36C25618U0323-0002006.pdf
PDF 3 MB Posted
- Attached to
- Services Commissioning for HVAC Digital Controls Federal contract opportunity
- Solicitation number
- 36C25618U0323
About this file
36C25618U0323 0002 Drawings - Building 4 (M4 Series).pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| -15380.docx | DOCX document | |
| 36C25618U0323-0002007.pdf | ||
| 36C25618U0323-0002005.pdf | ||
| 36C25618U0323-0002004.pdf | ||
| 36C25618U0323-0002012.pdf | ||
| 36C25618U0323-0002000.docx | DOCX document | |
| 36C25618U0323-0002013.pdf | ||
| 36C25618U0323-0002010.pdf | ||
| 36C25618U0323-0002002.pdf | ||
| 36C25618U0323-0002011.pdf | ||
| 36C25618U0323-0002009.pdf | ||
| 36C25618U0323-0002014.pdf | ||
| 36C25618U0323-0002001.docx | DOCX document | |
| 36C25618U0323-0002003.pdf | ||
| 36C25618U0323-0002008.pdf | ||
| 36C25618U0323-0001000.docx | DOCX document | |
| 36C25618U0323-002.pdf | ||
| 36C25618U0323-001.docx | DOCX document | |
| 36C25618U0323-000.docx | DOCX document |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELEV
ELEV.
CORRIDOR
1CC-4
DOCK
HALLWAY
108 109
1CN-4
107 106
105 2
1SN-4
104A
102D
102E
102F
102C 102B 102A
102G
101A
1CC-4
1SE-41201191181161SW-4
1C-2
DOCK
LOBBY
NEW LOADING
DOCK
LOADING
DOCK
STOR. STOR.
EQUIP
TOILET
MALE
LOCKERS
HANDICAP
TOILETSTOR.
TOILET
FEMALE
LOCKERS
CART
WASHSTOR.ELEC.
ELEC.
HVAC STOR. HVAC LOUNGE
CORRIDOR CORRIDOR
STOR.
VESTIBULE
CONFERENCE
CLASSROOM
OFFICEOFFICEOFFICE
OFFICE
OFFICE
STOR.
WORK
AREA
ELEC.
U360
EXIST HHW 4-P3
EXIST HHW 4-P4 EXIST 4-PH5
4-EF4
EXIST
4-EF1
EXIST
4-EF2
EXIST
4-EF3
EXIST CHW 4-P1
EXIST CHW 4-P2
EXIST VFD'S FOR
CHW PUMPS.
EXIST 4-C2
EXIST 4-C1
EXIST 4-FCU-A
EXIST 4-FCU-B
EXIST 4-FCU-H
EXIST 4-FCU-K
EXIST 4-FCU-J
EXIST 4-FCU-I
EXIST
4-FCU-G
EXIST
4-FCU-F
EXIST
4-FCU-CEXIST
4-FCU-D
EXIST
4-FCU-E
EXIST
4-RH1
EXIST 4-EF6
EXIST STEAM METER PANEL
EXIST DOMESTIC WATER METER PANEL
EXIST CHILLED WATER METER PANEL
EXIST JACE METER CONTROLLER
EXIST
4-AH5
EXIST DOMESTIC WATER
METER (16-502-4-PW-2).
EXIST CHILLED WATER METER
(16-502-4-CHW-1).
EXIST STEAM METER
(16-502-4-ST-1). EXIST STEAM METER
(16-502-4-ST-2).
EXIST DOMESTIC
WATER METER
(16-502-4-PW-1).
NOTES:
1. EXISTING DDC SYSTEM IS LOUISIANA CONTROLS.
REPLACE EQUIPMENT CONTROLLERS AND CONTROL
PANELS TO FULLY INTEGRATE TO SIEMENS CAMPUS
SYSTEM.
2. CONNECT EXISTING METERING TO CAMPUS DDC
CONTROL SYSTEM.
3. CONNECT NEW DDC CONTROLLERS TO EXISTING
ELECTRICAL SERVICE (TYP.)
ELEC PANEL SERVING
BLDG 4 (2 FEEDS),
BLDG 5, AND BLDG 6
(EXCEPT HVAC).
PROVIDE ELECTRICAL METERS FOR BLDG
4 (2 FEEDS), BLDG 5, AND BLDG 6 (EXCEPT
HVAC). PROVIDE NEW ELECTRICAL
METERS. CONTRACTOR SHALL PROVIDE
120V POWER CONNECTION TO NEW
ELECTRICAL METERS. CONTRACTOR
SHALL ROUTE TO NEAREST 120V PANEL
WITH SPARE CAPACITY, INSTALL NEW 20
A-1 POLE CIRCUIT BREAKER, & MAKE
CONNECTION. PROVIDE 20 A SWAP
SWITCH AT ELECTRICAL METERS FOR
DISCONNECT. CONTRACTOR TO VERIFY
120V PANEL LOCATION DURING PRE-BID
WALKTHROUGH.
EXIST
4-RH2
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
BASEMENT FLOOR PLAN -
MECHANICAL
4 --- NMT
M4-100 10-30-13
ELEV.
ELEV.
DRY FOOD
STORAGE
STORAGE
CORRIDOR
2CW-4
WORK SPACE
215 214 213
DRY
ELEC.
WORK SPACE THAW BOX
FREEZER
STORG
2SN-4
2CN-4
DISH
STORG
HAC
DISHWASHING
COOKS
COOLER
FREEZER
VEG/SALAD
PREP
DAIRY
COOLER
VEG/SALAD
COOLER
2CS-4
CORR.
2SW-4
FOOD PREP
COOKING
CORRIDOR
2CW-4
ICE AND
BEVERAGES
TRAY
ASSEMB.
AND CART
PARKING
OFFICE
DRY STOR.
CORRIDOR
2CE-4
2SE-4
EXIST
4-AHU1
ABOVE.
