36C25618U0323-0002009.pdf
PDF 4 MB Posted
- Attached to
- Services Commissioning for HVAC Digital Controls Federal contract opportunity
- Solicitation number
- 36C25618U0323
About this file
36C25618U0323 0002 Drawings - Buildings 8 _ 9 (M8 _ M9 Series).pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| -15380.docx | DOCX document | |
| 36C25618U0323-0002007.pdf | ||
| 36C25618U0323-0002005.pdf | ||
| 36C25618U0323-0002004.pdf | ||
| 36C25618U0323-0002006.pdf | ||
| 36C25618U0323-0002012.pdf | ||
| 36C25618U0323-0002000.docx | DOCX document | |
| 36C25618U0323-0002013.pdf | ||
| 36C25618U0323-0002010.pdf | ||
| 36C25618U0323-0002002.pdf | ||
| 36C25618U0323-0002011.pdf | ||
| 36C25618U0323-0002014.pdf | ||
| 36C25618U0323-0002001.docx | DOCX document | |
| 36C25618U0323-0002003.pdf | ||
| 36C25618U0323-0002008.pdf | ||
| 36C25618U0323-0001000.docx | DOCX document | |
| 36C25618U0323-002.pdf | ||
| 36C25618U0323-001.docx | DOCX document | |
| 36C25618U0323-000.docx | DOCX document |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXISTING DOMESTIC
WATER HEATER
EXISTING
8-AHU-2
EXISTING
8-AHU-1
EXISTING
8-AHU-1
DISCONNECT
EXISTING 8-P-1
EXISTING
8-P-1 VFD
EXISTING
FIRE PANELS
EXISTING
HVAC
CONTROL
PANEL
EXISTING KITCHEN EXHAUST FANS
REPLACE 8-AHU-2 STARTER/
DISCONNECT WITH NEW WET
LOCATION VFD. CONNECT TO
EXIST ELEC.
EXISTING
METASYS
CONTROL
PANEL
EXISTING
JCI
CONTROL
PANEL
EXISTING SIEMENS
CONTROL PANEL
8-AHU-1
8-AHU-1
8-AHU-1
8-AHU-1
EXISTING
KITCHEN HOOD,
HD-1, SERVED BY
8EF#1
NOTES:
1. EXISTING CONTROLS ARE A MIX OF JCI AND
SIEMENS DDC AND PNEUMATIC.
2. EXISTING DDC SENSORS, ACTUATORS, ETC. MUST
BE REPLACED.
3. CONTROLLERS AND SPACE THERMOSTATS SHALL
BE REPLACED. CONNECT TO EXISTING ELECTRICAL
SERVICES.
V F
D
PROVIDE NEW ELEC METER AND
CONNECT TO CAMPUS DDC
CONTROL SYSTEM.
PROVIDE NEW CHILLED WATER,
DOMESTIC WATER AND STEAM
METER PANEL. CONNECT TO
CAMPUS DDC CONTROL SYSTEM.
EXIST MAIN
ELEC PANEL.
PROVIDE NEW STEAM
METER IN SUPPLY PIPING
AND NEW CHW METER IN
RETURN PIPING.
PROVIDE NEW
DOMESTIC WATER
METER.
KEYNOTES:
PROVIDE NEW METER. CONTRACTOR SHALL PROVIDE
120V POWER CONNECTION TO NEW METER.
CONTRACTOR SHALL ROUTE TO NEAREST 120V PANEL
WITH SPARE CAPACITY, INSTALL NEW 20 A-1 POLE
CIRCUIT BREAKER, & MAKE CONNECTION. PROVIDE 20
A SWAP SWITCH AT DDC PANEL FOR DISCONNECT.
CONTRACTOR TO VERIFY 120V PANEL LOCATION
DURING PRE-BID WALKTHROUGH.
V F
D
REPLACE 8-AHU-1 STARTER/
DISCONNECT WITH NEW WET
LOCATION VFD. CONNECT TO
EXIST ELEC.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
1ST FLOOR PLAN - MECHANICAL
8 WLP NMT
M8-101 10-30-13
OUTSIDE AIR
DPS-1
C H
W R
SUPPLY
COIL
CLG
V-2
NO
VFD
FAN
DI4
DO1
AI8
AO4
DI5DI2AI1
AO1
AI12
AO6
PANEL
DDC CONTROL
AIR FILTER
T-5
NC
D-1
AI2
AO2
NO
D-2
AI5
T-4
T
T-3 H-1
AI4 AI6
L P
S
V-1
NO
AI10
T-7
AI9
AO5
AI11
TYP 3 ZONES
AI13
AO7
AI14
AO8
AI17
T-6
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE AIR HANDLING UNIT IS SCHEDULED FOR AUTOMATIC OPERATION ON A TIME OF DAY BASIS FOR
OCCUPIED AND UNOCCUPIED MODES.
1.2. WITHIN OCCUPIED MODE, THE SYSTEM CAN ENTER THE WARM-UP MODE WHEN THE SPACE
TEMPERATURE IS BELOW SETPOINT OR THE COOL-DOWN MODE WHEN THE SPACE TEMPERATURE IS
ABOVE SETPOINT. THE SYSTEM STAYS IN THE WARM-UP OR COOL-DOWN MODE UNTIL THE MODE
SETPOINT IS SATISFIED.
1.3. WITHIN THE UNOCCUPIED MODE, NIGHT HEATING IS AVAILABLE WHEN THE SPACE TEMPERATURE DROPS BELOW 65°F. THE LATEST START TIME IS THE SCHEDULED OCCUPANCY FOR THE SPACE.
1.4. ALL SUGGESTED SETPOINTS AND SETTINGS ARE ADJUSTABLE.
2. WARM-UP
2.1. THE SUPPLY FAN STARTS. THE MIXING DAMPERS ARE POSITIONED FOR 100% RETURN AIR AND THE COLD DECK COOLING COIL VALVE REMAINS CLOSED. THE HOT DECK HEATING COIL VALVE MODULATES
TO MAINTAIN THE HOT DECK SUPPLY TEMPERATURE SETPOINT.
2.2. IF TIME REACHES THE LATEST START TIME DURING THE WARM-UP MODE, THE OUTDOOR AIR DAMPER
OPENS TO ITS MIN. POSITION.
2.3. THE SYSTEM IS PREVENTED FROM ENTERING THE WARM-UP MODE MORE THAN ONCE PER DAY.
3. COOL-DOWN
3.1. THE SUPPLY FAN STARTS. THE HOT DECK HEATING COIL VALVE REMAINS CLOSED. THE COLD DECK COOLING VALVE AND THE MIXING DAMPERS MODULATE TO MAINTAIN THE COLD DECK SUPPLY AIR
TEMPERATURE AT SETPOINT.
3.2. IF TIME REACHES THE LATEST START TIME DURING THE COOL-DOWN MODE, THE OUTDOOR AIR
DAMPER OPENS TO ITS MIN. POSITION OR IS CONTROLLED IN ECONOMIZER OPERATION.
3.3. THE SYSTEM IS PREVENTED FROM ENTERING COOL-DOWN MODE MORE THAN ONCE PER DAY.
4. OCCUPIED
4.1. THE FAN STARTS OR CONTINUES TO RUN.
4.2. THE HOT DECK HEATING COIL VALVE MODULATES TO MAINTAIN THE HOT DECK SUPPLY AIR
TEMPERATURE SETPOINT.
4.3. THE CHILLED WATER COOLING COIL VALVE MODULATES TO MAINTAIN THE COLD DECK SUPPLY AIR
TEMPERATURE SETPOINT.
5. UNOCCUPIED
5.1. THE FAN IS OFF, THE COLD DECK COOLING COIL VALVE CLOSES, AND MIXING DAMPERS CLOSE TO THE
OUTDOOR AIR. THE HOT DECK HEATING COIL VALVE OPENS.
6. NIGHT HEATING
6.1. THE SUPPLY FAN STARTS WITH THE HOT DECK HEATING COIL VALVE OPEN TO MAINTAIN A MIN. SPACE TEMPERATURE OF 65°F IN ANY OF THE ZONES. THE COLD DECK COOLING COIL VALVE REMAINS CLOSED
AND THE MIXING DAMPERS REMAIN CLOSED TO OUTDOOR AIR.
7. ZONE CONTROL
7.1. EACH ZONE HOT DECK AND COLD DECK DAMPERS SHALL MAINTAIN SPACE TEMPERATURE SEPOINT.
ZONE AIRFLOW SHALL BE MAINTAINED BETWEEN MINIMUM AND MAXIMUM VALUES. SIMULTANIOUS
HEATING AND COOLING SHALL ONLY BE ALLOWED WITH ZONE AIRFLOW AT MIN.
7.2. THE VFD SHALL MAINTAIN MAXIMUM OPEN HEATING OR COOLING DAMPER AT 95% OPEN.
8. ALARMS
8.1. WHEN THE OAT IS LESS THAN 45°F, THE HOT DECK HEATING COIL VALVE MODULATES TO MAINTAIN THE HOT DECK AIR TEMPERATURE AT 45°F AND THE COLD DECK COOLING VALVE OPENS. WHEN THE OAT IS 45°F OR ABOVE, THE HOT DECK HEATING VALVE AND THE COLD DECK COOLING VALVE CLOSE. ALL
OTHER DAMPERS AND VALVES POSITION TO THEIR NORMAL POSITIONS AFTER THE FAN IS
EN-ENERGIZED.
8.2. A LOW TEMPERATURE DETECTOR IN THE DISCHARGE OF THE HEATING COIL DE-ENERGIZES THE SUPPLY FAN WHEN TEMPERATURES BELOW 38°F ARE SENSED. THE HOT DECK HEATING COIL VALVE MODULATES TO MAINTAIN THE HOT DECK AIR TEMPERATURE AT 45°F AND THE COLD DECK COOLING VALVE OPENS. ALL OTHER DAMPERS AND VALVES POSITION TO THEIR NORMAL POSITIONS AFTER THE
FAN IS DE-ENERGIZED.
8.3. THE DDC SYSTEM GENERATES AN ALARM IF STATUS DEVIATES FROM DDC START/STOP CONTROL.
KEYNOTES:
EXIST DDC CONTROL DEVICE TO BE REPLACED.
EXISTING PNEUMATIC CONTROL DEVICE TO BE REPLACED WITH DDC
DEVICE.
EXIST CONTROL DEVICE TO BE REPLACED. CONNECT TO EXISTING
ELECTRICAL SERVICES.
NEW CHILLED WATER VALVE TO BE 2-WAY. REPLACE TEE IN SUPPLY PIPE
WITH STRAIGHT PIECE OF PIPE.
PROVIDE NEW DDC AHU CONTROLLER.
NEW DDC DEVICE.
SEPARATE HOT DECK AND COLD DECK DAMPER RODS FOR INDEPENDENT
CONTROL.
PROVIDE NEW AIR FLOW METER IN EXISTING SA DUCTWORK. FIELD VERIFY
DUCT DIMENSIONS.
