36C25618U0323-0002002.pdf
PDF 5 MB Posted
- Attached to
- Services Commissioning for HVAC Digital Controls Federal contract opportunity
- Solicitation number
- 36C25618U0323
About this file
36C25618U0323 0002 Drawings - Building 45 Part 2 (M45-2XX Series).pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| -15380.docx | DOCX document | |
| 36C25618U0323-0002007.pdf | ||
| 36C25618U0323-0002005.pdf | ||
| 36C25618U0323-0002004.pdf | ||
| 36C25618U0323-0002006.pdf | ||
| 36C25618U0323-0002012.pdf | ||
| 36C25618U0323-0002000.docx | DOCX document | |
| 36C25618U0323-0002013.pdf | ||
| 36C25618U0323-0002010.pdf | ||
| 36C25618U0323-0002011.pdf | ||
| 36C25618U0323-0002009.pdf | ||
| 36C25618U0323-0002014.pdf | ||
| 36C25618U0323-0002001.docx | DOCX document | |
| 36C25618U0323-0002003.pdf | ||
| 36C25618U0323-0002008.pdf | ||
| 36C25618U0323-0001000.docx | DOCX document | |
| 36C25618U0323-002.pdf | ||
| 36C25618U0323-001.docx | DOCX document | |
| 36C25618U0323-000.docx | DOCX document |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPS-4
AI14
SPS-2
DI9
SUPPLY
VFD
FAN
DO3
AO3
DI8
AI9
COIL
L P
S
V-1
NO
PREHEAT
AI5
AO1
DI7DI2
D02DO1
DI1
SPS-1
AI2
SUPPLY
PANEL
DDC CONTROL
AI4
T-2
T
T-1
OUTSIDE AIR
D-1
DI3
D-2
T-9T
AI15
NOTES:
1. ALL DEVICES ARE EXISTING DDC. SENSOR, ACTUATORS, ETC. BE
REUSED IF FUNCTIONAL AND COMPATIBLE.
2. PROVIDE NEW CONTROLLER. CONNECT NEW CONTROLLER TO
EXISTING ELECTRICAL SERVICE.
3. ADJUST EXISTING SUPPLY AIR & RETURN AIR HIGH STATIC VENTS TO
PREVENT THEIR OPERATION PRIOR TO HIGH STATIC SHUTDOWN.
AI3
28" ROUND
RETURN AIR FROM
WEST DUCT CHASE
18" ROUND
RETURN AIR
FROM EAST
DUCT CHASE
FLOWMETER
H-1
AI6
T-3
T-4
C H
W R
COIL
CLG
V-2
NC
AI7
AO2
AI12
T-8
SPS-3
AI13
DPS-2
DI5
DPS-1
DI4AI1
AI10
AI11
F-1
F-2
F-3
AIR
FILTER
SD-1
DI11
SD-2
DI6
D-6
D-3
D-4
T-5
AI8
T-6
DI10
T-7
3/4 LONGEST
RUN. CONNECTED
TO V45-1-24 IN
LOBBY C1-1.
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE AIR HANDLING UNIT SHALL BE STARTED AND STOPPED AUTOMATICALLY AT THE ECC. THE HOA SWITCH SHALL BE KEPT IN THE AUTO POSITION. HAND AND OFF POSITIONS SHALL BE USED FOR
MAINTENANCE ONLY. UPON RECEIVING A START COMMAND THE SUPPLY FAN WILL START ONLY
AFTER ALL INTERNAL SAFETIES ARE PROVEN. ONCE FAN RUN STATUS IS PROVEN BY A CURRENT SENSING RELAY, THE CONTROLS SHALL OPERATE ACCORDING TO THE SEQUENCES AS DESCRIBED
BELOW.
2. AIR FLOW
2.1. OUTSIDE AIR IS METERED BY FLOWMETER, F-1, TO MONITOR AND MAINTAIN A CONSTANT MIN.
OUTSIDE AIR FLOW BY MODULATING THE RETURN DAMPER, D-2, AND OUTSIDE AIR DAMPER, D-1, UP
TO THE MAX. FLOW SETPOINT OF 3500 CFM (ADJUSTABLE).
3. TEMPERATURE CONTROL
3.1. TEMPERATURE SENSOR, T-3, IN THE PREHEAT COIL DISCHARGE SHALL TRANSMIT TEMPERATURE CHANGES TO THE DDC. THE DDC SYSTEM SHALL MODULATE THE 2-WAY STEAM PREHEAT CONTROL
VALVE, V-1, TO MAINTAIN PREHEAT TEMPERATURE SETPOINT (ADJUSTABLE).
3.2. TEMPERATURE SENSOR, T-8, IN THE SUPPLY AIR DUCT TRANSMITS TEMPERATURE CHANGES TO THE DDC. THE DDC MODULATES THE 2-WAY COOLING CONTROL VALVE, V-2, TO MAINTAIN DISCHARGE AIR
TEMPERATURE SETPOINT OF 55°F (ADJUSTABLE).
4. STATIC PRESSURE AND SUPPLY FAN SPEED CONTROL
4.1. THE VFD SHALL MODULATE THE SPEED OF THE SUPPLY FAN TO MAINTAIN DISCHARGE AIR STATIC PRESSURE TO ITS SETPOINT OF 1.0 IN. WC. (ADJUSTABLE) AS SENSED BY THE DUCT STATIC
PRESSURE SENSOR, SPS-4, LOCATED 3
4 OF THE WAY DOWN THE LONGEST DUCT MAIN.
4.2. THE SUPPLY FAN SPEED SHALL DECREASE TOWARDS ITS MIN. FREQUENCY. AS THE DISCHARGE AIR
STATIC PRESSURE DECREASES, THE SUPPLY FAN SPEED SHALL INCREASE.
4.3. THE STATIC PRESSURE IS RESET BASED ON ACTUAL BUILDING LOAD BY POLLING ALL VAV TERMINAL
UNITS.
5. DEHUMIDIFICATION CONTROL
5.1. WHEN THE OA DEW POINT IS ABOVE 55°F THE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE 55°F.
6. ALARMS
6.1. THE UNIT SHALL STOP UPON ANY OF THE SAFETIES BEING TRIPPED REGARDLESS OF THE MODE OF
OPERATION (AUTOMATIC, HAND OR BYPASS).
6.2. THE AIR HANDLER RETURN AIR SMOKE DETECTOR, SD-1, AND THE SUPPLY AIR SMOKE DETECTOR, SD-2, SHALL STOP THE UNIT AND CLOSE THE SMOKE DAMPERS UPON SENSING COMBUSTION
PRODUCTS IN THE SYSTEM. SMOKE DETECTORS MUST BE MANUALLY RESET AFTER AN ALARM
CONDITION IN ORDER FOR THE FAN TO RESTART AND THE SMOKE DAMPERS TO OPEN.
6.3. A MIXED AIR TEMPERATURE SENSOR, T-2, UPSTREAM OF THE COOLING COIL SIGNALS THE DDC UPON
A DROP IN TEMPERATURE BELOW 45°F, WHICH SHALL GENERATE AN ALARM TO THE ECC.
6.4. A TEMPERATURE LOW LIMIT SWITCH, T-4 OR T-5, SHALL STOP THE UNIT, CLOSE THE OUTSIDE AIR DAMPER, OPEN THE PREHEAT VALVE, AND SEND A CRITICAL ALARM TO THE ECC UPON SENSING A FALL IN TEMPERATURE BELOW SETPOINT (40°F ADJUSTABLE). THE LOW LIMIT SWITCHES MUST BE
MANUALLY RESET AFTER AN ALARM CONDITION.
6.5. A TEMPERATURE HIGH LIMIT, T-7, WILL SHUTDOWN THE FAN AND SEND AN ALARM TO THE ECC UPON A RISE IN DISCHARGE AIR ABOVE 125°F. THE HIGH LIMIT SWITCH MUST BE MANUALLY RESET AFTER
AN ALARM.
6.6. A DISCHARGE AIR HIGH STATIC PRESSURE SAFETY SWITCH, SPS-2, LOCATED AT THE SUPPLY FAN DISCHARGE WILL STOP THE UNIT UPON SENSING HIGH SUPPLY DUCT STATIC ABOVE 3 IN. STATIC
PRESSURE (ADJUSTABLE) TO PREVENT OVER PRESSURIZING THE DUCTWORK. STATIC PRESSURE
SWITCH IS HARDWIRED TO THE VFD AND UNIT IS SHUTDOWN IN HAND, AUTO, OR BYPASS MODE. THE
HIGH STATIC PRESSURE SAFETIES MUST BE MANUALLY RESET AFTER AN ALARM CONDITION.
6.7. UPON FAILURE OF THE VFD, THE SUPPLY FAN SHALL BE CONTROLLED MANUALLY AT THE DDC PANEL
OR THE ECC THROUGH THE BYPASS STARTER. FAN SHALL BE OPERATED AT CONSTANT SPEED.
7. MONITORING
7.1. THE DCC SYSTEM MONITORS THE DIFFERENTIAL PRESSURE ACROSS EACH FILTER AND GENERATES AN ALARM IF THE DIFFERENTIAL PRESSURE INCREASES ABOVE THE SETPOINT OF 0.75 IN. WC.
(ADJUSTABLE) TO PROVIDE NOTIFICATION OF A DIRTY FILTER.
8. SHUTDOWN
8.1. STOPPING THE UNIT SHALL DE-ENERGIZE THE CONTROL LOOPS AND SEND THE CONTROL VALVES TO THE CLOSED POSITION. THE OUTSIDE AIR DAMPER SHALL CLOSE AND THE RETURN AIR DAMPER
SHALL OPEN.
