36C25618U0323-0002008.pdf
PDF 4 MB Posted
- Attached to
- Services Commissioning for HVAC Digital Controls Federal contract opportunity
- Solicitation number
- 36C25618U0323
About this file
36C25618U0323 0002 Drawings - Building 7 Part 4 (M7-4XX Series).pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| -15380.docx | DOCX document | |
| 36C25618U0323-0002007.pdf | ||
| 36C25618U0323-0002005.pdf | ||
| 36C25618U0323-0002004.pdf | ||
| 36C25618U0323-0002006.pdf | ||
| 36C25618U0323-0002012.pdf | ||
| 36C25618U0323-0002000.docx | DOCX document | |
| 36C25618U0323-0002013.pdf | ||
| 36C25618U0323-0002010.pdf | ||
| 36C25618U0323-0002002.pdf | ||
| 36C25618U0323-0002011.pdf | ||
| 36C25618U0323-0002009.pdf | ||
| 36C25618U0323-0002014.pdf | ||
| 36C25618U0323-0002001.docx | DOCX document | |
| 36C25618U0323-0002003.pdf | ||
| 36C25618U0323-0001000.docx | DOCX document | |
| 36C25618U0323-002.pdf | ||
| 36C25618U0323-001.docx | DOCX document | |
| 36C25618U0323-000.docx | DOCX document |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPS-2
AI15
VFD
DO4
AO5
DI9
AI14
DI6DI2
D02DO1
DI1
SUPPLY AIR
PANEL
DDC CONTROL
OUTSIDE AIR
D-1
D-2
V-2
AI8
AO3
T-4
DPS-1
SD-1
DI10
SD-2
NC-SR
SPS-1
T-1
RETURN AIR
DPS-2
FLOWMETER
AI1
F-1
V-1A
V-1B
S C
R
T-3
NC-SR
NC-SR
T-5
10' MIN. BETWEEN
HUMIDIFIER AND
ELEMENT
V-4NC
AI13
AO4
HUMIDIFIER
M.P. STEAM
FROM CENTRAL
PLANT
T-6
SPS-3
DI12
T/H-2
AI2
DI3
AI3
DI4
DI5
AI5
V-3F T
C W
R
AI6
AO1
AI7
AO2
DI7
T
T-2
AI9
AI10
AI11
AI12
DI8
DO3
DI11
AI16
AI17
SUPPLY AIRSPS-4
AI18
AI19
DI13
T-7T
T/H-1
AI4
AI20
NC
NO
L P
S
F-3
F-4
F-2
SEQUENCE OF OPERATION
1. START/STOP CONTROL
1.1. 7E-AHU-7-2 IS NORMALLY STARTED AND STOPPED REMOTELY AT THE ECC. H-O-A SWITCH SHALL BE
KEPT IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR
MAINTENANCE. WHEN FAN RUN STATUS IS PROVEN VIA A CURRENT SENSING RELAY, CONTROL
LOOPS SHALL BE ENERGIZED. STOPPING THE UNIT SHALL DE-ENERGIZE THE CONTROL LOOPS AND ALL VALVES SHALL GO TO THE CLOSED POSITION, THE OUTSIDE AIR DAMPER SHALL CLOSE, AND THE RETURN AIR DAMPER SHALL OPEN. OUTSIDE AIR SHALL BE METERED TO MONITOR AND MAINTAIN CONSTANT MIN. O.A. AIRFLOW BY MODULATING THE RETURN AND OUTSIDE AIR CONTROL DAMPERS.
2. TEMPERATURE CONTROL
2.1. A TEMPERATURE SENSOR IN THE UNIT SUPPLY AIR SHALL TRANSMIT TEMPERATURE CHANGES TO THE ASC. THE ASC SHALL MODULATE THE 2-WAY COOLING COIL VALVE TO MAINTAIN SUPPLY AIR SETPOINT AT 55°F (ADJUSTABLE). A TEMPERATURE SENSOR IN THE PREHEAT COIL DISCHARGE
SHALL TRANSMIT TEMPERATURE CHANGES TO THE ASC. THE ASC SHALL MODULATE THE 2-WAY
STEAM VALVE PREHEAT COIL VALVE TO MAINTAIN PREHEAT SETPOINT (ADJUSTABLE).
3. DEHUMIDIFICATION CONTROL
3.1. HUMIDITY SENSOR, (1% ACCURACY), SHALL MEASURE RETURN AIR HUMIDITY AT THE AHU. THE BAS
SHALL AVERAGE THE POSITION OF THE VAV BOX AIR VALVES AND SHALL ADJUST THE AIR
TEMPERATURE UPWARD OR DOWNWARD TO MAXIMIZE THE SUPPLY AIR TEMPERATURE THAT SHALL
ALLOW FOR THE MOST EFFICIENT (HIGHEST) SUPPLY AIR TEMPERATURE TO SATISFY VAV BOX
OPERATION DURING THE OCCUPIED PERIOD OF OPERATION. IF THE RETURN AIR HUMIDITY RISES TO 60% (NOMINAL, ADJUSTABLE), THE SUPPLY AIR TEMPERATURE OF THE AHU SHALL BE LIMITED (LOWERED) SO AS TO KEEP THE RETURN AIR HUMIDITY AT OR BELOW 60% (ADJUSTABLE). ALSO, SYSTEM SHALL UTILIZE CALCULATED R.A. DEWPOINT TEMPERATURE TO COMPARE WITH A MAX.
DEWPOINT SETPOINT OF 55°F (ADJUSTABLE). IN ADDITION TO HUMIDITY, TO OVERRIDE CHW VALVE
FOR DEHUMIDIFICATION.
4. HUMIDIFICATION CONTROL
4.1. RETURN AIR HUMIDITY SHALL BE MONITORED. HUMIDIFIER STEAM VALVE SHALL MODULATE TO SUPPLY STEAM TO AHU MOUNTED DIRECT-INJECTION STEAM MANIFOLD REQUIRED TO MAINTAIN THE RETURN AIR RELATIVE HUMIDITY SETPOINT OF 30% (ADJUSTABLE AT ECC) AS SENSED BY THE
RETURN RELATIVE HUMIDITY SENSOR. PRIOR TO ACTIVATION OF MODULATING STEAM CONTROL
VALVE, THE ON/OFF CONTROL VALVE SHALL BE ENABLED THROUGH ECC AND JACKET
TEMPERATURE SENSED BY HIGH TEMPERATURE SENSOR SHALL BE WARM ENOUGH TO PREVENT
CONDENSATION. THE HIGH LIMIT HUMIDITY SENSOR, LOCATED IN THE SUPPLY AIR DUCT 10' AWAY FROM THE HUMIDIFIER, SHALL DISBALE THE HUMIDIFIER AND GIVE AN ALARM SIGNAL TO THE ECC, IF THE SUPPLY AIR HUMIDITY EXCEEDS 85% RH (ADJUSTABLE). THE AIRFLOW SWITCH SHALL PROVE
AIRFLOW BEFORE HUMIDITY CONTROLS ARE ACTIVATED. NORMALLY CLOSED HUMIDIFIER STEAM
SUPPLY VALVES SHALL OPEN WHEN OUTSIDE AIR TEMPERATURE DROPS BELOW 60°F AND SHALL
CLOSE ABOVE 62°F OUTSIDE AIR TEMPERATURE OR WHEN SUPPLY FAN IS OFF. TEMPERATURE
SWITCH SHALL KEEP HUMIDIFIER VALVE CLOSED UNTIL CONDENSATE DRIP LEG REACHES
OPERATING TEMPERATURE.
5. STATIC PRESSURE AND AIRFLOW CONTROL
5.1. THE SUPPLY AIR FAN FLOW SHALL BE CONTROLLED BY THE DIGITAL CONTROL PANEL MODULATING FAN'S INDIVIDUAL ADJUSTABLE SPEED MOTOR CONTROLLER TO MAINTAIN 1.0" OF DUCT STATIC PRESSURE (FIELD ADJUSTABLE), AS SENSED BY THE DUCT STATIC PRESSURE SENSOR LOCATED AT
4 DISTANCE DOWN LONGEST DUCT MAIN. RESET STATIC PRESSURE BASED ON ACTUAL BUILDING
LOAD BY POLLING ALL VAV TERMINAL UNITS.
5.2. FILTER STATUS SHALL BE MONITORED AT EACH PRE-FILTER AND AFTER-FILTER BANK.
AMBIENT AIR SENSOR
INSTALLED ON NORTH
SIDE OF BUILDING
T T T T
T
SUPPLY
FAN
CLG
COIL
HTG
COIL
OUTSIDE AIR FLOWMETER (F-1)
RETURN AIR FLOWMETER (F-2)
HEATING COIL STEAM CONTROL VALVE (V-1B)
HEATING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-4)
LOCAL DDC CONTROLLER
AI2
AI9
AI8
AI1
AI4
AI5
AI6
AI7
RETURN AIR TEMPERATURE SENSOR (T/H-1)AI3
RETURN AIR HUMIDITY SENSOR (T/H-1)
RETURN AIR STATIC PRESSURE SENSOR (SPS-1)
MIXED AIR TEMPERATURE SENSOR (T-2)
HEATING COIL STEAM CONTROL VALVE (V-1A)
AIR PRE-FILTER STATUS (DPS-1)
DI1
RETURN AIR HIGH LIMIT TEMPERATURE SENSOR (T-1) STATUS
AIR FILTER STATUS (DPS-2)
OUTSIDE AIR DAMPER (D-1) STATUS
DI2 RETURN AIR DAMPER (D-2) STATUS
DI3
DI4
DI5
DO1
AO1
AO2
AO3 CHILLED WATER CONTROL VALVE (V-2)
HEATING COIL STEAM CONTROL VALVE (V-1A)
HEATING COIL STEAM CONTROL VALVE (V-1B)
OUTSIDE AIR DAMPER (D-1)
DO2 RETURN AIR DAMPER (D-2) STATUS
SUPPLY FAN STATUS
DI6
SUPPLY DISCHARGE AIR HIGH LIMIT STATIC PRESSURE SENSOR (SPS-3) STATUS
RETURN AIR SMOKE DETECTOR (SD-1) STATUS
DI7
HUMIDIFIER ON/OFF STEAM CONTROL VALVE (V-3) STATUSDI8
DI9
DI10
DI12
HEATING COIL DISCHARGE AIR LOW LIMIT TEMPERATURE SENSOR (T-3) STATUS
AO4
AO5 SUPPLY FAN VFD SPEED
HUMIDIFIER STEAM CONTROL VALVE (V-4)
DO3 HUMIDIFIER ON/OFF STEAM CONTROL VALVE (V-3)
SUPPLY DISCHARGE AIR SMOKE DETECTOR (SD-2)
SUPPLY DISCHARGE AIR STATIC PRESSURE SENSOR (SPS-2)
SUPPLY DISCHARGE AIR TEMPERATURE SENSOR (T/H-2)AI16
AI15
AI11
AI12
AI13
AI14
COOLING COIL CHILLED WATER FLOWMETERAI10
CHILLED WATER CONTROL VALVE (V-2)
COOLING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-5)
HUMIDIFIER STEAM CONTROL VALVE (V-4)
SUPPLY FAN VFD STATUS
AIR
PRE-
FILTER
AIR
FILTER
ZONE 1 SUPPLY AIR FLOWMETER (F-3)
AMBIENT AIR SENSOR (T-7)AI20
AI19
AI17
AI18
SUPPLY DISCHARGE AIR HUMIDITY SENSOR (T/H-2)
ZONE 2 SUPPLY AIR FLOWMETER (F-4)
DI11 SUPPLY DISCHARGE AIR HIGH LIMIT TEMPERATURE SENSOR (T-6) STATUS
DO4 SUPPLY FAN START/STOP
6. FREEZE PROTECTION
6.1. IF THE AIR TEMPERATURE AS SENSED BY PREHEATED MIXED AIR SENSOR (FREEZESTAT) UPSTREAM OF COOLING COIL FALLS BELOW 45°F, AN ALARM SIGNAL SHALL INDICATE AT THE DIGITAL CONTROL PANEL AND ECC. IF THIS TEMPERATURE FALLS BELOW 40°F, AS SENSED BY THE LOW TEMPERATURE SWITCH, THE SUPPLY FAN SHALL SHUT DOWN AND A CRITICAL ALARM SHALL INDICATE AT THE DIGITAL CONTROL PANEL AND ECC. THE LOW TEMPERATURE SWITCH SHALL BE HARDWIRED TO THE
SUPPLY FAN VFD, AND THE UNIT SHALL BE SHUTDOWN IN HAND, AUTO, OR BYPASS MODE
WHENEVER THERE IS A LOW TEMPERATURE ALARM. THE LOW TEMPERATURE SWITCH SHALL
REQUIRE MANUAL RESET AT THE DEVICE.