EXIST
4-AHU3
ABOVE.
EXIST
4-AHU4
ABOVE.
EXIST
4-AHU2
ABOVE.
FM
INSTALL AIRFLOW
METER IN EXISTING
50X20 RA DUCT.
INSTALL AIRFLOW
METER IN EXISTING
42X16 RA DUCT.
FM
NEW DDC TSTAT
INSTALLED IN
LOCATION OF EXIST.
TYP.
NOTES:
1. EXISTING DDC SYSTEM IS LOUISIANA CONTROLS.
REPLACE EQUIPMENT CONTROLLERS AND CONTROL
PANELS TO FULLY INTEGRATE TO SIEMENS CAMPUS
SYSTEM.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
1ST FLOOR PLAN - MECHANICAL
4 WLP NMT
M4-101
EXIST 4-AHU1
EXIST 4-AHU2
EXIST 4-AHU3
EXIST 4-AHU4
EXIST 4-EFK2
EXIST 4-EFK1
EXIST 4-SFK1
EXIST 4-EF5
VFD
INSTALL NEW 10HP VFD
RATED FOR EXTERIOR
INSTALLATION. CONNECT
TO FAN MOTOR, EXISTING
ELECTRICAL SUPPLY, AND
NEW CONTROLS.
VFD
INSTALL NEW 5HP VFD RATED
FOR EXTERIOR INSTALLATION.
CONNECT TO FAN MOTOR,
EXISTING ELECTRICAL SUPPLY,
AND NEW CONTROLS.
VFD
INSTALL NEW 10HP VFD
RATED FOR EXTERIOR
INSTALLATION. CONNECT
TO FAN MOTOR, EXISTING
ELECTRICAL SUPPLY, AND
NEW CONTROLS.
INSTALL NEW 10HP VFD
RATED FOR EXTERIOR
INSTALLATION. CONNECT
TO FAN MOTOR, EXISTING
ELECTRICAL SUPPLY, AND
NEW CONTROLS.
V F
D
EXIST 4-EFD1
NOTES:
1. EXISTING DDC SYSTEM IS LOUISIANA CONTROLS.
REPLACE EQUIPMENT CONTROLLERS AND CONTROL
PANELS TO FULLY INTEGRATE TO SIEMENS CAMPUS
SYSTEM.
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
ROOF FLOOR PLAN - MECHANICAL
4 WLP NMT
M4-102
F E
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
AI11
AI12
OUTSIDE AIR DAMPER (D-1)
RETURN AIR DAMPER (D-2)
SUPPLY FAN VFD STATUS
SUPPLY AIR TEMPERATURE SENSOR (T-5)
FLOWMETER CFM (F-2)
AI2
AI9
AI10
AI8
AI1
AI4
AI5
AI6
AI7
SPACE TEMPERATURE SENSOR (T-6)
SUPPLY
VFD
FAN
DO1
DI5
COIL
L P
S
V-2
NC
REHEAT
AI8
AO4
T
AI4
AO1
AI1
PANEL
DDC CONTROL
AI5
T-2
D-1
DI1
D-2
T-7
AI13
KEYNOTES:
EXISTING DDC DEVICE TO BE REUSED
IF FUNCTIONAL AND COMPATIBLE.
NEW DDC DEVICE TO BE INSTALLED.
COORDINATE EXACT LOCATION, SIZE,
TYPE, ETC. WITH EXISTING
CONDITIONS PRIOR TO PURCHASING.
FLOWMETER
H-1
H
AI7
T-4
T-1
C H
W R
COIL
CHW
V-1
NO
AI6
AO3
DPS-2
DI6
AI11
F-2
AIR
FILTER
SD-1
DI4
T-3
T
AI10
T-5
AI2
DI2
T-6T
AI12
SPACE
THERMOSTAT
AMBIENT AIR
TEMPERATURE
SENSOR
STEAM
SUPPLY AIR
OUTSIDE AIR
RETURN AIR
AI3
F-1
NO
NC
AI9
AO5
DPS-1
DI3
AIR
FILTER
FLOWMETER CFM (F-2)AI3
RETURN AIR RELATIVE HUMIDITY SENSOR (H-1)
MIXED AIR TEMPERATURE SENSOR (T-2)
CHILLED WATER CONTROL VALVE (V-1)
CHILLED WATER DISCHARGE AIR TEMPERATURE SENSOR (T-4)
STEAM REHEAT CONTROL VALVE (V-2)
FILTER STATUS (DPS-1)
DI1
LOW LIMIT TEMPERATURE SENSOR (T-3) STATUS
SUPPLY FAN STATUS
RETURN AIR SMOKE DETECTOR (SD-1) STATUS
DI2 HIGH LIMIT TEMPERATURE SENSOR (T-1) STATUS
DI3
DI4
DI5
DI6
AI13 AMBIENT AIR TEMPERATURE SENSOR (T-7)
FILTER STATUS (DPS-2)
DO1
AO5
AO4
AO1
AO2
AO3 CHILLED WATER CONTROL VALVE (V-1)
STEAM REHEAT CONTROL VALVE (V-2)
SUPPLY FAN VFD SPEED
OUTSIDE AIR DAMPER (D-1)
NOT USED
SUPPLY FAN START/STOP
T
TTT
4AHU-1 & 4AHU-3 CONTROL
SCHEMATIC & SEQUENCE
4 WLP NMT
M4-200
SEQUENCE OF OPERATION
1. GENERAL
1.1. AIR UNIT FAN TO BE STARTED AND STOPPED AS SCHEDULED BY THE ECC.
1.2. MIN. VFD SPEED SHALL BE 30% (ADJUSTABLE).
2. AIR FLOW
2.1. WHEN THE AIR UNIT FAN IS RUNNING, OUTSIDE AIR DAMPER, D-1, AND RETURN AIR DAMPER, D-2, WILL BE MODULATED TO MAINTAIN OUTSIDE AIR QUANTITY OF 900 CFM AS CALCULATED BY THE DIFFERENCE
IN RA CFM AND SA CFM AS MEASURED AT FLOWMETER F-1 & F-2, RESPECTIVELY.
