Replacement CPU, Canadian French.

• NFS-320-RB-PO: Replacement CPU, Portuguese.

• NFS-320-RB-POE: Replacement CPU, Export, Portu-guese.

• NFS-320-RB-SP: Replacement CPU, Spanish.

• NFS-320-RB-SPE: Replacement CPU, Export, Spanish.

NOTE: For other options including compatibility with retrofit equip-ment, refer to the panel's installation manual, the SLC manual, and the Device Compatibility Document.

Page 6 of 6 — DN-7112:G • 12/19/2011

System Capacity

• Intelligent Signaling Line Circuits

• Intelligent detectors

• Addressable monitor/control modules

• Programmable internal hardware and output circuits

• Programmable software zones

• Special programming zones

• LCD annunciators per NFS-320/-320E

• ACS annunciators per NFS-320/-320E ....................... 32 addresses x 64 points

Specifications

• Primary input power

– NFS-320: 120 VAC, 50/60 Hz, 5.0 A.

– NFS-320E: 220/240 VAC, 50/60 Hz, 2.5 A.

• Total output 24 V power: 6.0 A in alarm.

NOTE: The power supply has a total of 6.0 A of available power.

This is shared by all internal circuits.

• Standard notification circuits (4): 1.5 A each.

• Resettable regulated 24V power: 1.25 A.

• Two non-resettable regulated 24V power outputs:

– 1.25 A.

– 0.50 A.

• Non-resettable 5V power: 0.15 A.

• Battery charger range: 18 AH – 200 AH. Use separate cabi-net for batteries over 26 AH.

• Float rate: 27.6 V.

Cabinet Specifications NFS-320 cabinet dimensions:

• Backbox: 18.12 in. (46.025 cm) width; 18.12 in. (46.025 cm) height; 5.81 in. (14.76 cm) depth.

• Door: 18.187 in. (46.195 cm) width; 18.40 in. (46.736 cm) height; 0.75 in. (1.905 cm) depth.

• Trim ring: Molding width is 0.905 in. (2.299 cm).

• Shipping weight (without batteries): 36.15 lb. (16.4 kg).

Temperature and Humidity Ranges This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic compo-nents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F.

Agency Listings and Approvals The listings and approvals below apply to the basic NFS-320 control panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Con-sult factory for latest listing status.

• UL Listed: S635.

• ULC Listed: S635 (NFS-320C only, excludes IPDACT).

• FM Approved.

• CSFM: 7165-0028:0243.

• MEA: 128-07-E.

• FDNY: COA#6085.

• City of Chicago.

NOTE: For additional information on UL- and ULC-listed model NFS-320C, see DN-60085. For information on NFS-320SYS, see

DN-60637.

When used with the MARINE-EQ, appropriate seismic bracket, and marine approved devices, these ONYX fire alarm control panels are approved by the following agencies:

• US Coast Guard: 161.002/50/0 (Standard 46 CFR).

• Lloyd's Register: 11/600013 (ENV 3 category).

Standards The NFS-320 complies with the following UL Standards and NFPA 72, IBC, and CBC Fire Alarm Systems requirements:

• UL 864 (Fire).

• UL 1076 (Burglary).

• LOCAL (Automatic, Manual, Waterflow and Sprinkler Super-visory).

• AUXILIARY (Automatic, Manual and Waterflow) (requires

TM-4).

• REMOTE STATION (Automatic, Manual, Waterflow and

Sprinkler Supervisory) (requires TM-4).

• PROPRIETARY (Automatic, Manual, Waterflow and Sprinkler

Supervisory). Not applicable for FM.

• CENTRAL STATION (Automatic, Manual, Waterflow and

Sprinkler Supervisory) (requires UDACT).

• EMERGENCY VOICE/ALARM.

• OT, PSDN (Other Technologies, Packet-switched Data Net-work).

• IBC 2000, IBC 2003, IBC 2006, IBC2009 (Seismic).

• CBC 2007 (Seismic).

NOTI•FIRE•NET™, IntelliQuad™, and ONYXWorks™ are trademarks; and Acclimate® Plus™, FlashScan®, NOTIFIER®, ONYX®, VeriFire®, and VIEW® are registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of Microsoft Corporation. IBM® is a registered trademark of IBM Corporation.

©2011 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

This document is not intended to be used for installation purposes.