DI1
T-2
AI3
T-1
1 1
1 1
SD-1
SD-2
OUTSIDE AIR DAMPER (D-1) CONTROLLERAO1
CHILLED WATER CONTROL VALVE (V-1)
AO2
AO3
STEAM CONTROL VALVE (V-2)
AO4
AO5
AO6 ZONE 1 COLD DECK DAMPER (D-3) CONTROLLER
ZONE 2 COLD DECK DAMPER (D-4) CONTROLLER
SUPPLY FAN START/STOPDO1
AI2
AI1
AI3
AI4
AI6
AI7
AI5
AI8
AI10
AI11
AI9
AI12
AI13
AI14
AI15 ZONE 1 SUPPLY AIR DISCHARGE TEMPERATURE SENSOR (T-8)
ZONE 2 SUPPLY AIR DISCHARGE TEMPERATURE SENSOR (T-9)
ZONE 3 SUPPLY AIR DISCHARGE TEMPERATURE SENSOR (T-10)
FILTER STATUS (DPS-1)DI2
DI3
DI1 HIGH LIMIT TEMPERATURE SENSOR (T-2) STATUS
RETURN AIR SMOKE DETECTOR (SD-1) STATUS
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
H
T T T T T
T
HTG
COIL
DI3
DI6
T-11
AI18
T T-12
AI19
T-13
AI20
T T
ZONE 2 THERMOSTAT
ZONE 3 THERMOSTAT
ZONE 1 THERMOSTAT
1 1 1
D-3 T-8
T-9
T-10 D-4
D-5
AI15
AI16
AI16
AI17
AI18 ZONE 1 AIR TEMPERATURE SENSOR (T-11)
ZONE 2 AIR TEMPERATURE SENSOR (T-12)
SUPPLY FAN STATUS
DI5
DI6
DI4
LOW LIMIT TEMPERATURE SENSOR (T-5) STATUS
SUPPLY SMOKE DETECTOR (SD-2) STATUS
T
AI19
ZONE 3 AIR TEMPERATURE SENSOR (T-13)
ZONE 1 COLD DECK DAMPER (D-3)
ZONE 2 COLD DECK DAMPER (D-4)
ZONE 3 COLD DECK DAMPER (D-5)
COLD DECK TEMPERATURE SENSOR (T-7)
HOT DECK TEMPERATURE SENSOR (T-6)
STEAM CONTROL VALVE (V-3)
CHILLED WATER CONTROL VALVE (V-2)
PRE-FILTERED MIXED AIR TEMPERATURE SENSOR (T-1)
RETURN AIR TEMPERATURE SENSOR (T-3)
RETURN AIR HUMIDITY SENSOR (H-1)
OUTSIDE AIR DAMPER (D-1)
RETURN AIR DAMPER (D-2)
FILTERED MIXED AIR TEMPERATURE SENSOR (T-4)
AO7
ZONE 3 COLD DECK DAMPER (D-5) CONTROLLER
RETURN AIR DAMPER (D-2) CONTROLLER
8-AHU-01 CONTROL SCHEMATIC
& SEQUENCE
8 WLP NMT
M8-200
D-6
D-7
D-8
AI21
AO9
AI22
AO10
AI23
AO11
F-1
AI24
AI25
AI26
F-2 F-3
AI20
ZONE 1 HOT DECK DAMPER (D-6)AI21
ZONE 2 HOT DECK DAMPER (D-7)AI22
ZONE 3 HOT DECK DAMPER (D-8)AI23
ZONE 1 AIR FLOW METER (F-1)AI24
ZONE 2 AIR FLOW METER (F-2)AI25
ZONE 3 AIR FLOW METER (F-3)
AO8
ZONE 1 HOT DECK DAMPER (D-6) CONTROLLERAO9
ZONE 2 HOT DECK DAMPER (D-7) CONTROLLER
AO10
ZONE 3 HOT DECK DAMPER (D-8) CONTROLLER
NOTES:
1. TEST AND BALANCE ALL AIR FLOWS TO AHU, FCU, VAV BOXES
(MAX. AND MIN.), ETC PRIOR TO STARTING WORK. PROVIDE
REPORT TO VA. BALANCE ALL AIR FLOWS TO
PRE-CONSTRUCTION VALUES.
AI7
AO3
AI26
SUPPLY FAN VFD SPEED
AO11
SUPPLY FAN VFD SPEED
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
SUPPLY
VFD
FAN
DO1
DI4
COIL
C H
W R
V-2
NO
CLG
AI7
AO4AO1
AI1 AI4
SUPPLY
PANEL
DDC CONTROL
AI5
T-3
T-2
OUTSIDE AIR
D-1
AI3
RETURN AIRH-1
L P
S
COIL
HTG
V-3
NC
AI8
AO5
AI9
T-5
AIR
FILTER
DI1
T-1
AI2
AO2
NOD-2
NC
S T
M
COIL
HTG
V-1
NC
AI6
AO3
DI5
SD-2
DI2
SD-1
ZONE THERMOSTAT SENSOR
T-7
AI10
T
ZONE OCCUPANCY SENSOR
OCC-1
AI12
OCC
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE AIR HANDLING UNIT IS SCHEDULED FOR AUTOMATIC OPERATION ON A TIME OF DAY BASIS FOR
OCCUPIED AND UNOCCUPIED MODES.
1.2. WITHIN OCCUPIED MODE, THE SYSTEM CAN ENTER THE WARM-UP MODE WHEN THE SPACE TEMPERATURE IS BELOW SETPOINT OR THE COOL-DOWN MODE WHEN THE SPACE TEMPERATURE IS ABOVE SETPOINT.
THE SYSTEM STAYS IN THE WARM-UP OR COOL-DOWN MODE UNTIL THE MODE SETPOINT IS SATISFIED.
1.3. WITHIN THE UNOCCUPIED MODE, NIGHT HEATING IS AVAILABLE WHEN THE SPACE TEMPERATURE DROPS
BELOW 65°F. THE LATEST START TIME IS THE SCHEDULED OCCUPANCY FOR THE SPACE.
1.4. PRE-HEAT STEAM VALVE, V-1, SHALL MODULATE TO MAINTAIN PRE-HEAT DISCHARGE AIR TEMPERATURE
BETWEEN 45°F AND 55°F.
1.5. ALL SUGGESTED SETPOINTS AND SETTINGS ARE ADJUSTABLE.
2. WARM-UP
2.1. THE SUPPLY FAN STARTS. THE MIXING DAMPERS ARE POSITIONED FOR 100% RETURN AIR AND THE PREHEAT COIL AND COOLING COIL VALVES REMAIN CLOSED. THE HEATING COIL VALVE MODULATES TO
MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT.
2.2. IF TIME REACHES THE LATEST START TIME DURING THE WARM-UP MODE, THE OUTDOOR AIR DAMPER
OPENS TO ITS MIN. POSITION.
2.3. THE SYSTEM IS PREVENTED FROM ENTERING THE WARM-UP MODE MORE THAN ONCE PER DAY.
3. COOL-DOWN
3.1. THE SUPPLY FAN STARTS. THE PREHEAT COIL AND HEATING COIL VALVES REMAIN CLOSED. THE COLD
DECK COOLING VALVE AND THE MIXING DAMPERS MODULATE TO MAINTAIN THE SUPPLY AIR
TEMPERATURE AT SETPOINT. WHEN THE OUTSIDE AIR DRY BULB TEMPERATURE IS ABOVE THE
ECONOMIZER CHANGEOVER VALUE, THE MIXING DAMPERS ARE POSITIONED FOR 100% RETURN AIR.
3.2. IF TIME REACHES THE LATEST START TIME DURING THE COOL-DOWN MODE, THE OUTDOOR AIR DAMPER
OPENS TO ITS MIN. POSITION OR IS CONTROLLED IN ECONOMIZER OPERATION.
3.3. THE SYSTEM IS PREVENTED FROM ENTERING COOL-DOWN MODE MORE THAN ONCE PER DAY.
4. OCCUPIED
4.1. WHEN OA DEWPOINT IS GREATER THAN 55°F, CHILLED WATER COIL LEAVING AIR TEMPERATURE SHALL BE MAINTAINED AT 55°F AS SENSED BY T-3 BY MODULATING CHILLED WATER VALVE, V-2. SPACE TEMPERATURE SETPOINT SHALL BE MAINTAINED BY MODULATING FAN VFD BETWEEN MIN. SPEED OF 30% (ADJ) MAX. SPEED OF 100%. WITH THE FAN AT MINIMUM SPEED, UPON A CALL FOR HEATING THE REHEAT VALVE WILL MODULATE, WITH AND UPPER LIMIT SUPPLY AIR TEMPERATURE AS SENSED T-5 OF 95°F.
4.2. WHEN OA DEW POINT TEMPERATURE IS LESS THAN OR EQAUL TO 55° THE VFD SPEED SHALL BE AT MIN SPEED OF 30% (ADJ.). SPACE TEMPERATURE SHALL BE MAINTAINED AT COOLING OR HEATING SETPOINT BY MODULATING THE CHILLED WATER VALVE, V-2, OR RE-HEAT VAVLE, V-3, RESPECTIVELY. IF EITHER VALVE IS 100% OPEN AND ADDITIONAL COOLING OR HEATING IS REQUIRED, VFD SPEED SHALL INCREASE
TO MAINTING SPACE TEMPERATURE SETPOINT.
5. UNOCCUPIED (NORMAL OFF)
5.1. THE SUPPLY FAN STOPS, THE COOLING COIL VALVE CLOSES AND THE MIXING DAMPERS CLOSE TO THE OUTDOOR AIR. IF THE OAT IS LESS THAN 45°F, THE HEATING COIL VALVE MODULATES TO MAINTAIN THE UNOCCUPIED SUPPLY AIR SETPOINT. IF THE OAT IS 45° OR ABOVE, THE HEATING COIL VALVE CLOSES.
6. HUMIDITY
6.1. MIXED AIR %RH IS TRANSMITTED TO THE ECC BY H-1.
6.2. WHEN RETURN HUMIDITY RISES ABOVE 60% RH AS SENSED BY SPACE HUMIDISTAT, H-2, VFD SPEED SHALL BE 100%, CHILLED WATER VALVE, V-2, SHALL MODULATE TO MAINTAIN CHILLED WATER COIL LAT, T-3, SHALL BE 55°F, AND REHEAT VALVE, V-1, SHALL MODULATE TO MAINTAIN SPACE TEMPERATURE SETPOINT.
WHEN SPACE HUMIDITY REACHES 50% RH NORMAL OPERATION SHALL RESUME.
7. NIGHT HEATING
7.1. THE SUPPLY FAN STARTS WITH THE HEATING COIL VALVE OPEN TO MAINTAIN A MIN. SPACE TEMPERATURE OF 65°F. THE COOLING COIL VALVE IS CLOSED AND THE MIXING DAMPERS CLOSE TO OUTDOOR AIR.
