36C25519R0050-004.pdf

PDF 20 MB Posted

Attached to
657-18-301JC, Correct Pharmacy Deficiencies (VA-19-00004222)
Solicitation number
36C25519R0050
Issued by

About this file

36C25519R0050 P09 - FINAL DRAWINGS - 657-18-301JC (55 PAGES).pdf

View the file

Other files

File Type Posted
36C25519C0064-000.docx DOCX document
36C25519R0050-A0003001.pdf PDF
36C25519R0050-A0003000.docx DOCX document
36C25519R0050-A0002002.pdf PDF
36C25519R0050-A0002000.docx DOCX document
36C25519R0050-A0002001.pdf PDF
36C25519R0050-A0001001.pdf PDF
36C25519R0050-A0001000.docx DOCX document
36C25519R0050-002.pdf PDF
36C25519R0050-001.docx DOCX document
36C25519R0050-003.pdf PDF
36C25519R0050-000.docx DOCX document
Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BID ITEMS

REFERENCE SECTION 01 00 00 GENERAL REQUIREMENTS ITEM 1.3 STATEMENT OF BID ITEMS:

Alternate #1: OMIT RENOVATION OF A402. EXISTING ROOM TO BE USED AS A CONSULTATION ROOM.

Alternate #2: OMIT PHASE 4 RENOVATION WORK. STAFF LOUNGE TO BE LOCATED IN OTHER AREA AND THE

EXISTING COMPOUNDING ROOM TO BE USED AS ICE MAKER ROOM.

VICINITY MAP LOCATION MAP

VERIFY STAGING LOCATION

WITH PROJECT ENGINEER.

VA ST LOUIS HEALTH CARE SYSTEM

JOHN COCHRAN FACILITY - 4TH

FLOOR

ST LOUIS, MO 63106

1A

6A

7A

8A

8B

MAIN HOSPITAL & CLINICAL ADDITION EMERGENCY

GENERATOR VAULT

EDUCATION, MEDICAL MEDIA, CHAPEL, RESEARCH

D.H.C.P. HYPERTENSION

ENGINEERING, A.F.G.E., H.B.H.C.

DRUG DEPENDENCE TREATMENT UNIT

RESEARCH

RESEARCH

RESEARCH

RESEARCH

BOILER PLANT

CHILLER PLANT

GENERATOR

FLAG POLE

GAD METER HOUSE

GARAGE

YEATMAN WAREHOUSE

PROJECT

NORTH

TRUE

NORTH

PROJECT

LOCATION

S

AR

AH

W A

R N

E

V A

N D

E V

EN

TE

R

O N

E S

K R

U M

R E

D D

F O

XX

P

R A

IR

IE

S

PR

IN

G

A

LP

H O

N S

U S

C O

M P

T O

N

C H

A N

N

IN

G

BA

C

O N

C O

LE

M

AN

LA

FL

IN

FR

AN

C

IS

TH

E

R E

S A

G R

A N

D B

LV

D

P R

O S

P E

C T

G R

A N

D

F O

R E

S T

C H

A N

N

IN

G

W A

T E

R C

O U

R S

E

W A

Y

C O

M P

T O

N

LA

C

LE

C T

C A

R D

IN

A

L P

LC

G A

R R

IS

O

N

W A

R

IN

G

E W

IN

G

R E

P O

S T

O R

Y

W

LK

JE

FF

E R

S O

N

U N

IV

E

R S

IT

Y

R

V

T

D H

U N

T

LE

Y

LE

F

F

IN

G W

E

LL

B E

A U

M O

N T

E

LL

IO

T

C A

R D

IN

A

L

G A

R R

IS

O

N

LE

O

N A

R D

G L

A S

G O

W

LE

F

F

IN

G W

E L

L

J E

F F

E R

S O

N

E

LL

IO

T

LE

F

F

IN

G W

E

LL

G

LA

S G

O W

S

LA

T T

E R

Y

G A

R R

IS

O

N

COZENS

EVANS

GARFIELDCOTE BRILLANTEALTOINECASS

COZENS

PAGE

EVANS

COOK

FINNEYBELL

WEST BELLE PLC

CD BANKS

BELL

ENRIGHTDELMARGRANDEL SQWASHINGTON

FRANKLIN

LUCASWESTMINSTER

OLIVE

LINDELL

WEST PINE

LACLEDE

FOREST PARKCLARK

LOCUST

OLIVE

COLLEGE LA

RED MAPLE

LAWTON PLLACLEDE SUGAR

MAPLE

KNOLLS

CHESTNUT

PINE

OLIVE

ST CHARLES

LOCUST

WASHINGTON

LUCAS

DELMAR

CARR

CASS

MULLAN

HOWARD

MADISON

MAIDEN

NORTH

MONTGOMMERY

MONTGOMMERY

BELL

BELL

DR SAMUAL T SHEPPARD

ST. LOUIS

HARRIS

STOWE

STATE

COLLEGE

MARKET

COLE

DAYTON

GAMBLE

STODDARD

MILLS

JAMES COOL PAPA BELL

THOMAS

SHERIDAN

HOWARD

BRANTNER

EVANS

MADISON

MAGAZINE

YEATMAN

NORTH MARKET

BENTON

M

ARTIN LUTHER KING

SCHOOL

SCHOOL

UNIVERSITY

S P

R

IN

G S

T R

E E

T

G R

A N

D B

LV

D

DELMAR AVE.

ENRIGHT AVE.

11 8B

8A

7A

6A

1A

VACANT

BLDG.

TAXI

CO. UNION

LOCAL

PRINTING

CO.

D.A.V. STORE

6378 SF

EXAM / ON-CALL SMOKE

COMPARTMENT

7436 SF

AETC / ONCOLOGY

SMOKE COMPARTMENT

(7168 SF EXISTING)

PRE-OP / POST-OP /

OUTPATIENT (4B)

SMOKE COMPARTMENT

13,003 SF

(13,289 SF EXISTING)

ELEVATOR NO.6

E6

ELEVATOR NO.5

E5

ELEVATOR LOBBY

H406

STAIRWELL NO.1

S401

CONSULT

A402

CONSULT

A401

SURGERY WAITING

A400

CORRIDOR

H403

SERVICE ELEVATOR LOBBY

H407

MED GAS STORAGE

A445

TOILET PUBLIC

A444

23 HOUR OBSERVATION

A476

CORRIDOR

H402

STAIRWELL NO.2

S402

ELEVATOR NO.4

E4

ELEVATOR NO.3

E3

ELEVATOR NO.1

E1

HD STORAGE (-)

A456A

HD BUFFER (-)

A457A

PHARMACY

A456

ANTE (+)

A457 NON-HD BUFFER (+)

A457B

TOILET, MALE

A454 ELEC. CLOSET

A454A

STAIRWELL NO.5

S405

STAFF LOUNGE

A452

CHEMO TREATMENT ROOM

A455

CORRIDOR

H405

CHASE

CH-A-6

F.E. CLOSET

A436E

ELEC. CLOSET

A436D

ELEC. CLOSET

A436F

F.E. CLOSET

H405A

ELEC. CLOSET

A458A

STORAGE

A436C

ELEC. CLOSET

A436A

F E

EX

FE

EXEX

FE

RELOCATE 1HR SMOKE BARRIER

2FB

2FB 2FB 2FB

2FB

2FB

2FB 2FB

1SB

1SB

1SB

1SB

1SB

1FB

1FB

2FB

2FB

2FB

2FB

1SB

1FB

ST. LOUIS VA MEDICAL CENTER - JOHN COCHRAN

CORRECT PHARMACY DEFICIENCIES ON 4TH LEVEL FOR USP 800 COMPLIANCE

ST. LOUIS, MISSOURI

APPLICABLE CODES:

INTERNATIONAL BUILDING CODE - 2018 IBC

LIFE SAFETY CODE - NFPA 101, 2018 EDITION

INTERNATIONAL MECHANICAL CODE - 2015 IMC

INTERNATIONAL PLUMBING CODE - 2018 IPC

INTERNATIONAL FIRE CODE - 2018 IFC

NATIONAL ELECTRIC CODE - 2017 NEC

INTERNATIONAL ENERGY CONSERVATION CODE - 2018 IECC

BUILDING CODE ANALYSIS:

AUTOMATIC FIRE SUPPRESSION SYSTEM:

FULLY SPRINKLED THROUGHOUT (407.5)

USE GROUPS:

NON-SEPARATED MIXED USE OCCUPANCY

PRIMARY USE GROUP: I-2, INSTITUTIONAL (308.3)

INCIDENTAL USE AREAS: (TABLE 508.2)

• MECHANICAL ROOMS: 1-HOUR OR SPRINKLER SYSTEM

• STORAGE ROOMS: 1-HOUR OR SPRINKLER SYSTEM

• GROUP I-2 WASTE AND LINEN COLLECTION ROOMS: 1-HOUR

• “WHERE TABLE 508.2 PERMITS AN AUTOMATIC FIRE-EXTINGUISHING SYSTEM WITHOUT A FIRE BARRIER, THE

INCIDENTAL USE AREA SHALL BE SEPARATED FROM THE REMAINDER OF THE BUILDING BY CONSTRUCTION CAPABLE OF RESISTING THE PASSAGE OF SMOKE.” THIS REQUIRES A SMOKE PARTITION WITH NO RATING

REQUIREMENT.

SPECIAL DETAILED REQUIREMENTS FOR USE GROUP I-2: (SECTION 407)

CORRIDOR WALLS: (407.3) SMOKE PARTITIONS REQUIRED (NO RATING)

SMOKE BARRIER AREAS: (1-HOUR RATED)

MAXIMUM AREA = 22,500 S.F.

MAXIMUM TRAVEL DISTANCE = 200 FEET

CONSTRUCTION TYPE: 1A (REQUIRED SINCE BUILDING IS OVER 4 STORIES)

FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS: (TABLE 601)

• STRUCTURAL FRAME: 3-HOUR

• BEARING WALLS:

EXTERIOR: 3-HOUR

INTERIOR: 3-HOUR

• EXTERIOR NONBEARING WALLS AND PARTITIONS: (TABLE 602)

FIRE SEPARATION DISTANCE > 30 FEET: 0-HOUR REQUIRED

• SHAFT ENCLOSURE: 2-HOUR

• FLOOR CONSTRUCTION: 2-HOUR

• ROOF CONSTRUCTION: 1 ½ HOUR

COMBUSTIBLE MATERIAL IN TYPE 1 CONSTRUCTION:

FIRE-RETARDANT TREATED WOOD ALLOWED IN:

NONBEARING PARTITIONS IF FIRE RATING < 2-HOURS

NONBEARING EXTERIOR WALLS IF NO FIRE RATING REQUIRED

FIRE-RETARDANT TREATED WOOD NOT ALLOWED IN ROOF CONSTRUCTION

THERMAL AND ACOUSTICAL INSULATION: MAXIMUM FLAME SPREAD INDEX = 25

ALLOWABLE / ACTUAL FLOOR AREA AND BUILDING HEIGHT: (TABLE 503)

ALLOWABLE AREA: UNLIMITED

ALLOWABLE HEIGHT: UNLIMITED

ACTUAL HEIGHT: 9 STORIES, 130 FEET

FIRE DOOR RATINGS: TABLE 715.4)

2-HOUR FIRE BARRIER AT STAIRS: 1 1/2 HOUR RATED DOOR. CLOSER, LATCH, AND SMOKE SEAL REQUIRED.

