36C25618U0323-0002014.pdf
PDF 3 MB Posted
- Attached to
- Services Commissioning for HVAC Digital Controls Federal contract opportunity
- Solicitation number
- 36C25618U0323
About this file
36C25618U0323 0002 Drawings - Building 2 (M2 Series).pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| -15380.docx | DOCX document | |
| 36C25618U0323-0002007.pdf | ||
| 36C25618U0323-0002005.pdf | ||
| 36C25618U0323-0002004.pdf | ||
| 36C25618U0323-0002006.pdf | ||
| 36C25618U0323-0002012.pdf | ||
| 36C25618U0323-0002000.docx | DOCX document | |
| 36C25618U0323-0002013.pdf | ||
| 36C25618U0323-0002010.pdf | ||
| 36C25618U0323-0002002.pdf | ||
| 36C25618U0323-0002011.pdf | ||
| 36C25618U0323-0002009.pdf | ||
| 36C25618U0323-0002001.docx | DOCX document | |
| 36C25618U0323-0002003.pdf | ||
| 36C25618U0323-0002008.pdf | ||
| 36C25618U0323-0001000.docx | DOCX document | |
| 36C25618U0323-002.pdf | ||
| 36C25618U0323-001.docx | DOCX document | |
| 36C25618U0323-000.docx | DOCX document |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXIST 2-HWP10
EXIST 2-HX-4
EXIST 2-HWP9
EXIST 2-HX-3
EXIST DDC
CONTROL PANEL
EXIST 2-SCHWP3
EXIST 2-SCHWP4
EXIST 2-SCHWP6
EXIST DDC
CONTROL PANEL
EXIST 2-SCHWP1
EXIST 2-SCHWP5
EXIST DDC
CONTROL PANEL
EXIST DDC
CONTROL PANEL
EXIST 2-HWP7
EXIST 2-SCHWP2
EXIST
2-HWP8
EXIST 2-HX-1 EXIST
2-HX-2
NOTES:
1. EXISTING DDC SYSTEM IS JCI. REPLACE
CONTROLLERS IN EXIST PANELS TO FULLY
INTEGRATE ALL EQUIPMENT TO SIEMENS
CAMPUS SYSTEM. CONNECT NEW
CONTROLLERS TO EXISTING 120V
ELECTRICAL SERVICE.
PROVIDE CHILLED WATER METER IN
SUPPLY PRIOR TO ANY TAKEOFF. METER
WILL BE FOR THE TOTAL OF BLDGS 1, 2, & 3.
CHW METERS WILL BE INSTALLED IN
FUTURE PROJECTS FOR BLDGS 1 & 3, AT
WHICH TIME CHW USAGE FOR BLDG 2 CAN
BE DETERMINED.
CHILLED WATER METER PANEL. CONNECT TO
CAMPUS DDC CONTROL SYSTEM.
VFD VFD
PROVIDE NEW 7.5 HP VFD FOR
2-SCHWP2. CONNECT TO EXIST POWER
AND NEW CONTROLS.
PROVIDE NEW 7.5 HP VFD FOR
2-SCHWP4. CONNECT TO EXIST POWER
AND NEW CONTROLS.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
BASEMENT FLOOR PLAN -
MECHANICAL
2 WLP NMT
M2-100 10-30-13
NOTES:
1. EXISTING INDUCTION UNITS AND CONTROLS
TO REMAIN.
EXISTING ELEC METER
ENCLOSURE. CONNECT
TO CAMPUS DDC
CONTROLS.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
1ST FLOOR PLAN - MECHANICAL
2 WLP NMT
M2-101
EXIST WINDOW
A/C UNIT TO
REMAIN ON UNIT
CONTROLS.
KEYNOTES:
EXISTING FAN COIL UNIT TO REMAIN.
REPLACE FAN COIL UNIT CONTROLLER
AND CONTROL PANELS TO FULLY
INTEGRATE TO SIEMENS CAMPUS
SYSTEM.
EXIST EF-2-1
T T
T
T T
TT
T
T
T T
T
T
T
T
T
T
TT
T
T
T T T T T T
TT
T
T
T
T
T
T
T
T
T
T
T T T T T T
T
T
T T
T
T
T
T
T
T
T
T
T
T TT T
T
T
T
T
T
1 1
1 1
1 1
1 1 1
1 1
1 1
1 1
1 1
1 1
1 1
EXIST EXHAUST FAN &
WINDOW A/C UNIT TO
REMAIN ON LOCAL
CONTROLS.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
2ND FLOOR PLAN - MECHANICAL
2 WLP NMT
M2-102
EXIST EF-2-6
EXIST EF-2-5
T T
T
T TT
T
T
T
T
TT
T
T T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T
T
TT
T
T
T TTTT
T
T
T
T
T
T T
T
T
T
T
T
T
T
T T
T
T
T T
T T
T T
T T
EXIST EF-2-4
EXIST EF-2-7
1 1
1 1
1 1 1
1 1
1 1
1 1
1 1
1 1
EXIST EF-2-2
EXIST EF-2-3
KEYNOTES:
EXISTING FAN COIL UNIT TO REMAIN.
REPLACE FAN COIL UNIT CONTROLLER
AND CONTROL PANELS TO FULLY
INTEGRATE TO SIEMENS CAMPUS
SYSTEM.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
3RD FLOOR PLAN - MECHANICAL
2 WLP NMT
M2-103
1. NO EXISTING OR NEW MECHANICAL EQUIPMENT TO
BE CONTROLLED ON THIS FLOOR.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
4TH FLOOR PLAN - MECHANICAL
2 WLP NMT
M2-104
EXISTING
2-AC-22
EXISTING
2-AC-21
EXISTING
2-AC-23
2-AC-22 IS CURRENTLY
INOPERABLE AND IS NOT TO BE
CONTROLLED.
