- Services Commissioning for HVAC Digital Controls Federal contract opportunity
- Solicitation number
- 36C25618U0323
About this file
36C25618U0323 0002 Drawings - Buildings 46 _ 49 (M46 _ M49 Series).pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| -15380.docx | DOCX document | |
| 36C25618U0323-0002007.pdf | ||
| 36C25618U0323-0002005.pdf | ||
| 36C25618U0323-0002004.pdf | ||
| 36C25618U0323-0002006.pdf | ||
| 36C25618U0323-0002012.pdf | ||
| 36C25618U0323-0002000.docx | DOCX document | |
| 36C25618U0323-0002013.pdf | ||
| 36C25618U0323-0002002.pdf | ||
| 36C25618U0323-0002011.pdf | ||
| 36C25618U0323-0002009.pdf | ||
| 36C25618U0323-0002014.pdf | ||
| 36C25618U0323-0002001.docx | DOCX document | |
| 36C25618U0323-0002003.pdf | ||
| 36C25618U0323-0002008.pdf | ||
| 36C25618U0323-0001000.docx | DOCX document | |
| 36C25618U0323-002.pdf | ||
| 36C25618U0323-001.docx | DOCX document | |
| 36C25618U0323-000.docx | DOCX document |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
FLOOR PLANS - MECHANICAL
46 WLP NMT
M46-101 10-30-13
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
MIXED AIR TEMPERATURE SENSOR (T-1)
CHILLED WATER CONTROL VALVE (V-1)AI2
AI1
REHEAT HOT WATER CONTROL VALVE (V-2)AI3
SUPPLY FAN VFD STATUSAI4
DI4
DI2
DI3
DI1
FILTER STATUS (DPS-1)
LOW LIMIT TEMPERATURE SENSOR (T-2) STATUS
SUPPLY FAN STATUS
MIXED AIR SMOKE DETECTOR (SD-1) STATUS
SUPPLY
VFD
FAN
DO1
DI4
COIL
C H
W R
V-1
CLG
AI2
AO1
PANEL
DDC CONTROL
AI1
T-1OUTSIDE AIR
RETURN AIR
H W
R
COIL
HTG
V-2
AI3
AO2
DI3
T-2
DI1
SD-1
2 3
TT
AIR
FILTER
DPS-1
DI2
KEYNOTES:
EXISTING DDC DEVICE TO BE REUSED IF FUNCTIONAL AND COMPATIBLE.
EXISTING PNEUMATIC DEVICE TO BE REPLACED.
INSTALL NEW DDC DEVICE.
PROVIDE NEW DDC CONTROLLER. CONNECT NEW CONTROLLER TO
EXISTING ELECTRICAL SERVICE.
CHILLED WATER CONTROL VALVE (V-1)
HEATING HOT WATER CONTROL VALVE (V-2)
AO1
AO2
AO3
DO1
SUPPLY FAN VFD SPEED
SUPPLY FAN START/STOP
46AC-2 CONTROL SCHEMATIC &
SEQUENCE & BALANCE SCHEDULE
46 WLP NMT
M46-200
SEQUENCE OF OPERATION
1. GENERAL
1.1. AIR UNIT FAN TO BE STARTED AND STOPPED AS SCHEDULED BY THE ECC.
2. TEMPERATURE CONTROL
2.1. COOLING SPACE TEMPERATURE SETPOINT OF EACH ZONE SHALL BE MAINTAINED A 74°F (ADJ). CHILLED WATER VALVE, V-1, SHALL MODULATE TO MAINTAIN AHU LEAVING AIR TEMP OF 55°F (ADJ) AND FAN VFD SHALL MODULATE TO MAINTAIN ONE ZONE REHEAT COIL HOT WATER VALVE CLOSED. ONCE VFD SPEED REACHES MIN SPEED OF 30% (ADJ), CHILLED WATER VALVE, V-1, SHALL MODULATE TO MAINTAIN CRITICAL ZONE SPACE TEMPERATURE SETPOINT WITH RESPECTIVE ZONE HOT WATER VALVE CLOSED.
2.2. HEATING SPACE TEMPERATURE SETPOINT OF EACH ZONE SHALL BE MAINTAINED AT 70°F (ADJ). WHEN ALL ZONES ARE CALLING FOR HEAT REHEAT VALVE, V-2, SHALL MODULATE TO MAINTAIN AHU LEAVING AIR TEMP OF 95°F (ADJ) AND FAN VFD SHALL MODULATE TO MAINTAIN ONE ZONE REHEAT COIL HOT WATER VALVE CLOSED. ONCE VFD SPEED REACHES MIN SPEED OF 30% (ADJ), REHEAT VALVE, V-2 SHALL MODULATE TO MAINTAIN CRITICAL AHU LEAVING AIR TEMP OF 70° UNITL ANY ZONE FALLS BELOW HEATING SPACE TEMPERATURE SETPOINT MINUS 2°F AT WHICH POINT AHU LEAVING AIR TEMP SHALL
RETURN TO 95°F.
3. ALARMS
3.1. THE UNIT AIR FAN SHALL BE DE-ENERGIZED ON A DROP IN COOLING COIL ENTERING AIR TEMPERATURE BELOW THE 35°F SETPOINT OF T-2 OR UPON DETECTION OF IONIZED PARTICLES BY SD-1 OR SD-2.
3.2. A SEPARATE ALARM SHALL BE INITIATED FOR EACH SAFETY. LIKEWISE, A SMOKE DETECTION ALARM
SHALL INITIATED, BY CONTRACT CLOSURE, TO THE FIRE ALARM SYSTEM PANEL.
3.3. THE PRE-FILTER STATUS IS SENSED AT DPS-1. SHOULD THE DROP ACROSS THE FILTER EXCEED 1.5", THE SWITCH SHALL CLOSE AND INITIATE AN ALARM TO THE ECC.