1-HOUR FIRE BARRIER: 3/4 HOUR RATED DOOR (45 MIN.) CLOSER, LATCH & SMOKE SEAL REQUIRED.

1-HOUR SMOKE BARRIER: 1/3 HOUR RATED DOOR (20 MIN.) CLOSER, LATCH & SMOKE SEAL REQUIRED.

1-HOUR FIRE PARTITION: 1/3 HOUR RATED DOOR (20 MIN.) NO SMOKE SEAL REQUIRED. CLOSER, & LATCH REQUIRED.

SMOKE PARTITIONS: NO DOOR RATING REQUIRED. NO CLOSER REQUIRED. LATCH & SMOKE SEAL REQUIRED.

BUILDING CODE SUMMARY

OCCUPANT LOAD: (TABLE 1004.1.1)

ACCESSORY STORAGE AND MECHANICAL ROOMS: 300 SF/PERSON (GROSS)

INSTITUTIONAL INPATIENT TREATMENT AREAS: 240 SF/PERSON (GROSS)

OFFICE AREAS: 100 S.F./PERSON (GROSS)

ROOF FIRE CLASSIFICATION: CLASS B ROOF ASSEMBLY (TABLE 1505.1)

MEANS OF EGRESS:

“MULTIPLE MEANS OF EGRESS SHALL BE SIZED SUCH THAT THE LOSS OF ANY ONE MEANS OF EGRESS SHALL NOT REDUCE THE AVAILABLE CAPACITY TO LESS THAN 50% OF THE REQUIRED CAPACITY.” (1005.1)

MINIMUM REQUIRED EGRESS WIDTH: (TABLE 1005.1)

STAIRWAYS: 0.3 INCHES PER OCCUPANT

OTHER EGRESS COMPONENTS: 0.2 INCHES PER OCCUPANT

DOOR ENCROACHMENT: SHALL NOT REDUCE REQUIRED EGRESS WIDTH TO LESS THAN 50%. DOORS SHALL NOT

ENCROACH MORE THAN 7” INTO EGRESS WIDTH WHEN FULLY OPEN. (1005.2)

AREA OF REFUGE: (1007.6)

30” X 48” SPACE REQUIRED FOR EVERY 200 OCCUPANTS AT EACH EXIT STAIRWAY.

SMOKE BARRIER SEPARATION REQUIRED.

TWO-WAY COMMUNICATION SYSTEM REQUIRED.

DOOR WIDTH: (1008.1.1)

MINIMUM CLEAR WIDTH = 41.5 INCHES AT USE GROUP I-2 WHEN USED FOR MOVEMENT OF BEDS.

MINIMUM CLEAR WIDTH = 32 INCHES (AT OTHER LOCATIONS)

DOOR SWING: “DOORS SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE SERVING AN OCCUPANT LOAD OF 50

OR MORE PERSONS.” (1008.1.2)

PANIC HARDWARE REQUIREMENTS AT ELECTRICAL ROOMS: (1008.1.9)

“ELECTRIC ROOMS WITH EQUIPMENT RATED 1,200 AMPS OR MORE AND OVER 6 FEET WIDE… REQUIRE PANIC HARDWARE

AND DOORS SWINGING IN DIRECTION OF EGRESS.”

STAIRWAYS: (1009.1)

MINIMUM WIDTH = 44 INCHES

MAXIMUM RISER = 7 INCHES

MINIMUM RISER = 4 INCHES

MINIMUM TREAD = 11 INCHES

EXIT ACCESS:

GROUP I-2: (1014.2.2)

HABITABLE ROOMS OR SUITES IN GROUP I-2 OCCUPANCIES SHALL HAVE AN EXIT ACCESS DOOR LEADING DIRECTLY TO A

CORRIDOR. (SEE EXCEPTIONS)

COMMON PATH OF EGRESS TRAVEL: (1014.3) MAXIMUM 75 FEET

EXIT ACCESS TRAVEL DISTANCE: MAXIMUM 200 FEET (TABLE 1016.1)

CORRIDOR FIRE RESISTANCE RATING: 0-HOUR REQUIRED (TABLE 1017.1)

MINIMUM CORRIDOR WIDTH: (1017.2)

96 INCHES WHERE BED MOVEMENT REQUIRED

44 INCHES AT OTHER LOCATIONS

72 INCHES FOR SURGICAL AREAS WITH NO BED MOVEMENT

MAXIMUM DEAD END CORRIDOR: 20 FEET (1017.3)

VERTICAL EXIT ENCLOSURES: 2-HOUR RATING REQUIRED WHEN CONNECTING 4 OR MORE STORIES (1020.1)

EXIT PASSAGEWAYS: (SECTION 1021)

2-HOUR FIRE RATING

DOORS FROM NORMALLY UNOCCUPIED SPACES PROHIBITED IN EXIT PASSAGEWAYS

LIFE SAFETY LEGEND

1HR SMOKE BARRIER1SB

2HR FIRE BARRIER

1HR FIRE BARRIER

2FB

1FB

FIRE EXTINGUISHER LOCATION

FE

EX

MEANS OF EGRESS TO EXITS /

EXTERIOR OF BUILDING

EXIT

VERT. OPG. (EXIT ENCLSR/SHAFT)

FIRE BARRIER

(2 HR = 4 OR MORE STORIES)

HAZ./INCIDENTAL USE

FIRE BARRIER

STRUCTURAL ENGINEER

PLUMBING ENGINEER

SUSAN SANDERS 316.262.2500 susans@hfgarchitecture.comINTERIOR DESIGNER

JOY MARTIN-CARMICHAEL 316.262.2691 joy.martincarmichael@pec1.com

MECHANICAL ENGINEER BRIAN HENRY 316.262.2691 brian.henry@pec1.com

ELECTRICAL ENGINEER JOSH WILCOX 316.262.2691 josh.wilcox@pec1.com

DALE MCKINNEY 712.252.4014 dalem@stonegrouparchitects.comARCHITECT OF RECORD

CONTACT PHONE EMAILPOSITION

JAMES HOLT 316.262.2691 james.holt@pec1.com

INDUSTRIAL HYGIENIST GREG CHAMBLISS 314.432.8073 greg.chambliss@psiusa.com

DESIGN TEAM CONTACTS

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

SEE COVER SHEET FOR IPT MEMBERS

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

303 S. TOPEKA

WICHITA, KANSAS 63202

316.262.2691

8669 OLIVE BOULEVARD

ST LOUIS, MISSOURI 63132

314.432.8073

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

ASSOCIATE DIRECTOR

ARCHITECT/ENGINEER:

JOHN COCHRAN DIVISION

915 NORTH GRAND BLVD - ST. LOUIS, MO 63106

PLAN

NORTH

Building Key Plan: 4th LevelSeal:

TRUE

NORTH

/9

/2

:3

:1

A

M

GI001

COVER SHEET CORRECT PHARMACY DEFICIENCIES ON 4TH

LEVEL FOR USP 800 COMPLIANCE

10/9/2018 DM JN/JB

100% BIDDING DOCUMENTS

657-18-301JC

1 55

GENERAL

GI001 COVER SHEET

GI002 GENERAL NOTES, LEGENDS, AND ABBREVIATIONS

GI101 PHASING PLAN

ARCHITECTURAL

AD101 4TH LEVEL DEMOLITION FLOOR PLAN AND CEILING PLAN

AE101 4TH LEVEL FLOOR PLAN, PARTITION TYPES AND ALTERNATE PLANS

AE102 4TH & 3RD LEVEL REFLECTED CEILING PLANS

AE103 4TH LEVEL FINISH, WALL PROTECTION, SIGNAGE PLAN, AND SCHEDULE

AE104 4TH LEVEL EQUIPMENT PLAN AND SCHEDULE

AE201 EXTERIOR ELEVATION AND PARTIAL PLANS

AE401 ENLARGED PLANS AND INTERIOR ELEVATIONS

AE501 DETAILS

AE601 DOOR SCHEDULE & DETAILS

PLUMBING

PP001 PLUMBING COVER SHEET

PD101 3RD LEVEL PLUMBING DEMOLITION PLAN

PD102 4TH LEVEL PLUMBING DEMOLITION PLAN

PD111 3RD LEVEL MEDICAL GAS DEMOLITION PLAN

PD112 4TH LEVEL MEDICAL GAS DEMOLITION PLAN

PL101 3RD LEVEL PLUMBING FLOOR PLAN

PL102 4TH LEVEL PLUMBING FLOOR PLAN

PL111 4TH LEVEL MEDICAL GAS FLOOR PLAN

PL501 PLUMBING SCHEDULES

MECHANICAL

MM001 MECHANICAL COVER SHEET

MM002 MECHANICAL SYMBOLS

MD101 MECHANICAL DEMOLITION PLANS

MD102 HYDRONIC DEMOLITION PLANS

MH101 MECHANICAL FLOOR PLANS

MP101 HYDRONICS FLOOR PLANS

MP102 HYDRONICS FLOOR PLANS

M-301 MECHANICAL SECTIONS

M-501 MECHANICAL DETAILS

M-502 MECHANICAL DETAILS

M-503 MECHANICAL DETAILS

M-601 MECHANICAL SCHEDULES

M-602 MECHANICAL SCHEDULES

M-701 MECHANICAL CONTROLS

M-801 MECHANICAL DIAGRAMS

ELECTRICAL

E-001 ELECTRICAL LEAD SHEET

ED100 ELECTRICAL BASEMENT OVERALL EXISTING PLAN

ED140 ELECTRICAL 4TH LEVEL OVERALL EXISTING PLAN

ED141 ELECTRICAL 4TH LEVEL DEMOLITION PLANS

EL141 ELECTRICAL 4TH LEVEL LIGHTING PLAN

EL501 ELECTRICAL LIGHTING DETAILS AND SCHEDULES

EP141 ELECTRICAL 4TH LEVEL POWER PLAN

EP501 ELECTRICAL POWER DETAILS

EP601 ELECTRICAL POWER SCHEDULES

EY141 ELECTRICAL 4TH LEVEL SYSTEMS PLAN

EY501 ELECTRICAL SYSTEMS DETAILS AND SCHEDULES

FIRE PROTECTION

FP101 FIRE PROTECTION PLAN

U.S. DEPARTMENT OF VETERANS AFFAIRS

VA ST. LOUIS HEALTH CARE SYSTEM

JOHN COCHRAN DIVISION

100% BIDDING DOCUMENTS

10/9/2018

VA #657-18-301JC

CORRECT PHARMACY DEFICIENCIES ON

4TH LEVEL FOR USP 800 COMPLIANCE

SHEET INDEX

HAZARDOUS

HA101 HAZARDOUS MATERIALS PLANS

STRUCTURAL

SF101 GENERAL NOTES, INSPECTION TABLES AND PLAN

SF201 ELEVATION AND DETAILS

SX101 4TH LEVEL EXISTING FLOOR FRAMING PLAN (INFO ONLY)

