This solicitation is for a medical gas expansion project at the Gulf Coast Veterans Health Care System in Biloxi, Mississippi. The project involves expanding medical gas services to additional wings of Building 15 and requires the contractor to provide all labor, materials, tools and equipment for installing new medical air and vacuum systems, oxygen piping and related components. The procurement is set aside exclusively for service-disabled veteran-owned small businesses. The request for proposals will be issued on January 26, 2021 with proposals due around February 26, 2021 and contract award anticipated within 30 days thereafter. The performance period is 150 calendar days from notice to proceed. The estimated value is between $500,000 to $1,000,000. Interested vendors must read the full solicitation and attend the scheduled site visit. The prime contractor must perform a minimum of 15% of the work with its own employees.
View the file
Other files
Show 40 more
Latest 50 of 69 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation No. 36C25621R0054 Project 520-22-162 Medical Gas Expansion, Building 15, Biloxi
Register of all RFI Proposal Inquiries & Responses:
First set of Proposal Inquiries dated 3/12/21:
Proposal RFI #1 – There are conflicting site visit dates for the project. On page 1 of solicitation in paragraph three, it states that the dates are Monday 3/29 and Tuesday 3/30. On page 30 of solicitation (2.8), it then states that the dates are Monday 3/22 and Tuesday 3/23 at the beginning of paragraph and repeats the former at the end. Which would be correct dates?
CO Response: The correct Site Visit dates are Monday 3/29 and Tuesday 3/30. As such, an Amendment will be posted to the Contracting Opps website to clarify these conflicting dates. Thank you for bringing this to my attention.
Second Set of Proposal Inquiries dated 3/22/21:
Proposal RFI #1 – The medical air compressor and vacuum pumps state that they should be sized to serve the entire building even though the scope of this project is just for one wing. Do you have an anticipated SCFM requirement for the building? To properly size the units, I would need the SCFM requirement or anticipated number of outlets for each gas in the entire building.
COR Response - Correct the new Medical Gas System is to be sized to service all patient bedrooms in the building (see provided floor plans to verify/accurate count), however in this effort you will be required to provide 3 service outlets (medical air, medical vacuum and oxygen) to a total of 24 patient beds (12 beds in Niagara Suite located on 1st floor and 12 beds in Potomac Suite located on 2nd floor). Our intent for sizing the medical gas system for the entire building is to give us the capability (at a later date) to expand medical gas services into the other wings should the need arise. Contractor to consult with “Powerex” representative and medical gas installer/expert to ensure equipment is sized properly. Our intent is for this to be a complete turn-key effort.
Proposal RFI #2 – Are there engineered plans for this project?
COR Response - There are no engineered plans for this project. Contractor to consult with “Powerex” representative, medical gas installer/expert and any engineers necessary to determine piping path, dimensions, equipment sizing/location, system requirements, outlet and panel locations, wiring, etc. as required for a complete turn-key project and to ensure new system meets all NFPA 99 requirements. In addition the contractor will need to consult with a structural engineer/architect for any renovation/modification work to the attic area to accommodate new equipment layout. Our intent is for this to be a complete turn-key effort.
Proposal RFI #3 – Will the outlet count be 1 oxygen and 1 vacuum per room?
COR Response - The outlet count for each bed location will be 1 oxygen, 1 medical air and 1 medical gas.
Add additional from COR - The VA will provide photos and video tour of existing space to help aide contractors. The pre-bid site visit will be helpful for all interested contractors intending to bid on this project.
Third Set of Proposal Inquiries dated 4/5/21:
Proposal RFI #1 – Attachments contained in the Scope of Work do not open through the Word document. Can these attachments be provided in another way?
CO Response - The above four noted attachments contained in the Scope of Work were printed out in plain black & white vs. color print and are attached hereto in one pdf document.
Fourth Set of Proposal Inquiries dated 4/7/21:
Proposal RFI #1 – In the attic area where unit will be brought in and placed a structural engineer will be needed to determine the loads. As this is not a design build, will the VA be providing the anticipated loads, or an allowance given for contractor to carry in price.
