36C25520R0021-006.pdf

PDF Posted

Attached to
Z2DA-- Relocate Community Living Center Project 589-335
Solicitation number
36C25520R0021
Issued by

About this file

This document outlines a federal contract solicitation for relocating a community living center. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15 is seeking offers for a project to construct a new 17,665 square foot single story structure with an 8,045 square foot basement. The project involves demolishing existing structures and utilities, installing new infrastructure and buildings, and landscaping. Offerors must provide all labor, materials, and services to complete demolition, civil, mechanical, electrical and other construction work. The estimated price range for the project is between $5 million and $10 million. The response due date is June 19, 2020. This solicitation implements a tiered evaluation process to prioritize offers from service-disabled veteran owned small businesses, then veteran owned small businesses, and finally other small businesses.

36C25520R0021 Drawings-589-335-VOL 1 General_Bid-7 Pages.pdf

View the file

Other files

File Type Posted
36C25520R0021-0001000.docx DOCX document
36C25520R0021-007.pdf PDF
36C25520R0021-004.pdf PDF
36C25520R0021-003.docx DOCX document
36C25520R0021-013.pdf PDF
36C25520R0021-012.pdf PDF
36C25520R0021-009.pdf PDF
36C25520R0021-005.pdf PDF
36C25520R0021-008.pdf PDF
36C25520R0021-010.pdf PDF
36C25520R0021-014.pdf PDF
36C25520R0021-011.pdf PDF
Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

�)*+),,-+)*.�)/0 12345�6+78)�9,):, �;,7<,-=+,>6. +778:-+?@44A

�;8),B?@?0A@405554 �CDB?@?0A@405255

+778:-+�,-<+=+/C<,8=�:<;8-+<EF��4413GG

'-CH+)*�+<>,

�II-89,6B�-8J,/<'+-,/<8-

�-8J,/<�+<>, 'C<, �8/C<+8)

�;,/K,6

!:+>6+)*�:LM,-

�-8J,/<�:LM,-

'-CH+)*�:LM,-

'-CH)

�����������B ���������N��"������B �==+/,8= �8)7<-:/<+8) C)6�C/+>+<+,7 C)C*,L,)<

O P Q Q

RS

T

UT

RP

V T W O P Q

XO

O U Y Z a b c

UT

dQ Q

RP

V T Q e W O P Q

XO

O U

Z f

Y

Z f

O P Q g P h O P Q T g iX

RP

V T Q e W O P Q

XO

O U

O P Q

RP

V T W O P Q

XO

O U j

Z f

Z f j

UT

dQ Q k l g dU Q de

RP

V T W O P Q

XO

O U

O P Q T g iX

RP

V T W O P Q

XO

O U

UT

dQ Q Q

RS

T

UT

e

RP

V T W O P Q

XO

O U

O P Q k l g dU Q d

RP

V T W O P Q

XO

O U m_ cnop ][qZjrY

Y j r \ s Z [t u c b a ut [Zs\rjY

!�����������������v��"������ !C)/-8=<���80

544�+/;8>C7!>960�:+<,@44 �>K"-89,�+>>C*,.��?4445

�B2G50wA30w@?3

HHH0MC)/-8=<xC,0/8L #yz{|}~y�}�� �y}y|{�����{�|�

���������������B

������������B

!���'��"�� !��B

�������������N ���������N����������N��� !��"B

�,9+7+8)7B 'C<, ��(����B

544�+/;8>C7!>960�:+<,@44 �>K"-89,�+>>C*,.��?4445 �B2G50wA30w@?3�B2G50wA30wG4@ HHH0MC)/-8=<xC,0/8L

����������N��������������B

12345�6+78)�9,):, �<0�8:+7. �?@44A �B?@?0A@405554�B?@?0A@405255

��������� !���B

�����B

3A5�;,7<,-=+,>6!:7+),77�C-KHCE

�<0�8:+7. �?@44A �B?@?0A@40w144�B?@?0A@40w1@4

3A5�;,7<,-=+,>6!:7+),77�C-KHCE

�<0�8:+7. �?@44A ��?@?�A@4xw144��?@?�A@4xw1@4

12345�6+78)�9,):, �;,7<,-=+,>6. �?@44A ��?@?�A@4x5554 ��?@?�A@4x5255

�0�,-<+=+/C<,8=�:<;8-+<EF��4413GG

©ª ±² ³°́ µ

©ª

1?x13@

����(�0��� ���� �

244��������'�������� !��. �

4AN11N3412 ' �����

A2wx@@A

"x441

244��������'�������� !��. �

A2wx@@A ��3AAx1?x�x43@G 1?x13@

¹

!�''��� ���� 4AN11N12

Drawing Title

Approved: Project Di rector

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

BANCROFT ARCHITECTS + ENGINEERS Bancroft AE No.

700 Nicholas Blvd. Suite 300 Elk Grove Village, IL 60007

T:847.952.9362 www.bancroft-ae.com Department of Veterans Affairs

VA CONTRACT NO.

Revisions: Date

KEY PLAN:

N

U :\5

-3

C ol um bi a

V A

M C

( C E

N T

R A

L)

_B

_c ro lli ns

.rv t

6/

/2

9:

:0

A

M

DRAWING INDEX

16-123

HARRY S. TRUMAN VAMC

RELOCATE CLC

800 HOSPITAL DRIVE COLUMBIA, MO

05/11/2018 DM CR II EM

589-335

G-002

BID DOCUMENTS

VA255-16-C-0234

DRAWING INDEX

DRAWING NUMBER DRAWING TITLE

M-603 MECHANICAL CONTROLS

M-604 MECHANICAL CONTROLS

09 ELECTRICAL

E-001 ELECTRICAL NOTES AND TABLES

E-002 ELECTRICAL SYMBOLS AND ABBREVIATIONS

EC-100 ELECTRICAL UNDERGROUND POWER AND NETWORK CONDUIT

PLAN

EC-101 ELECTRICAL NETWORK CONDUIT PLAN-FIRST FLOOR

EC-102 ELECTRICAL NETWORK CONDUIT PLAN-SECOND FLOOR

EG-100 ELECTRICAL GROUNDING PLAN

EG-101 ELECTRICAL LIGHTNING PROTECTION PLAN-ROOF

EP-100A ELECTRICAL POWER PLAN-BASEMENT FLOOR

EP-100B ELECTRICAL HVAC POWER PLAN-BASEMENT FLOOR

EP-101A ELECTRICAL POWER PLAN-FIRST FLOOR

EP-101B ELECTRICAL HVAC POWER PLAN-FIRST FLOOR

EP-102 ELECTRICAL POWER PLAN-ROOF

EL-100 ELECTRICAL LIGHTING PLAN-BASEMENT FLOOR

EL-101 ELECTRICAL LIGHTING PLAN-FIRST FLOOR

EL-101 (BI-6) ELECTRICAL LIGHTING PLAN - FIRST FLOOR - BID ITEM 6

ESD-100 ELECTRICAL SITE LIGHTING DEMOLITION PLAN

ESL-100 ELECTRICAL SITE LIGHTING PLAN

ET-101 COMMUNICATION AND TECHNOLOGY PLAN - FIRST FLOOR

EF-100 ELECTRICAL FIRE ALARM & SECURITY PLAN-BASEMENT FLOOR

EF-101 ELECTRICAL FIRE ALARM & SECURITY PLAN-FIRST FLOOR

EF-102 ELECTRICAL SECURITY PLAN-EXTERIOR

EN-101 ELECTRICAL NURSE CALL PLAN-FIRST FLOOR

E-501 ELECTRICAL SINGLE LINE DIAGRAM

E-502 ELECTRICAL SINGLE LINE DIAGRAM

E-701 LIGHTING FIXTURE SCHEDULE

E-702 ELECTRICAL PANEL SCHEDULE

E-703 ELECTRICAL PANEL SCHEDULE

E-704 ELECTRICAL PANEL SCHEDULE

E-801 ELECTRICAL TYPICAL INSTALLATION DETAILS

E-802 ELECTRICAL TYPICAL INSTALLATION DETAIL

E-803 ELECTRICAL GROUNDING SYSTEM DETAIL

E-804 ELECTRICAL TYPICAL SECURITY RISER AND DETAILS

E-805 ELECTRICAL TYPICAL FIRE ALARM SYSTEM RISERS AND DETAILS

T-801 TECHNOLOGY TYPICAL INSTALLATION DETAILS

E-901 REFERENCE - EXISTING SITE LIGHTING

Grand total: 202

DRAWING INDEX

DRAWING NUMBER DRAWING TITLE

A-520 CASEWORK DETAILS

A-521 CASEWORK DETAILS

A-522 CASEWORK DETAILS

A-601 DOOR AND HARDWARE SCHEDULE & DETAILS

A-602 DOOR & FRAME DETAILS

A-610 CURTAIN WALL ELEVATIONS & GLAZING SCHEDULE

A-611 CURTAIN WALL EXTERIOR ELEVATIONS

A-612 STOREFRONT & CURTAIN WALL INTERIOR & EXTERIOR ELEVATIONS

05 INTERIORS

I-101 FIRST FLOOR - FINISH PLAN

I-300 BASEMENT FLOOR - SIGNAGE PLAN

I-301A PARTIAL FIRST FLOOR - SIGNAGE PLAN - A

I-301B PARTIAL FIRST FLOOR - SIGNAGE PLAN - B

I-301C PARTIAL FIRST FLOOR - SIGNAGE PLAN - C

I-310 SIGN TYPES & SIGNAGE MOUNTING HEIGHTS

I-311 SIGN TYPES

I-312 SIGNAGE SCHEDULES & DETAIL ELEVATIONS

I-600 FINISH SCHEDULE & FINISH LEGEND

I-601 FINISH DETAILS

06 FIRE PROTECTION

FP-001 FIRE PROTECTION SYMBOLS, NOTES, AND SCHEDULES

FP-101 FIRE PROTECTION BASEMENT FLOOR PLAN

FP-102 FIRE PROTECTION FIRST FLOOR PLAN

07 PLUMBING

MG-001 MEDICAL GAS GENERAL NOTES AND SYMBOLS

MG-101 BASEMENT FLOOR PLAN - MEDICAL GAS PLAN

MG-101 (B.I. 5/8) BASEMENT FLOOR PLAN - MEDICAL GAS PLAN - BID ITEM 5+8

MG-102 FIRST FLOOR PLAN - MEDICAL GAS PLAN

MG-102 (B.I. 8) FIRST FLOOR PLAN - MEDICAL GAS PLAN - BID ITEM 8

MG-103 MEDICAL OXYGEN BUILDING 1 AND UNDERGROUND PLAN

MG-401 MEDICAL GAS DETAILS

P-001 PLUMBING GENERAL NOTES AND SYMBOLS

P-100U UNDERGROUND FLOOR PLAN - PLUMBING PLAN

P-100U (B.I. 8) UNDERGROUND FLOOR PLAN - PLUMBING PLAN - BID ITEM 8

P-100 BASEMENT FLOOR LEVEL - SANITARY & STORM PLUMBING PLAN

P-100 (B.I. 5/8) BASEMENT FLOOR LEVEL - SANITARY & STORM PLUMBING PLAN -

BID ITEM 5+8

P-101 BASEMENT FLOOR LEVEL - DOMESTIC WATER PLUMBING PLAN

P-101 (B.I. 5/8) BASEMENT FLOOR LEVEL - DOMESTIC WATER PLUMBING PLAN - BID

ITEM 5 & 8

P-102 FIRST FLOOR PLAN - PLUMBING PLAN

P-102 (B.I. 8) FIRST FLOOR PLAN - PLUMBING PLAN - BID ITEM 8

P-103 ROOF LEVEL PLAN - PLUMBING PLAN

P-201 PLUMBING SANITARY PIPING DIAGRAM

P-202 PLUMBING DOMESTIC WATER PIPING DIAGRAM

P-301 PLUMBING DETAILS

P-302 DOMESTIC HOT WATER PIPING & PLUMBING FIXTURE DESCRIPTION

08 MECHANICAL

M-001 MECHANICAL GENERAL NOTES AND SYMBOLS

MV-101 BASEMENT FLOOR PLAN - MECHANICAL VENTILATION PLAN

MV-102A PARTIAL FIRST FLOOR - MECHANICAL VENTILATION PLAN - A

MV-102B PARTIAL FIRST FLOOR - MECHANICAL VENTILATION PLAN - B

MV-102C PARTIAL FIRST FLOOR - MECHANICAL VENTILATION PLAN - C

MV-102B BI-5/6 PARTIAL FIRST FLOOR - MECHANICAL VENTILATION PLAN - B - BID

ITEM 5+6

MV-103 ROOF LEVEL PLAN - MECHANICAL VENTILATION PLAN

MP-100 MECHANICAL UNDERGROUND PIPING PLAN

MP-101 BASEMENT FLOOR PLAN - MECHANICAL PIPING PLAN

MP-102A PARTIAL FIRST FLOOR - MECHANICAL PIPING PLAN - A

MP-102B PARTIAL FIRST FLOOR - MECHANICAL PIPING PLAN - B

MP-102C PARTIAL FIRST FLOOR - MECHANICAL PIPING PLAN - C

MP-201 ENLARGED BASEMENT FLOOR PLAN - MECHANICAL PIPING PLAN

M-301 MECHANICAL RISER DIAGRAM AND SECTIONS

M-401 MECHANICAL DETAILS

M-402 MECHANICAL DETAILS

M-403 MECHANICAL DETAILS

M-404 MECHANICAL DETAILS

M-405 MECHANICAL DETAILS

M-501 MECHANICAL SCHEDULES

M-502 MECHANICAL SCHEDULES

M-503 MECHANICAL SCHEDULES

M-601 MECHANICAL CONTROLS

M-602 MECHANICAL CONTROLS

DRAWING INDEX

DRAWING NUMBER DRAWING TITLE

01 GENERAL

G-001 COVER

G-002 DRAWING INDEX

G-003 SYMBOLS, ABBREVIATIONS, & BID ITEMS - DEDUCT NARRATIVE

G-004 STANDARD MOUNTING HEIGHTS

G-005 CODE INFORMATION AND BASIS OF DESIGN PROTOCOLS

G-100 BASEMENT FLOOR - LIFE SAFETY PLAN

G-101 FIRST FLOOR - LIFE SAFETY PLAN

02 CIVIL

C-100 GENERAL NOTES, LEGEND AND EROSION CONTROL DETAILS

C-101 EXISTING CONDITIONS AND DEMOLITION PLAN

C-102 STORM WATER POLLUTION PREVENTION PLAN

C-103 SITE GRADING PLAN

C-104 SITE UTILITY PLAN

C-105 SITE GEOMETRIC PLAN

C-106 STORM SEWER PROFILES