We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements.

All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.

www.notifier.com

Made in the U.S. A.

SYSTEM SPECIFICATIONS

DN-60454:B • 10/07/2010 — Page 1 of 2

HS-NCM-W, HS-NCM-MF,

HS-NCM-SF, HS-NCM-WMF,

HS-NCM-WSF, HS-NCM-MFSF

High-Speed Network Communications Modules

Network Systems

DN-60454:B

General The High-Speed Network Communications Module (HS- NCM) provides NOTIFIER’s NFS-320, NFS-640, NFS2-640, NFS-3030, and NFS2-3030 Fire Alarm Control Panels, NCA and NCA-2 Network Control Annunciators, and DVC Digital Voice Command with a means to connect to High-Speed NOTI•FIRE•NET™. Six types of HS-NCM are available: HS- NCM-W for connecting nodes with twisted-pair wire, HS- NCM-MF for connecting nodes with multi-mode fiber-optic cable, HS-NCM-SF for connecting nodes with single-mode fiber-optic cable, HS-NCM-WMF for connecting wire and multi-mode fiber-optic medium on the same network, HS-NCM-WSF for connecting wire and single-mode fiber-optic mediums on the same network and HS-NCM-MFSF for connecting multi-mode and single-mode fiber optic mediums on the same net-work.

Each HS-NCM can accommodate up to two node addresses.

For example, one HS-NCM can provide network communica-tion for both an NFS2-640 and an NCA-2.

When not connected to a fire alarm panel, the HS-NCM defaults to repeater mode and can be used to boost signal dis-tances or to pass data transmissions between two differently configured network segments when wire and fiber co-exist on a network.

HS-NCM-W Features

• Supports twisted-pair wire medium.

• NFPA Style 4 (Class B) operation or NFPA Style 7 (Class A) operation.

• Transformer coupling provides electrical isolation between nodes.

• Pluggable terminal wiring with strain relief.

• Pluggable service connector (feeds signal directly through) in the event that power must be removed from a node.

• 12 Mb transmission rate.

• Data is regenerated at each node.

• Two network ports to allow simultaneous connection to fire alarm control panel and to programming computer.

• Enables software and database upload/download over

High-Speed NOTI•FIRE•NET™.

• Up to 3,000 feet (914.4 m) between nodes in a point-to-point fashion (actual distance varies with wire quality).

HS-NCM-W Interconnections: When wiring consecutive HS- NCM-W boards, wiring may enter or exit at Port A or Port B.

HS-NCM-W port-to-port wiring is polarity sensitive; use of Port A or Port B is not arbitrary. An HS-NCM-W may be connected to any of the following devices: HS-NCM-W (in another panel), HS-NCM-WMF, HS-NCM-WSF.

HS-NCM-W Switch Functions: The HS-NCM-W provides one set of switches to simplify network setup. Enable ground fault detection by setting “ON” switch SW4-1 (Channel A);

switch SW4-2 (Channel B). NOTE: Correct configuration is dependent on network design; refer to the High-Speed NOTI•FIRE•NET™ manual, PN 54013).

For further information and diagrams, refer to the HS-NCM Installation Document, 54014.

HS-NCM-MF and HS-NCM-SF Features

• Supports fiber-optic medium.

• NFPA Style 4 (Class B) or Style 7 (Class A) operation.

• Data is immune to all environmental noise.

• Optical isolation prevents ground loops.

• High-Speed NOTI•FIRE•NET™ fiber-optic medium.

• Fiber type: 62.5/125 micrometers (multi-mode); 50/125 micrometers (multimode), or 9/125 micrometers (single-mode).

• Maximum attenuation is 10 dB with 62.5/125 �m cable, and

6.5 dB with 50/125 �m cable, and 30 dB with 9/125 �m cable.

• Wavelength (1): 1310 nanometers.

• Connectors: LC style.

• 100 Mb baud transmission rate.

• Data is regenerated at each node.

• Two network ports to allow simultaneous connection to fire alarm control panel and to programming computer.

• Enables software and database upload/download over High-Speed NOTI•FIRE•NET™.

HS-NCM-MF/SF Interconnections: When wiring consecutive nodes/repeaters, fiber cable must exit one board on Transmit (TX) and enter the next node/repeater on Receive (RX). The fiber-optic pair (RX, TX) from Port A of one node/repeater con-nects to Port B of another node/repeater. A HS-NCM-MF/SF may be connected to any of the following devices: HS- NCM-MF/SF (respectively) on another panel, HS-NCM-WMF, HS-NCM-WSF, HS-NCM-MFSF.

