This file is a comprehensive operations and maintenance documentation package for boiler master panel and field instrument systems installed at the VA Medical Center Jefferson Barracks in St. Louis, Missouri. The documentation, submitted May 13, 2015, under Solicitation #VA-101-11-RP-0149 and Contract #VA101F-12-C-0039, covers equipment supplied by Protherm Corporation and includes detailed brief operating instructions and functional safety manuals for Endress & Hauser pressure transmitters (Cerabar M and S models), level transmitters (Deltabar S), and flowmeters (Prowirl models).

The documentation provides installation, wiring, commissioning, and operational guidance for multiple instrument types including pressure measurement devices (PMC51, PMP51, PMP55, PMC71, PMP71, PMP75), differential pressure and level transmitters (PMD55, PMD70, PMD75, FMD76, FMD77, FMD78), and associated control components. Functional safety manuals detail Safety Integrity Level (SIL) 2 and SIL 3 certifications per IEC 61508 standards, with specific performance parameters, proof-test intervals, and configuration procedures for safety-related applications. The materials include device configuration forms, parameter tables, alarm response settings, and maintenance protocols, with emphasis on proper installation positioning, wiring specifications, commissioning procedures for pressure and level measurement modes, and fail-safe operation requirements for process safety systems.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--657-26-109JB, Upgrade Master Boiler Program Logic Controls l STL, newest first.
File Type Posted
36C25526R0051 0001.docx DOCX document
657-26-109JB Upgrade Master Boiler Program Logic Controls Attendance Roster.pdf PDF
657-26-109JB_CONST_100PCT_Specifications - Rev3.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Boiler Master Panel /

Endress & Hauser Field

Instrument O&M Vol 1

Department of Veterans Affairs VA Medical Center

Jefferson Barracks Division

Energy Plant and Utility Infrastructure Project

1 Jefferson Barracks Drive, St. Louis, MO 63125 – Bldg 75

Solicitation #VA-101-11-RP-0149

Contract #VA101F-12-C-0039

Contractor – Rock Hill Mechanical Corporation – Kyle Kopp 314-966-0600

Architect – Christner, Inc. – Wayne Mandel 314-725-2927

Commissioning Authority – SSRCx – Bert Thomas 615-460-0410

Engineer – KJWW Engineering – Mike Vanden Berg 314-645-1132

Submitted May 13, 2015

PRO•THERM

PROCESS AND THERMAL SYSTEMS

STEAM GENERATION, HEAT TRANSFER

& ENERGY CONSERVATION SPECIALISTS

Protherm Corporation 11108 South Towne Square St. Louis, MO 63123-7813

(314) 894-6720 FAX (314) 892-0107 www.prothermcorp.com

TABLE OF CONTENTS

Boiler & Plant Master Control Panels

Endress & Hauser Field Instruments

VOL NO. TAB NO.

ITEM

Drawings A. Boiler Plant Master Control Panel B. Boiler 1 – 3 Control Panels C. Boiler Plant Master Control Panel Electrical Schematic including MSA Information

Pressure Transmitters – Endress & Hauser Cerabar M A. Brief Operating Instructions B. Functional Safety Manual C. Final Inspection Reports

Pressure Transmitters – Endress & Hauser Cerabar S A. Brief Operating Instructions B. Final Inspection Reports

Level Transmitters - Endress & Hauser Deltabar S A. Brief Operating Instructions B. Functional Safety Manual C. Final Inspection Reports D. Certificates of Conformance

Flowmeters – Endress & Hauser Prowirl 72 & 73 A. Brief Operating Instructions (Prowirl 72) B. Operating Instructions (Prowirl 72) C. Brief Operating Instructions (Prowirl 73) D. Operating Instructions (Prowirl 73) E. Functional Safety Manual (Prowirl 72 & 73) F. Technical Information (Prowirl 72 & 73) G. Flow Calibration & Parameter Setting Sheets

(Prowirl 72 & 73)

3 6 Boiler Plant Control System Operational Narrative 3 7 CompactLogix Controller Specifications 3 8 Fireye Components

A. YB110/YB230 BurnerLogix Burner Management Control B. YP BurnerLogix Programmer Modules C. BLV512/BLL510 BurnerLogix Display Modules D. YZ300 & YZ320 Interlock Annunciator for BurnerLogix E. Flame Monitor System Accessories

3 9 Preferred In-Situ Oxygen Sensor 3 10 Computer Information

A. Keyboard B. Monitors C. Network & Servers D. XL Reporter E. Printers

Ted Page Text Box

Ted Page

Ted Page

FLAME

Cerabar M -

Pressure

Transmitter

KA01030P/00/EN/14.12

71157136

Brief Operating Instructions

Cerabar M

PMC51, PMP51, PMP55

Process pressure measurement

These are Brief Operating Instructions.

For more detailed information, please refer to the Operating Instructions and the additional documentation on the CD-ROM provided.

These Brief Operating Instructions are not intended to replace the Operating

Instructions provided in the scope of supply.

The complete device documentation consists of:

• these Brief Operating Instructions

• Approvals and safety certificates

• a CD-ROM with:

– the Operating Instructions

– Technical Information

Table of contents Cerabar M 4...20 mA HART

2 Endress+Hauser

Table of contents

1 Safety instructions

1.1 Designated use

1.2 Installation, commissioning and operation

1.3 Operational safety and process safety

1.4 Return

1.5 Safety icons

2 Mounting

2.1 Installation position

2.2 Installation instructions for devices without diaphragm seals – PMP51, PMC51

2.3 Installation instructions for devices with diaphragm seals – PMP55

2.4 Assembling and mounting the "separate housing" version

2.5 Closing the cover on the stainless steel housing

2.6 Post-installation check

3 Wiring

3.1 Connecting the device

3.2 Connecting the measuring unit

3.3 Potential equalization

3.4 Post-connection check

4 Operation

4.1 Operation without operating menu

4.2 Operation with operating menu

5 Commissioning

5.1 Commissioning without operating menu

5.2 Commissioning with operating menu

5.3 Position zero adjustment

5.4 Commissioning of Level measurement

5.5 Pressure measurement

Cerabar M 4...20 mA HART Safety instructions

Endress+Hauser 3

1 Safety instructions

1.1 Designated use

The Cerabar M is a pressure transmitter for measuring level and pressure.