7. HIGH DUCT STATIC PROTECTION
7.1. A DUCT HIGH PRESSURE SENSOR LOCATED AT THE SUPPLY FAN DISCHARGE SHALL PREVENT THE SUPPLY FAN FROM DEVELOPING OVER 3" OF STATIC PRESSURE (FIELD ADJUSTABLE) IN THE SUPPLY DUCT. IF STATIC PRESSURE DOES EXCEED SET LIMIT, THE SUPPLY FAN SHALL STOP. DUCT HIGH
PRESSURE SENSOR SHALL BE HARDWIRED TO THE SUPPLY FAN VFD AND THE UNIT SHALL BE
SHUTDOWN IN HAND, AUTO OR BYPASS MODE WHENEVER THERE IS A HIGH DUCT PRESSURE ALARM.
THE DUCT HIGH STATIC PRESSURE SENSOR SHALL REQUIRE MANUAL RESET AT DEVICE.
8. SMOKE PROTECTION AND AUTOMATIC SHUTDOWN/RESTART
8.1. A SUPPLY AIR SMOKE DETECTOR IN THE SUPPLY AIR DUCT SHALL STOP THE UNIT AND TRANSMIT A
SIGNAL TO FIRE ALARM SYSTEM UPON DETECTION OF PRODUCTS OF COMBUSTION IN THE DUCT
AND CLOSE THE UNIT ISOLATION SMOKE DAMPERS LOCATED IN SUPPLY AND RETURN DUCT MAINS ADJACENT TO THE UNIT. RE: ELECTRICAL FOR ADDITIONAL REQUIREMENTS. EXHAUST FANS SERVING THE AREA OF THE SUPPLY FAN SHALL CONTINUE TO RUN. THE SUPPLY FAN SHALL RESTART AND
SMOKE DAMPERS SHALL OPEN WHEN FIRE ALARM IS RESET.
8.2. FIRESTATS SHALL BE PROVIDED FOR ANY FAN HANDLING 600CFM OR MORE. FIRESTATS SHALL STOP
ASSOCIATED FAN ON A RISE IN AIR TEMPERATURE ABOVE 125°F.
9. EMERGENCY CONSTANT SPEED OPERATION
9.1. UPON FAILURE OF VFD, THE SUPPLY FAN SHALL BE STARTED/STOPPED MANUALLY AT THE DDC OR
THE ECC THROUGH THE BYPASS STARTER. FANS SHALL THEN BE OPERATED AT CONSTANT SPEED.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
ZONE 2 SUPPLY AIR HIGH LIMIT STATIC PRESSURE SENSOR (SPS-4) STATUSDI13
AHU 7-2 CONTROL SCHEMATIC
& SEQUENCE
7 EXPANSION WLP NMT
M7-400
NOTES;
1. THESE DRAWINGS ARE REPRESENTATIVE OF THE DESIGN DRAWINGS FOR THE BUILDING 7
EXPANSION CURRENTLY ON GOING AND ARE FOR REFERENCE ONLY.
2. ALL EQUIPMENT IN THIS PROJECT WILL BE CONTROLLED BY THE CAMPUS SIEMENS SYSTEM.
MIGRATE ALL CONTROLS TO NEW SERVER.
10-30-13
AI14
VFD
DO4
AO5
DI9
AI13
DI6DI2
D02DO1
DI1
SUPPLY AIR
PANEL
DDC CONTROL
D-1
D-2
COIL
CLG
V-2
AO3
T-4
SD-1
DI10
SD-2
NC-SR
SPS-1
T-1
AI1
V-1
S C
R
T-3
NC-SR
T-5
10' MIN. BETWEEN
HUMIDIFIER AND
ELEMENT
V-4NC
AI12
AO4
HUMIDIFIER
M .P
S
T E
A M
F R
O M
C E
N T
R A
L P
L A
N T
T-6
SPS-3
DI12
T/H-2
AI2
DI3
AI3
DI4
DI5
AI5
V-3
C W
R
AI6
AO1
AI7 DI7
AI8
AI9
AI10
AI11
DI8
DO3
DI11
AI15
AI16
F-3
F-4
SPS-4
AI17
DI13
T/H-1
AI4
AI18
L P
S
F-2
SEQUENCE OF OPERATION
1. START/STOP CONTROL
1.1. 7E-AHU-7-3 IS NORMALLY STARTED AND STOPPED REMOTELY AT THE ECC. H-O-A SWITCH SHALL BE
KEPT IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR
MAINTENANCE. WHEN FAN RUN STATUS IS PROVEN VIA A CURRENT SENSING RELAY, CONTROL
LOOPS SHALL BE ENERGIZED. STOPPING THE UNIT SHALL DE-ENERGIZE THE CONTROL LOOPS AND ALL VALVES SHALL GO TO THE CLOSED POSITION, THE OUTSIDE AIR DAMPER SHALL CLOSE, AND THE RETURN AIR DAMPER SHALL OPEN. OUTSIDE AIR SHALL BE METERED TO MONITOR AND MAINTAIN CONSTANT MIN. O.A. AIRFLOW BY MODULATING THE RETURN AND OUTSIDE AIR CONTROL DAMPERS.
2. TEMPERATURE CONTROL
2.1. A TEMPERATURE SENSOR IN THE UNIT SUPPLY AIR SHALL TRANSMIT TEMPERATURE CHANGES TO THE ASC. THE ASC SHALL MODULATE THE 2-WAY COOLING COIL VALVE TO MAINTAIN SUPPLY AIR SETPOINT AT 55°F (ADJUSTABLE). A TEMPERATURE SENSOR IN THE PREHEAT COIL DISCHARGE
SHALL TRANSMIT TEMPERATURE CHANGES TO THE ASC. THE ASC SHALL MODULATE THE 2-WAY
STEAM VALVE PREHEAT COIL VALVE TO MAINTAIN PREHEAT SETPOINT (ADJUSTABLE).
3. DEHUMIDIFICATION CONTROL
3.1. HUMIDITY SENSOR, (1% ACCURACY), SHALL MEASURE RETURN AIR HUMIDITY AT THE AHU. THE BAS
SHALL AVERAGE THE POSITION OF THE VAV BOX AIR VALVES AND SHALL ADJUST THE AIR
TEMPERATURE UPWARD OR DOWNWARD TO MAXIMIZE THE SUPPLY AIR TEMPERATURE THAT SHALL
ALLOW FOR THE MOST EFFICIENT (HIGHEST) SUPPLY AIR TEMPERATURE TO SATISFY VAV BOX
OPERATION DURING THE OCCUPIED PERIOD OF OPERATION. IF THE RETURN AIR HUMIDITY RISES TO 60% (NOMINAL, ADJUSTABLE), THE SUPPLY AIR TEMPERATURE OF THE AHU SHALL BE LIMITED (LOWERED) SO AS TO KEEP THE RETURN AIR HUMIDITY AT OR BELOW 60% (ADJUSTABLE). ALSO, SYSTEM SHALL UTILIZE CALCULATED R.A. DEWPOINT TEMPERATURE TO COMPARE WITH A MAX.
DEWPOINT SETPOINT OF 55°F (ADJUSTABLE). IN ADDITION TO HUMIDITY, TO OVERRIDE CHW VALVE
FOR DEHUMIDIFICATION.
4. HUMIDIFICATION CONTROL
4.1. RETURN AIR HUMIDITY SHALL BE MONITORED. HUMIDIFIER STEAM VALVE SHALL MODULATE TO SUPPLY STEAM TO AHU MOUNTED DIRECT-INJECTION STEAM MANIFOLD REQUIRED TO MAINTAIN THE RETURN AIR RELATIVE HUMIDITY SETPOINT OF 30% (ADJUSTABLE AT ECC) AS SENSED BY THE
RETURN RELATIVE HUMIDITY SENSOR. PRIOR TO ACTIVATION OF MODULATING STEAM CONTROL
VALVE, THE ON/OFF CONTROL VALVE SHALL BE ENABLED THROUGH ECC AND JACKET
TEMPERATURE SENSED BY HIGH TEMPERATURE SENSOR SHALL BE WARM ENOUGH TO PREVENT
CONDENSATION. THE HIGH LIMIT HUMIDITY SENSOR, LOCATED IN THE SUPPLY AIR DUCT 10' AWAY FROM THE HUMIDIFIER, SHALL DISBALE THE HUMIDIFIER AND GIVE AN ALARM SIGNAL TO THE ECC, IF THE SUPPLY AIR HUMIDITY EXCEEDS 85% RH (ADJUSTABLE). THE AIRFLOW SWITCH SHALL PROVE
AIRFLOW BEFORE HUMIDITY CONTROLS ARE ACTIVATED. NORMALLY CLOSED HUMIDIFIER STEAM
SUPPLY VALVES SHALL OPEN WHEN OUTSIDE AIR TEMPERATURE DROPS BELOW 60°F AND SHALL
CLOSE ABOVE 62°F OUTSIDE AIR TEMPERATURE OR WHEN SUPPLY FAN IS OFF. TEMPERATURE
SWITCH SHALL KEEP HUMIDIFIER VALVE CLOSED UNTIL CONDENSATE DRIP LEG REACHES
OPERATING TEMPERATURE.
5. STATIC PRESSURE AND AIRFLOW CONTROL
5.1. THE SUPPLY AIR FAN FLOW SHALL BE CONTROLLED BY THE DIGITAL CONTROL PANEL MODULATING FAN'S INDIVIDUAL ADJUSTABLE SPEED MOTOR CONTROLLER TO MAINTAIN 1.0" OF DUCT STATIC PRESSURE (FIELD ADJUSTABLE), AS SENSED BY THE DUCT STATIC PRESSURE SENSOR LOCATED AT
4 DISTANCE DOWN LONGEST DUCT MAIN. RESET STATIC PRESSURE BASED ON ACTUAL BUILDING
LOAD BY POLLING ALL VAV TERMINAL UNITS.