3.4. WHEN THE AIR UNIT FAN IS DE-ENERGIZED FOR ANY REASON, THE AIR UNIT CONTROL VALVES SHALL
RETURN TO THEIR NORMAL POSITIONS.
4. UNOCCUPIED MODE
4.1. DURING UNSCHEDULED PERIODS, THE AIR UNIT FAN SHALL BE DE-ENERGIZED AND ALL CONTROLS AND
CONTROL VALVES SHALL RETURN TO THEIR NORMAL POSITIONS.
SUPPLY TO ZONE
REHEAT COILS
AI5
T-3
T
SUPPLY AIR TEMPERATURE SENSOR (T-3)AI5
DI5 SUPPLY AIR SMOKE DETECTOR (SD-1) STATUS
AO3
AI4
DI5
SD-2
AIR HANDLING UNITS BALANCING SCHEDULE
LABEL AREA SERVED
SUPPLY
CFM
OA CFM
COOLING
COIL GPM
REHEAT
COIL
LBS/HR
46AC-1 OFFICES & VEST. 3845 215 16.8 4.4
46AC-2 CHAPEL-NAVE 6950 100 34.1 8.3
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
MIXED AIR TEMPERATURE SENSOR (T-1)
MIXED AIR HUMIDITY SENSOR (H-1)AI2
AI1
CHILLED WATER CONTROL VALVE (V-1)AI3
HEATING HOT WATER CONTROL VALVE (V-2)AI4
AI5 SUPPLY FAN VFD STATUS
DI4
DI2
DI3
DI1
DI5
LOW LIMIT TEMPERATURE SENSOR (T-2) STATUS
FILTER STATUS (DPS-1)
SUPPLY FAN STATUS
SUPPLY DISCHARGE AIR SMOKE DETECTOR (SD-2) STATUS
MIXED AIR SMOKE DETECTOR (SD-1) STATUS
SUPPLY
VFD
FAN
AO3
AI5
COIL
C H
W R
V-1
CLG
AI3
AO1
SUPPLY
PANEL
DDC CONTROL
AI1
T-1OUTSIDE AIR
RETURN AIR
H W
R
COIL
REHEAT
V-2
AI4
AO2
DI2
T-2
DI5
SD-2
DI1
SD-1
TT
AIR
FILTER
DPS-1
DI3
KEYNOTES:
EXISTING DDC DEVICE TO BE REUSED IF FUNCTIONAL AND COMPATIBLE.
EXISTING PNEUMATIC DEVICE TO BE REPLACED.
PROVIDE NEW DDC DEVICE.
PROVIDE NEW DDC CONTROLLER.
AI2
H-1
H
DO1
DI4
CHILLED WATER CONTROL VALVE (V-1)
HEATING HOT WATER CONTROL VALVE (V-2)
AO1
AO2
AO3
DO1
SUPPLY FAN VFD SPEED
SUPPLY FAN START/STOP
46AC-1 CONTROL SCHEMATIC &
SEQUENCE
46 WLP NMT
M46-201
SEQUENCE OF OPERATION
1. GENERAL
1.1. AIR UNIT FAN TO BE STARTED AND STOPPED AS SCHEDULED BY THE ECC.
2. TEMPERATURE CONTROL
2.1. COOLING SPACE TEMPERATURE SETPOINT SHALL BE 74°F (ADJ). WHEN OA DEWPOINT IS ABOVE 55°F CHILLED WATER COIL LEAVING AIR TEMPERATURE OF 55°F AS SENSED BY T-3 BY MODULATING CHILLED WATER VALVE, V-1. FAN SPEED SHALL MODULATE BETWEEN FULL SPEED AND MIN. SPEED OF 30% TO MAINTAIN SPACE TEMPERATURE. WITH THE FAN AT MIN. SPEED, UPON A CALL FOR HEATING THE REHEAT VALVE SHALL MODULATE TO MAINTAIN SPACE TEMPERATURE SETPOINT WITH AND UPPER LIMIT SUPPLY AIR TEMPERATURE OF 95°F. WHEN OA SEW POINT TEMPERATURE IS LESS THAN OR EQUAL TO 55°F, THE UNIT AT MINIMUM FAN SPEED WILL ATTEMPT TO MAINTAIN SPACE TEMPERATURE BY MODULATING EITHER THE CHILLED WATER OR STEAM REHEAT VALVE TO MEET SPACE COOLING OR HEATING SETPOINT RESPECTIVELY. IF ONE OF THE VALVES IS 100% OPEN AND ADDITIONAL HEAT OR
COOLING IS REQUIRED THE FAN SPEED SAHLL INCREASE TO SATISFY SPACE DEMAND.
2.2. HEATING SPACE TEMPERATURE SETPOINT OF 70°F (ADJ) SHALL BE MAINTAINED WITH A REHEAT COIL LEAVING TEMP, T-4, OF 95°F BY MODULATING FAN SPEED, ONCE FAN VFD HAS REACHED MIN. SPEED OF 30% (ADJ) HEATING COIL VALVE, V-2, SHALL BE MODULATED TO MAINTAIN A SPACE AIR TEMPERATURE
SETPOINT. THE OUTSIDE AIR TEMPERATURE IS TRANSMITTED BY T-1.
2.3. WHEN SPACE TEMPERATURE IS BETWEEN COOLING TEMPERATURE SETPOINT AND HEATING SETPOINT FAN VFD SHALL AT MIN SETPOINT AND CHILLED WATER VALVE, V-1, AND REHEAT VAVLE, V-2, SHALL MODULATE TO MAINTAIN NEUTRAL REHEAT COIL LEAVING AIR TEMP. SIMULTANEOUS HEATING AND
COOLING SHALL NOT BE PERMITTED.