H
T T T T T T T
OUTSIDE AIR FLOWMETER (F-1)
RETURN AIR TEMPERATURE SENSOR (T-1)AI2
AI1
RETURN AIR HUMIDITY SENSOR (H-1)AI3
MIXED AIR TEMPERATURE SENSOR (T-2)AI4
AI6
AI7
AI5
AI8
AI10
AI11
AI9
AI12
AI13
AI14
AI15
PREHEAT STEAM CONTROL VALVE (V-1)
PREHEAT COIL DISCHARGE AIR TEMPERATURE SENSOR (T-3)
CHILLED WATER CONTROL VALVE (V-2)
COOLING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-5)
SUPPLY FAN VFD STATUS
RETURN AIR WEST CHASE FLOWMETER (F-3)
RETURN AIR EAST CHASE FLOWMETER (F-2)
SUPPLY AIR STATIC PRESSURE SENSOR (SPS-3)
SUPPLY AIR TEMPERATURE SENSOR (T-8)
DISCHARGE AIR STATIC PRESSURE SENSOR (SPS-4)
AMBIENT AIR TEMPERATURE SENSOR (T-9)
DI10
DI11 SUPPLY AIR SMOKE DETECTOR (SD-2) STATUS
HIGH LIMIT TEMPERATURE SENSOR (T-6) STATUS
DI8
DI6
DI7
DI4
DI2
DI3
DI1
DI5
RETURN AIR DAMPER (D-2) STATUS
RETURN AIR SMOKE DETECTOR (SD-1) STATUS
FILTER STATUS (DPS-1)
FILTER STATUS (DPS-2)
DI9
OUTSIDE AIR DAMPER (D-1) STATUS
SUPPLY AIR HIGH LIMIT STATIC PRESSURE SWITCH (SPS-2) STATUS
LOW LIMIT TEMPERATURE SENSORS (T-4 & T-5) STATUS
SUPPLY FAN STATUS
RETURN AIR STATIC PRESSURE LIMIT SENSOR (SPS-1) STATUS
PREHEAT STEAM CONTROL VALVE (V-1)
CHILLED WATER CONTROL VALVE (V-2)
AO1
AO2
AO3
DO1
DO2
DO3
SUPPLY FAN VFD SPEED
OUTSIDE AIR DAMPER (D-1)
RETURN AIR DAMPER (D-2)
SUPPLY FAN START/STOP
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
AMBIENT AIR
TEMPERATURE SENSOR
SMOKE
DAMPER
D-5
45-AHU-01 CONTROL SCHEMATIC,
SEQUENCE, & BALANCE SCHEDULE
45 WLP NMT
M45-200
SUPPLY AIR
SMOKE
DAMPER
DI15
DO7
DI13
DI14 SUPPLY AIR SMOKE DAMPER (D-5) STATUS
RETURN AIR SMOKE DAMPER (D-4) STATUS
DI12 RETURN AIR SMOKE DAMPER (D-3) STATUS
DO4
DO5
DO6
RETURN AIR SMOKE DAMPER (D-3)
RETURN AIR SMOKE DAMPER (D-4)
SUPPLY AIR SMOKE DAMPER (D-5)
RETURN
AIR SMOKE
DAMPER
RETURN
AIR SMOKE
DAMPER
DI13
DO5
DI12
DO4
DI14
DO6
DI15 SUPPLY AIR SMOKE DAMPER (D-6) STATUS
DO7 SUPPLY AIR SMOKE DAMPER (D-6)
AIR HANDLING UNITS BALANCING SCHEDULE
LABEL AREA SERVED SUPPLY CFM OA CFM
COOLING
COIL GPM
PREHEAT COIL
STEAM
(LBS/HR)
HOT WATER
(GPM)
45-AHU-1 FLOORS 1 & 2 CORE 14500 3500 125 310 N/A
45-AHU-2
FLOORS 1 & 2
BEDROOMS
20000 5250 183 464 N/A
45-AHU-3
FLOOR 1 KITCHEN &
DINING RM.
5200 1500 44 124 N/A
45-AHU-4 FLOOR 2 DINING RM. 1200 300 10 N/A 5.0
45-AHU-5
FLOOR 2 MULTPURP. /
CHAPEL
4000 600 24 N/A 7.6
45-AHU-6 FLOOR 1 ATRIUM 1675 250 9.8 N/A 4.0
45-AHU-7
VAV BOXES IN 1ST
FLOOR EXPANSION
8250 1310 50.2 74 N/A
45-AHU-8
VAV BOXES IN 2ND
FLOOR EXPANSION
9325 1835 60.5 104 N/A
10-30-13
AI14
SPS-2
DI9
SUPPLY
FAN
DO3
AO3
DI8
AI9
COIL
V-1
NO
PREHEAT
AI5
AO1
DI7DI2
D02DO1
DI1
SPS-1
AI2
SUPPLY
PANEL
DDC CONTROL
AI4
T-2
T-1
OUTSIDE AIR
D-1
DI3
D-2
AI3
36x24
RETURN AIR
FROM EAST
DUCT CHASE
36x24
RETURN AIR
FROM
CENTRAL
DUCT CHASE
FLOWMETER
H-1
AI6
T-3
T-4 COIL
CLG
V-2
NC
AI7
AO2
AI12
T-8
SPS-3
AI13
DPS-2
DI5
DPS-1
DI4AI1
AI10
AI11
F-1
AIR
FILTER
SD-1
DI11
SD-2
DI6
D-5
T-5
AI8
T-6
DI10
T-7
36x24
RETURN AIR
FROM WEST
DUCT CHASE
3/4 LONGEST
RUN. ABOVE
ROOM 117A.
CONNECTED
TO FEC.
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE AIR HANDLING UNIT SHALL BE STARTED AND STOPPED AUTOMATICALLY AT THE ECC. THE HOA SWITCH SHALL BE KEPT IN THE AUTO POSITION. HAND AND OFF POSITIONS SHALL BE USED FOR
MAINTENANCE ONLY. UPON RECEIVING A START COMMAND THE SUPPLY FAN WILL START ONLY
AFTER ALL INTERNAL SAFETIES ARE PROVEN. ONCE FAN RUN STATUS IS PROVEN BY A CURRENT SENSING RELAY, THE CONTROLS SHALL OPERATE ACCORDING TO THE SEQUENCES AS DESCRIBED
BELOW.
2. AIR FLOW
2.1. OUTSIDE AIR IS METERED BY FLOWMETER, F-1, TO MONITOR AND MAINTAIN A CONSTANT MIN.
OUTSIDE AIR FLOW BY MODULATING THE RETURN DAMPER, D-2, AND OUTSIDE AIR DAMPER, D-1, UP
TO THE MAX. FLOW SETPOINT OF 5250 CFM (ADJUSTABLE).
3. TEMPERATURE CONTROL
3.1. TEMPERATURE SENSOR, T-3, IN THE PREHEAT COIL DISCHARGE SHALL TRANSMIT TEMPERATURE CHANGES TO THE DDC. THE DDC SYSTEM SHALL MODULATE THE 2-WAY STEAM PREHEAT CONTROL
VALVE, V-1, TO MAINTAIN PREHEAT TEMPERATURE SETPOINT (ADJUSTABLE).
3.2. TEMPERATURE SENSOR, T-8, IN THE SUPPLY AIR DUCT TRANSMITS TEMPERATURE CHANGES TO THE DDC. THE DDC MODULATES THE 2-WAY COOLING CONTROL VALVE, V-2, TO MAINTAIN DISCHARGE AIR
TEMPERATURE SETPOINT OF 55°F (ADJUSTABLE).
4. STATIC PRESSURE AND SUPPLY FAN SPEED CONTROL
4.1. THE VFD SHALL MODULATE THE SPEED OF THE SUPPLY FAN TO MAINTAIN DISCHARGE AIR STATIC PRESSURE TO ITS SETPOINT OF 1.0 IN. WC. (ADJUSTABLE) AS SENSED BY THE DUCT STATIC
PRESSURE SENSOR, SPS-4, LOCATED 3
4 OF THE WAY DOWN THE LONGEST DUCT MAIN.
4.2. THE SUPPLY FAN SPEED SHALL DECREASE TOWARDS ITS MIN. FREQUENCY. AS THE DISCHARGE AIR
STATIC PRESSURE DECREASES, THE SUPPLY FAN SPEED SHALL INCREASE.
4.3. THE STATIC PRESSURE IS RESET BASED ON ACTUAL BUILDING LOAD BY POLLING ALL VAV TERMINAL
UNITS.
5. DEHUMIDIFICATION CONTROL
5.1. WHEN THE OA DEW POINT IS ABOVE 55°F THE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE 55°F.
6. ALARMS
6.1. THE UNIT SHALL STOP UPON ANY OF THE SAFETIES BEING TRIPPED REGARDLESS OF THE MODE OF
OPERATION (AUTOMATIC, HAND OR BYPASS).
6.2. THE AIR HANDLER RETURN AIR SMOKE DETECTOR, SD-1, AND THE SUPPLY AIR SMOKE DETECTOR, SD-2, SHALL STOP THE UNIT AND CLOSE THE SMOKE DAMPERS UPON SENSING COMBUSTION
PRODUCTS IN THE SYSTEM. SMOKE DETECTORS MUST BE MANUALLY RESET AFTER AN ALARM
CONDITION IN ORDER FOR THE FAN TO RESTART AND THE SMOKE DAMPERS TO OPEN.
6.3. A MIXED AIR TEMPERATURE SENSOR, T-2, UPSTREAM OF THE COOLING COIL SIGNALS THE DDC UPON
A DROP IN TEMPERATURE BELOW 45°F, WHICH SHALL GENERATE AN ALARM TO THE ECC.
6.4. A TEMPERATURE LOW LIMIT SWITCH, T-4 OR T-5, SHALL STOP THE UNIT, CLOSE THE OUTSIDE AIR DAMPER, OPEN THE PREHEAT VALVE, AND SEND A CRITICAL ALARM TO THE ECC UPON SENSING A FALL IN TEMPERATURE BELOW SETPOINT (40°F ADJUSTABLE). THE LOW LIMIT SWITCHES MUST BE
MANUALLY RESET AFTER AN ALARM CONDITION.
6.5. A TEMPERATURE HIGH LIMIT, T-7, WILL SHUTDOWN THE FAN AND SEND AN ALARM TO THE ECC UPON A RISE IN DISCHARGE AIR ABOVE 125°F. THE HIGH LIMIT SWITCH MUST BE MANUALLY RESET AFTER
AN ALARM.
6.6. A DISCHARGE AIR HIGH STATIC PRESSURE SAFETY SWITCH, SPS-2, LOCATED AT THE SUPPLY FAN DISCHARGE WILL STOP THE UNIT UPON SENSING HIGH SUPPLY DUCT STATIC ABOVE 3 IN. STATIC
PRESSURE (ADJUSTABLE) TO PREVENT OVER PRESSURIZING THE DUCTWORK. STATIC PRESSURE
SWITCH IS HARDWIRED TO THE VFD AND UNIT IS SHUTDOWN IN HAND, AUTO, OR BYPASS MODE. THE
HIGH STATIC PRESSURE SAFETIES MUST BE MANUALLY RESET AFTER AN ALARM CONDITION.
6.7. UPON FAILURE OF THE VFD, THE SUPPLY FAN SHALL BE CONTROLLED MANUALLY AT THE DDC PANEL
OR THE ECC THROUGH THE BYPASS STARTER. FAN SHALL BE OPERATED AT CONSTANT SPEED.
7. MONITORING
7.1. THE DCC SYSTEM MONITORS THE DIFFERENTIAL PRESSURE ACROSS EACH FILTER AND GENERATES AN ALARM IF THE DIFFERENTIAL PRESSURE INCREASES ABOVE THE SETPOINT OF 0.75 IN. WC.
(ADJUSTABLE) TO PROVIDE NOTIFICATION OF A DIRTY FILTER.