5.2. FILTER STATUS SHALL BE MONITORED AT EACH PRE-FILTER AND AFTER-FILTER BANK.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
T
OUTSIDE AIR
DPS-1
RETURN AIR
DPS-2
FLOWMETER
F-1
T-2NC
NO
AIR
PRE-
FILTER
AIR
FILTER
T T T T T
HTG
COIL
SUPPLY
FAN
SUPPLY AIR
F T
OUTSIDE AIR FLOWMETER (F-1)
RETURN AIR FLOWMETER (F-2)
HEATING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-4)
LOCAL DDC CONTROLLER
AI2
AI9
AI8
AI1
AI4
AI5
AI6
AI7
RETURN AIR TEMPERATURE SENSOR (T/H-1)AI3
RETURN AIR HUMIDITY SENSOR (T/H-1)
RETURN AIR STATIC PRESSURE SENSOR (SPS-1)
MIXED AIR TEMPERATURE SENSOR (T-2)
HEATING COIL STEAM CONTROL VALVE (V-1)
AIR PRE-FILTER STATUS (DPS-1)
DI1
RETURN AIR HIGH LIMIT TEMPERATURE SENSOR (T-1) STATUS
AIR FILTER STATUS (DPS-2)
OUTSIDE AIR DAMPER (D-1) STATUS
DI2 RETURN AIR DAMPER (D-2) STATUS
DI3
DI4
DI5
SUPPLY FAN STATUS
DI6 RETURN AIR SMOKE DETECTOR (SD-1) STATUS
DI7
HUMIDIFIER ON/OFF STEAM CONTROL VALVE (V-3) STATUSDI8
DI9
DI10
HEATING COIL DISCHARGE AIR LOW LIMIT TEMPERATURE SENSOR (T-3) STATUS
SUPPLY DISCHARGE AIR SMOKE DETECTOR (SD-2)
SUPPLY DISCHARGE AIR STATIC PRESSURE SENSOR (SPS-2)
SUPPLY DISCHARGE AIR TEMPERATURE SENSOR (T/H-2)
AI16
AI15
AI11
AI12
AI13
AI14
COOLING COIL CHILLED WATER FLOWMETER
AI10 CHILLED WATER CONTROL VALVE (V-2)
COOLING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-5)
HUMIDIFIER STEAM CONTROL VALVE (V-4)
SUPPLY FAN VFD STATUS
ZONE 1 SUPPLY AIR FLOWMETER (F-3)
AI17
AI18
SUPPLY DISCHARGE AIR HUMIDITY SENSOR (T/H-2)
ZONE 2 SUPPLY AIR FLOWMETER (F-4)
DI11 SUPPLY DISCHARGE AIR HIGH LIMIT TEMPERATURE SENSOR (T-6) STATUS
DO1
AO1
AO2
AO3 CHILLED WATER CONTROL VALVE (V-2)
HEATING COIL STEAM CONTROL VALVE (V-1A)
HEATING COIL STEAM CONTROL VALVE (V-1B)
OUTSIDE AIR DAMPER (D-1)
DO2 RETURN AIR DAMPER (D-2) STATUS
AO4
AO5 SUPPLY FAN VFD SPEED
HUMIDIFIER STEAM CONTROL VALVE (V-4)
DO3 HUMIDIFIER ON/OFF STEAM CONTROL VALVE (V-3)
DO4 SUPPLY FAN START/STOP
ZONE 2 SUPPLY AIR HIGH LIMIT STATIC PRESSURE SENSOR (SPS-4) STATUSDI13
SUPPLY DISCHARGE AIR HIGH LIMIT STATIC PRESSURE SENSOR (SPS-3) STATUSDI12
6. FREEZE PROTECTION
6.1. IF THE AIR TEMPERATURE AS SENSED BY PREHEATED MIXED AIR SENSOR (FREEZESTAT) UPSTREAM OF COOLING COIL FALLS BELOW 45°F, AN ALARM SIGNAL SHALL INDICATE AT THE DIGITAL CONTROL PANEL AND ECC. IF THIS TEMPERATURE FALLS BELOW 40°F, AS SENSED BY THE LOW TEMPERATURE SWITCH, THE SUPPLY FAN SHALL SHUT DOWN AND A CRITICAL ALARM SHALL INDICATE AT THE DIGITAL CONTROL PANEL AND ECC. THE LOW TEMPERATURE SWITCH SHALL BE HARDWIRED TO THE
SUPPLY FAN VFD, AND THE UNIT SHALL BE SHUTDOWN IN HAND, AUTO, OR BYPASS MODE
WHENEVER THERE IS A LOW TEMPERATURE ALARM. THE LOW TEMPERATURE SWITCH SHALL
REQUIRE MANUAL RESET AT THE DEVICE.
7. HIGH DUCT STATIC PROTECTION
7.1. A DUCT HIGH PRESSURE SENSOR LOCATED AT THE SUPPLY FAN DISCHARGE SHALL PREVENT THE SUPPLY FAN FROM DEVELOPING OVER 3" OF STATIC PRESSURE (FIELD ADJUSTABLE) IN THE SUPPLY DUCT. IF STATIC PRESSURE DOES EXCEED SET LIMIT, THE SUPPLY FAN SHALL STOP. DUCT HIGH
PRESSURE SENSOR SHALL BE HARDWIRED TO THE SUPPLY FAN VFD AND THE UNIT SHALL BE
SHUTDOWN IN HAND, AUTO OR BYPASS MODE WHENEVER THERE IS A HIGH DUCT PRESSURE ALARM.
THE DUCT HIGH STATIC PRESSURE SENSOR SHALL REQUIRE MANUAL RESET AT DEVICE.
8. SMOKE PROTECTION AND AUTOMATIC SHUTDOWN/RESTART
8.1. A SUPPLY AIR SMOKE DETECTOR IN THE SUPPLY AIR DUCT SHALL STOP THE UNIT AND TRANSMIT A
SIGNAL TO FIRE ALARM SYSTEM UPON DETECTION OF PRODUCTS OF COMBUSTION IN THE DUCT
AND CLOSE THE UNIT ISOLATION SMOKE DAMPERS LOCATED IN SUPPLY AND RETURN DUCT MAINS ADJACENT TO THE UNIT. RE: ELECTRICAL FOR ADDITIONAL REQUIREMENTS. EXHAUST FANS SERVING THE AREA OF THE SUPPLY FAN SHALL CONTINUE TO RUN. THE SUPPLY FAN SHALL RESTART AND
SMOKE DAMPERS SHALL OPEN WHEN FIRE ALARM IS RESET.
8.2. FIRESTATS SHALL BE PROVIDED FOR ANY FAN HANDLING 600CFM OR MORE. FIRESTATS SHALL STOP
ASSOCIATED FAN ON A RISE IN AIR TEMPERATURE ABOVE 125°F.
9. EMERGENCY CONSTANT SPEED OPERATION
9.1. UPON FAILURE OF VFD, THE SUPPLY FAN SHALL BE STARTED/STOPPED MANUALLY AT THE DDC OR
THE ECC THROUGH THE BYPASS STARTER. FANS SHALL THEN BE OPERATED AT CONSTANT SPEED.
AHU 7-3 CONTROL SCHEMATIC
& SEQUENCE
7 EXPANSION WLP NMT
M7-401
NOTES;
1. THESE DRAWINGS ARE REPRESENTATIVE OF THE DESIGN DRAWINGS FOR THE BUILDING 7
EXPANSION CURRENTLY ON GOING AND ARE FOR REFERENCE ONLY.
2. ALL EQUIPMENT IN THIS PROJECT WILL BE CONTROLLED BY THE CAMPUS SIEMENS SYSTEM.
AI17
DO6
AO6
DI11
AI16
DI2
D02
DO1
DI1
PANEL
DDC CONTROL
OUTSIDE AIR
D-2
D-3
V-2
AO4
T-4
SD-1
DI12
SD-2
NC-SR
SPS-1
T
T-1
RETURN AIR
FLOWMETER
AI1
F-1
S C
R
T-3
T-5
10' MIN. BETWEEN
HUMIDIFIER AND
ELEMENT
V-4NC
AI15
AO5
HUMIDIFIER T-6
SPS-3
DI14
T/H-2
AI2
DI4
DI6
DI7
V-3
C W
R
DI9
T-2
AI11
AI12
AI13
AI14
DI10
DO5
DI13
AI18
AI19
SUPPLY AIR
F-3
SPS-4
DI15
T/H-1
NC
NO
AI20AI6 AI9
V-1A
AI7
AO2
AI8
AO3
D-1
NC
F-2
DO3
DI3
DO4
AO1
DI5
AI3 AI4
AI5
DI8
AI10
L P
S
CLEAN STEAM
GENERATOR
L P
C L E
A N
S T
E A
M
EXHAUST AIR
F-4
SEQUENCE OF OPERATION
1. START/STOP CONTROL
1.1. 7E-AHU-7-AC102 IS NORMALLY STARTED AND STOPPED REMOTELY AT THE ECC. H-O-A SWITCH SHALL BE KEPT IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR MAINTENANCE.
WHEN FAN RUN STATUS IS PROVEN VIA A CURRENT SENSING RELAY, CONTROL LOOPS SHALL BE ENERGIZED. STOPPING THE UNIT SHALL DE-ENERGIZE THE CONTROL LOOPS AND ALL VALVES SHALL GO TO THE CLOSED POSITION, THE OUTSIDE AIR DAMPER SHALL CLOSE, AND THE RETURN AIR DAMPER SHALL OPEN. OUTSIDE AIR SHALL BE METERED TO MONITOR AND MAINTAIN CONSTANT MIN. O.A.
AIRFLOW BY MODULATING THE RETURN AND OUTSIDE AIR CONTROL DAMPERS.
2. TEMPERATURE CONTROL
2.1. A TEMPERATURE SENSOR IN THE UNIT SUPPLY AIR SHALL TRANSMIT TEMPERATURE CHANGES TO THE ASC. THE ASC SHALL MODULATE THE 2-WAY COOLING COIL VALVE TO MAINTAIN SUPPLY AIR SETPOINT AT 55°F (ADJUSTABLE). A TEMPERATURE SENSOR IN THE PREHEAT COIL DISCHARGE SHALL TRANSMIT TEMPERATURE CHANGES TO THE ASC. THE ASC SHALL MODULATE THE 2-WAY STEAM VALVE PREHEAT
COIL VALVE TO MAINTAIN PREHEAT SETPOINT (ADJUSTABLE).
3. DEHUMIDIFICATION CONTROL
3.1. HUMIDITY SENSOR, (1% ACCURACY), SHALL MEASURE RETURN AIR HUMIDITY AT THE AHU. THE BAS
SHALL AVERAGE THE POSITION OF THE VAV BOX AIR VALVES AND SHALL ADJUST THE AIR
TEMPERATURE UPWARD OR DOWNWARD TO MAXIMIZE THE SUPPLY AIR TEMPERATURE THAT SHALL
ALLOW FOR THE MOST EFFICIENT (HIGHEST) SUPPLY AIR TEMPERATURE TO SATISFY VAV BOX
OPERATION DURING THE OCCUPIED PERIOD OF OPERATION. IF THE RETURN AIR HUMIDITY RISES TO 60% (NOMINAL, ADJUSTABLE), THE SUPPLY AIR TEMPERATURE OF THE AHU SHALL BE LIMITED (LOWERED) SO AS TO KEEP THE RETURN AIR HUMIDITY AT OR BELOW 60% (ADJUSTABLE). ALSO, SYSTEM SHALL UTILIZE CALCULATED R.A. DEWPOINT TEMPERATURE TO COMPARE WITH A MAX.
