36C25618U0323-0002013.pdf
PDF 3 MB Posted
- Attached to
- Services Commissioning for HVAC Digital Controls Federal contract opportunity
- Solicitation number
- 36C25618U0323
About this file
36C25618U0323 0002 Drawings - Building 6 (M6 Series).pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| -15380.docx | DOCX document | |
| 36C25618U0323-0002007.pdf | ||
| 36C25618U0323-0002005.pdf | ||
| 36C25618U0323-0002011.pdf | ||
| 36C25618U0323-0002009.pdf | ||
| 36C25618U0323-0002014.pdf | ||
| 36C25618U0323-0002001.docx | DOCX document | |
| 36C25618U0323-0002003.pdf | ||
| 36C25618U0323-0002008.pdf | ||
| 36C25618U0323-0002004.pdf | ||
| 36C25618U0323-0002006.pdf | ||
| 36C25618U0323-0002012.pdf | ||
| 36C25618U0323-0002000.docx | DOCX document | |
| 36C25618U0323-0002010.pdf | ||
| 36C25618U0323-0002002.pdf | ||
| 36C25618U0323-0001000.docx | DOCX document | |
| 36C25618U0323-001.docx | DOCX document | |
| 36C25618U0323-002.pdf | ||
| 36C25618U0323-000.docx | DOCX document |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXIST
FCU#6-2
EXIST
V6-2-23
EXIST
V6-2-24
EXIST
V6-2-27
EXIST
V6-1-35
EXIST
V6-1-34
EXIST
V6-1-33
EXIST
V6-1-32
EXIST
V6-1-30 EXIST
V6-1-29
EXIST
V6-1-28
EXIST
V6-1-27
EXIST
V6-1-31
EXIST
V6-2-25
EXIST
V6-2-26
EXIST
FCU#6-3
EXIST
FCU#6-1
EXIST BCU#6-1
EXIST
6-CWP-2
EXIST
6-CWP-1
EXIST VFD'S FOR
6-CWP-1 & 6-CWP-2
M
EXIST DDC'S
EXIST EF#6-1
EXIST CP#6-1
EXIST
6-HWP-2
EXIST
6-HWP-1
6-HX-1 & 6-HX-2
NOTES:
1. EXISTING DDC SYSTEM IS JCI. REPLACE CONTROLLERS TO
FULLY INTEGRATE TO CAMPUS SIEMENS SYSTEM.
2. CONNECT NEW DDC CONTROLLERS TO EXISTING ELECTRICAL
SERVICE.
VAV TERMINAL
UNIT (TYP.)
EXIST MAIN ELEC PANEL
FOR HVAC EQUIP.
PROVIDE ELEC METER FOR HVAC PANEL.
CONNECT TO CAMPUS DDC CONTRTOL
SYSTEM. PROVIDE NEW ELECTRICAL
METERS. CONTRACTOR SHALL PROVIDE
120V POWER CONNECTION TO NEW
ELECTRICAL METERS. CONTRACTOR SHALL
ROUTE TO NEAREST 120V PANEL WITH
SPARE CAPACITY, INSTALL NEW 20 A-1
POLE CIRCUIT BREAKER, & MAKE
CONNECTION. PROVIDE 20 A SWAP SWITCH
AT ELECTRICAL METERS FOR DISCONNECT.
CONTRACTOR TO VERIFY 120V PANEL
LOCATION DURING PRE-BID
WALKTHROUGH.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
BASEMENT FLOOR PLAN -
MECHANICAL
6 WLP NMT
M6-100 10-30-13
V6-1-18
EXIST
V6-1-14
EXIST
V6-1-15
EXIST
V6-1-16
EXIST
V6-1-17
EXIST
V6-1-19
EXIST
V6-1-20
EXIST
V6-1-22
EXIST
V6-1-21
EXIST
V6-1-23
EXIST
V6-1-24
EXIST
V6-1-25EXIST
V6-1-26
EXIST
V6-2-22EXIST
V6-2-19
EXIST
V6-2-17
EXIST
V6-2-18
EXIST
V6-2-21
EXIST
V6-2-20
EXIST
V6-2-16
EXIST
V6-2-15
EXIST
V6-2-14
EXIST
V6-2-13
EXIST
V6-2-12
NOTES:
1. EXISTING DDC SYSTEM IS JCI. REPLACE CONTROLLERS TO
FULLY INTEGRATE TO CAMPUS SIEMENS SYSTEM.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
1ST FLOOR PLAN - MECHANICAL
6 WLP NMT
M6-101
V6-1-1
EXIST
V6-1-2
EXIST
V6-1-3
EXIST
V6-1-4
EXIST
V6-1-6EXIST
V6-1-7
EXIST
V6-1-9
EXIST
V6-1-10
EXIST
V6-2-13EXIST
V6-2-11
EXIST
V6-2-10
EXIST
V6-2-9
EXIST
V6-2-6
EXIST
V6-2-8
EXIST
V6-2-7
EXIST
V6-2-4
EXIST
V6-2-2
EXIST
V6-2-1
EXIST
V6-2-3
EXIST
V6-2-5
EXIST
V6-1-12
EXIST
V6-1-11
EXIST
V6-1-8
EXIST
V6-1-5
NOTES:
1. EXISTING DDC SYSTEM IS JCI. REPLACE CONTROLLERS TO
FULLY INTEGRATE TO CAMPUS SIEMENS SYSTEM.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
2ND FLOOR PLAN - MECHANICAL
6 WLP NMT
M6-102
EXIST AHU#6-1 EXIST AHU#6-2
V6-3-9
IN
ATTIC
EXIST
V6-3-8
IN
ATTIC
EXIST
V6-3-7
IN
ATTIC
EXIST
V6-3-6
IN
ATTIC
EXIST
V6-3-5
IN
ATTIC
EXIST
V6-3-4
IN
ATTIC
EXIST
V6-3-10
IN
ATTIC
EXIST
V6-3-3
IN
ATTIC
EXIST
V6-3-2
IN
ATTIC
EXIST
V6-3-1
IN
ATTIC
NOTES:
1. EXISTING DDC SYSTEM IS JCI. REPLACE CONTROLLERS TO
FULLY INTEGRATE TO CAMPUS SIEMENS SYSTEM.
EXIST PTHP#6-4
TO REMAIN ON
STANDALONE
CONTROLS.
EXIST PTHP#6-3
TO REMAIN ON
STANDALONE
CONTROLS.
EXIST PTHP#6-2
TO REMAIN ON
STANDALONE
CONTROLS.
EXIST PTHP#6-1
TO REMAIN ON
STANDALONE
CONTROLS.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
3RD FLOOR PLAN - MECHANICAL
6 WLP NMT
M6-103
V6-3-10
EXIST
V6-3-4
EXIST
V6-3-5
EXIST
V6-3-3
EXIST
V6-3-2 EXIST
V6-3-1
EXIST
V6-3-9
EXIST
V6-3-6
EXIST
V6-3-7
EXIST
V6-3-8
EXIST AHU#6-3
EXIST
HWUH#6-1
EXIST
VFD
EXIST
DDC
1. EXISTING DDC SYSTEM IS JCI. REPLACE CONTROLLERS TO
FULLY INTEGRATE TO CAMPUS SIEMENS SYSTEM.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
ATTIC FLOOR PLAN - MECHANICAL
6 WLP NMT
M6-104
SPS-4
AI14
SPS-2
DI9
SUPPLY
VFD
FAN
DO3
AO3
DI8
AI11
COIL
L P
S
V-1
NO
PREHEAT
AI5
AO1
DI7DI2
D02DO1
DI1
SPS-1
AI3
SUPPLY
PANEL
DDC CONTROL
AI4
T-2
T-1
OUTSIDE AIR
D-1
AI2
D-2
T-8T
AI15
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING DDC. SENSOR, VALVES,
ETC CAN BE REUSED IF FUNCTIONAL AND COMPATIBLE.
2. DDC CONTROLLER TO BE REPLACED. CONNECT NEW
CONTROLLER TO EXISTING ELECTRICAL SERVICE.
