This is a Test and Balance Report prepared by G Squared Solutions, Inc., dated December 26-27, 2024, documenting a preconstruction air audit for the Marion VA air handler replacement project in Building 1. The report evaluates three systems: AHU-03 (supply air handler), RF-03 (return air fan), and the existing ICU AHU, providing detailed measurements, equipment specifications, and operational findings for the design team and contractor.
The report identifies several critical deficiencies requiring correction before construction: AHU-03's supply fan VFD has been bypassed and operates at constant 60 Hz instead of variable speed control; part of the final filter bank in AHU-03 is missing, which will artificially reduce measured pressure differentials; and outside air dampers appear nearly closed, with only 1,907 CFM of 13,273 CFM supply air being outside air. Testing data includes AHU-03 supply airflow of 13,273 CFM, RF-03 return airflow of 11,366 CFM, and the existing ICU AHU providing 1,698 CFM outside air with filters in poor condition. Equipment details document a York air handler with 30 HP Siemens motor, Grundfos and Bell & Gossett hydronic pumps for ICU reheat service, and various filter configurations. The report includes velocity matrices, static pressure profiles, traverse data, equipment nameplate information, and manufacturer specifications necessary for balancing and commissioning the new air handler units.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
G Squared Solutions, Inc.
Test and Balance Report Marion VA – Replace Air Handler Units in Building 1 – AHU-03 Preconstruction Air Audit
Clint Walker G Squared Solutions, Inc.
12/26/2024
General Project Information
Project Name/Location: Marion VA – Replace Air Handlers in Building 1 Preconstruction Air Audit of AHU-03 Marion, Illinois 62959
Architect/Engineer: Toland Mizell Molnar 590 Means Street NW; Suite 200 Atlanta, Georgia 30318
Test & Balance Firm: G2 Solutions, Inc.
9090 Highway 13 West Carrier Mills, IL 62917
Test & Balance Supervisor Contact: Clint Walker (618) 926 0324 clint.gsquared@gmail.com TABB Certified Contractor # TB0476810C TABB Certified Supervisor # TB1071596S TABB Certified Technician #BB1071596T mailto:clint.gsquared@gmail.com
Table of Contents
PROJECT:
LOCATION:
Marion VA - Replace Air Handlers in Building 1 - Pre-Test Marion, IL
DATE:
CONTACT:
AUTHOR:
12/27/2024 Clint Walker Clint Walker
1 AHU03 Notes.pdf 2 AHU03 SF VFD1.pdf 3 AHU03 SF VFD2.pdf 4 AHU03 Missing Final Filter Section.pdf 5 Air Handling Unit
5.1 AHU-03
5.2 AHU-03/SPP-01
G Squared Solutions Inc.
AHU-03 Air Audit Notes
1. The supply fan VFD was not operating correctly. The supply fan has been wired around the VFD drive and is operating at a constant speed of 60 Hertz. Please see the attached picture.
2. A velocity matrix was performed at the discharge side of the cooling coil to determine the
Supply Fan CFM. The results are as follows.
3. Part of the final filter bank located inside the unit were not installed. Please see attached picture.
4. Return air is provided by RF-03. A traverse of the return air duct was completed in the penthouse. Those results are included in the RF-03 section of this report. The average reading of that process was 11,366 CFM. The outside air for AHU-03 was determined by subtracting 11,366 CFM of return air from 13,273 CFM of supply air. This equates to 1,907 CFM of outside air. The outside air dampers appeared to be almost closed.