8. SHUTDOWN
8.1. STOPPING THE UNIT SHALL DE-ENERGIZE THE CONTROL LOOPS AND SEND THE CONTROL VALVES TO THE CLOSED POSITION. THE OUTSIDE AIR DAMPER SHALL CLOSE AND THE RETURN AIR DAMPER
SHALL OPEN.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
T-9T
AI15
AMBIENT AIR
TEMPERATURE SENSOR
F-2
F-3
D-3
D-4
VFD
L P
S
T
C H
W R
H
T T T T T T T
OUTSIDE AIR FLOWMETER (F-1)
RETURN AIR TEMPERATURE SENSOR (T-1)AI2
AI1
RETURN AIR HUMIDITY SENSOR (H-1)AI3
MIXED AIR TEMPERATURE SENSOR (T-2)AI4
AI6
AI7
AI5
AI8
AI10
AI11
AI9
AI12
AI13
AI14
AI15
PREHEAT STEAM CONTROL VALVE (V-1)
PREHEAT COIL DISCHARGE AIR TEMPERATURE SENSOR (T-3)
CHILLED WATER CONTROL VALVE (V-2)
COOLING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-5)
SUPPLY FAN VFD STATUS
RETURN AIR WEST & CENTRAL CHASES FLOWMETER (F-3)
RETURN AIR EAST CHASE FLOWMETER (F-2)
SUPPLY AIR STATIC PRESSURE SENSOR (SPS-3)
SUPPLY AIR TEMPERATURE SENSOR (T-8)
DISCHARGE AIR STATIC PRESSURE SENSOR (SPS-4)
AMBIENT AIR TEMPERATURE SENSOR (T-9)
DI10
DI11 SUPPLY AIR SMOKE DETECTOR (SD-2) STATUS
HIGH LIMIT TEMPERATURE SENSOR (T-6) STATUS
DI8
DI6
DI7
DI4
DI2
DI3
DI1
DI5
RETURN AIR DAMPER (D-2) STATUS
RETURN AIR SMOKE DETECTOR (SD-1) STATUS
FILTER STATUS (DPS-1)
FILTER STATUS (DPS-2)
DI9
OUTSIDE AIR DAMPER (D-1) STATUS
SUPPLY AIR HIGH STATIC LIMIT PRESSURE SWITCH (SPS-2) STATUS
LOW LIMIT TEMPERATURE SENSORS (T-4 & T-5) STATUS
SUPPLY FAN STATUS
RETURN AIR STATIC PRESSURE LIMIT SENSOR (SPS-1) STATUS
PREHEAT STEAM CONTROL VALVE (V-1)
CHILLED WATER CONTROL VALVE (V-2)
AO1
AO2
AO3
DO1
DO2
DO3
SUPPLY FAN VFD SPEED
OUTSIDE AIR DAMPER (D-1)
RETURN AIR DAMPER (D-2)
SUPPLY FAN START/STOP
45-AHU-02 CONTROL SCHEMATIC
& SEQUENCE
45 WLP NMT
M45-201
NOTES:
1. ALL DEVICES ARE EXISTING DDC. SENSOR, ACTUATORS, ETC. BE
REUSED IF FUNCTIONAL AND COMPATIBLE.
2. PROVIDE NEW CONTROLLER. CONNECT NEW CONTROLLER TO
EXISTING ELECTRICAL SERVICE.
3. ADJUST EXISTING SUPPLY AIR & RETURN AIR HIGH STATIC VENTS TO
PREVENT THEIR OPERATION PRIOR TO HIGH STATIC SHUTDOWN.
DI13
DI14 SUPPLY AIR SMOKE DAMPER (D-5) STATUS
RETURN AIR SMOKE DAMPER (D-4) STATUS
DI12 RETURN AIR SMOKE DAMPER (D-3) STATUS
RETURN
AIR SMOKE
DAMPER
RETURN
AIR SMOKE
DAMPER
SUPPLY AIR
SMOKE
DAMPER
DI14
DO6
DI13
DO5
DI12
DO4
DO4
DO5
DO6
RETURN AIR SMOKE DAMPER (D-3)
RETURN AIR SMOKE DAMPER (D-4)
SUPPLY AIR SMOKE DAMPER (D-5)
AI12
SPS-2
DI9
SUPPLY
FAN
DO3
AO3
DI8
AI10
COIL
PREHEAT
AI5
AO1
DI7DI2
D02DO1
DI1
SPS-1
AI3
SUPPLY
PANEL
DDC CONTROL
AI4
T-2
T
T-1
OUTSIDE AIR
D-1
AI2
D-2
DI6
RETURN AIR
FROM 3RD
FLOOR
FLOWMETER
H-1
H
AI6
T-3
T-4 COIL
CLG
AI8
AO2
DI10
AI11
T-7
SPS-3
DI12
DPS-2
DI5
DPS-1
DI4AI1
AI7
F-1
F-2
AIR
FILTER
SD-1
DI11
SD-2
DI3 AI9
T-5
T-6
D-3
LOCATED IN
SAD BEFORE
V45-3-1 IN
PENTHOUSE
MECH RM.
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE AIR HANDLING UNIT SHALL BE STARTED AND STOPPED AUTOMATICALLY AT THE ECC. THE HOA SWITCH SHALL BE KEPT IN THE AUTO POSITION. HAND AND OFF POSITIONS SHALL BE USED FOR
MAINTENANCE ONLY. UPON RECEIVING A START COMMAND THE SUPPLY FAN WILL START ONLY
AFTER ALL INTERNAL SAFETIES ARE PROVEN. ONCE FAN RUN STATUS IS PROVEN BY A CURRENT SENSING RELAY, THE CONTROLS SHALL OPERATE ACCORDING TO THE SEQUENCES AS DESCRIBED
BELOW.
2. AIR FLOW
2.1. OUTSIDE AIR IS METERED BY FLOWMETER, F-1, TO MONITOR AND MAINTAIN A CONSTANT MIN.
OUTSIDE AIR FLOW BY MODULATING THE RETURN DAMPER, D-2, AND OUTSIDE AIR DAMPER, D-1, UP
TO THE MAX. FLOW SETPOINT OF 1500 CFM (ADJUSTABLE).
3. TEMPERATURE CONTROL
3.1. TEMPERATURE SENSOR, T-3, IN THE PREHEAT COIL DISCHARGE SHALL TRANSMIT TEMPERATURE CHANGES TO THE DDC. THE DDC SYSTEM SHALL MODULATE THE 2-WAY STEAM PREHEAT CONTROL
VALVE, V-1, TO MAINTAIN PREHEAT TEMPERATURE SETPOINT (ADJUSTABLE).
3.2. TEMPERATURE SENSOR, T-8, IN THE SUPPLY AIR DUCT TRANSMITS TEMPERATURE CHANGES TO THE DDC. THE DDC MODULATES THE 2-WAY COOLING CONTROL VALVE, V-2, TO MAINTAIN DISCHARGE AIR
TEMPERATURE SETPOINT OF 55°F (ADJUSTABLE).
4. STATIC PRESSURE AND SUPPLY FAN SPEED CONTROL
4.1. THE VFD SHALL MODULATE THE SPEED OF THE SUPPLY FAN TO MAINTAIN DISCHARGE AIR STATIC PRESSURE TO ITS SETPOINT OF 1.0 IN. WC. (ADJUSTABLE) AS SENSED BY THE DUCT STATIC
PRESSURE SENSOR, SPS-4, LOCATED 3
4 OF THE WAY DOWN THE LONGEST DUCT MAIN.
4.2. THE SUPPLY FAN SPEED SHALL DECREASE TOWARDS ITS MIN. FREQUENCY. AS THE DISCHARGE AIR
STATIC PRESSURE DECREASES, THE SUPPLY FAN SPEED SHALL INCREASE.
4.3. THE STATIC PRESSURE IS RESET BASED ON ACTUAL BUILDING LOAD BY POLLING ALL VAV TERMINAL
UNITS.
5. DEHUMIDIFICATION CONTROL
5.1. WHEN THE OA DEW POINT IS ABOVE 55°F THE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE 55°F.
6. ALARMS
6.1. THE UNIT SHALL STOP UPON ANY OF THE SAFETIES BEING TRIPPED REGARDLESS OF THE MODE OF
OPERATION (AUTOMATIC, HAND OR BYPASS).
6.2. THE AIR HANDLER RETURN AIR SMOKE DETECTOR, SD-1, AND THE SUPPLY AIR SMOKE DETECTOR, SD-2, SHALL STOP THE UNIT AND CLOSE THE SMOKE DAMPERS UPON SENSING COMBUSTION
PRODUCTS IN THE SYSTEM. SMOKE DETECTORS MUST BE MANUALLY RESET AFTER AN ALARM
CONDITION IN ORDER FOR THE FAN TO RESTART AND THE SMOKE DAMPERS TO OPEN.
6.3. A MIXED AIR TEMPERATURE SENSOR, T-2, UPSTREAM OF THE COOLING COIL SIGNALS THE DDC UPON
A DROP IN TEMPERATURE BELOW 45°F, WHICH SHALL GENERATE AN ALARM TO THE ECC.
6.4. A TEMPERATURE LOW LIMIT SWITCH, T-4 OR T-5, SHALL STOP THE UNIT, CLOSE THE OUTSIDE AIR DAMPER, OPEN THE PREHEAT VALVE, AND SEND A CRITICAL ALARM TO THE ECC UPON SENSING A FALL IN TEMPERATURE BELOW SETPOINT (40°F ADJUSTABLE). THE LOW LIMIT SWITCHES MUST BE
MANUALLY RESET AFTER AN ALARM CONDITION.
6.5. A TEMPERATURE HIGH LIMIT, T-7, WILL SHUTDOWN THE FAN AND SEND AN ALARM TO THE ECC UPON A RISE IN DISCHARGE AIR ABOVE 125°F. THE HIGH LIMIT SWITCH MUST BE MANUALLY RESET AFTER
AN ALARM.
6.6. A DISCHARGE AIR HIGH STATIC PRESSURE SAFETY SWITCH, SPS-2, LOCATED AT THE SUPPLY FAN DISCHARGE WILL STOP THE UNIT UPON SENSING HIGH SUPPLY DUCT STATIC ABOVE 3 IN. STATIC
PRESSURE (ADJUSTABLE) TO PREVENT OVER PRESSURIZING THE DUCTWORK. STATIC PRESSURE
SWITCH IS HARDWIRED TO THE VFD AND UNIT IS SHUTDOWN IN HAND, AUTO, OR BYPASS MODE. THE
HIGH STATIC PRESSURE SAFETIES MUST BE MANUALLY RESET AFTER AN ALARM CONDITION.
6.7. UPON FAILURE OF THE VFD, THE SUPPLY FAN SHALL BE CONTROLLED MANUALLY AT THE DDC PANEL
OR THE ECC THROUGH THE BYPASS STARTER. FAN SHALL BE OPERATED AT CONSTANT SPEED.
7. MONITORING
7.1. THE DCC SYSTEM MONITORS THE DIFFERENTIAL PRESSURE ACROSS EACH FILTER AND GENERATES AN ALARM IF THE DIFFERENTIAL PRESSURE INCREASES ABOVE THE SETPOINT OF 0.75 IN. WC.
(ADJUSTABLE) TO PROVIDE NOTIFICATION OF A DIRTY FILTER.