8. ALARMS
8.1. SMOKE DETECTORS IN THE SUPPLY AND RETURN AIR STREAMS DE-ENERGIZE THE SUPPLY FAN UPON ACTIVATION. WHEN THE OAT IS LESS THAN 45°F, THE HEATING COIL VALVE MODULATES TO MAINTAIN THE MIXED AIR TEMPERATURE AT 45°F. WHEN THE OAT IS 45°F OR ABOVE, THE HEATING COIL VALVE CLOSES.
ALL OTHER DAMPERS AND VALVES POSITION TO THEIR NORMAL POSITIONS AFTER THE FAN IS
EN-ENERGIZED.
8.2. A LOW TEMPERATURE DETECTOR IN THE DISCHARGE OF THE HEATING COIL DE-ENERGIZES THE SUPPLY FAN WHEN TEMPERATURES BELOW 38°F ARE SENSED. THE HEATING COIL VALVE MODULATES TO MAINTAIN THE MIXED AIR TEMPERATURE AT 45°F. ALL OTHER DAMPERS AND VALVES POSITION TO THEIR NORMAL
POSITIONS AFTER THE FAN IS DE-ENERGIZED.
8.3. A CURRENT SWITCH IS INSTALLED IN THE SUPPLY FAN STARTER. THE DDC SYSTEM USES THIS SWITCH TO CONFIRM THE FAN IS IN THE DESIRED STATE (I.E. ON OR OFF) AND GENERATES AN ALARM IF STATUS
DEVIATES FROM DDC START/STOP CONTROL.
KEYNOTES:
EXIST DDC CONTROL DEVICE TO BE REPLACED.
EXISTING PNEUMATIC CONTROL DEVICE TO BE REPLACED WITH DDC
DEVICE.
NEW CHILLED WATER VALVE TO BE 2-WAY. REPLACE TEE IN RETURN PIPE
WITH STRAIGHT PIECE OF PIPE.
PROVIDE NEW DDC AHU CONTROLLER. CONNECT NEW CONTROLLER TO
EXISTING ELECTRICAL SERVICE.
NEW DDC DEVICE.
2 2
DI3
T-4
1 1
5 5
OUTSIDE AIR DAMPER (D-1) CONTROLLERAO1
MEDIUM PRESSURE STEAM CONTROL VALVE (V-1)
AO2
AO3
CHILLED WATER CONTROL VALVE (V-2)AO4
AO5 LOW PRESSURE STEAM CONTROL VALVE (V-3)
SUPPLY FAN START/STOPDO1
AI2
AI1
AI3
AI4
AI6
AI7
AI5
AI8
AI10
AI11
AI9
AI12
RETURN AIR SMOKE DETECTOR (SD-1) STATUSDI2
DI3
DI1 MIXED AIR LOW LIMIT TEMPERATURE SENSOR (T-1)
LPS HEATING COIL DISCHARGE LOW LIMIT TEMPERATURE SENSOR (T-4) STATUS
SUPPLY FAN STATUS
DI5
DI4
SUPPLY AIR DISCHARGE SMOKE DETECTOR (SD-2) STATUS
NOT USED
ZONE OCCUPANCY SENSOR (OCC-1)
SUPPLY AIR DISCHARGE TEMPERATURE SENSOR (T-5)
ZONE TEMPERATURE SENSOR (T-7)
LOW PRESSURE STEAM RE-HEAT CONTROL VALVE (V-3)
CHILLED WATER CONTROL VALVE (V-2)
RETURN AIR TEMPERATURE SENSOR (T-2)
RETURN AIR HUMIDITY SENSOR (H-1)
MEDIUM PRESSURE STEAM PRE-HEAT CONTROL VALVE (V-1)
OUTSIDE AIR DAMPER (D-1)
RETURN AIR DAMPER (D-2)
MIXED AIR TEMPERATURE SENSOR (T-3)
RETURN AIR DAMPER (D-2) CONTROLLER
T H
T T T T
8-AHU-02 CONTROL SCHEMATIC
& SEQUENCE
8 WLP NMT
M8-201
AI13
AO6
AI13 SUPPLY FAN VFD SPEED
AO6 SUPPLY FAN VFD SPEED
AI14
T-6
T
AI14 COOLING COIL DISCHARGE AIR TEMPERATURE (T-6)
NOTES:
1. TEST AND BALANCE ALL AIR FLOWS TO AHU, FCU, VAV BOXES
(MAX. AND MIN.), ETC PRIOR TO STARTING WORK. PROVIDE
REPORT TO VA. BALANCE ALL AIR FLOWS TO
PRE-CONSTRUCTION VALUES.
AI15
T-8
T
AI15 PRE-HEAT COIL DISCHARGE AIR TEMPERATURE (T-7)
VFD
1-CHW P-1
P
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE SECONDARY CHILLED WATER SYSTEM CONSISTS OF ONE CHILLED WATER PUMP (1-CHW P-1) WITH A VARIABLE FREQUENCY DRIVE (VFD). THE SYSTEM IS DDC CONTROLLED WITH ELECTRIC ACTUATION.
2. SECONDARY CHILLED WATER PUMP CONTROL
2.1. WHEN COOLING IS REQUIRED, THE SECONDARY CHILLED WATER PUMP STARTS. THE VFD MODULATES PUMP SPEED TO MAINTAIN SYSTEM DIFFERENTIAL PRESSURE OF 20 PSI AS SENSED NEAR THE END OF
THE SECONDARY PIPING RUN.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
CAMPUS
CHWS
CAMPUS
CHWR
BLDG. 8
CHWR
AHU-8-1&2
CHWS
T
AI1
T
AI3
AI2
AO1 DO1
DI1
AI4
AI2
AI1
AI3
AI4
DI1 CHILLED WATER PUMP (1-CHW P-1) STATUS ?
BLDG. 8 CHILLED WATER RETURN TEMPERATURE SENSOR
DIFFERENTIAL PRESSURE SENSOR
CAMPUS CHILLED WATER SUPPLY TEMPERATURE SENSOR
CHILLED WATER PUMP (1-CHW P-1) VFD STATUS ?
CHILLED WATER PUMP (1-CHW P-1) VFD SPEED ?AO1
SUPPLY FAN START/STOPDO1
NOTES:
1. EXISTING PNEUMATIC CONTROL DEVICE TO BE REPLACED
WITH NEW DDC DEVICE.
2. PROVIDE NEW DDC CONTROLLER. CONNECT NEW
CONTROLLER TO EXISTING ELECTRICAL SERVICE.
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING DDC. VFD MAY BE
REUSED IF FUNCTIONAL AND COMPATIBLE. SENSORS MUST
BE REPLACED.
2. CONTROLLER SHALL BE REPLACED. CONNECT NEW
CONTROLLER TO EXISTING ELECTRICAL SERVICE.
STEAM CONV.
STEAM
SUPPLY
AI1
AO1
CONDENSATE
RETURN
D H
W S
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE DOMESTIC HOT WATER SYSTEM IS ENABLED CONTINUOUSLY.
2. DOMESTIC HOT WATER CONVERTER CONTROL
2.1. STEAM CONTROL VAVLE V-1 SHALL MODULATE TO MAINTAIN A DOMESTIC HOT WATER SUPPLY
TEMPERATURE SETPOINT OF 150°F (ADJUSTABLE).
AI2
AI1 STEAM CONTROL VAVLE V-1
DOMESTIC HOT WATER SUPPLY TEMPERATURE
STEAM CONTROL VALVE V-1AO1
D C
W S
T
AI2
SCHWS & DOMESTIC HOT WATER
SYSTEM CONTROL SCHEMATIC
& SEQUENCE
8 WLP NMT
M8-202
EXIST 9-CHWP-1
EXIST 9-CHWP-2
EXIST 9-CP-1
EXIST 9-HWHP-3
EXIST 9-HWHP-4
EXIST 9-C-1 & 9-C-2
STACKED ON TOP OF
EACH OTHER
DEMO EXIST CONTROL
AIR COMPRESSOR
EXIST
9-WH-1
EXIST
9-WH-2
EXIST
V9-3-1
EXIST
V9-3-2
EXIST
V9-3-5
EXIST
V9-3-6
EXIST
V9-3-7
EXIST
V9-3-3
EXIST
V9-3-4
EXIST
V9-3-8
EXIST
FCU#9-4
EXIST
FCU#9-3
EXIST
FCU#9-1
EXIST
FCU#9-2
KEYNOTES:
EXISTING FCU-A: FAN CFM, 190; OA CFM, 15; CHW
GPM, 1.4; HW GPM, 0.5.
EXISTING FCU-B: FAN CFM, 300; OA CFM, 20; CHW
GPM, 2.1; HW GPM, 1.0.
EXISTING FCU-C: FAN CFM, 400; OA CFM, 30; CHW
GPM, 2.8; HW GPM, 1.0.
EXISTING FCU-D: FAN CFM, 600; OA CFM, 40; CHW
GPM, 4.0; HW GPM, 1.0.
EXISTING FCU-F: FAN CFM, 1000; OA CFM, 60; CHW
GPM, 6.2; HW GPM, 1.6.
A
B
C
D
A
F
F C
D
D
B
B
B B B
B
B
A
C
A
B
B
B
B D
B
AA
EXIST ELEC AND MECHANICAL
METER ENCLOSURES. CONNECT
TO CAMPUS DDC CONTROL
SYSTEM.
EXIST 16-502-9-PW-1
EXIST STEAM METER
(16-502-9-ST-1)
EXIST CHILLED WATER METER
(16-502-9-CHW-1)
EXIST 1/8 HP EXHAUST FAN
(9EF-5) TO REMAIN ON
STANDALONE CONTROLS
EXIST
ABANDONED
EXHAUST FAN.
EXIST ABANDONED
EXHAUST FAN. EXIST PNEUMATIC DUCT
DAMPER. REPLACE
ACTUATOR AND
THERMOSTAT WITH DDC.
EXIST PNEUMATIC
SMOKE DAMPER
TO BE
CONVERTED TO
DDC CONTROL.
(TYP.)
V F
D V
F D
PROVIDE NEW 10 HP VFD'S FOR CHILLED WATER
PUMPS. CONNECT TO EXIST ELEC SERVICE.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
1ST FLOOR PLAN - MECHANICAL
9 WLP NMT
M9-101
B
B
B
B
D
B
B
B B B
B
B
B
B
B
A
C
C
C
B B
B C
A
D
A
D
D
E
KEYNOTES:
EXISTING FCU-A: FAN CFM, 190; OA CFM, 15; CHW
GPM, 1.4; HW GPM, 0.5.
EXISTING FCU-B: FAN CFM, 300; OA CFM, 20; CHW
GPM, 2.1; HW GPM, 1.0.
EXISTING FCU-C: FAN CFM, 400; OA CFM, 30; CHW
GPM, 2.8; HW GPM, 1.0.
EXISTING FCU-D: FAN CFM, 600; OA CFM, 40; CHW
GPM, 4.0; HW GPM, 1.0.
EXISTING FCU-E: FAN CFM, 800; OA CFM, 50; CHW
GPM, 5.1; HW GPM, 1.2.
