36C25618U0323-0002003.pdf
PDF 2 MB Posted
- Attached to
- Services Commissioning for HVAC Digital Controls Federal contract opportunity
- Solicitation number
- 36C25618U0323
About this file
36C25618U0323 0002 Drawings - Building 16 (M16 Series).pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| -15380.docx | DOCX document | |
| 36C25618U0323-0002008.pdf | ||
| 36C25618U0323-0002007.pdf | ||
| 36C25618U0323-0002005.pdf | ||
| 36C25618U0323-0002011.pdf | ||
| 36C25618U0323-0002009.pdf | ||
| 36C25618U0323-0002014.pdf | ||
| 36C25618U0323-0002001.docx | DOCX document | |
| 36C25618U0323-0002004.pdf | ||
| 36C25618U0323-0002006.pdf | ||
| 36C25618U0323-0002012.pdf | ||
| 36C25618U0323-0002000.docx | DOCX document | |
| 36C25618U0323-0002013.pdf | ||
| 36C25618U0323-0002010.pdf | ||
| 36C25618U0323-0002002.pdf | ||
| 36C25618U0323-0001000.docx | DOCX document | |
| 36C25618U0323-001.docx | DOCX document | |
| 36C25618U0323-002.pdf | ||
| 36C25618U0323-000.docx | DOCX document |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXIST INCOMING
DOMESTIC WATER
METER
EXIST INCOMING
DOMESTIC WATER
METER
EXIST STEAM
FLOW METER
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
BASEMENT FLOOR PLAN -
MECHANICAL
16 WLP NMT
M16-100 10-30-13
M
EXIST EUH#1
EXIST POWER METER REMOTE NETWORK
DISPLAY PANEL. INTEGRATE INTO CAMPUS
CONTROLS.
EXIST HVAC DDC
EXIST EF#16-3, BTM AT 6' A.F.F.
EXIST CHWP#16-2EXIST CHWP#16-1
EXIST MOTORIZED
DAMPER INTERLOCKED
TO EXIST EF#16-3.
T
T H
T H
T H
EXIST EF#16-1
MOUNTED ON WALL
EXIST EF#16-2
ABOVE ON ROOF
EXIST DDC NATURAL GAS METER REMOTE
NETWORK DISPLAY PANEL. INTEGRATE
INTO CAMPUS CONTROL SYSTEM.
EXIST DDC WATER METER
REMOTE NETWORK
DISPLAY PANEL.
INTEGRATE INTO CAMPUS
CONTROL SYSTEM.
EXIST HVAC DDC NETWORK
PANELS
EXIST PTAC TO REMAIN ON
UNIT MOUNTED CONTROLS.
EXIST DDC WATER METER
REMOTE NETWORK
DISPLAY PANEL.
INTEGRATE INTO CAMPUS
CONTROLS SYSTEM.
EXIST AHU#16-1
ABOVE ON ROOF
ABOVE.
EXIST AHU#16-3
ABOVE ON ROOF
ABOVE.
EXIST AHU#16-2
ABOVE ON ROOF
ABOVE.
EXIST CHILLER#16-1
EXIST GAS METER
EXIST ELECT. POWER
MONITORING SYSTEM
CONNECT TO HVAC DDC
CONTROLS
EXIST ELECT. POWER
MONITORING SYSTEM
CONNECTED TO HVAC DDC
CONTROLS
NOTES:
1. EXISTING DDC SYSTEM IS JCI. REPLACE CONTROLLERS TO
FULLY INTEGRATE TO CAMPUS SIEMENS SYSTEM.
2. INTEGRATE ALL EXISTING METERS EVEN IF THEY ARE
REDUNDANT.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
1ST FLOOR PLAN - MECHANICAL
16 WLP NMT
M16-101
ZONE THERMOSTAT/HUMIDITY SENSOR
OUTSIDE AIR
DPS-1
T/H-1
L P
S
V-1NO
STR
DI5
DO3
AI1
AO1
DI4DI2DI1
DO1
AI6
AI7
AO4
PANEL
DDC CONTROL
AIR FILTER
T-1
NC
D-1
TD-2
NO
T/H
C W
R
V-2
AI2
AO2
L P
S
V-3NC
AI3
AO3
DI6
T-2
AI4
T-3 SUPPLY AIR
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING DDC. SENSORS,
ACTUATORS, ETC MAY BE REUSED IF FUNCTIONAL AND
COMPATIBLE.