C-107 SANITARY SEWER & UTILITY PROFILES

C-108 WATER LINE PROFILE & DETAILS

C-109 CONSTRUCTION DETAILS

C-110 CONSTRUCTION DETAILS

C-111 SEWER DETAILS

C-112 SEWER DETAILS

C-113 DRAINAGE AREA PLAN

CX-100 GENERAL NOTES, LEGEND AND EROSION CONTROL DETAILS

CX-103 SITE GRADING PLAN FOR DEDUCTS 1, 4, & 7

CX-104 SITE UTILITY PLAN FOR DEDUCTS 1, 4, & 7

CX-105 SITE GEOMETRIC PLAN FOR DEDUCTS 1, 4, & 7

CX-106 STORM SEWER PROFILES FOR DEDUCTS 1, 4, & 7

CX-107 SANITARY SEWER & UTILITY PROFILES FOR DEDUCTS 4 & 7

CX-108 WATER LINE PROFILES & DETAILS FOR DEDUCT 1

CX-109 CONSTRUCTION DETAILS FOR DEDUCT 1

CX-111 SEWER DETAILS FOR DEDUCT 1

03 STRUCTURAL

S-001 STRUCTURAL GENERAL NOTES

S-002 STRUCTURAL SPECIAL INSPECTIONS

S-003 STRUCTURAL TYPICAL FOUNDATION DETAILS

S-004 STRUCTURAL TYPICAL DETAILS

S-005 STRUCTURAL TYPICAL STEEL DETAILS

S-100 STRUCTURAL FOUNDATION BASEMENT PLAN

S-101 STRUCTURAL FOUNDATION / FIRST FLOOR FRAMING PLAN

S-102 STRUCTURAL FUTURE FLOOR & ROOF FRAMING PLAN

S-103 STRUCTURAL HIGH ROOF FRAMING & WIND GIRT PLAN

S-200 STRUCTURAL CANOPY FRAMING & DETAIL PLANS

S-300 STRUCTURAL FOUNDATION SECTIONS

S-301 STRUCTURAL FOUNDATION SECTIONS

S-302 STRUCTURAL PILASTER DETAILS

S-400 STRUCTURAL FRAMING SECTIONS

S-401 STRUCTURAL FRAMING SECTIONS

S-500 STRUCTURAL BRACE FRAME ELEVATIONS AND DETAILS

S-501 WIND GIRT FRAMING ELEVATION & DETAILS

04 ARCHITECTURAL

AS-100 SITE PLAN

AS-100 BI-2 SITE PLAN - BID ITEM 2

AS-101 PARTIAL ENLARGED SITE PLAN & DETAILS

AS-102 SITE DETAILS

A-100 BASEMENT FLOOR PLAN

A-100 BI-8 BASEMENT FLOOR PLAN - BID ITEM 8

A-100B PARTIAL BASEMENT FLOOR PLAN - B

A-100C PARTIAL BASEMENT FLOOR PLAN - C

A-101 FIRST FLOOR PLAN

A-101 BI-5/8 FIRST FLOOR PLAN - BID ITEMS 5 & 8

A-101 BI-6 FIRST FLOOR PLAN - BID ITEM 6

A-101A PARTIAL FIRST FLOOR PLAN - A

A-101B PARTIAL FIRST FLOOR PLAN - B

A-101C PARTIAL FIRST FLOOR PLAN - C

A-102 ROOF PLAN

A-120 EQUIPMENT SCHEDULE

A-122A PARTIAL FIRST FLOOR - EQUIPMENT PLAN - A

A-122B PARTIAL FIRST FLOOR - EQUIPMENT PLAN - B

A-122C PARTIAL FIRST FLOOR - EQUIPMENT PLAN - C

A-130 BASEMENT FLOOR - REFLECTED CEILING PLAN

A-131 FIRST FLOOR - REFLECTED CEILING PLAN

A-131A FIRST FLOOR - REFLECTED CEILING PLAN - A

A-131B FIRST FLOOR - REFLECTED CEILING PLAN - B

A-131C FIRST FLOOR - REFLECTED CEILING PLAN - C

A-150 ENLARGED REFLECTED CEILING DETAIL PLANS & CEILING DETAILS

A-200 EXTERIOR ELEVATIONS

A-201 EXTERIOR ELEVATIONS

A-202 BUILDING ELEVATIONS BID ITEM 5 AND 8

A-300 BUILDING SECTIONS

A-301 BUILDING SECTIONS

A-302 STAIR AND ELEVATOR DETAILS

A-400 INTERIOR ELEVATIONS & ENLARGED PLANS

A-401 INTERIOR ELEVATIONS & ENLARGED PLAN

A-402 INTERIOR ELEVATIONS

A-403 INTERIOR ELEVATIONS

A-404 INTERIOR ELEVATIONS

A-405 INTERIOR ELEVATIONS

A-406 INTERIOR ELEVATIONS

A-407 INTERIOR ELEVATIONS

A-408 INTERIOR ELEVATIONS - FIRST FLOOR & BASEMENT

A-409 INTERIOR ELEVATIONS - BASEMENT

A-410 ENLARGED FIRST FLOOR PLANS & DETAILS

A-411 ENLARGED FIRST FLOOR PLANS & DETAILS

A-430 DETAILS

A-431 DETAILS

A-432 DETAILS

A-433 COLUMN DETAILS

A-434 DETAILS

A-435 DETAILS

A-500 WALL SECTIONS & DETAILS

A-501 WALL SECTIONS AND DETAILS

A-510 PARTITION TYPES

BID DOCUMENTS 05/11/18

EARTH

GRAVEL

CONCRETE

CONCRETE MASONRY UNIT

BRICK MASONRY

STEEL/STAINLESS STEEL

ALUMINUM

PLYWOOD

HARDWOOD

RIGID INSULATION

BATT INSULATION

MORTAR/SAND/STUCCO/

GYPSUM BOARD

SURFACE

ACOUSTIC CEILING

CERAMIC TILE

MATERIAL INDICATIONS

ASPHALT DRIVE

SECTION NUMBER

DRAWING NUMBER

DETAIL NUMBER

DRAWING NUMBER

NAME OF LEVEL

HEIGHT ABOVE

PROJECT DATUM

XXX

X

XXXX

BUILDING &

WALL SECTION

EXTERIOR ELEVATION

DETAIL BUBBLE

SECTION DETAIL

INTERIOR ELEVATION

(MULTIPLE)

INTERIOR ELEVATION

(SINGLE)

PARTITION TYPE

WINDOW UNIT

NUMBER

DOOR NUMBER

ROOM TAG

ELEVATION TAG

DRAWING TITLE AND SCALE

EQUIPMENT

NUMBER

NOTE:

SEE CORRESPONDING NUMBERED LIST

ON DRAWING WHERE TAG OCCURS

UNLESS NOTED OTHERWISE.

Room name

XXX

ELEVATION

0'-0"

View Name 1/8" = 1'-0"

NORTH ARROW

N

REVISION NUMBER

X

XXXX

X

XXXX

X

XXXX

X

X

X

X

ELEVATION NUMBER AND

DRAWING NUMBER

XXXX

X

XX

X

XX

XXX REVISION

NUMBER

ROOM NAME

ROOM

NUMBER

ELEVATION

NUMBER

DRAWING NUMBER

ELEVATION

NUMBER AND

DIRECTION OF VIEW

DRAWING NUMBER

DETAIL NUMBER

DRAWING NUMBER

/ XXXXX

0 4' 8' 16'

KEYNOTE TAG

VIEW NAME

ROOM

NAME

GRAPHIC SYMBOLS

ACT ACOUSTICAL CEILING TILE

ADJ ADJACENT

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

ALT ALTERNATE

ALUM ALUMINUM

AMT AMOUNT

APPROX APPROXIMATE

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AVG AVERAGE

BAT BATTEN

BD BOARD

BLDG BUILDING

BLK BLOCKING

BM BEAM

BO BY OWNER

BOD BASIS OF DESIGN

CEM CEMENT

CG CORNER GUARD

CJ CONTROL JOINT

CL CENTER LINE

CLG CEILING

CLR CLEAR

CMU CONCRETE MASONRY UNIT

CO CONTRACTING OFFICER

COL COLUMN

CONC CONCRETE

CONT CONTINUOUS

COORD COORDINATE

COR CONTRACTING OFFICER'S REP.

CORR CORRIDOR

CPT CARPET

CT CERAMIC TILE

CTR CENTER

CTRL CONTROL

DAT DATUM

DBL DOUBLE

DEG DEGREE

DEMO DEMOLITION

DEPT DEPARTMENT

DF DRINKING FOUNTAIN

DIA DIAMETER

DIFF DIFFUSER

DIM DIMENSION

DIST DISTANCE

DN DOWN

DR DOOR

DTL DETAIL

DWG DRAWING

E EAST

EA EACH

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRIC

ELEV ELEVATOR

ENCL ENCLOSURE

EQ EQUAL

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXH EXHAUST

EXIST EXISTING

EXP EXPOSED

EXT EXTERIOR

ARCHITECTURAL ABBREVIATIONS

FA FIRE ALARM

FCO FLOOR CLEAN OUT

FD FLOOR DRAIN

FDC FIRE DEPARTMENT CONNECTION

FDN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FF&E FURNITURE, FIXTURE, AND EQUIPMENT