SX102 5TH LEVEL EXISTING FLOOR FRAMING PLAN (INFO ONLY)

SX601 EXISTING COLUMN SCHEDULE (INFO ONLY)

SX602 EXISTING COLUMN SCHEDULE (INFO ONLY)

1" = 20'-0" F1

4TH LEVEL LIFE SAFETY PLAN

Revision# Description Date:

COMMON ABBREVIATIONS

SYMBOLS USED AS ABBREVIATIONS:

& AND

L ANGLE

LL DOUBLE ANGLE

@ AT

d PENNEY

# POUND OR NUMBER

Ø ROUND OR DIAMETER

ABBREVIATIONS:

A/E ARCHITECT/ENGINEER

AB ANCHOR BOLT/ROD

ABV ABOVE

AC ASPHALTIC CONCRETE/AIR

CONDITIONER

ACC ACCESSIBLE

ACM ALUMINUM COMPOSITE MATERIAL

ACOUS ACOUSTICAL

ACT ACOUSTICAL CEILING TILE

ADA AMERICANS WITH DISABILITIES ACT

ADD ADDENDUM

ADH ADHESIVE

ADJ ADJUSTABLE, ADJACENT,

ADJOINING

AFF ABOVE FINISH FLOOR

AFG ABOVE FINISH GRADE

AHJ AUTHORITY HAVING JURISDICTION

ALT ALTERNATE

ALUM ALUMINUM

ANSI AMERICAN NATIONAL STANDARDS

INSTITUTE

APC ACOUSTICAL PANEL CEILING

APPROX APPROXIMATE

ARCH ARCHITECT (URAL)

ASI ARCHITECTURAL SUPPLEMENTAL

INFORMATION

BD BOARD

BEV BEVELED

BFF BELOW FINISH FLOOR

BL BRICK LEDGE

BLDG BUILDING

BLKG BLOCK (ING)

BM BEAM

BOT BOTTOM

BO BOTTOM OF

BOC BOTTOM OF CONCRETE

BOF BOTTOM OF FOOTING

BRG BEARING

BRK BRICK

BSMT BASEMENT

BTWN BETWEEN

BUR BUILT-UP ROOFING

C CHANNEL/CELSIUS

CAB CABINET

CB CERAMIC BASE

CC CONTRACTOR

FURNISHED/CONTRACTOR

INSTALLED

CD CONSTRUCTION DOCUMENTS

CEM CEMENT

CF CUBIC FEET OR FOOT

CG CORNER GUARD

CIPC CAST-IN-PLACE CONCRETE

CJ CONTROL/CONSTRUCTION JOINT

CL CENTER LINE

CLG CEILING

CLKG CAULKING

CLR CLEAR, CLEARANCE

CMU CONCRETE MASONRY UNIT

CO CHANGE ORDER/CLEAN OUT

COL COLUMN

COMB COMBINATION

COMP COMPOSITE/COMPOSITION

CONC CONCRETE

CONN CONNECT (ION)

CONST CONSTRUCTION

CONT CONTINUOUS, CONTINUE

CONTR CONTRACT (OR)

COORD COORDINATE

CORR CORRUGATED/CORRIDOR

CPT CARPET

CPPT CARPET TILE

CSMT CASEMENT

CT CERAMIC TILE

CTB CARPET TILE BASE

CTR CENTER

D DEPTH

DBL DOUBLE

DEMO DEMOLITION, DEMOLISH

DEPT DEPARTMENT

DET DETAIL

DF DRINKING FOUNTAIN

DIA DIAMETER

DIAG DIAGONAL

DIM DIMENSION

DIV DIVIDE, DIVISION

DISP DISPENSER

DN DOWN

DR DOOR

DS DOWNSPOUT

DW DISHWASHER

DWG DRAWING (S)

DWR DRAWER

DWTR DUMBWAITER

(E) EXISTING

E EAST

EA EACH

EF EACH FACE

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRICAL

ELEV ELEVATOR

ENL ENLARGED

EMER EMERGENCY

ENGR ENGINEER

EOP EDGE OF PAVEMENT

EPDM ETHYLENE PROPYLENE DIENE

MONOMER

EPS EXPANDED POLYSTYRENE BOARD

EPT EPOXY PAINT

EQ EQUAL

EQUIP EQUIPMENT

ES EACH SIDE

EST ESTIMATE

ETC ETCETERA

ETR EXISTING TO REMAIN

EW EACH WAY

EXIST EXISTING

EXC EXCAVATE/EXCAVATION

EXH EXHAUST

EXP EXPANSION/EXPOSED

EXT EXTERIOR

EWC ELECTRIC WATER COOLER

FA FIRE ALARM

FAB FABRICATE/FABRICATION

FD FLOOR DRAIN

FDC FIRE DEPARTMENT CONNECTION

FDTN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FF FINISHED FLOOR

FFE FINISH FLOOR ELEVATION

FIN FINISH (ED)

FLOUR FLUORESCENT

FLR FLOOR (ING)

FO FACE OF

FOC FACE OF CONCRETE

FOM FACE OF MASONRY

FOS FACE OF STUD

FOF FACE OF FINISH

FR FIRE RESISTANT/FRAME

FRP FIBERGLASS REINFORCED PANEL

FS FLOOR SINK

FT FOOT, FEET/FIRE TREATED

FTG FOOTING

FURG FURRING

FUT FUTURE

GA GAGE, GAUGE

GB GRAB BAR

GC GENERAL CONTRACTOR

GALV GALVANIZED

GC GENERAL CONTRACTOR

GI GALVANIZED IRON

GL GLASS

GLU LAMGLUE LAMINATED (BEAM)

GWB GYPSUM WALL BOARD

GYP GYPSUM

HB HOSE BIB

HC HANDICAP / HOLLOW CORE

HD HEAVY DUTY

HDBD HARDBOARD

HDR HEADER

HDWD HARDWOOD

HDWR HARDWARE

HM HOLLOW METAL

HORIZ HORIZONTAL

HR HOUR

HT HEIGHT

HVAC HEATING, VENTILATION, AIR-

CONDITIONING

IBC INTERNATIONAL BUILDING CODE

ICC INTERNATIONAL CODE COUNCIL

ID INSIDE DIAMETER/DIMENSION

IFC INTERNATIONAL FIRE CODE

IN INCH(ES)

INCL INCLUDE (D), INCLUDING

INFO INFORMATION

INSP INSPECTION

INSTR INSTRUCTION(S)

INSUL INSULATE (D), INSULATION

INT INTERIOR

JAN JANITOR

JST JOIST

JT JOINT

KCJ KEYED CONSTRUCTION JOINT

KO KNOCK OUT

L LENGTH / ANGLE

LAB LABORATORY

LAM LAMINATE (ED)

LAV LAVATORY

LB POUND

LF LINEAR FEET

LH LEFT HAND

LKR LOCKER

LOC LOCATION

LONG LONGITUDINAL

LT LIGHT

LVR LOUVER

LVT LUXURY VINYL TILE

MAS MASONRY

MATL MATERIAL

MAX MAXIMUM

MC MEDICINE CABINET

MECH MECHANICAL

MEMB MEMBRANE

MEZZ MEZZANINE

MFR MANUFACTURE (R)

MIN MINIMUM

MISC MISCELLANEOUS

MO MASONRY OPENING

MR MIRROR

MTL METAL

(N) NEW

N NORTH

NA NOT APPLICABLE

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD

OPP OPPOSITE

OPG OPENING

ORIG ORIGINAL

ORD OVERFLOW ROOF DRAIN

OZ OUNCE

PAR PARALLEL

PCF POUNDS PER CUBIC FOOT

PED PEDESTAL

PERF PERFORATED

PERP PERPENDICULAR

PL PLATE

PLAM PLASTIC LAMINATE

PLYWD PLYWOOD

PNL PANEL

PR PAIR/PROPOSAL REQUEST

PRCST PRECAST CONCRETE

PREFAB PREFABRICATE

PSI POUNDS PER SQUARE INCH

PSF POUNDS PER SQUARE FOOT

PT PAINT / PRESSURE TREATED

PTD PAPER TOWEL DISPENSER

PTN PARTITION

PTR PAPER TOWEL RECEPTACLE

PVC POLYVINYL CHLORIDE

QT QUARRY TILE

R RADIUS/RISER

RB RUBBER BASE

RBR RUBBER

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

REBAR REINFORCING BAR

REC RECESSED

REF REFERENCE/REFRIGERATOR

REINF REINFORCE (D), (ING), (MENT)

REQ REQUIRE

REQD REQUIRED

RES RESILIENT FLOORING

RET RETURN

REV REVISION (S), REVISED

RFI REQUEST FOR INFORMATION

RFP REQUEST FOR PROPOSAL

RH RIGHT HAND

RL RIDGE LINE

RM ROOM

RO ROUGH OPENING

ROW RIGHT OF WAY

RVS REVERSE (SIDE)

RWL RAIN WATER LEADER

S SOUTH

SB SPLASH BLOCK

SC SOLID CORE

SCHED SCHEDULE

SCR SHOWER CURTAIN ROD

SCT SECTION

SD SOAP DISPENSER

SF SQUARE FOOT

SHT SHEET

SHTHG SHEATHING

SIM SIMILAR

SLDG SLIDING

SLNT SEALANT

SND SANITARY NAPKIN DISPENSER

SNX SANITARY NAPKIN DISPOSAL

SOG SLAB ON GRADE

SPEC SPECIFICATION (S)