2.2. D-1 AND D-2 WILL BE MODULATED TO MAINTAIN MIXED AIR TEMPERATURE AT A MIN. OF 38°F (ADJUSTABLE). IF THE RA CFM IS NOT SUFFICIENT TO MAINTAIN MAT MIN. AT REDUCED AIRFLOWS, THE
SUPPLY FAN VFD SHALL INCREASE TO MAINTAIN MIN. MAT SETPOINT. WHEN THE MIXED AIR
TEMPERATURE IS ABOVE 38°, THE DAMPERS WILL MODULATE TO MAINTAIN THE OUTSIDE AIR QUANTITY
AS BEFORE DESCRIBED. THE MIXED AIR TEMPERATURE IS TRANSMITTED BY T-2.
3. TEMPERATURE CONTROL
3.1. COOLING:
3.1.1. WHEN EITER OA OR RA DEWPOINT IS ABOVE 55°F CHILLED WATER VALVE, V-1, WILL BE MODULATED TO MAINTAIN CHILLED WATER COIL DISCHARGE AIR TEMPERATURE AT 55°F (ADJUSTABLE). SF VFD SHALL MODULATE TO MAINTAIN COOLING SPACE TEMPERATURE SETPOINT OF 74°F (ADJUSTABLE).
ONCE VFD IS AT MIN. SPEED STEAM REHEAT VALVE, V-2, SHALL BE MODULATED TO MAINTAIN
SPACE TEMPERATURE ABOVE HEATING SETPOINT. CHILLED WATER COIL DISCHARGE AIR
TEMPERATURE IS TRANSMITTED BY T-4 AND SPACE TEMPERATURE IS TRANSMITTED BY T-6.
3.1.2. WHEN BOTH OA AND RA DEWPOINT IS BELOW 56°F, SF VFD SHALL BE AT MIN. SPEED (30%) AND CHILLED WATER VALVE, V-1, SHALL BE MODULATED TO MAINTAIN SPACE TEMPERATURE SETPOINT.
ONCE CHILLED WATER VAVLE, V-1, IS 100% OPEN AND SPACE REQUIRES ADDITIONAL COOLING, SF
VFD SPEED SHALL INCREASE TO MAINTAIN SPACE TEMPERATURE SETPOINT.
3.2. HEATING: WHEN BOTH OA AND RA DEWPOINT IS BELOW 56°F, SF VFD SHALL BE AT MIN. SPEED AND STEAM REHEAT COIL VALVE, V-2, SHALL MODULATE TO MAINTAIN SPACE TMEPERATURE SETPOINT OF 68°F. ONCE STEAM REHEAT COIL VALVE, V-2 IS 100% OPEN, SF VFD SPEED SHALL INCREASE TO MAINTAIN SPACE TEMPERATURE SETPOINT. SUPPLY AIR SHALL BE LIMITED TO 95°F. SUPPLY AIR
TEMPERATURE IS TRANSMITTED BY T-5.
3.3. IF SPACE TEMPERATURE IS BETWEEN COOLING AND HEATING SPACE TEMPERATURE SETPOINT. VFD SHALL MAINTAIN MIN SPEED AND COOLING COIL VALVE, V-1, AND PREHEAT VALVE, V-2 SHALL REMAIN
CLOSED.
4. ALARMS
4.1. THE PRE-FILTER STATUS IS SENSED AT DPS-1 AND FINAL FILTER STATUS IS SENSED AT DPS-2. SHOULD THE DROP ACROSS THE FILTER EXCEED 1.5", THE SWITCH WILL CLOSE AND INITIATE AN ALARM TO THE
ECC.
4.2. THE UNIT AIR FAN WILL BE DE-ENERGIZED ON A RISE IN RETURN AIR TEMPERATURE ABOVE THE SETPOINT OF 85°F AS SENSED BY T-1, ON A DROP IN MIXED AIR TEMPERATURE BELOW THE SETPOINT
OF 35°F AS SENSED BY T-3, OR UPON DETECTION OF IONIZED PARTICLES BY SD-1.
4.3. A SEPARATE ALARM WILL BE INITIATED FOR EACH SAFETY. LIKEWISE, A SMOKE DETECTION ALARM WILL
INITIATED BY CONTRACT CLOSURE, TO THE FIRE ALARM SYSTEM PANEL.
4.4. WHEN THE AIR UNIT FAN IS DE-ENERGIZED FOR ANY REASON, THE AIR UNIT CONTROL VALVES AND
DAMPERS WILL RETURN TO THEIR NORMAL POSITIONS.
5. UNOCCUPIED MODE
5.1. DURING UNSCHEDULED PERIODS, THE AIR UNIT FAN WILL BE ENERGIZED SHOULD SPACE
TEMPERATURE EXCEED 80° (ADJUSTABLE), OR GO BELOW 60°F (ADJUSTABLE). ALL OPERATIONS WILL BE AS IN THE "OCCUPIED" MODE EXCEPT THE OUTSIDE AND RETURN DAMPERS WILL REMAIN IN THEIR
NORMAL POSITIONS. OUTSIDE AIR TEMPERATURE IS TRANSMITTED TO THE DCC BY T-7.
6. MORNING WARM-UP OR COOLDOWN
6.1. ONE HOUR PRIOR TO OCCUPANCY UNIT SHALL START IF SPACE TEMPERATURE IS ABOVE COOLING SETPOINT OR BELOW HEATING SETPOINT. ALL OPERATIONS WILL BE AS IN THE "OCCUPIED" MODE EXCEPT THAT OUTSIDE AIR AND RETURN AIR DAMPERS SHALL REMAIN IN THEIR NORMAL POSITIONS.
THIS ACTION SHALL BE LIMITED TO ONCE PER 24-HR PERIOD.