COR Response - This new Medical Gas System is a turn-key project. The Contractor will be fully responsible for consulting with a structural engineer for design, roofing system modification to accommodate new equipment layout in attic and any anticipated load information. The contractor is responsible for hiring and consulting with any engineer and medical gas expert to ensure all aspects of this new system is properly designed and installed according to NFPA 99 code requirements. Contractor is responsible for all costs associated with delivering a fully functional Medical Gas System in Building 15 as indicated in SOW.
Proposal RFI #2 – We are boring from the oxygen box to the mechanical door. After seeing inside the mechanical room there is a ton of equipment already installed inside. Will a mechanical engineer be required to determine a location to mount our equipment, or will the VA have a space determined inside by the time the project starts?
COR Response – Space in attic to mount new medical gas equipment was indicated on attic drawings provided in solicitation and shown during site visit. The location of piping path and of new equipment in centralized location in attic is specified on SOW and drawings as the most feasible option for pricing purposes. This new Medical Gas System is a turn-key project. The Contractor will be fully responsible for consulting with any engineer and medical gas expert for design and equipment/system integration in the building. Contractor is responsible for all costs associated with delivering a fully functional Medical Gas System in Building 15 as indicated in SOW.
Proposal RFI #3 - COVID test are required twice weekly, will there ever be a charge to the contractor for these biweekly tests?
COR Response - No. The VA will furnish all required COVID testing and results for contractors through the entire duration of the project.
Proposal RFI #4 – What is the depth that we are to bore? If it is over 15’ depth, there is a possibility that we may not be able to bore that deep in certain areas.
COR Response - Contractor to consult with an engineer, medical gas expert, boring contractor, or underground utility contractor to make depth determination and boring path for inserting oxygen into Building 15 from oxygen tie-in box located outside. This new Medical Gas System is a turn-key project.
Proposal RFI #5 – What size pipe/casing and type of pipe are we to use while boring?
COR Response - Oxygen piping is to be copper tubing or as specified by NFPA. Contractor to consult with an engineer, medical gas expert, boring contractor, or underground utility contractor to make pipe/casing and type of pipe determination. This new Medical Gas System is a turn-key project. All work needs to meet NFPA 99 code requirements.
Medical Air- pages (SR4329) 2018.pdf
NFPA 99 Medical Air Compressor Systems
72” 60”
73”
100”
Competitor’s 6-8 pump system
Powerex 6-8 pump scroll system
Our compressors are low maintenance, energy efficient, and easily serviceable.
• Patented Service Slide
• Common service items easily accesible
• Basemount extends 20” from rack
EASILY SERVICEABLE
Powerex designs and manufactures NFPA 99 medical air systems in the U.S.A.
Our newly redesigned and upgraded space-saving scroll compressors feature the smallest available footprint on the market, allowing for flexibility of hospital design and ease of installation.
• Up to 39% less footprint than leading competitor
• Systems designed to fit through 36” door
BEST IN CLASS FOOTPRINT
20”
Our innovative scroll technology is completely oil-less, extremely quiet, and energy efficient. The scroll pump has few moving parts, making it reliable and easier to maintain. The self lubricating tip seals and absence of a gearbox means the pump is 100% oil free.
SCROLL COMPRESSORS
SYSTEMS SPECIFICATIONS
Medical Scroll Multiplex Systems
Model SCFM @ 50 PSIG* HP Tank (Gal.)