SQ SQUARE

SSM SOLID SURFACE MATERIAL

SST STAINLESS STEEL

ST STREET

STC SOUND TRANSMISSION CLASS

STD STANDARD

STL STEEL

STOR STORAGE

STRUCT STRUCTURAL

SUSP SUSPENDED

SV SHEET VINYL

SW SHEARWALL

SYM SYMMETRICAL

T TREAD

T&B TOP AND BOTTOM

T&G TONGUE AND GROOVE

TB TOWEL BAR

TBD TO BE DETERMINED

TEMP TEMPORARY/TEMPERED

TER TERRAZZO

TFE TOP FOOTING ELEVATION

THD THREAD (ED) (S)

THK THICKNESS

THRU THROUGH

TKBD TACKBOARD

TL TILE

TO TOP OF

TOB TOP OF BEAM

TOC TOP OF CONCRETE/CURB

TOD TOP OF DECK

TOF TOP OF FOOTING (FOUNDATION)

TOM TOP OF MASONRY

TOP TOP OF PIER

TOJ TOP OF JOIST

TOS TOP OF SLAB/STEEL

TOW TOP OF WALL

TPD TOILET PAPER DISPENSER

TPO THERMOPLASTIC POLYOLEFIN

TPTN TOILET PARTITION

TRANS TRANSVERSE

TS TUBE STEEL

TYP TYPICAL

UG UNDERGROUND

UH UNIT HEATER

UNFIN UNFINISHED

UNO UNLESS NOTED OTHERWISE

UON UNLESS OTHERWISE NOTED

UTIL UTILITY

V SHEAR

VAR VARIES

VB VAPOR BARRIER

VC VA FURNISHED / CONTRACTOR

INSTALLED

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE

VIF VERIFY IN FIELD

VR VAPOR RETARDER

VV VA FURNISHED / VA INSTALLED

VWC VINYL WALL COVERING

W WEST/WIDTH

W/ WITH

W/O WITHOUT

WA WEDGE ANCHOR

WB WOOD BASE

WC WATER CLOSET

WD WOOD/WOODWORK

WDW WINDOW

WF (W) WIDE FLANGE

WG WALL GUARD

WH WATER HEATER

WI WROUGHT IRON

WL WIND LOAD

WP WATERPROOF (ING)

WR WATER RESISTANT

WSCT WAINSCOT

WT WEIGHT/WINDOW TREATMENT

WWF WELDED WIRE FABRIC

MEDICAL ABBREVIATIONS

ACPH AIR CHANGES PER HOUR

BSC BIOLOGICAL SAFETY CABINET

CACI COMPUNDING ASEPTIC CONTAINER

ISOLATOR

C-PEC CONTAINMENT PRIMARY

ENGINEERING CONTROL

C-SEC CONTAINMENT SECONDARY

ENGINEERING CONTROL

EPA ENVIRONMENTAL PROTECTION

AGENCY

HD HAZARDOUS DRUG

HEPA HIGH-EFFICIENCY PARTICULATE AIR

IV INTRAVENEOUS

LAFW LAMINAR AIRFLOW WORKBENCH

OSHA OCCUPATIONAL SAFETY AND

HEALTH ADMINSTRATION

PPE PERSONAL PROTECTIVE EQUIPMENT

SOP STANDARD OPERATING PROCEDURE

UPS UNINTERUPTED POWER SOURCE

SYMBOLS LEGEND

RIGID INSULATION

WOOD ROUGH (CONTINUOUS)

WOOD ROUGH (SPACED)

EARTH

CONCRETE

BLOCK WALL/VENEER

GYPSUM BOARD

PLYWOOD

BATT INSULATION

NEW CONSTRUCTION

EXISTING

CONSTRUCTION TO BE

REMOVED

DIMENSION LINE

BREAK LINE

DETAIL INDICATOR

X

X-XX

X

X-XX

BUILDING SECTION

INDICATOR

X

X-XX

X

X-XX

ELEVATION

INDICATOR, EXTERIOR

ELEVATION INDICATOR

CENTER LINE

ELEVATION INDICATOR,

INTERIOR,

X-XX

X

X-XX

X

X

X

X

NORTH ARROWXX DRAWING BLOCK TITLE

DRAWING TITLE

XX=XX

NORTH

EXISTING WALL

CG

CORNER GUARD

FEC

FIRE EXTINGUISHER

CABINET

XXX

ROOM

DOOR TAG

ROOM TAG

REVISION TAG

KEYNOTE TAG

INTERIOR PARTITION TYPES

WINDOW TAG

FURNITURE, FIXTURE, &

EQUIPMENT INDICATOR

W#

A10

CARD READERCR

CJ

CONTROL JOINT

FIRE EXTINGUISHERFE

PP

1. ALL EXISTING DUCTWORK, ELECTRICAL OR PIPING IS NOT NECESSARILY SHOWN ON

THE DRAWINGS.

2. BEFORE CONTRACTOR(S) BID THE JOB, IT IS IMPERATIVE THEY VISIT THE JOBSITE

AND FIELD VERIFY THE EXACT LOCATION OF ALL EXISTING EQUIPMENT,

DUCTWORK, ETC. IT WILL BE PART OF THE CONTRACTOR'S RESPONSIBILITY AND

COST TO ENGINEER AND RELOCATE ANY EXISTING OBSTACLES WHICH WILL

INTERFERE WITH THE CONTRACTOR'S ABILITY TO INSTALL ALL NEW OR RELOCATED

WORK ON HIS CONTRACT.

3. CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN FIELD AND NOTIFY PROJECT

ENGINEER OF ALL DISCREPANCIES IF ANY, FOUND PRIOR TO PLACEMENT OF ANY

COMPONENTS

4. THE CONTRACTOR WILL TAKE ALL NECESSARY PRECAUTIONS INCLUDING THE

BUILDING AND MAINTENANCE OF DUST TIGHT PARTITIONS, DAILY VACUUMING,

SWEEPING, AND PROVISION OF CLEAN FLOOR MATS AT THE PROJECT ENTRANCES,

TO PREVENT THE INFILTRATION OF DIRT AND DUST FROM THE CONSTRUCTION

AREAS INTO THE OWNER OCCUPIED AREAS.

5. PATCH ALL FINISHES WHERE DISTURBED BY THE WORK AND WHERE UNFINISHED

SURFACES HAVE BEEN EXPOSED BY DEMOLITION. PATCHING MUST MATCH

ADJACENT MATERIALS, COLORS, AND FINISHES. WALL SURFACES THAT ARE

PATCHED SHALL HAVE THE FINISHES (PAINT, VINYL WALL COVERING, ETC.)

REPLACED FROM CORNER TO CORNER AND FLOOR TO CEILING.

6. UNLESS OTHERWISE INDICATED FINISH ALL NEW FRAMES AND PARTITIONS TO

MATCH SURROUNDING. NEW HOLLOW METAL DOORS SHALL BE PAINTED SAME

COLOR AS FRAMES. EXISTING PARTITIONS RECEIVING NEW DOOR FRAMES THAT

HAVE VINYL WALL COVERING (VWC) SHALL HAVE THE VWC COMPLETELY REMOVED

AND REPLACED WITH NEW VWC OF MATCHING TEXTURE AND COLOR

7. PAINT ALL EXPOSED NEW AND EXISTING PIPING, CONDUIT, WIRE MOLD,

ELECTRICAL PANELS, ACCESS PANELS, ETC.,TO MATCH WALL FINISH UNLESS

OTHERWISE NOTED.

8. CORRIDOR WALLS AND PLUMBING PARTITIONS SHALL BE CONSIDERED 1 HOUR

FIRE RATED WALLS AND NEW OR EXISTING PENETRATIONS MUST BE SEALED

ACCORDINGLY WITH APPROVED FIRESTOPPING MATERIAL THE SAME DAY THE

PENETRATION IS MADE OR DISCOVERED. ALL FLOOR SLABS, VERTICAL SHAFTS

AND STAIRWELLS SHALL BE CONSIDERED 2 HOUR RATED PARTITIONS AND BE

SEALED ACCORDINGLY IN THE MANNER LISTED HEREIN. PENETRATIONS THROUGH

THE EXTERIOR WALLS SHALL BE SEALED WATERTIGHT.

9. ALL NEW VERTICAL AND HORIZONTAL DUCTS, PIPES, CONDUITS, ETC.,IN FINISHED

ROOMS OR AREAS THROUGHOUT BUILDING, NOT ENCASED IN MASONRY OR

CONCRETE CONSTRUCTION, SHALL BE FURRED IN, THE FURRING FINISHED TO

MATCH THE ROOM FINISH.

10. WHENEVER EXISTING EQUIPMENT, PIPING, DUCTS, ETC., ARE REQUIRED TO BE

REMOVED, SUCH REMOVAL SHALL INCLUDE ALL ANCHORS, HANGERS,

FOUNDATIONS, ETC., UNLESS NOTED OTHERWISE. AFTER REMOVAL; FLOORS,

WALLS, AND CEILINGS SHALL BE FINISHED TO MATCH ADJOINING SURFACES.

11. UTILITY WORK THAT WILL REQUIRE A SHUTDOWN OF EXISTING SERVICE(S) WILL BE

DONE AFTER NORMAL WORKING HOURS (NIGHTS, WEEKENDS, HOLIDAYS, ETC.) AT

NO ADDITIONAL COST TO THE GOVERNMENT. WORK MUST BE SCHEDULED WITH

THE V.A. PROJECT ENGINEER.

12. WORK THAT MUST OCCUR IN OCCUPIED AREAS, SUCH AS PUBLIC CORRIDORS, OF

THE MEDICAL CENTER OR DISRUPT A MEDICAL CENTER FUNCTION WILL BE DONE

AT TIMES OTHER THAN NORMAL WORKING HOURS (NIGHTS, WEEKENDS, HOLIDAYS,

ETC.) AT NO ADDITIONAL COST TO THE GOVERNMENT. WORK MUST BE SCHEDULED

WITH THE V.A. PROJECT ENGINEER.

13. ALL ELECTRICAL CIRCUITRY TO BE CONCEALED UNLESS OTHERWISE SPECIFIED.

CIRCUITING FOR ELECTRIC DOOR HOLD OPENS IN MASONRY WALLS SHALL BE

SURFACE RACEWAY.

14. COORDINATE ALL WORK WITH OTHER TRADES AND EXISTING CONDITIONS TO

ELIMINATE CONFLICTS AND/OR INTERFERENCES. THE CONTRACTOR SHALL

PROVIDE ALL OFFSETS, FITTINGS, TRANSITIONS, EXTENSIONS, ETC., REQUIRED FOR

A COMPLETE AND FUNCTIONAL SYSTEM.