AIR HANDLING UNITS BALANCING SCHEDULE
LABEL AREA SERVED SUPPLY CFM OA CFM
COOLING COIL
GPM
PREHEAT
COIL
LBS/HR
REHEAT
COIL
LBS/HR
4-AH1 1ST FLOOR DISHWASH 4900 900 45 - 185
4-AH2 1ST FLOOR CARTWASH 6700 2990 64 - 289
4-AH3 1ST FLOOR OFFICE 3800 600 25 - 164
4-AH4 1ST FLOOR KITCHEN 6600 2990 65 - 249
4-AH5 BASEMENT 1700 1700 30 92 -
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
SUPPLY
VFD
FAN
DO1
DI5
COIL
L P
S V-2
NC
REHEAT
AI8
AO4
T
AI4
AO2AO1
AI1
PANEL
DDC CONTROL
AI5
T-2
D-1
DI1
D-2
H-1
H
AI7
T-4
T-1
C H
W R
COIL
CHW
V-1
NO
AI6
AO3
DPS-2
DI6
AI11
AIR
FILTER
SD-1
T
DI4
T-3
AI10
T-5
AI3 DI2
STEAM
SUPPLY AIR
OUTSIDE AIR
RETURN AIR
AI2
F-1
F-2
SUPPLY
FAN
DI7
KITCHEN HOOD
SEQUENCE OF OPERATION
1. GENERAL
1.1. AIR UNIT FAN TO BE STARTED AND STOPPED AS SCHEDULED BY THE ECC.
1.2. MIN VFD SPEED SHALL BE 30% (ADJUSTABLE).
1.3. OA CFM SHALL BE CALCULATED BY THE DIFFERENCE IN RA CFM AND SA CFM AS MEASURED BY F-1 &
F-2, RESPECTIVELY.
2. AIR FLOW
2.1. WHEN THE KITCHEN SUPPLY AIR FAN IS ENERGIZED AND THE AIR UNIT FAN IS RUNNING, OUTSIDE AIR DAMPER, D-1, AND RETURN AIR DAMPER, D-2, SHALL BE MODULATED TO MAINTAIN A MIN. OF 2990 CFM
OA AIRFLOW.
2.2. WHEN THE KITCHEN SUPPLY AND EXHAUST FANS ARE DE-ENERGIZED, D-1 AND D-2 WILL BE MODULATED
TO MAINTAIN A MINIMUM OF 15% OF THE SUPPLY AIRFLOW MEASURED AT F-2.
2.3. D-1 AND D-2 WILL BE MODULATED TO MAINTAIN MIXED AIR TEMPERATURE AT A MIN. OF 38°F (ADJUSTABLE). IF THE RA CFM IS NOT SUFFICIENT TO MAINTAIN MAT MIN. AT REDUCED AIRFLOWS, THE
SUPPLY FAN VFD SHALL INCREASE TO MAINTAIN MIN. MAT SETPOINT. WHEN THE MIXED AIR
TEMPERATURE IS ABOVE 38°, THE DAMPERS WILL MODULATE TO MAINTAIN THE OUTSIDE AIR QUANTITY
AS BEFORE DESCRIBED. THE MIXED AIR TEMPERATURE IS TRANSMITTED BY T-2.
3. TEMPERATURE CONTROL
3.1. COOLING:
3.1.1. WHEN EITER OA OR RA DEWPOINT IS ABOVE 55°F CHILLED WATER VALVE, V-1, WILL BE MODULATED TO MAINTAIN CHILLED WATER COIL DISCHARGE AIR TEMPERATURE AT 55°F (ADJUSTABLE). SF VFD SHALL MODULATE TO MAINTAIN COOLING SPACE TEMPERATURE SETPOINT OF 74°F (ADJUSTABLE).
ONCE VFD IS AT MIN. SPEED STEAM REHEAT VALVE, V-2, SHALL BE MODULATED TO MAINTAIN
SPACE TEMPERATURE ABOVE HEATING SETPOINT. CHILLED WATER COIL DISCHARGE AIR
TEMPERATURE IS TRANSMITTED BY T-4 AND SPACE TEMPERATURE IS TRANSMITTED BY T-6.
3.1.2. WHEN BOTH OA AND RA DEWPOINT IS BELOW 56°F, SF VFD SHALL BE AT MIN. SPEED (30%) AND CHILLED WATER VALVE, V-1, SHALL BE MODULATED TO MAINTAIN SPACE TEMPERATURE SETPOINT.
ONCE CHILLED WATER VAVLE, V-1, IS 100% OPEN AND SPACE REQUIRES ADDITIONAL COOLING, SF
VFD SPEED SHALL INCREASE TO MAINTAIN SPACE TEMPERATURE SETPOINT.
3.2. HEATING: WHEN BOTH OA AND RA DEWPOINT IS BELOW 56°F, SF VFD SHALL BE AT MIN. SPEED AND STEAM REHEAT COIL VALVE, V-2, SHALL MODULATE TO MAINTAIN SPACE TMEPERATURE SETPOINT OF 68°F. ONCE STEAM REHEAT COIL VALVE, V-2 IS 100% OPEN, SF VFD SPEED SHALL INCREASE TO MAINTAIN SPACE TEMPERATURE SETPOINT. SUPPLY AIR SHALL BE LIMITED TO 95°F. SUPPLY AIR
TEMPERATURE IS TRANSMITTED BY T-5.
3.3. IF SPACE TEMPERATURE IS BETWEEN COOLING AND HEATING SPACE TEMPERATURE SETPOINT. VFD SHALL MAINTAIN MIN SPEED AND COOLING COIL VALVE, V-1, AND PREHEAT VALVE, V-2 SHALL REMAIN
CLOSED.