2-AC-21 IS CURRENTLY FULLY PNEUMATIC
CONTROLS. REPLACE ALL CONTROL DEVICES WITH
DDC AND CONNECT TO NEW DDC CAMPUS
SYSTEM.
2-AC-23 IS CURRENTLY FULLY PNEUMATIC
CONTROLS. REPLACE ALL CONTROL
DEVICES WITH DDC AND CONNECT TO
NEW DDC CAMPUS SYSTEM.
HVAC
KEYNOTES:
PROVIDE NEW DDC CONTROL PANEL. CONTRACTOR
SHALL PROVIDE 120V POWER CONNECTION TO NEW
CONTROL PANEL. CONTRACTOR SHALL ROUTE TO
NEAREST 120V PANEL WITH SPARE CAPACITY, INSTALL
NEW 20A-1 POLE CIRCUIT BREAKER, & MAKE
CONNECTION. PROVIDE 20A SNAP SWITCH AT DDC
PANEL FOR DISCONNECT. CONTRACTOR TO VERIFY
120V PANEL LOCATION DURING PRE-BID
WALKTHROUGH.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
ATTIC FLOOR PLAN - MECHANICAL
2 WLP NMT
M2-105
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
2-AC-21 & 2-AC-23 CONTROL
SCHEMATIC & SEQUENCE
2 WLP NMT
M2-200
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING PNEUMATIC AND ARE TO
BE REPLACED WITH APPROPIATE DDC DEVICES.
2. PROVIDE NEW DDC CONTROLLER. CONNECT NEW CONTROLLER
TO EXISTING 120V ELECTRICAL SERVICE.
3. TEST AND BALANCE ALL AIR FLOWS TO AHU, FCU, VAV BOXES
(MAX. AND MIN.), ETC PRIOR TO STARTING WORK. PROVIDE
REPORT TO VA. BALANCE ALL AIR FLOWS TO
PRE-CONSTRUCTION VALUES.
SUPPLY
STR
FAN
DO1
DI4
COIL
L P
S
V-1
PREHEAT
AI6
AO3
DI3
AO1
AI1
SUPPLY AIR
PANEL
DDC CONTROL
AI3
T-1
T
T-2
OUTSIDE AIR
D-1
AI4
RETURN AIR
AI7
T-3
T-4
C H
W R
COIL
CLG
V-2
NC
AI8
AO4
DI5
AI11
T-7
SPS-1
DI7
DPS-1
DI1
AIR
FILTER
DI6
SD-2
AI9
T-5
T-6
SEQUENCE OF OPERATION
1. GENERAL
1.1 THE AIR HANDLING UNIT SHALL BE STARTED AND STOPPED AUTOMATICALLY AT THE ECC. THE HOA SWITCH SHALL BE KEPT IN THE AUTO POSITION. HAND AND OFF POSITIONS SHALL BE USED FOR MAINTENANCE ONLY. UPON RECEIVING A START COMMAND THE SUPPLY FAN WILL START ONLY AFTER ALL INTERNAL SAFETIES ARE PROVEN. ONCE FAN RUN STATUS IS PROVEN BY A CURRENT SENSING RELAY, THE
CONTROLS SHALL OPERATE ACCORDING TO THE SEQUENCES AS DESCRIBED BELOW.
2. DAMPER CONTROL
3.1 DURING OCCUPIED MODE, OA DAMPER SHALL BE FULLY OPEN AND RA DAMPERS SHALL BE FULLY CLOSED.
3.2 DURING UNOCCUPIED MODE, IF THE UNIT IS RUNNING THE OA DAMPER SHALL BE FULLY CLOSED AND THE
RA DAMPER SHALL BE FULLY OPEN.
3. TEMPERATURE CONTROL
3.1 THE PREHEAT COIL VALVE (V-1) SHALL MODULATE TO MAINTAIN A PREHEAT DISCHARGE TEMPERATURE AS
SENSED BY (T-3) OF 45°F.
3.2 WHEN OA DEWPOINT IS ABOVE 55°F THE CHILLED WATER COIL VALVE (V-2) SHALL MODULATE TO MAINTAIN A UNIT DISCHARGE TEMPERATURE AS SENSED BY (T-7) OF 57°F. WHEN THE OA DEWPOINT IS BELOW 55°F THE CHILLED WATER COIL VALVE (V-2) SHALL MODULATE TO MAINTAIN A UNIT DISCHARGE TEMPERATURE
AS SENSED BY (T-7) OF 75°F.
3.3 WHEN ALL ZONES ARE CALLING FOR HEATING PREHEAT VALVE (V-1) AND REHEAT VALVE (V-3) SHALL
MODULATE TO MAINTAIN A DISCHARGE AIR TEMPERATURE OF 90°F AS SENSED BY (T-7).
4. ALARMS
4.1 THE UNIT SHALL STOP UPON ANY OF THE SAFETIES BEING TRIPPED REGARDLESS OF THE MODE OF
OPERATION (AUTOMATIC, HAND OR BYPASS).
4.2 THE RETURN AIR SMOKE DETECTOR, SD-1, OR THE SUPPLY AIR SMOKE DETECTOR, SD-2, SHALL STOP THE UNIT UPON SENSING COMBUSTION PRODUCTS IN THE SYSTEM. SMOKE DETECTORS MUST BE MANUALLY
REST AFTER AN ALARM CONDITION IN ORDER FOR THE FAN TO RESTART.
4.3 A TEMPERATURE LOW LIMIT SWITCH, T-4, SHALL STOP THE UNIT, CLOSE THE OUTSIDE AIR DAMPER, OPEN THE PREHEAT VALVE, AND SEND A CRITICAL ALARM TO THE ECC UPON SENSING A FALL IN TEMPERATURE BELOW SETPOINT (35°F ADJUSTABLE). THE LOW LIMIT SWITCHES MUST BE MANUALLY RESET AFTER AN
ALARM CONDITION.