DI5
OUTSIDE AIR FLOWMETER (F-1)
RETURN AIR TEMPERATURE SENSOR (T-1)AI2
AI1
RETURN AIR HUMIDITY SENSOR (H-1)AI3
MIXED AIR TEMPERATURE SENSOR (T-2)AI4
AI6
AI7
AI5
AI8
AI10
AI11
AI9
AI12
AI13
AI14
AI15
PREHEAT STEAM CONTROL VALVE (V-1)
PREHEAT COIL DISCHARGE AIR TEMPERATURE SENSOR (T-3)
CHILLED WATER CONTROL VALVE (V-2)
COOLING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-5)
RETURN AIR GROUND & 1ST FLOORS FLOWMETER (F-3)
RETURN AIR 2ND & 3RD FLOORS FLOWMETER (F-2)
SUPPLY FAN VFD STATUS
SUPPLY AIR STATIC PRESSURE SENSOR (SPS-3)
SUPPLY AIR TEMPERATURE SENSOR (T-7)
DISCHARGE AIR STATIC PRESSURE SENSOR (SPS-4)
AMBIENT AIR TEMPERATURE SENSOR (T-8)
DI10
DI11
RETURN AIR FROM
1ST & GROUND
FLOORS
RETURN AIR FROM
2ND FLOORS
FLOWMETER
H-1
AI6
T-3
T-4
C W
R
COIL
CLG
V-2
NC
AI7
AO2
DI10
T-6
AI12
T-7
DPS-2
DI4
DPS-1
DI3AI1
AI9
AI10
F-1
F-2
F-3
AIR
FILTER
SD-1
DI11
SD-2
DI6
SMOKE DAMPER
SMOKE DAMPER
AI8
T-5
T
SPS-3
AI13
SEQUENCE OF OPERATION
1. GENERAL
1.1 THE AIR HANDLING UNIT SHALL BE STARTED AND STOPPED AUTOMATICALLY AT THE ECC. THE HOA SWITCH SHALL BE KEPT IN THE AUTO POSITION. HAND AND OFF POSITIONS SHALL BE USED FOR MAINTENANCE ONLY. UPON RECEIVING A START COMMAND THE SUPPLY FAN SHALL START ONLY AFTER ALL INTERNAL SAFETIES ARE PROVEN. ONCE FAN RUN STATUS IS PROVEN BY A CURRENT SENSING RELAY, THE CONTROLS SHALL OPERATE ACCORDING TO THE SEQUENCES AS DESCRIBED BELOW.
2. AIR FLOW
2.1 OUTSIDE AIR IS METERED BY FLOWMETER, F-1, TO MONITOR AND MAINTAIN A CONSTANT MIN. OUTSIDE AIR FLOW BY MODULATING THE RETURN DAMPER, D-2, AND OUTSIDE AIR
DAMPER, D-1, UP TO THE MAX. FLOW SETPOINT OF 5000 CFM (ADJUSTABLE).
3. TEMPERATURE CONTROL
3.1 TEMPERATURE SENSOR, T-3, IN THE PREHEAT COIL DISCHARGE SHALL TRANSMIT TEMPERATURE CHANGES TO THE DDC. THE DDC SYSTEM SHALL MODULATE THE 2-WAY STEAM PREHEAT CONTROL VALVE, V-1, TO MAINTAIN PREHEAT TEMPERATURE SETPOINT (ADJUSTABLE).
3.2 TEMPERATURE SENSOR, T-7, IN THE DISCHARGE AIR DUCT TRANSMITS TEMPERATURE CHANGES TO THE DDC. THE DDC MODULATES THE 2-WAY COOLING CONTROL VALVE, V-2, TO MAINTAIN DISCHARGE AIR TEMPERATURE SETPOINT OF 55°F (ADJUSTABLE).
4. STATIC PRESSURE AND SUPPLY FAN SPEED CONTROL
4.1 THE VFD SHALL MODULATE THE SPEED OF THE SUPPLY FAN TO MAINTAIN DISCHARGE AIR STATIC PRESSURE TO ITS SETPOINT OF 1.0 IN. WC. (ADJUSTABLE) AS SENSED BY THE
DUCT STATIC PRESSURE SENSOR, SPS-4, LOCATED 3
4 OF THE WAY DOWN THE LONGEST DUCT MAIN.
4.2 THE SUPPLY FAN SPEED SHALL DECREASE TOWARDS ITS MIN. FREQUENCY. AS THE DISCHARGE AIR STATIC PRESSURE DECREASES, THE SUPPLY FAN SPEED SHALL INCREASE.
4.3 THE STATIC PRESSURE IS RESET BASED ON ACTUAL BUILDING LOAD BY POLLING ALL VAV TERMINAL UNITS.
5. DEHUMIDIFICATION CONTROL
5.1 A DUCT HUMIDITY SENSOR, H-1, SHALL MEASURE THE RETURN AIR HUMIDITY AT THE AHU. THE DDC WILL AVERAGE THE POSITION OF THE VAV BOX AIR VALVES AND SHALL ADJUST THE AIR TEMPERATURE UP OR DOWN TO PROVIDE THE MOST EFFICIENT SUPPLY AIR TEMPERATURE TO SATISFY VAV BOX DURING OCCUPIED OPERATION.
5.2 IF THE RETURN AIR HUMIDITY RISES ABOVE SETPOINT OF 60% (ADJUSTABLE) THE SUPPLY AIR TEMPERATURE OF THE AHU SHALL BE LOWERED TO KEEP THE RETURN AIR
HUMIDITY BELOW SETPOINT.
6. ALARMS
6.1 THE UNIT SHALL STOP UPON ANY OF THE SAFETIES BEING TRIPPED REGARDLESS OF THE MODE OF OPERATION (AUTOMATIC, HAND OR BYPASS).
6.2 THE AIR HANDLER RETURN AIR SMOKE DETECTOR, SD-1, AND THE DISCHARGE AIR SMOKE DETECTOR, SD-2, SHALL STOP THE UNIT AND CLOSE THE SMOKE DAMPERS UPON SENSING COMBUSTION PRODUCTS IN THE SYSTEM. SMOKE DETECTORS MUST BE MANUALLY REST AFTER AN ALARM CONDITION IN ORDER FOR THE FAN TO RESTART AND THE
SMOKE DAMPERS TO OPEN.
6.3 A MIXED AIR TEMPERATURE SENSOR, T-2, UPSTREAM OF THE COOLING COIL SIGNALS THE DDC UPON A DROP IN TEMPERATURE BELOW 45°F, WHICH SHALL GENERATE AN ALARM
TO THE ECC.
6.4 A TEMPERATURE LOW LIMIT SWITCH, T-4, SHALL STOP THE UNIT, CLOSE THE OUTSIDE AIR DAMPER, OPEN THE PREHEAT VALVE, AND SEND A CRITICAL ALARM TO THE ECC UPON SENSING A FALL IN TEMPERATURE BELOW SETPOINT (40°F ADJUSTABLE). THE LOW LIMIT SWITCHES MUST BE MANUALLY RESET AFTER AN ALARM CONDITION.
6.5 A TEMPERATURE HIGH LIMIT, T-6, SHALL SHUTDOWN THE FAN AND SEND AN ALARM TO THE ECC UPON A RISE IN DISCHARGE AIR ABOVE 125°F. THE HIGH LIMIT SWITCH MUST BE
MANUALLY RESET AFTER AN ALARM.
6.6 A DISCHARGE AIR HIGH STATIC PRESSURE SAFETY SWITCH, SPS-2, LOCATED AT THE SUPPLY FAN DISCHARGE SHALL STOP THE UNIT UPON SENSING HIGH DISCHARGE DUCT STATIC ABOVE 3 IN. STATIC PRESSURE (ADJUSTABLE) TO PREVENT OVER PRESSURIZING THE DUCTWORK. STATIC PRESSURE SWITCH IS HARDWIRED TO THE VFD AND UNIT IS SHUTDOWN IN HAND, AUTO, OR BYPASS MODE. THE HIGH STATIC PRESSURE SAFETIES MUST BE MANUALLY RESET AFTER AN ALARM CONDITION.