Duplex Systems
MTSD0303 9.5 3 (2) 80
MTSD0503 16.6 5 (2) 80
MSD02A3 6 2 (2) 80
MSD03A3 9.5 3 (2) 80
MSD05A3 16.6 5 (2) 80
MSD0754 23.8 7.5 (2) 120
MSD10B4 31.6 10 (2) 120
MSD10A4/5/6 33.2 10 (2) 120/200/240
MSD15B4 47.6 15 (2) 120
MSD15A4/5/6 49.8 15 (2) 120/200/240
MSD2004 63.2 20 (2) 120
MSD20B4 63.2 20 (2) 120
Triplex Systems
MST03A3 19 3 (3) 80
MST05A3/4 33.2 5 (3) 80/120
MST0755 47.6 7.5 (3) 200
MST10B5 63.2 10 (3) 200
MST10A4/5 66.4 10 (3) 120/200
MST15B5/6 95.2 15 (3) 200/240
MST15A4/5/6 99.6 15 (3) 120/200/240
MST20B5/6 126.4 20 (3) 200/240
Quadplex Systems
MSQ05A4 49.8 5 (4) 120
MSQ0755 71.4 7.5 (4) 200
MSQ10B5 94.8 10 (4) 200
MSQ10A5/6 99.6 10 (4) 200/240
MSQ15B5/6 142.8 15 (4) 200/240
MSQ15A5/6 149.4 15 (4) 200/240
MSQ20B5/6 189.6 20 (4) 200/240
Pentaplex Systems
MSP15A5/6 199.2 15 (5) 200/240
MSP15B5 190.4 15 (5) 200
Hexaplex Systems
MSH05A4/5 83 5 (6) 120/200
MSH10B6 158 10 (6) 240
MSH10A6 166 10 (6) 240
MSH15A5/6 249 15 (6) 200/240
Octoplex Systems
MSO10B6 221.2 10 (8) 240
Nonaplex Systems
MSN05A5 132.8 5 (9) 200
Medical Reciprocating Skidmount Systems
Duplex Package Systems
MPD0308 11.3 3 (2) 80
MPD0508 18.6 5 (2) 120
MPD0608 21.4 7.5 (2) 120
MPD0758 27.3 7.5 (2) 120
MPD1008 34.8 10 (2) 200
MPD1508 50.9 15 (2) 200
Triplex Package Systems
MPT0508 37.2 5 (3) 200
MPT0608 42.8 7.5 (3) 200
MPT0758 54.6 7.5 (3) 200
MPT1008 69.9 10 (3) 240
MPT1508 101.8 15 (3) 240
Quadplex Package Systems
MPQ0508 55.8 5 (4) 240
MPQ0608 64.2 7.5 (4) 240
MPQ0758 81.9 7.5 (4) 240
MPQ1008 108.6 10 (4) 240
MPQ1508 152.7 15 (4) 240
Medical Reciprocating Tankmount Systems
Duplex Tankmount Systems
MTD0103 3.4 1 (2) 80
MTD0203 8.3 2 (2) 80
MTD0303 11.3 3 (2) 80
MTD0304 11.3 3 (2) 120
MTD0504 18.6 5 (2) 120
MTD0505 18.6 5 (2) 200
MTD0756 27.3 7.5 (2) 240
MTD1006 34.8 10 (2) 240
MTD1506 50.9 15 (2) 240
Our reciprocating piston systems feature self-lubricating composite piston technology which increases ring life and reduces temperature, providing reliability for years to come. The dual cooling pistons reduce operating temperatures, while the corrosion-resistant components and coatings extend ring and valve life.
RECIPROCATING COMPRESSORS
*SCFM @ 50 PSIG is shown with one compressor in reserve per NFPA 99 guidelines
• UL508A listed and labeled, NEMA 4/12 enclosure
• Timed lead/lag compressor alternation
• Visual and audible reserve compressor in use alarm
• Redundant control circuit transformers
• Dry contacts for remote alarm monitoring
• Each compressor provided with:
• Hand/Off/Auto selector switch
• Magnetic starter with 3 leg overload protection
• Visual and audible high temperature shut down
• Hour meter.
• Compressor run light
• Dew point monitor with LCD dew point display
• Carbon monoxide monitor with LCD display of CO concentrations
• PLC controller and 6" color HMI (Human Machine Interface) touch screen displays the operating status of the unit
• Visual and audible alarms for:
• System overload trip
• High temperature conditions
• Service intervals
• High dew point and CO levels
• Panel door includes:
• Visual and audible alarms
• HOA switch for each pump
• 3-position dryer switch
• Integrated dew point and carbon monoxide monitors
• Building automation gateway with BacNet® protocol
• Email notifications for alarms and service alerts
STANDARD PREMIUM CONTROL PANEL OPTIONAL NON-HMI CONTROL PANEL
Skidmount
CONFIGURATION TYPES
• Multiple compressors
• ASME receiver
• UL508A control panel
• Air purification system
• Carbon monoxide monitor
• Dew point monitor
• All interconnecting piping and wiring
• Vibration isolation pads and flex connectors
• Most of our multiplex scroll packages now OSHPD certified
NFPA 99 MEDICAL AIR COMPRESSOR SYSTEMS
DESIGN FEATURES
All systems are fully compliant with the latest edition of NFPA 99 and are manufactured in ISO 9001:2015 certified facilities.