FHC FIRE HOSE CABINET

FIG FIGURE

FIN FINISH

FIXT FIXTURE

FL FLOOR

FO FACE OF

FP FIRE PROTECTION OR FIREPROOF

FT FOOT

FTG FOOTING

GC GENERAL CONTRACTOR

GL GLASS

GYP BD GYPSUM BOARD

GWB GYPSUM WALL BOARD

HAZ MAT HAZARDOUS MATERIALS

HDW HARDWARE

HM HOLLOW METAL

HT HEIGHT

IGU INSULATED GLAZING UNIT

INCL INCLUDED

INSUL INSULATION

INT INTERIOR

JAN JANITOR

JST JOIST

JT JOINT

J-BOX JUNCTION BOX

LAM LAMINATE

LAV LAVATORY

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LL LEAD LINED

LT LIGHT

LVT LUXURY VINYL TILE

MATL MATERIAL

MAX MAXIMUM

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MLWK MILLWORK

MO MASONRY OPENING

MR MOISTURE RESISTANT

MTD MOUNTED

MTG MOUNTING

MTL METAL

N NORTH

N/A NOT APPLICABLE

NAT NATURAL

NIC NOT IN CONTRACT

NO. NUMBER

NTS NOT TO SCALE

OA OVERALL

OC ON CENTER

OH OPPOSITE HAND

OPNG OPENING

OPT OPTIONAL

PAT PATTERN

PL PLASTIC LAMINATE

PLAM PLASTIC LAMINATE

PLAS PLASTER OR PLASTIC

PR PAIR

PRE PREFINISHED

PREP PREPARATION

PROVIDE FURNISH AND INSTALL

PT PAINT

PTME PAINT TO MATCH EXISTING

PTN PARTITION

PWR POWER

QT QUARRY TILE

QTR QUARTER

QTY QUANTITY

R RADIUS

RB RESILIENT BASE

RCP REFLECTED CEILING PLAN

REC RECESSED

RECPT RECEPTACLE

REINF REINFORCED

REQD REQUIRED

RES RESIDENT

RM ROOM

RO ROUGH OPENING

RSF RESILIENT SHEET FLOORING

S SOUTH

SAN SANITARY

SCHED SCHEDULE

SF SQUARE FOOT (FEET)

SHT SHEET

SIM SIMILAR

SPEC SPECIFICATION

SPKLR SPRINKLER

SPKR SPEAKER

SQ SQUARE

SS STAINLESS STEEL

STD STANDARD

STOR STORAGE

SUSP SUSPEND

SV SHEET VINYL

T&G TONGUE AND GROOVE

TEMP TEMPERED

TERR TERRAZZO

THK THICK

TO TOP OF ___

TS TRANSITION STRIP

TSTAT THERMOSTAT

TYP TYPICAL

UNO UNLESS NOTED OTHERWISE

VAR VARIES

VB VINYL BASE

VCT VINYL COMPOSITION TILE

VENT VENTILATION

VIF VERIFY IN FIELD

VOL VOLUME

VWC VINYL WALL COVERING

W WEST

W/ WITH

W/O WITHOUT

WC WALL COVERING

WD WOOD

WDW WINDOW

WP WALL PROTECTION

WWF WELDED WIRE FABRIC

A. BID ITEM 1, GENERAL CONSTRUCTION: Work includes general construction, alterations, roads, walks, earthworks, grading, drainage, utilities, necessary removal of existing structures and construction, fire protection, plumbing, mechanical, electrical and certain other items.

(Period of performance is 420 days after notice to proceed.)

B. BID ITEM 2 – (DEDUCT NO. 1): All work described in Bid Item 1 except deduct: Reduce Parking Area to the West by Five (5) Spaces. Eliminate retaining wall on this side and leave existing fence and office trailer in place. Eliminate fence around perimeter of future courtyard shown to the east of the new building. Eliminate perimeter security gate at the entrance along Hospital Drive. Eliminate the awning over the covered walkway. Reference contract drawing C-105.

(Period of performance is 420 days after notice to proceed.)

C. BID ITEM 3 – (DEDUCT NO. 2): All work described in Bid Item 2 except deduct: Exclude Elevator and related elevator equipment only in “Link Building Construction of the elevator shaft and coordination of structural elements required for future installation of elevator to be coordinated by GC, including but not limited to electrical conduit from electrical room to elevator shaft, and the Oil Separator and gravity line connection to the Sewer Line outside the building.

(Period of performance is 420 days after notice to proceed.)

D. BID ITEM 4 – (DEDUCT NO. 3): All work described in Bid Item 3 except deduct: Utilize 2mm Sheet Vinyl flooring (finish RSF-3 or RSF-4) in all resident rooms, (K101-K114), Living Room (K148) and Dining Room (K147). 2mm Sheet Vinyl flooring (RSF-3 or RSF-4) will be utilized in these rooms in lieu of the 5mm Sheet Vinyl with rubber padding floor finish RSF-1 and RSF-2.

(Period of performance is 420 days after notice to proceed.)

E. BID ITEM 5 – (DEDUCT NO. 4): All work described in Bid Item 4 except deduct: Exclude the “Link Building”.Remove the “Link Building”, containing the Elevator ‘P-18’, Stair ‘K053’ and Corridor ‘C0K01’ and Storage ‘K007’ on the Basement Level, and Elevator ‘P-18’, Stair ‘K153’, Corridor ‘C1K09’, Corridor ‘C1K011’ and Chapel ‘K151’ on the First Floor Level. This construction is shown on the plans as all new building construction including, and to the east of column line 8. Reference contract drawings C-105, A-100C, A-101C.

(Period of performance is 390 days after notice to proceed.)

F. BID ITEM 6 – (DEDUCT NO. 5): All work described in Bid Item 5 except deduct: All buildout work in the Administration Area and Four (4) Patient Rooms.

Exclude all furnishings, finishes, plumbing fixtures, supply lines, drain lines, vents; HVAC ductwork, grilles, manual dampers; electrical lighting fixtures, outlets, Voice/Data drops, conduit and conductors, flooring adhered to concrete, paint, etc., on the interior of the following rooms: Resident Rooms K111, K112, K113, and K114, Toilet K111A, K112A, K113A, and K114A, Medical Director Room K115, Nurse K116, Social Worker K117, MDS Room K119, Manager/Assistant Manager K120, Conference Room K121, Break Room K122, Swamp K123, Corridor C1K07, and that portion of Corridor C1K04 to the South of Column Line “K”. Room Entry Doors to the four (4) resident rooms will be installed, as well as the door from Corridor C1K02, to Corridor C1K07.

(Period of performance is 376 days after notice to proceed.)

G. BID ITEM 7 – (DEDUCT NO. 6): All work described in Bid Item 6 except deduct: Exclude Millwork (3 pieces) at the Footwall side of all Resident Rooms, including the desk unit, the drawer unit and the armoire. Reference Elevation 2/A-400, and Sections 3/A-521, 4/A-521, and 5/A-521.

(Period of performance is 376 days after notice to proceed.)

H. BID ITEM 8 – (DEDUCT NO. 7): All work described in Bid Item 7 except deduct: Exclude “Administration Area” containing one resident room, offices and staff areas on the Basement and First Floor Levels. This construction area is noted on the plans as all new building construction to the South of, but not including, Column “K”. Reference Contract Drawings A-100 (Alt) and A-101 (Alt), for the new configuration the exterior building south wall along Column “K”.

(Period of performance is 332 days after notice to proceed.)

I. BID ITEM 9 - (DEDUCT NO. 8): Shall be the cost for 1 year (365 days) of guaranteed period services for 1 elevator as further defined in the specification 14 24 00. This service contract shall start after construction final completion and acceptance. This service is to be billed monthly.

J. BID ITEM 10 – (DEDUCT NO. 9): Includes everything in Bid Item 1 & 2 with the exception of providing guaranteed period of services for elevator “P-18”.

This Bid Item will only be taken if Bid Item No. 1 and 2 are taken. Reference specification section 14 24 00.

BID ITEM - DEDUCT NARRATIVE

Drawing Title

Approved: Project Di rector

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

BANCROFT ARCHITECTS + ENGINEERS Bancroft AE No.

700 Nicholas Blvd. Suite 300 Elk Grove Village, IL 60007

T:847.952.9362 www.bancroft-ae.com Department of Veterans Affairs

VA CONTRACT NO.