The manufacturer accepts no liability for damages resulting from incorrect use or use other than that designated.

1.2 Installation, commissioning and operation

• The device must only be installed, connected, commissioned and maintained by qualified and authorized specialists (e.g. electrical technicians) in full compliance with the instructions in this manual, the applicable norms, legal regulations and certificates (depending on the application).

• The specialist must have read and understood this manual and must follow the instructions it contains. If you are unclear on anything in these Brief Operating Instructions, you must read the Operating Instructions (on the CD-ROM). The Operating Instructions provide detailed information on the device/measuring system.

• The device may only be modified or repaired if such work is expressly permitted in the

Operating Instructions (→ see CD-ROM).

• If faults cannot be rectified, the device must be taken out of service and secured against unintentional commissioning.

• Do not operate damaged devices. Mark them as defective.

1.3 Operational safety and process safety

• Alternative monitoring measures must be taken to ensure operational safety and process safety during confiugration, testing and maintenance work on the device.

• The device is safely built and tested according to state-of-the-art technology and has left the factory in perfect condition as regards technical safety. The applicable regulations and

European standards have been taken into account.

• Pay particular attention to the technical data on the nameplate.

• Devices for use in hazardous areas are fitted with an additional nameplate. If the device is to be installed in an explosion hazardous area, then the specifications in the certificate as well as all national and local regulations must be observed. The device is accompanied by separate

"Ex documentation", which is an integral part of this Operating Instructions. The installation regulations, connection values and Safety Instructions listed in this Ex document must be observed. The documentation number of the related Safety Instructions is also indicated on the additional nameplate.

• If using devices for applications with safety integrity level, the separate manual on functional safety must be observed thoroughly (→ see CD-ROM).

# Warning!

Only disassemble the device in pressurless condition!

Mounting Cerabar M 4...20 mA HART

4 Endress+Hauser

1.4 Return

Follow the instructions on returning the device as outlined in the Operating Instructions on the

CD-ROM provided.

1.5 Safety icons

2 Mounting

# Warning!

The seal is not allowed to press against the process isolating diaphragm as this could affect the measurement result.

2.1 Installation position

! Note!

• Due to the orientation of the Cerabar M, there may be a shift in the measured value, i.e. when the container is empty, the measured value does not display zero. You may correct this zero point shift by a position adjustment in one of the following ways:

– via the operation keys on the electronics module (→ ä 13, "Function of the operating elements")

– via the operating menu (→ ä 25, "Position zero adjustment")

• For PMP55, please refer to Section 2.3 "Installation instructions for devices with diaphragm seals – PMP55", → ä 6.

• Endress+Hauser offers a mounting bracket for installing on pipes or walls (see Operating

Instructions BA00382P).

Symbol Meaning

Warning!

A warning highlights actions or procedures which, if not performed correctly, will lead to personal injury, a safety hazard or destruction of the instrument.

Caution!

Caution highlights actions or procedures which, if not performed correctly, may lead to personal injury or incorrect functioning of the instrument.

Note!

A note highlights actions or procedures which, if not performed correctly, may indirectly affect operation or may lead to an instrument response which is not planned.

Cerabar M 4...20 mA HART Mounting

Endress+Hauser 5

2.2 Installation instructions for devices without diaphragm seals –

PMP51, PMC51

! Note!

• If a heated Cerabar M is cooled during the cleaning process (e.g. by cold water), a vacuum develops for a short time, whereby moisture can penetrate the sensor through the pressure compensation (1). If this is the case, mount the Cerabar M with the pressure compensation

(1) pointing downwards.

• Keep the pressure compensation and GORE-TEX® filter (1) free from contamination.

• Cerabar M transmitters without diaphragm seals are mounted as per the norms for a manometer (DIN EN 837-2). We recommend the use of shutoff devices and siphons. The orientation depends on the measuring application.

• Do not clean or touch process isolating diaphragms with hard or pointed objects.

2.2.1 Pressure measurement in gases

• Mount Cerabar M with shutoff device above the tapping point so that condensate which may be present, can flow into the process.

2.2.2 Pressure measurement in steams

• Mount Cerabar M with siphon above the tapping point.

• Fill the siphon with liquid before commissioning.

The siphon reduces the temperature to almost the ambient temperature.

2.2.3 Pressure measurement in liquids

• Mount Cerabar M with shutoff device below or at the same level as the tapping point.

2.2.4 Level measurement

• Always install the Cerabar M below the lowest measuring point.

• Do not mount the device in the filling curtain or at a point in the tank which could be affected by pressure pulses from an agitator.

• Do not mount the device in the suction area of a pump.

• The calibration and functional test can be carried out more easily if you mount the device downstream of a shutoff device.

6 Endress+Hauser

2.3 Installation instructions for devices with diaphragm seals –

PMP55

! Note!

• Cerabar M devices with diaphragm seals are screwed in, flanged or clamped, depending on the type of diaphragm seal.

• A diaphragm seal and the pressure transmitter together form a closed, oil-filled calibrated system. The fill fluid hole is sealed and may not be opened.

• Do not clean or touch the process isolating diaphragm of the diaphragm seal with hard or pointed objects.

• Do not remove process isolating diaphragm protection until shortly before installation.

• When using a mounting bracket, sufficient strain relief must be ensured for the capillaries in order to prevent the capillary bending down (bending radius ≥ 100 mm (3.94 in)).

• Please note that the hydrostatic pressure of the liquid columns in the capillaries can cause zero point shift. The zero point shift can be corrected. → ä 25, Section 5.3 "Position zero adjustment".

• Please observe the application limits of the diaphragm seal filling oil as detailed in the

Technical Information for Cerabar M TI00436P, "Planning instructions for diaphragm seal systems" section.

In order to obtain more precise measurement results and to avoid a defect in the device, mount the capillaries as follows:

• Vibration-free (in order to avoid additional pressure fluctuations)

• Not in the vicinity of heating or cooling lines

• Insulate if the ambient temperature is below or above the reference temperature

• With a bending radius of ≥100 mm (3.94 in).