HS-NCM-sm.JPG

HS-NCM

Page 2 of 2 — DN-60454:B • 10/07/2010

NOTI•FIRE•NET™ is a trademark; and NOTIFIER® are registered trademarks of Honeywell International Inc.

©2010 by Honeywell International Inc. All rights reserved.

Unauthorized use of this document is strictly prohibited.

This document is not intended to be used for installation purposes.

We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements.

All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.

www.notifier.com

Made in the U.S. A.

HS-NCM-WMF, HS-NCM-WSF, and HS- NCM-MFSF Features

• Supports twisted-pair wire and fiber-optic medium.

• NFPA Style 4 (Class B) operation or NFPA Style 7 (Class A) operation.

• Allows wire and fiber optic nodes to communicate as one network.

• Fiber type: 62.5/125 micrometers (multi-mode); 50/125 micrometers (multimode), or 9/125 micrometers (single-mode).

• Maximum attenuation is 10 dB with 62.5/125 �m cable, and

6.5 dB with 50/125 �m cable, and 30 dB with 9/125 �m cable.

• Wavelength (1): 1310 nanometers.

• Pluggable service connector (feeds signal directly through) in the event that power must be removed from a node.

• Data is regenerated at each node.

• Two network ports to allow simultaneous connection to fire alarm control panel and to programming computer.

• Enables software and database upload/download over

High-Speed NOTI•FIRE•NET™.

• Up to 3,000 feet (914.4 m) between nodes in a point-to-point fashion (actual distance varies with wire quality).

HS-NCM-WMF/WSF/MFSF Interconnections: When wiring consecutive nodes/repeaters, fiber cable must exit one board on Transmit (TX) and enter the next node/repeater on Receive (RX). The fiber-optic pair (RX, TX) from Port A of one node/ repeater connects to Port B of another node/repeater. An HS- NCM-WMF/WSF/MFSF may be connected to any of the fol-lowing devices: HS-NCM-WMF, HS-NCM-WSF or HS-NCM- MFSF on another panel, HS-NCM-MF, HS-NCM-SF.

Common Specifications Temperature and humidity ranges: This system meets NFPA requirements for operation at 0°C to 49°C (32°F to 120°F); and at a relative humidity (noncondensing) of 85% at 30°C (86°F) per NFPA, and 93% ± 2% at 32°C ± 2°C (89.6°F ± 1.1°F) per ULC. However, the useful life of the system’s standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humid-ity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15°C to 27°C (60°F to 80°F).

Weight: 5.2 ounces (147.4 grams)

Power supply: 24 VDC @ 400 mA

Mounting All models of the HS-NCM can be installed in any standard chassis such as the CHS-4L, CHS-M2, CHS-M3, CHS-4N or CPU2-640 chassis (see panel sheets). Additionally, the HS- NCM-W can be door-mounted on the ADP-4B dress panel on a single-space blank plate (BMP-1) for mounting in an CAB-4 Series cabinet.

Agency Listings and Approvals The following listings and approvals apply to the HS-NCM. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process.

Consult factory for latest listing status.

• UL Listed: S635

• ULC Listed: S635

• CSFM: 7300-0028:0257, 7165-0028:0224

• FM Approved

• FDNY: COA#6022

Product Line Information HS-NCM-W: High-Speed Network Communications Module, twisted-pair wire interface.

HS-NCM-MF: High-Speed Network Communications Module, fiber-optic cable interface (multi-mode).

HS-NCM-SF: High-Speed Network Communications Module, fiber-optic cable interface (single-mode)

HS-NCM-WMF: High-Speed Network Communications Mod-ule, wire and fiber-optic cable interface (wire/multi-mode).

HS-NCM-WSF: High-Speed Network Communications Mod-ule, wire and fiber-optic cable interface (wire/single-mode).

HS-NCM-MFSF: High-Speed Network Communications Mod-ule, fiber-optic cable interface (multi-mode/single-mode).