AHU-03 Cooling Coil Velocity Matrix Readings (FPM) 498 438 450 449 431 486 511 418 466 474 525 477 523 363 468 455 513 457 530 442 457 491 462 468
Length 84.5" Avg. FPM 469 Height 48.25" Avg. CFM 13273
Area Ft.2 28.3
Air Handling Unit
PROJECT:
LOCATION:
Marion VA - Replace Air Handlers in Building 1 - Pre-Test Marion, IL
DATE:
CONTACT:
AUTHOR:
12/27/2024 Clint Walker Clint Walker
SYSTEM/UNIT: AHU-03
Unit Data Unit Manufacturer York Unit Model Number Covered in Insulation Spray Unit Serial Number Covered in Insulation Spray Unit Discharge Horizontal
AHU-03/Final Filter Bank Filter Type 95% Rigid Box Filter Qty - S1 8 Filter Size - S1 24x24x12
AHU-03/Pre-Filter Bank Filter Type Pleated Box Filter Qty - S1 12 Filter Size - S1 16x25x4 Filter Qty - S2 4 Filer Size - S2 16x20x4
Test Data Actual Airflow 13273 CFM Actual Outside Airflow 1907 CFM Actual Return Airflow 11366 CFM
AHU-03/Supply Fan Motor Volts T1-T2 494 Volts Motor Volts T2-T3 495 Volts Motor Volts T1-T3 496 Volts Motor Amps T1 34.70 Amps Motor Amps T2 24.80 Amps Motor Amps T3 25.40 Amps
Motor Data AHU-03/Supply Fan
Motor Manufacturer Siemens Motor Frame 286T Motor HP 30 HP Motor RPM 1775 RPM Motor Rated Volts 460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 35 Amps Motor Service Factor 1.15
Sheave Data AHU-03/Supply Fan
Number of Belts 3
PROJECT:
LOCATION:
Marion VA - Replace Air Handlers in Building 1 - Pre-Test Marion, IL
DATE:
CONTACT:
AUTHOR:
12/27/2024 Clint Walker Clint Walker
SYSTEM/UNIT: AHU-03/SPP-01
Log: AHU-03/SPP-01 12/26/2024 Clint Walker The last “Final Filter” is the filter box located on the roof outside of the penthouse. I did not see anyway to access this as it is all insulated. I utilized an existing hole that had been drilled on the discharge side of the filter section.
AHU-03/SPP-01 12/26/2024 Clint Walker The pressure drop across the heating coil actually represents the drop across the heating coil and the cooling coil as they are located back to back.
AHU-03/SPP-01 12/26/2024 Clint Walker There are some final filters missing from the final filter section. I have to assume the pressure differential would have been higher if they are all in place. I have included a picture in the deficiencies section of this report.
Test Pressures Final Filter 2 SP In 3.89 in. w.c.
Final Filter 2 SP Out 2.86 in. w.c.
Final Filter SP In -1.75 in. w.c.
Final Filter SP Out -1.77 in. w.c.
Heating Coil SP In -1.77 in. w.c.
Heating Coil SP Out -2.38 in. w.c.
Pre Filter SP In -1.67 in. w.c.
Pre Filter SP Out -1.75 in. w.c.
Supply Fan SP In -2.38 in. w.c.
Supply Fan SP Out 3.89 in. w.c.
Static Pressure Profile
LOCATION:
Marion VA - Replace Air Handlers in Building 1 - Pre-Test Marion, IL
DATE:
CONTACT:
AUTHOR:
12/27/2024 Clint Walker Clint Walker
1 RF03 Notes.pdf 2 Fan Unit
2.1 RF-03
2.2 RF-03/SPP-01
2.3 RF-03/Duct-01
RF-03 Air Audit Notes
1. RF-03 provides the return air for AHU-03.
2. A traverse of the return duct located in the penthouse was completed. The results are included in the report following this notes section.
3. The VFD was operating in Hand at 50 Hertz. The final readings were recorded at this speed.
Fan Unit
PROJECT:
LOCATION:
Marion VA - Replace Air Handlers in Building 1 - Pre-Test Marion, IL
DATE:
CONTACT:
AUTHOR:
12/27/2024 Clint Walker Clint Walker
SYSTEM/UNIT: RF-03
Log: RF-03 12/26/2024 Clint Walker Final readings were recorded at 50 Hertz.
Unit Data Fan Manufacturer Peerless-Winsmith, Inc Fan Model Number 300L
Fan Serial Number Order # LA6732 Part # 100-30 -0037-5
Test Data Actual Airflow 11366 CFM T1-T2 Volts 383.00 Volts T1-T3 Volts 383.00 Volts T2-T3 Volts 384.00 Volts Motor Amps T1 5.70 Amps Motor Amps T2 5.70 Amps Motor Amps T3 5.60 Amps
Motor Data Rated Airflow Capacity 10000 CFM
PROJECT:
LOCATION:
Marion VA - Replace Air Handlers in Building 1 - Pre-Test Marion, IL
DATE:
CONTACT:
AUTHOR:
12/27/2024 Clint Walker Clint Walker
SYSTEM/UNIT: RF-03/SPP-01
Test Pressures Return Fan SP In -1.12 in. w.c.
Return Fan SP Out -0.68 in. w.c.