Cerabar M 4...20 mA HART Mounting

Endress+Hauser 7

2.3.1 Vacuum application

For applications under vacuum, Endress+Hauser recommends mounting the pressure transmitter below the diaphragm seal. This prevents vacuum loading of the diaphragm seal caused by the presence of filling oil in the capillaries.

When the pressure transmitter is mounted above the diaphragm seal, the maximum height difference H1 in accordance with the illustration below left must not be exceeded. The maximum height difference depends on the density of the filling oil and the smallest ever pressure that is permitted to occur at the diaphragm seal (empty container), see illustration below right.

P01-PMx5xxxx-11-xx-xx-xx-006

Fig. 1: Installation above the diaphragm seal P01-PMP75xxx-05-xx-xx-en-011

Fig. 2: Diagram of maximum installation height above the diaphragm seal for vacuum applications, depending on the pressure at the diaphragm seal

H1

0.0

2.0

4.0

6.0

8.0

10.0

12.0

50 100 300 400 500 600 700 800 900 1000200

Inert oil

High temperature oil

Vegetable oil

Silicone oil

Pressure at diaphragm seal [mbarabs]

H e ig h t d if fe re n c e

H

[m

Low temperature oil

8 Endress+Hauser

2.4 Assembling and mounting the "separate housing" version

P01-XMx5xxxx-11-xx-xx-xx-009

Fig. 3: "Separate housing" version

1 In the case of the "separate housing" version, the sensor is delivered with the process connection and cable ready mounted.

2 Cable with connection jack

3 Pressure compensation

4 Connector

5 Locking screw

6 Housing mounted with housing adapter, included

7 Mounting bracket provided, suitable for pipe and wall mounting (for pipes from 1 1/4" up to 2" diameter)

2.4.1 Assembly and mounting

1. Insert the connector (item 4) into the corresponding connection jack of the cable (item 2).

2. Plug the cable into the housing adapter (item 6).

3. Tighten the locking screw (item 5).

4. Mount the housing on a wall or pipe using the mounting bracket (item 7).

When mounting on a pipe, tighten the nuts on the bracket uniformly with a torque of at least 5 Nm (3.69 lbf ft).

Mount the cable with a bending radius (r) ≥ 120 mm (4.72 in).

r � 120 mm1

Cerabar M 4...20 mA HART Wiring

Endress+Hauser 9

2.5 Closing the cover on the stainless steel housing

P01-PMx5xxxx-17-xx-xx-xx-001

Fig. 4: Closing the cover

The cover for the electronics compartment is tightened by hand at the housing until the stop.

The screw serves as DustEx protection (only available for devices with DustEx approval).

2.6 Post-installation check

After installing the device, carry out the following checks:

• Are all screws firmly tightened?

• Are the housing covers screwed down tight?

3 Wiring

3.1 Connecting the device

! Note!

• When using the measuring device in hazardous areas, installation must comply with the corresponding national standards and regulations and the Safety Instructions or Installation or

Control Drawings.

• A suitable circuit breaker has to be provided for the device in accordance with IEC/EN

61010.

• Devices with integrated overvoltage protection must be earthed.

• Protective circuits against reverse polarity, HF influences and overvoltage peaks are integrated.

The procedure

1. Check if the supply voltage matches the specified supply voltage on the nameplate.

2. Switch off the supply voltage before connecting the device.

Wiring Cerabar M 4...20 mA HART

10 Endress+Hauser

3. Remove housing cover.

4. Guide cable through the gland. Preferably use twisted, screened two-wire cable.

5. Connect device in accordance with the following diagram.

6. Screw down housing cover.

7. Switch on supply voltage.

P01-PMD55xxx-04-xx-xx-xx-010

Electrical connection 4...20 mA HART

1 Terminals for supply voltage and signal

2 Test terminals

3 Grounding terminal

4 Supply voltage: 11,5 ... 45 VDC (versions with plug connectors: 35 V DC)

5 External ground terminal

3.2 Connecting the measuring unit

3.2.1 Supply voltage

! Note!

• When using the measuring device in hazardous areas, installation must comply with the corresponding national standards and regulations and the Safety Instructions or Installation or

Control Drawings.

• All explosion protection data are given in separate documentation which is available upon request. The Ex documentation is supplied as standard with all devices approved for use in explosion hazardous areas.

11.5 V DC

- +1

4…20 mA

Electronic version

4 to 20 mA HART, for non-hazardous areas

11.5 to 45 V DC

(versions with plug-in connector 35 V DC)

Cerabar M 4...20 mA HART Wiring

Endress+Hauser 11

Taking 4 to 20 mA test signal

A 4 to 20 mA test signal may be measured via the test terminals without interrupting the measurement. To keep the corresponding measured error below 0.1%, the current measuring device should exhibit an internal resistance of < 0.7 Ω.

3.2.2 Cable specification

• Endress+Hauser recommends using twisted, shielded two-wire cables.

• Terminals for wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)

• Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in) depends on the used cable gland (see technical information)

3.2.3 Shielding/potential equalization

• You achieve optimum shielding against disturbances if the shielding is connected on both sides (in the cabinet and on the device). If potential equalization currents are expected in the plant, only ground shielding on one side, preferably at the transmitter.

• When using in hazardous areas, you must observe the applicable regulations.

Separate Ex documentation with additional technical data and instructions is included with all Ex systems as standard.

3.3 Potential equalization

Hazardous area applications: Connect all devices to the local potential equalization.

Observe the applicable regulations.

3.4 Post-connection check

Perform the following checks after completing electrical installation of the device:

• Does the supply voltage match the specifications on the nameplate?

• Is the device connected as per Section 3.1?

• Are all screws firmly tightened?

• Are the housing covers screwed down tight?

As soon as voltage is applied to the device, the green LED on the electronic insert lights up for a few seconds or the connected local display lights up.

Operation Cerabar M 4...20 mA HART

12 Endress+Hauser

4 Operation

4.1 Operation without operating menu

4.1.1 Position of operating elements

The operating keys and DIP switches are located on the electronic insert in the device.