2. PROVIDE NEW CONTROLLER AND SPACE
TEMPERATURE/HUMIDITY SENSOR.
3. EF16-1 & EF16-2 ARE INTERLOCKED WITH AHU16-01.
4. CONNECT NEW CONTROLLER TO EXISTING ELECTRICAL
SERVICE.
NC
AI5
SEQUENCE OF OPERATION
1. SUPPLY FAN START/STOP
1.1 THE SUPPLY FAN SHALL BE STARTED ACCORDING TO THE SCHEDULE. AFTER THE START COMMAND IS SENT, OUTSIDE AIR DAMPER, D-1, SHALL OPEN AND UNIT SHALL START WHEN DAMPER END SWITCH HAS PROVEN OPEN STATUS. IF THE SUPPLY FAN STATUS DOES NOT MATCH THE COMMANDED VALUE, AN ALARM SHALL BE GENERATED. WHEN THE SUPPLY FAN STATUS INDICATES THE FAN STARTED, THE
CONTROL SEQUENCE SHALL BE ENABLED.
2. SUPPLY AIR TEMPERATURE CONTROL
2.1 THE SUPPLY AIR SETPOINT SHALL RESET AS NECESSARY TO MAINTAIN THE ZONE TEMPERATURE SETPOINT AS SENSED BY THE ZONE TEMPERATURE SENSOR, T/H-1. THE PREHEAT FACE & BYPASS, PREHEAT VALVE, REHEAT VALVE, & COOLING VALVE SHALL MODULATE IN SEQUENCE TO MAINTAIN
THE SUPPLY AIR TEMPERATURE AT SETPOINT.
2.2 WHENEVER THE OUTSIDE AIR TEMPERATURE IS GREATER THAN 40°F, THE PREHEAT DISCHARGE SENSOR SHALL MODULATE THE STEAM PREHEAT VALVE TO MAINTAIN DISCHARGE AIR TEMPERATURE SETPOINT AND FACE AND BYPASS DAMPER SHALL BE OPEN TO COIL FACE. WHENEVER THE OUTSIDE AIR IS LESS THAN 40°F, PREHEAT COIL WILL OPEN AND FACE AND BYPASS DAMPERS MODULATE TO
MAINTAIN DISCHARGE AIR SETPOINT.
3. DEHUMIDIFICATION CONTROL
3.1 IF THE RETURN AIR DEWPOINT IN THE ZONE RISES ABOVE SETPOINT OF 55°F, THE CHILLED WATER VALVE, V-2, SHALL MODULATE OPEN TO MAINTAIN DEHUMIDIFICATION SETPOINT. THE REHEAT VALVE
SHALL MODULATE TO MAINTAIN SUPPLY AIR TEMPERATURE AT SETPOINT.
4. NIGHT SETBACK / NIGHT SETUP
4.1 IN UNOCCUPIED MODE, UNIT WILL CYCLE AS NECESSARY TO MAINTAIN THE NIGHT SETBACK ZONE TEMPERATURE AT SETPOINT. A DIFFERENTIAL PREVENTS THE UNIT FROM CYCLING EXCESSIVELY.
5. SAFETY
5.1 ALL SAFETY DEVICES SHALL HAVE STATUS ALARMS THAT ARE MONITORED AT THE ECC. ALL OF THE SAFETY DEVICES ARE MANUAL RESET. THE DEVICE THAT HAS TRIPPED MUST BE MANUALLY RESET
BEFORE RESTARTING THE AHU.
5.2 IF A TEMPERATURE LOW LIMIT SWITCH, T-1, SENSES A TEMPERATURE BELOW SETPOINT, THE SUPPLY
FAN SHALL BE SHUTDOWN.
5.3 IF A TEMPERATURE HIGH LIMIT SWITCH, T-2, SENSES A TEMPERATURE ABOVE SETPOINT, THE SUPPLY
FAN SHALL BE SHUTDOWN.