4.4 A TEMPERATURE HIGH LIMIT, T-6, WILL SHUTDOWN THE FAN AND SEND AN ALARM TO THE ECC UPON A RISE IN DISCHARGE AIR ABOVE 125°F. THE HIGH LIMIT SWITCH MUST BE MANUALLY RESET AFTER AN ALARM.
4.5 A DISCHARGE AIR HIGH STATIC PRESSURE SAFETY SWITCH, SPS-1, LOCATED AT THE SUPPLY FAN DISCHARGE WILL STOP THE UNIT UPON SENSING HIGH SUPPLY DUCT STATIC ABOVE 3 IN. STATIC
PRESSURE (ADJUSTABLE) TO PREVENT OVER PRESSURIZING THE DUCTWORK.
5. MONITORING
5.1 THE DCC SYSTEM MONITORS THE DIFFERENTIAL PRESSURE ACROSS THE FILTER AND GENERATES AN ALARM IF THE DIFFERENTIAL PRESSURE INCREASES ABOVE THE SETPOINT OF 0.75 IN. WC. (ADJUSTABLE)
TO PROVIDE NOTIFICATION OF A DIRTY FILTER.
6. SHUTDOWN
6.1 STOPPING THE UNIT SHALL DE-ENERGIZE THE CONTROL LOOPS AND SEND THE CONTROL VALVES AND
OUTSIDE AIR DAMPER TO THE CLOSED POSITION.
T T T T T T
MIXED AIR TEMPERATURE SENSOR (T-1)
RETURN AIR TEMPERATURE SENSOR (T-2)AI4
AI1
RETURN AIR HUMIDITY SENSOR (H-1)AI5
AI6
AI8
AI9
AI7
AI10
AI11
PREHEAT COIL DISCHARGE AIR TEMPERATURE SENSOR (T-3)
CHILLED WATER CONTROL VALVE (V-2)
COOLING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-5)
OUTSIDE AIR TEMPERATURE SENSOR (T-8)
DI4
DI5
DI2
DI1
DI3
STEAM PREHEAT CONTROL VALVE (V-1)
CHILLED WATER CONTROL VALVE (V-2)
AO3
AO4
AHU DISCHARGE TEMPERATURE SENSOR (T-7)
FILTER STATUS (DPS-1)
LOW LIMIT TEMPERATURE SENSOR (T-4) STATUS
SUPPLY FAN STATUS
SUPPLY AIR SMOKE DETECTOR (SD-2) STATUS
HIGH LIMIT TEMPERATURE SENSOR (T-6) STATUS
SUPPLY AIR HIGH STATIC PRESSURE SWITCH (SPS-1) STATUS
AI2
AO2
D-2
DI6
DO3 SUPPLY FAN START/STOP
DI2
SD-1
NO
COIL
L P
S
V-3
REHEAT
AI10
AO5
NO
T
H-1
AI5
STEAM PREHEAT CONTROL VALVE (V-1)
STEAM REHEAT CONTROL VALVE (V-3)
AI12
RETURN AIR SMOKE DETECTOR (SD-1) STATUS
DI7
STEAM REHEAT CONTROL VALVE (V-3)AO5
AI2
AI1 OUTSIDE AIR DAMPER (D-1) STATUS
RETURN AIR DAMPER (D-2) STATUS
AO1
AO2
OUTSIDE AIR DAMPER (D-1)
RETURN AIR DAMPER (D-2)
T
T-8
T
H-2
AI12 AI13
OUTSIDE AIR HUMIDITY SENSOR (H-2)AI13
SUPPLY
FAN COIL
H W
S
V-2
HTG
AI2
AO2DO1
DI1
PANEL
DDC CONTROL
AI3
T-1
D-1
RETURN AIR
C H
W R
COIL
CLG
V-1
AI1
AO1DO2
DI2
NC
SUPPLY AIR
T-2
AI4
SPACE
THERMOSTAT
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING DDC.
2. FAN COIL UNIT CONTROLLER TO BE REPLACED.
3. SPACE THERMOSTAT TO BE REPLACED.
4. UNIT TEMP SENSORS AND ACTUATORS CAN BE
REUSED IF FUNCTIONAL AND COMPATIBLE WITH
NEW CONTROLS.
5. TYPICAL OF 110 UNITS.
SEQUENCE OF OPERATION: FAN COIL UNIT (TYP.)
1. SUPPLY FAN CONTROL
1.1. WHEN THE THERMOSTAT FAN MODE IS SET TO "ON", THE SUPPLY FAN SHALL RUN
CONTINUOUSLY.
1.2. WHEN THE THERMOSTAT FAN MODE IS SET TO "AUTO", THE SUPPLY FAN SHALL
RUN ANYTIME THERE IS A CALL FOR HEATING OR COOLING.
2. TEMPERATURE CONTROL
2.1. THE UNIT SHALL CONTROL TO MAINTAIN THE ZONE TEMPERATURE SETPOIINT AS
SENSED BY THE ZONE TEMPERATURE SENSOR, T-2.
3. OCCUPIED MODE
3.1. THE OCCUPANCY MODE SHALL BE CONTROLLED VIA A NETWORK INPUT.
4. OUTSIDE AIR DAMPER
4.1. OUTSIDE AIR DAMPER SHALL BE OPEN WHEN RESPECTIVE AHU IS ON.
T
T
AI2
AI1
AI3
OUTSIDE AIR DAMPER (D-1) STATUSDI1
DI2
AO1
AO2
DO1 OUTSIDE AIR DAMPER (D-1)
CHILLED WATER CONTROL VALVE (V-1)
HOT WATER CONTROL VALVE (V-2)
DO2 SUPPLY FAN START/STOP
CHILLED WATER CONTROL VALVE (V-1)
HOT WATER CONTROL VALVE (V-2)
DISCHARGE AIR TEMPERATURE SENSOR (T-1)
AI4 ZONE TEMPERATURE SENSOR (T-2)
SUPPLY FAN STATUS
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
FAN COIL UNIT (TYP.) & EXHAUST
FAN (TYP.) CONTROL SCHEMATICS,
SEQUENCES & BALANCE SCHEDULES
2 WLP NMT
M2-201
EXHAUST
FAN
EXHAUST FAN STATUSDI1
EXHAUST FAN (7-EF#4) START/STOPDO1
DI1
DO1
PANEL
DDC CONTROL
SEQUENCE OF OPERATION: EXHAUST FAN (TYP.)