8. SHUTDOWN
8.1. STOPPING THE UNIT SHALL DE-ENERGIZE THE CONTROL LOOPS AND SEND THE CONTROL VALVES TO THE CLOSED POSITION. THE OUTSIDE AIR DAMPER SHALL CLOSE AND THE RETURN AIR DAMPER
SHALL OPEN.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
OUTSIDE AIR FLOWMETER (F-1)
RETURN AIR TEMPERATURE SENSOR (T-1)AI2
AI1
RETURN AIR HUMIDITY SENSOR (H-1)AI3
MIXED AIR TEMPERATURE SENSOR (T-2)AI4
AI6
AI7
AI5
AI8
AI10
AI11
AI9
AI12
AI13
PREHEAT STEAM CONTROL VALVE (V-1)
PREHEAT COIL DISCHARGE AIR TEMPERATURE SENSOR (T-3)
RETURN AIR FLOWMETER (F-2)
CHILLED WATER CONTROL VALVE (V-2)
COOLING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-5)
SUPPLY FAN VFD STATUS
SUPPLY AIR TEMPERATURE SENSOR (T-7)
AMBIENT AIR TEMPERATURE SENSOR (T-8)
AHU DISCHARGE AIR STATIC PRESSURE SENSOR (SPS-3)
DI10
DI11 SUPPLY AIR SMOKE DETECTOR (SD-2) STATUS
HIGH LIMIT TEMPERATURE SENSOR (T-6) STATUS
DI8
DI6
DI7
DI4
DI2
DI3
DI1
DI5
RETURN AIR DAMPER (D-2) STATUS
RETURN AIR SMOKE DETECTOR (SD-1) STATUS
FILTER STATUS (DPS-1)
FILTER STATUS (DPS-2)
DI9
OUTSIDE AIR DAMPER (D-1) STATUS
SUPPLY AIR HIGH STATIC PRESSURE LIMIT SWITCH (SPS-2) STATUS
LOW LIMIT TEMPERATURE SENSORS (T-4 & T-5) STATUS
SUPPLY FAN STATUS
RETURN AIR STATIC PRESSURE LIMIT SENSOR (SPS-1) STATUS
PREHEAT STEAM CONTROL VALVE (V-1)
CHILLED WATER CONTROL VALVE (V-2)
AO1
AO2
AO3
DO1
DO2
DO3
SUPPLY FAN VFD SPEED
OUTSIDE AIR DAMPER (D-1)
RETURN AIR DAMPER (D-2)
SUPPLY FAN START/STOP
T-8T
AI13
AMBIENT AIR
TEMPERATURE SENSOR
T T T T T T V-2
NC VFD
C H
W R
V-1
NO
L P
S
DI12 SYSTEM AIR HIGH LIMIT STATIC PRESSURE SWITCH (SPS-4) STATUS
45-AHU-03 CONTROL SCHEMATIC
& SEQUENCE
45 WLP NMT
M45-202
NOTES:
1. ALL DEVICES ARE EXISTING DDC. SENSOR, ACTUATORS, ETC. BE
REUSED IF FUNCTIONAL AND COMPATIBLE.
2. PROVIDE NEW CONTROLLER. CONNECT NEW CONTROLLER TO
EXISTING ELECTRICAL SERVICES.
DI13 RETURN AIR SMOKE DAMPER (D-3) STATUS
DO4 RETURN AIR SMOKE DAMPER (D-3)
RETURN
AIR SMOKE
DAMPER
DI13
DO4
SUPPLY
STR
FAN
DO3
DI5
COIL
H W
R
V-1
PREHEAT
AI4
AO1
DI4
DO1
DI1 AI3
SUPPLY
PANEL
DDC CONTROL
AI1
T-1
T
T-2
OUTSIDE AIR
D-1
AI2
T-8
AI9
RETURN AIRH-1
AI5
T-3
T-4
C H
W R
COIL
CLG
V-2
NC
AI6
AO2
DI6
AI8
T-7
SPS-1
DI8
DPS-1
DI3
AIR
FILTER
DI7
SD-1
AI7
T-5
T-6
ZONE THERMOSTAT
SENSOR DINING RM
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE AIR HANDLING UNIT SHALL BE STARTED AND STOPPED AUTOMATICALLY AT THE ECC. THE HOA SWITCH SHALL BE KEPT IN THE AUTO POSITION. HAND AND OFF POSITIONS SHALL BE USED FOR MAINTENANCE ONLY. UPON RECEIVING A START COMMAND THE SUPPLY FAN WILL START ONLY AFTER ALL INTERNAL SAFETIES ARE PROVEN. ONCE FAN RUN STATUS IS PROVEN BY A CURRENT SENSING
RELAY, THE CONTROLS SHALL OPERATE ACCORDING TO THE SEQUENCES AS DESCRIBED BELOW.
2. TEMPERATURE CONTROL
2.1. THE ZONE TEMPERATURE SENSOR, T-8, IN THE CONDITIONED SPACE SHALL TRANSMIT TEMPERATURE
CHANGES TO THE DDC. THE DDC SYSTEM SHALL MODULATE THE 3-WAY HOT WATER PREHEAT
CONTROL VALVE, V-1, AND THE 2-WAY CHILLED WATER CONTROL VALVE, V-2, TO MAINTAIN SPACE
TEMPERATURE SETPOINT (ADJUSTABLE).
3. ALARMS
3.1. THE UNIT SHALL STOP UPON ANY OF THE SAFETIES BEING TRIPPED REGARDLESS OF THE MODE OF
OPERATION (AUTOMATIC, HAND OR BYPASS).
3.2. THE SUPPLY AIR SMOKE DETECTOR, SD-1, SHALL STOP THE UNIT UPON SENSING COMBUSTION
PRODUCTS IN THE SYSTEM. SMOKE DETECTORS MUST BE MANUALLY RESET AFTER AN ALARM
CONDITION IN ORDER FOR THE FAN TO RESTART.
3.3. A TEMPERATURE LOW LIMIT SWITCH, T-4, SHALL STOP THE UNIT, CLOSE THE OUTSIDE AIR DAMPER, OPEN THE PREHEAT VALVE, AND SEND A CRITICAL ALARM TO THE ECC UPON SENSING A FALL IN TEMPERATURE BELOW SETPOINT (40°F ADJUSTABLE). THE LOW LIMIT SWITCHES MUST BE MANUALLY
RESET AFTER AN ALARM CONDITION.
3.4. A TEMPERATURE HIGH LIMIT, T-6, WILL SHUTDOWN THE FAN AND SEND AN ALARM TO THE ECC UPON A RISE IN DISCHARGE AIR ABOVE 125°F. THE HIGH LIMIT SWITCH MUST BE MANUALLY RESET AFTER AN
ALARM.
3.5. A DISCHARGE AIR HIGH STATIC PRESSURE SAFETY SWITCH, SPS-1, LOCATED AT THE SUPPLY FAN DISCHARGE WILL STOP THE UNIT UPON SENSING HIGH SUPPLY DUCT STATIC ABOVE 3 IN. STATIC
PRESSURE (ADJUSTABLE) TO PREVENT OVER PRESSURIZING THE DUCTWORK.
4. MONITORING
4.1. THE DCC SYSTEM MONITORS THE DIFFERENTIAL PRESSURE ACROSS EACH FILTER AND GENERATES AN
ALARM IF THE DIFFERENTIAL PRESSURE INCREASES ABOVE THE SETPOINT OF 0.75 IN. WC.
(ADJUSTABLE) TO PROVIDE NOTIFICATION OF A DIRTY FILTER.
5. SHUTDOWN
5.1. STOPPING THE UNIT SHALL DE-ENERGIZE THE CONTROL LOOPS AND SEND THE CONTROL VALVES AND
OUTSIDE AIR DAMPER TO THE CLOSED POSITION.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
H
T T T T T T
T-9T
AI10
AMBIENT AIR
TEMPERATURE SENSOR
T
MIXED AIR TEMPERATURE SENSOR (T-1)
RETURN AIR TEMPERATURE SENSOR (T-2)AI2
AI1
RETURN AIR HUMIDITY SENSOR (H-1)AI3
HOT WATER CONTROL VALVE (V-1)AI4
AI6
AI7
AI5
AI8
AI9
PREHEAT COIL DISCHARGE AIR TEMPERATURE SENSOR (T-3)
CHILLED WATER CONTROL VALVE (V-2)
COOLING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-5)
AMBIENT AIR TEMPERATURE SENSOR (T-8)
DI6
DI7
DI4
DI2
DI3
DI1
DI5
OUTSIDE AIR DAMPER (D-1) STATUS
HOT WATER CONTROL VALVE (V-1)
CHILLED WATER CONTROL VALVE (V-2)
AO1
AO2
DO1
DO2
OUTSIDE AIR DAMPER (D-1)
ZONE TEMPERATURE SENSOR (T-8)
FILTER STATUS (DPS-1)
LOW LIMIT TEMPERATURE SENSOR (T-4) STATUS
SUPPLY FAN STATUS
SUPPLY AIR SMOKE DETECTOR (SD-1) STATUS
HIGH LIMIT TEMPERATURE SENSOR (T-6) STATUS
SUPPLY AIR HIGH STATIC PRESSURE SWITCH (SPS-1) STATUS
RETURN AIR DAMPER (D-2)
DI2
D02
D-2
DI8
RETURN AIR DAMPER (D-2) STATUS
DO3 SUPPLY FAN START/STOP
45-AHU-04 CONTROL SCHEMATIC
& SEQUENCE
45 WLP NMT
M45-203
NOTES:
1. ALL DEVICES ARE EXISTING DDC. SENSOR,
ACTUATORS, ETC. BE REUSED IF FUNCTIONAL AND
COMPATIBLE.
2. PROVIDE NEW CONTROLLER AND SPACE
TEMPERATURE SENSOR.
3. CONNECT NEW CONTROLLER TO EXISTING
ELECTRICAL SERVICE.
AI10
COOLING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-5)
AHU DISCHARGE AIR TEMPERATURE SENSOR (T-7)
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE AIR HANDLING UNIT SHALL BE STARTED AND STOPPED AUTOMATICALLY AT THE ECC. THE HOA SWITCH SHALL BE KEPT IN THE AUTO POSITION. HAND AND OFF POSITIONS SHALL BE USED FOR
MAINTENANCE ONLY.
1.2. UPON RECEIVING A START COMMAND THE SUPPLY FAN WILL START ONLY AFTER ALL INTERNAL SAFETIES ARE PROVEN. ONCE FAN RUN STATUS IS PROVEN BY A CURRENT SENSING RELAY, THE
CONTROLS SHALL OPERATE ACCORDING TO THE SEQUENCES AS DESCRIBED BELOW.
2. TEMPERATURE CONTROL
2.1. THE ZONE TEMPERATURE SENSOR, T-8, IN THE CONDITIONED SPACE SHALL TRANSMIT
TEMPERATURE CHANGES TO THE DDC. THE DDC SYSTEM SHALL MODULATE THE 3-WAY HOT WATER PREHEAT CONTROL VALVE, V-1, AND THE 2-WAY CHILLED WATER CONTROL VALVE, V-2, TO MAINTAIN
SPACE TEMPERATURE SETPOINT (ADJUSTABLE).
3. ALARMS
3.1. THE UNIT SHALL STOP UPON ANY OF THE SAFETIES BEING TRIPPED REGARDLESS OF THE MODE OF
OPERATION (AUTOMATIC, HAND OR BYPASS).
3.2. THE RETURN AIR SMOKE DETECTOR, SD-1, OR SUPPLY AIR SMOKE DETECTOR, SD-2, SHALL STOP
THE UNIT UPON SENSING COMBUSTION PRODUCTS IN THE SYSTEM. SMOKE DETECTORS MUST BE
MANUALLY RESET AFTER AN ALARM CONDITION IN ORDER FOR THE FAN TO RESTART.