EXISTING FCU-F: FAN CFM, 1000; OA CFM, 60; CHW
GPM, 6.2; HW GPM, 1.6.
A
B
C
D
E
F
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
2ND FLOOR PLAN - MECHANICAL
9 WLP NMT
M9-102
C
E C
B
B B B
B
B
B
B
B
A
B
B D
B B
C
D C
A
C
C
C
KEYNOTES:
EXISTING FCU-A: FAN CFM, 190; OA CFM, 15; CHW
GPM, 1.4; HW GPM, 0.5.
EXISTING FCU-B: FAN CFM, 300; OA CFM, 20; CHW
GPM, 2.1; HW GPM, 1.0.
EXISTING FCU-C: FAN CFM, 400; OA CFM, 30; CHW
GPM, 2.8; HW GPM, 1.0.
EXISTING FCU-D: FAN CFM, 600; OA CFM, 40; CHW
GPM, 4.0; HW GPM, 1.0.
EXISTING FCU-E: FAN CFM, 800; OA CFM, 50; CHW
GPM, 5.1; HW GPM, 1.2.
A
B
C
D
E
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
3RD FLOOR PLAN - MECHANICAL
9 WLP NMT
M9-103
M
EXIST WFM-9-11
EXIST 9AC-3
EXIST BYPASS
DAMPER
EXIST 9AC-1EXIST 9AC-2
EXIST 9EF-4
EXIST 1.5 HP EXHAUST FAN
(9EF-3)
EXIST 1 HP EXHAUST FAN
(9EF-1)
EXIST 0.5 HP EXHAUST FAN
(9EF-2)
EXIST ELEVATOR
HOISTWAY PNEUMATIC
SMOKE DAMPER TO BE
CONVERTED TO DDC
CONTROL. (TYP.)
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
4TH FLOOR PLAN - MECHANICAL
9 WLP NMT
M9-104
PREHEAT CONTROL VALVE (V-1)AO1
CHILLED WATER CONTROL VALVE (V-3)AO2
AO3 STEAM CONTROL VALVE (V-2)
AO4
AO5
AO6
ZONE 1 SUPPLY AIR DISCHARGE DAMPER (D-1) CONTROLLER
ZONE 2 SUPPLY AIR DISCHARGE DAMPER (D-2) CONTROLLER
ZONE 3 SUPPLY AIR DISCHARGE DAMPER (D-3) CONTROLLER
SUPPLY FAN START/STOPDO1
PREHEAT CONTROL VALVE (V-1)
PREHEAT COIL DISCHARGE AIR TEMPERATURE SENSOR (T-1)AI2
AI1
CHILLED WATER CONTROL VALVE (V-2)AI3
STEAM CONTROL VALVE (V-3)AI4
AI6
AI7
AI5
AI8
AI10
AI11
AI9
AI12
AI13
AI14
AI15
COLD DECK TEMPERATURE SENSOR (T-4)
HOT DECK TEMPERATURE SENSOR (T-3)
ZONE 1 SUPPLY AIR DISCHARGE DAMPER (D-1)
ZONE 2 SUPPLY AIR DISCHARGE DAMPER (D-2)
ZONE 3 SUPPLY AIR DISCHARGE DAMPER (D-3)
ZONE 1 SUPPLY AIR DISCHARGE TEMPERATURE SENSOR (T-5)
ZONE 2 SUPPLY AIR DISCHARGE TEMPERATURE SENSOR (T-6)
ZONE 1 AIR TEMPERATURE SENSOR (T-8)
ZONE 3 SUPPLY AIR DISCHARGE TEMPERATURE SENSOR (T-7)
NOT USESD
NOT USED
FILTER STATUS (DPS-1)
DI2
DI3
DI1
LOW LIMIT TEMPERATURE SENSOR (T-2) STATUS
SUPPLY FAN STATUS
KEYNOTES:
EXIST DDC CONTROL DEVICE MAY BE REUSEED IF FUNCTIONAL AND
COMPATIBLE.
EXISTING PNEUMATIC CONTROL DEVICE SHALL BE REPLACED WITH DDC
DEVICE.
EXIST DDC CONTROL DEVICE SHALL BE REPLACED.
REPLACE EXIST 3-WAY CHILLED WATER VALVE WITH 2-WAY.
PROVIDE NEW DDC CONTROLLER AND CONNECT TO EXISTING
ELECTRICAL SERVICES.
OUTSIDE AIR
DPS-1
T-8
C H
W R
SUPPLY
V-3
NCSTR
FAN
DI3
DO1
AI3
AO2
DI2DI1
AI13
AI7
AO4
PANEL
DDC CONTROL
AIR FILTER
T-2
D-1
T
AI10
T-5
L P
S
V-2
NO
AI5
T-4
AI4
AO3
AI6
TYP 3 ZONES
AI8
AO5
AI9
AO6
AI11
AI12
T-6
T-7 D-2
D-3
H W
R
V-1
NO
AI1
AO1
T
AI2
T-1
T-3
SEQUENCE OF OPERATION
1. GENERAL
1.1. ZONE 1 DIRECTLY SERVES COMMON SPACES. ZONES 2&3 SERVE FCU'S.
1.2. THE AIR HANDLING UNIT IS SCHEDULED FOR AUTOMATIC OPERATION ON A TIME OF DAY BASIS FOR
OCCUPIED AND UNOCCUPIED MODES.
1.3. WITHIN OCCUPIED MODE, THE SYSTEM CAN ENTER THE WARM-UP MODE WHEN THE SPACE
TEMPERATURE IS BELOW SETPOINT OR THE COOL-DOWN MODE WHEN THE SPACE TEMPERATURE IS
ABOVE SETPOINT. THE SYSTEM STAYS IN THE WARM-UP OR COOL-DOWN MODE UNTIL THE MODE
SETPOINT IS SATISFIED.
1.4. WITHIN THE UNOCCUPIED MODE, NIGHT HEATING IS AVAILABLE WHEN THE SPACE TEMPERATURE DROPS BELOW 65°F. THE LATEST START TIME IS THE SCHEDULED OCCUPANCY FOR THE SPACE.
1.5. ALL SUGGESTED SETPOINTS AND SETTINGS ARE ADJUSTABLE.
2. WARM-UP
2.1. THE SUPPLY FAN STARTS. THE OUTSIDE AIR DAMPER IS OPEN AND PREHEAT COIL MODULATES TO
MAINTAIN DISCHARGE TEMPERATURE OF 45°F AND COLD DECK COOLING COIL VALVE REMAIN
CLOSED. THE HOT DECK HEATING COIL VALVE MODULATES TO MAINTAIN THE HOT DECK SUPPLY
TEMPERATURE SETPOINT.
2.2. THE SYSTEM IS PREVENTED FROM ENTERING THE WARM-UP MODE MORE THAN ONCE PER DAY.
3. COOL-DOWN
3.1. THE SUPPLY FAN STARTS. THE HOT DECK HEATING COIL VALVE REMAINS CLOSED. THE COLD DECK
COOLING VALVE MODULATES TO MAINTAIN THE COLD DECK SUPPLY AIR TEMPERATURE AT
SETPOINT. THE OUTSIDE AIR DAMPER IS OPEN.
3.2. IF TIME REACHES THE LATEST START TIME DURING THE COOL-DOWN MODE, THE OUTDOOR AIR
DAMPER OPENS.
3.3. THE SYSTEM IS PREVENTED FROM ENTERING COOL-DOWN MODE MORE THAN ONCE PER DAY.
4. OCCUPIED
4.1. THE SUPPLY AIR TEMPERATURE SETPOINT FOR ZONE 1 IS RESET BASED ON THE ROOM
TEMPERATURE SETPOINT. SUPPLY AIR TEMPERATURE SETPOINT FOR ZONE 2&3 SHALL BE 55°F
WHEN OA DEWPOINT IS GREATER THAN 55°F AND RESET BETWEEN 55° & 75°F WHEN OA DEWPOINT IS BELOW 55°F BASED ON FCU VALVE POSITION TO MINIMIZE SIMULTANEOUS HEATING AND COOILING
AT THE FCU LEVEL.
4.2. HOT DECK AIR TEMPERATURE SETPOINT SHALL BE 95°F AND RESET BETWEEN 95°F AND 75°F BASED
ON ZONE 1 HEATING DEMAND. HEATING SHALL BE DISABLED WHEN OA IS ABOVE 70°F.
4.3. COLD DECK AIR TEMPERATURE SETPOINT SHALL BE 55°F WHEN OA DWPIONT IS GREATER THAN 55°F
AND RESET BETWEEN 55°F & 75°F BASED ON ZONE 1 COOLING DEMAND.
4.4. SUPPLY AIR DISCHARGE DAMPERS MODULATE TO MAINTAIN SUPPLY AIR TEMPERATURE SETPOINT
FOR EACH ZONE.
4.5. THE FAN STARTS OR CONTINUES TO RUN AND THE UNIT IS CONTROLLED AS FOLLOWS:
4.5.1. THE PREHEAT COIL MODULATES TO MAINTAIN A DISCHARGE TEMPERATURE OF 45°F
(ADJUSTABLE).
4.5.2. THE HOT DECK HEATING COIL VALVE MODULATES TO MAINTAIN THE HOT DECK AIR
TEMPERATURE SETPOINT.
4.5.3. THE COLD DECK COOILING COIL VALVE MODULATES TO MAINTAIN THE COLD DECK AIR
TEMPERATURE SETPOINT.
4.5.4. THE OUTSIDE AIR DAMPER IS OPEN.
5. UNOCCUPIED
5.1. THE FAN IS OFF, THE COLD DECK COOLING COIL VALVE CLOSES, AND THE OUTSIDE AIR DAMPER IS
CLOSED. THE HOT DECK HEATING COIL VALVE OPENS.
6. NIGHT HEATING
6.1. THE SUPPLY FAN STARTS WITH THE PREHEAT COIL MODULATING TO MAINTAIN DISCHARGE TEMPERATURE OF 45°F AND HOT DECK HEATING COIL VALVE OPEN TO MAINTAIN A MIN. SPACE TEMPERATURE OF 65°F IN ANY OF THE ZONES. THE COLD DECK COOLING COIL VALVE SHALL REMAIN
CLOSED AND THE OUTSIDE AIR DAMPER IS OPEN.
7. ALARMS
7.1. WHEN THE OAT IS LESS THAN 45°F, THE HOT DECK HEATING COIL VALVE MODULATES TO MAINTAIN THE HOT DECK AIR TEMPERATURE AT 45°F AND THE COLD DECK COOLING VALVE OPENS. WHEN THE OAT IS 45°F OR ABOVE, THE HOT DECK HEATING VALVE AND THE COLD DECK COOLING VALVE CLOSE.
ALL OTHER DAMPERS AND VALVES POSITION TO THEIR NORMAL POSITIONS AFTER THE FAN IS
EN-ENERGIZED.