Revisions: Date

KEY PLAN:

N

U :\5

-3

C ol um bi a

V A

M C

( C E

N T

R A

L)

_B

_c ro lli ns

.rv t

6/

/2

9:

:0

A

M

SYMBOLS, ABBREVIATIONS, & BID

ITEMS - DEDUCT NARRATIVE

16-123

HARRY S. TRUMAN VAMC

RELOCATE CLC

800 HOSPITAL DRIVE COLUMBIA, MO

05/11/2018 DM CR II EM

589-335

G-003

BID DOCUMENTS

VA255-16-C-0234

LC LC

LC

LC

LC

& TYPE A

ACCESSIBLE WATER CLOSET

TYPE A

TYPE B

U R

IN

A

L

S E

A T

C O

V E

R D

IS

P

E N

S E

R

M

IR

R O

R

O R

M

IR

R O

R

S H

E L F

M

IR

R O

R

O R

M

IR

R O

R

S H

E L F

O R

M E

D

IC

IN

E

C A

B

IN

E T

G R

A B

B A

R

U R

IN

A

L

G R

A B

B A

R

S T

D W

A T

E R

C L O

S E

T W

A L L

M T

D

S T

D W

A T

E R

C L O

S E

T F

L O

O R

M T

D

G R

A B

B A

R

F L O

O R

M T

D W

A T

E R

C L O

S E

T

W A

L L

M T

D W

A T

E R

C L O

S E

T

G R

A B

B A

R

G R

A B

B A

R

S A

N

IT

A R

Y N

A P

K

IN

D

IS

P O

S A

L

W A

T E

R C

L O

S E

T (W

D

IV

E

R T

E R

F L U

S H

C O

N T

R O

L

S A

N

IT

A R

Y N

A P

K

IN

D

IS

P O

S A

L

Accessible Single-Occupancy Toilet Room Minimum Clearances

T

IL

T M

IR

R

O R

T O

IL

E

T P

A P

E R

H O

L D

E R

T O

IL

E

T P

A P

E R

H O

L D

E R

E D

G E

O F

O U

T L E

T O

R W

A L L

W O

U T

L E

T

NOTE:

IN-SWINGING DOOR CANNOT

INFRINGE ON THE MINIMUM AREA

TO ACCOMMODATE A PERSON

IN A WHEEL CHAIR (ANSI 603.2.3)

BUT MAY SWING INTO THE

REQUIRED TURNING AREA.

MINIMUM AREA (30" x 48") TO

ACCOMMODATE A PERSON

IN A WHEEL CHAIR (ANSI

603.2.3)

TURNING

AREA

(304 ANSI)

INSULATE PIPES

36" GRAB BAR, PROVIDE

1/8" MIN FROM WALL TO

FACE OF ESCUTCHEON

42" LONG GRAB

BAR AT ALL

ACCESSIBLE UNITS

SURFACE

MOUNTED

TOILET PAPER

DISPENSER

TOILET

GRAB BAR, PROVIDE

1/8" MIN FROM WALL TO

FACE OF ESCUTCHEON

TOILET PAPER

DISPENSER

TOILET

PROVIDE BLOCKING FOR

FUTURE GRAB BARS IN ALL

ADAPT. UNIT BATHROOMS.

FORWARD &

PARALLEL

APPROACH

FORWARD

APPROACH

TOILET

FRONT

OF W.C.

FRONT

OF W.C.

GRAB BAR, PROVIDE

1/8" MIN FROM WALL TO

FACE OF ESCUTCHEON

TOILET PAPER

DISPENSER

PROVIDE BLOCKING FOR

FUTURE GRAB BARS IN ALL

ADAPT. UNIT BATHROOMS.

A

B

BA

7'-1" MIN. W/ 20" W. SINK

M

IN

C

L E

A R

42"

MIN. CLEAR

18"

(4.17.1)

32"

MIN. CLEAR

1'-3"

PREFERRED

18"

MIN.

M

IN

M A

X

24" MAX -

15" MIN

L A

V 2

M

IN 3

M A

X

T O

18" MIN

8" MIN

36" MIN

CLEAR

M A

X

M A

X

18"

7"-9"

12" MAX 42"

MIN

39"-41"

M

IN

M

IN

M A

X

60" MIN.

CLEAR

18"

M

IN

60" MIN.

CLEAR

18"18"

M

IN

W

/L A

V

18"

24" OR 36"

M

IN

M A

X

12" MAX 42"

MIN

7"-9"

18"15"

MIN

60" MIN.

CLEAR

48" MIN

M

IN

W /L

A V

M F

G S

T A

N D

M F

G S

T A

N D

U .O

.N

6" 36"

18"

7"-9"

M A

X

20"

M

IN

42" 12" 39"-41"

6" 36"

18"

7"-9"

M A

X

20"

M

IN

42" 12" 39"-41"

" 3

6" 36"

18"

"5" MAX

12" MAX 18" OR 42"

MIN

24" OR 36"

B E

H

IN

D T

L T

18"

NOTES:

1. MOUNTING DIMENSIONS SHOW ACCESSIBLE AND NON-ACCESSIBLE CONDITIONS. WHEN ONLY ONE OPTION IS SHOWN - ALL ITEMS IN PROJECT SHALL BE ACCESSIBLE. WHEN ITEMS CAN

BE ACCESSIBLE OR NON ACCESSIBLE DRAWINGS SHALL INDICATE LOCATION OF ACCESSIBLE ITEMS BY THIS SYMBOL:

2. COORDINATE ITEMS SHOWN ON THIS DRAWING WITH PLANS AND SPECIFICATIONS FOR ACTUAL ITEMS USED ON THIS PROJECT.

EVERY ITEM SHOWN ON THIS DRAWING MAY NOT BE USED ON THIS PROJECT.

MOUNTING DIMENSIONS (NOTE: THIS IS A "UNIVERSAL SHEET", ITEMS SHOWN MAY NOT ALL BE APPLICABLE TO THIS PROJECT)

G R

A B

B A

R

T Y

P

(RECESSED)

TOILET TISSUE DISPENSERS

(SURFACE)

TOP OF

UNIT

M

IN

T Y

P

SEAT - COVER

DISPENSER

SANITARY NAPKIN

DISPOSAL

(RECESSED - SHOWN)

F O

R C

O N

T R

O L S

M

IN

PAPER TOWEL DISPENSERS

R E

C O

M E

N D

E D

PUSH

BUTTON

R E

C O

M E

N D

E D

L A

V A

T O

R Y

M A

X A

B O

V E

M A

X O

T H

E R

L O

C A

T

IO

N S

(T O

B O

T T

O M

O F

R E

F L E

C T

IV

E

S U

R F

A C

E

SOAP

DISPENSER

HAND

DRYER

(SURFACE)

ALL FRAMED

MIRRORS

(SURFACE)

MANUAL FIRE

ALARM PULL

STATION

LIGHT

SWITCH &

DIMMER

DUPLEX

OUTLET

DUPLEX

OUTLET

DESK

INTERCOM

OUTLET

INTERCOM

STATION

TELECOMM

OUTLET

THERMOSTAT SPECIAL

PURPOSE

OUTLETS

SPECIAL

PURPOSE

OUTLETS

JUNCTION

BOX

WALL-MTD

TELEPHONE

OUTLET

COAT HOOK

(DOOR-MTD)

RACEWAY

H

IG

H R

E A

C H

M A

X

F O

R C

O N

T R

O L S

M

IN

L O

W R

E A

C H

M

IN

EQ EQ

" 5

ROBE

HOOK

(TYPICAL)

ROBE HOOK

(ACCESSIBLE)

CLOTHES

HOOK AND

BUMPER

MOP & BROOM

HOLDER

SHELF WITH

MOP & BROOM

HOLDER &

HOOKS

SHELF WITH

MOP & BROOM

HOLDER &

HOOKS

SWITCH AT

DOOR OR

CASED

OPENING

8" TYP

CARD READER,

LOCAL ALARM,

OR ARMING

STATION

AUDIBLE

AND/OR VISUAL

FIRE ALARM

SECURITY

STROBE

LIGHT

(BLUE LIGHT)

EMERGENCY

STROBE OR

LIGHT AND/OR

NURSE CALL LIGHT

FIREMAN'S

TELEPHONE

JACK

DISCONNECT

SWITCH &

MOTOR

STARTER

PRIMARY ROOM

IDENTIFICATION

SIGN (TYPE B)

MANDATORY

POLICY SIGNS

(TYPE P)

POLICIES AND

DIRECTIVES

SIGN(TYPE Q)

FIRE EQUIPMENT

IDENTIFICATION

SIGN (TYPE D)

F.E.C.

HIGH/LOW EWC

OR DRINKING

FOUNTAIN

MAX.

32" O.C.

HANDRAIL

CLOCK OR

CLOCK

OUTLET

CHALKBOARD,

TACKBOARD,

OR DRY

MARKER BOARD

MEDICAL

GAS

ALARM

PANEL

FEC OR

FHV

CABINET

ELECTRICAL

PANELBOARD

(FLUSH MTD)

ELECTRICAL

PANELBOARD

(SURFACE MTD)

COAT

HOOKS

(WALL-MTD)

R E

A C

H

M A

X H

IG

H

1' - 0"

M A

X

6"

INTERIOR WALL MTD

ROOM SIGNAGE

NURSE CALL

CORRIDOR LIGHT

EQ EQ

NURSE CALL

CORRIDOR LIGHT

(>8'-0"+ CEILING LOCATION) (<8'-0" CEILING LOCATION)

6"

R E

F E

R T

O S

C H

E D

U L E

ALIGN

HALL

LANTERN

ELEVATOR ENTRANCE

FLOOR

DESIGNATION

(BOTH JAMBS)

CALL

BUTTONS

M

IN

.T O

O R

IF

IC

E

M A

X .T

O O

R

IF

IC

E

M

IN

" 5

MAILBOX

A .F

.F

Drawing Title

Approved: Project Di rector

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

BANCROFT ARCHITECTS + ENGINEERS Bancroft AE No.