3. HUMIDITY
3.1. MIXED AIR %RH IS TRANSMITTED TO THE ECC BY H-1.
3.2. WHEN SPACE HUMIDITY RISES ABOVE 60% RH AS SENSED BY SPACE HUMIDISTAT, H-2, VFD SPEED SHALL BE 100%, CHILLED WATER VALVE, V-1, SHALL MODULATE TO MAINTAIN CHILLED WATER COIL LAT, T-3, SHALL BE 55°F, AND REHEAT VAVLVE, V-2, SHALL MODULATE TO MAINTAIN SPACE TEMPERATURE
SETPOINT. WHEN SPACE HUMIDITY REACHES 50% RH NORMAL OPERATION SHALL RESUME.
4. ALARMS
4.1. THE UNIT AIR FAN SHALL BE DE-ENERGIZED ON A DROP IN COOLING COIL ENTERING AIR TEMPERATURE BELOW THE 35°F SETPOINT OF T-2 OR UPON DETECTION OF IONIZED PARTICLES BY SD-1 OR SD-2.
4.2. A SEPARATE ALARM SHALL BE INITIATED FOR EACH SAFETY. LIKEWISE, A SMOKE DETECTION ALARM
SHALL INITIATED, BY CONTRACT CLOSURE, TO THE FIRE ALARM SYSTEM PANEL.
4.3. THE PRE-FILTER STATUS IS SENSED AT DPS-1. SHOULD THE DROP ACROSS THE FILTER EXCEED 1.5", THE SWITCH SHALL CLOSE AND INITIATE AN ALARM TO THE ECC.
4.4. WHEN THE AIR UNIT FAN IS DE-ENERGIZED FOR ANY REASON, THE AIR UNIT CONTROL VALVES SHALL
RETURN TO THEIR NORMAL POSITIONS.
5. UNOCCUPIED MODE
5.1. DURING UNSCHEDULED PERIODS, THE AIR UNIT FAN SHALL BE DE-ENERGIZED AND ALL CONTROLS AND
CONTROL VALVES SHALL RETURN TO THEIR NORMAL POSITIONS.
AI6
T-3
T
AI9 SPACE HUMIDIAT (H-2)
AI7
T-4
T
T-5T
AI8
SPACE
THERMOSTAT
T-2H
AI9
SPACE
HUMIDISTAT
AI7 REHEAT COIL LEAVING AIR TEMPERATURE SENSOR (T-4)
AI8 SPACE THERMOSTAT (T-5)
AI6 COOLING COIL LEAVING AIR TEMPERATURE SENSOR (T-3)
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
HWS
HWR
TEMPERATURE
SENSOR (TYP)
AI3
T
AI4
DI1
FTFS
STEAM CONV.
TO COND. PUMP
STEAM
SUPPLY
AI1
AO1 1
T
AI5
STR
DO1
DI2
DI2
STR
DO2
KEYNOTES:
EXISTING DDC DEVICE TO BE REUSED IF FUNCTIONAL AND COMPATIBLE.
DETERMINE IF DEVICE EXISTS. IF NONEXISTENT, INSTALL NEW DDC DEVICE.
STEAM CONVERTER CONTROL VALVE
NOT USEDAI2
AI1
HOT WATER SUPPLY FLOWMETERAI4
HOT WATER RETURN TEMPERATURE SENSORAI5
DI2
DI3
DI1
HOT WATER PUMP (46-P-2) STATUS
HOT WATER PUMP (46-P-1) STATUS
HOT WATER PUMP (46-P-1) START/STOP
HOT WATER PUMP (46-P-2) START/STOP
DO1
DO2
AO1 STEAM CONVERTER CONTROL VALVE
STEAM CONVERTER FLOW SWITCH
SEQUENCE OF OPERATION
1. OCCUPIED MODE
1.1. ONCE FLOW IS PROVEN BY STEAM CONVERTER FLOW SWITCH, STEAM CONTROL
VALVE SHALL MODULATE TO MAINTAIN THE HOT WATER SUPPLY TEMPERATURE AT
SETPOINT.
1.2. THE HOT WATER SUPPLY TEMPERATURE RESETS INVERSELY WITH THE OUTDOOR
TEMPERATURE AS SCHEDULED: AT 30°F OA - HWS AT 180°F, AT 70°F OA - HWS AT
140°F.
1.3. HOT WATER PUMPS ARE CONTROLLED BY THE DDC SYSTEM. THE PUMPS ARE 100%
REDUNDANT REQUIRING ONLY ONE PUMP AT A TIME TO OPERATE. THE LEAD/LAG
WATER PUMPS ARE SEQUENCED BY THE DDC SYSTEM TO CHANGE EVERY 7 DAYS. IN
THE EVENT A PUMP FAILS TO START IN 30 SECONDS OR NO FLOW CONDITION AT THE
HEAT EXCHANGER, AN ALARM IS GENERATED, AND THE SECOND PUMP/EXCHANGER
STARTS AUTOMATICALLY.
2. UNOCCUPIED MODE
2.1. IF THE OUTSIDE AIR TEMPERATURE IS BELOW 40°F (ADJUSTABLE) THE DDC SYSTEM
WILL PLACE THE HWS IN OCCUPIED MODE TO START PUMPS AND ACTUATE STEAM
VALVES TO MAINTAIN SETPOINT AS NEEDED BY THE RESET SCHEDULE.
STR
46-P-3
46-P-4
CAMPUS
CHWS
CAMPUS
CHWR
T T
STR
DO1
DI1
AI1
AI2
AI3
DO2
DI2
T
BLDG 46
CHWR
BLDG 46
CHWS
21 1
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE EXISTING CHILLED WATER SUPPLY FROM THE CENTRAL COOLING PLANT
PROVIDES CHILLED WATER TO THE SECONDARY PUMPING SYSTEM AT BUILDING 46.
THE SECONDARY PUMPS ARE 100% REDUNDANT REQUIRING ONLY ONE PUMP AT A
TIME TO OPERATE.