6.7 UPON FAILURE OF THE VFD, THE SUPPLY FAN SHALL BE CONTROLLED MANUALLY AT THE DDC PANEL OR THE ECC THROUGH THE BYPASS STARTER. FAN SHALL BE OPERATED AT
CONSTANT SPEED.
7. MONITORING
7.1 THE DCC SYSTEM MONITORS THE DIFFERENTIAL PRESSURE ACROSS EACH FILTER AND GENERATES AN ALARM IF THE DIFFERENTIAL PRESSURE INCREASES ABOVE THE
SETPOINT OF 0.75 IN. WC. (ADJUSTABLE) TO PROVIDE NOTIFICATION OF A DIRTY FILTER.
8. SHUTDOWN
8.1 STOPPING THE UNIT SHALL DE-ENERGIZE THE CONTROL LOOPS AND SEND THE CONTROL VALVES TO THE CLOSED POSITION. THE OUTSIDE AIR DAMPER WILL CLOSE AND THE
RETURN AIR DAMPER SHALL OPEN.
TTTTT
T
SUPPLY AIR SMOKE DETECTOR (SD-2) STATUS
HIGH LIMIT TEMPERATURE SENSOR (T-6) STATUS
DI8
DI6
DI7
DI4
DI2
DI3
DI1
DI5
RETURN AIR DAMPER (D-2) STATUS
FILTER STATUS (DPS-1)
FILTER STATUS (DPS-2)
RETURN AIR STATIC PRESSURE SENSOR (SPS-1) STATUS
DI9
OUTSIDE AIR DAMPER (D-1) STATUS
DISCHARGE AIR HIGH STATIC PRESSURE SWITCH (SPS-2) STATUS
LOW LIMIT TEMPERATURE SENSOR (T-4) STATUS
SUPPLY FAN STATUS
RETURN AIR SMOKE DETECTOR (SD-1) STATUS
PREHEAT STEAM CONTROL VALVE (V-1)
CHILLED WATER CONTROL VALVE (V-2)
AO1
AO2
AO3
DO1
DO2
DO3
SUPPLY FAN VFD SPEED
OUTSIDE AIR DAMPER (D-1)
RETURN AIR DAMPER (D-2)
SUPPLY FAN START/STOP
AMBIENT AIR
TEMPERATURE
SENSOR
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
AHU#6-1 & AHU#6-2 CONTROL
SCHEMATIC & SEQUENCE
6 WLP NMT
M6-200
DO4
DO4 SMOKE DAMPER OPEN/CLOSE
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING DDC. SENSORS,
VALVES, ETC CAN BE REUSED IF FUNCTIONAL AND
COMPATIBLE.
2. DDC CONTROLLER TO BE REPLACED. CONNECT NEW
CONTROLLER TO EXISTING ELECTRICAL SERVICE.
3. UNIT HEATER UH6-1 IS CONNECTED TO THIS CONTROL
PANEL.
SPS-4
AI14
SPS-2
DI10
SUPPLY
VFD
FAN
DO3
AO3
DI9
AI10
COIL
H W
R
V-1
NO
PREHEAT
AI6
AO1
DI8DI2
D02DO1
DI1
SPS-1
AI4
SUPPLY
PANEL
DDC CONTROL
AI5
T-2
T-1
OUTSIDE AIR
D-1
AI3
D-2
T-9
AI15
DI5
RETURN AIR
FROM 3RD
FLOOR
FLOWMETER
H-1
AI7
T-4
T-5
C W
R
COIL
CLG
V-2
NC
AI8
AO2
DI11
AI11
T-8
SPS-3
AI12
DPS-2
DI4
DPS-1
DI3AI1
AI2
F-1
F-2
AIR
FILTER
SD-1
DI12
SD-2
DI6 AI9
T-6
T-7
DI7
T-3
HWR
V-3
NO
NCC
UH6-1
UH1-TT
AI16
ZONE TEMPERATURE
AO4
AI13
AO5
DI13
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE AIR HANDLING UNIT SHALL BE STARTED AND STOPPED AUTOMATICALLY AT THE ECC. THE HOA SWITCH SHALL BE KEPT IN THE AUTO POSITION. HAND AND OFF POSITIONS SHALL BE USED FOR MAINTENANCE ONLY. UPON RECEIVING A START COMMAND THE SUPPLY FAN SHALL START ONLY AFTER ALL INTERNAL SAFETIES ARE PROVEN. ONCE FAN RUN STATUS IS PROVEN BY A CURRENT SENSING RELAY, THE CONTROLS SHALL OPERATE ACCORDING TO THE SEQUENCES AS DESCRIBED BELOW.
2. AIR FLOW
2.1. OUTSIDE AIR IS METERED BY FLOWMETER, F-1, TO MONITOR AND MAINTAIN A CONSTANT MIN. OUTSIDE AIR FLOW BY MODULATING THE RETURN DAMPER, D-2, AND OUTSIDE AIR DAMPER, D-1, UP TO THE MAX. FLOW SETPOINT OF 5000 CFM (ADJUSTABLE).
3. TEMPERATURE CONTROL
3.1. TEMPERATURE SENSOR, T-3, IN THE PREHEAT COIL DISCHARGE SHALL TRANSMIT TEMPERATURE CHANGES TO THE DDC. THE DDC SYSTEM SHALL MODULATE THE 2-WAY STEAM PREHEAT CONTROL VALVE, V-1, TO MAINTAIN PREHEAT TEMPERATURE SETPOINT
(ADJUSTABLE).
3.2. TEMPERATURE SENSOR, T-8, IN THE DISCHARGE AIR DUCT TRANSMITS TEMPERATURE CHANGES TO THE DDC. THE DDC MODULATES THE 2-WAY COOLING CONTROL VALVE, V-2, TO MAINTAIN DISCHARGE AIR TEMPERATURE SETPOINT OF 55°F (ADJUSTABLE).
4. STATIC PRESSURE AND SUPPLY FAN SPEED CONTROL
4.1. THE VFD SHALL MODULATE THE SPEED OF THE SUPPLY FAN TO MAINTAIN DISCHARGE AIR STATIC PRESSURE TO ITS SETPOINT OF 1.0 IN.
WC. (ADJUSTABLE) AS SENSED BY THE DUCT STATIC PRESSURE SENSOR, SPS-4, LOCATED 3
4 OF THE WAY DOWN THE LONGEST DUCT
MAIN.
4.2. THE SUPPLY FAN SPEED SHALL DECREASE TOWARDS ITS MIN. FREQUENCY. AS THE DISCHARGE AIR STATIC PRESSURE DECREASES, THE
SUPPLY FAN SPEED SHALL INCREASE.
4.3. THE STATIC PRESSURE IS RESET BASED ON ACTUAL BUILDING LOAD BY POLLING ALL VAV TERMINAL UNITS.
5. DEHUMIDIFICATION CONTROL
5.1. A DUCT HUMIDITY SENSOR, H-1, SHALL MEASURE THE RETURN AIR HUMIDITY AT THE AHU. THE DDC WILL AVERAGE THE POSITION OF THE VAV BOX AIR VALVES AND SHALL ADJUST THE AIR TEMPERATURE UP OR DOWN TO PROVIDE THE MOST EFFICIENT SUPPLY AIR
TEMPERATURE TO SATISFY VAV BOX DURING OCCUPIED OPERATION.
5.2. IF THE RETURN AIR HUMIDITY RISES ABOVE SETPOINT OF 60% (ADJUSTABLE) THE SUPPLY AIR TEMPERATURE OF THE AHU SHALL BE
LOWERED TO KEEP THE RETURN AIR HUMIDITY BELOW SETPOINT.
6. ALARMS
6.1. THE UNIT SHALL STOP UPON ANY OF THE SAFETIES BEING TRIPPED REGARDLESS OF THE MODE OF OPERATION (AUTOMATIC, HAND OR
BYPASS).
6.2. THE AIR HANDLER RETURN AIR SMOKE DETECTOR, SD-1, AND THE DISCHARGE AIR SMOKE DETECTOR, SD-2, SHALL STOP THE UNIT UPON SENSING COMBUSTION PRODUCTS IN THE SYSTEM. SMOKE DETECTORS MUST BE MANUALLY REST AFTER AN ALARM CONDITION IN
ORDER FOR THE FAN TO RESTART.