700 Nicholas Blvd. Suite 300 Elk Grove Village, IL 60007

T:847.952.9362 www.bancroft-ae.com Department of Veterans Affairs

VA CONTRACT NO.

Revisions: Date

KEY PLAN:

N

U :\5

-3

C ol um bi a

V A

M C

( C E

N T

R A

L)

_B

_c ro lli ns

.rv t

6/

/2

9:

:0

A

M

STANDARD MOUNTING HEIGHTS

16-123

HARRY S. TRUMAN VAMC

RELOCATE CLC

800 HOSPITAL DRIVE COLUMBIA, MO

05/11/2018 DM CR II EM

589-335

G-004

BID DOCUMENTS

VA255-16-C-0234

STANDARD MOUNTING HEIGHTS

A. ACCESSIBLE MAIN ENTRY

B. ACCESSIBLE ROUTE FROM ENTRY TO ELEVATOR LOBBY & ACCESSIBLE ELEVATOR

TO ALL FLOORS

C. ACCESSIBLE UNISEX TOILET ROOMS

D. ACCESSIBLE HI-LO DRINKING FOUNTAINS.

E. ALL CONTROLS AND OPERABLE PARTS FULLY COMPLY AND ARE BETWEEN 15" AND 48".

F. ALL SIGNAGE COMPLIES - IS OF BRAILLE AND TACTILE AND IS LOCATED ON THE DOOR HANDLE

SIDE OF DOOR. INSTALLED AT APPROPRIATE HEIGHT AND DISTANCE FROM DOOR FRAME.

G. ALL STORAGE AREAS FULLY COMPLY - CLOSET RODS, WALL MOUNTED CABINETRY

AND ANY TYPE OF SHELVING IS AT 48" ABOVE FINISH FLOOR TO TOP OF BOTTOM SHELF.

ARCHITECTURAL BARRIERS ACT (ABA) COMPLIANCE

CODE COMPLIANCE

APPLICABLE CODES

A. VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD

APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL INFORMATION LIBRARY

(TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).

B. INTERNATIONAL BUILDING CODE (IBC) 2015.

C. NFPA 101 LIFE SAFETY CODE 2015.

D. NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900.

E. OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.

F. VA SEISMIC DESIGN REQUIREMENTS, H-18-8.

G. NATIONAL ELECTRICAL CODE (NEC) 2014.

H. INTERNATIONAL PLUMBING CODE (IPC) 2015.

I. ASME BOILER AND PRESSURE VESSEL CODE 2010.

J. ASME CODE FOR PRESSURE PIPING.

K. ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS) INCLUDING VA

SUPPLEMENT, BARRIER FREE DESIGN GUIDE (PG-18-13).

L. BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, AMERICAN CONCRETE

INSTITUTE AND COMMENTARY (ACI 318).

M. INTERNATIONAL ENERGY CONSERVATION CODE (IECC) 2015.

BASIS OF DESIGN - PROTOCOLS

THE BASIS OF DESIGN (BOD) PROTOCOLS APPLY TO ALL SPECIFIED EQUIPMENT, CONSTRUCTION MATERIALS INDICATED AND ALL ASSEMBLY DETAILS CONTAINED WITHIN THE DRAWINGS/ DOCUMENTS

OR AS SPECIFICALLY REFERENCED BY SAME. EQUIPMENT AND MATERIAL PERFORMANCE

CHARACTERISTICS ALONG WITH ALL DIMENSIONAL LOGISTICS FEATURES THAT AFFECT SIZE,

PLACEMENT, REQUIRED CLEARANCES, SPACING, SERVICE ACCESS, DETAILING AND CONNECTION VARIANCES, UTILITIES IMPACTS, HEIGHT, FINISHING (IF REQUIRED), AVAILABILITY, ETC., WHICH NEED TO BE IDENTIFIED TO THE COR AND ALL AFFECTED SUBCONTRACTORS AND BE FULLY COORDINATED BY

THE PRIME CONTRACTOR IF DIFFERENT FROM THE BID/ CONSTRUCTION DOCUMENTS.

BASIS OF DESIGN COMPLIANCE:

1. CONTRACTOR SHALL BE RESPONSIBLE TO VERIFY AND CERTIFY THAT THE CHARACTERISTICS OF

THE EQUIPMENT OR MATERIAL HE/SHE WILL BE SUBMITTING FOR REVIEW MEETS OR EXCEEDS

THE CAPACITY AND DUTY REQUIREMENTS AS SPECIFIED IN ANY OF THE "BASIS OF DESIGN"

SPECIFICATIONS.

2. IF THE EQUIPMENT OR MATERIAL BEING SUBMITTED FOR REVIEW WILL REQUIRE THAT

MODIFICATIONS NEED TO BE MADE, TO THE WORK OF THE PROVIDING CONTRACTOR OR THE

WORK OF OTHER CONTRACTORS, THE SUBMITTING CONTRACTOR SHALL BE FULLY

RESPONSIBLE TO ADVISE/ INFORM THE PRIME CONTRACTOR OF ANY AND ALL SUCH NECESSARY

IMPACTS AND POSSIBLE DELAYS AND/OR COSTS AS A PART OF THEIR BID AND CONSTRUCTION

SCOPE OF WORK RESPONSIBILITIES.

3. THE SUBMITTING CONTRACTOR WILL BE FULLY RESPONSIBLE TO COORDINATE ALL DEVIATIONS

FROM THE "BASIS OF DESIGN" INTENT WITH THE GENERAL CONTRACTOR AND ALL AFFECTED

SUB-CONTRACTORS. THE FINAL INSTALLATION SHALL NOT COMPROMISE ANY OF THE "BASIS OF

DESIGN" PERFORMANCE CHARACTERISTICS NOR SHALL IT ENCUMBER ANY OF THE DESIGN

LAYOUT LOGISTICAL NECESSITIES.

4. THE FINAL INSTALLATION SHALL ALSO COMPLY WITH ALL APPLICABLE BUILDING CODES,

REGULATIONS, VA REQUIREMENTS PLUS ALLOW THE EQUIPMENT AND/OR MATERIALS TO

FUNCTION PROPERLY AND SAFELY.

5. ALL MATERIALS OR EQUIPMENT EQUIVALENT SUBSTITUTIONS SHALL BE PROVIDED ON A

CONTRACTOR PREPARED ITEMIZED LISTING PER SUBSTITUTION WITH A FULL AND DETAILED

DESCRIPTION OF ALL SPECIFICATIONS AND KNOWN DEVIATIONS FROM THE ORIGINAL BASIS OF

DESIGN.

6. THE PRIME/GENERAL CONTRACTOR SHALL NOTIFY AND COORDINATE WITH THE COR AT THE

BEGINNING OF THE PROJECT, ALL SUCH KNOWN DEVIATIONS AND IMPACTS FROM THE SPECIFIC BASIS OF DESIGN SPECIFICATIONS BEFORE STARTING THE PROJECT AND/OR THE SHOP DRAWING

SUBMITTAL.

7. IF ANY UNKNOWN DEVIATIONS FROM THE BOD REQUIREMENTS SURFACE DURING THE

CONSTRUCTION PHASE, NOTIFY THE COR IMMEDIATELY AND IDENTIFY ALL IMPACTS FOR THE

COR'S EVALUATION AND POSSIBLE AUTHORIZATION.

PROJECT GENERAL NOTES

(APPLIES TO ALL CONTRACTORS)

1. ALL WORK SHALL BE COMPLETED ACCORDING TO ALL PUBLISHED APPLICABLE LOCAL STATE /

FEDERAL / NATIONAL CODES AND ORDINANCES ALONG WITH ALL VA DIRECTIVES, DESIGN

MANUALS, SPECIFICATIONS, STANDARDS AND REQUIREMENTS.

2. EACH CONTRACTOR SHALL HAVE PUBLIC LIABILITY, PROPERTY DAMAGE AND WORKMAN'S

COMPENSATION INSURANCE. CONSULT VA FOR ALL COVERAGE REQUIREMENTS.