Static Pressure Profile
PROJECT:
LOCATION:
Marion VA - Replace Air Handlers in Building 1 - Pre-Test Marion, IL
DATE:
CONTACT:
AUTHOR:
12/27/2024 Clint Walker Clint Walker
SYSTEM/UNIT: RF-03/Duct-01
Traverse Data Points
Unit Data Type of Traverse Rectangular Outer Height 26.00 in.
Outer Width 26.00 in.
Air Flow Area 4.69 sq. ft.
Number Of Rows 4 Readings Per Row 5 Total Readings 20 Location of Holes 1 Left Location of Holes 2 Bottom
Final Data Sum of Readings 48333 Average Reading 2417 FPM Reading Std. Dev. 444 FPM Actual Total Flow 11336 CFM Duct Static Press. -1.20 in. wc
LOCATION:
Marion VA - Replace Air Handlers in Building 1 - Pre-Test Marion, IL
DATE:
CONTACT:
AUTHOR:
12/27/2024 Clint Walker Clint Walker
1 ICU AHU Notes.pdf 2 ICU AHU Return Air & Outside Air Dampers.pdf 3 ICU AHU Filters.pdf 4 Air Handling Unit
4.1 Existing ICU AHU
ICU AHU Outside Air Audit Notes
1. The design team requested that I try and determine the amount of outside air for the AHU that serves the ICU. A velocity matrix was performed at the outside air inlet. The results are as follows:
2. The outside air damper was opened approximately 10%. The return air damper was opened approximately 90%. The exhaust air damper was 100% closed. Please see the attached picture.
3. The filters are dirty. Please see the attached picture.
Size: 21.25" x 38.5" 1-AC-1 Outside Air Area 5.68 ft2 FPM FPM Avg FPM 299 248 302 Avg CFM 1698 316 364
281 280
PROJECT:
LOCATION:
Marion VA - Replace Air Handlers in Building 1 - Pre-Test Marion, IL
DATE:
CONTACT:
AUTHOR:
12/27/2024 Clint Walker Clint Walker
SYSTEM/UNIT: Existing ICU AHU
Log: Existing ICU AHU 12/26/2024 Clint Walker The manufacture date on this unit was 2003.
Unit Data Unit Manufacturer Govern Air Unit Model Number 1L10-1228 Unit Serial Number 32971 Unit Discharge Downblast
Test Data Actual Outside Airflow 1698 CFM
LOCATION:
Marion VA - Replace Air Handlers in Building 1 - Pre-Test Marion, IL
DATE:
CONTACT:
AUTHOR:
12/27/2024 Clint Walker Clint Walker
1 ICU ReHeat Pump Notes.pdf 2 ICU ReHeat Pump 1 Pump Nameplate .pdf 3 ICU ReHeat Pump 1 Motor Nameplate .pdf 4 Grundfoss Pump Information (From Grundfos Website).pdf 5 ICU ReHeat Pump 2 Pump Nameplate .pdf 6 ICU ReHeat Pump 2 Motor Nameplate .pdf 7 Pages from bellgossettseries60partslist.pdf 8 Pages from bellgossettseries60motorpartslist (1).pdf 9 Hydronic Pump
9.1 ICU Re-Heat Pump-01
9.2 ICU Re-Heat Pump-02
ICU Re-Heat Pump Notes
1. There are two pumps that run at the same time at a constant speed.
2. Neither pump has ports installed that would allow me to take a suction or discharge reading. Ther are no gauges installed. There are only check valves and isolation valves installed.
3. ICU Re-Heat Pump #1 is a Gurndfos pump. I was able to input the nameplate information into the website. I am attaching that as well as pictures of the nameplate data immediately following this notes section.
4. ICU Re-Heat Pump #2 is a Bell & Gossett pump. It is a Series 60 pump. These pumps have been replaced by the eSeries 60 pumps according to their website. I was able to use older pump parts lists and motor parts list to get some of the missing information from the name plate data. It appears that this pump was a generic Series 60 pump as the GPM, Feet of Head and impeller data was not stamped on the pump nameplate. I am attaching the pages I used as well as a picture of the motor and pump name plates. The J59 identifier in the Part #M80067 J59 identifies the production date of this pump as September of 1995.
Submittal Data
PROJECT:
REPRESENTATIVE:
ENGINEER:
CONTRACTOR:
UNIT TAG:
TYPE OF SERVICE:
SUBMITTED BY:
APPROVED BY:
ORDER NO.:
QUANTITY:
DATE:
DATE:
DATE:
Note! Product picture may differ from actual product
TP 50-80/2 A-G-A-BUBE-XX2
Grundfos TP pumps are single-stage, close-coupled in-line centrifugal pumps with mechanical shaft seal and primely for applications such as heating/cooling/district energy. The pumps are fitted with fixed speed motors.