1.2. THE LEAD CHILLED WATER PUMP SHALL RUN ON CALL FOR COOLING.
2. LEAD/STANDBY PUMP CONTROL
2.1. IF THE LEAD BUILDING SECONDARY CHILLED WATER PUMP FAILS TO OPERATE, THE
STANDBY PUMP SHALL BE AUTOMATICALLY STARTED, AND THE SYSTEM SHALL
RESUME NORMAL OPERATION. AN ALARM WILL BE GENERATED AT THE DDC PANEL
TO NOTIFY OF PUMP FAILURE.
2.2. THE LEAD/STANDBY STATUS OF THE PUMPS SHALL BE ROTATED EVERY 7 DAYS
FOR EVEN RUNTIME.
KEYNOTES:
EXISTING DDC DEVICE TO BE REUSED IF FUNCTIONAL AND COMPATIBLE.
DETERMINE IF DEVICE EXISTS. IF NONEXISTENT, INSTALL NEW DDC DEVICE.
AI2
AI1
AI3
CAMPUS CHILLED WATER SUPPLY TEMPERATURE SENSOR
BUILDING 46 CHILLED WATER SUPPLY TEMPERATURE SENSOR
DI1
CHILLED WATER PUMP (46-P-4) STATUS
CHILLED WATER PUMP (46-P-3) STATUS
DI2
DO1
DO2
CHILLED WATER PUMP (46-P-3) START/STOP
CHILLED WATER PUMP (46-P-4) START/STOP
CAMPUS CHILLED WATER RETURN TEMPERATURE
PANEL
DDC CONTROL
H W
R
V-1
NC
COIL
REHEAT
NO
NOTES:
1. POINTS SHALL BE LOCATED IN 46-AC-1 CONTROL PANEL.
2. TEST AND BALANCE ALL AIR FLOWS TO REHEAT COILS PRIOR TO
STARTING WORK. CONFIRM AREA SERVED BY REHEAT COILS.
PROVIDE REPORT TO VA. BALANCE ALL AIR FLOWS TO VALUES
SHOWN IN DRAWINGS.
AO1
AI1
TO SUPPLY
SEQUENCE OF OPERATION
1. GENERAL
1.1. WHEN AIR UNIT 46-AC-1 IS ENERGIZED, THE REHEAT CONTROLS WILL BE ENABLED. THE REHEAT VALVE, V-1, WILL BE MODULATED TO MAINTAIN MIN SPACE TEMP OF 70°F (ADJ).
1.2. WHEN 46-AC-2 IS DE-ENERGIZED, THE REHEAT CONTROLS WILL BE DISABLED.
T-1T
AI2
SPACE
THERMOSTAT HOT WATER CONTROL VALVE (V-1)
SPACE TEMPERATURE SENSOR (T-1)AI2
AI1
HOT WATER CONTROL VALVE (V-1)AO1
FROM
46-AC-2
KEYNOTES:
PROVIDE NEW VALVE ACTUATOR.
PROVIDE NEW SPACE THERMOSTAT.
NOTES:
1. PROVIDE NEW DDC CONTROLLER. CONNECT TO
EXISTING ELECTRICAL SERVICE.
NOTES:
1. PROVIDE NEW DDC CONTROLLER. CONNECT TO
EXISTING ELECTRICAL SERVICE.
HHWS, SCHWS, & REHEAT COIL
CONTROL SCHEMATIC & SEQUENCE
& BALANCE SCHEDULE
46 WLP NMT
M46-202
180 160 140
HOT WATER SETPOINT
(DEG F)
OUTDOOR
AIR
TEMPERATURE
(DEG F)
HEATING HOT WATER RESET
SCHEDULE
HOT WATER SUPPLY TEMPERATURE SENSORAI3
CORR.
DETOX
OBSERVATION
MHC
PSYCHIATRIST
MED ROOM
CORR.
CORR.
CORR.
COMM
PATIENT
TOILET
ADDICTION
THERAPIST
ADDICTION
THERAPIST
CORR.
CORR.
H. K.
SUPPLY
CORR.
BIO
up
CDOP
STORAGE
SUPPLY
COPY/MAIL
COLONNADE
ENTRY
VESTIBULE
VENDING
COMMON WAITING
ROOM
CDOP
CLERK/COPY
MHC
CLERKS
DETOX
PHYSICIAN
ASST/EXAM
DETOX
NURSE
DETOX
SOCIAL
WORKER
ADDICTION
THERAPIST
CDOP
GROUP
ROOM
ADDICTION
THERAPIST
PATIENT
TOILET
CDOP
GROUP
ROOM
CDOP
RECREATION
CDOP
COORDINATOR
ADDICTION
THERAPIST
CDOP
SOCIAL
WORKER
WOMENMEN
MECHANICAL
STAFF
BREAK
ROOMMHICM
RN
136126
MHICM
COORDINATOR
SECRETARY
MHC
ADMIN.
MEN
WOMEN
PC
LPN
MHC
PHYSICIAN
ASSISTANT
MHC
NURSE
MHC
NURSE
PC
RN
STAIR
STAIR
CORR.
PC
PHYSICIAN
EXAM
MECHANICAL
129B
MECH.
LAB DRAW
LAB
TOILET
CONFERENCE
MHICM
PHYSICIAN
ASSISTANT
MHC
SOCIAL
WORKER
MHC
PhD
H. KEEPING
MHC
PSYCHIATRIST
140 141
REAR
ENTRY
CORR.
MHC
PHYSICIAN
ASSISTANT
104A
PATIENT
TOILET
BIO
SAMPLES
SPRINKLER
ROOM
FE
C
FEC
FE
C
FEC
ELEC.