7.2. A LOW TEMPERATURE DETECTOR IN THE DISCHARGE OF THE HEATING COIL DE-ENERGIZES THE SUPPLY FAN WHEN TEMPERATURES BELOW 38°F ARE SENSED. THE HOT DECK HEATING COIL VALVE MODULATES TO MAINTAIN THE HOT DECK AIR TEMPERATURE AT 45°F AND THE COLD DECK COOLING VALVE OPENS. ALL OTHER DAMPERS AND VALVES POSITION TO THEIR NORMAL POSITIONS AFTER
THE FAN IS DE-ENERGIZED.
7.3. A CURRENT SWITCH IS INSTALLED IN THE SUPPLY FAN STARTER. THE DDC SYSTEM USES THIS SWITCH TO CONFIRM THE FAN IS IN THE DESIRED STATE (I.E. ON OR OFF) AND GENERATES AN
ALARM IF STATUS DEVIATES FROM DDC START/STOP CONTROL.
2 4
COIL
HTG
COIL
CLG
T T
T
T
ZONE 1 THERMOSTAT
COIL
PREHEAT
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
9AC-1 CONTROL SCHEMATIC
& SEQUENCE
9 WLP NMT
M9-200
AIR HANDLING UNITS BALANCING SCHEDULE
LABEL AREA SERVED SUPPLY CFM OA CFM
COOLING COIL
GPM
PREHEAT
COIL LBS/HR
REHEAT COIL
LBS/HR
9AC-1
FCU'S ON NORTHEAST
WING OF FLOORS 1-3
5300 5300 92.0 388 135
9AC-2
FCU'S ON SOUTHWEST
WING OF FLOORS 1-3
4000 4000 74.0 275 115
9AC-3
FCU'S & VAV BOXES IN
1ST FLOOR DINING &
CENTRAL OFFICES
4155 1100 36.0 270 -
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE AIR HANDLING UNIT IS SCHEDULED FOR AUTOMATIC OPERATION ON A TIME OF DAY BASIS FOR
OCCUPIED AND UNOCCUPIED MODES.
1.2. WITHIN OCCUPIED MODE, THE SYSTEM CAN ENTER THE WARM-UP MODE WHEN THE SPACE
TEMPERATURE IS BELOW SETPOINT OR THE COOL-DOWN MODE WHEN THE SPACE TEMPERATURE IS
ABOVE SETPOINT. THE SYSTEM STAYS IN THE WARM-UP OR COOL-DOWN MODE UNTIL THE MODE
SETPOINT IS SATISFIED.
1.3. WITHIN THE UNOCCUPIED MODE, NIGHT HEATING IS AVAILABLE WHEN THE SPACE TEMPERATURE DROPS BELOW 65°F. THE LATEST START TIME IS THE SCHEDULED OCCUPANCY FOR THE SPACE.
1.4. ALL SUGGESTED SETPOINTS AND SETTINGS ARE ADJUSTABLE.
2. WARM-UP
2.1. THE SUPPLY FAN STARTS. THE OUTSIDE AIR DAMPER IS OPEN AND PREHEAT COIL AND COLD DECK
COOLING COIL VALVE REMAIN CLOSED. THE HOT DECK HEATING COIL VALVE MODULATES TO
MAINTAIN THE HOT DECK SUPPLY AIR TEMPERATURE SETPOINT.
2.2. IF TIME REACHES THE LATEST START TIME DURING THE WARM-UP MODE, THE OUTDOOR AIR
DAMPER OPENS TO ITS MIN. POSITION.
2.3. THE SYSTEM IS PREVENTED FROM ENTERING THE WARM-UP MODE MORE THAN ONCE PER DAY.
3. COOL-DOWN
3.1. THE SUPPLY FAN STARTS. THE HOT DECK HEATING COIL VALVE REMAINS CLOSED. THE COLD DECK
COOLING COIL VALVE MODULATES TO MAINTAIN THE COLD DECK SUPPLY AIR TEMPERATURE AT
SETPOINT. THE OUTSIDE AIR DAMPER IS OPEN.
3.2. IF TIME REACHES THE LATEST START TIME DURING THE COOL-DOWN MODE, THE OUTDOOR AIR
DAMPER OPENS.
3.3. THE SYSTEM IS PREVENTED FROM ENTERING COOL-DOWN MODE MORE THAN ONCE PER DAY.
4. OCCUPIED
4.1. THE SUPPLY AIR TEMPERATURE SETPOINT FOR ZONE 1 IS RESET BASED ON THE ROOM
TEMPERATURE SETPOINT. SUPPLY AIR TEMPERATURE SETPOINT FOR ZONE 2&3 SHALL BE 55°F
WHEN OA DEWPOINT IS GREATER THAN 55°F AND RESET BETWEEN 55° & 75°F WHEN OA DEWPOINT IS BELOW 55°F BASED ON FCU VALVE POSITION TO MINIMIZE SIMULTANEOUS HEATING AND COOILING
AT THE FCU LEVEL.
4.2. HOT DECK AIR TEMPERATURE SETPOINT SHALL BE 95°F AND RESET BETWEEN 95°F AND 75°F BASED
ON ZONE 1 HEATING DEMAND. HEATING SHALL BE DISABLED WHEN OA IS ABOVE 70°F.
4.3. COLD DECK AIR TEMPERATURE SETPOINT SHALL BE 55°F WHEN OA DWPIONT IS GREATER THAN 55°F
AND RESET BETWEEN 55°F & 75°F BASED ON ZONE 1 COOLING DEMAND.
4.4. SUPPLY AIR DISCHARGE DAMPERS MODULATE TO MAINTAIN SUPPLY AIR TEMPERATURE SETPOINT
FOR EACH ZONE.
4.5. THE FAN STARTS OR CONTINUES TO RUN AND THE UNIT IS CONTROLLED AS FOLLOWS:
4.5.1. THE PREHEAT COIL MODULATES TO MAINTAIN A DISCHARGE PRESSURE OF 45°F (ADJUSTABLE).
4.5.2. THE HOT DECK HEATING COIL VALVE MODULATES TO MAINTAIN THE HOT DECK AIR
TEMPERATURE SETPOINT.
4.5.3. THE COLD DECK COOLING COIL VALVE MODULATES TO MAINTAIN THE COLD DECK AIR
TEMPERATURE SETPOINT.
4.5.4. THE OUTSIDE AIR DAMPER IS OPEN.
5. UNOCCUPIED
5.1. THE FAN IS OFF, THE COLD DECK COOLING COIL VALVE CLOSES, AND THE OUTSIDE AIR DAMPER IS
CLOSED. THE HOT DECK HEATING COIL VALVE OPENS.
6. NIGHT HEATING
6.1. THE SUPPLY FAN STARTS WITH THE HOT DECK HEATING COIL VALVE OPEN TO MAINTAIN A MIN.
SPACE TEMPERATURE OF 65°F IN ANY OF THE ZONES. THE COLD DECK COOLING COIL VALVE
REMAINS CLOSED AND PREHEAT VALVE MODULATES TO MAINTAIN DISCHARGE TEMPERATURE OF
45°F AND THE OUTSIDE AIR DAMPER IS OPEN.
7. ALARMS
7.1. WHEN THE OAT IS LESS THAN 45°F, THE HOT DECK HEATING COIL VALVE MODULATES TO MAINTAIN THE HOT DECK AIR TEMPERATURE AT 45°F AND THE COLD DECK COOLING VALVE OPENS. WHEN THE OAT IS 45°F OR ABOVE, THE HOT DECK HEATING COIL VALVE AND THE COLD DECK COOLING VALVE CLOSE. ALL OTHER DAMPERS AND VALVES POSITION TO THEIR NORMAL POSITIONS AFTER THE FAN
IS EN-ENERGIZED.
7.2. A LOW TEMPERATURE DETECTOR IN THE DISCHARGE OF THE HEATING COIL DE-ENERGIZES THE SUPPLY FAN WHEN TEMPERATURES BELOW 38°F ARE SENSED. THE HOT DECK HEATING COIL VALVE MODULATES TO MAINTAIN THE HOT DECK AIR TEMPERATURE AT 45°F AND THE COLD DECK COOLING VALVE OPENS. ALL OTHER DAMPERS AND VALVES POSITION TO THEIR NORMAL POSITIONS AFTER
THE FAN IS DE-ENERGIZED.
7.3. A CURRENT SWITCH IS INSTALLED IN THE SUPPLY FAN STARTER. THE DDC SYSTEM USES THIS SWITCH TO CONFIRM THE FAN IS IN THE DESIRED STATE (I.E. ON OR OFF) AND GENERATES AN
ALARM IF STATUS DEVIATES FROM DDC START/STOP CONTROL.
KEYNOTES:
EXIST DDC CONTROL DEVICE MAY BE REUSEED IF FUNCTIONAL AND
COMPATIBLE.
EXISTING PNEUMATIC CONTROL DEVICE SHALL BE REPLACED WITH DDC
DEVICE.
EXIST DDC CONTROL DEVICE SHALL BE REPLACED.
REPLACE 3-WAY CHILLED WATER VALVE WITH 2-WAY.
PROVIDE NEW DDC CONTROLLER AND CONNECT TO EXISTING ELECTRICAL
SERVICES.
2 4
DI3
DO1
AI3
AO2
DI2DI1 AI7
AO4
PANEL
DDC CONTROL
AI9AI5
AI4
AO3
AI6
AI8
AO5
AI1
AO1
AI2
OUTSIDE AIR
DPS-1
C H
W R
SUPPLY
V-3
NCSTR
FAN
AIR FILTER
T-2
D-1 T-5
L P
S
V-2
NO
T-3
TYP 2 ZONES
T-6D-2
L P
S
V-1
NO
T
T-1
T-4
COIL
HTG
COIL
CLG
T
T
T
COIL
PREHEAT
T
T-7
AI11
T
ZONE 1 THERMOSAT
AI10
PREHEAT CONTROL VALVE (V-1)AO1
CHILLED WATER CONTROL VALVE (V-3)AO2
AO3 STEAM CONTROL VALVE (V-2)
AO4
AO5
ZONE 1 SUPPLY AIR DISCHARGE DAMPER (D-1) CONTROLLER
ZONE 2 SUPPLY AIR DISCHARGE DAMPER (D-2) CONTROLLER
SUPPLY FAN START/STOPDO1
PREHEAT CONTROL VALVE (V-1)
PREHEAT COIL DISCHARGE AIR TEMPERATURE SENSOR (T-1)AI2
AI1
CHILLED WATER CONTROL VALVE (V-2)AI3
STEAM CONTROL VALVE (V-3)AI4
AI6
AI7
AI5
AI8
AI10
AI11
AI9
AI12
COLD DECK TEMPERATURE SENSOR (T-3)
HOT DECK TEMPERATURE SENSOR (T-4)
ZONE 1 SUPPLY AIR DISCHARGE DAMPER (D-1)
ZONE 2 SUPPLY AIR DISCHARGE DAMPER (D-2)
ZONE 1 SUPPLY AIR DISCHARGE TEMPERATURE SENSOR (T-5)
ZONE 2 SUPPLY AIR DISCHARGE TEMPERATURE SENSOR (T-6)
ZONE 1 AIR TEMPERATURE SENSOR (T-7)
NOT USED
FILTER STATUS (DPS-1)
DI2
DI3
DI1
LOW LIMIT TEMPERATURE SENSOR (T-2) STATUS
SUPPLY FAN STATUS
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
9AC-2 CONTROL SCHEMATIC
& SEQUENCE
9 WLP NMT
M9-201
SUPPLY
VFD
FAN
DO3
DI6
COIL
L P
S
V-1
NO
HTG
AI4
AO1DO1
DI1 AI3
PANEL
DDC CONTROL
H-1
OUTSIDE AIR
D-1
AI2
RETURN AIRT-2
C H
W R
COIL
CLG
V-2
NC
AI5
AO2
AI8
T-5
SPS-1
AI7
AIR
FILTER
DI4
T-3
DI2
D02
D-2
AI1
T-1
D-2
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE AIR HANDLING UNIT IS SCHEDULED FOR AUTOMATIC OPERATION ON A TIME OF DAY BASIS FOR OCCUPIED
AND UNOCCUPIED MODES.