Conditions of Service
Flow: 87.8 US GPM Head: 21.22 ft Efficiency: % Liquid: Water Temperature: 120 °F NPSH required: 5.93 ft Specific Gravity: 0.990
Pump Data
Maximum operating pressure: 145.04 psi Liquid temperature range: 5 .. 284 °F Shaft seal: BUBE Flange standard: USA Pipe connection: 2" Product number: 96405263
Motor Data
Mains frequency: 60 Hz
H [ft]
Q [US GPM]0 10 20 30 40 50 60 70 80 90 100 110
eta
TP 50-80/2
Q = 87.8 US GPM
H = 21.22 ft Pumped liquid = Water Liquid temperature during operation = 120 °F Density = 61.68 lb/ft³
Eta pump = 74.6 %
P2
[HP]
0.0
0.1
0.2
0.3
0.4
0.5
NPSH
[ft]
P2 = 0.624 HP
NPSH = 5.93 ft
Submittal Data
NPT 1/4
0.16"
0.
M12
4.
11.50"3.
6.
5.75"
2.
3.
5.24" 4.06"
2.09" 3.44"
3.74" 2.95"
Materials:
Pump housing: Cast iron Pump housing: EN-JL1040 Pump housing: ASTM 25 B Impeller: Stainless steel Impeller: DIN W.-Nr. 1.4301 Impeller: AISI 304
Company name:
Created by:
Phone:
Date: 27/12/2024
Printed from Grundfos Product Centre [2024.51.002]
Qty. Description
1 TP 50-80/2 A-G-A-BUBE-XX2
Product No.: 96405263 Pump without motor
Single-stage centrifugal in-line single-head pump:
- neck rings and impeller made of stainless steel
- cataphoresis treatment
- shell coupling
- top-pull-out principle for easy maintenance
- optimized hydraulics
- in-line design with opposite suction and discharge ports enabling mounting in pipework or on a concrete foundation
- corrosion resistant maintenance-free mechanical shaft seal.
Liquid:
Pumped liquid: Water Liquid temperature range: 5 .. 284 °F Selected liquid temperature: 120 °F Density: 61.68 lb/ft³
Technical:
Actual calculated flow: 87.8 US GPM Resulting head of the pump: 21.22 ft Primary shaft seal: BUBE Curve tolerance: ISO 9906:1999 Annex A
Materials:
Pump housing: Cast iron
EN-JL1040
ASTM 25 B
Impeller: Stainless steel DIN W.-Nr. 1.4301
AISI 304
Installation:
Maximum operating pressure: 145.04 psi Flange standard: USA Pipe connection: 2"
Others:
Gross weight: 26.5 lb https://product-selection.grundfos.com/products.gotoproduct.json?productnumber=96405263&custid=GPU&frequency=60
Created by:
Phone:
Date: 27/12/2024
Printed from Grundfos Product Centre [2024.51.002]
96405263 TP 50-80/2 A-G-A-BUBE-XX2 60 Hz H [ft]
Q [US GPM]0 10 20 30 40 50 60 70 80 90 100 110
eta
TP 50-80/2
Q = 87.8 US GPM H = 21.22 ft Pumped liquid = Water Liquid temperature during operation = 120 °F Density = 61.68 lb/ft³ Eta pump = 74.6 %
P2
[HP]
0.0
0.1
0.2
0.3
0.4
0.5
0.6
NPSH
[ft]
P2 = 0.624 HP
NPSH = 5.93 ft
Created by:
Phone:
Date: 27/12/2024
Printed from Grundfos Product Centre [2024.51.002]
H [ft]
Q [US GPM]0 20 40 60 80 100
eta
TP 50-80/2
Q = 87.8 US GPM H = 21.22 ft Pumped liquid = Water Density = 61.68 lb/ft³ Eta pump = 74.6 % Liquid temperature during operation = 120 °F
P2
[HP]
0.0
0.1
0.2
0.3
0.4
0.5
NPSH
[ft]
P2 = 0.624 HP
NPSH = 5.93 ft