4. ALARMS
4.1. THE PRE-FILTER AND FINAL FILTER STATUS IS SENSED AT DPS-1 & DPS-2, RESPECTIVELY. SHOULD THE DROP ACROSS THE FILTER EXCEED 1.5", THE SWITCH WILL CLOSE AND INITIATE AN ALARM TO THE ECC.
4.2. THE UNIT AIR FAN WILL BE DE-ENERGIZED ON A RISE IN RETURN AIR TEMPERATURE ABOVE THE SETPOINT OF 85°F AS SENSED BY T-1, ON A DROP IN MIXED AIR TEMPERATURE BELOW THE SETPOINT
OF 35°F AS SENSED BY T-3, OR UPON DETECTION OF IONIZED PARTICLES BY SD-1.
4.3. A SEPARATE ALARM WILL BE INITIATED FOR EACH SAFETY. LIKEWISE, A SMOKE DETECTION ALARM WILL
INITIATED BY CONTRACT CLOSURE, TO THE FIRE ALARM SYSTEM PANEL.
4.4. WHEN THE AIR UNIT FAN IS DE-ENERGIZED FOR ANY REASON, THE AIR UNIT CONTROL VALVES AND
DAMPERS WILL RETURN TO THEIR NORMAL POSITIONS.
5. UNOCCUPIED MODE
5.1. DURING UNSCHEDULED PERIODS, THE AIR UNIT FAN WILL BE ENERGIZED SHOULD SPACE
TEMPERATURE EXCEED 80° (ADJUSTABLE), OR GO BELOW 60°F (ADJUSTABLE). ALL OPERATIONS WILL BE AS IN THE "OCCUPIED" MODE EXCEPT THE OUTSIDE AND RETURN DAMPERS WILL REMAIN IN THEIR
NORMAL POSITIONS. OUTSIDE AIR TEMPERATURE IS TRANSMITTED TO THE DCC BY T-7.
6. MORNING WARM-UP OR COOLDOWN
6.1. ONE HOUR PRIOR TO OCCUPANCY UNIT SHALL START IF SPACE TEMPERATURE IS ABOVE COOLING SETPOINT OR BELOW HEATING SETPOINT. ALL OPERATIONS WILL BE AS IN THE "OCCUPIED" MODE EXCEPT THAT OUTSIDE AIR AND RETURN AIR DAMPERS SHALL REMAIN IN THEIR NORMAL POSITIONS.
THIS ACTION SHALL BE LIMITED TO ONCE PER 24-HR PERIOD.
DPS-1
DI3
AIR
FILTER
KEYNOTES:
EXISTING DDC DEVICE TO BE REUSED IF FUNCTIONAL AND
COMPATIBLE.
NEW DDC DEVICE TO BE INSTALLED. COORDINATE EXACT
LOCATION, SIZE, TYPE, ETC. WITH EXISTING CONDITIONS PRIOR
TO PURCHASING.
KITCHEN FANS ARE TERMINATED IN 4-AHU2 PANEL. EXTEND
SIGNAL TO 4-AHU4.
1 2
AI9
AO5
EXHAUST
FAN-1
KITCHEN HOOD
DI8 DI9
EXHAUST
FAN-2
KITCHEN HOOD
T-7
AI13
T-6T
AI12
SPACE
THERMOSTAT
AMBIENT AIR
TEMPERATURE
SENSOR
T
AI11
AI12
OUTSIDE AIR DAMPER (D-1)
RETURN AIR DAMPER (D-2)
SUPPLY FAN VFD STATUS
SUPPLY AIR TEMPERATURE SENSOR (T-5)
SUPPLY AIR FLOWMETER (F-2)
AI2
AI9
AI10
AI8
AI1
AI4
AI5
AI6
AI7
SPACE TEMPERATURE SENSOR (T-6)
RETURN AIR RELATIVE HUMIDITY SENSOR (H-1)AI3
RETURN AIR FLOWMETER (F-1)
MIXED AIR TEMPERATURE SENSOR (T-2)
CHILLED WATER CONTROL VALVE (V-1)
CHILLED WATER DISCHARGE AIR TEMPERATURE SENSOR (T-4)
STEAM REHEAT CONTROL VALVE (V-2)
FILTER STATUS (DPS-1)
DI1
LOW LIMIT TEMPERATURE SENSOR (T-3) STATUS
SUPPLY FAN STATUS
RETURN AIR SMOKE DETECTOR (SD-1) STATUS
DI2 HIGH LIMIT TEMPERATURE SENSOR (T-1) STATUS
DI3
DI4
DI5
DI6
AI13 AMBIENT AIR TEMPERATURE SENSOR (T-6)
AIR FILTER STATUS (DPS-6)
KITCHEN HOOD EXHAUST FAN-2 STATUS
KITCHEN HOOD EXHAUST FAN-1 STATUS
DI9
DI8
DI7 KITCHEN HOOD SUPPLY FAN STATUS
DO1
AO5
AO4
AO1
AO2
AO3 CHILLED WATER CONTROL VALVE (V-1)
STEAM REHEAT CONTROL VALVE (V-2)
SUPPLY FAN VFD SPEED
OUTSIDE AIR DAMPER (D-1)
NOT USED
SUPPLY FAN START/STOP
T T
4AHU-2 & 4AHU-4 CONTROL
SCHEMATIC & SEQUENCE
4 WLP NMT
M4-201
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
OUTSIDE AIR TEMPERATURE SENSOR (T-1)
DUCT STEAM REHEAT CONTROL VALVE (V-1)
SUPPLY AIR SMOKE DETECTOR (SD-1) STATUS
AIR FILTER STATUS (DPS-2)
AI2
AI1
CHILLED WATER CONTROL VALVE (V-2)AI3
OUTSIDE AIR DAMPER (D-1) STATUS
AIR FILTER STATUS (DPS-1)
FREEZESTAT (T-2)