Horizontal Tankmount
The leader in oil-free air technology
Powerex manufactures industry-leading comprehensive medical gas systems,from source equipment to pipeline
For more information contact your local Powerex distributor or Powerex sales representative today
150 Production Drive • Harrison, OH 45030 • USA T 1.888.769.7979 • F 513.367.3125 • www.powerexinc.com
SR4329
10/2018 image3.emf
VPD5-10 EX3 PREMIUM.pdf
Medical Vacuum Expandable Package 5-10HP with Premium Controls
Powerex • 150 Production Drive • Harrison, OH 45030 • USA
(T) 1.888.769.7979 • (F) 513.367.3125 • www.powerexinc.com
01/2017
Medical Vacuum Expandable Package with Premium Controls
Model HP SCFM @ 19” Hg each
NFPA
System
Capacity(1)
Tank Size (gal) BTU/Hr (2) dB(A)
Level (3)
System F.L.A. System Weight (lbs)208V 230V 460V
VPD0504-EX3 5 (3) 37 37 (74) 120 21,676 75 46.4 40.7 21.3 1,700
VPD0754-EX3 7.5 (3) 52 52 (104) 120 32,512 83 65 63.2 32.6 2,350
VPD1004-EX3 10 (3) 77 77 (154) 120 43,350 84 81.2 78.8 40.4 2,650
Notes:
1 – System Capacity is shown with one or more pumps in reserve per NFPA 99. Values are shown for duplex (triplex) configuration.
2 – BTU/Hr levels are shown with reserve pump(s) on standby.
3 – dB(A) levels are shown with one pump in reserve per NFPA 99.
4 – 3 Year Limited Warranty.
Note: All values and images shown are for fully expanded system.
Dimensions Model Dim. A Dim. B Dim. C Inlet Outlet (x3)
VPD0504-EX3 64” 55” 88” 2” 2”
VPD0754-EX3 64” 56” 88” 3” 2”
VPD1004-EX3 64” 56” 88” 3” 2”
DGoggans
Highlight
Slide Number 1 image4.emf
Medical Vacuum - pages (SR4325) 2018.pdf
Medical Vacuum Systems
19" Hg HP Tank
(Gal.)
Duplex Enclosure
MCED050 33 5 120
MCED070 52.8 7.5 small 120
MCED075 67.8 7.5 big 120
Triplex Enclosure
MCET050 66 5 200
MCET070 105.6 7.5 small 200
MCET075 135.6 7.5 big 200
Quadplex Enclosure
MCEQ050 99 5 200
MCEQ070 158.4 7.5 small 200
MCEQ075 203.4 7.5 big 200
• Most energy efficient technology
• Oil-free compression chamber
• Extremely low maintenance
• No water and sewage costs
• Suitable for dedicated waste anesthesia (WAGD) systems
• Air-cooled design
BENEFITS
• NEW Enclosed Systems
• Premium Warranty
• Expandable Systems
• Variable Frequency Drive
• Oxygen Assured Pumps
• Internal Tank Lining
• Non-HMI Controls
• Alternate Tank Sizes &
Custom Configurations
Duplex Modular Skidmount
CVPD0504A° 29 4 120
CVPD0504B° 38 5 120
CVPD0754A° 52 6.4 120
CVPD0754B° 65 7.5 120
CVPD1005° 87 10 200
CVPD1505° 129 15 200
Triplex Modular Skidmount
CVPT0504A° 58 4 120
CVPT0504B° 76 5 120
CVPT0755A° 104 6.4 200
CVPT075сB° 130 7.5 2п0
CVPT1005° 174 10 200
CVPT1505° 258 15 200
Quadplex Modular Skidmount
CVPQ0505A° 87 4 200
CVPQ0505B° 114 5 200
CVPQ0755A° 156 6.4 200
CVPQ0755B° 195 7.5 200
CVPQ1005° 261 10 200
CVPQ1505° 387 15 200
Pentaplex Modular Skidmount
CVPP1505 516 15 200
DRY CLAW
Inside the pump housing, two claw shaped rotors take in air as they rotate in opposite directions. The air is compressed by the rotors, then discharged through a silencer to atmosphere. The pumping chamber is dry. There is no contact between the rotors or the cylinder wall eliminating internal wear and parts to replace. The rotors are synchronized by gears requiring a small amount of oil in the gear housing. Gear oil change requirements are minimal at approximately 20,000 hours.