Description Value General information:
Product name: TP 50-80/2 A-G-A-BUBE-XX2 Product No: 96405263 EAN number: 5700390747831 Price:
Technical:
Actual calculated flow: 87.8 US GPM Resulting head of the pump: 21.22 ft Primary shaft seal: BUBE Curve tolerance: ISO 9906:1999 Annex A Materials:
Pump housing: Cast iron Pump housing: EN-JL1040 Pump housing: ASTM 25 B Impeller: Stainless steel Impeller: DIN W.-Nr. 1.4301 Impeller: AISI 304 Installation:
Maximum operating pressure: 145.04 psi Flange standard: USA Pipe connection: 2" Liquid:
Pumped liquid: Water Liquid temperature range: 5 .. 284 °F Selected liquid temperature: 120 °F Density: 61.68 lb/ft³ Others:
Gross weight: 26.5 lb Country code: Namreg https://product-selection.grundfos.com/products.gotoproduct.json?productnumber=96405263&custid=GPU&frequency=60
Created by:
Phone:
Date: 27/12/2024
Printed from Grundfos Product Centre [2024.51.002]
Order Data:
Position Your pos. Product name Amount Product No Total
TP 50-80/2 A-G-A-BUBE-XX2 1 96405263
PARTS LIST CP 105H-PL (CONTINUED) SERIES 60 PUMPS
(6) SLEEVE BEARING
POWER PACK (5) (8)
STANDARD EQUIVALENT 1 PHASE 3 PHASE IMPELLER
PUMP SIZE SIZE HP 115/230 TRI VOLT COUPLER DIAMETER IMPELLER
60-1S & 60-1T 1"AA 1/4 169035+ 169037 118473 51/4" 186359
60-2S & 60-2T 11/4"AA 1/3 169038 169039 118473 51/4" 186359
60-3S & 60-3T 11/2"AA 1/2 111044 111046 118473 51/4" 186368
60-4S & 60-4T 2"AA 3/4 111047 111049 118473 51/4" 186326
60-5S & 60-5T 11/2"A 1/2 111044 111046 186410 53/4" P57447
60-6S & 60-6T 11/2"A 3/4 111047 111049 186410 61/2" P57445*
60-7S & 60-7T 11/2"A 1 N/A N/A 186004 7" P57445
60-8S & 60-8T 2"A 3/4 111047 111049 186410 55/8" P57452*
60-9S & 60-9T 2"A 1 N/A N/A 186004 61/8" P57451*
60-10T 2"A 11/2 – N/A 186003 63/4" P57450*
60-10S 1"AA 1/4 169035+ – 118473 53/4" 186359
60-11S & 60-11T 11/4"AA 1/4 169035+ 169037 118473 53/16" 186360
60-B11S 11/4"AA 1/4 169035+ – 118473 53/16" 186360
60-13S & 60-13T 11/2"AA 1/2 111044 111046 118473 51/4" 186368
60-B13S & 60-B13T 11/2"AA 1/2 111044 111046 118473 51/4" 186368
60-14S & 60-14T 2"AA 3/4 111047 111049 118473 51/4" 118626
60-B14S & 60-B14T 2"AA 3/4 111047 111049 118473 51/4" 118626
60-15S & 60-15T 11/2"A 1/2 111044 111046 186410 53/4" P57447
60-16S & 60-16T 11/2"A 3/4 111047 111049 186410 63/8" P57446
60-17S & 60-17T 11/2"A 1 N/A N/A 186004 7" P57445
60-19S & 60-19T 2"A 1 N/A N/A 186004 6" P57452
60-20S & 60-20T 2"A 11/2 N/A N/A 186003 61/2" P57451
60-21T 2"A 2 – N/A 186003 7" P57450
60-22T 21/2"F 3 – 169221 P77279 73/4" P57584
STANDARD SIZE DESIGNATIONS
– Factory recommended spare parts.
+ 115V only. For 230V, use 169036.
*Trim impeller to diameter shown.
N/A – No longer available. See note below.
NOTE: Sleeve bearing power packs and maintenance-free ball bearing power packs are interchangeable. Refer to the Power Pack Cross Reference chart on page 14.