Function of the DIP switches

P01-Mxxxxxxx-19-xx-xx-xx-009

Fig. 5: HART electronic insert

1 DIP switch for locking/unlocking parameters relevant to the measured value

2 DIP switch for switching damping on/off

3 DIP switch for alarm current SW / Alarm Min (3.6 mA)

4 DIP switch (not used)

5 Slot for optional local display

6 Green LED to indicate successful operation

7 Operating keys for lower range value (zero) and upper range value (span)

➂➁

➅ on off

S W

A la rm m in d a m p in g

1 2 3 4 5

➃

➄

➀

➆ on off

Display Zero

Span

H A

R T

R

F

IE

L D

C O

M M

U N

IC

A

T

IO

N P

R O

T O

C O

L

S W

P

H ig h d e lt a p o n ly

S W

A la rm m in

S W d a m p in g

Switches Symbol/ labeling

Switch position

"off" "on"

1 The device is unlocked.

Parameters relevant to the measured value can be modified.

The device is locked 1).

Parameters relevant to the measured value cannot be modified.

2 damping τ Damping is switched off.

The output signal follows measured value changes without any delay.

Damping is switched on.

The output signal follows measured value changes with the delay time τ.2)

Cerabar M 4...20 mA HART Operation

Endress+Hauser 13

Function of the operating elements

4.2 Operation with operating menu

4.2.1 Operation concept

The operation concept makes a distinction between the following user roles:

3 SW/Alarm min The alarm current is defined by the setting in the operating menu.

("Setup" -> "Extended setup" ->

"Curr. output" -> "Output fail mode")

The alarm current is 3.6 mA regardless of the setting in the operating menu.

1) If operation is locked by means of the DIP switch, you can only unlock operation again by means of the DIP switch. If ope-ration is locked by means of the operating menu, you can only unlock operation again using the operating menu.

2) The value for the delay time can be configured via the operating menu ("Setup" -> "Damping").

Factory setting: τ = 2 s or as per order specifications.

Switches Symbol/ labeling

Switch position

"off" "on"

Operating key(s) Meaning

"Zero" pressed for at least

3 seconds

Get LRV

• "Pressure" measuring mode

The pressure present is accepted as the lower range value (LRV).

• "Level" measuring mode, "In pressure" level selection, "Wet" calibration mode

The pressure present is assigned to the lower level value ("Empty calibration").

! Note!

No function is assigned to the key if level selection = "In height" and/or calibration mode = "Dry"

"Span" pressed for at least

3 seconds

Get URV

• "Pressure" measuring mode

The pressure present is accepted as the upper range value (LRV).

• "Level" measuring mode, "In pressure" level selection, "Wet" calibration mode

The pressure present is assigned to the upper level value ("Full calibration").

! Note!

No function is assigned to the key if level selection = "In height" and/or calibration mode = "Dry"

"Zero" and "Span" pressed simultaneously for at least 3 seconds

Position adjustment

The sensor characteristic curve is shifted such that the pressure present becomes the zero value.

User role Meaning

Operator Operators are responsible for the devices during normal "operation". This is usually limited to reading process values either directly at the device or in a control room. If the work with the devices extends beyond value read-off tasks, the tasks involve simple, application-specific functions that are used in operation. Should an error occur, these users simple forward the information on the errors but do not intervene themselves.

14 Endress+Hauser

4.2.2 Structure of the operating menu

Service engineer/ technician

Service engineers usually work with the devices in the phases following device commissioning.

They are primarily involved in maintenance and troubleshooting activities for which simple settings have to be made at the device.

Technicians work with the devices over the entire life cycle of the product.

Thus, commissioning and advanced settings and configurations are some of the tasks they have to carry out.

Expert Experts work with the devices over the entire product life cycle, but their device requirements are often extremely high. Individual parameters/functions from the overall functionality of the devices are required for this purpose time and again.

In addition to technical, process-oriented tasks, experts can also perform administrative tasks (e.g. user administration).

"Experts" can avail of the entire parameter set.

User role Meaning

User role Submenu Meaning/use

Operator Language Only consists of the "Language" parameter (000) where the operating language for the device is specified.

The language can always be changed even if the device is locked.

Operator Display/operat. Contains parameters that are needed to configure the measured value display (selecting the values displayed, display format, display contrast, etc.).

With this submenu, users can change the measured value display without affecting the actual measurement.

Service engineer/ technician

Setup Contains all the parameters that are needed to commission measuring operations. This submenu has the following structure:

• Standard setup parameters

A wide range of parameters, which can be used to configure a typical application, is available at the start. The measuring mode selected determines which parameters are available.

After making settings for all these parameters, the measuring operation should be completely configured in the majority of cases.

• "Extended setup" submenu

The "Setup" submenu contains additional parameters for more in-depth configuration of the measurement operation to convert the measured value and to scale the output signal.

This menu is split into additional submenus depending on the measuring mode selected.

Service engineer/ technician

Diagnosis Contains all the parameters that are needed to detect and analyze operating errors. This submenu has the following structure:

• Diagnostic list

Contains up to 10 error messages currently pending.

• Event logbook

Contains the last 10 error messages (no longer pending).

• Instrument info

Contains information on the device identification.

• Measured values

Contains all the current measured values

• Simulation

Is used to simulate pressure, level, current and alarm/warning.

• Reset

Endress+Hauser 15

4.2.3 Operation with device display (optional)

A 4-line liquid crystal display (LCD) is used for display and operation. The local display shows measured values, dialog texts, fault messages and notice messages.

For easy operation the display can be taken out of the housing (see figure steps 1 to 3). It is connected to the device through a 90 mm (3.54 in) cable.

The display of the device can be turned in 90° stages (see figure steps 4 to 6).

Depending on the orientation of the device, this makes it easy to operate the device and read the measured values.

P01-Mxxxxxxx-19-xx-xx-xx-008

Expert Expert Contains all the parameters of the device (including those in one of the submenus). The

"Expert" submenu is structured by the function blocks of the device. It thus contains the following submenus:

• System

Contains all the device parameters that neither affect measurement nor integration into a distributed control system.

• Measurement

Contains all the parameters for configuring the measurement.

• Output

Contains all the parameters for configuring the current output.

• Communication

Contains all the parameters for configuring the HART interface.

• Application

Contains all the parameters for configuring the functions that go beyond the actual measurement.