3.3. A TEMPERATURE LOW LIMIT SWITCH, T-4, SHALL STOP THE UNIT, CLOSE THE OUTSIDE AIR DAMPER, OPEN THE PREHEAT VALVE, AND SEND A CRITICAL ALARM TO THE ECC UPON SENSING A FALL IN TEMPERATURE BELOW SETPOINT (40°F ADJUSTABLE). THE LOW LIMIT SWITCHES MUST BE MANUALLY
RESET AFTER AN ALARM CONDITION.
3.4. A TEMPERATURE HIGH LIMIT, T-6, WILL SHUTDOWN THE FAN AND SEND AN ALARM TO THE ECC UPON A RISE IN DISCHARGE AIR ABOVE 125°F. THE HIGH LIMIT SWITCH MUST BE MANUALLY RESET AFTER
AN ALARM.
3.5. A DISCHARGE AIR HIGH STATIC PRESSURE SAFETY SWITCH, SPS-1, LOCATED AT THE SUPPLY FAN DISCHARGE WILL STOP THE UNIT UPON SENSING HIGH SUPPLY DUCT STATIC ABOVE 3 IN. STATIC
PRESSURE (ADJUSTABLE) TO PREVENT OVER PRESSURIZING THE DUCTWORK.
4. MONITORING
4.1. THE DCC SYSTEM MONITORS THE DIFFERENTIAL PRESSURE ACROSS EACH FILTER AND GENERATES AN ALARM IF THE DIFFERENTIAL PRESSURE INCREASES ABOVE THE SETPOINT OF 0.75 IN. WC.
(ADJUSTABLE) TO PROVIDE NOTIFICATION OF A DIRTY FILTER.
5. SHUTDOWN
5.1. STOPPING THE UNIT SHALL DE-ENERGIZE THE CONTROL LOOPS AND SEND THE CONTROL VALVES
AND OUTSIDE AIR DAMPER TO THE CLOSED POSITION.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
SUPPLY
STR
FAN
DO3
DI6
COIL
H W
R
V-1
PREHEAT
AI4
AO1
DI5
DO1
DI1 AI2
SUPPLY
PANEL
DDC CONTROL
AI3
T-2
T
T-1
OUTSIDE AIR
D-1
AI1
T-8
AI9
RETURN AIRH-1
AI5
T-3
T-4
C H
W R
COIL
CLG
V-2
NC
AI6
AO2
DI7
AI8
T-7
SPS-1
DI9
DPS-1
DI3
AIR
FILTER
DI8
SD-2
AI7
T-5
T-6
ZONE THERMOSTAT
SENSOR DINING RM
H
T T T T T T
T-9T
AI10
AMBIENT AIR
TEMPERATURE SENSOR
T
RETURN AIR TEMPERATURE SENSOR (T-1)
RETURN AIR HUMIDITY SENSOR (H-1)AI2
AI1
MIXED AIR TEMPERATURE SENSOR (T-2)AI3
HOT WATER CONTROL VALVE (V-1)AI4
AI6
AI7
AI5
AI8
AI9
PREHEAT COIL DISCHARGE AIR TEMPERATURE SENSOR (T-3)
CHILLED WATER CONTROL VALVE (V-2)
COOLING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-5)
ZONE TEMPERATURE SENSOR (T-8)
DI6
DI7
DI4
DI2
DI3
DI1
DI5
OUTSIDE AIR DAMPER (D-1) STATUS
HOT WATER CONTROL VALVE (V-1)
CHILLED WATER CONTROL VALVE (V-2)
AO1
AO2
DO1
DO2
OUTSIDE AIR DAMPER (D-1)
AHU DISCHARGE AIR TEMPERATURE SENSOR (T-7)
FILTER STATUS (DPS-1)
LOW LIMIT TEMPERATURE SENSOR (T-4) STATUS
SUPPLY FAN STATUS
SUPPLY AIR SMOKE DETECTOR (SD-2) STATUS
HIGH LIMIT TEMPERATURE SENSOR (T-6) STATUS
SUPPLY AIR HIGH STATIC PRESSURE SWITCH (SPS-1) STATUS
OUTSIDE AIR DAMPER (D-1)
SD-1
DI4
RETURN AIR SMOKE DETECTOR (SD-1) STATUS
DI8
DI2
D02
D-2
DI9
RETURN AIR DAMPER (D-2) STATUS
DO3 SUPPLY FAN START/STOP
45-AHU-05 CONTROL SCHEMATIC
& SEQUENCE
45 WLP NMT
M45-204
NOTES:
1. ALL DEVICES ARE EXISTING DDC. SENSOR, ACTUATORS,
ETC. BE REUSED IF FUNCTIONAL AND COMPATIBLE.
2. PROVIDE NEW CONTROLLER AND SPACE TEMPERATURE
SENSOR.
3. CONNECT NEW CONTROLLER TO EXISTING ELECTRICAL
SERVICE.
AI10 AMBIENT AIR TEMPERATURE SENSOR (T-9)
NOTES:
1. ALL DEVICES ARE EXISTING DDC. SENSORS,
ACTUATORS, ETC. MAY BE REUSED IF
FUNCTIONAL AND COMPATIBLE.
2. PROVIDE NEW CONTROLLER. CONNECT NEW
CONTROLLER TO EXISTING ELECTRICAL
SERVICE.
3. AHU IS LOCATED OUTSIDE. ALL CONTROL
DEVICES SHALL BE EXTERIOR GRADE OR
PROVIDE WITH WEATHERPROOF COVERING.
REPLACE EXISTING COVERS AS REQUIRED.
SUPPLY
FAN
DO3
DI5
COIL
CLG
AI4
AO1
SUPPLY
PANEL
DDC CONTROL
AI3
T-2
T-8
AI10
RETURN AIR
AI5
T-4
COIL
HTG
AI6
AO2
DI6
AI8
T-7
SPS-1
DI8
DI7
SD-1
AI7
T-5
T-6
ZONE THERMOSTAT
SENSOR CHAPEL RM
DI4
T-3
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE AIR HANDLING UNIT SHALL BE STARTED AND STOPPED AUTOMATICALLY AT THE ECC. THE HOA SWITCH SHALL BE KEPT IN THE AUTO POSITION. HAND AND OFF POSITIONS SHALL BE USED FOR
MAINTENANCE ONLY.
1.2. UPON RECEIVING A START COMMAND THE SUPPLY FAN WILL START ONLY AFTER ALL INTERNAL SAFETIES ARE PROVEN. ONCE FAN RUN STATUS IS PROVEN BY A CURRENT SENSING RELAY, THE
CONTROLS SHALL OPERATE ACCORDING TO THE SEQUENCES AS DESCRIBED BELOW.
2. TEMPERATURE CONTROL
2.1. THE ZONE TEMPERATURE SENSOR, T-8, IN THE CONDITIONED SPACE SHALL TRANSMIT
TEMPERATURE CHANGES TO THE DDC. THE DDC SYSTEM SHALL MODULATE THE 2-WAY CHILLED
WATER CONTROL VALVE, V-1, AND THE 3-WAY HOT WATER REHEAT CONTROL VALVE, V-2, TO
MAINTAIN SPACE TEMPERATURE SETPOINT (ADJUSTABLE).
3. HUMIDITY CONTROL
3.1. THE ZONE HUMIDITY SENSOR, H-2, SHALL OVERRIDE THE THERMOSTAT AND CONTROL THE COOLING VALVE TO MAINTAIN 55°F DISCHARGE AIR. THE THERMOSTAT SHALL CONTROL SPACE TEMPERATURE
AT SETPOINT BY MODULATING THE REHEAT WATER COIL VALVE.
4. ALARMS
4.1. THE UNIT SHALL STOP UPON ANY OF THE SAFETIES BEING TRIPPED REGARDLESS OF THE MODE OF
OPERATION (AUTOMATIC, HAND OR BYPASS).
4.2. THE SUPPLY AIR SMOKE DETECTOR, SD-1, SHALL STOP THE UNIT UPON SENSING COMBUSTION
PRODUCTS IN THE SYSTEM. SMOKE DETECTORS MUST BE MANUALLY RESET AFTER AN ALARM
CONDITION IN ORDER FOR THE FAN TO RESTART.
4.3. A TEMPERATURE LOW LIMIT SWITCH, T-3, SHALL STOP THE UNIT, CLOSE THE OUTSIDE AIR DAMPER, OPEN THE PREHEAT VALVE, AND SEND A CRITICAL ALARM TO THE ECC UPON SENSING A FALL IN TEMPERATURE BELOW SETPOINT (40°F ADJUSTABLE). THE LOW LIMIT SWITCHES MUST BE MANUALLY
RESET AFTER AN ALARM CONDITION.
4.4. A TEMPERATURE HIGH LIMIT, T-6, WILL SHUTDOWN THE FAN AND SEND AN ALARM TO THE ECC UPON A RISE IN DISCHARGE AIR ABOVE 125°F. THE HIGH LIMIT SWITCH MUST BE MANUALLY RESET AFTER
AN ALARM.
4.5. A DISCHARGE AIR HIGH STATIC PRESSURE SAFETY SWITCH, SPS-1, LOCATED AT THE SUPPLY FAN DISCHARGE WILL STOP THE UNIT UPON SENSING HIGH SUPPLY DUCT STATIC ABOVE 3 IN. STATIC
PRESSURE (ADJUSTABLE) TO PREVENT OVER PRESSURIZING THE DUCTWORK.
5. MONITORING
5.1. THE DCC SYSTEM MONITORS THE DIFFERENTIAL PRESSURE ACROSS EACH FILTER AND GENERATES AN ALARM IF THE DIFFERENTIAL PRESSURE INCREASES ABOVE THE SETPOINT OF 0.75 IN. WC.
(ADJUSTABLE) TO PROVIDE NOTIFICATION OF A DIRTY FILTER.
6. SHUTDOWN
6.1. STOPPING THE UNIT SHALL DE-ENERGIZE THE CONTROL LOOPS AND SEND THE CONTROL VALVES
AND OUTSIDE AIR DAMPER TO THE CLOSED POSITION.