AVAILABLE OPTIONS
CVPT0755 with VFD
Contact factory for alternate tank sizes and expandable systems °System is OSHPD (seismic) certified; Certification No. OSP-3093-10
Duplex Horizontal Tankmount
CVTD0203 16 2 80
CVTD0303 21 3 80
CVTD0504A 29 4 120
CVTD0504B 38 5 120
Duplex Vertical Tankmount
CVTD0203V 16 2 80
CVTD0303V 21 3 80
CVTD0504AV 29 4 120
CVTD0504BV 38 5 120
Duplex Tank-over Skidmount
CVPDT0502A 29 4 60
CVPDT0502B 38 5 60
CVPDT0752A 52 6.4 60
CVPDT0752B 65 7.5 60
VOPD0403 17 5 80
VOPD0503 20 5 80
VOPD0754 30.4 7.5 120
VOPD1004 56 8.6 120
VOPT0503 40 2 80
VOPT0755 60.8 7.5 200
VOPT1004 112 8.6 120
VOPQ0505 60 5 200
VOPQ0755 91.2 7.5 200
VOPQ1005 168 8.6 200
• Expandable Systems
• Internal Tank Lining
• X-Series Vanes for up to
20,000 hours of life
DRY ROTARY VANE
A rotor is mounted eccentrically in the pump cylinder and contains several sliding vanes.
As the rotor turns, centrifugal force causes the vanes to slide outward creating a seal against the cylinder wall. The vanes are constructed of a self-lubricating graphite composite material which allows them to operate against the cylinder wall without the need for any other sealing or lubricating fluid. As a result of the offset rotor, a succession of variable volumes are formed in the cylinder housing creating the flow of vapor through the pump.
Vapor is pulled into the pump inlet which is then compressed and discharged through the exhaust to atmosphere.
SYSTEMS SPECIFICATIONS• No oil anywhere
• Easy to maintain
• Suitable for dedicated waste anesthesia (WAGD) systems
• Less routine maintenance
(no oil changes)
• Lower initial cost as compared to oil-free pump technology
VOTD0755 30.4 7.5 200
VOTD1006 56 8.6 240
VVOTD0153 5.3 1.5 80
VVOTD0203 8 2 80
VVOTD0303 13.5 3 80
VVOTD0404 17 5 120
VVOTD0504 20 5 120
VOPD1004
VTD0153 7 1.5 80
VTD0203 11 2 80
VTD0303 17 3 80
VTD0404 25 5 120
VTD0504 37 5 120
VTD0755 52 7.5 200
VTD1006 77 10 240
VVTD0153 7 1.5 80
VVTD0203 11 2 80
VVTD0303 17 3 80
VVTD0403 25 5 80
VVTD0503 37 5 80
Duplex Tankover Systems
VPDT0402 25 5 60
VPDT0502 37 5 60
VPDT0752 52 7.5 60
OIL-SEALED ROTARY VANE
A rotor is mounted eccentrically in the pump cylinder and contains several sliding vanes. As the rotor turns, centrifugal force causes the vanes to slide outward against the cylinder wall.
Oil is injected into the pumping chamber to create a seal between the vanes and the cylinder wall and to lubricate the vanes for reduced wear. As a result of the offset rotor, a succession of variable volumes is formed in the cylinder housing creating the flow of air through the pump. Air is pulled into the pump inlet which is then compressed and discharged into the exhaust box. At this point oil is mixed with the air and is passed through several stages of internal oil and mist eliminators to remove 99.9% of the lubricating oil before the exhaust is released to atmosphere. The separated oil is then returned to the oil reservoir.