15. DRAWINGS ARE DIAGRAMMATIC AND SHOW ONLY THE GENERAL ARRANGEMENT OF

EACH SYSTEM. BECAUSE OF SMALL SCALE OF DRAWINGS IT IS NOT POSSIBLE TO

SHOW OR INDICATE ALL BRANCHES, OFFSETS, FITTINGS, BOXES, AND

ACCESSORIES WHICH MAY BE REQUIRED. CONTRACTOR MUST CAREFULLY

INVESTIGATE STRUCTURAL AND FINISH CONDITIONS AFFECTING ALL WORK,

FURNISHING SUCH FITTINGS, TRAPS, VALVES, BOXES, ACCESSORIES, ETC., AS MAY

BE REQUIRED.

16. LOCATIONS OF NEW EQUIPMENT, PIPING, AND ASSOCIATED ITEMS SHOWN ON THE

DRAWINGS ARE SCHEMATIC ONLY. THE CONTRACTOR SHALL FIELD VERIFY EXACT

LOCATION AND ELEVATION FOR ALL WORK, INCLUDING CONNECTIONS TO EXISTING

WORK. ALL OFFSETS, FITTINGS, TRANSITIONS, EXTENSIONS, ETC., REQUIRED FOR

A COMPLETE AND FUNCTIONAL SYSTEM SHALL BE PROVIDED AT NO ADDITIONAL

COST.

17. ALL EXISTING DUCTWORK, ELECTRICAL OR MECHANICAL PIPING, CABLE TRAYS,

ETC., IS NOT NECESSARILY SHOWN ON THE DRAWINGS. BEFORE CONTRACTOR

PLACES A BID IT IS IMPERATIVE THEY VISIT THE JOBSITE AND FIELD VERIFY THE

EXACT LOCATION OF ALL EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC. IT WILL

BE PART OF THE CONTRACTOR'S RESPONSIBILITY AND THE CONTRACTOR WILL

BEAR THE COST TO ENGINEER AND RELOCATE ANY EXISTING OBSTACLES WHICH

WILL INTERFERE WITH THE CONTRACTOR'S ABILITY TO INSTALL ALL NEW OR

RELOCATED WORK IN THIS PROJECT.

18. CONTRACTOR SHALL NOT INSTALL CONDUIT, PIPING, LIGHTING, OR OTHER

OBSTRUCTIONS UNDER OR ADJACENT TO HVAC EQUIPMENT THAT WILL ELIMINATE

OR OBSTRUCT ACCESS TO COILS, MOTORS, VALVES, SWITCHES, PANELS, ETC.

19. BEFORE THE CONTRACTOR BEGINS WORK HE SHALL RECORD ANY EXISTING

SYSTEM INFORMATION SUCH AS TEMPERATURE, FLOW RATE, PRESSURE,

CURRENT, VOLTAGE, OR ANY OTHER INFORMATION NECESSARY FOR HIM TO

RETURN THE AFFECTED SYSTEM TO ORIGINAL OPERATING CONDITION. UNLESS

NOTED OTHERWISE IT IS ASSUMED THAT ALL SYSTEMS ( HVAC, ELECTRICAL,

PLUMBING, ETC.) ARE WORKING PROPERLY IN EVERY MANNER AT THE BEGINNING

OF THE PROJECT. THE CONTRACTOR'S RECORDED MEASUREMENTS MUST BE

SUBMITTED TO THE PROJECT ENGINEER FOR REVIEW AND ACCEPTANCE BEFORE

ANY DEMOLITION OR OTHER RELATED WORK CAN PROCEED.

20. FOR DOORS BEING REPLACED: IF THE EXISTING DOOR HAS SIGNAGE APPLIED TO

IT, THIS SIGNAGE SHOULD BE CAREFULLY REMOVED AND REAPPLIED TO THE NEW

DOOR. IF THE SIGNAGE IS DAMAGED DURING REMOVAL OR CANNOT OTHERWISE

BE REAPPLIED IT SHOULD BE REPLACED WITH NEW SIGNAGE OF IDENTICAL TYPE.

21. THE CONTRACTOR WILL BE RESPONSIBLE FOR MAINTAINING ALL EXISTING ACCESS

DOORS TO CONSTRUCTION AREAS, EXISTING MECHANICAL AND ELECTRICAL

AREAS, ASSIGNED STORAGE AREAS, EQUIPMENT ACCESS AREAS, ETC. DOORS

MUST BE RESTORED TO THE CONDITION ENCOUNTERED AT BEGINNING OF

PROJECT. THIS INCLUDES DOOR REPLACEMENT, HARDWARE REPLACEMENT,

HARDWARE REPAIR, DOOR REPAIR, ETC.

22. IT IS IMPORTANT THAT ALL REPLACEMENT DOORS HAVE A GAP OF LESS THAN 3/4"

BETWEEN THE BOTTOM OF THE DOOR AND THE FLOOR AT ALL POINTS.

CONTRACTOR MUST COORDINATE INSTALLED DOOR FRAME HEIGHT OR MAKE

OTHER NECESSARY MODIFICATIONS0 TO MEET THIS REQUIREMENT AND KEEP FIRE

RATING OF DOOR AND FRAME. BOTTOM SWEEPS ARE NOT ACCEPTABLE UNLESS

SPECIFICALLY STATED ON DRAWING.

23. THERE IS NO CONTRACTOR PARKING ON HOSPITAL PROPERTY AT THE JOHN

COCHRAN (JC) DIVISION. CONTRACTOR MAY LOAD AND UNLOAD MATERIALS IN

UNRESTRICTED AREAS ONLY.

24. IF THERE IS ANY WORK TO BE DONE ON EXISTING ROOFS, SUCH AS ROOF

PENETRATIONS OR STANDS, OR ANYTHING THAT DAMAGES THE INTEGRITY OF THE

ROOF, THIS WORK MUST BE DONE BY A CONTRACTOR LICENSED BY THE ROOFING

MEMBRANE MANUFACTURER. HE MUST BE APPROVED BY THE MEMBRANE

MANUFACTURER SO AS TO NOT VOID OR INTERRUPT EXISTING SINGLE PLY

MEMBRANE ROOF WARRANTIES.

25. EXISTING CIRCUITRY (CONDUIT, BOXES, WIRE, ETC.) MAY BE REUSED AT THE

CONTRACTOR'S OPTION AS LONG AS IT MEETS THE SAME SPECIFICATIONS

REQUIRED FOR NEW CIRCUITRY. ALL WORK, NEW AND EXISTING, SHALL COMPLY

WITH THE LATEST NEC CODE.

26. WHERE DOOR AND HARDWARE ARE SHOWN TO BE REMOVED, THE DOOR STOPS

ARE TO REMAIN AND BE REUSED UNLESS NOTED OTHERWISE.

CONTRACTOR NOTES

1. CONTRACTOR IS NOT AUTHORIZED TO SCALE CONSTRUCTION DOCUMENTS.

ARCHITECT IS TO BE NOTIFIED IN THE EVENT A DISCREPANCY IS FOUND IN EITHER

SPECIFICATIONS OR CONTRACT DOCUMENTS AT THE EARLIEST PRACTICAL

OPPORTUNITY.

2. GENERAL CONTRACTOR SHALL OBSERVE ALL REGULATIONS IMPOSED BY

GOVERNING BODIES.

3. CONSTRUCTION SHALL PROCEED IN AN ORDERLY AND CONTINUOUS FASHION IN

ACCORDANCE WITH THE INTERNATIONAL BUILDING CODES AND ALL OTHER

APPLICABLE CODES.

4. THE CONTRACTOR SHALL CONTAIN ALL CONSTRUCTION ACTIVITY, INCLUDING

STORAGE OF MATERIAL AND EQUIPMENT, WITHIN THE CONSTRUCTION LIMITS, AT ALL

TIMES BEING RESPONSIBLE FOR AND ABIDING BY RULES AND REGULATIONS OF THE

OWNER.

5. GENERAL CONTRACTOR TO BE RESPONSIBLE FOR REPAIRING ANY AND ALL

SURFACES DAMAGED BY HIMSELF OR SUBCONTRACTORS UNDER HIS CONTROL.

REPAIRS ARE TO MATCH EXISTING MATERIALS AND MUST BE ACCEPTABLE TO

OWNER.

6. ADEQUATELY PATCH/REPAIR TO MATCH ADJACENT CONSTRUCTION, ALL BUILDING

STRUCTURES, COMPONENTS, AND UTILITIES WHICH ARE DISTURBED AND REQUIRE

REPAIR AS A RESULT OF WORK PERFORMED UNDER THIS CONTRACT.

7. ALL FLOOR TRANSITIONS BETWEEN DIFFERENT MATERIALS SHALL BE SMOOTH AND

FLUSH (MAXIMUM SLOPE = 1/8" PER FOOT).

8. GENERAL CONTRACTOR SHALL REMOVE ALL CONSTRUCTION DEBRIS FROM JOBSITE.

ALL CONSTRUCTION DEBRIS SHALL BE CONTAINED INSIDE CONSTRUCTION LIMITS.

9. ALL WALLS WITH ITEMS SUCH AS GRAB BARS, TOILET ACCESSORIES, WOOD TRIM,

SHELVING, CASEWORK, ETC. SHALL BE REINFORCED WITH CONCEALED, FIRE

TREATED WOOD BLOCKING OR METAL STUD BLOCKING. (GENERAL CONTRACTOR TO

INSTALL BLOCKING TYP.)

10. BUILDING 1 WILL REMAIN IN PARTIAL OCCUPANCY THROUGHOUT THE CONSTRUCTION

PERIOD. THE CONTRACTOR SHALL TAKE EVERY NECESSARY PRECAUTION TO

ENSURE THE UNINTERRUPTED OPERATION OF THE FACILITY, STAFF, PATIENTS AND

VISITORS. DISRUPTION TO ADJACENT DEPARTMENTS AS WELL AS DEPARTMENTS ON

FLOORS ABOVE OR BELOW SHALL BE COORDINATED WITH THE FACILITY CONTRACT

OFFICER. THE CONTRACTOR SHALL COORDINATE ALL WORK, CONSTRUCTION,

PATHWAYS, ELEVATOR USAGE, AND UTILITY INTERRUPTION WITH THE OWNER.