6.3. A MIXED AIR TEMPERATURE SENSOR, T-3 UPSTREAM OF THE COOLING COIL SIGNALS THE DDC UPON A DROP IN TEMPERATURE BELOW
45°F, WHICH SHALL GENERATE AN ALARM TO THE ECC.
6.4. A TEMPERATURE LOW LIMIT SWITCH, T-5, SHALL STOP THE UNIT, CLOSE THE OUTSIDE AIR DAMPER, OPEN THE PREHEAT VALVE, AND SEND A CRITICAL ALARM TO THE ECC UPON SENSING A FALL IN TEMPERATURE BELOW SETPOINT (40°F ADJUSTABLE). THE LOW LIMIT
SWITCHES MUST BE MANUALLY RESET AFTER AN ALARM CONDITION.
6.5. A TEMPERATURE HIGH LIMIT, T-7, SHALL SHUTDOWN THE FAN AND SEND AN ALARM TO THE ECC UPON A RISE IN DISCHARGE AIR ABOVE
125°F. THE HIGH LIMIT SWITCH MUST BE MANUALLY RESET AFTER AN ALARM.
6.6. A DISCHARGE AIR HIGH STATIC PRESSURE SAFETY SWITCH, SPS-2, LOCATED AT THE SUPPLY FAN DISCHARGE SHALL STOP THE UNIT UPON SENSING HIGH DISCHARGE DUCT STATIC ABOVE 3 IN. STATIC PRESSURE (ADJUSTABLE) TO PREVENT OVER PRESSURIZING THE DUCTWORK. STATIC PRESSURE SWITCH IS HARDWIRED TO THE VFD AND UNIT IS SHUTDOWN IN HAND, AUTO, OR BYPASS MODE. THE HIGH
STATIC PRESSURE SAFETIES MUST BE MANUALLY RESET AFTER AN ALARM CONDITION.
6.7. UPON FAILURE OF THE VFD, THE SUPPLY FAN SHALL BE CONTROLLED MANUALLY AT THE DDC PANEL OR THE ECC THROUGH THE BYPASS
STARTER. FAN SHALL BE OPERATED AT CONSTANT SPEED.
7. MONITORING
7.1. THE DCC SYSTEM MONITORS THE DIFFERENTIAL PRESSURE ACROSS EACH FILTER AND GENERATES AN ALARM IF THE DIFFERENTIAL PRESSURE INCREASES ABOVE THE SETPOINT OF 0.75 IN. WC. (ADJUSTABLE) TO PROVIDE NOTIFICATION OF A DIRTY FILTER.
8. SHUTDOWN
8.1. STOPPING THE UNIT SHALL DE-ENERGIZE THE CONTROL LOOPS AND SEND THE CONTROL VALVES TO THE CLOSED POSITION. THE
OUTSIDE AIR DAMPER WILL CLOSE AND THE RETURN AIR DAMPER SHALL OPEN.
9. UNIT HEATER CONTROL
9.1. A ZONE TEMPERATURE SENSOR MOUNTED IN THE ATTIC SPACE TRANSMITS TEMPERATURE READINGS TO THE DDC SYSTEM. UPON A FALL IN ZONE TEMPERATURE BELOW SETPOINT, THE DDC SYSTEM COMMANDS THE UNIT HEATER ON AND OPENS THE UNIT HEATER CONTROL VALVE, V-3, TO ALLOW HOT WATER TO FLOW THROUGH THE UNIT'S HEATING COIL UNTIL THE ZONE HAS REACHED THE SETPOINT TEMPERATURE (ADJUSTABLE). IF THE UNIT HEATER FAILS TO OPERATE WHEN COMMANDED, AN ALARM WILL BE GENERATED
AT THE ECC, AND THE HEATING CONTROL VALVE SHALL CLOSE.
AI2
AI1
AI3
AI4
AI6
AI7
AI5
AI8
AI10
AI11
AI9
AI12
AI13
AI14
AI15
AI16
HOT WATER CONTROL VALVE (V-1)
CHILLED WATER CONTROL VALVE (V-2)
AO1
AO2
AO3
AO4
AO5
SUPPLY FAN VFD SPEED
UNIT HEATER (UH6-1) HOT WATER CONTROL VALVE (V-3)
UNIT HEATER (UH6-1) OUTPUT LEVEL
T
TTTTT
T H
OUTSIDE AIR FLOWMETER (F-1)
RETURN AIR TEMPERATURE SENSOR (T-1)
RETURN AIR HUMIDITY SENSOR (H-1)
MIXED AIR TEMPERATURE SENSOR (T-2)
6-AHU-3 HOT WATER CONTROL VALVE (V-1)
PREHEAT COIL DISCHARGE AIR TEMPERATURE SENSOR (T-4)
CHILLED WATER CONTROL VALVE (V-2)
COOLING COIL DISCHARGE AIR TEMPERATURE SENSOR (T-6)
SUPPLY FAN VFD STATUS
SUPPLY AIR TEMPERATURE SENSOR (T-7)
SUPPLY AIR STATIC PRESSURE SENSOR (SPS-3)
DISCHARGE AIR STATIC PRESSURE SENSOR (SPS-4)
UNIT HEATER (UH6-1) HOT WATER CONTROL VALVE (V-3)
AMBIENT AIR TEMPERATURE SENSOR (T-9)
ZONE TEMPERATURE SENSOR (UH1-T)
DI10
DI11
DI8
DI6
DI7
DI4
DI3
DI1
DI5
DI9
HIGH LIMIT TEMPERATURE SENSOR (T-7) STATUS
RETURN AIR DAMPER (D-2) STATUS
FILTER STATUS (DPS-1)
FILTER STATUS (DPS-2)
RETURN AIR STATIC PRESSURE SENSOR (SPS-1) STATUS
OUTSIDE AIR DAMPER (D-1) STATUS
SUPPLY FAN STATUS
LOW LIMIT TEMPERATURE SENSOR (T-3) STATUS
HIGH LIMIT TEMPERATURE SENSOR (T-5) STATUS
RETURN AIR SMOKE DETECTOR (SD-1) STATUS
DI2
RETURN AIR FLOWMETER (F-2)
T T
AMBIENT AIR
TEMPERATURE
SENSOR
DI12
DI13 UNIT HEATER (UH6-1) STATUS
SUPPLY AIR SMOKE DETECTOR (SD-2) STATUS
DISCHARGE AIR HIGH STATIC PRESSURE SWITCH (SPS-2) STATUS
DO1
DO2
DO3
OUTSIDE AIR DAMPER (D-1)
RETURN AIR DAMPER (D-2)
SUPPLY FAN START/STOP
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
AHU#6-3 CONTROL SCHEMATIC
& SEQUENCE
6 WLP NMT
M6-201
STR
STEAM CONV.
TO COND. PUMP
T
AI8
HWR
HWS
SENSOR (TYP)
TEMPERATURE
TO COND. PUMP
STEAM
SUPPLY
STEAM
SUPPLY
HWR TEMPERATURE
NO
180 160 140
HOT WATER SETPOINT
(DEG F)
OUTDOOR
AIR
TEMPERATURE
(DEG F)
HEATING HOT WATER RESET
SCHEDULE
NO
SEQUENCE OF OPERATION
1. OCCUPIED MODE
1.1. STEAM CONTROL VALVES SHALL MODULATE TO MAINTAIN THE HOT WATER
SUPPLY TEMPERATURE AT SETPOINT.
1.2. THE HOT WATER SUPPLY TEMPERATURE RESETS INVERSELY WITH THE
OUTDOOR TEMPERATURE AS SCHEDULED: AT 30°F OA - HWS AT 180°F, AT 70°F
OA - HWS AT 140°F.
1.3. STEAM HOT WATER CONVERTERS, 6-HTX-1 & 6-HTX-2, ARE 100% REDUNDANT
AND ONLY ONE UNIT AT A TIME WILL OPERATE.