1. START/STOP CONTROL
1.1. FAN TO BE STARTED AND STOPPED BY A TIME SCHEDULE OF 24 HOURS A DAY (ADJ.).
2. ALARM
2.1. ALARM SHALL BE GENERATED WHEN STATUS DOES NOT MATCH COMMAND.
2ND FLOOR FAN COIL UNITS BALANCING SCHEDULE
QTY. FCU
PER ROOM
AREA SERVED
SUPPLIED BY
AHU
TOTAL
CFM
OA CFM
GPM
COOLING HEATING
2 201 2-AC-21 220 30 1.50 1.0
1 201C 2-AC-21 420 45 2.25 1.0
1 201B 2-AC-21 450 45 2.50 1.0
1 203 2-AC-21 200 30 1.50 1.0
1 203 2-AC-21 400 40 2.25 1.0
1 205 2-AC-21 150 20 0.75 0.75
1 206 2-AC-21 280 30 1.25 1.0
1 208 2-AC-21 240 30 1.25 0.75
1 209 2-AC-21 450 45 2.50 1.0
2 210 2-AC-21 570 40 3.50 1.0
2 210 2-AC-21 320 40 2.25 1.0
1 210 2-AC-21 250 40 1.25 1.0
1 212 2-AC-21 150 30 1.0 0.75
1 213 2-AC-21 150 30 1.0 0.75
1 214 2-AC-21 150 30 1.0 0.75
1 217 2-AC-21 560 90 4.0 1.0
1 217B 2-AC-21 840 90 5.75 0.75
1 217E 2-AC-21 560 90 4.0 1.0
1 217F 2-AC-21 560 90 4.0 1.0
1 POST DEPLOYMENT CLERK 2-AC-21 560 90 4.0 1.0
1 218 2-AC-21 80 20 0.75 0.50
1 219 2-AC-21 190 30 1.25 0.75
2 220 2-AC-21 450 50 3.25 1.0
2 211 2-AC-21 350 40 2.0 1.0
2 222 2-AC-21 250 40 1.25 1.0
1 226 2-AC-21 570 45 3.0 1.0
1 227 2-AC-21 350 40 2.0 1.0
1 228 2-AC-21 320 40 1.75 1.0
1 229 2-AC-21 270 40 1.25 1.0
1 230 2-AC-21 320 40 1.75 1.0
1 231 2-AC-21 340 40 1.75 1.0
1 232 2-AC-23 330 30 1.75 1.0
1 233 2-AC-23 325 30 1.75 1.0
1 234 2-AC-23 200 20 1.00 0.75
1 235 2-AC-23 300 40 1.50 1.0
1 236 2-AC-23 400 50 2.0 1.0
1 237 2-AC-23 80 20 0.75 0.50
1 237A 2-AC-23 200 30 1.25 1.0
2 238 2-AC-23 530 40 2.75 1.0
2 239 2-AC-23 530 40 2.75 1.0
1 240 2-AC-23 210 45 1.50 1.0
1 241A 2-AC-23 620 65 3.50 0.75
1 241 2-AC-23 840 120 6.70 1.0
1 242 2-AC-23 630 60 3.00 0.75
1 242B 2-AC-23 840 80 5.75 0.75
1 242C 2-AC-23 760 50 3.50 0.75
1 242D 2-AC-23 250 30 1.25 1.0
1 245 2-AC-23 90 30 0.75 0.50
1 246 2-AC-23 80 20 0.75 0.50
1 247 2-AC-23 80 20 1.25 0.50
4 248 2-AC-23 530 55 3.50 1.0
2 249 2-AC-23 270 40 1.50 1.0
1 250 2-AC-23 430 45 2.50 1.0
1 252 2-AC-21 200 20 1.25 0.75
1 254 2-AC-21 250 30 1.25 1.0
1 255 2-AC-21 170 25 1.0 0.75
1 256 2-AC-21 450 45 2.50 1.0
2ND FLOOR SOUTHEAST
CORRIDOR
2-AC-21 830 90 3.50 0.75
2ND FLOOR SOUTHWEST
CORRIDOR
2-AC-21 830 90 3.75 0.75
1 2ND FLOOR NORTH CORRIDOR 2-AC-23 830 80 3.50 0.75
OUTSIDE AIR
FROM AHU
3RD FLOOR FAN COIL UNITS BALANCING SCHEDULE
QTY. FCU
PER ROOM
AREA SERVED
SUPPLIED BY
AHU
TOTAL
CFM
OA CFM
GPM
COOLING HEATING
2 301 2-AC-21 300 40 2.25 1.0
1 301C 2-AC-21 450 45 2.50 1.0
1 301B 2-AC-21 540 60 2.50 1.0
2 303 2-AC-21 430 60 3.50 1.0
1 305 2-AC-21 150 20 0.75 0.75
1 306 2-AC-21 150 20 0.75 0.75
2 308 2-AC-21 280 35 1.50 1.0
1 309 2-AC-21 270 45 1.75 1.0
2 310 2-AC-21 550 50 3.0 1.0
2 311 2-AC-21 430 50 2.75 1.0
1 312 2-AC-21 130 45 0.75 0.75
1 313 2-AC-21 240 65 1.25 1.0
4 316 2-AC-21 750 90 5.25 0.75
1 316B 2-AC-21 840 90 6.70 0.75
1 319 2-AC-21 80 20 0.75 0.5
1 320 2-AC-21 240 65 1.25 1.0
1 321 2-AC-21 270 45 1.25 1.0
1 322 2-AC-21 460 45 2.75 1.0
1 323 2-AC-21 460 45 2.50 1.0
1 324 2-AC-21 270 45 1.25 1.0
1 325 2-AC-21 270 45 1.25 1.0
1 326 2-AC-21 230 30 1.25 1.0
1 329 2-AC-21 230 30 1.25 1.0
1 330 2-AC-21 270 45 1.25 1.0