• Diagnosis

Contains all the parameters that are needed to detect and analyze operating errors.

User role Submenu Meaning/use

1. 2. 3.

4. 5. 6.

16 Endress+Hauser

Functions:

• 8-digit measured value display including sign and decimal point, bargraph for 4 to 20 mA

HART as current display

• Three keys for operation

• Simple and complete menu guidance as parameters are split into several levels and groups

• Each parameter is given a 3-digit parameter code for easy navigation

• Possibility of configuring the display to suit individual requirements and preferences, such as language, alternating display, contrast setting, display of other measured values such as sensor temperature etc.

• Comprehensive diagnostic functions (fault and warning message etc.)

P01-Mxxxxxxx-07-xx-xx-xx-002

E+–

Symbol

Operating keys

ValueDevice tag

Measured value display

Unit

Bargraph

Operating menu

Parameter with selection list

Freely editable parameter

Direct Access Code

Value that can be edited

Selection options

Header line

Information line

Main line

Endress+Hauser 17

Display symbols

Operating keys on the display and operating module

Symbol Meaning

Lock symbol

The operation of the device is locked. To unlock the device, → ä 20, Locking/unlocking operation.

Communication symbol

Data transfer via communication

Error message "Out of specification"

The device is being operated outside its technical specifications (e.g. during warmup or cleaning processes).

Error message "Service mode"

The device is in the service mode (during a simulation, for example).

Error message "Maintenance required"

Maintenance is required. The measured value remains valid.

Error message "Failure detected"

An operating error has occurred. The measured value is no longer valid.

Operating key(s) Meaning

O – Navigate downwards in the picklist

– Edit the numerical values and characters within a function

S – Navigate upwards in the picklist

– Edit the numerical values and characters within a function

F

– Confirm entry

– Jump to the next item

– Selection of a menu item and activation of the editing mode

O and F Contrast setting of local display: darker

S and F Contrast setting of local display: brighter

O and S ESC functions:

– Exit the edit mode for a parameter without saving the changed value.

– You are in a menu at a selection level. Each time you press the keys simultaneously, you go up a level in the menu.

18 Endress+Hauser

Parameters with a picklist

Example: selecting "Deutsch" as the language of the menu.

User-definable parameters

Example: setting "Set URV" parameter from 100 mbar (1.5 psi) to 50 mbar (0.75 psi).

Local display Operation

P01-PMD55xxx-19-xx-xx-xx-002

"English" is set as the menu language (default value). A ✓ in front of the menu text indicates the active option.

P01-PMD55xxx-19-xx-xx-xx-001

Select "Deutsch" with "+" or "–" .

P01-PMD55xxx-19-xx-xx-xx-000

1. Confirm your choice with "E". A ✓ in front of the menu text indicates the active option. ("Deutsch" is now selected as the menu language.)

2. Exit the edit mode for the parameter with "E" .

Local display Operation

P01-PMD55xxx-19-xx-xx-xx-003

The local display shows the parameter to be changed. The value highlighted in black can be changed. The "mbar" unit is specified in another parameter and cannot be modified here.

P01-PMD55xxx-19-xx-xx-xx-004

1. Press "+" or "–" to get to the editing mode.

2. The first digit is highlighted in black.

Endress+Hauser 19

Accepting the pressure present

Example: setting position adjustment

P01-PMD55xxx-19-xx-xx-xx-005

1. Use "+" to change "1" to "5".

2. Confirm "5" with "E". The cursor jumps to the next position

(highlighted in black).

3. Confirm "0" with "E" (second position).

P01-PMD55xxx-19-xx-xx-xx-006

The third position is highlighted in black and can now be edited.

P01-PMD55xxx-19-xx-xx-xx-007

1. Switch to the "↵" symbol with the "-" key.

2. Use "E" to save the new value and exit the editing mode. → See next graphic.

P01-PMD55xxx-19-xx-xx-xx-008

The new value for the upper range value is 50.0 mbar (0.75 psi).

– You exit the edit mode for the parameter with "E" .

– You can get back to the editing mode with "+" or

Local display Operation

P01-PMD55xxx-19-xx-xx-xx-009

The pressure for position adjustment is present at the device.

Local display Operation

20 Endress+Hauser

4.2.4 Locking/unlocking operation

Once you have entered all the parameters, you can lock your entries against unauthorized and undesired access.

Locked operation is indicated as follows:

• By the symbol on the onsite display

• The parameters are grayed out in FieldCare and the HART handheld terminal, which means they cannot be edited. Indicated in the corresponding "Locking" parameter.

Parameters which refer to how the display appears, e.g. "Language" and "Display contrast", can still be altered.

! Note!

If operation is locked by means of the DIP switch, you can only unlock operation again by means of the DIP switch. If operation is locked by means of the operating menu, you can only unlock operation again using the operating menu.

The "Operator code" parameter is used to lock and unlock the device.

P01-PMD55xxx-19-xx-xx-xx-010

Use "+" or "–" to switch to the "Confirm" option. The active option is highlighted in black.

P01-PMD55xxx-19-xx-xx-xx-011

Accept the pressure present as position adjustment with the "E" key.

The device confirms the adjustment and goes back to the "Pos. zero adjust" parameter.

P01-PMD55xxx-19-xx-xx-xx-009

Exit the edit mode for the parameter with "E" .

Local display Operation

Cerabar M 4...20 mA HART Commissioning

Endress+Hauser 21

The release code is defined in the "Code definition" parameter.

5 Commissioning

# Warning!

• If a pressure smaller than the minimum permitted pressure or greater than the maximum permitted pressure is present at the device, the following messages are output in succession:

1. "S140 Working range P" or "F140 Working range P" 1)

2. "S841 Sensor range" or "F841 Sensor range"1)

3. "S971 Sensor range"1)

! Note!

The device is configured for the Pressure measuring mode as standard. The measuring range and the unit in which the measured value is transmitted correspond to the specifications on the nameplate.

Parameter name Description

Operator code (021)

Entry

Menu path:

Setup → Extended setup

→ Operator code

Use this function to enter a code to lock or unlock operation.

User input:

• To lock: Enter a number ≠ the release code (value range: 1 up to 9999).