• Expandable Systems
• High Temperature Alarm
• Oil Temperature Gauges
• Synthetic Oil
• Internal Tank Lining
SYSTEMS SPECIFICATIONS• 30,000 hour vane life
• Air-cooled design
• Semi-synthetic oil
• Oil-flooded for lubrication and heat dissipation
• Lowest initial cost
• Highest ultimate vacuum levels 29.3” Hg
• Most suitable for high ambient temperatures
VPD0754° 52 7.5 120
VPD1004° 77 10 120
VPD1505° 111 15 200
VPD2005° 137 20 200
VPD2505° 168 25 200
VPT0504° 74 5 120
VPT0754° 104 7.5 120
VPT1004° 154 10 120
VPT1505° 222 15 200
VPT2005° 274 20 200
VPT2505° 336 25 200
VPQ0505° 111 5 200
VPQ0755° 156 7.5 200
VPQ1005° 231 10 200
VPQ1505° 333 15 200
VPQ2005° 411 20 200
VPQ2505° 504 25 200
VVTD0503
°System is OSHPD (seismic) certified; Certification No. OSP-3093-10
MEDICAL VACUUM SYSTEMS OPTIONS
STANDARD PREMIUM CONTROL PANEL
• PLC controller and 6" color HMI (Human Machine Interface) touch screen displays the operating status of the unit
• Visual and audible alarms for:
• System overload trip
• High temperature conditions
• Service intervals
• Panel door includes:
• Visual and audible alarms
• HOA switch for each pump
• Building automation gateway with BacNet® protocol
• Email notifications for alarms and service alerts.
OPTIONAL NON-HMI CONTROL PANEL
• UL508A listed and labeled, NEMA 4/12 enclosure.
• Timed lead/lag alternation.
• Visual and audible reserve in use alarm.
• Redundant control circuit transformers.
• Dry contacts for remote alarm monitoring.
• Each vacuum pump provided with:
• Hand/Off/Auto selector switch.
• Magnetic starter with 3 leg overload protection.
• Visual and audible high temperature shut down.
• Hour meter.
• Fully compliant with the latest edition of
NFPA 99
• Multiple vacuum pumps
• ASME receiver
• UL Listed control panel (HMI or Non-HMI)
• All interconnecting piping and wiring
• Vibration isolation pads and flex connectors
• Manufactured in ISO 9001:2008 UL certified facilities
SYSTEM DESIGN FEATURES CONFIGURATION TYPES
Horizontal TankmountVertical TankmountModular SkidmountTank-over Skidmount
SR4325
03/2018
The leader in oil-free air technology
Powerex manufactures industry-leading comprehensive medical air and vacuum systems, from source equipment to pipeline
For more information contact your local Powerex distributor or Powerex sales representative today
150 Production Drive • Harrison, OH 45030 • USA T 1.888.769.7979 • F 513-367-3125 • www.powerexinc.com
7 Medical Vacuum - pages (SR4325) 2018
7 Medical Vacuum - pages (SR4325) 2018 (2)
6 Medical Vacuum - pages (SR4325) 2018 (2) image1.emf
MSD-A 5HP EX PREMIUM.pdf
Medical Scroll Skidmount Package Duplex with Premium Controls
Powerex • 150 Production Drive • Harrison, OH 45030 • USA
(T) 1.888.769.7979 • (F) 513.367.3125 • www.powerexinc.com
8/2018
Dimensions Model Dim. A Dim. B Dim. C Inlet Outlet
MSD05A3-EX3 52” 73” 75” 1.5” 1”
MSD05A4-EX4 52” 73” 76” 2” 1”
Medical Scroll Skidmount Package Duplex with Premium Controls
Model HP ICFM @
50 PSIG
SCFM @
50 PSIG(1,3)
Tank Size (gal) BTU/Hr (2) dB(A)
Level (3) System F.L.A. System
Weight (lbs)208V 230V 460V
MSD05A3-EX3 5 (2) / 5 (3) 18.4 (36.8) 16.6 (33.2) 80 25450 75 44 40.1 21 1500
MSD05A4-EX4 5 (2) / 5 (4) 18.4 (55.2) 16.6 (49.8) 120 38175 77 58 52.8 27.3 1700
Notes:
1 – ICFM and SCFM values @ 50 PSIG are shown with one compressor in reserve per NFPA 99.
*Powerex recommends using performance ratings in SCFM (Standard Cubic Feet per Minute) when sizing medical air systems.
*ICFM is standardly defined within the Medical Air Compressor Industry.
2 – BTU/Hr levels are shown with reserve pump(s) on standby.
3 – dB(A) levels are shown with one pump in reserve per NFPA 99.
4 – 3 Year Limited Warranty.
5 – Drawing is representative and not exact.
Slide Number 1 image2.emf