SUPPLY FAN STATUS
NOT USED
SUPPLY
STR
FAN
DO2
DI4
COIL
L P
S
V-1
NC
PREHEAT
AI2
AO1 DO1
DI1
PANEL
DDC CONTROL
T
AI1
T-1
D-1
DI6
C H
W R
COIL
CHW
V-2
NO
AI3
AO2
DPS-2
DI7
AIR
FILTER
DI3
T-2
T-3
STEAM
OUTSIDE AIR
SD-1
NC
AI5
TO REHEAT
COILS AND
FAN COIL
UNITS
SEQUENCE OF OPERATION
1. GENERAL
1.1. AIR UNIT FAN TO BE STARTED AND STOPPED AS SCHEDULED BY THE ECC.
2. AIR FLOW
2.1. WHEN THE AIR UNIT FAN IS RUNNING, OUTSIDE AIR DAMPER, D-1 WILL OPEN 100%.
3. TEMPERATURE CONTROL
3.1. THE PREHEAT COIL DISCHARGE TEMPERATURE SETPOINT SHALL BE 45°F AS MEASURED BY T-4 AND
MAINTAINED BY MODULATING STEAM PREHEAT VAVLE, V-1.
3.2. WHEN THE OUTSIDE DEWPOINT TEMPERATURE IS ABOVE 55°F, CHILLED WATER VALVE, V-1, WILL BE MODULATED TO MAINTAIN SUPPLY AIR TEMPERATURE OF 55°F AS TRANSMITTED BY T-3. THE OUTSIDE
AIR TEMPERATURE IS TRANSMITTED BY T-1.
3.3. WHEN THE OUTSIDE AIR DEWPOINT TEMPERATURE IS BELOW 55°F, CHILLED WATER VALVE, V-1, WILL BE MODULATED TO MAINTAIN SUPPLY AIR TEMPERATURE SETPOINT OF 75°F SUPPLY AIR TEMPERATURE IS
TRANSMITTED BY T-3. THE OUTSIDE AIR TEMPERATURE IS TRANSMITTED BY T-1.
4. ALARMS
4.1. THE UNIT AIR FAN WILL BE DE-ENERGIZED ON A DROP IN COOLING COIL ENTERING AIR TEMPERATURE
BELOW THE 35°F SETPOINT OF T-2 OR UPON DETECTION OF IONIZED PARTICLES BY SD-1.
4.2. A SEPARATE ALARM WILL BE INITIATED FOR EACH SAFETY. LIKEWISE, A SMOKE DETECTION ALARM WILL
INITIATED BY CONTRACT CLOSURE, TO THE FIRE ALARM SYSTEM PANEL.
4.3. THE PRE-FILTER AND FINAL FILTER STATUS IS SENSED AT DPS-1 & DPS-2, RESPECTIVELY. SHOULD THE DROP ACROSS THE FILTER EXCEED 1.5", THE SWITCH WILL CLOSE AND INITIATE AN ALARM TO THE ECC.
4.4. WHEN THE AIR UNIT FAN IS DE-ENERGIZED FOR ANY REASON, THE AIR UNIT CONTROL VALVES AND
DAMPERS WILL RETURN TO THEIR NORMAL POSITIONS.
5. UNOCCUPIED MODE
5.1. DURING UNSCHEDULED PERIODS, THE AIR UNIT FAN WILL BE DE-ENERGIZED AND ALL CONTROLS AND CONTROL VALVES WILL RETURN TO THEIR NORMAL POSITIONS AND THE OUTSIDE AIR DAMPER WILL BE
CLOSED.
DUCT
DPS-1
DI2
KEYNOTES:
EXISTING DDC DEVICE TO BE REUSED IF
FUNCTIONAL AND COMPATIBLE.
NEW DDC DEVICE TO BE INSTALLED.
COORDINATE EXACT LOCATION, SIZE, TYPE, ETC.
WITH EXISTING CONDITIONS PRIOR TO
PURCHASING.
1 1
T T
DI1
DI2
DI3
DI4
DI5
DI6
DI7
AO1
AO2
DO1 OUTSIDE AIR DAMPER (D-1)
DUCT STEAM PREHEAT CONTROL VALVE (V-1)
CHILLED WATER CONTROL VALVE (V-2)
DO2 SUPPLY FAN START/STOP
4AHU-5 CONTROL SCHEMATIC
& SEQUENCE
4 WLP NMT
M4-202
H
AI4
H-1
OUTSIDE AIR HUMIDITY (H-1)AI4
AI5 SUPPLY FAN TEMPERATURE SENSOR (T-3)
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
VFD
CAMPUS CHWS
CHWS
SEQUENCE OF OPERATION
1. GENERAL
1.1. THE ECC WILL ENERGIZE THE SCHEDULED CHILLED WATER PUMP WHEN ANY AIR UNIT OR FAN COIL
CALLS FOR COOLING. THE SELECTED PUMP VFD WILL BE ENABLED WITH STATUS OF THE PUMP
TRANSMITTED BY CONTACT CLOSURE IN THE VFD.
1.2. THE DRIVE SPEED WILL BE MODULATED TO MAINTAIN DIFFERENTIAL PRESSURE IN THE SYSTEM AT SETPOINT. STATIC PRESSURE SETPOINT SHALL BE RESET BASED ON CHILLED WATER VALUE POSITION TO MINIMIZE PUMP SPEED. SYSTEM PRESSURE IS SENSED AT THE SPECIFIED LOCATION ON THE FIRST FLOOR IN THE DISHWASHING EQUIPMENT AREA. THIS PRESSURE IS SENSED AT THAT LOCATION AND
TRANSMITTED TO THE ECC BY THE SPECIFIC TRANSMITTER IN 4-AHU-01 CONTROL PANEL.
1.3. THE CHILLED WATER PUMPS WILL BE ALTERNATED ON A WEEKLY (ADJUSTABLE) SCHEDULE.
1.4. WHEN ENABLED, THE LEAD PUMP SHALL BE STARTED. IF THE PUMP STATUS DOES NOT MATCH THE COMMAND, AN ALARM SHALL BE GENERATED AND THE PUMP SHALL BE STOPPED. THE LAG PUMP SHALL
AUTOMATICALLY START.