ROOM
EXISTING
COLONNADE
129A
ELEC.
up
CLOSET
104B
EXIST 49-VAV-2-3
EXIST 49-VAV-2-4
EXIST 49-VAV-2-11
EXIST 49-VAV-2-12
EXIST 49-VAV-2-13
EXIST
49-VAV-1-1
EXIST
49-VAV-1-2
EXIST
49-VAV-1-5
EXIST
49-VAV-1-10
EXIST
49-VAV-1-4
EXIST
49-VAV-1-2
EXIST
49-VAV-1-6
EXIST
49-VAV-1-7
EXIST
49-VAV-1-8
EXIST
49-VAV-1-11
EXIST
49-VAV-1-12
EXIST
49-VAV-1-9
EXIST 49-HWUH-1
EXIST
49-HWH-1
EXIST
49-C-1
EXIST
49-C-2
EXIST 49-HWP-1
STARTER
EXIST 49-HWP-2
STARTEREXIST 49-HWP-2
EXIST 49-HWP-1
EXIST 49-SF-1
EXIST
BMS
CONTROL
PANEL
EXIST VFD FOR
49-AHU-1
EXIST 49-VAV-1-13
EXIST 49-VAV-1-14
EXIST STATIC PRES. SEN.
EXIST
49-VAV-2-1
EXIST CHILLED
WATER METER
(49-WFMD-1)
EXIST 49-CWP-1
EXIST VFD FOR
49-CWP-1
EXIST 49-CWP-2
EXIST VFD FOR
49-CWP-2
EXIST 49-VAV-2-9
EXIST STATIC PRES. SEN.
EXIST 49-VAV-2-10
EXIST
49-VAV-2-5
EXIST
49-VAV-2-8
EXIST
49-VAV-2-2
EXIST VFD FOR
49-SF-2
EXIST BMS
CONTROL PANEL
KEYNOTES
EXISTING 49-VAV-2-6
EXISTING 49-SF-2
EXISTING VFD FOR 49-AHU-2
EXISTING 49-CP-1
EXISTING STEAM FLOW METER
EXISTING 49-VAV-2-7
EXISTING VFD FOR 49-SF-1
EXIST 0.090 HP EXHAUST FAN (49-EF-6) TO REMAIN
ON STANDALONE CONTROLS
EXIST 0.167 HP EXHAUST FAN (49-EF-9) TO REMAIN
ON STANDALONE CONTROLS
EXIST 0.167 HP EXHAUST FAN (49-EF-10) TO
REMAIN ON STANDALONE CONTROLS
EXIST 1/20 HP EXHAUST FAN
(49-EF-3) ON ROOF TO
REMAIN ON STANDALONE
CONTROLS
EXIST 0.167 HP EXHAUST FAN
(49-EF-1) TO REMAIN ON
STANDALONE CONTROLS
EXIST 0.167 HP EXHAUST FAN
(49-EF-5) TO REMAIN ON
STANDALONE CONTROLS
EXIST 0.064 HP EXHAUST FAN
(49-EF-12) TO REMAIN ON
STANDALONE CONTROLS
EXIST 1/20 HP
EXHAUST FAN
(49-EF-4) TO REMAIN
ON STANDALONE
CONTROLS
EXIST 49-AHU-1
EXIST
49-AHU-2
EXIST 0.167 HP EXHAUST FAN
(49-EF-2) TO REMAIN ON
STANDALONE CONTROLS
EXIST 0.064 HP EXHAUST
FAN (49-EF-11) TO
REMAIN ON STANDALONE
CONTROLS
EXIST 0.160 HP EXHAUST FAN
(49-EF-7) TO REMAIN ON
STANDALONE CONTROLS
EXIST 0.160 HP EXHAUST FAN
(49-EF-8) TO REMAIN ON
STANDALONE CONTROLS
EXIST ELEC.
PANELS.
EXIST MAIN
ELEC PANEL.
NEW ELEC METER.
CONNECT TO
CAMPUS EMS.
NOTES:
1. EXIST SPACE THERMOSTATS AND
SENSORS TO BE REUSED FOR
BUILDING 49.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
1ST FLOOR PLAN - MECHANICAL
49 WLP NMT
M49-101
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING DDC. SENSORS, ACTUATORS,
SPACE THERMOSTATS/SENSORS ETC MAY BE REUSED IF
FUNCTIONAL AND COMPATIBLE.
2. PROVIDE NEW DDC CONTROLLER. CONNECT TO EXISTING
ELECTRICAL SERVICE.
OUTSIDE AIR
DPS-1
T-4T
C W
R
PANEL
DDC CONTROL
T-3
V-1
NC
RETURN AIR
DI8
DI3
AI4
AI2
SD-1
AI3
T-2VFD
OUTSIDE AIR
FAN
T-1
SPS-1
DI1
SUPPLY
FAN
SPS-2
AI7
T-5
T SPS-3
AI8
DPS-2
DI7
AIR FILTER
DI5 DI6
DO1
AO1
DI2
AI1
DO2
AO3
DI4
AI6
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE VARIABLE VOLUME UNIT CONSISTS OF AN OUTSIDE AIR FAN, PRE-FILTER, CHILLED WATER COOLING COIL, AN AHU SUPPLY FAN WITH VFD, AND A FINAL FILTER RACK. THE UNIT IS DDC
CONTROLLED USING ELECTRONIC ACTUATION.
1.2. THE UNIT IS SCHEDULED FOR AUTOMATIC OPERATION ON A TIME OF DAY BASIS FOR OCCUPIED AND UNOCCUPIED MODES. THE LATEST START TIME IS THE SCHEDULED OCCUPANCY FOR THE SPACE.
1.3. THE UNIT OPERATES IN OCCUPIED AND SAFETY MODES AS FOLLOWS (ALL SUGGESTED SETPOINTS
AND SETTINGS ARE ADJUSTABLE).