6. SHUTDOWN
6.1 WHEN THE UNIT IS SHUTDOWN BY EITHER A STOP COMMAND OR SYSTEM SAFETY, THE UNIT SHALL BE
SET AS FOLLOWS:
SUPPLY FAN SHALL BE OFF
OUTSIDE DAMPER, D-1, SHALL CLOSE
PREHEAT FACE & BYPASS REMAIN IN CONTROLS
PREHEAT VALVE SHALL REMAIN IN CONTROL
COOLING VALVE SHALL CLOSE
REHEAT VALVE SHALL CLOSE
T T
SUPPLY
FAN
STEAM
REHEAT
COIL
CLG
COIL
STEAM
PREHEAT
COIL
STEAM PREHEAT CONTROL VALVE (V-1)
COOLING CONTROL VALVE (V-2)AI2
AI1
AI4
AI5
AI6
STEAM REHEAT CONTROL VALVE (V-3)AI3
DISCHARGE AIR TEMPERATURE SENSOR (T-3)
ZONE TEMPERATURE SENSOR (T/H-1)
ZONE HUMIDITY SENSOR (T/H-1)
NOT USED
DI1
LOW LIMIT TEMPERATURE SENSOR (T-1) STATUS
SUPPLY FAN STATUS
OUTSIDE AIR DAMPER (D-1) STATUS
DI2 FILTER STATUS (DPS-1)
DI3
DI4
DI5
DI6 HIGH LIMIT TEMPERATURE SENSOR (T-2) STATUS
DO2
DO1
AO1
AO2
AO3 STEAM REHEAT CONTROL VALVE (V-3)
OUTSIDE AIR DAMPER (D-1) CONTROLLER
NOT USED
STEAM PREHEAT CONTROL VALVE (V-1)
COOLING CONTROL VALVE (V-2)
SUPPLY FAN START/STOPDO3
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
AHU#16-1 CONTROL SCHEMATIC,
SEQUENCE, & BALANCE SCHEDULE
16 WLP NMT
M16-200
AO4 PREHEAT FACE AND BYPASS DAMPER (D-2) CONTROLLER
AI7 PREHEAT FACE AND BYPASS DAMPER (D-2) STATUS
AIR HANDLING UNITS BALANCING SCHEDULE
LABEL AREA SERVED
SUPPLY
CFM
OA CFM
COOLING
COIL GPM
PREHEAT
COIL LBS/HR
REHEAT
COIL LBS/HR
AHU#16-1
LAUNDRY - DIRTY
AREA
13000 13000 177 520 737
AHU#16-2
LAUNDRY - CLEAN
AREA
15500 6000 131 495 794
AHU#16-3
LAUNDRY - CLEAN
AREA
15500 6000 131 495 794
OUTSIDE AIR
DPS-1
L P
S
V-1NO
VFD
DI7
DO4
AI2
AO1
DI6DI3DI1
DO1
AI8
AI9
AO5
NC
PANEL
DDC CONTROL
AIR FILTER
T-2
NC
D-1
D-3
NO
C W
R
V-2
AI3
AO2
L P
S
V-3NC
AI4
AO3
DI8
T-3
AI6
T-4
SUPPLY AIR
SD-1
DI4
DI2
DO2
NO
D-2
T
AI1
T-1 SD-2
DI9
AI7
SEQUENCE OF OPERATION
1. SUPPLY FAN START/STOP
1.1 THE SUPPLY FAN SHALL BE STARTED ACCORDING TO THE SCHEDULE. AFTER THE START COMMAND IS SENT, OUTSIDE AIR DAMPER, D-1, SHALL OPEN AND UNIT SHALL START WHEN DAMPER END SWITCH HAS PROVEN OPEN STATUS. IF THE SUPPLY FAN STATUS DOES NOT MATCH THE COMMANDED VALUE, AN ALARM SHALL BE GENERATED. WHEN THE SUPPLY FAN STATUS INDICATES THE FAN STARTED, THE CONTROL
SEQUENCE SHALL BE ENABLED.
2. SUPPLY AIR TEMPERATURE CONTROL
2.1 THE SUPPLY AIR SETPOINT SHALL RESET AS NECESSARY TO MAINTAIN THE ZONE TEMPERATURE SETPOINT AS SENSED BY THE ZONE TEMPERATURE SENSOR, T/H-1. THE PREHEAT FACE & BYPASS, PREHEAT VALVE, REHEAT VALVE, & COOLING VALVE SHALL MODULATE IN
SEQUENCE TO MAINTAIN THE SUPPLY AIR TEMPERATURE AT SETPOINT.