CHWS
SENSOR (TYP)
(N.C.)
CONTROL VALVE
TEMPERATURE
STR1
STEAM CONVERTER
TO COND.
PUMP
PUMP
TO COND.
FROM BLDG
FROM
CAMPUS
STEAM
FROM
CAMPUS
STEAM
(N.C.)
CONTROL VALVE
TO BLDG
FS
(TYP)
FLOW SWITCH
180 160 140
HOT WATER SETPOINT
(DEG F)
OUTDOOR
AIR
TEMPERATURE
(DEG F)
HEATING HOT WATER RESET SCHEDULE SEQUENCE OF OPERATION
1. START/STOP CONTROLS - THE HEATING SYSTEM SHALL AUTOMATICALLY START WHEN ANY
TERMINAL UNIT CALLS FOR HEAT.
1.1. WHEN THE SYSTEM IS "ON":
1.1.1. STEAM CONTROL VALVES SHALL MODULATE TO MAINTAIN THE HOT WATER
SUPPLY TEMPERATURE AT SETPOINT.
1.1.2. THE HOT WATER SUPPLY TEMPERATURE RESETS INVERSELY WITH THE OUTDOOR
TEMPERATURE AS SCHEDULED: AT 30°F OA, HWS TEMPERATURE AT 180°F, AT 70°F
(AND ABOVE) OA, HWS TEMPERATURE AT 140°F.
1.1.3. STEAM HOT WATER CONVERTERS, 4-HX1 & 4-HX2, ARE 100% REDUNDANT AND
ONLY ONE UNIT AT A TIME SHALL OPERATE.
1.2. WHEN NO TERMINAL UNIT IS CALLING FOR HEAT THE SYSTEM IS "OFF", THE HEATING
SHALL BE DISABLED.
2. HEAT EXCHANGER CONTROL
2.1. ONCE FLOW IS PROVEN BY THE RESPECTIVE FLOW SWITCH, THE STEAM INLET VALVE
WILL MODULATE TO MAINTAIN THE DESIRED HOT WATER SUPPLY TEMPERATURE TO
SETPOINT AS RESET BY THE OUTDOOR AIR TEMPERATURE.
3. HOT WATER PUMP CONTROL
3.1. WHEN ENABLED, THE LEAD PUMP SHALL BE STARTED. IF THE PUMP STATUS DOES NOT
MATCH THE COMMAND, AN ALARM SHALL BE GENERATED AND THE PUMP SHALL BE
STOPPED. THE LAG PUMP SHALL AUTOMATICALLY START.
3.2. PUMPS SHALL SWITCH LEAD/LAG STATUS ON A WEEKLY BASIS (ADJUSTABLE).
STR
STEAM CONVERTER
FS
T
DI1
DI2
AI1
DI3
DO1
DI4
DO2
SUPPLY STEAM TEMPERATURE SENSOR
STEAM CONVERTER (4-C-2) FLOW SWITCH STATUS
HOT WATER PUMP (4-HWP-3) START/STOP
HOT WATER PUMP (4-HWP-4) START/STOP
DI1
AI1
STEAM CONVERTER (4-C-1) FLOW SWITCH STATUSDI2
HOT WATER PUMP (4-HWP-3) STATUS
HOT WATER PUMP (4-HWP-4) STATUS
STEAM CONVERTER (4-C-2) CONTROL VALVE
STEAM CONVERTER (4-C-1) CONTROL VALVE
DI3
DI4
AO1
A02
DO1
DO2
AI1
DO1
DI1
AO1
AI2
DO2
DI2
AO2
AI3
VFD
DIFFERENTIAL PRESSURE SENSOR
CHILLED WATER PUMP (4-P1) VFD STATUS
CHILLED WATER PUMP (4-P1) START/STOP
CHILLED WATER PUMP (4-P2) START/STOP
AI2
AI1
CHILLED WATER PUMP (4-P2) VFD STATUSAI3
CHILLED WATER PUMP (4-P1) STATUS
CHILLED WATER PUMP (4-P2) STATUS
CHILLED WATER PUMP (4-P1) VFD SPEED
CHILLED WATER PUMP (4-P2) VFD STATUS
DI1
DI2
AO1
A02
DO1
DO2
HEATING HOT WATER & SCHW
SYSTEMS CONTROL SCHEMATICS
& SEQUENCES
4 WLP NMT
M4-203
KEYNOTES:
EXISTING DEVICE TO BE REUSED IF
FUNCTIONAL AND COMPATIBLE.
ADD DEVICE.
NOTES:
1. ALL EXISTING CONTROL DEVICES ARE
DDC. SENSORS AND VFD CAN BE REUSED
IF FUNCTIONAL AND COMPATIBLE.
2. DDC CONTROLLER TO BE REPLACED.
CONNECT NEW CONTROLLER TO
EXISTING ELECTRICAL SERVICE.
AO1
AO2
NOTES:
1. DDC CONTROLLER TO BE REPLACED.
P
D C
B G
Alexandria, Louisiana
A&E Design - Upgrade Energy Management Control Systems
October 30, 2013
VA256-12-C-0253
VETERANS HEALTH CARE
SYSTEM
Alexandria, LA
A
U.S. Department of Veterans Affairs
PANEL
DDC CONTROL
H W
R
V-1
NC
COIL
HTG
NO
NOTES:
1. EXISTING HOT WATER VALVE TO
REMAIN. REPLACE TWO POSITION
VALVE ACTUATOR WITH
MODULATING ACTUATOR.
2. REPLACE CONTROLLER AND SPACE
TEMPERATURE SENSOR.
3. REHEAT COIL 4RH-1 IS TYPICAL FOR
4RH-2.