clint Rectangle
ITEM MFG. DATE MFG. DATE
NO. DESCRIPTION 7/82 - CURRENT 1/75 - 6/82
MOTOR ID NUMBER M80067 M80066
Power Pack (Series 60) 111044 111044 Power Pack (Series 1522) 169047 169047 Motor Bracket (For Series 60) P61970 P61970 Motor Bracket (For 1522) P61980 P61980 Conduit Box Cover P45010 P45010
1 Capacitor M75064 M75064 2 End Plate (Shaft End) M49301 M49301 3 End Plate (Lead End) M49302 M49302 7 Overload Protector** M74791 M74791 14 Sleeve Bearing (2) M23250 M23250 16 Wicking (2) M72131 M72131 6 Motor Mount Set 118228 118228 12 Resilient Washer - Buna N (2) M25320 M25320 11 Cupped Washer - Steel (2) M26010 M26010 13 Washer - Phenolic (2) M26040 M26040 18 Shim Washer - Mylar (5) M26070 M26070 15 Cover & Tube M72555 M72555 19 Oil Retainer (Shaft End) M23280 M23280 5 Oil Retainer (Lead End) M23130 M23130
PARTS LIST CP-25B-PL (CONTINUED) B&G Motors
111044 and 169047
1/2HP, 115/230-60-1, 5.2/2.6 AMP, 1725 Motor for Series 60 or 1522 Pump
* * - Overload protector is wound in stator windings.
- Factory recommended spare parts.
Use the list below for cross-reference purposes only. Consult factory if replacement parts are needed for these obsolete motors.
111044 replaces: 169047 replaces:
MAGOOD-5106B MAGOOD-5106B
M80065 MOT212-6
MOT330-6
MOT929-6
M80065
NOTE: Refer to page 8 for exploded view of 6" motor.
clint Rectangle
Hydronic Pump
PROJECT:
LOCATION:
Marion VA - Replace Air Handlers in Building 1 - Pre-Test Marion, IL
DATE:
CONTACT:
AUTHOR:
12/27/2024 Clint Walker Clint Walker
SYSTEM/UNIT: ICU Re-Heat Pump-01
Unit Data Pump Manufacturer Grundfos Pump Model Number 96405263 P1 975L Pump Serial Number Product # 96405263 P1 9751 Rated Waterflow 88 GPM Required NPSH 6 PSI
Motor Data Motor Manufacturer Baldor Motor Frame 56C Motor HP .75 HP Motor RPM 3450 RPM Motor Rated Volts 115/208-230 Motor Phase 1 Motor Hertz 60 Motor F.L. Amps 9.6/5.3-4.8 Motor Service Factor 1.25
Hydronic Pump
PROJECT:
LOCATION:
Marion VA - Replace Air Handlers in Building 1 - Pre-Test Marion, IL
DATE:
CONTACT:
AUTHOR:
12/27/2024 Clint Walker Clint Walker
SYSTEM/UNIT: ICU Re-Heat Pump-02
Unit Data Pump Manufacturer Bell & Gossett Pump Model Number Series 60 Size 13S Pump Serial Number 1940135
Motor Data Motor Manufacturer Bell & Gossett Motor HP 1/2 HP Motor RPM 1725 RPM Motor Rated Volts 115/230 Motor Phase 1 Motor Hertz 60 Motor F.L. Amps 5.2/2.6 Motor Service Factor 1.25 Pump Impeller Diam. 5.25 in.
| Cover Page.pdf |
| AHU03.pdf |
| Table of Contents |
| AHU03 Notes.pdf |
| AHU03 SF VFD1.pdf |
| AHU03 SF VFD2.pdf |
| AHU03 Missing Final Filter Section.pdf |
| Air Handling Unit |
| AHU-03 |
| AHU-03/SPP-01 |
| RF03.pdf |
| Table of Contents |
| RF03 Notes.pdf |
| Fan Unit |
| RF-03 |
| RF-03/SPP-01 |
| RF-03/Duct-01 |
| ICU AHU.pdf |
| Table of Contents |
| ICU AHU Notes.pdf |
| ICU AHU Return Air & Outside Air Dampers.pdf |
| ICU AHU Filters.pdf |
| Air Handling Unit |
| Existing ICU AHU |
| ICU ReHeat Pumps.pdf |
| Table of Contents |
| ICU ReHeat Pump Notes.pdf |
| ICU ReHeat Pump 1 Pump Nameplate .pdf |
| ICU ReHeat Pump 1 Motor Nameplate .pdf |
| Grundfoss Pump Information (From Grundfos Website).pdf |
| ICU ReHeat Pump 2 Pump Nameplate .pdf |
| ICU ReHeat Pump 2 Motor Nameplate .pdf |
| Pages from bellgossettseries60partslist.pdf |
| Pages from bellgossettseries60motorpartslist (1).pdf |
| Hydronic Pump |
| ICU Re-Heat Pump-01 |
| ICU Re-Heat Pump-02 |
File details come from the government source that posted it. Updated .