DN-60686:A1 • 4/2/12 — Page 1 of 2

UDACT-2

Universal Digital Alarm Communicator Transmitter

Annunciator Control System

DN-60686:A1

General The Universal Digital Alarm Communicator Transmitter (UDACT-

2) is designed for use on Notifier Fire Alarm Control Panels and on the NCA-2 Network Control Annunciator. When used in con-junction with the NCA-2 network control annunciator, the UDACT-2 can report the status of all control panels on NOTI•FIRE•NET™. The UDACT-2 transmits system status to UL listed Central Station Receivers via the public switched tele-phone network. The UDACT-2 can be installed in the panel cab-inet or remotely in a separate enclosure.

NOTE: The UDACT-2 can also be used with legacy panels.

Please refer to the UDACT-2 manual for more information.

The UDACT-2 upload/download programming and firmware updates are accomplished with VeriFire Tools. Refer to the Pro-gramming Section for further details.

The UDACT-2 is capable of transmitting the status of software zones (Alarm and Trouble), System Trouble, Panel Off-Normal, Supervisory, Bell Trouble, Low Battery, and AC Fail. The UDACT-2 is capable of transmitting all of the zone and point sta-tus associated with each panel.

When the UDACT-2 is used with the NFS-3030, NFS2-3030, and NCA-2 it is capable of reporting up to 2,040 points. Report-ing may be in the form of points or zones (refer to the UDACT-2 manual for specific reporting parameters). Points transmitted may be programmed for a variety of types, including fire, water-flow, supervisory, etc.

NOTE: Descriptions regarding point capacity, listed above, are for receivers which receive in Ademco Contact ID format. See chart on page 2 for compatible receivers.

Features

• Programmable with VeriFire Tools version 6.60 or higher, allowing the UDACT-2 programming to be uploaded/down-loaded and saved.

• Maximum of 14 point trouble messages transmitted per hour.

• Dual phone lines with line voltage detect.

• Compact in size: 6.75" x 4.25" (17.145 x 10.795 cm).

• USB port for upload/download programming.

• Manual Test Report function.

• Manual Transmission Clear function.

• Mounts in a separate enclosure (ABS-8RB or UBS-1B/R).

• Communicates vital system status including:

– Independent zone fire alarm.

– Independent zone non-fire alarm.

– Independent zone trouble.

– Independent zone supervisory.

– AC (mains) Power Loss (programmable).

– Low Battery and Earth Fault.

– System Off-Normal.

– 12 or 24 hour test signal.

– Abnormal Test Signal per new UL requirements.

– EIA-485 Communication Bus Failure.

• Annunciation of UDACT-2 Troubles including: loss of phone lines, communication failure with either Central Station, total communications failure.

• Individual LEDs for: Power, EIA-485 Loss, Manual Test, Kis-soff, Comm Fail, Primary Line Seize, Secondary Line Seize and Modem Communications.

• Open Collector relay driver for Total Communications Failure or UDACT-2 trouble.

• Real-time clock.

• Extensive transient protection.

• EIA-485 interface to host panel.

Programming The UDACT-2 programming is created and downloaded using VeriFire Tools. This enables the unit to be programmed prior to installation, be easily modified, and saved either online or offline. A printed report with point or zone information can be generated from VeriFire Tools for an ONYX Series panel or net-work annunciator. The point report consists of the central station point address, ACS point, ACS point function, panel label, panel point, type code, custom and extended label, alarm verification, walktest participation, presignal, and PAS information. The zone report consists of a grid with the central station point address, ACS point address, source, ACS point function, custom label and panel label. This report may be sent to the Central Station for their records. VeriFire Tools also supports upgrading the UDACT-2 operating firmware.

UDACT-2

Page 2 of 2 — DN-60686:A1 • 4/2/12

NOTI•FIRE•NET™ is a trademark and Notifier® is a registered trademark of Honeywell International Inc.

©2012 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

This document is not intended to be used for installation purposes.

We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements.

All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.

www.notifier.com

Made in the U.S. A.

Communication Formats

• Ademco Contact ID

• 4+2 Standard

• SIA

NOTE: Ademco Contact ID must be used for independent zone reporting.

Type Mode Feature Ademco Contact ID format - only Use Type Mode to identify reports to Central Station as:

• Fire Alarm • Burglary

• Supervisory • 24 hour Non-Burglary

• Pull Station • High Temperature

• Heat Detector • Low Temperature

• Waterflow • Low Water Pressure

• Duct Detector • Low Water Level

• Flame Sensor • Pump Failure

• Smoke Zone

Electrical Specifications Standby current: 40 mA.