DEWPOINT SETPOINT OF 55°F (ADJUSTABLE). IN ADDITION TO HUMIDITY, TO OVERRIDE CHW VALVE FOR
DEHUMIDIFICATION.
4. HUMIDIFICATION CONTROL
4.1. RETURN AIR HUMIDITY SHALL BE MONITORED. HUMIDIFIER STEAM VALVE SHALL MODULATE TO SUPPLY STEAM TO AHU MOUNTED DIRECT-INJECTION STEAM MANIFOLD REQUIRED TO MAINTAIN THE RETURN AIR RELATIVE HUMIDITY SETPOINT OF 30% (ADJUSTABLE AT ECC) AS SENSED BY THE RETURN RELATIVE HUMIDITY SENSOR. PRIOR TO ACTIVATION OF MODULATING STEAM CONTROL VALVE, THE ON/OFF
CONTROL VALVE SHALL BE ENABLED THROUGH ECC AND JACKET TEMPERATURE SENSED BY HIGH
TEMPERATURE SENSOR SHALL BE WARM ENOUGH TO PREVENT CONDENSATION. THE HIGH LIMIT
HUMIDITY SENSOR, LOCATED IN THE SUPPLY AIR DUCT 10' AWAY FROM THE HUMIDIFIER, SHALL DISBALE THE HUMIDIFIER AND GIVE AN ALARM SIGNAL TO THE ECC, IF THE SUPPLY AIR HUMIDITY EXCEEDS 85% RH (ADJUSTABLE). THE AIRFLOW SWITCH SHALL PROVE AIRFLOW BEFORE HUMIDITY CONTROLS ARE ACTIVATED. NORMALLY CLOSED HUMIDIFIER STEAM SUPPLY VALVES SHALL OPEN WHEN OUTSIDE AIR TEMPERATURE DROPS BELOW 60°F AND SHALL CLOSE ABOVE 62°F OUTSIDE AIR TEMPERATURE OR WHEN SUPPLY FAN IS OFF. TEMPERATURE SWITCH SHALL KEEP HUMIDIFIER VALVE CLOSED UNTIL
CONDENSATE DRIP LEG REACHES OPERATING TEMPERATURE.
5. STATIC PRESSURE AND AIRFLOW CONTROL
5.1. THE SUPPLY AIR FAN FLOW SHALL BE CONTROLLED BY THE DIGITAL CONTROL PANEL MODULATING FAN'S INDIVIDUAL ADJUSTABLE SPEED MOTOR CONTROLLER TO MAINTAIN 1.0" OF DUCT STATIC PRESSURE (FIELD ADJUSTABLE), AS SENSED BY THE DUCT STATIC PRESSURE SENSOR LOCATED AT 3
DISTANCE DOWN LONGEST DUCT MAIN. RESET STATIC PRESSURE BASED ON ACTUAL BUILDING LOAD
BY POLLING ALL VAV TERMINAL UNITS.
5.2. FILTER STATUS SHALL BE MONITORED AT EACH PRE-FILTER AND AFTER-FILTER BANK.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
RETURN
FAN
HTG
COIL
CLG
COIL
SUPPLY
FAN
DPS-1 DPS-2
AIR
PRE-
FILTER
AIR
FILTER
VFD
VFD
TTTTT
F T
V-1B
NC-SR
NC-SR
M.P. STEAM
FROM CENTRAL
PLANT
OUTSIDE AIR FLOWMETER (F-1)
RETURN AIR DISCHARGE FLOWMETER (F-2)
HEATING COIL STEAM CONTROL VALVE (V-1B)
HEATING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-4)
LOCAL DDC CONTROLLER
AI2
AI9
AI8
AI1
AI4
AI5
AI6
AI7
RETURN AIR TEMPERATURE SENSOR (T/H-1)
AI3
RETURN AIR HUMIDITY SENSOR (T/H-1)
RETURN AIR STATIC PRESSURE SENSOR (SPS-1)
MIXED AIR TEMPERATURE SENSOR (T-2)
HEATING COIL STEAM CONTROL VALVE (V-1A)
RETURN AIR DAMPER (D-3) STATUS
DI1
AIR PRE-FILTER STATUS (DPS-1)
AIR FILTER STATUS (DPS-2)
EXHAUST AIR DAMPER (D-1) STATUS
DI2 OUTSIDE AIR DAMPER (D-2) STATUS
DI3
DI4
DI5
DO1
AO1
AO2
AO3 HEATING COIL STEAM CONTROL VALVE (V-1B)
RETURN FAN VFD SPEED
HEATING COIL STEAM CONTROL VALVE (V-1A)
EXHAUST AIR DAMPER (D-1)
DO2 OUTSIDE AIR DAMPER (D-2)
HUMIDIFIER ON/OFF STEAM CONTROL VALVE (V-3) STATUS
DI6
SUPPLY DISCHARGE AIR HIGH LIMIT TEMPERATURE SENSOR (T-6) STATUS
RETURN AIR SMOKE DETECTOR (SD-1) STATUS
DI7
DI8
DI9
DI10
DI12
HEATING COIL DISCHARGE AIR LOW LIMIT TEMPERATURE SENSOR (T-3) STATUS
AO4
AO5 HUMIDIFIER STEAM CONTROL VALVE (V-4)
CHILLED WATER CONTROL VALVE (V-2)
DO3 RETURN AIR DAMPER (D-3)
SUPPLY FAN STATUS
SUPPLY DISCHARGE AIR STATIC PRESSURE SENSOR (SPS-2)
SUPPLY DISCHARGE AIR TEMPERATURE SENSOR (T/H-2)
AI16
AI15
AI11
AI12
AI13
AI14
COOLING COIL CHILLED WATER FLOWMETER
AI10
CHILLED WATER CONTROL VALVE (V-2)
COOLING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-5)
HUMIDIFIER STEAM CONTROL VALVE (V-4)
SUPPLY FAN VFD STATUS
SUPPLY DISCHARGE AIR FLOWMETER (F-4)AI20
AI19
AI17
AI18
SUPPLY DISCHARGE AIR HUMIDITY SENSOR (T/H-2)
DI11
SUPPLY DISCHARGE AIR SMOKE DETECTOR (SD-2)
DO4 RETURN FAN START/STOP
SUPPLY DISCHARGE AIR HIGH LIMIT STATIC PRESSURE SENSOR (SPS-3) STATUS
DI13
DO5 HUMIDIFIER ON/OFF STEAM CONTROL VALVE (V-3)
DI14
DO6 SUPPLY FAN START/STOP
AO6 SUPPLY FAN VFD SPEED
RETURN FAN STATUS
SUPPLY AIR HIGH LIMIT STATIC PRESSURE SENSOR (SPS-4) STATUSDI15
RETURN AIR HIGH LIMIT TEMPERATURE SENSOR (T-1) STATUS
RETURN AIR INTAKE FLOWMETER (F-3)
RETURN FAN VFD STATUS
6. FREEZE PROTECTION
6.1. IF THE AIR TEMPERATURE AS SENSED BY PREHEATED MIXED AIR SENSOR (FREEZESTAT) UPSTREAM OF COOLING COIL FALLS BELOW 45°F, AN ALARM SIGNAL SHALL INDICATE AT THE DIGITAL CONTROL PANEL AND ECC. IF THIS TEMPERATURE FALLS BELOW 40°F, AS SENSED BY THE LOW TEMPERATURE SWITCH, THE SUPPLY FAN SHALL SHUT DOWN AND A CRITICAL ALARM SHALL INDICATE AT THE DIGITAL CONTROL PANEL AND ECC. THE LOW TEMPERATURE SWITCH SHALL BE HARDWIRED TO THE SUPPLY FAN VFD, AND THE UNIT SHALL BE SHUTDOWN IN HAND, AUTO, OR BYPASS MODE WHENEVER THERE IS A LOW
TEMPERATURE ALARM. THE LOW TEMPERATURE SWITCH SHALL REQUIRE MANUAL RESET AT THE
DEVICE.
7. HIGH DUCT STATIC PROTECTION
7.1. A DUCT HIGH PRESSURE SENSOR LOCATED AT THE SUPPLY FAN DISCHARGE SHALL PREVENT THE SUPPLY FAN FROM DEVELOPING OVER 3" OF STATIC PRESSURE (FIELD ADJUSTABLE) IN THE SUPPLY DUCT. IF STATIC PRESSURE DOES EXCEED SET LIMIT, THE SUPPLY FAN SHALL STOP. DUCT HIGH
PRESSURE SENSOR SHALL BE HARDWIRED TO THE SUPPLY FAN VFD AND THE UNIT SHALL BE
SHUTDOWN IN HAND, AUTO OR BYPASS MODE WHENEVER THERE IS A HIGH DUCT PRESSURE ALARM.
THE DUCT HIGH STATIC PRESSURE SENSOR SHALL REQUIRE MANUAL RESET AT DEVICE.
8. SMOKE PROTECTION AND AUTOMATIC SHUTDOWN/RESTART
8.1. A SUPPLY AIR SMOKE DETECTOR IN THE SUPPLY AIR DUCT SHALL STOP THE UNIT AND TRANSMIT A SIGNAL TO FIRE ALARM SYSTEM UPON DETECTION OF PRODUCTS OF COMBUSTION IN THE DUCT AND
CLOSE THE UNIT ISOLATION SMOKE DAMPERS LOCATED IN SUPPLY AND RETURN DUCT MAINS
ADJACENT TO THE UNIT. RE: ELECTRICAL FOR ADDITIONAL REQUIREMENTS. EXHAUST FANS SERVING THE AREA OF THE SUPPLY FAN SHALL CONTINUE TO RUN. THE SUPPLY FAN SHALL RESTART AND
SMOKE DAMPERS SHALL OPEN WHEN FIRE ALARM IS RESET.
8.2. FIRESTATS SHALL BE PROVIDED FOR ANY FAN HANDLING 600CFM OR MORE. FIRESTATS SHALL STOP
ASSOCIATED FAN ON A RISE IN AIR TEMPERATURE ABOVE 125°F.
9. EMERGENCY CONSTANT SPEED OPERATION
9.1. UPON FAILURE OF VFD, THE SUPPLY FAN SHALL BE STARTED/STOPPED MANUALLY AT THE DDC OR THE
ECC THROUGH THE BYPASS STARTER. FANS SHALL THEN BE OPERATED AT CONSTANT SPEED.
AHU 7-AC102 CONTROL SCHEMATIC
& SEQUENCE
7 EXPANSION WLP NMT
M7-402
NOTES;
1. THESE DRAWINGS ARE REPRESENTATIVE OF THE DESIGN DRAWINGS FOR THE BUILDING 7
EXPANSION CURRENTLY ON GOING AND ARE FOR REFERENCE ONLY.