1 331 2-AC-21 200 30 1.25 1.0
1 332 2-AC-21 270 30 1.0 1.0
2 333 2-AC-21 250 25 1.25 1.0
1 334 2-AC-23 750 60 3.50 0.75
1 335 2-AC-23 840 90 5.80 0.75
1 336 2-AC-23 300 30 1.50 1.0
1 337 2-AC-23 350 30 2.0 1.0
1 338 2-AC-23 310 30 1.0 1.0
3 339 2-AC-23 400 35 2.50 1.0
3 340 2-AC-23 320 35 2.0 1.0
2 341 2-AC-23 120 35 1.0 0.50
1 342 2-AC-23 550 50 2.50 1.0
1 342A 2-AC-23 840 240 6.70 0.75
4 343 2-AC-23 630 70 4.50 1.0
1 346 2-AC-23 150 20 0.75 0.5
1 347 2-AC-23 200 45 1.25 0.5
2 348 2-AC-23 450 50 3.0 1.0
2 349 2-AC-23 330 25 2.0 1.0
1 350 2-AC-23 280 45 1.25 0.75
1 351 2-AC-23 280 45 1.25 0.75
1 352 2-AC-23 280 45 1.25 0.75
1 353 2-AC-23 300 45 1.25 0.75
1 355 2-AC-23 220 30 1.0 0.75
1 357 2-AC-23 220 40 1.25 0.75
1 358 2-AC-23 180 20 1.0 0.50
1 359 2-AC-23 400 40 2.25 1.0
3RD FLOOR SOUTHEAST
CORRIDOR
2-AC-21 1000 80 6.70 0.75
3RD FLOOR SOUTHWEST
CORRIDOR
2-AC-21 1000 80 6.70 0.75
1 3RD FLOOR NORTH CORRIDOR 2-AC-23 1100 80 6.70 0.75
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
NORTH & SOUTH SCHWS CONTROL
SCHEMATICS & SEQUENCES
2 WLP NMT
M2-202
CHWS TO FCU'S
CHWR FROM FCU'S
STR
2-SCHWP3
2-SCHWP4
CHWS TO 2-AC-23
CHWR FROM 2-AC-23
CAMPUS
PRIMARY CHW
SUPPLY
CHWS TO INDUCTION UNITS
2-SCHWP6
CHWR FROM INDUCTION UNITS
CAMPUS PRIMARY
CHW RETURN
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING
DDC. TEMPERATURE SENSORS, VALVE
ACTUATORS, ETC. CAN BE REUSED IF
FUNCTIONAL AND COMPATIBLE.
2. CONTROLLERS ARE TO BE REPLACED.
3. SERVES NORTHSIDE OF BLDG 2, 2ND
AND 3RD FLOOR FCUS AND INDUCTION
UNITS.
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING DDC.
TEMPERATURE SENSORS, VALVE ACTUATORS, ETC.
CAN BE REUSED IF FUNCTIONAL AND COMPATIBLE.
2. CONTROLLERS ARE TO BE REPLACED. CONNECT NEW
CONTROLLERS TO EXISTING ELECTRICAL SERVICE.
3. SERVES SOUTHSIDE OF BLDG 2, 2ND AND 3RD FLOOR
FCUS AND INDUCTION UNITS.
2-VLV6-0
2-VLV4-0
SEQUENCE OF OPERATION
1. START/STOP CONTROLS
1.1. THE EXISTING CHILLED WATER SUPPLY FROM THE CENTRAL COOLING PLANT PROVIDES CHILLED WATER TO THE SECONDARY PUMPING SYSTEM FOR BUILDING 2. SYSTEM ENABLE SHALL BE CONTROLLED BY THE DDC SYSTEM.
1.2. WHEN THE SYSTEM IS ENABLED THE SECONDARY CHILLED WATER PUMPS SHALL BE COMMANDED "ON".
1.3. WHEN THE SYSTEM IS "OFF", THE SYSTEM SHALL BE DISABLED.
2. CHILLED WATER VALVE CONTROLS
2.1. THE VALVES SHALL MODULATE TO MAINTAIN THE DESIRED CHILLED WATER SUPPLY TEMPERATURE TO SETPOINT FOR EACH
SECTION. INITIAL SETTING WILL BE 60°F FOR THE INDUCTION UNITS SECTION.
3. CHILLED WATER PUMP CONTROLS
3.1. WHEN ENABLED, THE PUMPS WILL BE STARTED. IF THE PUMP STATUS DOES NOT MATCH THE COMMAND, AN ALARM SHALL BE GENERATED, AND THE PUMP SHALL BE STOPPED. THE PUMP SHALL AUTOMATICALLY RETRY TO START
3.2. 2-SCHWP4 VFD SHALL MODULATE TO MAINTAIN STATIC PRESSURE SETPOINT. STATIC PRESSURE SETPOINT SHALL BE RESET BASED
ON VALVE POSITION.
SEQUENCE OF OPERATION
1. START/STOP CONTROLS
1.1. THE EXISTING CHILLED WATER SUPPLY FROM THE CENTRAL COOLING PLANT PROVIDES CHILLED WATER TO THE SECONDARY PUMPING
SYSTEM FOR BUILDING 2. SYSTEM ENABLE SHALL BE CONTROLLED BY THE DDC SYSTEM.