2.2 WHENEVER THE OUTSIDE AIR TEMPERATURE IS GREATER THAN 40°F, THE PREHEAT DISCHARGE SENSOR SHALL MODULATE THE STEAM PREHEAT VALVE TO MAINTAIN DISCHARGE AIR TEMPERATURE SETPOINT AND FACE AND BYPASS DAMPER SHALL BE OPEN TO COIL FACE. WHENEVER THE OUTSIDE AIR IS LESS THAN 40°F, PREHEAT COIL WILL OPEN AND FACE AND BYPASS DAMPERS MODULATE TO MAINTAIN DISCHARGE AIR
SETPOINT.
3. DEHUMIDIFICATION CONTROL
3.1 IF THE RETURN AIR DEWPOINT IN THE ZONE RISES ABOVE SETPOINT OF 55°F, THE CHILLED WATER VALVE, V-2, SHALL MODULATE OPEN TO MAINTAIN DEHUMIDIFICATION SETPOINT. THE REHEAT VALVE SHALL MODULATE TO MAINTAIN SUPPLY AIR TEMPERATURE AT SETPOINT.
4. ECONOMIZER CONTROL
4.1 ECONOMIZER IS ENABLED WHEN OUTSIDE AIR TEMPERATURE IS BELOW 65°F AND OA ENTHALPY IS BELOW RA ENTHALPY.
4.2 WHEN OA TEMPERATURE IS BETWEEN 65°F AND 55° RA DAMPER SHALL CLOSE AND OA DAMPER SHALL FULLY OPEN.
4.3 WHEN OA TEMPERATURE IS BELOW 55°F THE RETURN AIR DAMPER AND OUTSIDE AIR DAMPER SHALL MODULATE TO MAINTAIN THE MIXED AIR
TEMPERATURE SETPOINT.
5. NIGHT SETBACK / NIGHT SETUP
5.1 IN UNOCCUPIED MODE, UNIT WILL CYCLE AS NECESSARY TO MAINTAIN THE NIGHT SETBACK ZONE TEMPERATURE AT SETPOINT. A DIFFERENTIAL
PREVENTS THE UNIT FROM CYCLING EXCESSIVELY.
6. SAFETY
6.1 ALL SAFETY DEVICES SHALL HAVE STATUS ALARMS THAT ARE MONITORED AT THE ECC. ALL OF THE SAFETY DEVICES ARE MANUAL RESET. THE
DEVICE THAT HAS TRIPPED MUST BE MANUALLY RESET BEFORE RESTARTING THE AHU.
6.2 IF A TEMPERATURE LOW LIMIT SWITCH, T-2, SENSES A TEMPERATURE BELOW SETPOINT, THE SUPPLY FAN SHALL BE SHUTDOWN.
6.3 IF A TEMPERATURE HIGH LIMIT SWITCH, T-3, SENSES A TEMPERATURE ABOVE SETPOINT, THE SUPPLY FAN SHALL BE SHUTDOWN.
7. SHUTDOWN
7.1 WHEN THE UNIT IS SHUTDOWN BY EITHER A STOP COMMAND OR SYSTEM SAFETY, THE UNIT SHALL BE SET AS FOLLOWS:
SUPPLY FAN SHALL BE OFF
OUTSIDE DAMPER, D-1, SHALL CLOSE
PREHEAT FACE & BYPASS REMAIN IN CONTROLS
PREHEAT VALVE SHALL REMAIN IN CONTROL
COOLING VALVE SHALL CLOSE
REHEAT VALVE SHALL CLOSE
AI5
AO4
KEYNOTES:
EXISTING DDC DEVICE TO BE REUSED IF
FUNCTIONAL AND COMPATIBLE.
NEW DDC DEVICE TO BE INSTALLED.
COORDINATE EXACT LOCATION, SIZE,
TYPE, ETC. WITH EXISTING CONDITIONS
PRIOR TO PURCHASING.
PROVIDE NEW DDC CONTROLLER.
CONNECT NEW CONTROLLER TO
EXISTING ELECTRICAL SERVICE.