2. ALL EQUIPMENT IN THIS PROJECT WILL BE CONTROLLED BY THE CAMPUS SIEMENS SYSTEM.
AI15
VFD
DO4
AO5
DI9
AI14DI2
D02DO1
DI1
PANEL
DDC CONTROL
OUTSIDE AIR
D-1
D-2
AO3
T-4
DPS-1
SD-1
DI10
SD-2
SPS-1
T-1
DPS-2
FLOWMETER
AI1
F-1 T-3
T-5
10' MIN. BETWEEN
HUMIDIFIER AND
ELEMENT
V-4NC
AI13
AO4
SPS-3
DI12
T/H-2
AI2
DI3 DI4
AI5
DI7
T-2
AI9
AI10
AI11
AI12
DI8
DO3
DI11
AI16
AI17
DI13
T/H-1
NC
NO
AI18DI5 AI8
AI6
AO1
AI7
AO2
AI3
AI4 DI6
T-7T
AI19
F-2
SEQUENCE OF OPERATION
1. START/STOP CONTROL
1.1. 7E-AHU-7-AC103 IS NORMALLY STARTED AND STOPPED REMOTELY AT THE ECC. H-O-A SWITCH SHALL BE KEPT IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR
MAINTENANCE. WHEN FAN RUN STATUS IS PROVEN VIA A CURRENT SENSING RELAY, CONTROL
LOOPS SHALL BE ENERGIZED. STOPPING THE UNIT SHALL DE-ENERGIZE THE CONTROL LOOPS AND ALL VALVES SHALL GO TO THE CLOSED POSITION, THE OUTSIDE AIR DAMPER SHALL CLOSE, AND THE RETURN AIR DAMPER SHALL OPEN. OUTSIDE AIR SHALL BE METERED TO MONITOR AND MAINTAIN CONSTANT MIN. O.A. AIRFLOW BY MODULATING THE RETURN AND OUTSIDE AIR CONTROL DAMPERS.
2. TEMPERATURE CONTROL
2.1. A TEMPERATURE SENSOR IN THE UNIT SUPPLY AIR SHALL TRANSMIT TEMPERATURE CHANGES TO THE ASC. THE ASC SHALL MODULATE THE 2-WAY COOLING COIL VALVE TO MAINTAIN SUPPLY AIR SETPOINT AT 55°F (ADJUSTABLE). A TEMPERATURE SENSOR IN THE PREHEAT COIL DISCHARGE
SHALL TRANSMIT TEMPERATURE CHANGES TO THE ASC. THE ASC SHALL MODULATE THE 2-WAY
STEAM VALVE PREHEAT COIL VALVE TO MAINTAIN PREHEAT SETPOINT (ADJUSTABLE).
3. DEHUMIDIFICATION CONTROL
3.1. HUMIDITY SENSOR, (1% ACCURACY), SHALL MEASURE RETURN AIR HUMIDITY AT THE AHU. THE BAS
SHALL AVERAGE THE POSITION OF THE VAV BOX AIR VALVES AND SHALL ADJUST THE AIR
TEMPERATURE UPWARD OR DOWNWARD TO MAXIMIZE THE SUPPLY AIR TEMPERATURE THAT SHALL
ALLOW FOR THE MOST EFFICIENT (HIGHEST) SUPPLY AIR TEMPERATURE TO SATISFY VAV BOX
OPERATION DURING THE OCCUPIED PERIOD OF OPERATION. IF THE RETURN AIR HUMIDITY RISES TO 60% (NOMINAL, ADJUSTABLE), THE SUPPLY AIR TEMPERATURE OF THE AHU SHALL BE LIMITED (LOWERED) SO AS TO KEEP THE RETURN AIR HUMIDITY AT OR BELOW 60% (ADJUSTABLE). ALSO, SYSTEM SHALL UTILIZE CALCULATED R.A. DEWPOINT TEMPERATURE TO COMPARE WITH A MAX.
DEWPOINT SETPOINT OF 55°F (ADJUSTABLE). IN ADDITION TO HUMIDITY, TO OVERRIDE CHW VALVE
FOR DEHUMIDIFICATION.
4. HUMIDIFICATION CONTROL
4.1. RETURN AIR HUMIDITY SHALL BE MONITORED. HUMIDIFIER STEAM VALVE SHALL MODULATE TO SUPPLY STEAM TO AHU MOUNTED DIRECT-INJECTION STEAM MANIFOLD REQUIRED TO MAINTAIN THE RETURN AIR RELATIVE HUMIDITY SETPOINT OF 30% (ADJUSTABLE AT ECC) AS SENSED BY THE
RETURN RELATIVE HUMIDITY SENSOR. PRIOR TO ACTIVATION OF MODULATING STEAM CONTROL
VALVE, THE ON/OFF CONTROL VALVE SHALL BE ENABLED THROUGH ECC AND JACKET
TEMPERATURE SENSED BY HIGH TEMPERATURE SENSOR SHALL BE WARM ENOUGH TO PREVENT
CONDENSATION. THE HIGH LIMIT HUMIDITY SENSOR, LOCATED IN THE SUPPLY AIR DUCT 10' AWAY FROM THE HUMIDIFIER, SHALL DISBALE THE HUMIDIFIER AND GIVE AN ALARM SIGNAL TO THE ECC, IF THE SUPPLY AIR HUMIDITY EXCEEDS 85% RH (ADJUSTABLE). THE AIRFLOW SWITCH SHALL PROVE
AIRFLOW BEFORE HUMIDITY CONTROLS ARE ACTIVATED. NORMALLY CLOSED HUMIDIFIER STEAM
SUPPLY VALVES SHALL OPEN WHEN OUTSIDE AIR TEMPERATURE DROPS BELOW 60°F AND SHALL
CLOSE ABOVE 62°F OUTSIDE AIR TEMPERATURE OR WHEN SUPPLY FAN IS OFF. TEMPERATURE
SWITCH SHALL KEEP HUMIDIFIER VALVE CLOSED UNTIL CONDENSATE DRIP LEG REACHES
OPERATING TEMPERATURE.
AMBIENT AIR TEMPERATURE
SENSOR INSTALLED ON
NORTH SIDE OF BUILDING
AIR
FILTER
AIR
PRE-
FILTER
T
T T T T
HTG
COIL
CLG
COIL HUMIDIFIER T-6
SUPPLY AIRSPS-4
F-3
SUPPLY
FAN
V-3
L P
S
CLEAN STEAM
GENERATOR
L P
C L E
A N
S T
E A
M
V-2
NC-SR
C W
R
F
TS
C R
V-1A
V-1B
NC-SR
NC-SR
M.P. STEAM
FROM CENTRAL
PLANT
RETURN AIR
T
OUTSIDE AIR FLOWMETER (F-1)
RETURN AIR FLOWMETER (F-2)
HEATING COIL STEAM CONTROL VALVE (V-1B)
HEATING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-4)
LOCAL DDC CONTROLLER
AI2
AI9
AI8
AI1
AI4
AI5
AI6
AI7
RETURN AIR TEMPERATURE SENSOR (T/H-1)AI3
RETURN AIR HUMIDITY SENSOR (T/H-1)
RETURN AIR STATIC PRESSURE SENSOR (SPS-1)
MIXED AIR TEMPERATURE SENSOR (T-2)
HEATING COIL STEAM CONTROL VALVE (V-1A)
RETURN AIR DAMPER (D-2) STATUS
DI1
AIR PRE-FILTER STATUS (DPS-1)
AIR FILTER STATUS (DPS-2)
DI2
OUTSIDE AIR DAMPER (D-1) STATUS
DI3
DI4
DI5
DO1
AO1
AO2
AO3
HEATING COIL STEAM CONTROL VALVE (V-1B)
HEATING COIL STEAM CONTROL VALVE (V-1A)
DO2
OUTSIDE AIR DAMPER (D-1)
HUMIDIFIER ON/OFF STEAM CONTROL VALVE (V-3) STATUS
DI6
SUPPLY DISCHARGE AIR HIGH LIMIT TEMPERATURE SENSOR (T-6) STATUS
RETURN AIR SMOKE DETECTOR (SD-1) STATUS
DI7
DI8
DI9
DI10
DI12
HEATING COIL DISCHARGE AIR LOW LIMIT TEMPERATURE SENSOR (T-3) STATUS
AO4
AO5
HUMIDIFIER STEAM CONTROL VALVE (V-4)
CHILLED WATER CONTROL VALVE (V-2)
DO3
RETURN AIR DAMPER (D-2)
SUPPLY FAN STATUS
SUPPLY DISCHARGE AIR STATIC PRESSURE SENSOR (SPS-2)
SUPPLY DISCHARGE AIR TEMPERATURE SENSOR (T/H-2)AI16
AI15
AI11
AI12
AI13
AI14
COOLING COIL CHILLED WATER FLOWMETERAI10
CHILLED WATER CONTROL VALVE (V-2)
COOLING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-5)
HUMIDIFIER STEAM CONTROL VALVE (V-4)
SUPPLY FAN VFD STATUS
SUPPLY DISCHARGE AIR FLOWMETER (F-3)
AI19
AI17
AI18
SUPPLY DISCHARGE AIR HUMIDITY SENSOR (T/H-2)
DI11
SUPPLY DISCHARGE AIR SMOKE DETECTOR (SD-2)
DO4
SUPPLY DISCHARGE AIR HIGH LIMIT STATIC PRESSURE SENSOR (SPS-3) STATUS
DI13
HUMIDIFIER ON/OFF STEAM CONTROL VALVE (V-3)
SUPPLY FAN START/STOP
SUPPLY FAN VFD SPEED
SUPPLY AIR HIGH LIMIT STATIC PRESSURE SENSOR (SPS-4) STATUS
RETURN AIR HIGH LIMIT TEMPERATURE SENSOR (T-1) STATUS
AMBIENT AIR TEMPERATURE SENSOR (T-7)
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
5. STATIC PRESSURE AND AIRFLOW CONTROL
5.1. THE SUPPLY AIR FAN FLOW SHALL BE CONTROLLED BY THE DIGITAL CONTROL PANEL MODULATING FAN'S INDIVIDUAL ADJUSTABLE SPEED MOTOR CONTROLLER TO MAINTAIN 1.0" OF DUCT STATIC PRESSURE (FIELD ADJUSTABLE), AS SENSED BY THE DUCT STATIC PRESSURE SENSOR LOCATED AT
4 DISTANCE DOWN LONGEST DUCT MAIN. RESET STATIC PRESSURE BASED ON ACTUAL BUILDING
LOAD BY POLLING ALL VAV TERMINAL UNITS.
5.2. FILTER STATUS SHALL BE MONITORED AT EACH PRE-FILTER AND AFTER-FILTER BANK.
6. FREEZE PROTECTION
6.1. IF THE AIR TEMPERATURE AS SENSED BY PREHEATED MIXED AIR SENSOR (FREEZESTAT) UPSTREAM OF COOLING COIL FALLS BELOW 45°F, AN ALARM SIGNAL SHALL INDICATE AT THE DIGITAL CONTROL PANEL AND ECC. IF THIS TEMPERATURE FALLS BELOW 40°F, AS SENSED BY THE LOW TEMPERATURE SWITCH, THE SUPPLY FAN SHALL SHUT DOWN AND A CRITICAL ALARM SHALL INDICATE AT THE DIGITAL CONTROL PANEL AND ECC. THE LOW TEMPERATURE SWITCH SHALL BE HARDWIRED TO THE
SUPPLY FAN VFD, AND THE UNIT SHALL BE SHUTDOWN IN HAND, AUTO, OR BYPASS MODE
WHENEVER THERE IS A LOW TEMPERATURE ALARM. THE LOW TEMPERATURE SWITCH SHALL
REQUIRE MANUAL RESET AT THE DEVICE.