1.4. HOT WATER PUMPS ARE CONTROLLED BY THE DDC SYSTEM. THE PUMPS ARE
100% REDUNDANT REQUIRING ONLY ONE PUMP AT A TIME TO OPERATE. THE
LEAD/LAG WATER PUMPS AND HEAT EXCHANGERS ARE SEQUENCED BY THE DDC
SYSTEM TO CHANGE EVERY 7 DAYS. IN THE EVENT A PUMP FAILS TO START IN 30
SECONDS OR NO FLOW CONDITION AT THE HEAT EXCHANGER, AN ALARM IS
GENERATED, AND THE SECOND PUMP/EXCHANGER STARTS AUTOMATICALLY.
2. UNOCCUPIED MODE
2.1. IF THE OUTSIDE AIR TEMPERATURE IS BELOW 40°F (ADJUSTABLE) THE DDC
SYSTEM WILL PLACE THE HWS IN OCCUPIED MODE TO START PUMPS AND
ACTUATE STEAM VALVES TO MAINTAIN SETPOINT AS NEEDED BY THE RESET
SCHEDULE.
3. VALVE SEQUENCE FOR LEAD HEAT EXCHANGER
3.1. AFTER THE FLOW THROUGH THE HEAT EXCHANGER HAS BEEN CONFIRMED VIA
THE FLOW SWITCH (FS-X), THE DDC CONTROLLER WILL RECEIVE AN INPUT AND
THE 24VAC POWER WILL BE APPLIED TO THE STEAM VALVE ACTUATORS. THE
STEAM VALVES SHALL OPERATE IN THREE MODES OF CONTROL.
3.2. FIRST MODE: THE 13 CAPACITY STEAM VALVE MODULATES TO MAINTAIN THE
ACTIVE SETPOINT. AFTER THE 1
3 VALVE HAS REACHED 100% CAPACITY FOR 5
MINUTES, THE SECOND MODE WILL BE ENABLED.
3.3. SECOND MODE: THE 13 VALVE IS COMMANDED TO CLOSE AND THE 2
3 CAPACITY
STEAM VALVE MODULATES TO MAINTAIN SETPOINT. AFTER THE 2
3 VALVE HAS
REACHED 100% CAPACITY FOR 5 MINUTES, THE THIRD MODE WILL BE ENABLED.
3.4. THIRD MODE: THE 13 VALVE WILL BE RE-ENABLED, AND BOTH STEAM VALVES
MODULATE TOGETHER TO MAINTAIN SETPOINT.
3.5. AS DEMAND REDUCES, THE MODES WILL BE DISABLED AT 40% COMMANDED
VALVE (DIFFERENTIAL OF 60%), AND A 5 MINUTE DELAY WILL BE ACTIVATED
BETWEEN MODES. UPON A LOSS OF FLOW THE STEAM VALVES WILL BE CLOSED
(HARDWIRED AND SOFTWARE INTERLOCKS).
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING
DDC. SENSORS, ACTUATORS, ETC CAN
BE REUSED IF FUNCTIONAL AND
COMPATIBLE.
2. DDC CONTROLLER TO BE REPLACED.
CONNECT NEW CONTROLLER TO
EXISTING ELECTRICAL SERVICE.
AI2
AI1
AI3
AI4
AI6
AI7
AI5
AI8
STEAM CONVERTER (6-HTX-1) VALVE 2 STATUS
STEAM CONVERTER (6-HTX-2) VALVE 2 STATUS
STEAM CONVERTER (6-HTX-2) VALVE 1 STATUS
HOT WATER SUPPLY TEMPERATURE SENSOR
HOT WATER SUPPLY FLOWMETER
HOT WATER RETURN TEMPERATURE SENSOR
AMBIENT AIR TEMPERATURE SENSOR
STEAM CONVERTER (6-HTX-1) VALVE 1 STATUS
T
T
STEAM CONV.
6-HTX-1 VALVE 2
3 VALVE OUTPUT
6-HTX-1 VALVE 1
3 VALVE OUTPUT
6-HTX-2 VALVE 2
3 VALVE OUTPUT
6-HTX-2 VALVE 1
3 VALVE OUTPUT
AI5
AI6
AI7
DI1
DI2
DI3
DO1
DI4
DO2
STR
AMBIENT AIR
TEMPERATURE SENSOR
INSTALLED ON NORTH
SIDE OF BUILDING
DI4
DI3
DI1
STEAM CONVERTER (6-HTX-2) FLOW SWITCH STATUS
HOT WATER PUMP (6-HWP-1) STATUS
HOT WATER PUMP (6-HWP-2) STATUS
STEAM CONVERTER (6-HTX-1) FLOW SWITCH STATUS
DI2
DO1
DO2
HOT WATER PUMP (6-HWP-1) START/STOP
HOT WATER PUMP (6-HWP-2) START/STOP
FT
FS
FS
VFD
6-CHWP-1
6-CHWP-2
CAMPUS
CHWS
CAMPUS
CHWR
BLDG 6
CHWS
BLDG 6
CHWR
P
LOCATED 3 4 DOWN LONGEST
RUN.
FT
T
AI19
H
AI18
AMBIENT AIR TEMPERATURE
& HUMIDITY SENSOR
INSTALLED ON NORTH SIDE
OF BUILDING
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE EXISTING CHILLED WATER SUPPLY FROM THE CENTRAL COOLING PLANT PROVIDES CHILLED WATER TO THE VFD SECONDARY PUMPING SYSTEM AT BUILDING 6. THE SECONDARY PUMPS ARE 100% REDUNDANT REQUIRING ONLY ONE PUMP AT A TIME TO OPERATE.
1.2. UPON A CALL FOR COOLING FROM ANY AIR HANDLER, FAN COIL, OR BLOWER COIL, THE LEAD CHILLED WATER PUMP SHALL ENERGIZE AND THE RESPECTIVE VFD SHALL MODULATE THE PUMP TO MAINTAIN THE PRESSURIZATION SETPOINT (ADJUSTABLE) AT THE DIFFERENTIAL PRESSURE
SENSOR LOCATED 3
4 OF THE WAY DOWN THE LONGEST PIPING RUN. THE VFD WILL MODULATE AS REQUIRED TO MAINTAIN THE SYSTEM PRESSURE
SETPOINT.
1.3. A HYDRONIC BRIDGE CIRCUIT DOWNSTREAM OF THE CHILLED WATER PUMPS WITH A FLOWMETER, TEMPERATURE SENSOR AND MANUAL BALANCING VALVE SHALL BE UTILIZED TO BYPASS SECONDARY CHILLED WATER FLOW BACK TO THE PRIMARY LOOP AT MIN. VFD SETPOINT, WHILE COOLING COIL 2-WAY VALVES FLOW SHUT OFF AS COOLING LOAD DICTATES. MANUAL BALANCING VALVES SHALL BE SET AS A PRESSURE DROP TO MATCH REMAINDER OF BUILDING PIPING CIRCUIT AT MIN. FLOW. CHILLED WATER FLOWS WILL BE MEASURED AND TOTALLIZED BY HIGH ACCURACY FLOWMETERS AT EACH PUMP DISCHARGE, HYDRONIC BRIDGE BYPASS, AND COMMON SECONDARY CHW SUPPLY.
2. LEAD/STANDBY PUMP CONTROL
2.1. IF THE LEAD BUILDING SECONDARY CHILLED WATER PUMP FAILS TO OPERATE, THE STANDBY PUMP SHALL BE AUTOMATICALLY STARTED, AND THE SYSTEM SHALL RESUME NORMAL OPERATION. AN ALARM WILL BE GENERATED AT THE DDC PANEL TO NOTIFY OF PUMP FAILURE.