AI9
H-2
ZONE HUMIDITY
SENSOR CHAPEL RM
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
DO1
DI1 AI2
T
T-1
OUTSIDE AIR
D-1
AI1
H-1
DPS-1
DI3
AIR
FILTER
H
STR
C H
W R
V-1
NC
H W
R
V-2 T T T T T
T-9T
AI11
AMBIENT AIR
TEMPERATURE SENSOR
HT
RETURN AIR TEMPERATURE SENSOR (T-1)
RETURN AIR HUMIDITY SENSOR (H-1)AI2
AI1
MIXED AIR TEMPERATURE SENSOR (T-2)AI3
CHILLED WATER CONTROL VALVE (V-1)AI4
AI6
AI7
AI5
AI8
AI9
COOLING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-5)
HOT WATER CONTROL VALVE (V-2)
HEATING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-5)
ZONE TEMPERATURE SENSOR (T-8)
DI6
DI7
DI4
DI2
DI3
DI1
DI5
OUTSIDE AIR DAMPER (D-1) STATUS
CHILLED WATER CONTROL VALVE (V-1)
HOT WATER CONTROL VALVE (V-2)
AO1
AO2
DO1
DO2
OUTSIDE AIR DAMPER (D-1)
SUPPLY AIR TEMPERATURE SENSOR (T-7)
FILTER STATUS (DPS-1)
LOW LIMIT TEMPERATURE SENSOR (T-4) STATUS
SUPPLY FAN STATUS
SUPPLY AIR SMOKE DETECTOR (SD-1) STATUS
HIGH LIMIT TEMPERATURE SENSOR (T-6) STATUS
SUPPLY AIR HIGH STATIC PRESSURE SWITCH (SPS-1) STATUS
RETURN AIR DAMPER (D-2)
AI10
AI11 AMBIENT AIR TEMPERATURE SENSOR (T-9)
ZONE HUMIDITY SENSOR (H-2)
DI2
D02
D-2
RETURN AIR DAMPER (D-2) STATUS
DI8
DO3 SUPPLY FAN START/STOP
45-AHU-06 CONTROL SCHEMATIC
& SEQUENCE
45 WLP NMT
M45-205
FAN
AO4
AI8
COIL
L P
S
V-1
NO
HTG
AI4
AO2
PANEL
DDC CONTROL
AI3
T-1OUTSIDE AIR
RETURN AIR
T
AI5
T-2
C H
W R
COIL
CLG
V-2
NC
AI6
AO3
AI9
T-3
SPS-1
DI5
DPS-1
DI2
AIR
FILTER
FLOWMETER
AI1
F-1
DO2
DI4
OA
VFD
FAN
AO1
AI2
DO1
DI1
C H
W S
AI7
DPS-2
DI6
AIR
FILTER
AI10
F-2
SPS-2
DI7
AI11
F-3
SPS-3
DI8
CONTROL PANEL
VAV45-7-8
CONTROL PANEL
VAV45-7-9
F T
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE AIR HANDLING UNIT SHALL BE STARTED AND STOPPED AUTOMATICALLY AT THE ECC. THE HOA SWITCH SHALL BE KEPT IN THE AUTO POSITION. HAND AND OFF POSITIONS SHALL BE USED FOR
MAINTENANCE ONLY.
2. TEMPERATURE CONTROLS
2.1. WHEN OA DEWPOINT TEMPERATURE IS ABOVE 55°F THE SUPPLY AIR TEMPERATURE, SENSED BY T-3, SHALL BE MAINTAIN AT TEMPERATURE SETPOINT 55°F (ADJUSTABLE) VIA DDC BY MODULATING THE COOLING CONTROL VALVE, V-2. SUPPLY AIR TEMPERATURE SETPOINT SHALL BE RESET WHEN OA DEWPOINT IS BELOW 55°F BASED ON TERMINAL BOX DEMAD, FAN SPEED, AND OUTSIDE AIR DEW
POINT.
2.2. WHEN THE TEMPERATURE OF THE MIXED AIR, SENSED BY T-1, IS BELOW 40°F, THE DDC SHALL MODULATE THE HEATING CONTROL VALVE, V-1, TO MAINTAIN THE AIR TEMPERATURE SENSED BY T-3
AT 55°F (ADJUSTABLE).
3. AIR FLOW CONTROLS
3.1. THE SUPPLY AIR FLOW SHALL BE CONTROLLED BY MODULATING THE SUPPLY FAN VFD TO MAINTAIN 1.0" OF DUCT STATIC PRESSURE (ADJUSTABLE) SENSED BY SPS-2. SEE FLOOR PLANS FOR THE
LOCATION OF SPS-2. STATIC PRESSURE SETPOINT SHALL BE RESET BASED ON TERMINAL BOX
DAMPER POSITIONS TO MINIMIZE FAN ENERGY.
3.2. THE OUTSIDE AIR FLOW SHALL BE CONTROLLED THE DDC MODULATING THE OUTSIDE AIR FAN VFD
TO MAINTAIN OUTSIDE AIR FLOW AT THE SCHEDULED CFM.
3.3. THE DDC, USING HIGH PRESSURE SENSOR, SPS-1, LOCATED AT THE SUPPLY FAN DISCHARGE SHALL PREVENT THE SUPPLY FAN FROM DEVELOPING OVER 3" OF STATIC PRESSURE (ADJUSTABLE). IF
STATIC PRESSURE AT SPS-1 DOES EXCEED 3", THE SUPPLY AIR FAN SHALL STOP.
4. FREEZE PROTECTION
4.1. IF THE AIR TEMPERATURE, AS SENSED BY T-2, FALLS BELOW 45°F, AN ALARM SIGNAL SHALL INDICATE AT THE DDC AND ECC. IF THE TEMPERATURE FALLS BELOW 40°F, THE SUPPLY AND RETURN FANS
SHALL SHUT DOWN AND A CRITICAL ALARM SHALL INDICATE DDC AND ECC.
5. EMERGENCY CONTACT SPEED OPERATION
5.1. UPON FAILURE OF THE VFD, THE SUPPLY FAN SHALL BE STARTED/STOPPED MANUALLY AT THE DDC
OR THE ECC THROUGH THE BYPASS STARTER. FANS SHALL THEN BE OPERATED AT CONSTANT
SPEED.
6. FILTER STATUS
6.1. WHEN FILTER STATIC PRESSURE, AS SENSED BY EITHER DPS-1 OR DPS-2, EXCEEDS SPECIFIED MAX.
STATIC PRESSURE, AN ALARM SIGNAL SHALL INDICATE AT THE DDC AND ECC.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
TT VFD
OUTSIDE AIR FLOWMETER (F-1)
OUTSIDE AIR FAN VFD STATUSAI2
AI1
MIXED AIR TEMPERATURE SENSOR (T-1)AI3
HOT WATER CONTROL VALVE (V-1)AI4
AI6
AI7
AI5
AI8
AI9
HEATING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-2)
CHILLED WATER CONTROL VALVE (V-2)
CHILLED WATER SUPPLY FLOWMETER
SUPPLY AIR TEMPERATURE SENSOR (T-3)
DI6
DI7
DI4
DI2
DI3
DI1
DI5
OUTSIDE AIR FAN STATUS
OUTSIDE AIR FAN VFD SPEED
HOT WATER CONTROL VALVE (V-1)
AO1
AO2
DO1
DO2
OUTSIDE AIR FAN START/STOP
SUPPLY FAN VFD STATUS
RETURN AIR SMOKE DETECTOR (SD-1) STATUS
SUPPLY FAN STATUS
FILTER STATUS (DPS-2)
SUPPLY FAN DISCHARGE HIGH STATIC PRESSURE SWITCH (SPS-1) STATUS
SUPPLY AIR HIGH STATIC PRESSURE SWITCH (SPS-2) STATUS
AI10
AI11 DOWNSTREAM SUPPLY AIR FLOWMETER (F-3)
DISCHARGE SUPPLY AIR FLOWMETER (F-2)
DI8 DOWNSTREAM SUPPLY AIR HIGH STATIC PRESSURE SWITCH (SPS-3) STATUS
CHILLED WATER CONTROL VALVE (V-2)
SUPPLY FAN VFD SPEED
AO3
AO4
KEYNOTES:
EXISTING TEMPERATURE ELEMENT IS LAYING
IN BOTTOM OF AHU. SECURELY AND
PERMANENTLY REINSTALL EXISTING
TEMPERATURE ELEMENT.
SD-1
DI3
FILTER STATUS (DPS-1)
SUPPLY FAN START/STOP
45-AHU-07 CONTROL SCHEMATIC
& SEQUENCE
45 WLP NMT
M45-206
NOTES:
1. ALL DEVICES ARE EXISTING DDC. SENSOR, ACTUATORS,
ETC. BE REUSED IF FUNCTIONAL AND COMPATIBLE.
2. PROVIDE NEW CONTROLLER. CONNECT NEW
CONTROLLER TO EXISTING ELECTRICAL SERVICE.
FAN
AO4
AI7
COIL
V-1
NO
HTG
AI4
AO2
PANEL
DDC CONTROL
AI3
T-1OUTSIDE AIR
RETURN AIR
AI5
T-2
COIL
CLG
NC
AI6
AO3
AI8
T-3
SPS-1
DI5
DPS-1
DI2
AIR
FILTER
FLOWMETER
AI1
F-1
DO2
DI4
OA
FAN
AO1
AI2
DO1
DI1
CONTROL PANEL
VAV45-8-8
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE AIR HANDLING UNIT SHALL BE STARTED AND STOPPED AUTOMATICALLY AT THE ECC. THE HOA SWITCH SHALL BE KEPT IN THE AUTO POSITION. HAND AND OFF POSITIONS SHALL BE USED FOR
MAINTENANCE ONLY.
2. TEMPERATURE CONTROLS
2.1. WHEN THE OA DEWPOINT TEMPERATURE IS ABOVE 55°F THE SUPPLY AIR TEMPERATURE, SENSED BY T-3, SHALL BE MAINTAIN AT TEMPERATURE SETPOINT 55°F (ADJUSTABLE) VIA DDC BY MODULATING
THE COOLING CONTROL VALVE, V-2. WHEN OA DEWPOINT IS BELOW 55°F THE SUPPLY AIR
TEMPERATURE SETPOINT SHALL BE RESET BASED ON TERMINAL BOX DEMAND, FAN SPEED, AND
OUTSIDE AIR DEW POINT TO MINIMIZE TOTAL ENERGY USAGE.
2.2. WHEN THE TEMPERATURE OF THE MIXED AIR, SENSED BY T-2, IS BELOW 40°F, THE DDC SHALL MODULATE THE HEATING CONTROL VALVE, V-1, TO MAINTAIN THE AIR TEMPERATURE SENSED BY T-3
AT 55°F (ADJUSTABLE).
3. AIR FLOW CONTROLS
3.1. THE SUPPLY AIR FLOW SHALL BE CONTROLLED BY THE DDC MODULATING THE SUPPLY FAN VFD TO MAINTAIN 1.0" OF DUCT STATIC PRESSURE (ADJUSTABLE) SENSED BY SPS-2. SEE FLOOR PLANS FOR THE LOCATION OF SPS-2. STATIC PRESSURE SETPOINT SHALL BE RESET BASED ON TERMINAL BOX
DAMPER POSITIONS TO MINIMIZE FAN ENERGY.
3.2. THE OUTSIDE AIR FLOW SHALL BE CONTROLLED MODULATING THE OUTSIDE AIR FAN VFD TO
MAINTAIN OUTSIDE AIR FLOW AT THE SCHEDULED CFM.
3.3. THE DDC, USING HIGH PRESSURE SENSOR, SPS-1, LOCATED AT THE SUPPLY FAN DISCHARGE SHALL PREVENT THE SUPPLY FAN FROM DEVELOPING OVER 3" OF STATIC PRESSURE (ADJUSTABLE). IF
STATIC PRESSURE AT SPS-1 DOES EXCEED 3", THE SUPPLY AIR FAN SHALL STOP.
4. FREEZE PROTECTION
4.1. IF THE AIR TEMPERATURE, AS SENSED BY T-2, FALLS BELOW 45°F, AN ALARM SIGNAL SHALL INDICATE AT THE DDC AND ECC. IF THE TEMPERATURE FALLS BELOW 40°F, THE SUPPLY AND RETURN FANS
SHALL SHUT DOWN AND A CRITICAL ALARM SHALL INDICATE DDC AND ECC.