3. EACH CONTRACTOR SHALL COORDINATE WITH ALL OTHER CONTRACTORS AND CHECK, PRIOR

TO COMMENCEMENT OF WORK, FOR SPACE REQUIREMENTS WITH ALL OTHER TRADES, TO

AVOID CONFLICTS.

4. RELOCATION OF DUCTS, PIPING, CONDUIT, ELECTRICAL BOXES WHICH MAY ALTER THE

ARCHITECTURAL OR STRUCTURAL CONSTRUCTION MUST BE APPROVED BY THE COR, PRIOR TO

RELOCATION.

5. MECHANICAL CONTRACT DRAWINGS SHALL BE TAKEN IN A SENSE AS DIAGRAMMATIC. SIZE & MEANS OF RUNNING PIPING ARE SHOWN BUT IT IS NOT INTENDED TO SHOW EVERY FITTING AND

OFFSET, NOR EVERY STRUCTURAL DIFFICULTY THAT CAN BE ENCOUNTERED DURING THE

INSTALLATION OF THE WORK.

6. SPECIFICATIONS AND SITE: BEFORE SUBMITTING A BID, THE BIDDERS SHALL CAREFULLY

EXAMINE THE DRAWINGS AND SPECIFICATIONS SO AS TO BE THOROUGHLY FAMILIAR WITH ALL

THE REQUIREMENTS. THE BIDDER SHALL VISIT THE SITE OF THE WORK TO BECOME

ACQUAINTED WITH ALL THE CONDITIONS AFFECTING THE CONTRACT, OBSTACLES WHICH MAY

BE ENCOUNTERED AND ALL OTHER CONDITIONS RELATIVE TO THE WORK TO BE PERFORMED:

AND, IF AWARDED THE CONTRACT, SHALL NOT BE ALLOWED ANY EXTRA COMPENSATION BY

REASON OF ANY UNFORESEEN DIFFICULTIES OR OBSTACLES WHICH THE BIDDER COULD HAVE

REASONABLY ANTICIPATED PRIOR TO BIDDING. SHOULD ANY DISCREPANCIES, ERRORS,

CONFLICT OR ITEMS NEEDING CLARIFICATION BE DISCOVERED IN THE PLANS AND/OR

SPECIFICATIONS, THE CONTRACTOR SHALL NOTIFY THE VA/CO PRIOR TO SUBMITTING A BID

AND THE VA/COR BEFORE STARTING WORK.

7. EACH CONTRACTOR SHALL MAINTAIN A COMPETENT FOREMAN OR DIRECT REPRESENTATIVE ON

THE JOB AT ALL TIMES. THE CONTRACTOR SHALL COOPERATE WITH THE SUPERINTENDENT AND

FOREMAN OF OTHER TRADES IN ORDER THAT THERE MAY NOT BE DELAY IN THE ERECTION AND

COMPLETION OF THE WORK.

SPECIAL SAFETY NOTICE

1. ALL CONTRACTORS, SUBCONTRACTORS AND THEIR REPRESENTATIVES WORKING ON THIS

PROJECT SHALL AT ALL TIMES PRIOR AND DURING THE COURSE OF THEIR ACTIVITY BE

RESPONSIBLE FOR THE SAFETY OF THEIR EMPLOYEES AS WELL AS ALL OTHERS AND IN THE

CARE OF THE PROPERTY.

2. EACH CONTRACTOR OR SUBCONTRACTOR, AS REPRESENTATIVES OF THEIR EMPLOYEES,

SHALL ASCERTAIN THAT THE CONDITIONS UNDER WHICH THEY WILL BE REQUIRED TO

ACCOMPLISH THEIR WORK ARE SAFE AND MEET ALL REGULATIONS OF THE OCCUPATIONAL

SAFETY AND HAZARD ACT OR OTHER GOVERNING REGULATIONS AND ALL VA REQUIREMENTS.

THE BEGINNING OF WORK BY A CONTRACTOR OR SUBCONTRACTOR SHALL INDICATE

SATISFACTION CONCERNING SAFETY AND FULL RESPONSIBILITY FOR ACCIDENTS, INJURIES,

AND/OR DAMAGES.

3. IF UNSATISFIED, THE CONTRACTOR OR SUBCONTRACTOR SHALL INDICATE THE ACTIONS

AND/OR DEVICES NECESSARY TO RENDER THE JOB-SITE SAFE. IF THE WORK OF OTHER

PARTIES IS, UPON INSPECTION, FOUND AT ANY TIME TO BE UNSAFE THE CONTRACTOR OR

SUBCONTRACTOR SHALL IMMEDIATELY STOP ALL WORK AND NOTIFY THE GENERAL

CONTRACTOR AND THE COR. THE BID SUBMISSIONS AND BEGINNING OF WORK SHALL

INDICATE ACKNOWLEDGMENT AND ACCEPTANCE OF THESE REQUIREMENTS.

FIRE RESISTIVE RATINGS

HAZARDOUS AREA SEPARATION PROTECTION

BUILDING DATA

PROJECT INFORMATION

AUTOMATIC SPRINKLER SYSTEM REQUIREMENT

COMMON PATH TRAVEL DISTANCE

ROOF CONSTRUCTION

DEAD END CORRIDORS

TRAVEL DISTANCE TO EXITS

EXITING REQUIREMENTS

EXTERIOR NON-BEARING WALLS

COLUMNS, BEAMS, GIRDERS, TRUSSES

FLOOR CONSTRUCTION

EXTERIOR BEARING WALLS

INTERIOR BEARING WALL

APPLICABLE CODE

USE/OCCUPANCY (FIRE AREA)

BUILDING

1-HOUR

100 FT.

30 FT.

100 FT.

200 FT.

30 FT.

1-HOUR REQUIRED

2-HOUR PROVIDED

1-HOUR REQUIRED

2-HOUR PROVIDED

YES YES

NFPA 101, 2015IBC, 2015

HEALTH CARE

BUILDING FULLY SPRINKLED

STANDPIPE SYSTEM REQUIREMENT CLASS I

1-HOUR REQUIRED

2-HOUR PROVIDED

1-HOUR REQUIRED

2-HOUR PROVIDED

(MOST RESTRICTIVE APPLIES)

200 FT.

< 5 FEET 1-HOUR

< 10 FEET 1-HOUR

<= 30 FEET 1-HOUR

> 30 FEET 0-HOUR (SEPARATION DISTANCE)0-HOUR (>40f t. SEPARATION)

STORAGE ROOMS > 100 SF

STORAGE ROOMS > 50 SF < 100 SF

1-HOUR

1-HOUR 1-HOUR

1-HOUR

APPLICABLE CODE

ACTUAL HEIGHT

ACTUAL AREA (FIRST FLOOR) (BUILDING FOOTPRINT)

NFPA 101, 2015IBC, 2015

14'-0"/1 STORY ABOVE GRADE

17,665 SF

AUTOMATIC SPRINKLER INCREASE

MAXIMUM ALLOWABLE HEIGHT

ALLOWABLE HEIGHT

CONSTRUCTION TYPE

USE GROUP

APPLICABLE CODE

USE/OCCUPANCY (FIRE AREA)

BUILDING

TYPE II -A TYPE II (111)

I-2; INSTITUTIONAL

HEALTHCARE

CH.18; NEW

NFPA 101, 2015IBC, 2015

HEALTHCARE

(504.2)

(S.F. /FLOOR)MAXIMUM ALLOWABLE AREA 45,000 SF

2 STORIES

3 STORIES

BUILDING FULLY SPRINNKED

GENERAL BUILDING INFORMATION

1. CONSTRUCTION CLASSIFICATION: TYPE II -A

2. AUTOMATIC FIRE SUPPRESSION: ALL AREAS IN ACCORDANCE WITH NFPA 13- 2016 EDITION

3. HEALTHCARE HOSPITAL: 181.2.1

4. OCCUPANCIES CLASSIFICATION: IBC GROUP I-2 OCCUPANCY

1-HOUR REQUIRED

2-HOUR PROVIDED

(BASEMENT FLOOR)

SOILED LINEN ROOMS 1-HOUR 1-HOUR

SHAFT ENCLOSURES (LESS THAN 4 ST.) 1-HOUR 1-HOUR

STAIRWAY (LESS THAN 4 ST.) 1-HOUR

1-HOUR

8,045 SF

OCCUPANT LOADS (FIRST FLOOR-HEALTHCARE) 17,418 SF/120 SF PER PERSON = 147 OCC.