1.2. WITHIN OCCUPIED MODE, THE SYSTEM CAN ENTER THE WARM-UP MODE WHEN THE SPACE TEMPERATURE IS BELOW SETPOINT OR THE COOL-DOWN MODE WHEN THE SPACE TEMPERATURE IS ABOVE SETPOINT. THE SYSTEM STAYS IN THE WARM-UP OR COOL-DOWN MODE UNTIL THE MODE SETPOINT IS SATISFIED.
1.3. WITHIN THE UNOCCUPIED MODE, NIGHT HEATING IS AVAILABLE WHEN THE SPACE TEMPERATURE DROPS BELOW
65°F. THE LATEST START TIME IS THE SCHEDULED OCCUPANCY FOR THE SPACE.
1.4. ALL SUGGESTED SETPOINTS AND SETTINGS ARE ADJUSTABLE.
2. WARM-UP
2.1. THE SUPPLY FAN STARTS. THE RETURN AIR DAMPER IS OPEN, THE OUTSIDE AIR DAMPER IS CLOSED, AND COOLING COIL VALVE REMAIN CLOSED. THE HEATING COIL VALVE MODULATES TO MAINTAIN THE HEATING AIR
TEMPERATURE SETPOINT.
2.2. IF TIME REACHES THE LATEST START TIME DURING THE WARM-UP MODE, THE OUTDOOR AIR DAMPER OPENS TO
ITS MIN. POSITION.
2.3. THE SYSTEM IS PREVENTED FROM ENTERING THE WARM-UP MODE MORE THAN ONCE PER DAY.
3. COOL-DOWN
3.1. THE SUPPLY FAN STARTS AND THE HEATING COIL VALVE REMAINS CLOSED. THE COOLING COIL VALVE AND RETURN AIR AND OUTSIDE AIR DAMPERS MODULATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE AT SETPOINT.
3.2. WHEN THE OUTSIDE AIR DRY BULB TEMPERATURE IS ABOVE THE ECONOMIZER CHANGEOVER VALUE, THE MIXING
DAMPERS ARE POSITIONED FOR 100% RETURN AIR.
3.3. IF TIME REACHES THE LATEST START TIME DURING THE COOL-DOWN MODE, THE OUTDOOR AIR DAMPER OPENS
TO ITS MIN. POSITION OR IS CONTROLLED IN ECONOMIZER OPERATION.
3.4. THE SYSTEM IS PREVENTED FROM ENTERING COOL-DOWN MODE MORE THAN ONCE PER DAY.
4. OCCUPIED
4.1. THE FAN STARTS OR CONTINUES TO RUN AND THE UNIT IS CONTROLLED AS FOLLOWS:
4.1.1. WHEN THE OUTSIDE AIR DRY BULB TEMPERATURE IS BELOW THE 70°F AND THE OA ENTHALPY IS BELOW THE RA ENTHALPY, THE HEATING COIL VALVE, COOLING COIL VALVE, AND RETURN AIR AND OUTSIDE AIR DAMPERS MODULATE IN SEQUENCE WITHOUT OVERLAP TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT WITH A LOW LIMIT OF 48°F AT THE MIXED AIR SENSOR. THE MIXING DAMPERS OPEN SLOWLY TO
MINIMIZE OVERSHOOTING. MAXIMUM OA VALUE SHALL BE SET TO PREVENT BUILDING OVER
PRESSURIZATION.
4.1.2. WHEN THE OUTSIDE AIR DRY BULB TEMPERATURE IS ABOVE ABOVE 70° OR THE OA ENTHALPY IS ABOVE THE RA ENTHALPY, THE RETURN AIR AND OUTSIDE AIR DAMPERS ARE PLACED IN THE MIN. OUTDOOR AIR POSITION. THE HEATING COIL VALVE AND COOLING COIL VALVE MODULATE IN SEQUENCE WITHOUT OVERLAP TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. SUPPLY AIR TEMPERATURE SETPOINT SHALL BE 55°F. WHEN OA DEQPOINT IS BELOW 55°F THE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE RESET BASED
ON TERMINAL BOX DEMAND.
5. UNOCCUPIED
5.1. THE SUPPLY FAN STOPS, THE COOLING COIL VALVE CLOSES AND THE MIXING DAMPERS CLOSE TO THE OUTDOOR AIR. IF THE OAT IS LESS THAN 45°F, THE HEATING COIL VALVE MODULATES TO MAINTAIN THE UNOCCUPIED SUPPLY AIR SETPOINT. IF THE OAT IS 45°F OR ABOVE, THE HEATING COIL VALVE CLOSES.
6. NIGHT HEATING
6.1. THE SUPPLY FAN STARTS WITH THE HEATING COIL VALVE OPEN TO MAINTAIN A MIN. SPACE TEMPERATURE OF 65°F. THE OUTSIDE AIR DAMPER IS CLOSED, THE RETUREN AIR DAMPER IS OPEN AND THE COOLING COIL VALVE
REMAINS CLOSED.
7. NIGHT COOLING
7.1. THE SUPPLY FAN STARTS WITH THE COOLING COIL VALVE OPEN TO MAINTAIN A MIN. SPACE TEMPERATURE OF 85°F. THE OUTSIDE AIR DAMPER IS CLOSED, THE RETURN AIR DAMPER IS OPEN, AND THE HEATING COIL VALVE
REMAINS CLOSED.
8. STATIC PRESSURE CONTROL
8.1. THE SUPPLY FAN VFD MODULATES TO MAINTAIN A CONSTANT DUCT STATIC PRESSURE OF 1.5 INCHES OF WATER
AS SENSED AT LEAST 2
3 OF THE WAY DOWNSTREAM OF THE SUPPLY FAN IN THE LONGEST OR MOST CRITICAL
DUCT. STATIC PRESSURE SETPOINT SHALL BE RESET BASED ON TERMINAL BOX DAMPER POSITIONS TO MINIMIZE
FAN ENERGY.
8.2. UPON INITIAL STARTUP OF THE AIR HANDLING SYSTEM, THE SUPPLY FAN SPEED SLOWLY RAMPS TO THE
DESIRED STATIC PRESSURE SETPOINT.
8.3. UPON SHUTDOWN OF THE AIR HANDLING SYSTEM, THE SUPPLY FAN VFD STOPS AND THE SPEED SIGNAL GOES
TO ZERO SPEED.
9. ALARMS
9.1. DISCHARGE HIGH STATIC CUTOUT, SMOKE DETECTORS IN THE SUPPLY AND RETURN AIR STREAMS, AND SUPPLY FAN VFD FAULT ALARMS DE-ENERGIZE THE SUPPLY FAN UPON ACTIVATION. WHEN THE OAT IS LESS THAN 45°F, THE HEATING COIL VALVE MODULATES TO MAINTAIN THE MIXED AIR TEMPERATURE AT 45°F. WHEN THE OAT IS 45°F OR ABOVE, THE HEATING COIL VALVE CLOSES. ALL OTHER DAMPERS AND VALVES POSITION TO THEIR
NORMAL POSITIONS AFTER THE FAN IS EN-ENERGIZED.
9.2. A LOW TEMPERATURE DETECTOR IN THE DISCHARGE OF THE HEATING COIL DE-ENERGIZES THE SUPPLY FAN WHEN TEMPERATURES BELOW 38°F ARE SENSED. THE HEATING COIL VALVE MODULATES TO MAINTAIN THE HOT DECK AIR TEMPERATURE AT 45°F. ALL OTHER DAMPERS AND VALVES POSITION TO THEIR NORMAL POSITIONS
AFTER THE FAN IS DE-ENERGIZED.
9.3. A CURRENT SWITCH IS INSTALLED ON THE LOAD SIDE OF THE SUPPLY FAN VFD. THE DDC SYSTEM USES THIS SWITCH TO CONFIRM THE FAN IS IN THE DESIRED STATE (I.E. ON OR OFF) AND GENERATES AN ALARM IF STATUS DEVIATES FROM DDC START/STOP CONTROL. THE DDC SYSTEM GENERATES A VFD TROUBLE ALARM
INDEPENDENT FROM THE FAN STATUS.
KEYNOTES:
EXIST DDC CONTROL DEVICE MAY BE REUSEED IF FUNCTIONAL AND
COMPATIBLE.
EXISTING PNEUMATIC CONTROL DEVICE SHALL BE REPLACED WITH DDC
DEVICE.
NEW DDC DEVICE.
EXISTING DDC DEVICE SHALL BE REPLACED.
REPLACE 3-WAY CHILLED WATER VAVLE WITH 2-WAY.
PROVIDE NEW DDC CONTROLLER AND CONNECT TO EXISTING ELECTRICAL
SERVICES.
SD-2SD-1
AI6
AO3
2 5
EXISTING BYPASS
DAMPER TO BE
REMOVED. CAP AND
SEAL BOTH
REMAINING DUCT
OPENINGS.
DI5
T-4
1 1
1 1
TH
T T T T
DI3 DI7
STEAM CONTROL VALVE (V-1)AO1
CHILLED WATER CONTROL VALVE (V-2)AO2
AO3 SUPPLY FAN VFD SPEED
OUTSIDE AIR DAMPER (D-1) STATUSDO1
MIXED AIR TEMPERATURE SENSOR (T-1)
RETURN AIR HUMIDITY SENSOR (H-1)AI2
AI1
STEAM CONTROL VALVE (V-1)AI4
AI6
AI7
AI5
AI8
CHILLED WATER CONTROL VALVE (V-2)
SUPPLY FAN VFD STATUS
STATIC PRESSURE SENSOR (SPS-1) STATUS
SUPPLY AIR DISCHARGE TEMPERATURE SENSOR (T-5)
OUTSIDE AIR DAMPER (D-1)
DI2
DI3
DI1
RETURN AIR DAMPER (D-2)
MIXED AIR SMOKE DETECTOR (SD-1)
LOW LIMIT TEMPERATURE SENSOR (T-3) STATUS
DI5
DI6
DI4
HIGH LIMIT TEMPERATURE SENSOR (T-4) STATUS
SUPPLY FAN STATUS
DI7 SUPPLY AIR DISCHARGE SMOKE DETECTOR (SD-2)
RETURN AIR DAMPER (D-2) STATUSDO2
SUPPLY FAN START/STOPDO3
RETURN AIR TEMPERATURE SENSOR (T-2)AI3
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
9AC-3 CONTROL SCHEMATIC
& SEQUENCE & SMOKE DAMPER
CONTROL SCHEMATIC
9 WLP NMT
M9-202
H-2 T-6 3 3
TH
AI10AI9
AI9 STATIC PRESSURE SENSOR (SPS-2) STATUS
AI10 NOT USED
EXIST SMOKE
WALL
M
JB 120 V
POWER
SMOKE DETECTOR
AUX CONTACT
EXIST SMOKE
DAMPER
DEMO EXIST PNEUMATIC SMOKE
DAMPER CONTROL VALVE AND
PNEUMATIC LINES BACK TO MAIN.