11. CONTRACTOR TO EXERCISE ALL PRECAUTIONS TO PROVIDE FOR STAFF, PATIENTS,

VISITORS, AND WORKMEN'S SAFETY DURING THE PERFORMANCE OF THIS CONTRACT

PER EPA, OSHA, AND OTHER APPLICABLE CODES, STANDARDS, AND REGULATIONS.

12. THE CONTRACTOR SHALL MAINTAIN & KEEP BARRIER FREE THE EXISTING MEANS OF

EGRESS.

13. ALL GYPSUM BOARD TO BE MOISTURE/MOLD RESISTANT TYPE X.

14. THE CONTRACTOR IS RESPONSIBLE FOR CONSTRUCTION OF TEMPORARY

PARTITIONS AND TEMPORARY VENTILATION SYSTEMS AS REQUIRED TO PREVENT THE

SPREAD OF DUST FROM THE CONSTRUCTION AREA TO OCCUPIED AREAS OF THE

BUILDING. OCCUPIED AREAS SHALL REMAIN DUST FREE THROUGHOUT THE

CONSTRUCTION. THE CONTRACTOR SHALL MAINTAIN THE AFFECTED AREAS OF THE

BUILDING (INCLUDING MATERIAL TRANSPORT ROUTES) CLEAN AND DUST FREE.

15. ALL WOOD USED IN WALL CONSTRUCTION SHALL BE FIRE-RETARDANT-TREATED

LUMBER.

16. ALL WRITTEN CORRESPONDENCE WILL BE TRANSMITTED FROM SUBCONTRACTOR

THROUGH GENERAL CONTRACTOR THROUGH ARCHITECT TO OWNER. ALL PARTIES

CORRESPONDENCE ARE TO RECEIVE WRITTEN AND SIGNED COPIES OF SUCH. NO

VERBAL AGREEMENTS AFFECTING COST OR ALTERNATIVE CONSTRUCTION METHODS

AND ARRANGEMENTS WILL BE CONSIDERED VALID OR BINDING, AND ARE

THEREFORE, DISALLOWED.

17. GENERAL CONTRACTOR SHALL COMPLY WITH ALL DIRECTIVES OF THE OWNER. IF

CONFLICTS BETWEEN DRAWINGS, SPECIFICATIONS AND REQUIREMENTS OF BUILDING

OWNER AND/OR OPERATORS ARISE, THEY SHALL BE BROUGHT TO THE ATTENTION OF

THE ARCHITECT IMMEDIATELY.

18. THE HVAC, PLUMBING AND ELECTRICAL CONTRACTORS SHALL COORDINATE THEIR

WORK WITH THE WORK OF OTHER TRADES TO ASSURE THAT THE WORK CAN BE

INSTALLED IN A WORKMAN-LIKE MANNER. EACH CONTRACTOR SHALL BE EXPECTED

TO COOPERATE WITH OTHER CONTRACTORS IN THE PLACEMENT OF WORK TO AVOID

CONFLICTS AND MAINTAIN JOB PROGRESS.

19. IT IS THE INTENT OF THESE DRAWINGS THAT A COMPLETE JOB IS TO BE

ACCOMPLISHED IN PREPARING THE BID. THE BIDDER SHALL MAKE ALLOWANCES FOR

DETAILS WHICH MIGHT HAVE BEEN INADVERTENTLY OMITTED FROM THE DRAWINGS.

20. ALL EXISTING DUCTWORK, ELECTRICAL OR PIPING IS NOT NECESSARILY SHOWN ON

THE DRAWINGS.

21. BEFORE CONTRACTOR(S) BID THE JOB, IT IS IMPERATIVE THEY VISIT THE JOBSITE

AND FIELD VERIFY THE EXACT LOCATION OF ALL EXISTING EQUIPMENT, DUCTWORK,

ETC. IT WILL BE PART OF THE CONTRACTOR'S RESPONSIBILITY TO DESIGN AND

RELOCATE ANY EXISTING OBSTACLES WHICH WILL INTERFERE WITH THE

CONTRACTOR'S ABILITY TO INSTALL ALL NEW OR RELOCATED WORK ON HIS

CONTRACT.

PROJECT GENERAL NOTES

• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD

STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE INFORMATION ON THE

TECHNICAL INFORMATION LIBRARY (TIL)

• INTERNATIONAL BUILDING CODE (IBC) (ONLY WHEN SPECIFICALLY REFERENCED

IN VA DESIGN DOCUMENTS)

• NFPA 101 LIFE SAFETY CODE

• NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900

• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS

• VA SEISMIC DESIGN REQUIREMENTS, H-18-8

• NATIONAL ELECTRICAL CODE (NEC)

• INTERNATIONAL PLUMBING CODE (IPC)

• ASME BOILER AND PRESSURE VESSEL CODE

• ASME CODE FOR PRESSURE PIPING

• ARCHITECTURAL BARRIER ACT ACCESSIBILITY STANDARDS (ABAAS) INCLUDING

VA SUPPLEMENT, BARRIER FREE DESIGN GUIDE (PG-18-13)

• BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, AMERICAN

CONCRETE INSTITUTE AND COMMENTARY (ACI 318)

• MANUAL OF STEEL CONSTRUCTION, LOAD AND RESISTANCE FACTOR DESIGN

SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS, AMERICAN INSTITUTE OF

STEEL CONSTRUCTION (AISC)

• ENERGY POLICY ACT OF 2005 (EPACT)

• DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW

FEDERAL, COMMERCIAL AND MULTI-FAMILY HIGH-RISE RESIDENTIAL BUILDINGS

AND NEW LOW-RISE RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434, AND 435.

• FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS:

MEMORANDUM OF UNDERSTANDING (MOU)

• EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL ENVIRONMENT, ENERGY,

AND TRANSPORTATION MANAGEMENT.

• THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE

GENERAL REQUIREMENTS SECTION 01010 IF THE VA MASTER CONSTRUCTION

SPECIFICATION.

• VENTILATION FOR THE ACCEPTABLE INDOOR AIR QUALITY – ASHRAE STANDARD

62.1 – 2004.

• SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE STANDARD 15 –

2007.

NOTE: ALL WORK IS TO BE PERFORMED TO THE LATEST EDITION OF THE FOLLOWING

CODES, ORDINANCES, AND LAWS WHICH INCLUDE, BUT ARE NOT LIMITED TO:

BUILDING CODES, GUIDES, MANUALS

PHARMACY DESIGN GUIDES

• USP 800

• USP 797 - PROPOSED

• USP 795

• VA PHARMACY SERVICE DESIGN GUIDE (PG-18-12) DATED: APRIL 1, 2018

3'-0" 4'-0" 3'-0"

3'-6" 3'-6"

6"

M

IN

HANDRAILS

WHEELCHAIR MANEUVERING

MANEUVERING CLEARANCES AT DOORS

LATCH SIDE APPROACH LATCH SIDE APPROACH

HINGE SIDE APPROACHHINGE SIDE APPROACH

FRONT APPROACHFRONT APPROACH

GENERAL REACH DIMENSIONS

LAVATORY DIMENSIONS

MOUNTING HEIGHT DIMENSIONS

90 TURNS 180 TURN

1 1/2 " CLEAR1.25"-2" DIA.

IF CIRCULAR

Pull Side

Push Side

Push Side

Push Side Pull Side m in

24"min.

X

Y

X m in

Y m in

Y

54" min.

m in

X

24" min.

X

Y m in

NOTE: y=48" minimum if door has both a latch and closer.

NOTE: y = 54" minimum if door has closer

NOTE: y=48" min if door has closer

NOTE: x = 36" min if y = 60", x = 42" min if y = 54"

18" minimum 24" preferred

NOTE: x = 12" if door has both a closer and latch.

SOAP DISPENSER

MIRROR

TELEPHONE

CLOCK

LIGHT SWITCH

M

A X

M

A X

M

A X

(TO HIGHEST

OPERABLE PART)

17" MIN

M

IN

M

IN

M

A X

M

A X

M

IN

6" MAX

17" MIN

M

IN

M

A X

M

A X

M

IN

6" MAX

8" MIN

PAPER TOWEL

DISPENSER

OCCUPANCY SIGN

LATCH SIDE PERFERED

THERMOSTAT

OR OTHER

CONTROL

48"

M

IN

Z

48"

Y

X 30" 24"

M

A X

30"

10" MAX

21" MAX

M

IN

M

A X

36" MIN

M

IN

M

A X

NOTE: X SHALL BE < 25";

Z SHALL BE > X, WHEN X < 20",

THEN Y SHALL BE 48" MAX

WHEN X IS 20"-25",

THEN Y SHALL BE 44" MAX.

INSULATE

EXPOSED PIPES

NO SCALE

NO SCALE

NO SCALE

M A

X

COUNTER

OR

LAVATOR

Y

GRAB BARS

1 1/2 " CLEAR1.25"-2" DIA.

IF CIRCULAR

IF NON-CIRCULAR

PERIMETER MUST

BE 4"-6.25" AND

DIAMETER MUST

NOT EXCEED 2.25"

IF NON-CIRCULAR

PERIMETER MUST

BE 4"-6.25" AND

DIAMETER MUST

NOT EXCEED 2.25"

.5 m in m in

/4

/2

BEVELED FLOORING TRANSITIONS

/4 m a x

/2 m a x

CARPET ON FLOOR SURFACES

/4 m a x

BEVELED FLOORING TRANSITIONS

TURNING CLEAR

5'-0" 2'-6"

TOP AND SIDES

MUST BE

UNOBSTRUCTED. UP

TO 20% OF BOTTOM

MAY BE

OBSTRUCTED FOR

SUPPORTS.