Current while communicating: 75 mA.

Maximum current while communicating and with open collector output activated: 100 mA.

Voltage: Regulated 24 volts. Range: 21.2 to 28.2 volts.

Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.

• UL/ULC Listed: S635

• FM Approved

• CSFM: 7165-0028:0243 (NFS2-640/320), 7165-0028:0224

(NFS2-3030)

• FDNY: COA#6085, COA#6098

Ordering Information UDACT-2: Universal Digital Alarm Communicator Transmitter.

Includes operating and programming instructions, and mounting hardware.

MCBL-7: DACT phone cord, 7 ft (2.13 m) long (two required).

ABS-8RB: Metal enclosure for externally mounting UDACT-2 up to 6,000 ft./1828.8 m from host FACP. 9.94" H x 4.63" W x 2.50" D (cm: 25.248 H x 11.760 W x 6.350 D).

UBS-1B: Metal enclosure with solid door, Black.

UBS-1BR: Metal enclosure with solid door, Red.

R-10E: SPDT Form-C relay. Contacts rated for 10 A @ 115 VAC.

Connects to open collector relay driver.

R-20E: DPDT Two Form-C relays. Contacts rated for 10A @ 115 VAC. Connects to open collector relay driver.

FBD-1: Ferrite bead kit. Use for remote mounting only.

UL Listed Receivers The chart below shows UL listed receivers compatible with the UDACT-2. A check in the protocol column indicates the receiver supports that protocol.

(1) With 685-8 Line Card with Rev 4.4d software

(2) With 124060V206B and 124063 Line Card Rev B

(3) With version V2.4 Receiver & 126047 Line Card Rev G

(4) With 124077V2.00 Receiver &126047 Line Card Rev M

(5) With software V3.9

(6) With V.7301 Receiver S/W

(7) With 01.01.03 Receiver S/W & Line Card 01.01.03

(8) With software V1.86

(9) With sotware V1.72

(10) With DSP4016 and V1.6 Line Card

Receiver

4+2 Standard 1800/2300

Ademco Contact

ID SIA

Ademco 685 (1) � �

Ademco MX8000 (2) � � �

Silent Knight 9500 (3) � � �

Silent Knight 9800 (4) � � �

FBI CP220FB (5) � � �

Osborne Hoffman 2000E (6) � �

Radionics 6600 (7) � �

SurGard MLR2 (8) � �

SurGard System III (9) � �

SurGard MLR-2000 (10) �

DN-6933:D • 02/28/2013 — Page 1 of 2

BAT Series Batteries Sealed Lead-Acid

Power Supplies

DN-6933:D • E-205

General BAT Series Batteries are Power-Sonic brand batteries. BAT Series (or Power-Sonic brand) batteries are recommended for secondary power or backup power for all NOTIFIER fire alarm control equipment.

Features

• Provide secondary power for control panels.

• Sealed and maintenance-free.

• Overcharge protected.

• Easy handling with leak-proof construction.

• Ruggedly constructed, high-impact case (ABS).

• Long service life.

• Compact design.

Agency Listings and Approvals The listings and approvals below apply to BAT Series Batter-ies. In some cases, certain modules may not be listed by cer-tain approval agencies, or listing may be in process. Consult factory for latest listing status.

• UL Recognized Components: MH20845 (Power-Sonic).

Ordering Information BAT-1250-BP: 10-unit bulk pack of BAT-1250 (12 V 5 AH).

BAT-1270-BP: 5-unit bulk pack of BAT-1270 (12 V 7 AH).

BAT-12120-BP: 4-unit bulk pack of BAT-12120 (12V 12 AH).

BAT-12180-BP: 2-unit bulk pack of BAT-12180 (12 V 18 AH).

BAT-12260-BP: 2-unit bulk pack of BAT-12260 (12 V 26 AH).

BAT-12550: single battery (12 V 55 AH).

BAT-121000: single battery (12 V 100 AH).

Part Number Reference & Specifications

6933cov.jpg

Part Number

Power- Sonic Part

Number

Battery Description DIMENSIONS

Nominal Voltage V

Nominal Capacity @ 20 hr.

rate A.H.

Width Depth Height Height over terminal Weight

in. mm in. mm in. mm in. mm lb. kg.

