Replace Underground Water Storage Tanks - 667-22-118 - Drawings.pdf

PDF 5 MB Posted

Attached to
C1AA--667-22-1-513-0003 - Project 667-22-118 Above ground potable water storage tank system (VA-22-00005162)
Solicitation number
36C25622R0034
Issued by

About this file

This solicitation package seeks proposals for architectural and engineering services for the replacement of underground water storage tanks at the Overton Brooks VA Medical Center in Shreveport, Louisiana. Firms must have an office located within 500 miles of the medical center to be considered. The project involves designing an above-ground potable water storage tank system with at least two proposed siting options, including new water treatment, softening, and monitoring systems housed in a climate-controlled building. The tank system must sustain 10 days of domestic water consumption and be serviceable without disrupting supply. Existing below-grade tanks will solely support fire suppression. Proposals are due by 3:00 PM Central time on February 14, 2022. The contract will be a negotiated firm-fixed price contract awarded to a service-disabled veteran-owned small business. The period of performance is 180 days from notice to proceed.

View the file

Other files

File Type Posted
Questions for the VA 01-31-22.docx DOCX document
36C25622R0034_1.docx DOCX document
36C25622R0034.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Replacement of Underground

Utilities Proj 1984

VHASHRMoralJ Typewritten Text Drawings are provided as a reference. Contractor to verify all existing conditions.

Relocate Water Main and Fire Main – YR 2020 vhashrlanhaa Line vhashrlanhaa Line vhashrlanhaa Line vhashrlanhaa Line vhashrlanhaa Line vhashrlanhaa Line vhashrlanhaa Line vhashrlanhaa Line vhashrlanhaa Line vhashrlanhaa Line vhashrlanhaa Line vhashrlanhaa Text Box Existing 6" Water Main to be abandoned vhashrlanhaa Line vhashrlanhaa Text Box 3" water line to (BP) Boiler Plant vhashrlanhaa Line vhashrlanhaa Text Box New Location 6" Water Main vhashrlanhaa Line vhashrlanhaa Text Box 6" Water Main Break vhashrlanhaa Text Box 3" Water line BP break vhashrlanhaa Line vhashrlanhaa Line vhashrlanhaa Text Box Existing 6" Water Main to be abandoned vhashrlanhaa Line vhashrlanhaa Text Box New Water Main Connection vhashrlanhaa Line vhashrlanhaa Text Box Underground water tanks vhashrlanhaa Polygonal Line vhashrlanhaa Polygonal Line vhashrlanhaa Polygonal Line vhashrlanhaa Text Box Abandon Portion of 6" Fire Main between new connections vhashrlanhaa Line vhashrlanhaa Oval vhashrlanhaa Oval vhashrlanhaa Text Box New Fire Main vhashrlanhaa Line vhashrlanhaa Oval vhashrlanhaa Oval

Site Utility Map – YR 2018

Underground Storage Tanks Procedures

Schematic – YR 2020

EAST

TANK

WEST

TANK

WATER IN

#7

DRAIN VALVE

#8

DRAIN VALVE

#1

FILL VALVE

EAST TANK SUPPLY

#2

FILL VALVE

WEST TANK SUPPLY

#3

ISOLATION VALVE

#4

ISOLATION VALVE

#5

BYPASS VALVE

#6

BYPASS VALVE

BACKFLOW PREVENTER

WEST LINE TO

FIRE PUMP

EAST LINE TO

DOMESTIC WATER

ISOLATION VALVE

EAST LINE TO

DOMESTIC WATER

WEST LINE TO

FIRE PUMPCRAWL SPACE

#9

#10

#12#11 #9

WEST

FP

CLOSED

DOMESTIC

OPEN

#10

EAST

DOMESTIC

OPEN

FP

CLOSED

#12

WEST

FP

OPEN

DOMESTIC

CLOSED

#11

EAST

DOMESTIC

CLOSED

FP

OPEN

44' 44'

ELEVATION VIEW A

12" - 16,452 GAL

27" - 37,017 GAL

42" - 57,582 GAL

57" - 78,147 GAL

72" - 98,712 GAL

87" - 119,277 GAL

102" - 139,842 GAL

117" - 160,407 GALHIGH LEVEL ALARM

NORMAL WATER LEVEL

LOW LEVEL ALARM

BOTTOM OF TANK

TOP OF TANK

ELEVATION VIEW A

HIGH LEVEL ALARM

NORMAL WATER LEVEL

LOW LEVEL ALARM

BOTTOM OF TANK

TOP OF TANK

"DO NOT OPERATE THESE VALVES UNLESS APPROVED BY CHIEF OF ENGINEERING"

DRAIN

VIEW A VIEW A

12" - 16,452 GAL

27" - 37,017 GAL

42" - 57,582 GAL

57" - 78,147 GAL

72" - 98,712 GAL

87" - 119,277 GAL

102" - 139,842 GAL

117" - 160,407 GAL

Underground Water Tank SOP

WATER TANKS

VALVE OPERATION

EAST TANK Valve positions - Hospital Domestic Water

1. Close #7 Drain Valve

2. Open #3 Isolation Valve

3. Close #5 Bypass Valve

4. Open #1 Fill Valve

WEST TANK Valve positions – Fire Pump

1. Close #8 Drain Valve

2. Open #4 Isolation Valve

3. Close #6 Bypass Valve

4. Open #2 Fill Valve

PROCEDURES FOR TANK CLEANING & EMERGENCIES

EAST TANK Valve positions – Simultaneously feeding Hospital Domestic Water AND Fire Pump

1. Close #7 Drain Valve

2. Open #3 Isolation Valve

3. Open #5 Bypass Valve

4. Open #6 Bypass Valve

5. Close #4 Isolation Valve

6. Open #1 Fill Valve

7. Close #2 Fill Valve

WEST TANK Valve positions – Simultaneously feeding Hospital Domestic Water AND Fire Pump

1. Close #8 Drain Valve

2. Open #4 Isolation Valve

3. Open #6 Bypass Valve

4. Open #5 Bypass Valve

5. Close #3 Isolation Valve

6. Open #2 Fill Valve

7. Close #1 Fill Valve

Underground Water Storage Reservoir

Plans & Details

71-06-U1r – YR 1947

Utilities Plot Plan 71-01-U1 –

YR 1947

VHASHRCopelJ Highlight

Replacement of Underground Utilities Proj 1984.1
Replacement of Underground Utilities Proj 1984
Relocate Water Main and Fire Main - 2020.1
Relocate Water Main and Fire Main - 2020
Site Utility Map - 2018.1
Site Utility Map - 2018
Underground Storage Tanks Procedures Schematic - 2020.1
Underground Storage Tanks Procedures Schematic - 2020
Sheets and Views
Layout Only
Underground Water Tank SOP.1
Underground Water Tank SOP
Underground Water Storage Reservoir Plans & Details 71-06-U1r - 1947.1
Underground Water Storage Reservoir Plans & Details 71-06-U1r - 1947
Utilities Plot Plan 71-01-U1 - 1947.1
Utilities Plot Plan 71-01-U1 - 1947