1.2. WHEN THE SYSTEM IS ENABLED THE SECONDARY CHILLED WATER PUMPS SHALL BE COMMANDED "ON".
1.3. WHEN THE SYSTEM IS "OFF", THE SYSTEM SHALL BE DISABLED.
2. CHILLED WATER VALVE CONTROLS
2.1. THE VALVES SHALL MODULATE TO MAINTAIN THE DESIRED CHILLED WATER SUPPLY TEMPERATURE TO SETPOINT FOR EACH SECTION. INITIAL
SETTING WILL BE 60°F FOR THE INDUCTION UNITS SECTION.
3. CHILLED WATER PUMP CONTROLS
3.1. WHEN ENABLED, THE PUMPS WILL BE STARTED. IF THE PUMP STATUS DOES NOT MATCH THE COMMAND, AN ALARM SHALL BE GENERATED, AND THE PUMP SHALL BE STOPPED. THE PUMP SHALL AUTOMATICALLY RETRY TO START.
3.2. 2-SCHWP1 & 2-SCHWP2 VFD SHALL MODULATE TO MAINTAIN STATIC PRESSURE SETPOINT. STATIC PRESSURE SETPOINT SHALL BE RESET
BASED ON VALVE POSITION.
AI3
AO1 T
AI5
T
AI2 AI4
AO2 T
AI6
VFD
STR
DI2 DO2
DI3 DO3
DI1 DO1
AI2
AI1
AI3
AI4
AI6
AI5
INDUCTION UNITS CHWS CONTROL VALVE (2-VLV6-0)
FCU'S CHWS TEMPERATURE SENSOR
INDUCTION UNITS CHWS TEMPERATURE SENSOR
INDUCTION UNITS CHILLED WATER BYPASS TEMPERATURE SENSOR
DI1
CHILLED WATER PUMP (2-SCHWP4) STATUS
CHILLED WATER PUMP (2-SCHWP3) STATUS
DI2
CHILLED WATER PUMP (2-SCHWP6) STATUSDI3
DO1
DO2
CHILLED WATER PUMP (2-SCHWP3) START/STOP
CHILLED WATER PUMP (2-SCHWP4) START/STOP
AO1
AO2 INDUCTION UNITS CHWS CONTROL VALVE (2-VLV6-0)
DO3 CHILLED WATER PUMP (2-SCHWP5) START/STOP
CHWS TO FCU'S
CHWR FROM FCU'S
VFD
2-SCHWP1
2-SCHWP2
CHWS TO FCU'S AND AHU'S
CHWR FROM FCU'S AND AHU'S
CAMPUS
PRIMARY CHW
SUPPLY
CHWS TO INDUCTION UNITS
2-SCHWP5
CHWR FROM INDUCTION UNITS
CAMPUS PRIMARY
CHW RETURN
2-VLV5-0
2-VLV2-0
AI3
AO1 T
AI5
T
AI2 AI4
AO2 T
AI6
VFD
STR
DI2 DO2
DI3 DO3
DI1 DO1
AI2
AI1
AI3
AI4
AI6
AI5
2-SCHWP1 CHILLED WATER PUMP VFD STATUS
2-SCHWP1 CHILLED WATER PUMP DIFFERENTIAL PRESSURE SENSOR
INDUCTION UNITS CHWS CONTROL VALVE (2-VLV5-0)
FCU'S CHWS TEMPERATURE SENSOR
INDUCTION UNITS CHWS TEMPERATURE SENSOR
INDUCTION UNITS CHILLED WATER BYPASS TEMPERATURE SENSOR
DI1
CHILLED WATER PUMP (2-SCHWP2) STATUS
CHILLED WATER PUMP (2-SCHWP1) STATUS
DI2
CHILLED WATER PUMP (2-SCHWP5) STATUSDI3
DO1
DO2
CHILLED WATER PUMP (2-SCHWP1) START/STOP
CHILLED WATER PUMP (2-SCHWP2) START/STOP
AO1
AO2
2-SCHWP1 CHILLED WATER PUMP VFD SPEED
INDUCTION UNITS CHWS CONTROL VALVE (2-VLV5-0)
DO3 CHILLED WATER PUMP (2-SCHWP5) START/STOP
KEYNOTES:
DEMO CHILLED WATER BYPASS LINE AND
3-WAY CONTROL VALVE ON FCU CHILLED
WATER PUMP. CONNECT PUMP INLET TO
CAMPUS PRIMARY CHILLED WATER SUPPLY.
AI3
P
AI1 AO1
AI7 2-SCHWP-1 SYSTEM DIFFERENTIAL PRESSURE SETPOINT SENSOR
P AI7
INSTALL DIFFERENTIAL PRESSURE
SETPOINT SENSOR 2
3 DOWN LONGEST
RUN IN ATTIC MECH. RM.
AI8 AO3
P AI9
INSTALL DIFFERENTIAL PRESSURE
SETPOINT SENSOR 2
3 DOWN LONGEST
RUN IN ATTIC MECH. RM.
AI8 2-SCHWP-2 CHILLED WATER PUMP VFD STATUS
AI9 2-SCHWP-2 SYSTEM DIFFERENTIAL PRESSURE SETPOINT SENSOR
AO3 2-SCHWP2 CHILLED WATER PUMP VFD SPEED
KEYNOTES:
DEMO CHILLED WATER BYPASS LINE AND
3-WAY CONTROL VALVE ON FCU CHILLED
WATER PUMP. CONNECT PUMP INLET TO
CAMPUS PRIMARY CHILLED WATER SUPPLY.
AI1 AO1
2-SCHWP4 CHILLED WATER PUMP VFD SPEED
2-SCHWP4 CHILLED WATER PUMP VFD STATUS
P AI3
INSTALL DIFFERENTIAL PRESSURE
SETPOINT SENSOR 2
3 DOWN LONGEST
RUN IN ATTIC MECH. RM.