2. OCCUPIED
2.1. THE AHU SUPPLY FAN MODULATES TO MAINTAIN THE SUPPLY DUCT STATIC PRESSURE SETPOINT.
THE OUTSIDE AIR FAN MODULATES TO ITS SCHEDULED CFM VALUE. WHEN THE OA DEWPOINT IS ABOVE 55°F THE CHILLED WATER VALVE, V-1, MODULATES TO MAINTAIN 55°F (ADJUSTABLE) SUPPLY
AIR TEMPERATURE.
2.2. STATIC PRESSURE IS MEASURED AT LEAST 2
3 OF THE DISTANCE DOWNSTREAM OF THE SUPPLY FAN
IN EITHER THE LONGEST OR CRITICAL DUCT RUN. UPON INITIAL STARTUP OF THE AIR HANDLING
SYSTEM, THE SUPPLY FAN SPEED SLOWLY RAMPS UP TO THE DESIRED STATIC PRESSURE.
2.4. STATIC PRESSURE SHALL BE RESET BASED ON TERMINAL BOX DAMPER POSITIONS TO MINIMIZE FAN
SPEED.
2.5. SUPPLY AIR TEMPERATURE SETPOINT SHALL BE RESET BASED ON SPACE DEMAND, FAN SPEED, AND
OUTSIDE AIR DEW POINT TEMPERATURE MIN MINIMIZE TOTAL ENERGY USAGE.
3. SAFETIES
3.1. DISCHARGE HIGH STATIC CUTOUTS AND SMOKE DETECTORS IN THE SUPPLY AIR STREAM AND
SUPPLY FAN VFD FAULT ALARMS DE-ENERGIZE THE OUTSIDE AIR AND SUPPLY FANS UPON
ACTIVATION. ALL DAMPERS AND VALVES POSITION TO THEIR NORMAL POSITIONS AFTER THE FANS
ARE DE-ENERGIZED.
3.2. WHEN THE LOW TEMPERATURE DETECTOR, T-3, IN THE MIXED AIR STREAM SENSES TEMPERATURES BELOW 38°F, THE OUTSIDE AIR AND SUPPLY FANS SHALL BE DE-ENERGIZED. AFTER THE FANS ARE
DE-ENERGIZED, THE COOLING COIL VALVE SHALL BE OPENED AND ALL OTHER DAMPERS AND
VALVES SHALL BE POSITIONED TO THEIR NORMAL POSITIONS. AN ALARM SHALL BE GENERATED AT
THE WORKSTATION.
3.3. A CURRENT SWITCH IS INSTALLED ON THE LOAD SIDE OF THE SUPPLY FAN VFD. THE DDC SYSTEM
USES THIS SWITCH TO DETERMINE IF THE FAN IS IN THE DESIRED STATE (ON OR OFF) AND
GENERATES AN ALARM IF STATUS DEVIATES FROM FROM DDC START/STOP CONTROL.
3.4. THE DDC SYSTEM GENERATES A VFD TROUBLE ALARM INDEPENDENT FROM FAN STATUS.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
AMBIENT AIR SENSOR
INSTALLED ON NORTH
SIDE OF BUILDING
CLG
COIL SUPPLY AIR
VFDTT
T
OUTSIDE AIR FAN VFD STATUS
RETURN AIR TEMPERATURE SENSOR (T-1)AI2
AI1
MIXED AIR TEMPERATURE SENSOR (T-2)AI3
AMBIENT AIR TEMPERATURE SENSOR (T-4)AI4
AI6
AI7
AI5 CHILLED WATER CONTROL VALVE (V-1)
SUPPLY FAN VFD STATUS
SUPPLY FAN DISCHARGE TEMPERATURE SENSOR (T-5)
DI6
DI7
DI4
DI2
DI3
DI1
DI5
OUTSIDE AIR FAN STATUS
LOW LIMIT TEMPERATURE SENSOR (T-3) STATUS
SUPPLY FAN STATUS
SUPPLY FAN DISCHARGE HIGH LIMIT STATIC PRESSURE SENSOR (SPS-1) STATUS
OUTSIDE AIR HIGH LIMIT STATIC PRESSURE SENSOR (SPS-1) STATUS
FILTER STATUS (DPS-2)
SUPPLY FAN DISCHARGE SMOKE DETECTOR (SD-1)
OUTSIDE AIR FAN VFD SPEED
CHILLED WATER CONTROL VALVE (V-1)
AO1
AO2
AO3
DO1
DO2
SUPPLY FAN VFD SPEED
OUTSIDE AIR FAN START/STOP
SUPPLY FAN START/STOP
AI5
AO2
AI8 SUPPLY AIR STATIC PRESSURE SENSOR (SPS-3)
49-VAV-1-1
49-VAV-1-2
49-VAV-1-3
49-VAV-1-4
49-VAV-1-5
49-VAV-1-6
49-VAV-1-7
49-VAV-1-8
49-VAV-1-9
49-VAV-1-10
49-VAV-1-11
49-VAV-1-12
49-VAV-1-13
49-VAV-2-1
49-VAV-2-2
49-VAV-2-3
49-VAV-2-4
49-VAV-2-5
49-VAV-2-6
49-VAV-2-7
49-VAV-2-8
49-VAV-2-9
49-VAV-2-10
49-VAV-2-11
49-VAV-2-12
49-VAV-2-13
GPM
HEATING
MAXMIN
CFM COOLING
VARIABLE AIR VOLUME BOX SCHEDULE
55 215 0.8
AREA SERVED
124 MHICM PHYS. ASSISTANT
49-VAV-1-14
130 510 1.8120 MHC PHD / 121 MHC PHYS. ASSISTANT / 123 MHC SOCIAL WORKER
60 230 0.8118 LAB DRAW / 122 CORRIDOR
120 485 1.7113 PHYSICIAN-EXAM ROOM / 114 CORRIDOR
50 195 0.7117 MHC PSYCHIATRIST
160 635 2.2125 MED RM. / 126 MHICM COOR. / 130 MHICM RN / 131 MHC PSYCHIATRIST
200 800 2.8132 SECRETARY / 136 MHC ADMIN. / 134 STORAGE / 133 CORRIDOR
100 400129 ELEC.