7. HIGH DUCT STATIC PROTECTION
7.1. A DUCT HIGH PRESSURE SENSOR LOCATED AT THE SUPPLY FAN DISCHARGE SHALL PREVENT THE SUPPLY FAN FROM DEVELOPING OVER 3" OF STATIC PRESSURE (FIELD ADJUSTABLE) IN THE SUPPLY DUCT. IF STATIC PRESSURE DOES EXCEED SET LIMIT, THE SUPPLY FAN SHALL STOP. DUCT HIGH
PRESSURE SENSOR SHALL BE HARDWIRED TO THE SUPPLY FAN VFD AND THE UNIT SHALL BE
SHUTDOWN IN HAND, AUTO OR BYPASS MODE WHENEVER THERE IS A HIGH DUCT PRESSURE ALARM.
THE DUCT HIGH STATIC PRESSURE SENSOR SHALL REQUIRE MANUAL RESET AT DEVICE.
8. SMOKE PROTECTION AND AUTOMATIC SHUTDOWN/RESTART
8.1. A SUPPLY AIR SMOKE DETECTOR IN THE SUPPLY AIR DUCT SHALL STOP THE UNIT AND TRANSMIT A
SIGNAL TO FIRE ALARM SYSTEM UPON DETECTION OF PRODUCTS OF COMBUSTION IN THE DUCT
AND CLOSE THE UNIT ISOLATION SMOKE DAMPERS LOCATED IN SUPPLY AND RETURN DUCT MAINS ADJACENT TO THE UNIT. RE: ELECTRICAL FOR ADDITIONAL REQUIREMENTS. EXHAUST FANS SERVING THE AREA OF THE SUPPLY FAN SHALL CONTINUE TO RUN. THE SUPPLY FAN SHALL RESTART AND
SMOKE DAMPERS SHALL OPEN WHEN FIRE ALARM IS RESET.
8.2. FIRESTATS SHALL BE PROVIDED FOR ANY FAN HANDLING 600CFM OR MORE. FIRESTATS SHALL STOP
ASSOCIATED FAN ON A RISE IN AIR TEMPERATURE ABOVE 125°F.
9. EMERGENCY CONSTANT SPEED OPERATION
9.1. UPON FAILURE OF VFD, THE SUPPLY FAN SHALL BE STARTED/STOPPED MANUALLY AT THE DDC OR
THE ECC THROUGH THE BYPASS STARTER. FANS SHALL THEN BE OPERATED AT CONSTANT SPEED.
AHU 7-AC103 CONTROL SCHEMATIC
& SEQUENCE
7 EXPANSION WLP NMT
M7-403
NOTES;
1. THESE DRAWINGS ARE REPRESENTATIVE OF THE DESIGN DRAWINGS FOR THE BUILDING 7
EXPANSION CURRENTLY ON GOING AND ARE FOR REFERENCE ONLY.
2. ALL EQUIPMENT IN THIS PROJECT WILL BE CONTROLLED BY THE CAMPUS SIEMENS SYSTEM.
SPS-1
AI10
VFD
DO2
AO3
DI5
AI9
DO1
DI1
PANEL
DDC CONTROL
OUTSIDE AIR
D-1
V-2
AO2
T-4
DPS-1
DI6
SD-1
NC-SR
FLOWMETER
T-5
DI2
C W
R
AI5
AI6
AI7
AI8
SUPPLY AIR
F-1
T/H-1
NC
AI14
AO1
AI4
AI2
AI3
T-2
DI3
H W
R
V-1
T-3
DI4
PREHEAT
COIL
T-6
AI11
T-7
AI13
T/H-2T-8T
AI15
T
T-1
AI1
AO4
AI12
H W
R
V-3
HTG
COIL
SEQUENCE OF OPERATION
1. START/STOP CONTROL
1.1. 7E-AHU-7-4 IS NORMALLY STARTED AND STOPPED REMOTELY AT THE ECC. H-O-A SWITCH SHALL BE
KEPT IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR
MAINTENANCE. WHEN FAN RUN STATUS IS PROVEN VIA A CURRENT SENSING RELAY, CONTROL
LOOPS SHALL BE ENERGIZED. STOPPING THE UNIT SHALL DE-ENERGIZE THE CONTROL LOOPS, ALL
VALVES SHALL GO TO THE CLOSED POSITION, AND THE OUTSIDE AIR DAMPER SHALL CLOSE.
2. SAFETIES
2.1. AN INTELLIGENT DUCT SMOKE DETECTOR IN THE PURE SUPPLY AIR (RE: ELECTRICAL) SHALL STOP
THE UNIT UPON DETECTION OF PRODUCTS OF COMBUSTION.
2.2. ELECTRIC LOW LIMIT THERMOSTAT IN THE MIXED AIR SHALL STOP THE UNIT UPON DETECTION OF
TEMPERATURE BELOW ITS SETPOINT.
2.3. FIRESTATS SHALL BE PROVIDED FOR ANY FAN HANDLING 600 CFM OR MORE. FIRESTATS SHALL STOP
ASSOCIATED FAN ON A RISE IN AIR TEMPERATURE ABOVE 125°F.
3. TEMPERATURE CONTROL
3.1. SPACE TEMPERATURE SENSOR LOCATED AS SHOWN THE PLANS SHALL TRANSMIT TEMPERATURE
CHANGES TO THE DDC. THE DDC SHALL MODULATE THE 2-WAY CHILLED WATER AND 3-WAY HOT
WATER PREHEAT VALVE IN SEQUENCE TO MAINTAIN SPACE TEMPERATURE SETPOINT.
4. HUMIDIFICATION CONTROL
4.1. PROVIDE SPACE HUMIDISTAT THAT SHALL OVERRIDE THE THERMOSTAT AND CONTROL THE
COOLING VALVE TO MAINTAIN 55°F LEAVING AIR. THE THERMOSTAT SHALL CONTROL SPACE
TEMPERATURE AT SETPOINT THROUGH THE MODULATION OF THE REHEAT POSITIONED HEATING
HOT WATER COIL VALVE.
5. FILTER STATUS
5.1. FILTER STATUS SHALL BE MONITORED AT EACH PRE-FILTER AND AFTER-FILTER BANK.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
ZONE AIR
TEMPERATURE
SENSOR
ZONE AIR
TEMPERATURE/
HUMIDITY
SENSOR
AI17
AI16
T/H
RETURN AIR
SUPPLY
FAN
CLG
COIL
AIR
FILTER
T T T T T
F T
COOLING COIL CHILLED WATER FLOWMETER
CHILLED WATER CONTROL VALVE (V-2)
LOCAL DDC CONTROLLER
AI2
AI9
AI8
AI1
AI4
AI5
AI6
AI7
MIXED AIR TEMPERATURE SENSOR (T-1)
AI3
RETURN AIR TEMPERATURE SENSOR (T/H-1)
RETURN AIR HUMIDITY SENSOR (T/H-1)
PREHEAT COIL HOT WATER CONTROL VALVE (V-1)
PREHEAT COIL DISCHARGE AIR TEMPERATURE SENSOR (T-4)
DI1
AIR FILTER STATUS (DPS-1)DI2
OUTSIDE AIR DAMPER (D-1) STATUS
DI3
DI4
DI5
DO1
AO1
AO2
AO3
HEATING COIL STEAM CONTROL VALVE (V-1B)
HEATING COIL STEAM CONTROL VALVE (V-1A)
DO2
OUTSIDE AIR DAMPER (D-1)
DI6
AO4
CHILLED WATER CONTROL VALVE (V-2)
SUPPLY FAN STATUS
REHEAT COIL DISCHARGE AIR TEMPERATURE SENSOR (T-7)
SUPPLY AIR FLOWMETER
AI16
AI15
AI11
AI12
AI13
AI14
COOLING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-5)
AI10
SUPPLY FAN VFD STATUS
SUPPLY DISCHARGE AIR STATIC PRESSURE SENSOR (SPS-1)
SUPPLY DISCHARGE AIR TEMPERATURE SENSOR (T-6)
REHEAT COIL HOT WATER CONTROL VALVE (V-3)
AI17
ZONE AIR TEMPERATURE SENSOR (T-8)
SUPPLY DISCHARGE AIR SMOKE DETECTOR (SD-1)
SUPPLY FAN START/STOP
SUPPLY FAN VFD SPEED
MIXED AIR LOW LIMIT TEMPERATURE SENSOR (T-1) STATUS
ZONE AIR HUMIDITY SENSOR (T/H-2)
ZONE AIR TEMPERATURE SENSOR (T/H-2)
T
PREHEAT COIL DISCHARGE AIR LOW LIMIT TEMPERATURE SENSOR (T-1) STATUS
AHU 7-4 CONTROL SCHEMATIC
& SEQUENCE
7 EXPANSION WLP NMT
M7-404
NOTES;
1. THESE DRAWINGS ARE REPRESENTATIVE OF THE DESIGN DRAWINGS FOR THE BUILDING 7
EXPANSION CURRENTLY ON GOING AND ARE FOR REFERENCE ONLY.
2. ALL EQUIPMENT IN THIS PROJECT WILL BE CONTROLLED BY THE CAMPUS SIEMENS SYSTEM.
SEQUENCE OF OPERATION
1. START/STOP CONTROL
1.1. 7E-AHU-7-4 IS NORMALLY STARTED AND STOPPED REMOTELY AT THE ECC. H-O-A SWITCH SHALL BE
KEPT IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR
MAINTENANCE. WHEN FAN RUN STATUS IS PROVEN VIA A CURRENT SENSING RELAY, THE CONTROL LOOPS SHALL BE ENERGIZED. STOPPING THE UNIT SHALL DE-ENERGIZE THE CONTROL LOOPS AND ALL VALVES SHALL GO TO THE CLOSED POSITION, THE OUTSIDE AIR DAMPER SHALL CLOSE. SUPPLY
AIR SHALL BE METERED TO MONITOR AIRFLOW.
2. SAFETIES
2.1. AN INTELLIGENT DUCT SMOKE DETECTOR IN THE PURE SUPPLY AIR (RE: ELECTRICAL) SHALL STOP
THE UNIT UPON DETECTION OF PRODUCTS OF COMBUSTION.
2.2. ELECTRIC LOW LIMIT THERMOSTAT IN THE MIXED AIR SHALL STOP THE UNIT UPON DETECTION OF
TEMPERATURE BELOW ITS SETPOINT.
2.3. FIRESTATS SHALL BE PROVIDED FOR ANY FAN HANDLING 600 CFM OR MORE. FIRESTATS SHALL STOP
ASSOCIATED FAN ON A RISE IN AIR TEMPERATURE ABOVE 125°F.