2-SCHWP-4 SYSTEM DIFFERENTIAL PRESSURE SETPOINT SENSOR
1. ALL CONTROL DEVICES ARE EXISTING DDC.
TEMPERATURE SENSORS, VALVE ACTUATORS, ETC. CAN
BE REUSED IF FUNCTIONAL AND COMPATIBLE.
2. CONTROLLERS ARE TO BE REPLACED.
3. SERVES SOUTHSIDE OF BLDG 2, 2ND AND 3RD FLOOR
FCU'S AND INDUCTION UNITS.
SEQUENCE OF OPERATION
1. START/STOP CONTROLS
1.1. THE HEATING SYSTEM SHALL AUTOMATICALLY START WHEN THE
OUTSIDE AIR TEMPERATURE FALLS BELOW THE SYSTEM ENABLE
SETPOINT.
1.2. WHEN THE SYSTEM IS "ON":
1.2.1. STEAM CONTROL VALVES SHALL MODULATE TO MAINTAIN THE
HOT WATER SUPPLY TEMPERATURE AT SETPOINT.
1.2.2. THE HOT WATER SUPPLY TEMPERATURE RESETS INVERSELY
WITH THE OUTDOOR TEMPERATURE AS SCHEDULED: AT 30°F OA,
HWS TEMPERATURE AT 180°F, AT 70°F OA, HWS TEMPERATURE
AT 140°F.
1.2.3. STEAM HOT WATER CONVERTERS, 2-HTX-1 & 2-HTX-2, ARE 100%
REDUNDANT AND ONLY ONE UNIT AT A TIME SHALL OPERATE.
1.2.4. HOT WATER PUMPS ARE CONTROLLED BY THE DDC SYSTEM. THE
PUMPS ARE 100% REDUNDANT REQUIRING ONLY ONE PUMP AT A
TIME TO OPERATE.
1.3. WHEN THE OUTSIDE AIR TEMPERATURE RISES ABOVE THE SYSTEM
ENABLE SETPOINT OR THE SYSTEM IS "OFF", THE HEATING SHALL BE
DISABLED.
2. HEAT EXCHANGER CONTROL
2.1. THIS SYSTEM CONSISTS OF TWO STEAM HEAT EXCHANGERS WITH 1
3 -
3 STEAM VALVES. AFTER THE FLOW THROUGH THE HEAT
EXCHANGER HAS BEEN CONFIRMED VIA THE FLOW SWITCH (FS-X),
THE 24VAC POWER SHALL BE APPLIED TO THE STEAM VALVE
ACTUATORS. THE TWO STEAM INLET VALVES WILL MODULATE IN
SEQUENCE TO MAINTAIN THE DESIRED HOT WATER SUPPLY
TEMPERATURE TO SETPOINT AS RESET BY THE OUTDOOR AIR
TEMPERATURE.
3. HOT WATER PUMP CONTROL
3.1. WHEN ENABLED, A PUMP SHALL BE STARTED. IF THE PUMP STATUS
DOES NOT MATCH THE COMMAND, AN ALARM SHALL BE GENERATED
AND THE LAG PUMP SHALL BE STARTED. LEAD/LAG STATUS SHALL BE
SWITCHED WEEKLY TO EQUALIZE RUNTIME.
SEQUENCE OF OPERATION
1. START/STOP CONTROLS
1.1. THE HEATING SYSTEM SHALL AUTOMATICALLY START WHEN THE
OUTSIDE AIR TEMPERATURE FALLS BELOW THE SYSTEM ENABLE
SETPOINT.
1.2. WHEN THE SYSTEM IS "ON":
1.2.1. STEAM CONTROL VALVES SHALL MODULATE TO MAINTAIN THE
HOT WATER SUPPLY TEMPERATURE AT SETPOINT.
1.2.2. THE HOT WATER SUPPLY TEMPERATURE RESETS INVERSELY
WITH THE OUTDOOR TEMPERATURE AS SCHEDULED: AT 30°F OA,
HWS TEMPERATURE AT 180°F, AT 70°F OA, HWS TEMPERATURE
AT 140°F.
1.2.3. STEAM HOT WATER CONVERTERS, 2-HTX-3 & 2-HTX-4, ARE 100%
REDUNDANT AND ONLY ONE UNIT AT A TIME SHALL OPERATE.
1.2.4. HOT WATER PUMPS ARE CONTROLLED BY THE DDC SYSTEM. THE
PUMPS ARE 100% REDUNDANT REQUIRING ONLY ONE PUMP AT A
TIME TO OPERATE.
1.3. WHEN THE OUTSIDE AIR TEMPERATURE RISES ABOVE THE SYSTEM
ENABLE SETPOINT OR THE SYSTEM IS "OFF", THE HEATING SHALL BE
DISABLED.
2. HEAT EXCHANGER CONTROL
2.1. THIS SYSTEM CONSISTS OF TWO STEAM HEAT EXCHANGERS WITH 1
3 -
3 STEAM VALVES. AFTER THE FLOW THROUGH THE HEAT
EXCHANGER HAS BEEN CONFIRMED VIA THE FLOW SWITCH, THE
24VAC POWER SHALL BE APPLIED TO THE STEAM VALVE ACTUATORS.
THE TWO STEAM INLET VALVES WILL MODULATE IN SEQUENCE TO
MAINTAIN THE DESIRED HOT WATER SUPPLY TEMPERATURE TO
SETPOINT AS RESET BY THE OUTDOOR AIR TEMPERATURE.
3. HOT WATER PUMP CONTROL
3.1. WHEN ENABLED, A PUMP SHALL BE STARTED. IF THE PUMP STATUS
DOES NOT MATCH THE COMMAND, AN ALARM SHALL BE GENERATED
AND THE LAG PUMP SHALL BE STARTED. LEAD/LAG STATUS SHALL BE
SWITCHED WEEKLY TO EQUALIZE RUNTIME.