5. EMERGENCY CONTACT SPEED OPERATION
5.1. UPON FAILURE OF THE VFD, THE SUPPLY FAN SHALL BE STARTED/STOPPED MANUALLY AT THE DDC
OR THE ECC THROUGH THE BYPASS STARTER. FANS SHALL THEN BE OPERATED AT CONSTANT
SPEED.
6. FILTER STATUS
6.1. WHEN FILTER STATIC PRESSURE, AS SENSED BY EITHER DPS-1 OR DPS-2, EXCEEDS SPECIFIED MAX.
STATIC PRESSURE, AN ALARM SIGNAL SHALL INDICATE AT THE DDC AND ECC.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
T-4T
AI10
AMBIENT AIR
TEMPERATURE SENSOR
L P
S
C H
W R
V-2
VFD VFDT T T
OUTSIDE AIR FLOWMETER (F-1)
OUTSIDE AIR FAN VFD STATUSAI2
AI1
MIXED AIR TEMPERATURE SENSOR (T-1)AI3
HOT WATER CONTROL VALVE (V-1)AI4
AI6
AI7
AI5
AI8
AI9
HEATING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-2)
CHILLED WATER CONTROL VALVE (V-2)
SUPPLY AIR TEMPERATURE SENSOR (T-3)
DI6
DI7
DI4
DI2
DI3
DI1
DI5
OUTSIDE AIR FAN STATUS
SUPPLY FAN VFD STATUS
SUPPLY FAN STATUS
FILTER STATUS (DPS-2)
SUPPLY FAN DISCHARGE HIGH STATIC PRESSURE SWITCH (SPS-1) STATUS
SUPPLY AIR HIGH STATIC PRESSURE SWITCH (SPS-2) STATUS
AI10 AMBIENT AIR TEMPERATURE SENSOR (T-4)
DISCHARGE SUPPLY AIR FLOWMETER (F-2)
1 1
SD-1
DI3
FILTER STATUS (DPS-1)
RETURN AIR SMOKE DETECTOR (SD-1) STATUS
OUTSIDE AIR FAN VFD SPEED
HOT WATER CONTROL VALVE (V-1)
AO1
AO2
DO1
DO2
OUTSIDE AIR FAN START/STOP
CHILLED WATER CONTROL VALVE (V-2)
SUPPLY FAN VFD SPEED
AO3
AO4
SUPPLY FAN START/STOP
DPS-2
DI6
AIR
FILTER
AI9
F-2
SPS-2
DI7
45-AHU-08 CONTROL SCHEMATIC
& SEQUENCE
45 WLP NMT
M45-207
KEYNOTES:
EXISTING TEMPERATURE ELEMENT IS LAYING
IN BOTTOM OF AHU. SECURELY AND
PERMANENTLY REINSTALL EXISTING
TEMPERATURE ELEMENT.
NOTES:
1. ALL DEVICES ARE EXISTING DDC. SENSOR, ACTUATORS,
ETC. BE REUSED IF COMPATIBLE.
2. PROVIDE NEW CONTROLLER. CONNECT NEW
CONTROLLER TO EXISTING ELECTRICAL SERVICE.
STR
HWR
HWS
45-WFM-15
HWS FLOW
HWR TEMPERATURE
SEQUENCE OF OPERATION
1. OCCUPIED MODE
1.1. STEAM CONTROL VALVES SHALL MODULATE TO MAINTAIN THE HOT WATER SUPPLY
TEMPERATURE AT SETPOINT.
1.2. THE HOT WATER SUPPLY TEMPERATURE RESETS INVERSELY WITH THE OUTDOOR
TEMPERATURE AS SCHEDULED: AT 30°F OA - HWS AT 180°F, AT 70°F OA - HWS AT
140°F.
1.3. STEAM HOT WATER CONVERTERS, 45-HTX-5 & 45-HTX-6, ARE 100% REDUNDANT AND
ONLY ONE UNIT AT A TIME WILL OPERATE.
1.4. HOT WATER PUMPS ARE CONTROLLED BY THE DDC SYSTEM. THE PUMPS ARE 100%
REDUNDANT REQUIRING ONLY ONE PUMP AT A TIME TO OPERATE. THE LEAD/LAG
WATER PUMPS AND HEAT EXCHANGERS ARE SEQUENCED BY THE DDC SYSTEM TO
CHANGE EVERY 7 DAYS. IN THE EVENT A PUMP FAILS TO START IN 30 SECONDS OR
NO FLOW CONDITION AT THE HEAT EXCHANGER, AN ALARM IS GENERATED, AND THE
SECOND PUMP/EXCHANGER STARTS AUTOMATICALLY.
2. UNOCCUPIED MODE
2.1. IF THE OUTSIDE AIR TEMPERATURE IS BELOW 40°F (ADJUSTABLE) THE DDC SYSTEM
WILL PLACE THE HWS IN OCCUPIED MODE TO START PUMPS AND ACTUATE STEAM
VALVES TO MAINTAIN SETPOINT AS NEEDED BY THE RESET SCHEDULE.
3. VALVE SEQUENCE FOR LEAD HEAT EXCHANGER
3.1. AFTER THE FLOW THROUGH THE HEAT EXCHANGER HAS BEEN CONFIRMED VIA THE
FLOW SWITCH, THE DDC CONTROLLER WILL RECEIVE AN INPUT AND THE 24VAC
POWER WILL BE APPLIED TO THE STEAM VALVE ACTUATORS. THE STEAM VALVES
SHALL OPERATE IN THREE MODES OF CONTROL.
3.2. FIRST MODE: THE 13 CAPACITY STEAM VALVE MODULATES TO MAINTAIN THE ACTIVE
SETPOINT. AFTER THE 13 VALVE HAS REACHED 100% CAPACITY FOR 5 MINUTES, THE
SECOND MODE WILL BE ENABLED.
3.3. SECOND MODE: THE 13 VALVE IS COMMANDED TO CLOSE AND THE 2
3 CAPACITY
STEAM VALVE MODULATES TO MAINTAIN SETPOINT. AFTER THE 2
3 VALVE HAS
REACHED 100% CAPACITY FOR 5 MINUTES, THE THIRD MODE WILL BE ENABLED.
3.4. THIRD MODE: THE 13 VALVE WILL BE RE-ENABLED, AND BOTH STEAM VALVES
MODULATE TOGETHER TO MAINTAIN SETPOINT.
3.5. AS DEMAND REDUCES, THE MODES WILL BE DISABLED AT 40% COMMANDED VALVE
(DIFFERENTIAL OF 60%), AND A 5 MINUTE DELAY WILL BE ACTIVATED BETWEEN
MODES. UPON A LOSS OF FLOW THE STEAM VALVES WILL BE CLOSED (HARDWIRED
AND SOFTWARE INTERLOCKS).
SEQUENCE OF OPERATION
1. OCCUPIED MODE
1.1. STEAM CONTROL VALVES SHALL MODULATE TO MAINTAIN THE HOT WATER SUPPLY
TEMPERATURE AT SETPOINT.
1.2. THE HOT WATER SUPPLY TEMPERATURE RESETS INVERSELY WITH THE OUTDOOR
TEMPERATURE AS SCHEDULED: AT 30°F OA - HWS AT 180°F, AT 70°F OA - HWS AT 140°F.
1.3. STEAM HOT WATER CONVERTERS, 45-HTX-1 & 45-HTX-2, ARE 100% REDUNDANT AND
ONLY ONE UNIT AT A TIME WILL OPERATE.
1.4. HOT WATER PUMPS ARE CONTROLLED BY THE DDC SYSTEM. THE PUMPS ARE 100%
REDUNDANT REQUIRING ONLY ONE PUMP AT A TIME TO OPERATE. THE LEAD/LAG
WATER PUMPS AND HEAT EXCHANGERS ARE SEQUENCED BY THE DDC SYSTEM TO
CHANGE EVERY 7 DAYS. IN THE EVENT A PUMP FAILS TO START IN 30 SECONDS OR NO
FLOW CONDITION AT THE HEAT EXCHANGER, AN ALARM IS GENERATED, AND THE
SECOND PUMP/EXCHANGER STARTS AUTOMATICALLY.
2. UNOCCUPIED MODE
2.1. IF THE OUTSIDE AIR TEMPERATURE IS BELOW 40°F (ADJUSTABLE) THE DDC SYSTEM
WILL PLACE THE HWS IN OCCUPIED MODE TO START PUMPS AND ACTUATE STEAM
VALVES TO MAINTAIN SETPOINT AS NEEDED BY THE RESET SCHEDULE.
3. VALVE SEQUENCE FOR LEAD HEAT EXCHANGER
3.1. AFTER THE FLOW THROUGH THE HEAT EXCHANGER HAS BEEN CONFIRMED VIA THE
FLOW SWITCH, THE DDC CONTROLLER WILL RECEIVE AN INPUT AND THE 24VAC
POWER WILL BE APPLIED TO THE STEAM VALVE ACTUATORS. THE STEAM VALVES
SHALL OPERATE IN THREE MODES OF CONTROL.
3.2. FIRST MODE: THE 13 CAPACITY STEAM VALVE MODULATES TO MAINTAIN THE ACTIVE
SETPOINT. AFTER THE 13 VALVE HAS REACHED 100% CAPACITY FOR 5 MINUTES, THE
SECOND MODE WILL BE ENABLED.
3.3. SECOND MODE: THE 13 VALVE IS COMMANDED TO CLOSE AND THE 2
3 CAPACITY STEAM
VALVE MODULATES TO MAINTAIN SETPOINT. AFTER THE 2
3 VALVE HAS REACHED 100%
CAPACITY FOR 5 MINUTES, THE THIRD MODE WILL BE ENABLED.
3.4. THIRD MODE: THE 13 VALVE WILL BE RE-ENABLED, AND BOTH STEAM VALVES
MODULATE TOGETHER TO MAINTAIN SETPOINT.
3.5. AS DEMAND REDUCES, THE MODES WILL BE DISABLED AT 40% COMMANDED VALVE
(DIFFERENTIAL OF 60%), AND A 5 MINUTE DELAY WILL BE ACTIVATED BETWEEN MODES.
UPON A LOSS OF FLOW THE STEAM VALVES WILL BE CLOSED (HARDWIRED AND
SOFTWARE INTERLOCKS).
TEMPERATURE
SENSOR (TYP)
AI5
T
AI6
DI1
FTFS
T
AI7
DO1
DI3
DO2
DI4
STEAM CONV.
TO COND. PUMP
TO COND. PUMP
STEAM
SUPPLY
STEAM
SUPPLY
STEAM CONV.