2.2. THE LEAD/STANDBY STATUS OF THE PUMPS SHALL BE ROTATED EVERY 7 DAYS FOR EVEN RUNTIME.
AI2
AI1
AI3
AI4
AI6
AI7
AI5
AI8
AI9
CAMPUS CHILLED WATER SUPPLY PRESSURE SENSOR
CAMPUS CHILLED WATER SUPPLY FLOWMETER (6-WFM-11)
EMERGENCY BYPASS TEMPERATURE SENSOR
EMERGENCY BYPASS FLOWMETER (6-WFM-12)
CAMPUS CHILLED WATER RETURN TEMPERATURE
CHILLED WATER PUMP (6-CHWP-1) VFD STATUS
CHILLED WATER PUMP (6-CHWP-2) VFD STATUS
6-CHWP-1 DISCHARGE FLOWMETER (6-FWM-13)
CAMPUS CHILLED WATER SUPPLY TEMPERATURE SENSOR
AI13
AI12
AI10
BUILDING 6 CHILLED WATER SUPPLY PRESSURE SENSOR
BUILDING 6 CHILLED WATER SUPPLY TEMPERATURE SENSOR
BUILDING 6 CHILLED WATER SUPPLY FLOWMETER (6-WFM-17)
6-CHWP-1 DISCHARGE FLOWMETER (6-FWM-14)
AI11
TPTP FT
VFD
DO1
DI1
AO1
AI7
FT
F T
AI1 AI2 AI3
AI5
AI6
AI10
AI9
AI11 AI12 AI13
AI4 AI14
F
T AI15
TT
AI16
AI17
FT
AI14 HYDRONIC BYPASS BRIDGE TEMPERATURE SENSOR
AI17
AI16
HYDRONIC BYPASS BRIDGE FLOWMETER (6-WFM-15)
BUILDING 6 CHILLED WATER RETURN TEMPERATURE SENSOR
DIFFERENTIAL PRESSURE SENSOR
AI15
AI18 AMBIENT AIR HUMIDITY SENSOR
DO2
DI2
AO2
AI8
6-WFM-176-WFM-11
6-WFM-12
6-WFM-13
6-WFM-14
AI19 AMBIENT AIR TEMPERATURE SENSOR
6-WFM-15
TT
DI1
CHILLED WATER PUMP (6-CHWP-2) STATUS
CHILLED WATER PUMP (6-CHWP-1) STATUS
DI2
DO1
DO2
CHILLED WATER PUMP (6-CHWP-1) START/STOP
CHILLED WATER PUMP (6-CHWP-2) START/STOP
AO1
AO2
CHILLED WATER PUMP (6-CHWP-1) VFD SPEED
CHILLED WATER PUMP (6-CHWP-2) VFD SPEED
AO1
AO2
STEAM CONVERTER (6-HTX-1) VALVE 2 CONTROLLER
STEAM CONVERTER (6-HTX-1) VALVE 1 CONTROLLER
AI2
AO2
AI1
AO1
AI3
AO3
AI4
AO4
AO3
AO4
STEAM CONVERTER (6-HTX-2) VALVE 2 CONTROLLER
STEAM CONVERTER (6-HTX-2) VALVE 1 CONTROLLER
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
HEATING HOT WATER & SCHW
SYSTEMS CONTROL SCHEMATICS
& SEQUENCES
6 WLP NMT
M6-202
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING
DDC. SENSORS, ACTUATORS, ETC CAN
BE REUSED IF FUNCTIONAL AND
COMPATIBLE.
2. DDC CONTROLLER TO BE REPLACED.
CONNECT NEW CONTROLLER TO
EXISTING ELECTRICAL SERVICE.
COIL
H W
R
V-1
NC
HTG
AI3
AO1
PANEL
DDC CONTROL
AI4
T-1
AI2
NOTES:
1. ALL CONTROL DEVICES ARE
EXISTING DDC. SENSORS &
ACTUATORS CAN BE
REUSED IF FUNCTIONAL
AND COMPATIBLE.
2. CONTROLLER AND SPACE
TEMPERATURE SENSOR TO
BE REPLACED.
SUPPLY
STR
FAN
DO1
DI4
COIL
H W
R
V-1
NO
HTG
AI1
AO1
T
DI3
RETURN AIR
T-2
C W
R
COIL
CLG
V-2
NC
AI2
AO2
AI3
T-3
DPS-1
DI2
PANEL
DDC CONTROL
SUPPLY AIR
DI1
T-1
NOTES:
1. ALL CONTROL DEVICES
ARE EXISTING DDC.
SENSORS, AND
ACTUATORS CAN BE
REUSED IF FUNCTIONAL
AND COMPATIBLE.
2. CONTROLLER AND SPACE
TEMPERATURE SENSOR
TO BE REPLACED.
3. TYPICAL OF 3 UNITS.
AO2
FLOWMETER
AI1
F-1
T-4T
AI4
SPACE TEMPERATURE
SENSOR
T-2
AI5
SPACE TEMPERATURE SENSOR
SEQUENCE OF OPERATION
1. START/STOP CONTROL
1.1. THE BLOWER COIL WILL OPERATE ON A SCHEDULE AS SET BY THE ECC. THE UNIT FAN WILL BE
STARTED AND STOPPED BY THE DDC SYSTEM THROUGH THE ECC. THE CONTROL LOOPS ARE
ENERGIZED WHEN FAN RUN STATUS IS PROVEN BY THE CURRENT SENSING RELAY. STOPPING THE
UNIT WILL DE-ENERGIZE THE CONTROL LOOPS AND SEND THE HOT WATER AND CHILLED WATER
CONTROL VALVES TO THE CLOSED POSITION.
2. TEMPERATURE CONTROL
2.1. A ZONE TEMPERATURE SENSOR SENDS TEMPERATURE INFORMATION TO THE DDC SYSTEM. THE DDC SYSTEM THEN MODULATES THE CHILLED WATER AND HOT WATER CONTROL VALVES, V-2 AND
V-1 RESPECTIVELY, IN SEQUENCE TO MAINTAIN ZONE TEMPERATURE SETPOINT.
2.2. UPON A RISE IN ZONE TEMPERATURE, THE CHILLED WATER VALVE WILL MODULATE OPEN TO
MAINTAIN ZONE TEMPERATURE SETPOINT OF 75°F (ADJUSTABLE).
2.3. IF THE ZONE TEMPERATURE FALLS BELOW 70°F SETPOINT (ADJUSTABLE), THE HOT WATER VALVE
WILL MODULATE OPEN TO MAINTAIN ZONE SETPOINT.
2.4. IF THE UNIT FAILS TO OPERATE BETWEEN THE RANGE OF 70-75°F (ADJUSTABLE), AN ALARM MESSAGE WILL BE SENT TO THE ECC, AND BOTH CHILLED AND HOT WATER CONTROL VALVES WILL
CLOSE.
3. SYSTEM SAFETIES
3.1. HIGH LIMIT THERMOSTAT, T-1, IN THE RETURN AIR PATH WILL STOP THE UNIT UPON DETECTION OF
TEMPERATURE ABOVE ITS SETPOINT OF 125°F.
3.2. LOW LIMIT THERMOSTAT, T-2, LOCATED BEFORE THE CHILLED WATER COILS WILL STOP THE UNIT
UPON DETECTION OF AIR TEMPERATURE BELOW ITS SETPOINT OF 35°F.
3.3. FILTER STATUS WILL BE MONITORED BY A DIFFERENTIAL PRESSURE SENSOR, DPS-1, AT THE FILTER
BANK.
SEQUENCE OF OPERATION
1. OCCUPIED MODE
1.1. THE ZONE TEMPERATURE SENSOR, T-2, TRANSMITS READINGS TO THE VAV CONTROLLER WHICH IN TURN MODULATES THE PRIMARY AIRFLOW VAV DAMPER, D-1, AND REHEAT CONTROL VALVE, V-1, TO
MAINTAIN SPACE TEMPERATURE SETPOINTS (ADJUSTABLE).
1.2. UPON A RISE IN ZONE TEMPERATURE ABOVE SETPOINT, THE VAV BOX CONTROLLER MODULATES
THE PRIMARY AIRFLOW VAV DAMPER TO MAX. CFM SETPOINT.
1.3. A DROP IN SPACE TEMPERATURE SETPOINT SIGNALS THE VAV TO MODULATE THE PRIMARY
AIRFLOW VAV DAMPER TO THE MIN. CFM SETPOINT. A FURTHER DROP IN ZONE TEMPERATURE
SIGNALS THE VMA TO MODULATE THE VAV BOX REHEAT CONTROL VALVE OPEN TO HEAT THE ZONE
TO WITHIN +/- 0.5°F OF SETPOINT.