REPLACE EXIST PNEUMATIC ACTUATOR WITH
ELECTRIC ACTUATOR. EXTEND EXIST POWER
AND CONTROL TO NEW ACTUATOR. CONNECT
TO FIRE ALARM SYSTEM.
TO OTHER SMOKE
DAMPERS.
SPS-2
AI9
SUPPLY
AIR
INSTALL NEW STATIC
PRESSURE SENSOR 2
DOWN LONGEST RUN.
SCHWS
SCHWR
STR
HWS HWS
HWR HWR
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE HOT WATER SYSTEM CONSISTS OF HOT WATER PUMPS WITH INDIVIDUAL VARIABLE FREQUENCY DRIVES (VFD) AND TWO STEAM HEAT
EXCHANGERS. THE SYSTEM IS DDC CONTROLLED WITH ELECTRIC ACTUATION.
1.2. THE SYSTEM IS ON WHEN ANY FCU OR REHEAT COIL CALLS FOR HEATING.
2. HEAT EXCHANGER CONTROL
1.1 ONCE FLOW IS PROVEN BY FLOW SWITCH AT EXCHANGER, STEAM CONTROL VALVES SHALL MODULATE TO MAINTAIN THE HOT WATER SUPPLY
TEMPERATURE AT SETPOINT.
1.2 THE HOT WATER SUPPLY TEMPERATURE RESETS INVERSELY WITH THE OUTDOOR TEMPERATURE AS SCHEDULED: AT 30°F OA - HWS AT 180°F, AT
70°F OA - HWS AT 140°F.
1.3 STEAM HOT WATER CONVERTERS ARE 100% REDUNDANT AND ONLY ONE UNIT AT A TIME WILL OPERATE.
3. HOT WATER PUMP ALTERNATION
3.1. SECONDARY HOT WATER PUMPS ALTERNATE TO EQUALIZE RUNTIME. SELECTION OF THE LEAD PUMP IS EVALUATED ON A WEEKLY BASIS. THE PUMP WITH THE LEAST RUNTIME IS THE LEAD PUMP. THE PUMP WITH THE MOST RUNTIME IS THE LAG PUMP.
4. HOT WATER PUMP CONTROL
4.1. WHEN THE HOT WATER SYSTEM IS ON THE LEAD SECONDARY HOT WATER PUMP STARTS.
4.2. THE DDC SYSTEM USES CURRENT SWITCHES TO CONFIRM THE LEAD PUMP IS IN THE DESIRED STATE (I.E. ON OR OFF) AND GENERATES AN ALARM IF STATUS DEVIATES FROM DDC START/STOP CONTROL. IF THE LEAD PUMP GOES INTO ALARM, THE LAG PUMP STARTS.
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING DDC.
SENSOR, ACTUATORS, ETC MAY BE REUSED IF
FUNCTIONAL AND COMPATIBLE.
2. PROVIDE NEW CONTROLLER. CONNECT TO
EXISTING ELECTRICAL SERVICES.
3. PROVIDE NEW DIFFERENTIAL PRESSURE SENSOR.
4. PROVIDE NEW 10 HP VFD'S.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
T
T
AI3
STR
DI3
DO1
DI4
DO2
VFD
T
AI4
T
AI3
VFD
DI1
DO1
DI2
DO2
CAMPUS
CHWR
CAMPUS
CHWS
T AI4
RELOCATE EXISITNG
TEMPERATURE SENSOR TO
COMMON PIPE.
DI1
FS
STEAM CONV.
TO COND. PUMP
TO COND. PUMP
STEAM
SUPPLY
STEAM
SUPPLY
STEAM CONV.
AI1
DI2
FS
AO1
AI2
AO2
KEYNOTES
EXISTING DDC DEVICE MAY BE
REUSED IF IN FUNCTIONAL AND
COMPATABLE.
NEW DDC DEVICE TO BE INSTALLED.
EXISTING PNEUMATIC DEVICE TO BE
REPLACED WITH DDC DEVICE.3
S T
E A
M C
O N
V
TO COND. PUMP
AI1
AO1
STEAM
SUPPLY
DCWS
D H
W S
T
AI2
KEYNOTES:
EXISTING PNEUMATIC CONTROL DEVICE TO BE
REPLACED WITH NEW DDC DEVICE.
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE DOMESTIC HOT WATER SYSTEM IS ENABLED CONTINUOUSLY.
2. DOMESTIC HOT WATER CONVERTER CONTROL
2.1. STEAM CONTROL VAVLE V-1 & V-2 SHALL MODULATE TO MAINTAIN A DOMESTIC HOT WATER SUPPLY
TEMPERATURE SETPOINT OF 120°F (ADJUSTABLE).
AI2
AI1 STEAM CONTROL VALVE (V-1)
DOMESTIC HOT WATER SUPPLY TEMPERATURE
STEAM CONTROL VALVE (V-1)AO1
S T
E A
M C
O N
V
TO COND. PUMP
AI3
AO2
STEAM
SUPPLY
DCWS
D H
W S
T
AI4
AI4
AI3 STEAM CONTROL VALVE (V-2)
DOMESTIC HOT WATER SUPPLY TEMPERATURE
STEAM CONTROL VALVE (V-2)AO2
STEAM CONTROL VALVE (V-1)
STEAM CONTROL VALVE (V-2)AI2
AI1
AI4
HOT WATER RETURN TEMPERATURE SENSOR (T-1)
HOT WATER SUPPLY TEMPERATURE SENSOR (T-2)
STEAM CONVERTER FLOW SWITCH SENSOR STATUS
DI2
DI1
STEAM CONVERTER FLOW SWITCH SENSOR STATUS
AI3
V-1 V-2
V-1
V-2
T-1
T-2
STEAM CONTROL VALVE (V-1)AO1
STEAM CONTROL VALVE (V-2)AO2
CHILLED WATER PUMP 1 VFD STATUS
CHILLED WATER PUM 2 VFD STATUSAI2
AI1
AI4
DI1
CHILLED WATER SUPPLY TEMPERATURE SENSOR (T-2)
CHILLED WATER PUMP 1 START/STOP
CHILLED WATER RETURN TEMPERATURE (T-1)AI3
CHILLED WATER PUMP 1 VFD STATUSAO1
CHILLED WATER PUMP 2 VFD STATUSAO2
DO1 CHILLED WATER PUMP 1 START/STOP
T-1
T-2
DOMESTIC HOT WATER, HHW, &
SCHW SYSTEMS CONTROL
SCHEMATICS & SEQUENCES
9 WLP NMT
M9-203
NOTES:
1. PROVIDE DDC CONTROLLER. CONNECT
TO EXISTING ELECTRICAL SERVICES.
NOTES:
1. PROVIDE DDC CONTROLLER. CONNECT
TO EXISTING ELECTRICAL SERVICES.
PANEL
DDC CONTROL
EF9-4
DI1
DO1
EXHAUST FAN STATUSDI1
EXHAUST FAN START/STOPDO1
SEQUENCE OF OPERATION
1. START/STOP CONTROL
1.1. FAN TO RUN ON SCHEDULE (CONTINUOUSLY.)
2. ALARM
2.1. ALARM SHALL BE GENERATED WHEN STATUS
DOES NOT MATCH COMMAND.
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING
PNEUMATIC TO BE REPLACED WITH DDC
DEVICE TO FULLY INTEGRATE TO SIEMENS
CAMPUS SYSTEM.
AI1
AO1
AI2
AO2
DI2 CHILLED WATER PUMP 2 START/STOP
DO2 CHILLED WATER PUMP 2 START/STOP
SEQUENCE OF OPERATION
1. GENERAL
1.1 THE EXISTING CHILLED WATER SUPPLY FROM THE CENTRAL COOLING PLANT PROVIDES CHILLED WATER TO THE VFD SECONDARY PUMPING SYSTEM AT BUILDING 9. THE SECONDARY PUMPS ARE 100% REDUNDANT REQUIRING ONLY ONE PUMP AT A TIME TO OPERATE.
1.2 UPON A CALL FOR COOLING FROM ANY AIR HANDLER OR FAN COIL, THE LEAD CHILLED WATER PUMP SHALL ENERGIZE AND THE RESPECTIVE VFD SHALL MODULATE THE PUMP TO MAINTAIN THE DIFFERENTIAL PRESSURE SETPOINT (ADJUSTABLE) AT THE DIFFERENTIAL PRESSURE
SENSOR LOCATED 3
4 OF THE WAY DOWN THE LONGEST PIPING RUN. THE VFD WILL MODULATE AS REQUIRED TO MAINTAIN THE SYSTEM
PRESSURE SETPOINT. MIN. VFD SPEED SHALL BE 30%.
1.3 CHILLED WATER DIFFERENTIAL SETPOINT SHALL BE RESET BASED ON CHILLED WATER VALVE POSITIONS TO MINIMIZE PUMP SPEED.
4. LEAD/STANDBY PUMP CONTROL
2.1 IF THE LEAD BUILDING SECONDARY CHILLED WATER PUMP FAILS TO OPERATE, THE STANDBY PUMP SHALL BE AUTOMATICALLY STARTED, AND THE SYSTEM SHALL RESUME NORMAL OPERATION. AN ALARM WILL BE GENERATED AT THE DDC PANEL TO NOTIFY OF PUMP FAILURE.
2.2 THE LEAD/STANDBY STATUS OF THE PUMPS SHALL BE ROTATED EVERY 7 DAYS FOR EVEN RUNTIME.
P
LOCATED 3 4 DOWN LONGEST
RUN.
AI5
AI5 DIFFERENTIAL PRESSURE SENSOR
180 160 140
HOT WATER SETPOINT
(DEG F)
OUTDOOR
AIR
TEMPERATURE
(DEG F)
HEATING HOT WATER RESET
SCHEDULE
HOT WATER PUMP START/STOPDO1
HOT WATER PUMP START/STOPDO2
F
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
VAV, FCU & 9EF-4 CONTROL
SCHEMATICS & SEQUENCES
9 WLP NMT
M9-204
H W
R
AI3
PANEL
DDC CONTROL
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING JCI PNEUMATIC TO
BE REPLACED WITH DDC DEVICE TO FULLY INTEGRATE TO
SIEMENS CAMPUS SYSTEM.