ROBE HOOK

NEED TO VERIFY ALL

FIXTURE TYPE & SIZES

WITH MANUFACTURER

HAND

SANITIZER

24x 36

MARKER

BOARD

TRIPLE

GLOVE

BOX

SHARPS

CONTAINE

R

T

O T

H E

R

IM

WAITING

TV

PROVIDE APPROPRIATE IN-WALL BLOCKING FOR SUPPORT OF FURNITURE AND ACCESSORIES.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

SEE COVER SHEET FOR IPT MEMBERS

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

303 S. TOPEKA

WICHITA, KANSAS 63202

316.262.2691

8669 OLIVE BOULEVARD

ST LOUIS, MISSOURI 63132

314.432.8073

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

ASSOCIATE DIRECTOR

ARCHITECT/ENGINEER:

JOHN COCHRAN DIVISION

915 NORTH GRAND BLVD - ST. LOUIS, MO 63106

PLAN

NORTH

Building Key Plan: 4th LevelSeal:

TRUE

NORTH

/9

/2

:3

:0

A

M

GI002

GENERAL NOTES, LEGENDS, AND

ABBREVIATIONS

CORRECT PHARMACY DEFICIENCIES ON 4TH

LEVEL FOR USP 800 COMPLIANCE

10/9/2018 DM JN/JB

100% BIDDING DOCUMENTS

657-18-301JC

2 55Revision# Description Date:

23 HOUR

OBSERVATION

A476

23 HOUR

OBSERVATION

A476

23 HOUR

OBSERVATION

A476

CORRIDOR

H405

S405

SERVICE

ELEVATOR

LOBBY

H407

ELEVATOR

NO.5

E5

E6

23 HOUR

OBSERVATION

A456

CLEAN ROOM

A453

TOILET, MALE

A454

CHEMO

TREATMENT

ROOM

A455

PHARMACY

A452

STAFF LOUNGE

A476

S401

ELEVATOR

NO.6

STAIR

NO.1

STAIR

NO.5

A402

A401

SURGERY

WAITING

A400

CONSULT

CONSULT

CORRIDOR

H403

CORRIDOR

H405

S405

SERVICE

ELEVATOR

LOBBY

H407

ELEVATOR

NO.5

E5

E6 CLEAN ROOM

A453

TOILET, MALE

A454

CHEMO

TREATMENT

ROOM

A455

PHARMACY

A452

S401

ELEVATOR

NO.6

STAIR

NO.1

STAIR

NO.5

CONSULT

A402

CONSULT

A401

SURGERY

WAITING

A400

HD STORAGE (-)

A456A

HD BUFFER

(-)A457A

ANTE (+)

A457

PHARMACY

A456

NON-HD

BUFFER (+)

A457B

STAFF LOUNGE

A452

CORRIDOR

H403

CORRIDOR

H405

S405

SERVICE

ELEVATOR

LOBBY

H407

ELEVATOR

NO.5

E5

E6

TOILET, MALE

A454

CHEMO

TREATMENT

ROOM

A455

S401

ELEVATOR

NO.6

STAIR

NO.1

STAIR

NO.5

CORRIDOR

H403

CORRIDOR

H405

S405

SERVICE

ELEVATOR

LOBBY

H407

ELEVATOR

NO.5

E5

E6

23 HOUR

OBSERVATION

A456

CLEAN ROOM

A453

TOILET, MALE

A454

CHEMO

TREATMENT

ROOM

A455

PHARMACY

A452

S401

ELEVATOR

NO.6

STAIR

NO.1

STAIR

NO.5

CONSULT

A402

CONSULT

A401

SURGERY

WAITING

A400

CORRIDOR

H403

CONSULT

A402

CONSULT

A401

ICE MAKER

A476A

SURGERY

WAITING

A400

SURGERY

WAITING

A400

HD STORAGE (-)

A456A

HD BUFFER

(-)A457A

ANTE (+)

A457

PHARMACY

A456

NON-HD

BUFFER (+)

A457B

ICE MAKER

A452A

PHASE 1 - 4TH LEVEL

1" = 20'-0"

1. REMOVE EXIST FURNITURE/EQUIPMENT TO BE SALVAGED.

SEE DEMOLITION PLAN FOR SPECIFIC NOTES.

2. ADJUST SIZE OF EXISTING RECEPTION DESK AND MOVE

KIOSK CHECK-IN.

3. BUILD TEMPORARY CONSTRUCTION PARTITIONS TO

CONTAIN CONSTRUCTION WORK AS PER DRAWINGS.

3.1 TEMPORARY DOOR LOCATION.

4. CARRY OUT DEMOLITION AND NEW CONSTRUCTION AS

PER DRAWINGS.

5. UPDATE FLOORING AND FINISHES IN THIS AREA ON

WEEKEND BETWEEN PHASE 1 AND 2.

6. REMOVE TEMPORARY CONSTRUCTION PARTITIONS.

PHASE 1 - 4TH LEVEL NOTES: #

PHASE 3 - 4TH LEVEL NOTES: # PHASE 4 - 4TH LEVEL NOTES: #

1 4 1 5

1 3

1 3

1. REMOVE EXIST FURNITURE/EQUIPMENT TO BE SALVAGED.

SEE DEMOLITION PLAN FOR SPECIFIC NOTES.

2. BUILD TEMPORARY CONSTRUCTION PARTITIONS TO CONTAIN

CONSTRUCTION WORK AS PER DRAWINGS.

2.1 TEMPORARY DOOR LOCATION.

3. CARRY OUT DEMOLITION AND NEW CONSTRUCTION AS PER

DRAWINGS.

4. BUILD NEW EQUIPMENT ON ROOF AND EXTERIOR DUCT

CHASE.

5. DUCTWORK IN CEILING OVER LOCKER ROOM TO NEW

PHARMACY.

6. REMOVE TEMPORARY CONSTRUCTION PARTITIONS.

1. REMOVE EXIST FURNITURE/EQUIPMENT TO BE SALVAGED.

SEE DEMOLITION PLAN FOR SPECIFIC NOTES.

2. BUILD TEMPORARY CONSTRUCTION PARTITIONS TO

CONTAIN CONSTRUCTION WORK AS PER DRAWINGS.

2.1 TEMPORARY DOOR LOCATION.

3. CARRY OUT DEMOLITION AND NEW CONSTRUCTION AS PER

DRAWINGS.

4. REMOVE TEMPORARY CONSTRUCTION PARTITIONS.

P L A

N N

O R

T H

PHASE 2 - 4TH LEVEL

1" = 20'-0"

P L A

N N

O R

T H

PHASE 3 - 4TH LEVEL

1" = 20'-0"

P L A

N N

O R

T H

PHASE 4 - 4TH LEVEL

1" = 20'-0"

P L A

N N

O R

T H

1. REMOVE EXIST FURNITURE/EQUIPMENT TO BE SALVAGED.

SEE DEMOLITION PLAN FOR SPECIFIC NOTES.

2. ADJUST SIZE OF EXISTING RECEPTION DESK LOCATION

AND KIOSK CHECK-IN.

3. BUILD TEMPORARY CONSTRUCTION PARTITIONS TO

CONTAIN CONSTRUCTION WORK AS PER DRAWINGS.

3.1 TEMPORARY DOOR LOCATION.

3.2 BUILD TEMPORARY CONSTRUCTION PARTITIONS TO

CONTAIN CONSTRUCTION WORK AS PER DRAWINGS. THIS

TEMPORARY PARTITION NEEDS TO BE 1-HR SMOKE

BARRIER.

4. FINALIZE FINISHES AND MOVE RECEPTION DESK AND

KIOSK TO FINAL LOCATION WHEN THIS TEMP PARTITION

CAN BE REMOVED.

5. CARRY OUT DEMOLITION AND NEW CONSTRUCTION AS

PER DRAWINGS.

6. REMOVE TEMPORARY CONSTRUCTION PARTITIONS.

PHASE 2 - 4TH LEVEL NOTES: #

(NEW 23-HOUR ROOM)(EXPAND WAITING)

(NEW PHARMACY) (STAFF LOUNGE)

3.2

3.2

PHASE 3

3.1

3.1 3.13.1

3.1

2.1

2.1

PHASE 1

PHASE 4

PHASE 2

PHASING PLAN LEGEND

TEMPORARY CONSTRUCTION PARTITION AND DOORS

KEYNOTE#

LOCATION OF 1-HR TEMP CONSTRUCTION LIMITS

A. TEMPORARY CONSTRUCTION PARTITION BARRIERS FOR INFECTION

CONTROL AND TO MAINTAIN FIRE BARRIER ASSEMBLIES AS

REQUIRED.

B. CONTRACTOR TO COORDINATE WITH OWNER FOR STAGING AREA

ON SITE AND MOBILIZATION ACCESS POINTS FOR EACH PHASE.

C. REFERENCE SPECIFICATION FOR INFORMATION REGARDING

ASBESTOS IN THE EVENT THAT ASBESTOS IS PRESENT,

CONTRACTOR IS RESPONSIBLE FOR ASBESTOS REMOVAL.

D. COORDINATE THE TRANSITIONS BETWEEN PHASES WITH THE

OWNER TO ALLOW FOR ADEQUATE TIME TO RELOCATE EXISTING

EQUIPMENT / FURNITURE.

E. COORDINATE TEMPORARY INTERIOR FINISHES, POWER, HVAC, AND

PLUMBING WITH OWNER IN TEMPORARY (INTERIM) SPACES.

D. COORDINATE WITH OWNER WHEN A SHUT DOWN OF ANY SYSTEMS

WILL OCCUR TO MINIMIZE DISRUPTION OF EXISTING SERVICES.

E. OWNER COORDINATED RISK ASSESSMENT TO OCCUR PRIOR TO

CONSTRUCTION COMMENCEMENT AND DURING PHASING

TRANSITIONS.

PHASING GENERAL NOTES

EXIST. DECK ABOVE

FIRE CAULK EACH SIDE

FIRESAFE PENETRATIONS @ EXIST. UTIL.

WITH 1HR RATED SYSTEM

CONT. 1HR RATED PTN. TO UNDERSIDE OF

DECK ABOVE

CONTRACTOR OPTION, PROVIDE 1HR HORIZ.

ASSEMBLY TO NEAREST RATED CONST. IN LIEU

OF PTN. TO DECK

NOTE: AS A CONTRACTOR OPTION, RECONFIGURE EXISTING SPRINKLER SYSTEMS TO

PROVIDE UPRIGHT HEADS FOR FULL SPRINKLER COVERAGE OF THE CONSTRUCTION AREA IN

LIEU OF RATED TEMPORARY SEPARATIONS UNTIL NEW CEILING FINISHES ARE INSTALLED.

5/8" TYPE "X" GYP. BD. BOTH SIDES ON 3-5/8"

METAL STUDS. LEVEL 2 FINISHES AND

PAINT ON CORRIDOR / ROOM SIDE.

CORRIDOR / ROOM

SIDE

WORK SIDE

METAL SLIP TRACK; ALLOW FOR MIN.