2. UNOCCUPIED MODE
2.1. WHEN THE SYSTEM IS INDEXED TO UNOCCUPIED MODE, THE AIR HANDLER STOPS, THE PRIMARY
AIRFLOW VAV DAMPER AND THE REHEAT CONTROL VALVE CLOSES.
2.2. IF THE ZONE TEMPERATURE FALLS BELOW THE NIGHT SETBACK SETPOINT (ADJUSTABLE), THE AIR HANDLING UNIT WILL START, THE VAV BOX DAMPER OPEN, AND THE REHEAT CONTROL VALVE WILL
MODULATE OPEN TO MAINTAIN THE UNOCCUPIED ZONE TEMPERATURE AT SETPOINT.
2.3. IF THE ZONE TEMPERATURE RISES ABOVE THE NIGHT CYCLE SETPOINT, THE AIR HANDLING UNIT
WILL START AND THE VAV BOX DAMPER WILL MODULATE OPEN TO COOL THE ZONE TO THE
UNOCCUPIED COOLING SETPOINT TEMPERATURE.
2.4. T-2 CONTAINS A PUSH BUTTON OVERRIDE TO ALLOW OCCUPANTS TO INDEX THE SYSTEM TO
OCCUPIED MODE FOR AFTER HOURS USE. THE VMA CONTROLLER WILL FUNCTION PER THE
OCCUPIED MODE OF OPERATION UNTIL THE TEMPORARY OCCUPANCY TIMER EXPIRES, AT WHICH
TIME THE VAV CONTROLLER WILL REVERT TO UNOCCUPIED MODE OF OPERATION DEPENDING ON
TIME OF DAY SCHEDULING.
3. MORNING WARM-UP MODE
3.1. WHEN INDEXED TO THE MORNING WARM-UP MODE OF OPERATION, THE DDC SYSTEM WILL SET THE
SPACE SENSOR TO ITS OCCUPIED HEATING TEMPERATURE SETPOINT (ADJUSTABLE). THE VMA
CONTROLLER WILL INDEX THE PRIMARY AIRFLOW VAV DAMPER TO 100% OPEN. THE REHEAT
CONTROL VALVE WILL OPEN AND ALLOW THE PRIMARY AIRFLOW TO HEAT THE ZONE WHEN THE
RESPECTIVE AIR HANDLER IS CYCLED TO MORNING WARM-UP MODE.
3.2. WHEN THE ZONE TEMPERATURE REACHES ITS OCCUPIED SETPOINT, THE PRIMARY AIRFLOW VAV
DAMPER AND THE REHEAT CONTROL VALVE WILL CLOSE AND THE AIR HANDLER IS STILL IN
WARM-UP MODE. AS THE AIR HANDLER IS INDEXED TO OCCUPIED MODE OF OPERATION, THE VAV
BOX WILL INDEX TO OCCUPIED MODE AS WELL.
D-1
T
T
TM
AI2
AI1
AI3
AI4
AI5
INTAKE AIR FLOWMETER
HOT WATER CONTROL VALVE (V-1)
DISCHARGE AIR TEMPERATURE SENSOR (T-1)
SPACE TEMPERATURE SENSOR (T-2)
PRIMARY AIRFLOW VAV DAMPER (D-1)
AO1
AO2
PRIMARY AIRFLOW VAV DAMPER (D-1) CONTROLLER
HOT WATER CONTROL VALVE (V-1)
AI2
AI1
AI3
AI4
HOT WATER CONTROL VALVE (V-1)
DISCHARGE AIR TEMPERATURE SENSOR (T-3)
SPACE TEMPERATURE SENSOR (T-4)
CHILLED WATER CONTROL VALVE (V-2)
AO1 HOT WATER CONTROL VALVE (V-1)
DI4
DI3
DI1
FILTER STATUS (DPS-1)
LOW LIMIT TEMPERATURE SENSOR (T-2) STATUS
SUPPLY FAN STATUS
HIGH LIMIT TEMPERATURE SENSOR (T-1) STATUS
DI2
AO2 CHILLED WATER CONTROL VALVE (V-2)
DO1 SUPPLY FAN START/STOP
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
T
VAV TERMINAL (TYP.) & FCU (TYP.)
CONTROL SCHEMATICS &
SEQUENCES
6 WLP NMT
M6-203
SUPPLY
VFD
FAN
DO1
AO3
DI4
AI3
COIL
H W
R
V-1
HTG
AI1
AO1
DI3
RETURN AIR
T-2
C W
R
COIL
CLG
V-2
NC
AI2
AO2
AI4
T-3
DPS-1
DI2
OUTSIDE AIR
PANEL
DDC CONTROL
SUPPLY AIR
DI1
T-1
NOTES:
1. ALL CONTROL DEVICES ARE EXISTING DDC. SENSORS, ACTUATORS, ETC
CAN BE REUSED IF FUNCTIONAL AND COMPATIBLE.
2. CONTROLLER AND SPACE TEMPERATURE SENSOR TO BE REPLACED.
3. EXHAUST FAN INTERLOCKED WITH BOILER COIL UNIT.
STR
DO3
DI7
T
DI6
T-5
EF6-1 5000
CFM
DO2
DI5
D-1
NC
T-4T
AI5
SPACE TEMPERATURE
SENSOR
SEQUENCE OF OPERATION
1. START/STOP CONTROL
1.1. THE BLOWER COIL WILL OPERATE ON A SCHEDULE AS SET BY THE ECC. THE UNIT FAN WILL BE
STARTED AND STOPPED BY THE DDC SYSTEM THROUGH THE ECC. THE CONTROL LOOPS ARE
ENERGIZED WHEN FAN RUN STATUS IS PROVEN BY THE CURRENT SENSING RELAY. STOPPING THE
UNIT WILL DE-ENERGIZE THE CONTROL LOOPS AND SEND THE HOT WATER AND CHILLED WATER
CONTROL VALVES TO THE CLOSED POSITION.
1.2. EF6-1 OPERATES ONLY WHEN THE BCU IS OFF AND THE WALL MOUNTED THERMOSTAT, T-6, IS ABOVE ZONE TEMPERATURE SETPOINT 86°F (ADJUSTABLE). WHEN EF6-1 TURNS ON, THE EXHAUST AIR
DAMPER WILL OPEN. EF6-1 IS COMMANDED OFF WHEN THE ZONE TEMPERATURE REACHES
SETPOINT OR WHEN THE BCU TURNS ON. WHEN EF6-1 IS COMMANDED OFF, THE EXHAUST AIR
DAMPER WILL CLOSE.
2. TEMPERATURE CONTROL
2.1. A ZONE TEMPERATURE SENSOR SENDS TEMPERATURE INFORMATION TO THE DDC SYSTEM. THE DDC SYSTEM THEN MODULATES THE CHILLED WATER AND HOT WATER CONTROL VALVES, V-2 AND
V-1 RESPECTIVELY, IN SEQUENCE TO MAINTAIN ZONE TEMPERATURE SETPOINT.
2.2. UPON A RISE IN ZONE TEMPERATURE, THE CHILLED WATER VALVE WILL MODULATE OPEN TO
MAINTAIN ZONE TEMPERATURE SETPOINT OF 75°F (ADJUSTABLE).
2.3. IF THE ZONE TEMPERATURE FALLS BELOW 70°F SETPOINT (ADJUSTABLE), THE HOT WATER VALVE
WILL MODULATE OPEN TO MAINTAIN ZONE SETPOINT.
2.4. IF THE UNIT FAILS TO OPERATE BETWEEN THE RANGE OF 70-75°F (ADJUSTABLE), AN ALARM MESSAGE WILL BE SENT TO THE ECC, AND BOTH CHILLED AND HOT WATER CONTROL VALVES WILL
CLOSE.
3. SYSTEM SAFETIES
3.1. HIGH LIMIT THERMOSTAT, T-1, IN THE RETURN AIR PATH WILL STOP THE UNIT UPON DETECTION OF
TEMPERATURE ABOVE ITS SETPOINT OF 125°F.