2. 3-WAY HW VALVE TO BE REPLACED WITH 2-WAY.
3. PROVIDE NEW CONTROLLER. CONNECT NEW
CONTROLLER TO EXISTING ELECTRICAL SERVICE.
AO2
AI4
SEQUENCE OF OPERATION
1. OCCUPIED MODE
1.1. A SPACE SENSOR SHALL TRANSMIT ROOM TEMPERATURE TO THE BOX CONTROLLER,
WHICH SHALL VARY THE PRIMARY AIRFLOW AND VARY HEATING VALVE TO MAINTAIN
SPACE TEMPERATURE SETPOINTS.
1.2. A RISE IN SPACE TEMPERATURE ABOVE SETPOINT SHALL MODULATE PRIMARY
AIRFLOW TO MAXIMUM CFM INTO THE SPACE. A DROP IN SPACE TEMPERATURE ABOVE
SETPOINT SHALL MODULATE PRIMARY AIRFLOW TO MINIMUM CFM SETPOINT. A
FURTHER DROP IN SPACE TEMPERATURE SHALL MODULATE THE BOX REHEAT
CONTROL VALVE OPEN TO HEAT THE SPACE TO MAINTAIN SETPOINT +/- 0.5°F
(ADJUSTABLE). THE ADJUSTABLE TOLERANCE OF +/- 0.5°F HAS BEEN SELECTED TO
PREVENT VALVE HUNTING.
2. UNOCCUPIED MODE
2.1. WHEN THE SYSTEM IS INDEXED TO UNOCCUPIED MODE, THE AIR HANDLING UNIT
SHALL STOP, THE BOX DAMPER SHALL CLOSE AND THE REHEAT VALVE SHALL CLOSE.
IF THE SPACE TEMPERATURE FALLS BELOW THE NIGHT SETBACK POINT, THE AIR
HANDLING UNIT SHALL START, THE VAV BOX DAMPER SHALL OPEN, AND THE HEATING
VALVE SHALL OPEN TO ALLOW THE AIR HANDLING UNIT TO HEAT THE SPACE TO
UNOCCUPIED HEATING SETPOINT. IF THE SPACE TEMPERATURE RISES ABOVE THE
NIGHT CYCLE SETPOINT, THE AIR HANDLING UNIT SHALL START AND THE BOX
CONTROLLER SHALL VARY THE PRIMARY AIRFLOW TO COOL THE SPACE TO
UNOCCUPIED COOLING SETPOINT. A PUSH-BUTTON OVERRIDE ON THE SPACE
THERMOSTAT SHALL ALLOW OCCUPANTS TO INDEX THE SYSTEM TO OCCUPIED MODE
FOR AFTER-HOURS USE. THE BOX CONTROLLER SHALL FUNCTION PER OCCUPIED
MODE OF OPERATION UNTIL THE TEMPORARY OCCUPANCY TIMER EXPIRES, AT WHICH
TIME THE BOX CONTROLLER SHALL INDEX TO UNOCCUPIED MODE, SUBJECT TO TIME
OF DAY SCHEDULING.
3. MORNING WARM-UP MODE
3.1. WHEN THE SYSTEM IS INDEXED TO THE MORNING WARM-UP, THE SYSTEM SHALL SET
THE SPACE SENSOR TO ITS OCCUPIED HEATING TEMPERATURE. THE BOX
CONTROLLER SHALL INDEX THE PRIMARY AIRFLOW TO 100%, THE HEATING VALVE
SHALL OPEN AND ALLOW PRIMARY AIR TO HEAT THE SPACE WHEN THE RESPECTIVE
AIR HANDLING UNIT IS CYCLED TO MORNING WARM-UP. THE DAMPER AND HEATING
VALVE SHALL CLOSE WHEN THE SPACE IS SATISFIED AND THE AIR HANDLING UNIT IS
STILL IN WARM-UP MODE. WHEN THE AIR HANDLING UNIT RETURNS TO OCCUPIED
OPERATION, THE BOX SHALL INDEX TO OCCUPIED MODE OF OPERATION.
COIL
V-1
NC
REHEAT
T-2T
SPACE
THERMOSTAT
AI2
AI1
AI3
INLET AIR TEMPERATURE (T-1)
REHEAT CONTROL VALVE STATUS (V-1)
DAMPER STATUS
AO1 DAMPER STATUS
COIL
H W
R
V-2
NC
HTG
AI1
DO1
PANEL
DDC CONTROL
DI4
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING JCI
PNEUMATIC TO BE REPLACED WITH DDC DEVICE
TO FULLY INTEGRATE TO SIEMENS CAMPUS
SYSTEM.
2. EXISTING 3-WAY HW & CHW VALVES TO BE
REPLACED WITH 2-WAY.
3. PROVIDE NEW CONTROLLER. CONNECT NEW
CONTROLLER TO EXISTING ELECTRICAL SERVICE.
AO1
T-4T
AI4
STR
COIL
C H
W R
V-1
NC
CLG
AI2
AO2
SEQUENCE OF OPERATION
1. START/STOP CONTROL: FAN COIL SHALL OPERATE AS SET BY ECC. FAN SHALL RUN CONTINUOUSLY IN OCCUPIED MODE. THE UNIT FAN SHALL BE STARTED AND STOPPED VIA AN ASC THROUGH THE ECC.
WHEN FAN RUN STATUS IS PROVEN VIA A CURRENT SENSING RELAY, THE CONTROL LOOPS SHALL BE ENERGIZED. STOPPING THE UNIT SHALL DE-ENERGIZE THE CONTROL LOOPS AND HEATING HOT WATER
AND CHILLED WATER VALVES SHALL GO TO THE CLOSED POSITION.
2. SAFETIES: A RETURN AIR HIGH LIMIT THERMOSTAT IN THE RETURN AIR SHALL STOP THE UNIT UPON DETECTION OF TEMPERATURE ABOVE ITS SETPOINT. FIRESTATS SHALL BE PROVIDED FOR ANY FAN HANDLING 600 CFM OR MORE. FIRESTATS SHALL STOP ASSOCIATED FAN ON A RISE IN AIR TEMPERATURE ABOVE 125°F. LOW LIMIT THERMOSTAT IN THE RETURN AIR SHALL STOP THE UNIT UPON DETECTION OF
TEMPERATURE BELOW ITS SETPOINT.
3. TEMPERATURE CONTROL: SPACE TEMPERATURE SENSOR LOCATED AS SHOWN ON THE PLANS SHALL TRANSMIT TEMPERATURE CHANGES TO THE ASC. THE ASC SHALL MODULATE THE CHILLED WATER AND HEATING HOT WATER VALVES IN SEQUENCE TO MAINTAIN SPACE SETPOINT. AN ALARM MESSAGE SHALL BE GENERATED IN THE EVENT THE UNIT FAILS TO RUN BETWEEN THE RANGE OF 70°F-75°F (ADJUSTABLE) SPACE TEMPERATURE BOTH CHILLED AND HOT WATER VALVES SHALL BE CLOSED. UPON RISE IN TEMPERATURE ABOVE 75°F, THE CHILLED WATER VALVE SHALL MODULATE OPEN TO MAINTAIN 75°F (ADJUSTABLE). UPON A FALL IN TEMPERATURE BELOW 70°F, THE HEATING HOT WATER VALVE SHALL
MODULATE TO OPEN TO MAINTAIN 70°F (ADJUSTABLE).
4. FILTER STATUS SHALL BE MONITORED AT EACH FILTER BANK.
SPACE
THERMOSTAT
HEATING HOT WATER CONTROL VALVE (V-1)
CHILLED WATER CONTROL VALVE (V-2)AI2
AI1
HIGH LIMIT TEMPERATURE SENSOR (T-1) STATUSDI1
AO1
A02
UNIT FAN START/STOPDO1
HEATING HOT WATER CONTROL VALVE (V-1)
CHILLED WATER CONTROL VALVE (V-2)
FAN DISCHARGE AIR TEMPERATURE SENSOR (T-3)AI3
A
IR
F L O
W (C
F M
ROOM TEMPERATURE (°F)
HEATING
MINIMUM
VAV BOX CONTROL SEQUENCE
SP
NO DEADBAND
100% R
EH
EAT FLO
W
VAV A
IR
F
LO
W
T
T-1
AI2
AO1
M
AI1
DI3
T-2
T
DPS-1
DI2DI1
T-1
T T
T-3
AI3
G&B FAN COIL UNITS SCHEDULE
UNIT
SYMBOL
HW
GPM
CHW
GPM
O.A.
CFM
FAN
CFM
SPACE TEMPERATURE SENSOR (T-4)AI4
AIR FILTER STATUS (DPS-1)DI2
LOW LIMIT TEMPERATURE SENSOR (T-1) STATUSDI3
UNIT FAN STATUSDI4
AI1
PANEL
DDC CONTROL
AO1
AI3
COIL
V-1
NC
T-1T
SPACE
THERMOSTAT
T
DO1
DI2
STR
H W
R
HEATING
DPS-1
DI1
HOT WATER CONTROL VAVLE (V-1)
CHILLED WATER CONTROL VALVE (V-2)AI2
AI1
AIR FILTER STATUS (DPS-1)DI1
AO1
UNIT FAN START/STOPDO1
HOT CONTROL VALVE (V-1)
SPACE TEMPERATURE SENSOR (T-1)AI3
UNIT FAN STATUSDI2
RETURN
AIR
SUPPLY
AIR
OUTSIDE
AIR
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING PNEUMATIC TO BE
REPLACED WITH DDC DEVICE TO FULLY INTEGRATE TO
SIEMENS CAMPUS SYSTEM.
2. EXIST 3-WAY HW/CHW VALVES TO BE REPLACED WITH
2-WAY.
3. PROVIDE NEW CONTROLLER. CONNECT NEW
CONTROLLER TO EXISTING ELECTRICAL SERVICE.
PANEL
DDC CONTROL
EF9-4
DI1
DO1
EXHAUST FAN (EF9-4) STATUSDI1
EXHAUST FAN (EF9-4) START/STOPDO1
SEQUENCE OF OPERATION
1. START/STOP CONTROL
1.1. FAN TO RUN ON SCHEDULE (CONTINUOUSLY.)
1.2. FAN TO STOP WHEN SMOKE DAMPER CLOSES.
2. ALARM
2.1. ALARM SHALL BE GENERATED WHEN STATUS
DOES NOT MATCH COMMAND.
SMOKE
DAMPER
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING
PNEUMATIC TO BE REPLACED WITH DDC
DEVICE TO FULLY INTEGRATE TO SIEMENS
CAMPUS SYSTEM.
DI2
SMOKE DAMPER STATUSDI2
PANEL
DDC CONTROL
DAMPER STATUSAI1
DAMPER STATUSAO1
SEQUENCE OF…