• To unlock: Enter the release code.

! Note!

The release code is "0" in the order configuration. Another release code can be defined in the

"Code definition" parameter.

If the user has forgotten the release code, it can be made visible again by entering the number sequence "5864".

Factory setting:

Parameter name Description

Code definition (023)

Entry

Menu path:

Setup → Extended setup

→ Code definition

Use this function to enter a release code with which the device can be unlocked.

User input:

• A number between 0 and 999

Factory setting:

1) depending on the setting in the "Alarm behavior" (050) parameter

Commissioning Cerabar M 4...20 mA HART

22 Endress+Hauser

5.1 Commissioning without operating menu

5.1.1 Pressure measuring mode

If no local display is connected, the following functions are possible by means of the keys on the electronic insert:

• Position adjustment (zero point correction)

• Setting lower range value and upper range value

• Device reset

! Note!

• Operation must be unlocked. → ä 20, "Locking/unlocking operation"

• The device is configured for the "Pressure" measuring mode as standard. You can switch measuring modes by means of the "Measuring mode" parameter. → ä 24, "Measuring mode selection"

• The pressure applied must be within the nominal pressure limits of the sensor. See information on the nameplate.

5.1.2 Level measuring mode

The following functions are possible by means of the keys on the electronic insert:

• Position adjustment (zero point correction)

• Setting the lower and upper pressure value and assigning to the lower and upper level value

• Device reset

Carrying out position adjustment.1) Setting lower range value. Setting upper range value.

Pressure is present at device. Desired pressure for lower range value is present at device.

Desired pressure for upper range value is present at device.

Press the "Zero" and "Span" keys simultaneously for at least 3 s.

Press the "Zero" key for at least 3 s. Press the "Span" key for at least 3 s.

Does the LED on the electronic insert light up briefly?

Does the LED on the electronic insert light up briefly?

Does the LED on the electronic insert light up briefly?

Yes No Yes No Yes No

Applied pressure for position adjustment has been accepted.

Applied pressure for position adjustment has not been accepted.

Observe the input limits.

Applied pressure for lower range value has been accepted.

Applied pressure for lower range value has not been accepted. Observe the input limits.

Applied pressure for upper range value has been accepted.

Applied pressure for upper range value has not been accepted. Observe the input limits.

1) Observe warning on commissioning (→ ä 21)

Endress+Hauser 23

! Note!

• The "Zero" and "Span" keys only have a function with the following setting:

– "Level selection" = "In pressure", "Calibration mode" = "Wet"

The keys have no function in other settings.

• The device is configured for the "Pressure" measuring mode as standard. You can switch measuring modes by means of the "Measuring mode" parameter. → ä 24, "Measuring mode selection"

The following parameters are set to the following values at the factory:

– "Level selection" = "In pressure"

– "Calibration mode": wet

– "Output unit": %

– "Empty calib.": 0.0

– "Full calib.": 100.0

– "Set LRV": 0.0 (corresponds to 4 mA value)

– "Set URV": 100.0 (corresponds to 20 mA value)

• Operation must be unlocked. → ä 20, "Locking/unlocking operation".

• The pressure applied must be within the nominal pressure limits of the sensor. See information on the nameplate.

Carrying out position adjustment.1) Setting lower pressure value. Setting upper pressure value.

Pressure is present at device. Desired pressure for lower pressure value ("empty pressure") is present at device.

Desired pressure for upper pressure value ("full pressure") is present at device.

Press the "Zero" and "Span" keys simultaneously for at least 3 s.

Press the "Zero" key for at least 3 s. Press the "Span" key for at least 3 s.

Does the LED on the electronic insert light up briefly?

Does the LED on the electronic insert light up briefly?

Does the LED on the electronic insert light up briefly?

Yes No Yes No Yes No

Applied pressure for position adjustment has been accepted.

Applied pressure for position adjustment has not been accepted.

Observe the input limits.

The pressure present was saved as the lower pressure value

("empty pressure") and assigned to the lower level value

("empty calibration").

The pressure present was not saved as the lower pressure value.

Observe the input limits.

The pressure present was saved as the upper pressure value

("full pressure") and assigned to the upper level value

("full calibration").

The pressure present was not saved as the upper pressure value.

Observe the input limits.

1) Observe warning on commissioning (→ ä 21)

24 Endress+Hauser

5.2 Commissioning with operating menu

5.2.1 Selecting the language, measuring mode and pressure unit

Language selection

Measuring mode selection

Pressure unit selection

Parameter name Description

Language (000)

Selection

Menu path:

Main menu → Language

Select the menu language for the local display.

Options:

• English

• Another language (as selected when ordering the device)

• Possibly a third language (language of the manufacturing plant)

Factory setting:

English

Parameter name Description

Measuring mode

(005)

Selection

Menu path: Setup

→ Measuring mode

Select the measuring mode.

The operating menu is structured differently depending on the measuring mode selected.

! Note!

If the measuring mode is changed, no conversion takes place. If necessary, the device has to be recalibrated after the measuring mode has been changed.

Options:

• Pressure

• Level

Factory setting:

Pressure

Parameter name Description

Press. eng. unit (125)

Selection

Menu path: Setup

→ Press. eng. unit

Select the pressure unit.

If a new pressure unit is selected, all pressure-specific parameters are converted and displayed with the new unit.

Options:

• mbar, bar

• mmH2O, mH2O, inH2O

• ftH2O

• Pa, kPa, MPa

• psi

• mmHg, inHg

• kgf/cm2

Factory setting:

mbar or bar depending on the sensor nominal measuring range, or as per order specifications

Endress+Hauser 25

5.3 Position zero adjustment

The pressure resulting from the orientation of the device can be corrected here.

5.4 Commissioning of Level measurement

5.4.1 Information on level measurement

! Note!

You have a choice of two methods for calculating the level: "In pressure" and "In height". The table in the "Overview of level measurement" section that follows provides you with an overview of these two measuring tasks.

• The limit values are not checked, i.e. the values entered must be appropriate for the sensor and the measuring task for the device to be able to measure correctly.

Parameter name Description

Corrected press.

(172)

Display

Menu path:

Setup → Corrected press.