EGRESS REQUIREMENTS

APPLICABLE CODE NFPA 101, 2015IBC, 2015

STAIR WIDTH 44 INCHES 44 INCHES

(BASEMENT FLOOR-

ACCESSORY STORAGE, MECH. EQUIPMENT ROOM)

8,045 SF/300 SF PER PERSON = 26 OCC.

V A

R

IE

S

M

IN

8' - 0"

WOOD STRIPS

BRACING. SEE

CONSTRUCTION

SIGN DETAIL

4"x4" POST IF SIGN IS

INSTALLED ON GRADE

FINISH GRADE

MDO PLYWOOD OR

ALUMINUM SIGN PANEL

HARRY S. TRUMAN MEMORIAL

VETERANS HOSPITAL

CONSTRUCTION FIRM NAME

CITY, STATE

GENERAL CONTRACTOR

BANCROFT ARCHITECTS + ENGINEERS

ELK GROVE VILLAGE, IL

ARCHITECT ENGINEER

VA Office of Construction & Facilities Management

NOTE:

SURFACE APPLIED VINYL

OR SCREENED GRAPHICS

ALL TYPOGRAPHY TO BE

HELVETICA BOLD IN BLACK

VA LOGO WITH BLUE

BACKGROUND AND WHITE FONT

/2

/2

/2

/2

M

IN

M

IN

4' - 0"

HAS WORKED DAYS00 0

WITHOUT A LOST TIME ACCIDENT

GENERAL CONTRACTOR'S NAME

THE LIFE YOU SAVE MAY BE YOUR OWN

/4

BRACING. SEE

CONSTRUCTION SIGN

DETAIL

4"x4" POST

IF SIGN IS INSTALLED

ON GRADE

FINISH GRADE

ERZ

IN ON SAFETY

MDO PLYWOOD OR

ALUMINUM SIGN PANEL

NOTE:

SURFACE APPLIED VINYL

OR SCREENED GRAPHICS

ALL TYPOGRAPHY TO BE

HELVETICA BOLD IN BLACK

VA LOGO WITH BLUE

BACKGROUND AND

WHITE FONT

Drawing Title

Approved: Project Di rector

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

BANCROFT ARCHITECTS + ENGINEERS Bancroft AE No.

700 Nicholas Blvd. Suite 300 Elk Grove Village, IL 60007

T:847.952.9362 www.bancroft-ae.com Department of Veterans Affairs

VA CONTRACT NO.

Revisions: Date

KEY PLAN:

N

U :\5

-3

C ol um bi a

V A

M C

( C E

N T

R A

L)

_B

_c ro lli ns

.rv t

6/

/2

9:

:0

A

M

CODE INFORMATION AND BASIS OF

DESIGN PROTOCOLS

16-123

HARRY S. TRUMAN VAMC

RELOCATE CLC

800 HOSPITAL DRIVE COLUMBIA, MO

05/11/2018 DM CR II EM

589-335

G-005

BID DOCUMENTS

VA255-16-C-0234

BID DOCUMENTS 05/11/18

3/4" = 1'-0"

CONSTRUCTION SIGN

1 1/2" = 1'-0"

SAFETY CONSTRUCTION SIGN

0 1' 2'

0 1' 2' 3'

81'-0"

75'-0"

75'-0"

58'-0"

STORAGE

K006

STORAGE

K002

ELEC.

ROOM

K003

MED.

GAS

EQUIPMENT

ROOM

K004

CORRIDOR

C0K03

LOADING

K005

MECHANICAL

K001

CORRIDOR

C0K01

STAIR

K053

ELEV

P-18

U N

E X

C A

V A

T E

D

UNEXCAVATED

STORAGE

K007

SYMBOLS LIST

PARTITION LEGEND

FIRE/SMOKE BARRIER (1HR)

FIRE BARRIER (1 HR)

FIRE BARRIER (2 HR)

0'-0"

EGRESS PATH AND DISTANCE

EXIT DIRECTION

FIRE EXTINGUISHER

Drawing Title

Approved: Project Di rector

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

BANCROFT ARCHITECTS + ENGINEERS Bancroft AE No.

700 Nicholas Blvd. Suite 300 Elk Grove Village, IL 60007

T:847.952.9362 www.bancroft-ae.com Department of Veterans Affairs

VA CONTRACT NO.

Revisions: Date

KEY PLAN:

N

U :\5

-3

C ol um bi a

V A

M C

( C E

N T

R A

L)

_B

_c ro lli ns

.rv t

6/

/2

9:

:1

A

M

BASEMENT FLOOR - LIFE SAFETY PLAN

16-123

HARRY S. TRUMAN VAMC

RELOCATE CLC

800 HOSPITAL DRIVE COLUMBIA, MO

05/11/2018 DM CR II EM

589-335

G-100

BID DOCUMENTS

VA255-16-C-0234

N

1/8" = 1'-0"

BASEMENT FLOOR - LIFE SAFETY PLAN

4'0 8' 16'

SYMBOLS LIST

PARTITION LEGEND

FIRE/SMOKE BARRIER (1HR)

FIRE BARRIER (1 HR)

FIRE BARRIER (2 HR)

0'-0"

EGRESS PATH AND DISTANCE

EXIT DIRECTION

FIRE EXTINGUISHER

RES. RM.

K103

CORRIDOR

C1K01

RES. RM.

K101

TOILET

K101A

RES. RM.

K104

RES. RM.

K105

RES. RM.

K107

RES. RM.

K106

RES. RM.

K108

RES. RM.

K109

RES. RM.

K110

RES. RM.

K111

RES. RM.

K112

RES. RM.

K113

RES. RM.

K114

SWAMP

K123

BREAK

RM.

K122

CONF.

RM.

K121

MED.

DIRECT

K115 NURSE

K116

SOCIAL

WORKER

K117 MDS

K119

MANAGER/

ASSISTANT

MANAGER

K120

IT/COMM.

K136

LAUNDRY

K135

BATH

SUITE

K134

MEN'S

TOILET

K137

WOMEN'S

TOILET

K138HOUSE

KEEPING

K139

STORAGE

K140CLEAN/

MEDS

K142

SOILED

UTILITY

K141

MED.

SUPPLY

RM.

K143

PANTRY

K144

KITCHEN

K145 STORAGE

K146

CONCIERGE

K100

COPY/SUPPLY

RM.

K131

STAFF

TOILET

K133

LOCKERS

K132 CORRIDOR

C1K04

CORRIDOR

C1K07

CORRIDOR

C1K03

LIVING

K148

DINING

K147

BISTRO

K149

VESTIBULE

K100B

ACTIVITY

RM.

K150

SALON

K130

CORRIDOR

C1K05

VESTIBULE

K100A

GALLERIA

C1K06

ELEC.

RM.

K125

ALCOVE

K124

CORRIDOR

C1K02

RES. RM.

K102

83'-0"

84'-0" 3

49'-0" 20'-0"

58'-0"

CHAPEL

K151

CORRIDOR

C1K09

STAIR

K153

ELEV

P-18

CORRIDOR

C1K11

25'-0"

'-0

36'-0"

31'-0"

TOILET

K102A

TOILET

K103A

TOILET

K104A

TOILET

K105A

TOILET

K106A

TOILET

K107A

TOILET

K108A

TOILET

K109A

TOILET

K110A

TOILET

K111A

TOILET

K112A

TOILET

K113A

TOILET

K114A

ALCOVE

C1K01A

Drawing Title

Approved: Project Di rector

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

BANCROFT ARCHITECTS + ENGINEERS Bancroft AE No.

700 Nicholas Blvd. Suite 300 Elk Grove Village, IL 60007

T:847.952.9362 www.bancroft-ae.com Department of Veterans Affairs

VA CONTRACT NO.

Revisions: Date

KEY PLAN:

N

U :\5

-3

C ol um bi a

V A

M C

( C E

N T

R A

L)

_B

_c ro lli ns

.rv t

6/

/2

9:

:1

A

M

FIRST FLOOR - LIFE SAFETY PLAN

16-123

HARRY S. TRUMAN VAMC

RELOCATE CLC

800 HOSPITAL DRIVE COLUMBIA, MO

05/11/2018 DM CR II EM

589-335

G-101

BID DOCUMENTS

VA255-16-C-0234

N

1/8" = 1'-0"

FIRST FLOOR - LIFE SAFETY PLAN

4'0 8' 16'

File details come from the government source that posted it. Updated .