3. TEMPERATURE CONTROL
3.1. SPACE TEMPERATURE SENSOR LOCATED AS SHOWN THE PLANS SHALL TRANSMIT TEMPERATURE
CHANGES TO THE DDC. THE DDC SHALL MODULATE THE 2-WAY CHILLED WATER AND 3-WAY HOT
WATER PREHEAT VALVE IN SEQUENCE TO MAINTAIN SPACE TEMPERATURE SETPOINT.
4. HUMIDIFICATION CONTROL
4.1. PROVIDE SPACE HUMIDISTAT THAT SHALL OVERRIDE THE THERMOSTAT AND CONTROL THE
COOLING VALVE TO MAINTAIN 55°F LEAVING AIR. THE THERMOSTAT SHALL CONTROL SPACE
TEMPERATURE AT SETPOINT THROUGH THE MODULATION OF THE REHEAT POSITIONED HEATING
HOT WATER COIL VALVE.
5. FILTER STATUS
5.1. FILTER STATUS SHALL BE MONITORED AT EACH PRE-FILTER AND AFTER-FILTER BANK.
SPS-1
AI10
VFD
DO2
AO3
DI5
AI9
DO1
DI1
PANEL
DDC CONTROL
OUTSIDE AIR
D-1
V-2
AO2
T-4
DPS-1
DI6
SD-1
NC-SR
FLOWMETER
T-5
DI2
C
W R
AI5
AI6
AI7
AI8
SUPPLY AIR
F-1
T/H-1
NC
AI14
AO1
AI4
AI2
AI3
T-2
DI3
H W
R
V-1
T-3
DI4
PREHEAT
COIL
T-6
AI11
T-7
AI13
T/H-2T-8T
AI15
T
T-1
AI1
AO4
AI12
H W
R
V-3
HTG
COIL
ZONE AIR
TEMPERATURE
SENSOR
ZONE AIR
TEMPERATURE/
HUMIDITY
SENSOR
AI17
AI16
T/H
RETURN AIR
SUPPLY
FAN
CLG
COIL
AIR
FILTER
T T T T T
F T
T
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
COOLING COIL CHILLED WATER FLOWMETER
CHILLED WATER CONTROL VALVE (V-2)
LOCAL DDC CONTROLLER
AI2
AI9
AI8
AI1
AI4
AI5
AI6
AI7
MIXED AIR TEMPERATURE SENSOR (T-1)
AI3
RETURN AIR TEMPERATURE SENSOR (T/H-1)
RETURN AIR HUMIDITY SENSOR (T/H-1)
PREHEAT COIL HOT WATER CONTROL VALVE (V-1)
PREHEAT COIL DISCHARGE AIR TEMPERATURE SENSOR (T-4)
DI1
AIR FILTER STATUS (DPS-1)DI2
OUTSIDE AIR DAMPER (D-1) STATUS
DI3
DI4
DI5
DO1
AO1
AO2
AO3
HEATING COIL STEAM CONTROL VALVE (V-1B)
HEATING COIL STEAM CONTROL VALVE (V-1A)
DO2
OUTSIDE AIR DAMPER (D-1)
DI6
AO4
CHILLED WATER CONTROL VALVE (V-2)
SUPPLY FAN STATUS
REHEAT COIL DISCHARGE AIR TEMPERATURE SENSOR (T-7)
SUPPLY AIR FLOWMETER
AI16
AI15
AI11
AI12
AI13
AI14
COOLING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-5)
AI10
SUPPLY FAN VFD STATUS
SUPPLY DISCHARGE AIR STATIC PRESSURE SENSOR (SPS-1)
SUPPLY DISCHARGE AIR TEMPERATURE SENSOR (T-6)
REHEAT COIL HOT WATER CONTROL VALVE (V-3)
AI17
ZONE AIR TEMPERATURE SENSOR (T-8)
SUPPLY DISCHARGE AIR SMOKE DETECTOR (SD-1)
SUPPLY FAN START/STOP
SUPPLY FAN VFD SPEED
MIXED AIR LOW LIMIT TEMPERATURE SENSOR (T-1) STATUS
ZONE AIR HUMIDITY SENSOR (T/H-2)
ZONE AIR TEMPERATURE SENSOR (T/H-2)
PREHEAT COIL DISCHARGE AIR LOW LIMIT TEMPERATURE SENSOR (T-1) STATUS
AHU 7-5 CONTROL SCHEMATIC
& SEQUENCE
7 EXPANSION WLP NMT
M7-405
NOTES;
1. THESE DRAWINGS ARE REPRESENTATIVE OF THE DESIGN DRAWINGS FOR THE BUILDING 7
EXPANSION CURRENTLY ON GOING AND ARE FOR REFERENCE ONLY.
2. ALL EQUIPMENT IN THIS PROJECT WILL BE CONTROLLED BY THE CAMPUS SIEMENS SYSTEM.
VFD
VFD
CHWP#7-2b
SCHWS
SCHWS
DIFFERENTIAL PRESSURE
SENSOR 3/4 LONGEST RUN.
CHWS (EXISTING)
CHWR (EXISTING)
PRIMARY
CHWS
EXISTING
CW PUMPS
EXISTING
CW PUMPS
NC-NSR
NC-NSR
CHWP#7-1b
CHWS (EXISTING BRANCH #3,
NORTH LOOP)
CHWS (NEW BRANCH #4,
BLDG. 7 ADDITION)
CHWS (EXISTING BRANCH
#2, OLD LOOP)
CHWS (EXISTING
BRANCH #1, SOUTH
LOOP)
FCV-1 (EXISTING)
FCV-2 (EXISTING)
FCV-3 (EXISTING)
FLOW CTRL VALVE (TYP)
CHWR (FROM
EXISTING PUMP
147-P-1)
V-1 (EXISTING)
CHWR (FROM
EXISTING PUMP
147-P-2)
V-2 (EXISTING)
CHWR (FROM
EXISTING PUMP
147-P-3)
V-3 (EXISTING)
NC-NSR
7E-V-1
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE EXISTING CONSTANT VOLUME PRIMARY CHILLED WATER SUPPLY FROM THE CENTRAL PLANT PROVIDES CHILLED WATER TO THE VARIABLE (CONTROLLED BY VFD) SECONDARY PUMPING SYSTEM
LOCATED AT THE BUILDING. THERE ARE 2 SECONDARY CHILLED WATER PUMPS (EACH 100%
REDUNDANT). ONLY 1 PUMP AT A TIME SHALL OPERATE TO COOL BUILDING.
1.2. ALL THE PUMP STARTERS ARE EQUIPPED WITH HOA SWITCHES. THE SWITCHES ARE KEPT IN THE "AUTO" POSITION. HAND AND OFF ARE USED ONLY FOR MAINTENANCE PURPOSES. ALL PUMPS SHALL BE STARTED/STOPPED BY THE FMS. ALL PUMPS SHALL PROPER INTERLOCKS TO RESPECTIVE EQUIPMENT
AS PRE MANUFACTURER'S RECOMMENDATIONS.
1.3. UPON A CALL FOR COOLING FROM ANY AIR HANDLING UNIT, FAN COIL UNIT, OR BLOWER COIL UNIT, 1 LEAD CHILLED WATER PUMP SHALL ENERGIZE AND RESPECTIVE VARIABLE FREQUENCY DRIVE (VFD) SHALL MODULATE THE PUMP TO MAINTAIN PRESSURIZATION (ADJUSTABLE) AT THE DIFFERENTIAL
PRESSURE SENSOR LOCATED 3
4 (MIN.) DOWN THE LONGEST PIPING RUN. THE DIFFERENTIAL PRESSURE
SENSOR AND A FLOW SENSOR IN THE SECONDARY LINE SHALL BE USED TO CONTROL THE SPEED OF THE VFD-DRIVEN SECONDARY BUILDING CHILLED WATER PUMP. THE VFD SHALL RAMP UP OR DOWN AS REQUIRE TO MAINTAIN THIS SYSTEM PRESSURE SETPOINT. DIFFERENTIAL PRESSURE SETPOINT IS THE DIFFERENTIAL PRESSURE REQUIRED TO SATISFY THE BRANCH WITH THE HIGHEST PRESSURE DROP AT
DESIGN FLOW. THE DIFFERENTIAL PRESSURE SENSOR MAINTAINS A CONSTANT DIFFERENTIAL
BETWEEN THE SUPPLY LINE AND THE RETURN LINE TO COMPENSATE FOR SYSTEM LOAD CHANGES.
ALSO, CHILLED WATER DIFFERENTIAL PRESSURE SETPOINT SHALL BE RESET BASED ON WEIGHTED
AVERAGE OF THE CHW VALVE DEMAND FROM AHU'S.
1.4. 2-WAY CONTROL VALVE LOCATED AT HYDRONIC BRIDGE CIRCUIT DOWNSTREAM OF THE SECONDARY CHILLED WATER PUMPS WITH A FLOWMETER, TEMPERATURE SENSOR, AND MANUAL BALANCING VALVE SHALL BE UTILIZED TO BYPASS SECONDARY CHILLED WATER FLOW BACK TO THE PRIMARY LOOP AT MIN. VFD SETPOINT, WHILE COOLING COIL 2-WAY VALVES SHUT OFF AS COOLING LOAD DICTATES.
MANUAL BALANCING VALVE SET AT PRESSURE DROP TO MATCH REMAINDER OF BUILDING PIPING
CIRCUIT AT MIN. FLOW.
1.5. SECONDARY CHILLED WATER FLOWS SHALL BE MEASURED AND TOTALIZED AS MEASURED BY
HIGH-ACCURACY FLOWMETERS AT EACH PUMP DISCHARGE, THE SECONDARY HYDRONIC BRIDGE
BYPASS DOWNSTREAM OF PUMP DISCHARGE, AND THE COMMON SECONDARY CHILLED WATER SUPPLY
DOWNSTREAM OF THE BRIDGE BYPASS.
2. LEAD/STANDBY PUMP CONTROL
2.1. IF THE LEAD BUILDING SECONDARY CHILLED WATER PUMP FAILS, THE STANDBY PUMP SHALL BE AUTOMATICALLY STARTED, AND THE SYSTEM SHALL RESUME NORMAL OPERATION. AN ALARM SHALL
SOUND AND DISPLAY AT THE DDC CONTROL PANEL THAT A PUMP HAS FAILED.
2.2. THE LEAD/STANDBY NATURE OF THE PUMPS SHALL BE ROTATED EVERY WEEK TO ENSURE EVEN RUN
TIME OF THE PUMPS.
SEQUENCE OF OPERATION
1. WATER METERING AND TOTALIZING
1.1. IN LINE ELECTROMAGNETIC FLOWMETER (NO MOVING PARTS, FLANGED 316 STAINLESS STEEL BODY) SHALL BE SUITABLE FOR MEASUREMENT OF ELECTRICALLY CONDUCTIVE LIQUIDS IN A WIDE VARIETY OF APPLICATIONS. THE FLOWMETER SHALL HAVE 0.4% FLOW METERING ACCURACY. COMPONENTS SHALL BE MOUNTED IN NEMA 4X ENCLOSURE. PROVIDE INHERENTLY BI-DIRECTIONAL, STANDARD TRANSMITTER THAT PROVIDES A SINLE ANALOG 4-20mA OUTPUT FOR FLOW RATE AND TWO PROGRAMMABLE PULSE OUTPUTS. OUTPUT OF METER SHALL BE SENT TO A WALL-MOUNTED REMOTE DISPLAY PANEL (COORDINATE LOCATION WITH VA AND ENGINEER) FOR TOTALIZATION AND BUILDING ENERGY MANAGEMENT SYSTEM VIA 4-20mA SIGNAL. PROVIDE ALL AC TO DC TRANSFORMERS AS REQUIRED TO POWER METER AND REMOTE DISPLAY PANEL. ALL METER AND REMOTE DISPLAY POWER
AC POWER AC POWER REQUIREMENTS, AND INTERCONNECTING CABLING AND CONDUIT BETWEEN
METER AND REMOTE DISPLAY PANEL TO BE SUPPLIED BY ELECTRICAL.