STR
STEAM CONV.
T
AI7
HWR
HWS
STEAM
SUPPLY
STEAM
SUPPLY
180 160 140
HOT WATER SETPOINT
(DEG F)
OUTDOOR
AIR
TEMPERATURE
(DEG F)
HEATING HOT WATER RESET
SCHEDULE
T
T
STEAM CONV.
2-HTX-3 VALVE 2
3 VALVE OUTPUT
2-HTX-3 VALVE 1
3 VALVE OUTPUT
2-HTX-4 VALVE 2
3 VALVE OUTPUT
2-HTX-4 VALVE 1
3 VALVE OUTPUT
AI6
DI1
DI2
DI3
DO1
DI4
DO2
STR
AMBIENT AIR
TEMPERATURE SENSOR
INSTALLED ON NORTH
SIDE OF BUILDING
FS
FS
AI2
AO2
AI1
AO1
AI3
AO3
AI4
AO4
SENSOR (TYP)
TEMPERATURE
AI5
CAMPUS STEAM
CONDENSATE
RETURN
CAMPUS STEAM
CONDENSATE
RETURN
FLOW SWITCH
(TYP)
AI2
AI1
AI3
AI4
AI6
AI7
AI5
STEAM CONVERTER (2-HTX-3) VALVE 2 STATUS
STEAM CONVERTER (2-HTX-4) VALVE 2 STATUS
STEAM CONVERTER (2-HTX-4) VALVE 1 STATUS
HOT WATER SUPPLY TEMPERATURE SENSOR
HOT WATER RETURN TEMPERATURE SENSOR
AMBIENT AIR TEMPERATURE SENSOR
STEAM CONVERTER (2-HTX-3) VALVE 1 STATUS
DI4
DI3
DI1
STEAM CONVERTER (2-HTX-4) FLOW SWITCH STATUS
HOT WATER PUMP (2-HWP9) STATUS
HOT WATER PUMP (2-HWP10) STATUS
STEAM CONVERTER (2-HTX-3) FLOW SWITCH STATUS
DI2
DO1
DO2
HOT WATER PUMP (2-HWP9) START/STOP
HOT WATER PUMP (2-HWP10) START/STOP
AO1
AO2
STEAM CONVERTER (2-HTX-3) VALVE 2 CONTROLLER
STEAM CONVERTER (2-HTX-3) VALVE 1 CONTROLLER
AO3
AO4
STEAM CONVERTER (2-HTX-4) VALVE 2 CONTROLLER
STEAM CONVERTER (2-HTX-4) VALVE 1 CONTROLLER
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING DDC.
TEMPERATURE SENSORS, VALVE ACTUATORS, ETC. CAN
BE REUSED IF FUNCTIONAL AND COMPATIBLE.
2. CONTROLLERS ARE TO BE REPLACED.
3. SERVES NORTHSIDE OF BLDG 2, 2ND AND 3RD FLOOR
FCU'S AND INDUCTION UNITS.
STR
STEAM CONV.
T
AI7
HWR
HWS
STEAM
SUPPLY
STEAM
SUPPLY
180 160 140
HOT WATER SETPOINT
(DEG F)
OUTDOOR
AIR
TEMPERATURE
(DEG F)
HEATING HOT WATER RESET
SCHEDULE
T
T
STEAM CONV.
2-HTX-1 VALVE 2
3 VALVE OUTPUT
2-HTX-1 VALVE 1
3 VALVE OUTPUT
2-HTX-2 VALVE 2
3 VALVE OUTPUT
2-HTX-2 VALVE 1
3 VALVE OUTPUT
AI6
DI1
DI2
DI3
DO1
DI4
DO2
STR
AMBIENT AIR TEMPERATURE SENSOR
INSTALLED ON NORTH SIDE OF
BUILDING
FS
FS
AI2
AO2
AI1
AO1
AI3
AO3
AI4
AO4
SENSOR (TYP)
TEMPERATURE
AI5
CAMPUS STEAM
CONDENSATE
RETURN
CAMPUS STEAM
CONDENSATE
RETURN
AI2
AI1
AI3
AI4
AI6
AI7
AI5
STEAM CONVERTER (2-HTX-1) VALVE 2 STATUS
STEAM CONVERTER (2-HTX-2) VALVE 2 STATUS
STEAM CONVERTER (2-HTX-2) VALVE 1 STATUS
HOT WATER SUPPLY TEMPERATURE SENSOR
HOT WATER RETURN TEMPERATURE SENSOR
AMBIENT AIR TEMPERATURE SENSOR
STEAM CONVERTER (2-HTX-1) VALVE 1 STATUS
DI4
DI3
DI1
STEAM CONVERTER (2-HTX-2) FLOW SWITCH STATUS
HOT WATER PUMP (2-HWP7) STATUS
HOT WATER PUMP (2-HWP8) STATUS
STEAM CONVERTER (2-HTX-1) FLOW SWITCH STATUS
DI2
DO1
DO2
HOT WATER PUMP (2-HWP7) START/STOP
HOT WATER PUMP (2-HWP8) START/STOP
AO1
AO2
STEAM CONVERTER (2-HTX-1) VALVE 2 CONTROLLER
STEAM CONVERTER (2-HTX-1) VALVE 1 CONTROLLER
AO3
AO4
STEAM CONVERTER (2-HTX-2) VALVE 2 CONTROLLER
STEAM CONVERTER (2-HTX-2) VALVE 1 CONTROLLER
FLOW SWITCH
(TYP)
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
NORTH & SOUTH HEATING HOT
WATER SYSTEMS CONTROL
SCHEMATICS & SEQUENCES
2 WLP NMT
M2-203