205 815 2.8106 MHC CLERKS / 135 COPY.-MAN.
145 570 2.0112 PC LPN / 115 PC RN / 116 MHC NURSES
105 410 1.4110 CONFERENCE
85 330 1.1109 MHC PHYS. ASSISTANTS
270 1080 3.7101 COMMON WAITING ROOM
250 985 3.4100 VEST. / 102 VENDING / 103 MEN / 104 CORRIDOR / 105 WOMEN
185 735 2.5140 BREAK ROOM / 141 MEN / 142 WOMEN
60 240 0.8165 CORRIDOR / 166 CDOP CLERK-COPY / 166 CDOP STORAGE
135 540 1.9168 CDOP GROUP ROOM
100 405 1.4164 CDOP GROUP ROOM
50 190146 ELEC. ROOM
125 505145 COMM. / MECH. 142
60 230 0.8148 CORRIDOR / 152 DETOX OBSERVATION
80 310 1.1157 ADDICTION THERAPIST / 158 CORRIDOR / 160 SAMPLES
130 525 1.8149 DETOX SOCIAL WORKER / 150 DETOX PHYS ASSISTANT-EXAM / 151 DETOX NURSE
190 760 2.6153 CDOP RECREATION
50 185 0.6154 ADDICTION THERAPIST / 163 CORRIDOR
190 765 2.7156 CDOP SOC. WRK / 161 ADD. THERAPIST / 162 ADD. THERAPIST / 167 ADD. THERAPIST
70 285 1.0155 CDOP COORDINATOR
LABEL AHU SERVED
49-AHU-1
49-AHU-1
49-AHU-1
49-AHU-1
49-AHU-1
49-AHU-1
49-AHU-1
49-AHU-1
49-AHU-1
49-AHU-1
49-AHU-1
49-AHU-1
49-AHU-1
49-AHU-1
49-AHU-2
49-AHU-2
49-AHU-2
49-AHU-2
49-AHU-2
49-AHU-2
49-AHU-2
49-AHU-2
49-AHU-2
49-AHU-2
49-AHU-2
49-AHU-2
49-AHU-2
N/A
N/A
N/A
45-AHU-1 & 45-AHU-2 CONTROL
SCHEMATICA & SEQUENCE &
BALANCE SCHEDULE
49 WLP NMT
M49-200
DI8 FILTER STATUS (DPS-1)
AIR HANDLING UNITS BALANCING SCHEDULE
LABEL UNITS SERVED
SUPPLY
CFM
OA CFM
COOLING
COIL GPM
49-AHU-1
VAV BOXES ON
WEST WING
8000 1200 16.8
49-AHU-2
VAV BOXES ON
EAST WING
6000 990 34.1
DIFFERENTIAL PRESSURE SENSOR
CWR
CWS
VFD
C W
S
C W
R
CAMPUS LOOP
TO AHU-1&2
FROM AHU-1&2
49-CWP-1
49-CWP-2
1 EXISTING DEVICE TO BE REUSED
IF FUNCTIONAL AND COMPATIBLE.
2 NEW DDC DEVICE.
KEYNOTES
TEMPERATURE SENSOR (TYP.)
SEQUENCE OF CONTROL: HEATING HOT WATER SYSTEM
1. WHEN ANY PUMP IS ON OPERATION ITS RESPECTIVE STEAM CONTROL VALVE SHALL MODULATE TO MAINTAIN THE LEAVING HOT WATER TEMPERATURE AT THE SET POINT ONCE FLOW IS PROVEN BY RESPECTIVE FLOW SWITCH.
2. THE LEAVING HOT WATER TEMPERATURE SHALL BE RESET INVERSELY WITH THE OUTDOOR AIR TEMPERATURE AS
SCHEDULED.
3. UPON A CALL FOR HEATING FROM ANY TERMINAL UNIT, HOT WATER PUMP 49-HWP-1 OR 49-HWP-2 SHALL ENERGIZE AND AFTER FLOW IS VERIFIED BY THE RESPECTIVE FLOW SWITCH, THE RESPECTIVE STEAM CONTROL VALVE SHALL MODULATE TO MAINTAIN LEAVING HOT WATER TEMPERATURE SETPOINT AT TEMPERATURE SENSOR (T1). HOT WATER PUMPS 49-HWP-1 AND 49-HWP-2 SHALL ALTERNATE AT REGULAR WEEKLY INTERVALS (ADJUSTABLE).
STR
STEAM CONV.
T
FROM BLDG 49
FROM
CAMPUS
STEAM
FROM
CAMPUS
STEAM
TO BLDG 49
SEQUENCE OF OPERATION: SECONDARY CHILLED WATER SYSTEM
1. GENERAL
1.1. UPON A CALL FOR COOLING FROM AIR HANDLING UNIT, THE LEAD CHILLED WATER PUMP SHALL
MODULATE THE PUMP TO MAINTAIN DIFFERENTIAL PRESSURE SETPOINT. (ADJUSTABLE).
DIFFERENTIAL PRESSURE SETPOINT SHALL BE RESET BASED ON VALVE POSITIONS.
1.2. SENSOR LOCATED 2
3 DOWN THE LONGEST CHILLED WATER PIPING BRANCH.
1.3. CHILLED WATER PUMPS 49-CWP-1 AND 49-CWP-2 SHALL ALTERNATE LEAD/LAG AT REGULARLY
WEEKLY INTERVALS (ADJUSTABLE).
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
KEYNOTES
EXISTING DEVICE TO BE REUSED
IF FUNCTIONAL AND
COMPATIBLE.