1 1 1 1 1
1 1 1
ZONE THERMOSTAT/HUMIDITY SENSOR
T/H-1T/H
T T T
MIXED AIR TEMPERATURE SENSOR (T-1)
STEAM PREHEAT CONTROL VALVE (V-1)AI2
AI1
AI4
AI5
AI6
COOLING CONTROL VALVE (V-2)AI3
STEAM REHEAT CONTROL VALVE (V-3)
SUPPLY FAN VFD STATUS
DISCHARGE AIR TEMPERATURE SENSOR (T-4)
FILTER STATUS (DPS-1)
DI1
RETURN AIR SMOKE DETECTOR (SD-1) STATUS
FACE DAMPER (D-3) STATUS
OUTSIDE AIR DAMPER (D-1) STATUS
DI2 RETURN AIR DAMPER (D-2) STATUS
DI3
DI4
DI5
DI6 LOW LIMIT TEMPERATURE SENSOR (T-2) STATUS
DO2
DO1
AO1
AO2
AO3 STEAM REHEAT CONTROL VALVE (V-3)
OUTSIDE AIR DAMPER (D-1) CONTROLLER
RETURN AIR DAMPER (D-2) CONTROLLER
STEAM PREHEAT CONTROL VALVE (V-1)
COOLING CONTROL VALVE (V-2)
NOT USEDDO3
AI7
AI8
ZONE TEMPERATURE SENSOR (T/H-1)
ZONE HUMIDITY SENSOR (T/H-1)
SUPPLY
FAN
STEAM
REHEAT
COIL
CLG
COIL
STEAM
PREHEAT
COIL
SUPPLY FAN STATUSDI7
DI8 HIGH LIMIT TEMPERATURE SENSOR (T-3) STATUS
DI9 SUPPLY AIR SMOKE DETECTOR (SD-2) STATUS
AO4 SUPPLY FAN VFD SPEED
SUPPLY FAN START/STOPDO4
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
AHU#16-2 & AHU#16-3 CONTROL
SCHEMATIC & SEQUENCE
16 WLP NMT
M16-201
AO5 PREHEAT FACE AND BYPASS DAMPER (D-3) CONTROLLER
AI9 PREHEAT FACE AND BYPASS DAMPER (D-3) STATUS
STR
CHWP#16-1
CHWP#16-2
CHWR
ZONE THERMOSTAT
NOTES:
1. PROVIDE NEW CONTROLLER AND
SPACE THERMOSAT.
OUTSIDE TEMPERATURE/HUMIDITY SENSOR
LOCATED IN THE SHADE ON THE NORTH SIDE OF
THE BUILDING
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING
DDC. SENSORS MAY BE REUSED IF
FUNCTIONAL AND COMPATIBLE.
2. PROVIDE NEW CONTROLLER.
CONNECT TO EXISTING ELECTRICAL
SERVICES.
3. CHILLER HAS INTERNAL CONTROLS.
SEQUENCE OF OPERATION
1. OCCUPIED MODE
1.1 DURING THIS MODE, THE FAN AND ELECTRIC HEATING COIL WILL BE
ENERGIZED AS NEEDED TO MAINTAIN ZONE HEATING TEMPERATURE
SETPOINT.
2. UNOCCUPIED MODE
2.1 DURING THIS MODE, THE FAN AND HEATING COIL WILL BE DE-ENERGIZED.
3. ALARMS.
3.1 ALARM SHALL BE GENERATED WHEN STATUS DOES NOT MATCH
COMMAND.
SEQUENCE OF OPERATION
1. CHILLED WATER PUMP CONTROL
1.1 THE CHILLED WATER SYSTEM INCLUDING PUMPS SHALL BE ENABLED WHEN ANY AIR HANDLING UNIT IS ON.
1.2 THE LEAD CHILLED WATER PUMP SHALL AUTOMATICALLY START WHEN THE OUTSIDE AIR TEMPERATURE RISES ABOVE THE SYSTEM ENABLE SETPOINT. WHEN THE OUTSIDE AIR TEMPERATURE FALLS BELOW THIS SETPOINT, THE CHILLED WATER
PUMP SHALL TURN OFF.
1.3 WHEN ENABLED, THE LEAD PUMP SHALL START AND RUN CONTINUOUSLY. IF FOR ANY REASON ITS STATUS DOES NOT MATCH ITS COMMANDED VALUE, AN ALARM WILL BE GENERATED. THE LAG PUMP (100% REDUNDANT) WILL START OF THE LEAD
PUMP IS IN ALARM.
1.4 EACH PUMP'S OPERATIONS DUTY SHALL BE ROTATED BETWEEN LEAD & LAG POSITION TO ALLOW FOR EQUAL RUN-TIME PER
PUMP.