Displays the measured pressure after sensor trim and position adjustment.

! Note!

If this value is not equal to "0", it can be corrected to "0" by the position adjustment.

Pos. zero adjust (007)

(relative pressure sensor) Selection

Menu path:

Setup → Pos. zero adjust

Position zero adjustment – the pressure difference between zero (set point) and the measured pressure need not be known.

Example:

– Measured value = 2.2 mbar (0.033 psi)

– You correct the measured value via the "Pos. zero adjust" parameter with the "Confirm" option. This means that you assign the value 0.0 to the pressure present.

– Measured value (after pos. zero adjust) = 0.0 mbar

– The current value is also corrected.

Options

• Confirm

• Abort

Factory setting:

Abort

Calib. offset (192) /

(008)

(absolute pressure sensor)

Entry

Position adjustment – the pressure difference between set point and the measured pressure must be known.

Example:

– Measured value = 982.2 mbar (14.73 psi)

– You correct the measured value with the value entered (e.g. 2.2 mbar (0.033 psi)) via the

"Calib. offset" parameter. This means that you are assigning the value 980.0 (14.7 psi) to the pressure present.

– Measured value (after calib. offset) = 980.0 mbar (14.7 psi)

– The current value is also corrected.

Factory setting:

0.0

26 Endress+Hauser

• Customer-specific units are not possible.

• The values entered for "Empty calib./Full calib.", "Empty pressure/Full pressure", "Empty height/Full height" and "Set LRV/Set URV" must be at least 1% apart. The value will be rejected, and a message output, if the values are too close together.

5.4.2 Overview of level measurement

5.4.3 Level selection "in pressure"

Calibration with reference pressure (wet calibration)

Example:

In this example, the level in a tank should be measured in "m". The maximum level is 3 m (9.8 ft). The pressure range is set to 0 to 300 mbar (4.5 psi).

Prerequisite:

• The measured variable is in direct proportion to the pressure.

• The tank can be filled and emptied.

! Note!

The values entered for "Empty calib./Full calib." and" Set LRV/Set URV" must be at least 1% apart. The value will be rejected, and a message output, if the values are too close together.

Other limit values are not checked, i.e. the values entered must be appropriate for the sensor and the measuring task for the device to be able to measure correctly.

Measuring task Level selection

Measured variable options

Description Measured value display

Calibration takes place by entering two pressure/level value pairs.

"In pressure" Via the "Output unit" parameter: %, level, volume or mass units.

• Calibration with reference pressure (wet calibration), → ä 26

• Calibration without reference pressure

(dry calibration) → ä 28

The measured value display and the

"Level before lin" parameter display the measured value.

Calibration takes place by entering the density and two height/level value pairs.

"In height" • Calibration with reference pressure (wet calibration), → ä 32

• Calibration without reference pressure

(dry calibration) → ä 29

Endress+Hauser 27

Description

1 Perform "position zero adjustment" → ä 25.

P01-xxxxxxxx-05-xx-xx-xx-011

Calibration with reference pressure (wet calibration)

1 See Table, Step 7

2 See Table, Step 8

2 Select the "Level" measuring mode via the "Measuring mode (005)" parameter (→ ä 24).

Menu path: Setup → Measuring mode

3 Select a pressure unit via the "Press eng. unit" parameter, here "mbar" for example.

Menu path: Setup → Press. eng. unit

4 Select the "In pressure" level mode via the "Level selection" parameter.

Menu path: Setup → Extended setup → Level →

Level selection

5 Select a level unit via the "Output unit" parameter, here

"m" for example.

Menu path: Setup → Extended setup → Level → Output unit

6 Select the "Wet" option via the "Calibration mode" parameter.

Menu path: Setup → Extended setup → Level →

Calibration mode

7 a. The pressure for the lower calibration point is present at the device, here "0 mbar" for example.

b. Select the "Empty calib." parameter.

c. Enter the level value, here "0 m" for example.

Confirming the value means you assign the pressure value present to the lower level value.

Menu path: Setup → Extended setup → Level → Empty calib.

8 a. The pressure for the upper calibration point is present at the device, here "300 mbar" (4.5 psi) for example.

b. Select the "Full calib." parameter.

c. Enter the level value, here "3 m" (9.8 ft) for example. Confirming the value means you assign the pressure value present to the upper level value.

Menu path: Setup → Extended setup → Level → Full calib.

9 Result:

The measuring range is set for 0 to 3 m (9.8 ft).

0 m corresponds to an output current of 4 mA.

3 m (9.8 ft) corresponds to an output current of 20 mA.

h [m]

0 300 p [mbar]

➀

➁

28 Endress+Hauser

5.4.4 Level selection "in pressure"

Calibration without reference pressure (dry calibration)

Example:

In this example, the volume in a tank should be measured in liters. The maximum volume of

1000 liters (264 US gal) corresponds to a pressure of 400 mbar (6 psi). The minimum volume of 0 liters corresponds to a pressure of 0 mbar.

Prerequisite:

• The measured variable is in direct proportion to the pressure.

• This is a theoretical calibration i.e. the pressure and volume values for the lower and upper calibration point must be known.

! Note!

The values entered for "Empty calib./Full calib." and" Set LRV/Set URV" must be at least 1% apart. The value will be rejected, and a message output, if the values are too close together.

Other limit values are not checked, i.e. the values entered must be appropriate for the sensor and the measuring task for the device to be able to measure correctly.

Description

1 Perform "position zero adjustment" → ä 25.

2 Select the "Level" measuring mode via the "Measuring mode (005)" parameter (→ ä 24).

Menu path: Setup → Measuring mode

3 Select a pressure unit via the "Press eng. unit" parameter (→ ä 24), here "mbar" for example.

Menu path: Setup → Press. eng. unit

4 Select the "In pressure" level mode via the "Level selection" parameter.

Menu path: Setup → Extended setup → Level →

Level selection

5 Select a volume unit via the "Output unit" parameter, here "l" for example.

Menu path: Setup → Extended setup → Level → Output unit

6 Select the "Dry" option via the "Calibration mode" parameter.

Menu path: Setup → Extended setup → Level →

Calibration mode

Endress+Hauser 29

5.4.5 Level selection "in height"

Calibration without reference pressure (dry calibration)

Example:

In this example, the volume in a tank should be measured in liters. The maximum volume of

1000 liters (264 US gal) corresponds to a level of 4 m (13 ft). The minimum volume of 0 liters corresponds to a height of 0 m. The density of the medium is 1 g/cm3 (1 SGU).