3.2. LOW LIMIT THERMOSTAT, T-2, LOCATED BEFORE THE CHILLED WATER COILS WILL STOP THE UNIT
UPON DETECTION OF AIR TEMPERATURE BELOW ITS SETPOINT OF 35°F.
3.3. FILTER STATUS WILL BE MONITORED BY A DIFFERENTIAL PRESSURE SENSOR, DPS-1, AT THE FILTER
BANK.
T TT
AI2
AI1
AI3
AI4
HOT WATER CONTROL VALVE (V-1)
SUPPLY FAN VFD STATUS
DISCHARGE AIR TEMPERATURE SENSOR (T-3)
CHILLED WATER CONTROL VALVE (V-2)
AI5 SPACE TEMPERATURE SENSOR (T-4)
DI4
DI3
DI1
FILTER STATUS (DPS-1)
LOW LIMIT TEMPERATURE SENSOR (T-2) STATUS
RETURN AIR HIGH LIMIT TEMPERATURE SENSOR (T-1) STATUS
DI2
DI5 EXHAUST AIR DAMPER (D-1) STATUS
SUPPLY FAN STATUS
DI6 HIGH LIMIT TEMPERATURE SENSOR (T-5) STATUS
DI7
AO1 HOT WATER CONTROL VALVE (V-1)
AO2 CHILLED WATER CONTROL VALVE (V-2)
AO3 SUPPLY FAN VFD SPEED
DO1 SUPPLY FAN START/STOP
DO2 EXHAUST AIR DAMPER (D-1) CONTROLLER
DO3 EXHAUST FAN (EF6-1) START/STOP
EXHAUST FAN (EF6-1) STATUS
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
BCU & EXHAUST FAN (TYP.)
CONTROL SCHEMATICS &
SEQUENCES & BALANCE SCHEDULES
6 WLP NMT
M6-204
SHUT-OFF VARIABLE AIR VOLUME BOX WITH HOT WATER REHEAT
LABEL AREA SERVED AHU SERVED
CFM HEATING
COIL GPMMAX. MIN.
V6-1-1 213, 2C1 AHU#6-1 650 450 1.75
V6-1-2 212 AHU#6-1 370 230 1.0
V6-1-3 211 AHU#6-1 330 225 1.0
V6-1-4 208, 209, 209A, 210 AHU#6-1 880 550 2.50
V6-1-5 213A, 214, 215 AHU#6-1 680 400 1.75
V6-1-6 216 AHU#6-1 1000 450 2.0
V6-1-7 217, 218 AHU#6-1 1100 500 2.25
V6-1-8 204, 205, 206, 2C2 AHU#6-1 960 525 2.50
V6-1-9 219, 219A AHU#6-1 1100 450 2.0
V6-1-10 238, 2C3 AHU#6-1 360 230 1.0
V6-1-11 202 AHU#6-1 640 400 1.75
V6-1-12 201 AHU#6-1 400 200 0.90
V6-1-13 220 AHU#6-1 930 430 1.75
V6-1-14 113, 113A AHU#6-1 630 325 1.50
V6-1-15 112 AHU#6-1 330 170 0.75
V6-1-16 111, 1C1 AHU#6-1 510 230 1.0
V6-1-17 108, 109, 110, 110A AHU#6-1 750 500 2.25
V6-1-18 114 AHU#6-1 420 230 1.0
V6-1-19 116 AHU#6-1 1000 400 1.75
V6-1-20 117, 118, 1C2 AHU#6-1 1160 450 1.75
V6-1-21 104, 105, 106 AHU#6-1 650 500 2.50
V6-1-22 119, 119A AHU#6-1 1150 450 1.75
V6-1-23 101, 1C3 AHU#6-1 870 550 2.25
V6-1-24 120 AHU#6-1 900 450 1.75
V6-1-25 122 AHU#6-1 300 170 0.75
V6-1-26 123 AHU#6-1 400 250 1.0
V6-1-27 14 AHU#6-1 370 370 2.0
V6-1-28 015, 016 AHU#6-1 350 230 1.0
V6-1-29 17 AHU#6-1 870 600 3.0
V6-1-30 18 AHU#6-1 930 550 2.5
V6-1-31 011, 012 AHU#6-1 220 220 1.25
V6-1-32 0C3, 008, 009, 010 AHU#6-1 1140 850 3.75
V6-1-33 020A AHU#6-1 460 340 1.50
V6-1-34 020B AHU#6-1 350 250 1.25
V6-1-35 020C AHU#6-1 220 170 0.75
V6-2-1 229, 229B AHU#6-2 2510 1350 6
V6-2-2 229A, 229C AHU#6-2 1080 500 2.25
V6-2-3 229D AHU#6-2 780 380 1.75
V6-2-4 228 AHU#6-2 950 390 1.75
V6-2-5 231, 232, 233, 234, 235 AHU#6-2 910 630 3
V6-2-6 227, 228A, 2C4 AHU#6-2 1110 500 2
V6-2-7 236 AHU#6-2 330 160 0.75
V6-2-8 237, 237A AHU#6-2 450 275 1.25
V6-2-9 225, 225A, 2C3 AHU#6-2 1310 475 2
V6-2-10 223 AHU#6-2 640 350 1.5
V6-2-11 222 AHU#6-2 430 150 0.5
V6-2-12 129, 129B AHU#6-2 2100 1160 4.5
V6-2-13 129A, 129C AHU#6-2 1020 450 2
V6-2-14 129D AHU#6-2 430 220 1
V6-2-15 129E AHU#6-2 300 170 0.75
V6-2-16 128 AHU#6-2 830 350 1.5
V6-2-17 126, 127, 1C5 AHU#6-2 1090 500 2
V6-2-18 131, 132, 133, 134, 135 AHU#6-2 800 550 2.5
V6-2-19 125, 125A, 1C3 AHU#6-2 1150 460 1.75
V6-2-20 136 AHU#6-2 340 225 1
V6-2-21 137, 137A AHU#6-2 430 210 1
V6-2-22 124 AHU#6-2 820 300 1.25
V6-2-23 004 AHU#6-2 380 310 1.5
V6-2-24 001 AHU#6-2 2100 1300 5.5
V6-2-25 005, 006, 0C3 AHU#6-2 940 700 3.25
V6-2-26 007 AHU#6-2 700 580 2.75
V6-2-27 001A AHU#6-2 300 210 1
V6-3-1 303 AHU#6-3 400 325 1.50
V6-3-2 304 AHU#6-3 400 325 1.50
V6-3-3 305 AHU#6-3 820 700 3.25
V6-3-4 309, 3C3 AHU#6-3 600 475 2.25
V6-3-5 310 AHU#6-3 300 250 1.10
V6-3-6 311 AHU#6-3 550 450 2.25
V6-3-7 300, 3C3 AHU#6-3 550 450 2.25
V6-3-8 301 AHU#6-3 500 400 2.0
V6-3-9 302 AHU#6-3 430 320 1.50
V6-3-10 306, 308 AHU#6-3 700 700 3.50
AIR HANDLING UNITS BALANCING SCHEDULE
LABEL AREA SERVED SUPPLY CFM OA CFM
COOLING
COIL GPM
PREHEAT
COIL LBS/HR
AHU#6-1
SOUTH SIDE OF BASEMENT,
1ST FLOOR, & 2ND FLOOR 24500 5000 148 570
AHU#6-2
NORTH SIDE OF BASEMENT,
1ST FLOOR, & 2ND FLOOR 24500 5000 148 570
AHU#6-3 3RD FLOOR 5250 790 30 -
FAN COIL UNITS BALANCING SCHEDULE
LABEL AREA SERVED AHU SERVED FAN CFM OA CFM
GPM
COOLING HEATING
FCU#6-1 BSMT SOUTH REAR ENTRY - 650 0 2.4 1.75
FCU#6-2 BSMT NORTH REAR ENTRY - 650 0 2.4 1.75
FCU#6-3 022 MECH SPACE - 650 0 2.4 1.75