1" DEFLECTION - UNO. SEE SPEC

METAL STUD RUNNER

GYPSUM BD CLADDING

UL #U419

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

SEE COVER SHEET FOR IPT MEMBERS

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

303 S. TOPEKA

WICHITA, KANSAS 63202

316.262.2691

8669 OLIVE BOULEVARD

ST LOUIS, MISSOURI 63132

314.432.8073

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

ASSOCIATE DIRECTOR

ARCHITECT/ENGINEER:

JOHN COCHRAN DIVISION

915 NORTH GRAND BLVD - ST. LOUIS, MO 63106

PLAN

NORTH

Building Key Plan: 4th LevelSeal:

TRUE

NORTH

/9

/2

:3

:0

A

M

GI101

PHASING PLAN CORRECT PHARMACY DEFICIENCIES ON 4TH

LEVEL FOR USP 800 COMPLIANCE

10/9/2018 DM JN/JB

100% BIDDING DOCUMENTS

657-18-301JC

3 55

1 1/2" = 1'-0" F4

TEMPORARY PARTITION - FIRE RATED

UP

UTSR

QPONH-AG-AMLKJIHGFE

ROOF BELOW

NOT IN

SCOPE

NOT IN

SCOPE

NOT IN

SCOPE

LIMITS

PHASE #1

LIMITS

PHASE #1

LIMITS

PHASE #2

LIMITS

PHASE #2

LIMITS

PHASE #3

LIMITS

PHASE #3

LIMITS

PHASE #3

LIMITS

PHASE #3

LIMITS

PHASE #4

LIMITS

PHASE #4 ALT #2

ALT #1

ACM ON PIPING

AND PIPE FITTINGS

ACM FLOORING

LBP ON DOOR

FRAMES

ACM ON PIPING

AND PIPE FITTINGS

ACM ON PIPING

AND PIPE FITTINGS

ACM ON PIPING

AND PIPE FITTINGS

LBP WINDOW SILLS

AND FRAMES

LBP WINDOW SILLS

AND FRAMES

ACM FLOORING

ACM FLOORING

ACM FLOORING

GENERAL NOTES - ASBESTOS ABATEMENT:

A. REMOVE ALL ASBESTOS PIPE FITTING INSULATION WITHIN THE ASBESTOS

ABATEMENT WORK SPACE, ABOVE CEILINGS, (INCLUDING THERMAL

INSULATION ON PIPING SERVING 9TH FLOOR CONVECTORS), AND IN THOSE

CHASES SCHEDULED FOR DEMOLITION, REMOVE ALL DEBRIS FOUND IN THE

WORK AREA. USE TRADITIONAL ASBESTOS ABATEMENT METHODS IN THOSE

AREAS WHERE INSULATION MAY BE DAMAGED AND SIGNIFICANT PORTIONS

OF DEBRIS MAY EXIST SUCH AS IN CHASES THAT CANNOT BE ACCESSED

WITHOUT DEMOLITION. CHASES SHOWN TO BE REMOVED SHALL BE INITIALLY

OPENED UP ONLY AS NECESSARY TO ALLOW VISUAL INSPECTION OF THE

TO TAKE PLACE TO DETERMINE THE CONDITION OF THE MATERIAL INSIDE. IF

SIGNIFICANT DAMAGE IS BELIEVED TO EXIST, THAN THE REMAINING CHASE

WALLS SHALL BE REMOVED USING TRADITIONAL ASBESTOS ABATEMENT TO

PRECLUDE ANY POSSIBLE RELEASE OF MATERIAL INTO THE AREA DUE TO

DEMOLITION ACTIVITIES.

B. REMOVE ALL FLOOR TILE AND FLOOR TILE MASTIC WITHIN THE ASBESTOS

ABATEMENT WORK AREA.

C. REINSULATE ANY PLUMBING/MECHANICAL SYSTEM THAT IS TO REMAIN IN USE.

REFER TO MECHANICAL DRAWINGS AND SPECIFICATIONS.

PLUMBING/MECHANICAL SYSTEMS TO BE PERMANENTLY REMOVED , MAY BE

CUT AND WRAPPED AND REMOVED IN SECTIONS WITH THE INSULATION STILL

ATTACHED.

D. ENCAPSULATE THE EXPOSED ENDS OF ANY PIPE INSULATION THAT IS NOT

REMOVED AT ADJOINING FLOOR LEVELS.

ACM - FLOOR TILE AND/OR MASTIC

ACM - THERMAL PIPE INSULATION/FITTINGS

ABOVE CEILING AND WITHIN PIPE CHASES

SYMBOLS - HAZARDOUS

LBP - LEAD BASED PAINT AS NOTED

REFER TO ASBESTOS AND LBP SURVEY REPORT IN

SPECIFICATIONS FOR ADDITIONAL DETAILS AND

QUANTITIES.

STAIRWELL NO.

S401 SERVICE

ELEVATOR

LOBBY

H407

STAIRWELL NO.

S405

PHARMACY

A452

CLEAN ROOM

A453

TOILET, MALE

A454

23 HOUR

OBSERVATION

A456

ICE MAKER

A476A

STAFF LOUNGE

A476

SURGERY

WAITING

A400

EXAM

A401

EXAM

A402

CHASE

CH-A-3

ELEC. CLOSET

A454AF.E. CLOSET

H405A

CHASE

CH-A-6

ELEVATOR

NO.5

E5

ELEVATOR NO.

E6

CORRIDOR

H403

CHEMO

TREATMENT

ROOM

A455

CORRIDOR

H405

ELEC. CLOSET

A436A

HAC

A403

TOILET

A406A

CORRIDOR

H402

LAB

A435

WAITING

CONSULT

A436

CONSULT

A436A

STORAGE

A436C

HAC

A475

TOILET

A472A

CLEAN UTILITY

A458

ELEC. CLOSET

A458A

TOILET

A461A

PUBLIC TOILET

A444

ELEVATOR NO.

E4

ELEVATOR NO.

E3

ELEVATOR

LOBBY

H406

F.E. CLOSET

A436E

ELEC. CLOSET

A436D

ELEC. CLOSET

A436F

STORAGE

A404

UTSRQPONH-AG-AMLKJIHGFE

NOT IN

SCOPE

NOT IN

SCOPE

NOT IN

SCOPE

REMOVED WASTE ASSUMED

ACM ON PIPING AND FITTINGS

REMOVED WASTE ASSUMED

ACM ON PIPING AND FITTINGS

ALT #2

ALT #1

REMOVED WASTE ASSUMED

ACM ON PIPING AND FITTINGS

REMOVED WASTE ASSUMED

ACM ON PIPING AND FITTINGS

VACANT

A302B

VACANT

A302A

TOILET

A375A

OFFICE

A375

CLINICAL

NUTRITION

A374

OFFICE

A374A

CORRIDOR

H304

LAUNDRY

A350

PT WORK

A345 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

SEE COVER SHEET FOR IPT MEMBERS

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

303 S. TOPEKA

WICHITA, KANSAS 63202

316.262.2691

8669 OLIVE BOULEVARD

ST LOUIS, MISSOURI 63132

314.432.8073

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

ASSOCIATE DIRECTOR

ARCHITECT/ENGINEER:

JOHN COCHRAN DIVISION

915 NORTH GRAND BLVD - ST. LOUIS, MO 63106

PLAN

NORTH

Building Key Plan: 4th LevelSeal:

TRUE

NORTH

/9

/2

:3

:1

A

M

HA101

HAZARDOUS MATERIALS PLANS CORRECT PHARMACY DEFICIENCIES ON 4TH

LEVEL FOR USP 800 COMPLIANCE

10/9/2018 DM JN/JB

100% BIDDING DOCUMENTS

657-18-301JC

4 55

1/8" = 1'-0" F1

4TH LEVEL HAZARDOUS PLAN P

L A

N N

O R

T H

1/8" = 1'-0" C1

3RD LEVEL HAZARDOUS CEILING PLAN P

L A

N N

O R

T H

NOTE:

UNKNOWN CONDITIONS OF PIPING BEING

REMOVED ON 3RD LEVEL. ASSUMED ASBESTOS

CONTAINING MATERIALS IN THESE LOCATIONS.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

SEE COVER SHEET FOR IPT MEMBERS

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

303 S. TOPEKA

WICHITA, KANSAS 63202

316.262.2691

8669 OLIVE BOULEVARD

ST LOUIS, MISSOURI 63132

314.432.8073

SHEET FOR

REFERENCE ONLY

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

ASSOCIATE DIRECTOR

ARCHITECT/ENGINEER:

JOHN COCHRAN DIVISION

915 NORTH GRAND BLVD - ST. LOUIS, MO 63106

PLAN

NORTH

Building Key Plan: 4th LevelSeal:

TRUE

NORTH

/9

/2

:2

:4

A

M

SX101

4TH LEVEL EXISTING FLOOR FRAMING

PLAN (INFO ONLY)

CORRECT PHARMACY DEFICIENCIES ON 4TH

LEVEL FOR USP 800 COMPLIANCE

10/9/2018 DM JN/JB

100% BIDDING DOCUMENTS

657-18-301JC

7 55

1/8" = 1'-0"

EXISTING 4TH LEVEL FRAMING PLAN

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

SEE COVER SHEET FOR IPT MEMBERS

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

303 S. TOPEKA

WICHITA, KANSAS 63202

316.262.2691

8669 OLIVE BOULEVARD

ST LOUIS, MISSOURI 63132

314.432.8073

SHEET FOR

REFERENCE ONLY

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

ASSOCIATE DIRECTOR

ARCHITECT/ENGINEER:

JOHN COCHRAN DIVISION

915 NORTH GRAND BLVD - ST. LOUIS, MO 63106

PLAN

NORTH

Building Key Plan: 4th LevelSeal:

TRUE

NORTH

/9

/2

:2

:4

A

M

SX102

5TH LEVEL EXISTING FLOOR FRAMING

PLAN (INFO ONLY)

CORRECT PHARMACY DEFICIENCIES ON 4TH

LEVEL FOR USP 800 COMPLIANCE

10/9/2018 DM JN/JB

100% BIDDING DOCUMENTS

657-18-301JC

8 55

1/8" = 1'-0"

EXISTING 5TH LEVEL FRAMING PLAN

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

SEE COVER SHEET FOR IPT MEMBERS

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

303 S. TOPEKA

WICHITA, KANSAS 63202

316.262.2691

8669 OLIVE BOULEVARD

ST LOUIS, MISSOURI 63132

314.432.8073

SHEET FOR

REFERENCE ONLY

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

VA Health Care System Approval:

ASSOCIATE DIRECTOR

ARCHITECT/ENGINEER:

JOHN COCHRAN DIVISION

915 NORTH GRAND BLVD - ST. LOUIS, MO 63106

PLAN

NORTH

Building Key Plan: 4th LevelSeal:

TRUE

NORTH

/9

/2

:2

:4

A

M

SX601

EXISTING COLUMN SCHEDULE (INFO

ONLY)

CORRECT PHARMACY DEFICIENCIES ON 4TH

LEVEL FOR USP 800 COMPLIANCE

10/9/2018 DM JN/JB

100% BIDDING DOCUMENTS

9 55Revision# Description Date:

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e…