2. CHILLER CONTROL
2.1 THE CHILLER SHALL BE ENABLED WHEN THE OUTSIDE AIR TEMPERATURE RISES ABOVE THE SYSTEM ENABLE SETPOINT AND THE CHILLED WATER PUMP HAS A STATUS OF ON. THE CHILLER VIA ITS INTERAL CONTROLS SHALL MAINTAIN THE CHILLED WATER SUPPLY TEMPERATURE SETPOINT. IF THE CHILLED WATER SUPPLY TEMPERATURE RISES ABOVE THE HIGH LIMIT
SETPOINT AFTER OPERATING FOR A PERIOD OF TIME, AN ALARM WILL BE GENERATED.
3. FREEZE PROTECTION
3.1 WHENEVER OUTSIDE AIR TEMPERATURE REACHES 40°F (ADJUSTABLE) OR BELOW, THE LEAD CHILLED WATER PUMP SHALL BE
STARTED.
T/H-1
AI4
T/H
AI3
T
T
T-1T
AI1
ZONE TEMPERATURE SENSOR (T-1)AI1
CHILLED WATER SUPPLY TEMPERATURE SENSOR
CHILLED WATER RETURN TEMPERATURE SENSORAI2
AI1
AI4
OUTSIDE TEMPERATURE SENSOR (T/H-1)AI3
OUTSIDE HUMIDITY SENSOR (T/H-1)
CHILLED WATER PUMP (16-CHWP2) STATUS
DI1 CHILLER#16-1 STATUS
DI2 CHILLED WATER PUMP (16-CHWP1) STATUS
DI3
DO2
DO1 CHILLER#16-1 START/STOP
CHILLED WATER PUMP (CHWP#16-1) START/STOP
CHILLED WATER PUMP (CHWP#16-2) START/STOPDO3
DI2
DO2
DI3
DO3
DI1
DO1
AI1
AI2
STR
CHWS
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
ELECTRIC HEATING COIL UNIT &
CHILLED WATER SYSTEM CONTROL
SCHEMATIC & SEQUENCE
16 WLP NMT
M16-202
AI2
AO1
UNIT STATUSAI2
UNIT START/STOPAO1
DO1
DI1
EF#16-1
EF#16-2
RM 101
DO1
DI1
EF#16-3
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING DDC
AND ARE TO BE REUSED IF FUNCTIONAL AND
COMPATIBLE.
2. EF#16-1 IS LOCATED ON NORTHEAST OUTSIDE
WALL BY WASHER AREA, RM 101.
3. EF#16-2 IS LOCATED ON THE WESTERN SIDE
OF THE ROOF ABOVE WASHER AREA, RM 101.
4. POINTS ARE CONNECTED IN AHU#16-1 PANEL.
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING
DDC AND ARE TO BE REUSED IF
FUNCTIONAL AND COMPATIBLE.
2. POINTS ARE CONNECTED IN AHU#16-1
PANEL.
THERMOSTAT
T-1
AI1
SEQUENCE OF OPERATION
1. EXHAUST FAN START/STOP
1.1 EACH FAN SHALL BE INTERLOCKED TO OPERATE WHILE AHU#16-1 IS IN
OPERATION. DDC CONTROLS SHALL MONITOR FAN STATUS AND ALARM
WHEN EF#16-1 & EF#16-2 ARE NOT IN OPERATION. FAN TOTAL RUN TIME
SHALL BE MONITORED.
SEQUENCE OF OPERATION
1. EXHAUST FAN START/STOP
1.1 EF#16-3 SHALL BE START/STOPPED VIA ROOM THERMOSTAT TO CYCLE
FAN TO MAINTAIN ROOM TEMPERATURE (ADJUSTABLE). DDC
CONTROLS SHALL MONITOR FAN STATUS INDICATION WITH ALARM AND
FAN TOTAL RUN TIME.
DI1 EXHAUST FAN STATUS
DO1 EXHAUST FAN START/STOP
T
THERMOSTAT TEMPERATURE SENSOR (T-1)AI1
DI1 EXHAUST FAN STATUS
DO1 EXHAUST FAN START/STOP
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
EF#16-1, EF#16-2 & EF#16-3 CONTROL
SCHEMATICS & SEQUENCES
16 WLP NMT
M16-203