2. CHILLED WATER METERING AND TOTALIZING
2.1. TYPE POINT DESCRIPTION UNITS TREND ALARM TOTALIZE
AI-1 CHW-F FLOWRATE FT/SEC X X X
AI-1 CHW-TS SUPPLY TEMP °F X X X
AI-1 CHW-TR RETURN TEMP °F X X X
3. PROGRAMS TO BE PROVIDED
3.1. NIGHT SETBACK / MORNING WARM-UP CONTROL
3.2. OPTIMUM START/STOP
3.3. EVENT SCHEDULING
3.4. ALARM REPORTING
3.5. CHILLED WATER PLANT OPERATION AND OPTIMIZATION
3.6. AUTOMATIC RESTART OF EQUIPMENT SEQUENCE AFTER POWER OUTAGE, & UPON RESUMPTION OF
POWER SERVICE
3.7. POWER DEMAND LIMITING
3.8. PREVENTIVE MAINTENANCE INSTRUCTION
3.9. CALCULATING AIRFLOWS, WATERFLOWS, TONNAGE, BTU'S, W, kW, LB/HR, CFM, GPM, CCF, GPH, ETC.
3.10. UTILITY METERING AND TOTALIZATION
3.11. COMPUTER DIAGNOSTIC AND TESTING PROGRAMS
3.12. REMOTE COMMUNICATIONS
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
CHILLER 1
(EXISTING)
DO1
DI1 AI1
CHILLER 2
(EXISTING)
DO2
DI2 AI2
CHILLER 3
(EXISTING)
DO3
DI3 AI3
FS
AI11
AO4
AI7
AO5
AI8
AO6
AI9
AO7
AI10
AO3
AI6
AO2
AI5
AO1
AI4
AI18
AO6
TP FT
AI1 AI2 AI6
F T
AI4
AO1
TAI3
T
AI5
T
AI11
T
AI13
FT
AI9
AI12
AO4
FT
AI16
PAI17
FT
AI10
CHILLER 3 CONTROL VALVE (V-3)
CHWS (BRANCH #4, BLDG. 7 ADD.) CONTROL VALVE (7E-V-1)
LOCAL DDC CONTROLLER
AI2
AI9
AI8
AI1
AI4
AI5
AI6
AI7
CHILLER 1 INTERNAL VFD STATUS
AI3
CHILLER 2 INTERNAL VFD STATUS
CHILLER 3 INTERNAL VFD STATUS
CHILLER 1 CONTROL VALVE (V-1)
CHILLER 2 CONTROL VALVE (V-2)
DI1
CHILLER 2 STATUSDI2
CHILLER 1 STATUS
DO1
AO1
AO2
AO3
DO2
AO4
CHWS (BRANCH #3, NORTH LOOP) CONTROL VALVE (FCV-3)
CHWS (BRANCH #2, OLD LOOP) CONTROL VALVE (FCV-2)
AO5
AO6
CHILLER 1 CONTROL VALVE (V-1)
CHILLER 2 CONTROL VALVE (V-2)
CHILLER 3 CONTROL VALVE (V-3)
CHWS (BRANCH #4, BLDG. 7 ADD.) CONTROL VALVE (7E-V-1)
CHWS (BRANCH #3, NORTH LOOP) CONTROL VALVE (FCV-3)
CHWS (BRANCH #2, OLD LOOP) CONTROL VALVE (FCV-2)
CHILLER 1 START/STOP
CHILLER 2 START/STOP
DO1
DI1
AO2
AI7
DO2
DI2
AO3
AI8
AI14
AO5
AI15
AI10 CHWS (BRANCH #1, SOUTH LOOP) CONTROL VALVE (FCV-1)
AI11 CHWS (BRANCH #4, BLDG. 7 ADD.) FLOWMETER
CHILLER 3 STATUSDI3
AO7 CHWS (BRANCH #1, SOUTH LOOP) CONTROL VALVE (FCV-1)
DO3 CHILLER 3 START/STOP
PRIMARY CHWS FLOWMETER
CHILLED WATER PUMP (CHWP#7-1b) VFD STATUS
LOCAL DDC CONTROLLER
AI2
AI9
AI8
AI1
AI4
AI5
AI6
AI7
PRIMARY CHWS PRESSURE SENSOR
AI3
PRIMARY CHWS TEMPERATURE SENSOR
PRIMARY CHWS BYPASS TEMPERATURE SENSOR
PRIMARY CHWS BYPASS FLOW SWITCH
PRIMARY CHWR TEMPERATURE SENSOR
AI12
SECONDARY CHWS TEMPERATURE SENSORAI13
HYDRONIC BYPASS BRIDGE CONTROL VALVE
AO1
AO2
AO3
AO4
CHILLED WATER PUMP (CHWP#7-2b) VFD STATUS
CHILLED WATER PUMP (CHWP#7-1b) DISCHARGE FLOWMETER
AO5
AO6
CHILLER 1 CONTROL VALVE (V-1)
CHILLED WATER PUMP (CHWP#7-1b) VFD SPEED
CHILLED WATER PUMP (CHWP#7-2b) VFD SPEED
SECONDARY HYDRONIC BRIDGE BYPASS VALVE
SECONDARY CHWS BYPASS LOOP FLOWMETER
SECONDARY CHWS BYPASS VALVE
AI10 CHILLED WATER PUMP (CHWP#7-2b) DISCHARGE FLOWMETER
AI11 SECONDARY CHWR TEMPERATURE SENSOR
HYDRONIC BYPASS BRIDGE FLOWMETERAI14
HYDRONIC BYPASS BRIDGE TEMPERATURE SENSORAI15
SECONDARY CHWS FLOWMETERAI16
PRIMARY
CHWR
F T
T
DIFFERENTIAL PRESSURE SENSORAI17
SECONDARY CHWS BYPASS VALVEAI18
CHILLED WATER PUMP (CHWP#7-1b) STATUSDI1
CHILLED WATER PUMP (CHWP#7-2b) STATUSDI2
DO1
DO2
CHILLED WATER PUMP (CHWP#7-1b) START/STOP
CHILLED WATER PUMP (CHWP#7-2b) START/STOP
PRIMARY & SECONDARY CHILLED
WATER SYSTEMS CONTROL
SCHEMATICS & SEQUENCES
7 EXPANSION WLP NMT
M7-406
NOTES;
1. THESE DRAWINGS ARE REPRESENTATIVE OF THE DESIGN DRAWINGS FOR THE BUILDING 7
EXPANSION CURRENTLY ON GOING AND ARE FOR REFERENCE ONLY.
2. ALL EQUIPMENT IN THIS PROJECT WILL BE CONTROLLED BY THE CAMPUS SIEMENS SYSTEM.
HTG. SET
POINT
CLG. SET
POINT
VALVE OPEN MAX. AIR
VALVE CLOSED
MIN. AIR
SUPPLY AIR
REHEAT COIL
VALVE
ROOM TEMPERATURE
°F (-°C)
°F (+°C)
CONTROL SCHEDULE
COIL
H W
R
V-1
HTG
AI2
AO1
PANEL
DDC CONTROL
T
AI3
T-1
AI4
M
AI1
ROOM SENSOR
T/H-1
T T-1
SEQUENCE OF OPERATION
1. OCCUPIED MODE
1.1. THE STEAM CONTROL VALVE SHALL MODULATE TO MAINTAIN THE LEAVING HOT WATER TEMPERATURE
AT SETPOINT.
1.2. STEAM TO HOT WATER CONVERTERS 7E-HX-1 AND 7E-HX-2 ARE 100% REDUNDANT, REQUIRING ONLY
ONE UNIT TO OPERATE AT FULL LOAD.
1.3. THE LEAVING HOT WATER TEMPERATURE SHALL BE RESET INVERSELY WITH THE OUTDOOR
TEMPERATURE AS SCHEDULED (AT 30 °F O.A., HWS AT 180°F; AT 70°F O.A., HWS AT 140°F). ALSO, LWT
SHALL BE RESET BASED ON HOT WATER RETURN SCHEDULE.
1.4. HOT WATER PUMPS SHALL BE STARTED/STOPPED BY THE FMS. ALL PUMPS SHALL HAVE PROPER INTERLOCKS TO RESPECTIVE EQUIPMENT AS PER EQUIPMENT MANUFACTURER'S RECOMMENDATION.
EACH PUMP IS SIZED FOR 100& OF THE LOAD, I.E. 100% REDUNDANT, REQUIRING ONLY 1 PUMP FOR OPERATION. THE LEAD AND LAG HOT WATER PUMPS AND HEAT EXCHANGERS SHALL BE SEQUENCED BY THE OPERATOR CONTROLS AT THE PRE-DETERMINED INTERVAL (USUALLY 7 DAYS). IN THE EVENT LEAD PUMP FAILS TO START WITHIN 30 SECONDS, AN ALARM SHALL BE INITIATED AND THE LAG PUMP SHALL
START AUTOMATICALLY.
2. VALVE SEQUENCE FOR LEAD HEAT EXCHANGER
2.1. THE 13 CAPACITY STEAM CONTROL VALVE MODULATES FULLY OPEN TO MAINTAIN SETPOINT.
2.2. THE 2 3 CAPACITY STEAM CONTROL VALVE MODULATES FULLY OPEN TO MAINTAIN SETPOINT.
2.3. BOTH THE 13 CAPACITY & 2
3 CAPACITY STEAM CONTROL VALVES MODULATE TOGETHER TO MAINTAIN
SETPOINT.
3. UNOCCUPIED MODE
3.1. WHENEVER OUTSIDE AIR TEMPERATURE IS 40°F (ADJUSTABLE) OR BELOW, THE LOCAL DDC SHALL PLACE THE HOT WATER SYSTEM IN THE OCCUPIED MODE, START PUMPS, AND ACTUATE STEAM VALVES
TO MAINTAIN SETPOINT.
SEQUENCE OF OPERATION
1. OCCUPIED MODE
1.1. A SPACE SENSOR SHALL TRANSMIT ROOM TEMPERATURE AND HUMIDITY TO THE BOX CONTROLLER, WHICH SHALL VERY THE PRIMARY AIRFLOW AND VARY HEATING VALVE TO MAINTAIN SPACE
TEMPERATURE SETPOINTS.
1.2. A RISE IN SPACE TEMPERATURE ABOVE SETPOINT MODULATE PRIMARY AIRFLOW TO MAX. CFM
SETPOINT INTO THE SPACE. A DROP IN SPACE TEMPERATURE SHALL MODULATE THE PRIMARY
AIRFLOW TO MIN. CFM SETPOINT.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it.