Prerequisite:

• The measured variable is in direct proportion to the pressure.

• This is a theoretical calibration i.e. the pressure and volume values for the lower and upper calibration point must be known.

! Note!

The values entered for "Empty calib./Full calib." and " Set LRV/Set URV" must be at least 1% apart. The value will be rejected, and a message output, if the values are too close together.

Other limit values are not checked, i.e. the values entered must be appropriate for the sensor and the measuring task for the device to be able to measure correctly.

Description

7 Enter the volume value for the lower calibration point via the "Empty calib." parameter, here "0 liter" for example.

Menu path: Setup → Extended setup → Level →

Empty calib.

P01-FMX21xxx-05-xx-xx-xx-026

Calibration without reference pressure (dry calibration)

1 See Table, Step 7.

2 See Table, Step 8.

3 See Table, Step 9.

4 See Table, Step 10.

8 Enter the pressure value for the lower calibration point via the "Empty pressure" parameter, here "0 mbar" for example.

Menu path: Setup → Extended setup → Level →

Empty pressure

9 Enter the volume value for the upper calibration point via the "Full calib." parameter, here "1000 liters (264

US gal)" for example.

Menu path: Setup → Extended setup → Level →

Full calib.

10 Enter the pressure value for the upper calibration point via the "Full pressure" parameter, here "400 mbar (6 psi)" for example.

Menu path: Setup → Extended setup → Level →

Full pressure

11 Result:

The measuring range is set for 0 to 1000 l (264 US gal).

0 l corresponds to an output current of 4 mA.

1000 l (264 US gal) corresponds to an output current of

20 mA.

V [l]

0 400 p [mbar]

➀

➁

➂

➃

30 Endress+Hauser

Description

1 Perform "position zero adjustment" → ä 25.

2 Select the "Level" measuring mode via the "Measuring mode (005)" parameter (→ ä 24).

Menu path: Setup → Measuring mode

3 Select a pressure unit via the "Press eng. unit" parameter (→ ä 24), here "mbar" for example.

Menu path: Setup → Press. eng. unit

4 Select the "In height" level mode via the "Level selection" parameter.

Menu path: Setup → Extended setup → Level →

Level selection

5 Select a volume unit via the "Output unit" parameter, here "l" for example.

Menu path: Setup → Extended setup → Level → Output unit

6 Select a height unit via the "Height unit" parameter, here "m" for example.

Menu path: Setup → Extended setup → Level → Height unit

7 Select the "Wet" option via the "Calibration mode" parameter.

Endress+Hauser 31

Description

8 Enter the height value for the lower calibration point via the "Empty height" parameter, here "0 m" for example.

Menu path: Setup → Extended setup → Level →

Empty height

P01-FMX21xxx-05-xx-xx-xx-029

P01-FMX21xxx-05-xx-xx-xx-032

Calibration without reference pressure (dry calibration)

1 See table, Step 12.

2 See table, Step 8.

3 See table, Step 9.

4 See table, Step 10.

5 See table, Step 11.

9 Enter the volume value for the upper calibration point via the "Full calib." parameter, here "1000 liters (264

US gal)" for example.

Menu path: Setup → Extended setup → Level →

Full calib.

10 Enter the volume value for the lower calibration point via the "Empty calib." parameter, here "0 liter" for example.

Menu path: Setup → Extended setup → Level →

Empty calib.

11 Enter the height value for the upper calibration point via the "Full height" parameter, here "4 m" (13 ft) for example.

Menu path: Setup → Extended setup → Level →

Full height

12 Enter the density of the medium, using the "Adjust density" parameter, here 1 g/cm3 (1 SGU) for example.

Menu path: Setup → Extended setup → Level → Adjust density

13 Result:

The measuring range is set for 0 to 1000 l (264 US gal).

0 l corresponds to an output current of 4 mA.

1000 l (264 US gal) corresponds to an output current of

20 mA.

4.08 h [m]

0 400 p [mbar] h = p

� · g

� = 1 g cm3

➀

V [l]

0.0 4.0 ➁

➂ h = p

� · g h [m]

➃

➄

32 Endress+Hauser

5.4.6 Level selection "in height"

Calibration with reference pressure (wet calibration)

Example:

In this example, the volume in a tank should be measured in liters. The maximum volume of

1000 liters (264 US gal) corresponds to a level of 4 m (13 ft). The minimum volume of 0 liters corresponds to a height of 0 m. The density of the medium is 1 g/cm3 (1 SGU).

Prerequisite:

• The measured variable is in direct proportion to the pressure.

• The tank can be filled and emptied.

! Note!

The values entered for "Empty calib./Full calib." and" Set LRV/Set URV" must be at least 1% apart. The value will be rejected, and a message output, if the values are too close together.

Other limit values are not checked, i.e. the values entered must be appropriate for the sensor and the measuring task for the device to be able to measure correctly.

Description

1 Perform "position zero adjustment" → ä 25.

2 Select the "Level" measuring mode via the "Measuring mode (005)" parameter (→ ä 24).

Menu path: Setup → Measuring mode

3 Select a pressure unit via the "Press eng. unit" parameter (→ ä 24), here "mbar" for example.

Menu path: Setup → Press. eng. unit

4 Select the "In height" level mode via the "Level selection" parameter.

Menu path: Setup → Extended setup → Level →

Level selection

5 Select a volume unit via the "Output unit" parameter, here "l" for example.

Menu path: Setup → Extended setup → Level → Output unit

6 Select a height unit via the "Height unit" parameter, here "m" for example.

Menu path: Setup → Extended setup → Level → Height unit

7 Select the "Wet" option via the "Calibration mode" parameter.

Endress+Hauser 33

Description

8 a. The pressure for the lower calibration point is present at the device, here "0 mbar" for example.

b. Select the "Empty calib." parameter.

c. Enter the volume value, here "0 l" for example.

Menu…