AI2
45-HTX-6 VALVE 2
3 VALVE OUTPUT
45-HTX-6 VALVE 1
3 VALVE OUTPUT
DI2
FS
45-HTX-5 VALVE 2
3 VALVE OUTPUT
45-HTX-5 VALVE 1
3 VALVE OUTPUT
T
AI8
AMBIENT AIR
TEMPERATURE SENSOR
INSTALLED ON NORTH
SIDE OF BUILDING 180 160 140
HOT WATER SETPOINT
(DEG F)
OUTDOOR
AIR
TEMPERATURE
(DEG F)
HEATING HOT WATER RESET
SCHEDULE
AI2
AI1
AI3
AI4
AI6
AI7
AI5
AI8
STEAM CONVERTER (45-HTX-5) VALVE 2 STATUS
STEAM CONVERTER (45-HTX-6) VALVE 2 STATUS
STEAM CONVERTER (45-HTX-6) VALVE 1 STATUS
HOT WATER SUPPLY TEMPERATURE SENSOR
HOT WATER SUPPLY FLOWMETER (45-WFM-15)
HOT WATER RETURN TEMPERATURE SENSOR
STEAM CONVERTER (45-HTX-5) VALVE 1 STATUS
DI4
DI3
DI1
STEAM CONVERTER (45-HTX-6) FLOW SWITCH STATUS
HOT WATER PUMP (45-HWP-5) STATUS
HOT WATER PUMP (45-HWP-6) STATUS
STEAM CONVERTER (45-HTX-5) FLOW SWITCH STATUS
DI2
STR
AO2
AI1
AO1
AI3
AO3
AI4
AO4
DO1
DO2
HOT WATER PUMP (45-HWP-5) START/STOP
HOT WATER PUMP (45-HWP-6) START/STOP
AO1
AO2
STEAM CONVERTER (45-HTX-5) VALVE 2 CONTROLLER
STEAM CONVERTER (45-HTX-5) VALVE 1 CONTROLLER
AO3
AO4
STEAM CONVERTER (45-HTX-6) VALVE 2 CONTROLLER
STEAM CONVERTER (45-HTX-6) VALVE 1 CONTROLLER
AMBIENT AIR TEMPERATURE SENSOR
HWR
HWS
45-WFM-16
HWS FLOW
HWR TEMPERATURE
TEMPERATURE
SENSOR (TYP)
AI5
T
AI6
DI1
FTFS
T
AI7
STEAM CONV.
TO COND. PUMP
TO COND. PUMP
STEAM
SUPPLY
STEAM
SUPPLY
STEAM CONV.
AI2
45-HTX-2 VALVE 2
3 VALVE OUTPUT
45-HTX-2 VALVE 1
3 VALVE OUTPUT
DI2
FS
45-HTX-1 VALVE 2
3 VALVE OUTPUT
45-HTX-1 VALVE 1
3 VALVE OUTPUT
T
AI8
AMBIENT AIR
TEMPERATURE SENSOR
INSTALLED ON NORTH
SIDE OF BUILDING
180 160 140
HOT WATER SETPOINT
(DEG F)
OUTDOOR
AIR
TEMPERATURE
(DEG F)
HEATING HOT WATER RESET
SCHEDULE
AO2
AI1
AO1
AI3
AO3
AI4
AO4
AI2
AI1
AI3
AI4
AI6
AI7
AI5
AI8
STEAM CONVERTER (45-HTX-1) VALVE 2 STATUS
STEAM CONVERTER (45-HTX-2) VALVE 2 STATUS
STEAM CONVERTER (45-HTX-2) VALVE 1 STATUS
HOT WATER SUPPLY TEMPERATURE SENSOR
HOT WATER SUPPLY FLOWMETER (45-WFM-16)
HOT WATER RETURN TEMPERATURE SENSOR
STEAM CONVERTER (45-HTX-1) VALVE 1 STATUS
DI4
DI3
DI1
STEAM CONVERTER (45-HTX-2) FLOW SWITCH STATUS
HOT WATER PUMP (45-HWP-1) STATUS
HOT WATER PUMP (45-HWP-2) STATUS
STEAM CONVERTER (45-HTX-1) FLOW SWITCH STATUS
DI2
DO1
DO2
HOT WATER PUMP (45-HWP-1) START/STOP
HOT WATER PUMP (45-HWP-2) START/STOP
AO1
AO2
STEAM CONVERTER (45-HTX-1) VALVE 2 CONTROLLER
STEAM CONVERTER (45-HTX-1) VALVE 1 CONTROLLER
AO3
AO4
STEAM CONVERTER (45-HTX-2) VALVE 2 CONTROLLER
STEAM CONVERTER (45-HTX-2) VALVE 1 CONTROLLER
AMBIENT AIR TEMPERATURE SENSOR
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
NOTES:
1. ALL DEVICES ARE EXISTING DDC. SENSORS,
ACTUATORS, ETC MAY BE REUSED IF
FUNCTIONAL AND COMPATIBLE.
2. PROVIDE NEW CONTROLLER. CONNECT NEW
CONTROLLER TO EXISTING ELECTRICAL
SERVICE.
STR
DO1
DI3
DO2
DI4
STR
HHW SYSTEMS 1 & 2 CONTROL
SCHEMATICS & SEQUENCES
45 WLP NMT
M45-208
NOTES:
1. ALL DEVICES ARE EXISTING DDC. SENSORS,
ACTUATORS, ETC MAY BE REUSED IF
FUNCTIONAL AND COMPATIBLE.
2. PROVIDE NEW CONTROLLER. CONNECT NEW
CONTROLLER TO EXISTING ELECTRICAL
SERVICE.
HWS
HWR
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE HOT WATER SYSTEM CONSISTS OF HOT WATER PUMPS WITH INDIVIDUAL
VARIABLE FREQUENCY DRIVES (VFD) AND TWO STEAM HEAT EXCHANGERS. THE
SYSTEM IS DDC CONTROLLED WITH ELECTRIC ACTUATION.
1.2. THE SYSTEM IS ON WHEN ANY HOT WATER COIL CALLS FOR HEATING.
2. OCCUPIED MODE
2.1. ONCE FLOW IS PROVEN BY THE FLOW SWITCH AT THE CONVERTER, STEAM CONTROL
VALVES SHALL MODULATE TO MAINTAIN THE HOT WATER SUPPLY TEMPERATURE AT
SETPOINT.
2.2. THE HOT WATER SUPPLY TEMPERATURE RESETS INVERSELY WITH THE OUTDOOR
TEMPERATURE AS SCHEDULED: AT 30°F OA - HWS AT 180°F, AT 70°F OA - HWS AT
140°F.
2.3. STEAM HOT WATER CONVERTERS ARE 100% REDUNDANT AND ONLY ONE UNIT AT A
TIME WILL OPERATE.
2.4. HOT WATER PUMPS ARE CONTROLLED BY THE DDC SYSTEM. THE PUMPS ARE 100%
REDUNDANT REQUIRING ONLY ONE PUMP AT A TIME TO OPERATE. THE LEAD/LAG
WATER PUMPS AND HEAT EXCHANGERS ARE SEQUENCED BY THE DDC SYSTEM TO
CHANGE EVERY 7 DAYS. IN THE EVENT A PUMP FAILS TO START IN 30 SECONDS OR
NO FLOW CONDITION AT THE HEAT EXCHANGER, AN ALARM IS GENERATED, AND THE
SECOND PUMP/EXCHANGER STARTS AUTOMATICALLY.
3. UNOCCUPIED MODE
3.1. IF THE OUTSIDE AIR TEMPERATURE IS BELOW 40°F (ADJUSTABLE) THE DDC SYSTEM
WILL PLACE THE HWS IN OCCUPIED MODE TO START PUMPS AND ACTUATE STEAM
VALVES TO MAINTAIN SETPOINT AS NEEDED BY THE RESET SCHEDULE.
TEMPERATURE
SENSOR (TYP)
AI3
T
AI4
DI1
FTFS
STEAM CONV.
TO COND. PUMP
TO COND. PUMP
STEAM
SUPPLY
STEAM
SUPPLY
STEAM CONV.
AI1
DI2
FS
T
AI6
AMBIENT AIR
TEMPERATURE SENSOR
INSTALLED ON NORTH
SIDE OF BUILDING 180 160 140
HOT WATER SETPOINT
(DEG F)
OUTDOOR
AIR
TEMPERATURE
(DEG F)
HEATING HOT WATER RESET
SCHEDULE
AO1
AI2
AO2
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
1 EXISTING DDC DEVICE TO BE REUSED
IF FUNCTIONAL AND COMPATIBLE.
2 NEW DDC DEVICE TO BE INSTALLED.
KEYNOTES
AI2
AI1
AI3
AI4
AI6
AI5
STEAM CONVERTER VALVE STATUS
HOT WATER SUPPLY TEMPERATURE SENSOR
HOT WATER SUPPLY FLOWMETER
HOT WATER SUPPLY TEMPERATURE SENSOR
DI4
DI3
DI1
STEAM CONVERTER FLOW SWITCH STATUS
HOT WATER PUMP (45-P-9) STATUS
HOT WATER PUMP (45-P-10) STATUS
STEAM CONVERTER FLOW SWITCH STATUS
DI2
DO1
DO2
HOT WATER PUMP (45-P-9) START/STOP
HOT WATER PUMP (45-P-10) START/STOP
AO1
AO2
AMBIENT AIR TEMPERATURE SENSOR
STEAM CONVERTER VALVE STATUS
STEAM CONVERTER VALVE CONTROLLER
STEAM CONVERTER VALVE CONTROLLER
T
AI5
STR
DO1
DI3
DI4
STR
DO2
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE EXISTING CHILLED WATER SUPPLY FROM THE CENTRAL
COOLING PLANT PROVIDES CHILLED WATER TO THE VFD
SECONDARY PUMPING SYSTEM AT BUILDING 45. THE
SECONDARY PUMPS ARE 100% REDUNDANT REQUIRING ONLY
ONE PUMP AT A TIME TO OPERATE.
1.2. UPON A CALL FOR COOLING FROM ANY AIR HANDLER, FAN COIL,
OR BLOWER COIL, THE LEAD CHILLED WATER PUMP SHALL
ENERGIZE AND THE RESPECTIVE VFD SHALL MODULATE THE
PUMP TO MAINTAIN THE PRESSURIZATION SETPOINT
(ADJUSTABLE) AT THE DIFFERENTIAL PRESSURE SENSOR
LOCATED 3 4 OF THE WAY DOWN THE LONGEST PIPING RUN. THE
VFD WILL MODULATE AS REQUIRED TO MAINTAIN THE SYSTEM
PRESSURE SETPOINT.
1.3. CHILLED WATER DIFFERENTIAL SETPOINT SHALL BE RESET
BASED ON CHILLED WATER VALVE POSITIONS TO MINIMIZE
PUMP SPEED.
1.4. A HYDRONIC BRIDGE CIRCUIT DOWNSTREAM OF THE CHILLED
WATER PUMPS WITH A FLOWMETER, TEMPERATURE SENSOR
AND MANUAL BALANCING VALVE SHALL BE UTILIZED TO BYPASS
SECONDARY CHILLED WATER FLOW BACK TO THE PRIMARY
LOOP AT MIN. VFD SETPOINT, WHILE COOLING COIL 2-WAY
VALVES FLOW SHUT OFF AS COOLING LOAD DICTATES. MANUAL
BALANCING VALVES SHALL BE SET AS A PRESSURE DROP TO
MATCH REMAINDER OF BUILDING PIPING CIRCUIT AT MIN.
This is the start of the file's text. The full file is on GovTribe.