BAT-1250 PS-1250 12 5 sealed 3.54 90 2.76 70 3.98 101 4.21 107 3.50 1.59 BAT-1270 PS-1270 12 7 sealed 5.95 151 2.56 65 3.7 94 3.86 98 4.8 2.18

BAT-12120 PS-12120 12 12 sealed 5.95 151 3.86 98 3.7 94 3.94 100 7.92 3.59 BAT-12180 PS-12180 12 18 sealed 7.13 181 3.00 76 6.59 167 6.59 167 12.6 5.72 BAT-12260 PS-12260 12 26 sealed 6.5 167 6.97 177 4.92 125 4.92 125 17 7.71 BAT-12550 PS-12550 12 55 sealed 9.04 230 5.45 138 8.15 207 8.98 228 36 16.33

BAT-121000 PS-121000 12 100 sealed 12 305 6.6 168 8.15 207 8.98 228 68 30.84

Page 2 of 2 — DN-6933:D • 02/28/2013

NOTIFIER® is a registered trademark of Honeywell International Inc.

Batteries display trademarks of the manufacturer.

©2013 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

This document is not intended to be used for installation purposes.

We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements.

All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.

www.notifier.com oita R yticapa

C

Temperature (°C)

Discharge Time egatloV lani mreT

Discharge Characteristic Curves at 20°C (68°F) Effect of Temperature on Capacity gr f1

.a i gr f2

.a i gr f3

.a i

PS-121000 Shelf-Life and Storage a C p ca iyt ete R nt noi ta R oi

Standing Period (Months)

0 2 4 6 8 10 12 14 16 18 20

40oC (104oF)

30oC (86oF)

20oC (68oF)

5oC (41oF)

Charging is not necessary unless 100% of capacity is required.

Charging before use is necessary to help recover full capacity.

Charge may fail to restore full capacity. Do not let batteries reach this state.

13.0

12.0

11.0

10.0

9.0

8.0

14.0 lani mreT

)V( egatloV

Ambient Temperature 20oC (68oF)

1.2 2.4 6 12 24 36 48 1 2 4 6 8 10 20 4 0

Discharge Time

Final Voltage mi n h

5.010 gr f4

.a i

PS-121000 Discharge Characteristics

DN-6935:D • 12/08/2011 — Page 1 of 2

FSP-851(A) Series Intelligent Plug-In Photoelectric� Smoke Detectors with FlashScan®

Intelligent/Addressable Devices

DN-6935:D • H-202

General Notifier FSP-851(A) Series intelligent plug-in smoke detectors with integral communication provide features that surpass con-ventional detectors. Detector sensitivity can be programmed in the control panel software. Sensitivity is continuously monitored and reported to the panel. Point ID capability allows each detec-tor’s address to be set with rotary, decimal address switches, providing exact detector location for selective maintenance when chamber contamination reaches an unacceptable level.

The FSP-851(A) photoelectric detector’s unique optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources. Dual electronic thermistors add 135°F (57°C) fixed-temperature thermal sensing on the FSP- 851T(A). The FSP-851R(A) is a remote test capable detector for use with DNR(A)/DNRW duct detector housings. FSP-851(A) series detectors are compatible with Notifier Onyx and CLIP series Fire Alarm Control Panels (FACPs).

FlashScan® (U.S. Patent 5,539,389) is a communication proto-col developed by Notifier that greatly increases the speed of communication between analog intelligent devices. Intelligent devices communicate in a grouped fashion. If one of the devices in the group has new information, the panel’s CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of earlier designs.

Features

• Sleek, low-profile design.

• Addressable-analog communication.

• Stable communication technique with noise immunity.

• Low standby current.

• Two-wire SLC connection.

• Compatible with FlashScan® and CLIP protocol systems.

• Rotary, decimal addressing (1-99 on CLIP systems, 1-159 on

FlashScan systems).

• Optional remote, single-gang LED accessory.

• Dual LED design provides 360° viewing angle.

• Visible bi-color LEDs blink green every time the detector is addressed, and illuminate steady red on alarm (FlashScan systems only).

• Remote test feature from the panel.

• Walk test with address display (an address on 121 will blink the detector LED: 12-[pause]-1(FlashScan systems only).

• Built-in functional test switch activated by external magnet.

• Built-in…