AI5
T
AI6
VFD
DO2
DI2
AO2
AI3
AI1
DO1
DI1
AO1
AI2
AI4
CAMPUS CHWS FLOWMETER
CHILLED WATER PUMP (49-CWP-1) VFD STATUSAI2
AI1
CHILLED WATER PUMP (49-CWP-2) VFD STATUSAI3
DIFFERENTIAL PRESSURE SENSORAI4
AI6
AI5 CHILLED WATER SUPPLY TEMPERATURE SENSOR
CHILLED WATER RETURN TEMPERATURE SENSOR
DI2
DI1
CHILLED WATER PUMP (49-CWP-2) STATUS
CHILLED WATER PUMP (49-CWP-1) STATUS
CHILLED WATER PUMP (49-CWP-1) VFD SPEED
CHILLED WATER PUMP (49-CWP-2) VFD SPEED
AO1
AO2
AO3
DO1
DO2
NOT USED
CHILLED WATER PUMP (49-CWP-1) START/STOP
CHILLED WATER PUMP (49-CWP-2) START/STOP
1 1
T
AI2
P
AMBIENT AIR TEMPERATURE
SENSOR INSTALLED ON NORTH SIDE
OF BUILDING
CONTROL
VALVE (N.C.)AO1
AO2
TO COND.
PUMP
TO COND.
PUMP
STEAM CONV.CONTROL
VALVE (N.C.)
STR
AI1 TEMPERATURE
SENSOR (TYP.)
T
DO1
DI1
DO2
DI2
HOT WATER BLDG. 49 SUPPLY TEMPERATURE SENSOR
AI2
AI1
AMBIENT AIR TEMPERATURE SENSOR
DI2
DI1 HOT WATER PUMP (49-HWP-1) STATUS
HOT WATER PUMP (49-HWP-2) STATUS
STEAM CONVERTER (49-C-2) CONTROL VALVE
STEAM CONVERTER (49-C-1) CONTROL VALVE
AO1
AO2
DO1
DO2
HOT WATER PUMP (49-HWP-1) START/STOP
HOT WATER PUMP (49-HWP-2) START/STOP
FT
CHW & HHW SYSTEMS & VAV
TERMINAL CONTROL SCHEMATICS &
SEQUENCES
49 WLP NMT
M49-201
COIL
H W
R
V-1
NC
HTG
AI2
AO1
PANEL
DDC CONTROL
T
AI3
T-1
AI4
M
AI1
NOTES:
1. PROVIDE NEW VAV CONTROLLER.
T
T-2
HTG. SET
POINT
CLG. SET
POINT
VALVE OPEN MAX. AIR
VALVE CLOSED
MIN. AIR
SUPPLY AIR
REHEAT COIL
VALVE
ROOM TEMPERATURE
°F (-°C)
°F (+°C)
VAV CONTROL SCHEDULE
AI5
SEQUENCE OF OPERATION: VAV TERMINAL (TYP.)
1. OCCUPIED MODE
1.1. A SPACE SENSOR SHALL TRANSMIT ROOM TEMPERATURE AND HUMIDITY TO THE BOX CONTROLLER, WHICH SHALL VERY THE PRIMARY AIRFLOW AND VARY HEATING VALVE TO MAINTAIN SPACE
TEMPERATURE SETPOINTS.
1.2. A RISE IN SPACE TEMPERATURE ABOVE SETPOINT MODULATE PRIMARY AIRFLOW TO MAX. CFM
SETPOINT INTO THE SPACE. A DROP IN SPACE TEMPERATURE SHALL MODULATE THE PRIMARY
AIRFLOW TO MIN. CFM SETPOINT. A FURTHER DROP IN SPACE TEMPERATURE SHALL MODULATE THE BOX REHEAT CONTROL VALVE OPEN TO HEAT THE SPACE TO MAINTAIN SETPOINT (+/- 0.5°F). THE ADJUSTABLE TOLERANCE OF (+/- 0.5°F) HAS BEEN SELECTED TO PREVENT VALVE HUNTING. VAV BOXES SHALL HAVE SEPARATE HEATING AND COOLING SPACE TEMPERATURE SETPOINTS FOR BOTH
OCCUPIED AND UNOCCUPIED MODES.
2. UNOCCUPIED MODE
2.1. WHEN THE SYSTEM IS INDEXED TO UNOCCUPIED MODE, THE AIR HANDLING SHALL STOP, THE BOX DAMPER SHALL CLOSE, AND THE REHEAT VALVE SHALL CLOSE. IF THE SPACE TEMPERATURE FALLS
BELOW THE NIGHT SETBACK POINT, THE AIR HANDLING UNIT SHALL START,
LOCAL DDC CONTROLLER
AI2
AI1
AI4
INTAKE AIR DAMPER STATUS
AI3
HEATING COIL CONTROL VALVE (V-1)
DISCHARGE AIR TEMPERATURE SENSOR (T-1)
ROOM AIR TEMPERATURE SENSOR (T/H-1)
AO1 HEATING COIL CONTROL VALVE (V-1)
AI5 ROOM AIR HUMIDITY SENSOR (T/H-1)
NOTES
1. PROVIDE NEW CONTROLLER.
CONNECT TO EXISTING
ELECTRICAL SERVICES.
NOTES
1. PROVIDE NEW CONTROLLER. CONNECT TO
EXISTING ELECTRICAL SERVICE.
EXIST ROOM THERMOSTAT & HUMIDITY
SENSOR TO REMAIN AND REUSED.
180 160 140
HOT WATER SETPOINT
(DEG F)
OUTDOOR
AIR
TEMPERATURE
(DEG F)
HEATING HOT WATER RESET
SCHEDULE
F
DI3
FLOW SWITCH
(TYP.)
F
DI4
AI3 STEAM CONVERTER (49-C-2) CONTROL VALVE STATUS
AI4 STEAM CONVERTER (49-C-1) CONTROL VALVE STATUS
DI4
DI3 STEAM CONVERTER (49-C-2) FLOW SWITCH
STEAM CONVERTER (49-C-1) FLOW SWITCH
AI3
AI4