AO1
AI1
PANEL
DDC CONTROL
NOTES:
1. EXISTING HOT WATER VALVE AND
CHILLED WATER VALVE TO REMAIN.
REPLACE TWO POSITION VALVE
ACTUATORS WITH MODULATING
ACTUATORS.
2. REPLACE CONTROLLER AND SPACE
TEMPERATURE SENSOR.
3. FAN COIL UNIT "A" IS TYPICAL OF "B"
TO "K".
C H
W R
COIL
CHW SUPPLY
FAN COIL
HTG
H W
R
TO SUPPLY
FROM B-4
AHU-05
TO SUPPLY
FROM B-4
AHU-05
AO1
AI1
DO1
DI1
AO2
AI2
SEQUENCE OF OPERATION
1. GENERAL
1.1 WHEN AIR UNIT 4-AHU-05 IS ENERGIZED, THE REHEAT CONTROLS WILL BE
ENABLED. THE REHEAT VALVE, V-1, WILL BE MODULATED TO MAINTAIN SPACE
TEMPERATURE AT ROOM TEMPERATURE SENSOR SETPOINTS.
1.2 WHEN 4-AHU-05 IS DE-ENERGIZED, THE REHEAT CONTROLS WILL BE DISABLED.
SEQUENCE OF OPERATION
1. GENERAL
1.1. WHEN AIR UNIT 4-AHU-05 IS ENERGIZED, THE FAN COIL UNIT WILL BE
ENERGIZED. WITH THE FAN COIL UNIT RUNNING, CHILLED WATER VALVE, V-1,
AND HOT WATER VALVE, V-2, WILL BE MODULATED, IN SEQUENCE, TO
MAINTAIN SPACE TEMPERATURE AT THE ROOM TEMPERATURE SETPOINT.
1.2. WHEN 4-AHU-05 IS DE-ENERGIZED, THE FAN COIL UNIT WILL BE DE-ENERGIZED
AND ALL CONTROL VALVES WILL BE CLOSED TO THEIR RESPECTIVE COILS.
T-1T
AI2
SPACE
TEMPERATURE
SENSOR
HOT WATER CONTROL VALVE (V-1)
SPACE TEMPERATURE SENSOR (T-1)AI2
AI1
CHILLED WATER CONTROL VALVE (V-1)
HOT WATER CONTROL VALVE (V-2)AI2
AI1
SUPPLY FAN STATUSDI1
V-2
NCNO
V-1
NO
AO1
A02
SUPPLY FAN START/STOPDO1
CHILLED WATER CONTROL VALVE (V-1)
HEAT HOT WATER CONTROL VALVE (V-2)
HOT WATER CONTROL VALVE (V-1)AO1
REHEAT COIL (TYP.), FAN COIL UNIT
(TYP.) & EXHAUST FANS CONTROL
SCHEMATICS & SEQUENCES
4 WLP NMT
M4-204
PANEL
DDC CONTROL
EXHAUST
FAN
DO1
DI1
T-1T
AI1
SPACE
TEMPERATURE
SENSOR
SEQUENCE OF OPERATION
1. GENERAL
1.1 FAN SHALL BE ENERGIZED WHEN SPACE TEMPERATURE IS ABOVE
SETPOINT.
1.2 ALARM SHALL BE GENERATED IF FAN STATUS DOES NOT MATCH FAN
COMMAND.
PANEL
DDC CONTROL
EXHAUST
FAN
DO1
DI1
SEQUENCE OF OPERATION
1. GENERAL
1.1 FAN SHALL BE ENERGIZED WHEN BUILDING IS OCCUPIED.
1.2 ALARM SHALL BE GENERATED IF FAN STATUS DOES NOT MATCH FAN
COMMAND.
PANEL
DDC CONTROL
DI1
SEQUENCE OF OPERATION
1. GENERAL
1.1 FAN IS ENERGIZED FROM DISHWASHER. FAN
STATUS SHALL BE COMMUNICATED TO THE
ECC.
EXHAUST FAN STATUSDI1
EXHAUST FAN START/STOPDO1
SPACE TEMPERATURE SENSOR (T-1)AI1
EXHAUST FAN STATUSDI1
EXHAUST FAN START/STOPDO1
EXHAUST FAN STATUSDI1
NOTES:
1. DDC CONTROLLER TO BE REPLACED.
NOTES:
1. DDC CONTROLLER TO BE REPLACED.
CONNECT NEW CONTROLLER TO
EXISTING ELECTRICAL SERVICE.
NOTES:
1. DDC CONTROLLER TO BE REPLACED.
CONNECT NEW CONTROLLER TO
EXISTING ELECTRICAL SERVICE.
EXHAUST
FAN
HOT WATER HEATING COIL BALANCING SCHEDULE
LABEL SERVES AHU SERVED CFM HEATING GPM
4-RH1 104A MALE LOCKERS 4-AHU5 500 2.2
4-RH2 103 STOR. 4-AHU5 500 0.8
FOUR PIPE FAN COIL UNITS BALANCING SCHEDULE
LABEL AREA SERVED AHU SERVED FAN CFM OA CFM
GPM
COOLING HEATING
A 120 LOUNGE 4-AH5 300 40 1.4 0.5
B 102 WORK AREA 4-AH5 600 40 3.0 0.5
C 102C OFFICE 4-AH5 300 20 1.4 0.5
D 102E OFFICE 4-AH5 200 20 0.9 0.5
E 102D OFFICE 4-AH5 300 20 1.4 0.5
F 102B OFFICE 4-AH5 300 20 1.4 0.5
G 102A OFFICE 4-AH5 200 20 0.9 0.5
H VESTIBULE 4-AH5 800 190 3.6 1.0
I 101 CONFERENCE CLASSROOM 4-AH5 600 190 3.6 1.0
J 101 CONFERENCE CLASSROOM 4-AH5 800 190 3.6 1.0
K 101 CONFERENCE CLASSROOM 4-AH5 800 190 3.6 1.0