Item Number
Deliverable Due Date Complete Date
Fire Alarm System software and hardware updates as they become available.
Within 30 Calendar Days of Notification of Update by the Manufacturer
If a deficiency exists that is out of the scope of this contract, submit a document to the Electric Shop Supervisor explaining the deficiency and what will need to be done to rectify the deficiency
Within one hour of identifying deficiency
Update software for completed construction and renovation projects.
Within 30 Calendar Days of substantial completion of contractural requirements.
4 Provide a backup copy of software. Semi-Annually 5 Conduct annual inspections on all devices Annually
Conduct semi-annual inspections on water flow devices
Semi-Annually
7 Prior notification of inspection and testing 14 working days in advance
Critical deficiencies found during testing reported immediately to Engineering Electric Shop and/or COR
Within one hour of identifying deficiency
Immediately repair deficiency found during testing
Within 24 hours of identifying deficiency
Re-test after failed device or other issue has been repaired or replaced
Immediately upon completion of repair or replacement
Provide documentation of failure and follow-up repair and retesting
Within 5 business days of completion
Prior notification to the commencement of any scheduled test or task
Provide a schedule of what is to be inspected, the sequence of th einspecting, and the time froame of inspecting for each area
13 Off hours work must be scheduled in advance 14 working days in advance
AHU shutdown testing must be scheduled in advance
14 working days in advance
Fire Alarm System Service and Maintenance Contract Deliverables
14 working days in advance
Smoke damper work must be scheduled in advance
14 working days in advance
Replace all batteries every two years
Replace Fire Alarm System batteries no more than every two years
Submit required documentation to the COR for a record of compliance that the Central Station Monitoring Company and Auto Dialer (DACT)/ Transmission to the Fire Department has been tested and maintained per the most recent edition of NFPA 72, along with documentation required from the monitoring company per
NFPA
Annually
Test reports filled out immediately after each test is complete
Within 24 hours of completed testing
19 Submit new master test reports to the COR Within 30 calendar days of Contract Award
Submit field test reports (including documentation that the test method follows NFPA criteria)
Within 24 hours of completed testing
21 Submit bound copies of test reports Within 7 business days of completion of testing
Return updated, current set of paper as-built drawings to COR
At the end of each work shift
Manage and track all Joint Commission Fire and Life Safety standards for all buildings included in the contract, provide customized Joint Commission reports, a documentation managemtn system, and regular Joint Commission Compliance Review Meetings, for all elements of performance, along with providing a binder for all Joint Commission test reports, the annual delivery scheudle, as well as any related documenation and paperwork
Annually
16 On or about December 15 in even-numbered years
Submit discrepancy reports to COR summarizing all devices/systems that did not pass testing criteria
At the end of each work shift
25 Submit all test reports to the COR Within 14 calendar days from the completion of testing
Provide one master test report showing each device and piece of equipment that was tested that year
A minimum of 14 calendar days prior to the contract expiration date
Submit a signed letter stating that all equipment included in the contract has been tested according to the contract and to the requirements of the most current edition of
NFPA 72
A minimum of 14 calendar days prior to the contract expiration date
28 Submit a PM schedule to the COR for approval Within 14 calendar days of Contract Award
Repair troubles in the system as soon as they are noticed (during testing)
Within 24 hours of identifying trouble
Submit report of repair of trouble to the Electric Shop Supervisor (COR)
Within 3 business days
Document all maintenance services using a service invoice receipt and submit
Within 14 calendar days of completion of the work
Provide a list of recommended spare devices and parts for inventory
Within 7 business days of Contract Award
Update as-built drawings for completed construction and renovation projects.
Within 30 Calendar Days of substantial completion of project
Update master device list from as-built drawings and keep list up to date
On-going basis
35 Provide fully updated set of as-built drawings Quarterly
36 Correct malfunctions Within 24 hours of the knowledge of the malfunction
Non-emergency call response, respond and report to the site
Normal business hours. Calls on a Friday may be addressed the following Monday.
VA declared emergency call response, respond and report to the site
Within 2 hours of receipt of an emergency call
Provide a list of non-automated phone numbers that will be used to provide notification of emergency service
At the time of Contract Award
Fire Alarm System is not out of service for any period greater than 4 hours or more
Fire Alarm System is not out of service for 4 or more hours
Provide an itemized list of labor, showing the number of hours, the pre-agreed upon hourly rate, and the parts used where the VA is responsible for charges after any applicable service
Within 24 hours of service that identifies work for which the VA is responsible for charges (work not under contract)
After completion of any service, report back to Building 6 and furnish a written job sheet report or work ticket of service performed.
Report shall describe the conditions causing the problem and actions taken to make corrections
At the completion of each test or maintenance service, prior to leaving the site after a service call
Provide written and verbal report to Electric Shop Foreman of any devices or systems that were found to not operate properly. Advise of what device or system is malfunctioning and the location of that device or system which will need to be repaired immediately.
At the completion of each test or maintenance service, prior to leaving the site after a service call
All contracting personnel have mandatory VA safety training and are badged prior to working at the Medical Center
Employee training and badging completed prior to working on-site
Submit Fire Alarm Systems equipment Operating and Maintenance Manuals to the Electric Shop Supervisor (COR)
Within 30 calendar days of Contract Award
Provide a materials list of system components with the addresses and telephone numbers of the manufacturer and the local supplier for the items
Within 30 calendar days of Contract Award